TD45 New
TD45 New
TD45 New
TD45
LIMITING CONDITION
RATING ANSI 600
PMA 100 bar
TMA 400°C
MAX DIFFERENTIAL PRESSURE 45 bar
MAIN FEATURES
• Discharges air and not condensable gases 2500
• Integral seat with hardened seating surfaces 2000
• Operates with superheated steam 1500
• Simple and compact design
1000
• Intermittent discharge
Flowrate [kg/h]
25
500 DN
ORDERING INFORMATION 20
DN
• Inlet pressure 300 15
DN
• Back pressure
200
• Operating temperature
• Condensate load
• End connection 100
0.1 0.5 1 2 3 5 10 20 40
Pressure [barg]
INSTALLATION MAINTENANCE
The trap will operate in any position, but the preferred The trap can be maintained without disturbing the piping
installation is in the horizontal plane with the cap on the connections. Ensure that trap is isolated upstream and
top. Isolating valve should be installed upstream and downstream before attempting to dismantle it.
downstream of the trap for safe maintenance. Allow the trap to cool before dismantling.
Always open isolation valve slowly until normal operating Periodic cleaning of the disc and seat will facilitate trouble
conditions are achieved to avoid system shocks. free performance. Only the disc and seat are subject to wear.
A worn disc can be replaced and slight seat can be corrected
by resurfacing an a lap plate.
In the interest of products development and improvment, CDB Engineering reserves the right to carry out any necessary modification without prior notice.
PMA and TMA can change with the materials of steam trap components. For more information please contacts our sales department.