Delta PLC Manual
Delta PLC Manual
Delta PLC Manual
Manuals
The following describes the system structure for connecting the GP to Toshiba
Machine PLCs.
Match up the GP Unit No. and each PC Number when multiple PCs are
Note: connected using PC Link.
SIO M odule
TC C U H TC C M W RS -232C
TC C M O (C able Diagram 1)
*1
Link I/F on C P U
TC C U H S RS -232C connector on RS -232C G P S eries
TC C U S S C P U module (C able Diagram 2)
TC C M WA
TC C M O A
NC
CD
* 1 Word Address fields can differ between GP-PRO/PBIII for Windows and the
corresponding PLC manual.
E.g. Input Relay
GP-PRO/PBIII PLC Manual
XW00~XWF7 X00W~XF7W
Data cannot be written from the GP/GLC to the input relay (x,1). The calcu-
lation result in a ladder program takes priority for all the ladder program
output section devices. Therefore, no data can be written from the GP/GLC.
E.g. Ladder Program
Input Output
Section Section
GP-PRO/PBIII for Windows Device/PLC Connection Manual 2-11-3
2.11 Toshiba Machine Chapter 2 - PLC-GP Connection
*2 In GP-PRO/PB III for Windows, the word address' last digit is hexadecimal.
You can enter any number between 0 and F as the last digit, however, since
the PLC's word address' last digit is octal, you can only enter a number
between 0 and 7 as the last digit.
*3 In GP-PRO/PB III for Windows, the word address' second to last digit is hexa-
decimal and you can enter any number between 0 and F. However, since the
PLC's word address' second to last digit and octal is you can only enter a
number between 0 and 7 as the second to last digit.
*4 The addresses of the timer/counter (contact) range from TW/CW00 to TW/
CW77, however the internal memory area is not consecutive. This range is
divided into two areas, e.g., TW/CW00 to TW/CW37 and TW/CW40 to TW/
CW77.
! • The number of consecutive words that can be used for the fol-
Important lowing GP-PRO/PB III and Pro-Server is limited:
1) Number of monitored words using tag
• Bit device (X, Y, I, O, R, G, H, J, K, A, L, S, E, T, C): No more
than eight words can be specified.
• Word device (P, V, D, B, U, M, Q): No more than 127 words
can be specified.
• Even if data is within the above word limit, no word can be
specified outside of the octal range.
The use of the a-tag allows you to specify words exceeding
the limit.
E.g.) To monitor more than eight words (If the a-tag's) Moni-
tored Word Address is RW0 and you wish to monitor
more than eight words, on the a-tag, set the Monitored
Word Address to RW0 and set the Number of Monitored
Words to 9 or more.
2) Number of addresses specified for copying stored data or ini-
tializing memory using D-Script's memory operation function
• All devices: No more than 40 words can be specified.
If this limit is exceeded, divide the words (into blocks that are
within the limit) and then use the memory operation function.
3) LS Read area
• When the entire system area is selected:
no more than 107 words can be specified.
• When the entire system area is deselected:
no more than 127 words can be specified.
* The size that can be specified varies depending upon the
selected number (20 words maximum) in the system area.
• The device type and range that can be used may vary depending upon your
Note: CPU. Check with the manual for your CPU before use.