GENERAL NOTES:

ANGLE IRON REINFORCING 1. THIS DRAWING IS THE COPYRIGHT OF AL JABAL ENGINEERING


WHERE REQUIRED CONSULTANCY EST. (DUBAI) AND MUST NOT BE RETAINED, COPIED
BOLTS
SCREEN OR USED WITHOUT THE ABOVE CONSULTANT'S AUTHORITY.
FLASHING DETAILS
2. DO NOT SCALE FROM THE DRAWINGS.

20 GA. MOUNTING BOLTED 3. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS IN METERS
TO WALL AND SLEEVE UNLESS NOTED OTHERWISE. ALL DIMENSIONS TO BE VERIFIED ON
CAULK ALL WALL WATERPROOF SITE & APPROVED BY THE ENGINEER.
SEAMS AND WEATHER PROOF
AROUND (TYP.) BLOCK
SHEET METAL DUCT JOINTS FLEXIBLE MASTIC 4. THIS DRAWING SHOULD BE READ IN CONJUNCTION WITH OTHER
WORK
RELEVANT ARCHITECTURAL, STRUCTURAL, MECHANICAL AND
EXTERNAL LOUVRES ANGLE RIVETED OR TACK
ELECTRICAL DRAWINGS AND ALL RELEVANT SECTIONS OF THE

VARIES
(BY BUILDERS) WELDED AS REQUIRED DUCT SPECIFICATIONS.
(OR PIPE)

DUCT WIDTH
12mm SCREEN

DU
135° MIN

CT
SI
ZE
ROOF LEVEL

+m
in
SLEEVE

25
WATER PROOFING Notes:

%
DUCT BIRD SCREEN
1. All dimensions are in millimeters unless
otherwise specified.

300mm min,
No. 10 x 20 mm SHEET

450mm min
2. For legend & Gen.Notes refer to drawing
METAL SCREW (TYP.)
MINERAL FIBER No. M 001
INSULATION CHB WALL 150 VARIES 150 3. For standard details refer to drawing No. M 901,
ACCESS PANEL
M 902, & M 903
MOTORISE DAMPER
4. All Duct Risers sizes as per the schematic
drawings.
5. If Location of Thermostats are not marked on
Drawings, Contractor to Propose a Suitable
Location and Co-ordinate with Architect's
during Construction stage.
01 DUCT THROUGH WALLS 02 EXTERNAL LOUVRES DUCT c/w MD INSTALLATION 03 GOOSENECK DETAIL 04 ROOF SLAB A/C DUCT/PIPE PENETRATION DETAIL

DUCT INSULATION

METAL CLADDING
GALVANIZED SHEET METAL PLATE SAME
GALVANIZED SHEET METAL PLATE SAME GAUGE AS DUCT.
GAUGE AS DUCT. WELD VANES TO WELD VANES TO PLATE OR ATTACH WITH SEE ARCH'L DWGS FOR DUCT
PLATE OR ATTACH WITH ANGLE ANGLE BRACKET, RIVETED FLASHING DETAILS
DOUBLE THICKNESS VANES SEE DETAIL 5 WEATHERING SKIRT
STANDARD VANES SEE DETAIL 5 ON THIS PAGE
SPLITTER SECTION
ON THIS SHEET ROOF LINE

AIR FLOW AIR FLOW


D2

MIN.
200
AIR FLOW
D1

50

AIR FLOW R= 75mm ``A" MIN. 4


D

45°

``A"
R= 75mm VCD
1.5x``A"
AIR FLOW

R= 75mm
DUCT VCD
AIR FLOW

DUCT

D
D NOTE:
ALL 90° SQUARE BENDS SHALL BE FITTED
WITH TURNING VANES
08 DUCT THROUGH ROOF SLAB DETAIL

05 SINGLE ELBOW 90° 06 DOUBLE ELBOW 90° 07 SMALL BRANCH DUCT TAKE OFF FROM MAIN DUCT
WITH VELOCITIES UP TO 9 m/s.

DUCT CONSTRUCTION LOW PRESSURE UP TO 500 Pa

REINFORCEMENT SUPPORT

LONGEST SIZE OF DUCT LONGITUDINAL ROD SIZE GAL. SPACING


CLASS TYPE Rev Description Date
DUCT (mm) GAGE CONNECTIONS (mm) ANGLE (m)

