1156-Ma-Dets-M 901 - 00
1156-Ma-Dets-M 901 - 00
1156-Ma-Dets-M 901 - 00
20 GA. MOUNTING BOLTED 3. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS IN METERS
TO WALL AND SLEEVE UNLESS NOTED OTHERWISE. ALL DIMENSIONS TO BE VERIFIED ON
CAULK ALL WALL WATERPROOF SITE & APPROVED BY THE ENGINEER.
SEAMS AND WEATHER PROOF
AROUND (TYP.) BLOCK
SHEET METAL DUCT JOINTS FLEXIBLE MASTIC 4. THIS DRAWING SHOULD BE READ IN CONJUNCTION WITH OTHER
WORK
RELEVANT ARCHITECTURAL, STRUCTURAL, MECHANICAL AND
EXTERNAL LOUVRES ANGLE RIVETED OR TACK
ELECTRICAL DRAWINGS AND ALL RELEVANT SECTIONS OF THE
VARIES
(BY BUILDERS) WELDED AS REQUIRED DUCT SPECIFICATIONS.
(OR PIPE)
DUCT WIDTH
12mm SCREEN
DU
135° MIN
CT
SI
ZE
ROOF LEVEL
+m
in
SLEEVE
25
WATER PROOFING Notes:
%
DUCT BIRD SCREEN
1. All dimensions are in millimeters unless
otherwise specified.
300mm min,
No. 10 x 20 mm SHEET
450mm min
2. For legend & Gen.Notes refer to drawing
METAL SCREW (TYP.)
MINERAL FIBER No. M 001
INSULATION CHB WALL 150 VARIES 150 3. For standard details refer to drawing No. M 901,
ACCESS PANEL
M 902, & M 903
MOTORISE DAMPER
4. All Duct Risers sizes as per the schematic
drawings.
5. If Location of Thermostats are not marked on
Drawings, Contractor to Propose a Suitable
Location and Co-ordinate with Architect's
during Construction stage.
01 DUCT THROUGH WALLS 02 EXTERNAL LOUVRES DUCT c/w MD INSTALLATION 03 GOOSENECK DETAIL 04 ROOF SLAB A/C DUCT/PIPE PENETRATION DETAIL
DUCT INSULATION
METAL CLADDING
GALVANIZED SHEET METAL PLATE SAME
GALVANIZED SHEET METAL PLATE SAME GAUGE AS DUCT.
GAUGE AS DUCT. WELD VANES TO WELD VANES TO PLATE OR ATTACH WITH SEE ARCH'L DWGS FOR DUCT
PLATE OR ATTACH WITH ANGLE ANGLE BRACKET, RIVETED FLASHING DETAILS
DOUBLE THICKNESS VANES SEE DETAIL 5 WEATHERING SKIRT
STANDARD VANES SEE DETAIL 5 ON THIS PAGE
SPLITTER SECTION
ON THIS SHEET ROOF LINE
MIN.
200
AIR FLOW
D1
50
45°
``A"
R= 75mm VCD
1.5x``A"
AIR FLOW
R= 75mm
DUCT VCD
AIR FLOW
DUCT
D
D NOTE:
ALL 90° SQUARE BENDS SHALL BE FITTED
WITH TURNING VANES
08 DUCT THROUGH ROOF SLAB DETAIL
05 SINGLE ELBOW 90° 06 DOUBLE ELBOW 90° 07 SMALL BRANCH DUCT TAKE OFF FROM MAIN DUCT
WITH VELOCITIES UP TO 9 m/s.
REINFORCEMENT SUPPORT
DROP ROD. - TABLE BASED ON SMACNA DUCTS CONSTRUCTION STANDARD MAG GROUP FZE
ISOLATORS
ALU GLASS INSULATION - CROSS BREAK OR CROSS BEAD DUCT SIDES 480 mm AND LARGER
AS SPECIFIED THERMAL LEAD CONSULTANT:
INSULATION
25 mm THK ACOUSTIC
INSULATION (WHEN SPECIFIED)
STATED DUCT DUCT WALL
DUCT CONNECTION DIMENSION
.
DETAIL "A" PLOT NO. (PLOT NO. 6314130, 6314105, 6316782 & 6313779)
RECTANGULAR GALVANIZED STEEL DUCT CONSTRUCTION HADAEQ SHEIKH MOHAMMED BIN RASHID - DUBAI
TITLE:
M 901 00