Cable Selection
Cable Selection
Cable Selection
1. We must first calculate the design current that the circuit will have to carry ( I b )
Calculation is ( Ib design current = Power / Voltage).
2. A over current protective device must now be selected ( In ); this must be equal to or greater than
Ib .
3. Select the cable size. If the cable is to be installed in areas where environmental conditions will not
allow the cable to cool, rating factors will be need to be used. This will ensure that the cable size
selected will be suitable for installation and will not be adversely affected by the additional
temperatures likely to be encountered.
EXAMPLE 1
Cable Selection
Ca is a rating factor to be used where ambient temperature is above or below 30 deg C. This factor can
be found in Table 4B1 Appendix 4 of BS7671.
Cg is a rating factor to be used where the cable is grouped or bunched (touching) with other cables.
This factor can be found in Table 4C1 Appendix 4 of BS7671.
Ci is a factor for use where a conductor is surrounded by thermal insulation and can be found in Table
52.2 part 5 of BS7671.
Cf is a factor for rewirable fuses and is always 0.725. This factor must always be used when rewirable
fuses protect a circuit.
EXAMPLE 1
Cable Selection
These factors should be multiplied together and then divided into In
Therefore the calculation is
𝑰𝒏
It = Iz 𝑰𝒕 ≥
𝑪𝒂 𝒙 𝑪𝒈𝒙 𝑪𝒊 𝒙 𝑪𝒇
𝑰𝒏 𝟐𝟎
𝑰𝒕 ≥ = 𝑨 = 𝟐𝟔. 𝟓𝟗𝑨
𝑪𝒂 𝒙 𝑪𝒈 𝟎. 𝟗𝟒𝑿𝟎. 𝟖
This is the minimum value of current that the cable must be able to carry to enable it to be installed in
the environmental conditions affecting the cable.
Cable Selection
EXAMPLE 1
From Table 4D5 columns 1 and 4 it can be seen that a 4mm2 cable has an It (current carrying capacity)
of 27 amperes. A cable with 4mm2 live conductors will carry the current in these conditions
without overheating.
EXAMPLE 1 Cable Selection
But will it comply with the voltage drop requirements?
From Table 4D5 column 8 it can be seen that 4mm2 cable has a voltage drop of 11 (mV/A/m) or
millivolts x load current x length of circuit. As the value is in millivolts it must be converted to volts by
dividing by 1000.
Cable Selection
EXAMPLE 1
But will it comply with the voltage drop requirements?
The circuit length is 32 meters and the load current is 18.26 amperes.
Standard voltage drop = 11 (mV/A/m)
𝟏𝟏𝒙𝟏𝟖. 𝟐𝟔𝒙𝟑𝟐
𝑽𝒐𝒍𝒕𝒂𝒈𝒆 𝒅𝒓𝒐𝒑 = = 𝟔. 𝟒𝟐 𝑽𝒐𝒍𝒕𝒔
𝟏𝟎𝟎𝟎
The voltage drop in this cable will be 6.42 volts which is acceptable as the maximum
permissible for the circuit is 7 volts.
Cable Selection
EXAMPLE 2
A 6kW load is to be supplied at 230 V by a PVC sheathed and insulated twin and cpc copper cable, 8
metres in length. The cable is clipped on the surface through an area with an ambient temperature
of 40°C and is grouped with three other cables of similar size and loading. The protection is by means
of a BS 3036 fuse. Calculate the minimum cable size required (it is assumed in this example that all the
correction factors need to be applied).
Cable Selection
EXAMPLE 2
Cable Selection
EXAMPLE 2
Cable Selection
EXAMPLE 2
Cable Selection
Calculating the right size - SUMMARY
There are five steps to calculating the right size of cable for a particular load. These are as follows:
1. Calculate the design current (Ib). This is the normal current drawn by the load. It is usually
determined as follows:
Ib = Watts / Volts
2. Select the type and current rating of the overcurrent device (In).
3. Apply the relevant correction factors to obtain the tabulated current (It). Correction factors are
applied to situations which inhibit a cable from dissipating its heat caused by
the normal flow of current through it. Therefore, the following correction factors, if applicable, are
applied:
Cable Selection
Calculating the right size – SUMMARY…
Ambient temperature, Ca This factor is obtained from Table 4C1 (or Table 4C2 if a rewireable fuse to BS
3036 is used) in Appendix 4 of BS 7671.
Grouping, Cg This factor is found by reference to Table 4B1 in Appendix 4. Table 4B2 is used where
mineral insulated cables are installed on perforated cable tray. Thermal insulation, Ci Where a cable is
in contact with thermal insulation on one side only, the current-carrying capacity of the cable should
be calculated using Reference Method 4, which is described in Appendix 4 (Table 4A) of BS
7671. Where a cable is totally surrounded by thermal insulation for a distance greater than 0.5 meters,
the current-carrying capacity should be taken, in the absence of further information, as 0.5 times the
current-carrying capacity for that cable when using Installation Method 1 (open and clipped direct).
Cable Selection
Calculating the right size – SUMMARY…
Where a cable is totally surrounded by thermal insulation for a distance of 0.5 metres or less, Table
52A in BS 7671 gives derating factors which must be applied.
Rewireable fuse (BS 3036) factor, Cf Where a rewireable fuse to BS 3036 is used, a further correction
factor of 0.725 is applied, due to the poor fusing factor of rewireable fuses.
How to apply correction factors
These correction factors are applied as divisors to the nominal current rating of the overcurrent
protective device (In), to obtain the tabulated current, It . For example, in the worst possible situation
where all four factors are applied, the formula would look like this:
Cable Selection
How to apply correction factors…
The more correction factors we apply, the larger the value of It will be and hence the larger the size of
cable we will require. Consequently, it is advantageous to avoid having to apply correction
factors where possible by, such measures as, avoiding grouping of cables and avoiding contact
with thermal insulation.
However the formula given above is based on the assumption that the conditions requiring the
application of correction factors apply simultaneously to the same part of the cable along its route.
Where particular correction factors are appropriate to different parts of the cable along its route, each
part can be treated separately. Alternatively, only the correction factor (or combination of factors)
applicable to the worst situation along the cable route can be applied to the whole route. (See Item 6.4
of Appendix 4 in BS 7671)
Correct order of Selection
Needs
1. BS7671 on site guide book
2. Calculator
Correct order of Selection
Determine
1. The design current (load current)
2. The size of the breaker (BS EN60898 - MCB)
3. Size of the cable
Cable installation reference methods
On site guide Part 7 Page 74
Table 7.1(ii)
Installation reference methods and
cable ratings for 700C
thermoplastic (PVC) insulated and
sheathed flat cable with protective
conductor
Answer is RCBO
In = 32A
Correct order of Selection
On site guide Part 7 Page 72
3. Size of the
cable