15.

0mm

Metric
Entry
'G' Approx (Compressed Length)

Armour/Braid
'C'
Cable Gland Type
501/453/RAC
Entry Thread

Ø 'A' ATEX

Ø 'B'
Flameproof and Increased Safety

Application
CABLE GLAND SELECTION TABLE
Cable Acceptance Details Outdoor or Indoor use.
Entry Thread Hexagon For use with single wire
Inner Sheath 'A' Outer 'C'
Size Size Dimensions armoured 'W', wire braided 'X'
Standard Alternative Sheath Armour/Braid 'G'

501/453/RAC Cable Gland


Ref. and steel tape armoured 'Z',
NPT* Seal Seal (S) 'B' Across Across
Metric Std./ elastomer and plastic insulated
Option Min. Max. Min. Max. Min. Max. Orientation
1
Orientation
2
Flats Corners cables.
Os M202 ½" - - 5.5 12.0 0/0.7 65.1 24.0 27.7 See technical section of
3.0 8.0 0.9/1.25
2 catalogue for installation rules
O M20 ½" 6.5 11.9 - - 9.5 16.0 0.9/1.25 0/0.7 65.1 24.0 27.7 and regulations.
A M20 ¾"/½" 10.0 14.3 8.5 13.4 12.5 20.5 0.9/1.25 0/0.7 66.1 30.0 34.6
B M25 1"/¾" 12.5 20.2 9.5 15.4 16.9 26.0 1.25/1.6 0/0.7 71.4 36.0 41.6 Features
C M32 1¼"/1" 19.0 26.5 14.5 21.2 22.0 33.0 1.6/2.0 0/0.7 75.2 46.0 53.1 Provides armour clamping
C2 M40 1½"/1¼" 25.0 32.5 22.0 28.0 28.0 41.0 1.6/2.0 0/0.7 77.1 55.0 63.5 using one clamping
D M50 2"/1½" 31.5 44.4/42.31 27.5 34.8 36.0 52.6 1.8/2.5 0/1.0 90.3 65.0 75.1 arrangement for all armour/
E M63 2½"/2" 42.5 56.3/54.31 39.0 46.5 46.0 65.3 1.8/2.5 0/1.0 96.7 80.0 92.4 braid types.
F M75 3"/2½" 54.5 68.2/65.31 48.5 58.3 57.0 78.0 1.8/2.5 0/1.0 96 95.0 109.6 Provides a seal on the cables
inner sheath.
Larger cable glands available in 501/453 design.
Provides a cable retention and
G M80 3½" 67.0 73.0 - - 75.0 89.5 # # 95.6 106.4 123.0 low smoke and fume, zero
H M90 3½" 67.0 77.6 - - 75.0 89.5 # # 95.6 115.0 132.8 halogen seal onto the cables
J M100 4" 75.0 91.6 - - 88.0 104.5 # # 95.6 127.0 146.7 outer sheath.
1 Smaller value is applicable when selecting reduced NPT entry option.
2 SizesOs and O are available with an M16 thread size. For O size with M16 thread, Technical Data
the maximum cable inner sheath diameter is 10.9mm.
3 Flameproof Exd and Increased
This cable gland type is also available for use with lead sheath cables - 501/453/RAC/L. Contact
Hawke sales for more information. Safety Exe. II 2 GD
4 Deluge protection option available. Baseefa 06ATEX0056X.
# Dedicated armour clamping rings are fitted. Please specify armour type and size when ordering. IECEx BAS06.0013X.
General Information Alternative Reversible Armour Suitable for use in Zone 1,
Os - F size metric entry threads are 1.5mm Clamping Rings (RAC) Zone 2, Zone 21 and Zone 22.
pitch as standard. Suitable for use in Gas Groups
SELECTION TABLE
For G size glands and above, a 2mm pitch is Steel Wire Armour/Braid/Tape
IIA, IIB and IIC.
Size
Construction and test standards
supplied as standard. Ref. Orientation 1 Orientation 2
O/Os 0.8 - 1.0 0.4 - 0.8 EN 50014, EN 50018, EN 50019
(1.5mm pitch with 15mm length of thread can
be supplied) please specify when ordering. A 0.8 - 1.0 0.4 - 0.8 and EN 50281-1-1.
B 0.9 - 1.25 0.5 - 0.9 IEC 60079-0, IEC 60079-1 and
Thread length is 15mm for sizes Os to F and C 1.2 - 1.6 0.6 - 1.2
20mm for sizes G to J. C2 1.2 - 1.6 0.6 - 1.2
IEC 60079-7.
All dimensions in millimetres D 1.45 - 1.8 1.0 - 1.45 IP66, IP67 and IP68 (30 metres for 7 days)
E 1.45 - 1.8 1.0 - 1.45 ingress protection to IEC 60529,
(except* where dimensions are in inches). 1.45 - 1.8 1.0 - 1.45
F
Assembly instruction data sheet No. A.I. 302. EN 60529 and NEMA 4X.
DTS01 deluge protection
Accessories including locknuts, sealing washers, serrated washers, earth tags, shrouds, certified by ITS.
adaptors and reducers available. See pages 53 - 57. Operating temperature range
Materials & Finishes -60°C to +80°C as standard.
The 501/453/RAC cable gland is manufactured in brass (standard), nickel plated brass, Alternative Certification Options Available.
316 stainless steel or aluminium. Exd IIC/Exe II.
Brass NPT entries are nickel plated as standard.
Cable Gland Ordering Examples
GOST R-Exd IICU/Exe IIU.
Cable Gland Type/Size/Thread Cable Gland with Alternative
Clamping Ring (AR) Approved for use in Kazakhstan.
e.g. 501/453/RAC/C/M32
501/453/RAC/C/1¼" NPT e.g. 501/453/RAC/C/M32/AR AUS-Exd IIC/Exe II.
501/453/RAC/C/1¼" NPT/AR Marine Approval.
Cable Gland with Alternative Seal (S)