0-300 G 26 PITTSBURGH - - 6 25x25 2.4


* T1
325 - 450 G 24 PITTSBURGH A 24 8 25x25 2.4
*T12 - 1"X26ga
* T1
475 - 750 G 24 PITTSBURGH C 24 8 25x25 2
*T12 - 1"x26ga
UNIT HOUSING * T1
800 - 900 G 22 PITTSBURGH D 22 10 25x25 2
SEE DETAIL "A" *T12 - 1"x24ga
* T1
950 - 1050 G 22 PITTSBURGH E 22 10 40x40 2
*T12 - 1 1/8"x18ga
DUCT * T1
TABLE 1100 - 1350 G 20 PITTSBURGH F 20 10 40x40 1.8
*T12 - 1½"x24ga ISSUED FOR TENDER 00 23-02-24
MAX WIDTH
ANGLE ( ) *T14 ANGLE REF..
OF DUCT SIZE SIZE H 18 Purpose of issue Rev Date
MINIMUM 75mm GAP 1400 - 1800 G 18 PITTSBURGH H= 1½" x 20 GA 12 40x40 1.8
(cm) (mm) F+ROD
ABOVE DUCT FOR JOINING +1½"x1½"x 3/16"
0-110 25x25x3 *T14 ANGLE REIF. CLIENT:
J 18
EXPANSION BOLTS 1800 - 2130 G 18 PITTSBURGH H= 2" x 20 GA 12 40x40 1.8
111-224 40x40x5 F+ROD
+2" x2" x 3/16"
OVER 225 50x50x6

DROP ROD. - TABLE BASED ON SMACNA DUCTS CONSTRUCTION STANDARD MAG GROUP FZE
ISOLATORS
ALU GLASS INSULATION - CROSS BREAK OR CROSS BEAD DUCT SIDES 480 mm AND LARGER
AS SPECIFIED THERMAL LEAD CONSULTANT:
INSULATION
25 mm THK ACOUSTIC
INSULATION (WHEN SPECIFIED)
STATED DUCT DUCT WALL
DUCT CONNECTION DIMENSION
.

LOCK NUTS & WASHERS. Tel.:04-3353356,P.O.Box34320,Dubai.


HANGER RODS 6mm BOLT & NUT
COLLAR
AS PER TABLE
40mm ANGLE BRACKET. H H MEP CONSULTANT:
UNIT HOUSING SHEET METAL P.O.Box 124246
OR DUCT FLEXIBLE "U" STRIP FOLDED SHEET METAL EDGE Dubai, United Arab Emirates
REINFORCEMENT ANGLES (TYP) Tel: +9714 4255001
RUBBER-IN-SHEAR SPRING TYPE CONNECTION HMEHILARION
MECHANICAL & ELECTRICAL
Fax: +9714 4538102
www.hme.ae
HIGH DENSITY INSULATION CONSULTING ENGINEERS
RECTANGULAR
TO SUIT INSULATION THICK
AIR DUCT
MINIMUM 100mm WIDE
T-12 T-14 T-1
PROJECT:
100mm STANDING S ANGLE REINFORCED DRIVE SLIP KETURAH AMENITY STRIPS AND PARKS

DETAIL "A" PLOT NO. (PLOT NO. 6314130, 6314105, 6316782 & 6313779)
RECTANGULAR GALVANIZED STEEL DUCT CONSTRUCTION HADAEQ SHEIKH MOHAMMED BIN RASHID - DUBAI

TITLE:

09 VIBRATION ISOLATORS HANGER DETAIL 10 AIR DUCT FLEXIBLE CONNECTION MECHANICAL


11 TYPICAL DUCT WORK SUPPORT DETAILS
GENERAL DETAILS
12 TYPICAL DUCT WORK SUPPORT DETAILS
SHEET-1
Original Scale Drawn : Checked : Size :
HME HME A1
Date: Date: