Ft518 Technicalbrochure USA RevD

Download as pdf or txt
Download as pdf or txt
You are on page 1of 100

FT 518

High - Medium Pressure Gas Regulator

TECHNICAL BROCHURE
Pietro Fiorentini USA Inc.
606 Park Drive | Weirton, WV 26062, United States of America | +1 304 232 9115
fio.westvirginia@fiorentini.com

Pietro Fiorentini S.p.A.


Via E.Fermi, 8/10 | 36057 Arcugnano, Italy | +39 0444 968 511
sales@fiorentini.com

The data is not binding. We reserve the right


to make changes without prior notice.

ft518_technicalbrochure_USA_revB

www.fiorentini.com
Who we are
We are a global organization specialized in designing and manufacturing technologically advanced
solutions for natural gas treatment, transmission and distribution systems.

We are the ideal partner for operators in the Oil & Gas sector, with a business offer that goes across
the whole natural gas chain.

We are in constant evolution to meet our customers’ highest expectations in terms of quality and
reliability.

Our aim is to be a step ahead of the competition, with customized technologies and an after-sale
service program undertaken with the highest grade of professionalism.

Pietro Fiorentini advantages


Localized technical support

Experience since 1940

We operate in over 100 countries

3
High - Medium Pressure Gas Regulator

Area of Application
LEGEND
GA
L
NATURAL GAS

OIL

HYDROGEN
GAS DISTRIBUTION
BIOMETHANE
MEDIUM PRESSURE
HIGH PRESSURE GAS

MEDIUM PRESSURE GAS


He
LOW PRESSURE GAS
indu

CARBON DIOXIDE GAS TRANSMISSION


LIQUID GAS HIGH PRESSURE
Power
generation
LNG marine
transportation

City
Gas gates
liquefaction

Oil
gathering
Gas compression/
booster stations
Topside
wellhead
Floating Gas
units storage

Gas
Offshore processing
wellhead

Subsea
wellhead OIL AND GAS
PRODUCTION

Green icon indicates the application where this product is suitable for

4
AS DISTRIBUTION
LOW PRESSURE
Medium / small Commercial
industry users

Regasification
Residential
users
eavy
ustry

Gas
engines
District
stations

Gas
reverse-flow GREEN GAS
PRODUCTION

P2G &
Methanation

P2Hy

Hydrogen Distribution
Network
Biomethane
Production
Carbon
Capturing

Figure 1 Area of Application Map

5
High - Medium Pressure Gas Regulator

Introduction
FT 518 is a lever-operated regulator controlled by a diaphragm and setting spring which controls
the valve.

It is mainly used for farm tap applications, high-pressure transmission systems and for medium
pressure natural gas distribution networks with previously filtered non-corrosive gases.

According to the European Standard, it is classified as Fail Open.

Inlet pressure

Outlet pressure

Figure 2 FT 518

6
Features and
Calibration ranges
FT 518 is a lever-operated device for high and medium pressure with multiple replaceable orifice.

FT 518 is an unbalanced pressure regulator.

This regulator is suitable for use with previously filtered, non corrosive gases. It is a truly top entry
design which allows an easy maintenance of parts directly in the field without removing the body
from the pipework.

When the built-in token relief valve is active, it prevents undesiderable slam shut trip due to minor
internal leakages or ambient temperature variation.

The modular design of FT 518 pressure regulators allows to retrofit either slam shut valve or integral
full monitor.

Figure 3 FT 518 Figure 4 FT 518 with PM/518

7
High - Medium Pressure Gas Regulator

FT 518 competitive advantages


Compact and simple design Top entry

Operates with high differential pressure Built-in accessories

Built-in filter Easy maintenance

Biomethane compatible and


Token IRV available with specific versions
for full Hydrogen or blending

Features
Features Values
up to 6.94 MPa
Design pressure* (PS1 / DP²)
up to 1000 psig
Standard version Arctic version
from -20 °C to +65 °C from -40 °C to + 65°C
Ambient temperature* (TS¹)**
from -4 °F to +150 °F from -40 °F to +150 °F
from -10°C to + 60°C from -20 °C to +60 °C
Inlet gas temperature*,***
from +14 °F to +140 °F from -4 °F to +140 °F
from 0.14 to 6.94 MPa
Inlet pressure (MAOP / pumax¹)
from 20 to 1000 psig
from 0.034 to 3.4 MPa
Range of downstream pressure (Wd¹)
from 5 to 500 psig
Token IRV, built-in strainer, incorporated monitor,
Available accessories
incorporated slam-shut
49 kPa
Minimum operating differential pressure (Δpmin¹)
7 psig

Accuracy class (AC¹) up to 10 (depending on working conditions)

Lock-up pressure class (SG¹) up to 20 (depending on working conditions)

Nominal size (DN1,2) DN 20 | 3/4”; DN 25 | 1”; DN 50 | 2”

Orifice Sizes 3/32”; 1/8”; 3/16”; 1/4”; 3/8”; 1/2”

Connections threaded NPT, flanged or SW (available soon)

(¹) according to EN334 standard


(²) according to ISO 23555-1 standard
(*) NOTE: Different functional features and/or extended temperature ranges may be available on request. Stated inlet gas temperature range is the
maximum for which the equipment’s full performance, including accuracy is guaranteed. Product may have a different pressure or temperature ranges
according to the version and/or installed accessories.
(**) NOTE: Stated temperature range is the operating range for which the equipment’s mechanical resistance and leakage rate are guaranteed. Some body
materials, if multiple choices are available, may not be suitable for all the available versions shown.
(***) NOTE: Stated temperature range is the range for which the equipment’s full performance, including accuracy and lock-up are guaranteed. Some body
materials, if multiple choices are available, may not be suitable for all the available versions shown.

Table 1 Features

8
Materials
and Approvals
Part Material

Body Ductile iron GS400-18 equivalent to ASTM 536 60-40-18

Cover Die cast aluminum

Valve Nitrile rubber / High performance compound

Seat Brass

Diaphragm Nitrile rubber

Sealing ring Nitrile rubber

Stem Stainless steel

NOTE: The materials indicated above refer to the standard models. Different materials can be provided according to specific needs.

Table 2 Materials

Construction Standards and Approvals


FT 518 regulator, is designed according to the ANSI B 109.4 standard where applicable.
The regulator reacts in opening (Fail Open) according to EN 334 classification.
Leakage class: bubble tight, better than class VIII according to ANSI/FCI 70-3.

ANSI B109.4

9
High - Medium Pressure Gas Regulator

Design pressure by version


Design pressure (PS according to EN334)

Body Slam shut


Version
MPa psig MPa psig

all versions 6.89 1000 6.89 1000

Table 3 Design pressure for body and slam shut

Design pressure (PS according to EN334)

Control head

Parts FT518 LP FT518 HP

MPa psig MPa psig

Covers 5.17 750 5.17 750

Diaphgragm 1.72 250 5.17 750

Max Diaphgragm Δp 1.37 200 4.48 650

Table 4 Design pressure for regulator’s parts

Maximum allowable
operating pressure
MAOP Maximum Allowable Operating Pressure (pumax according to EN334)

Control head

Version FT518 LP FT518 HP

MPa psig MPa psig


MARKING
WITHOUT
CE

all versions 6.89 1000 6.89 1000

Table 5 MAOP Maximum Allowable Operating Pressure without CE marking

10
Springs ranges and
control heads
Range Wh Spring Table
Type Model Operation
MPa psig web link

Main regulator FT 518 LP Manual 0.03 - 0.86 5 - 125 TT 1810

Main regulator FT 518 HP Manual 0.76 - 3.45 110 - 500 TT 1810

Table 6 Settings table

LP FT 518

Spring range (psi)


Pos. Spring item code Spring colour d Lo De
Min. Max.
1 US2701270 Grey 3.5 100 35 5.00 9.99
2 US2701541 White 4 100 35 10.00 20
3 US2701800 Yellow 4.5 100 35 20.01 31.99
4 US2702080 Orange 5 100 35 32.00 49.99
5 US2702290 Red 5.5 100 35 50.00 80
6 US2702460 Green 6 100 35 80.01 124.98
d = Wire Diameter (mm) Lo = Spring Length (mm) De = External Diameter (mm)

Table 7 TT1810 - LP FT 518 setting springs

HP FT 518

Spring range (psi)


Pos. Spring item code Spring colour d Lo De
Min. Max.
1 US2702460 Green 6 100 35 109.99 219.98
2 US2702660 Black 6.5 100 35 220 319.98
3 US2702820 Blue 7 100 35 320 499.98
d = Wire Diameter (mm) Lo = Spring Length (mm) De = External Diameter (mm)

Table 8 TT1810 - HP FT 518 setting springs

11
High - Medium Pressure Gas Regulator

Accessories
For the pressure regulators:

• Integral full monitor PM/518

• Slam shut valve SB/518

• Strainer

Inline monitor
A monitor is an emergency pressure regulator that is usually upstream from the worker regulator.

In an abnormal event when the worker regulator is unable to maintain downstream pressure from
exceeding the set point, the monitor will take over the worker regulator at a set point slightly higher.

An external sensing line is required in upstream monitor configurations, and the internal sensing line
shall be plugged.

Inlet pressure Outlet pressure

Figure 5 FT 518 with inline monitor setup

12
PM/518 monitor
This emergency regulator (monitor) is directly integrated onto the body of the main regulator.
Both pressure regulators, therefore, use the same valve body, although they have independent
actuators and valve’s seats.

The monitor is normally in the fully open position during normal operation of the active/worker regulator
and takes over in the event of its failure.

The operational characteristics of the PM/518 monitor are the same as for the FT 518 regulator.

The Cg coefficients of regulators having an incorporated monitor is 5% lower than those for standard
version.

This solution allows the construction of pressure reduction lines with compact dimensions.

Another great advantage offered by the incorporated monitor regulator is that it can be installed at
any time, even on an existing regulator, without major changes to the pipework.

The main characteristics of this device are:

Compact dimensions

Completely independent

“Fail to open” action

Easy maintenance

Inlet pressure Outlet pressure

Figure 6 FT 518 with PM/518

13
High - Medium Pressure Gas Regulator

Range Wh Spring Table


Type Model Operation
MPa psig web link

Monitor PM/518 LP Manual 0.03 - 0.86 5 - 125 TT 1810

Monitor PM/518 HP Manual 0.76 - 3.45 110 - 500 TT 1810

Table 9 Setting table

General link to the calibration tables: PRESS HERE or use the QR code:

14
SB/518 slam shut valve
FT 518 pressure regulator offers the possibility of installing an incorporated slam shut valve SB/518
and this can be done either during the manufacturing process or be retrofited in the field.

SB/518 is available for all sizes.

Retrofitting can be done without modifying the pressure regulator assembly.


With the built-in slam shut, the Cg valve coefficients is 5% lower than the corresponding version
without.

The main characteristics of this device are:

Over Pressure Shut-Off Compact dimensions

Under Pressure Shut-Off Easy maintenance

Internal by-pass Remote tripping option

Push botton for tripping test Limit switch option

Inlet pressure

Outlet pressure

Figure 7 FT 518 with SB/518

15
High - Medium Pressure Gas Regulator

Pressure switch types and ranges

Range Wh Spring Table


SSV Type Model Operation
MPa psig web link

OPSO 0.2 - 2.2 29 - 319


SB/518 103 TT 1331
UPSO 0.02 - 1.9 2.9 - 275.6

OPSO 1.5 - 4.5 217.6 - 652.6


SB/518 104 TT 1331
UPSO 0.16 - 4.1 23.2 - 594.6

Table 10 Settings table

MOD.103M (OPSO) - 103MH (OPSO)

Spring range (psi)


Pos. Spring item code Spring colour d Lo De
Min. Max.
1 US2701530 Yellow 4 60 35 29.00 58.01
2 US2701790 Yellow/Black 4.5 60 35 58.02 108.77
3 US2702280 White/Red 5.5 60 35 108.7 217.54
4 US2702454 Fuchsia 6 70 35 217.56 319.07
d = Wire Diameter (mm) Lo = Spring Length (mm) De = External Diameter (mm)

Table 11 TT 872 - MOD.103M (OPSO) - 103MH (OPSO) setting springs

MOD.103M (UPSO)

Spring range (psi)


Pos. Spring item code Spring colour d Lo De
Min. Max.
1 US2700464 Orange 1.7 40 15 2.90 7.25
2 US2700513 Red 2 40 15 7.26 11.60
3 US2700713 Green 2.3 40 15 11.61 24.65
4 US2700750 Black 2.5 40 15 24.67 58.01
5 US2700985 Brown 3 40 15 58.02 116.02
d = Wire Diameter (mm) Lo = Spring Length (mm) De = External Diameter (mm)

Table 12 TT 872 - MOD.103M (UPSO) setting springs

MOD.103MH (UPSO)

Spring range (psi)


Pos. Spring item code Spring colour d Lo De
Min. Max.
US2700985 Brown 3 40 15
1 116.02 188.54
US2700980 Blue 3 35 15
US2700985 Brown 3 40 15
2 188.55 275.5
US2700985 Brown 3 40 15
d = Wire Diameter (mm) Lo = Spring Length (mm) De = External Diameter (mm)

Table 13 TT 872 - MOD.103MH (UPSO) setting springs

16
MOD.104M (OPSO) - 104MH (OPSO)

Spring range (psi)


Pos. Spring item code Spring colour d Lo De
Min. Max.
2 US2702280 White/Red 5.5 60 35 217.56 435.09
3 US2702454 Fuchsia 6 70 35 435.11 652.64
d = Wire Diameter (mm) Lo = Spring Length (mm) De = External Diameter (mm)

Table 14 TT 872 - MOD.104M (OPSO) - 104MH (OPSO) setting springs

MOD.104M (UPSO)

Spring range (psi)


Pos. Spring item code Spring colour d Lo De
Min. Max.
1 US2700713 Green 2.3 40 15 23.20 43.50
2 US2700750 Black 2.5 40 15 43.52 116.02
3 US2700985 Brown 3 40 15 116.04 261.05
d = Wire Diameter (mm) Lo = Spring Length (mm) De = External Diameter (mm)

Table 15 TT 872 - MOD.104M (UPSO) setting springs

MOD.104MH (UPSO)

Spring range (psi)


Pos. Spring item code Spring colour d Lo De
Min. Max.
US2700985 Brown 3 40 15
1 261.05 435.09
US2700980 Blue 3 35 15
US2700985 Brown 3 40 15
2 435.11 594.63
US2700985 Brown 3 40 15
d = Wire Diameter (mm) Lo = Spring Length (mm) De = External Diameter (mm)
Table 16 TT 872 - MOD.104MH (UPSO) setting springs

General link to the calibration tables: PRESS HERE or use the QR code:

17
High - Medium Pressure Gas Regulator

Integral strainer (Fig. 8 - Item 2)


FT 518 is equipped with a removable internal 300 micron strainer to prevent foreign particles, such
as weld slag or PE shavings, to get stucked between orifice and seat/disk thus preventing lockup.

Futhermore, the strainer provides protection to all integral accessories as well as downstream
customer’s assets.

The strainer can be easily accessed without removing the regulator body from the piping, to be
cleaned or replaced, if necessary.

Token relief valve (Fig. 8 - Item 3)


FT 518 has an optional token relief valve that discharges a small volume of gas to the atmosphere
when the regulator exceeds the relief valve set point. Token relief valve cannot be used as overpressure
protection device.

During no-flow conditions, thermal expansion of the gas can cause downstream static pressure to
build up. The token relief valve will prevent downstream pressure from rising, and if equipped, prevent
nuisance tripping of the slam shut valve.

2
Figure 8 FT 518 components location

18
Outlet pressure sensing
FT 518 can sense downstream pressure internally (4a), externally (4b), or by using both.

Internal sense versions have a sense line built into the outlet of the regulator body.

Externally sensed versions require the internal sense line to be plugged, and use a secondary external
sense line connected to the lower diaphragm case.

When using the external sense configuration without plugging the internal sense line, the higher
pressure of the two will provide the control pressure to the lower diaphragm.

This can be used to improve response time in applications where the load changes quickly.

4b

4a

Figure 9 FT 518 components location

19
High - Medium Pressure Gas Regulator

Safety limitation
In case of a single regulator supplied without built-in overpressure protection device (SSV, IMD or
IFM), the regulator shall be protected with a secondary means of overpressure protection per the
DOT §192.740 & NFPA 54 5.9.3.1 standard.

The over pressure protection must be provided per code capable of limiting the downstream pressure
to the system.

FT 518 Safety limitation table

Maximum pressure to
Maximum pressure to Maximum diaphragm
MAXIMUM prevent burst of casings
prevent external leak other casing overpressure
PRESSURE during abnormal operation
than IRV action (internal (above setpoint) to prevent
DESCRIPTION (leak and internal parts
parts damage may occur) damage to internal parts
damage may occur)

DIAPHRAGM CASING
Die casting aluminum Die casting aluminum Die casting aluminum
MATERIAL

Type FT518 psig 250 750 60


LP
MPa 1.72 5.17 0.41

Type FT518 psig 250 750 150


LP IRV
MPa 1.72 5.17 1.03

Type PM/518 psig 250 750 60


LP
MPa 1.72 5.17 0.41

Type PM/518 psig 250 750 150


LP IRV
MPa 1.72 5.17 1.03

Type FT518 psig 750 750 120


HP
MPa 5.17 5.17 0.83

Type FT518 psig 750 750 240


HP IRV
MPa 5.17 5.17 1.65

Type PM/518 psig 750 750 120


HP
MPa 5.17 5.17 0.83

Type PM/518 psig 750 750 120


HP IRV
MPa 5.17 5.17 0.83

Table 17 Safety limitation

20
Weights
and Dimensions
FT 518
E D
Ø
N

A
Q

H
P

C
S F G
L
Figure 10 FT 518 dimensions

Weights and Dimensions (for other connections please contact your closest Pietro Fiorentini representative)
[mm] inches

A 195 7.7”
B 213 8.4”
C 35.5 1.4”
D 162 6.38”
E 88 3.46”
F 47 1.85”
G 143.5 5.65”
H 231 9.1”
L 190.5 7.5”
P 46 1.8”
Q 171 6.73”
103 for DN20 and DN25 4 for DN20 and DN25
S
132 for DN50 5.2 for DN50
Ø 100 3.94”
SENSING 1/4 NPT
VENT 3/4 NPT

Weight Kg lbs

1” NPT and 3/4” NPT 3.5 7.7


2” NPT 4.6 10.1

Table 18 Weights and dimensions

21
High - Medium Pressure Gas Regulator

FT 518 + PM/518

E D

A
Q

H
P

C
F G
L

Figure 11 FT 518 with PM/518 dimensions

Weights and Dimensions (for other connections please contact your closest Pietro Fiorentini representative)
[mm] inches

A 195 7.7”
B 213 8.4”
C 35.5 1.4”
D 162 6.38”
E 162 6.38”
F 143.5 5.65”
G 143.5 5.65”
H 231 9.1”
L 287 11.3”
P 46 1.8”
Q 171 6.73”
103 for DN20 and DN25 4 for DN20 and DN25
S
132 for DN50 5.2 for DN50
Ø 100 3.94”
SENSING 1/4 NPT
VENT 3/4 NPT

Weight Kg lbs

1” NPT and 3/4” NPT 5.5 12.12


2” NPT 6.6 14.5

Table 19 Weights and dimensions

22
FT 518 + SB/518
E D
Ø

H
B
A

C
R

S F G
T L
Figure 12 FT 518 with SB/518 dimensions

Weights and Dimensions (for other connections please contact your closest Pietro Fiorentini representative)
[mm] inches

A 94 3.7”
B 102 4.0”
C 36 1.4”
D 162 6.38”
E 188 7.4”
F 168 6.6”
G 143.5 5.65”
H 231 9.1”
I 152.5 6.0”
L 312.4 12.3”
P 55 2.15”
103 for DN20 and DN25 4 for DN20 and DN25
S
132 for DN50 5.2 for DN50
T 132 5.2”
Ø 100 3.94”
SENSING 1/4 NPT
VENT 3/4 NPT

Weight Kg lbs

1” NPT and 3/4” NPT 7.4 16.3


2” NPT 8.5 18.7

Table 20 Weights and dimensions

23
High - Medium Pressure Gas Regulator

Sizing and Cg
In general, the choice of a regulator is made based on the calculation of the flow rate determined by
the use of formulae using the flow rate coefficients (Cg) and the form factor (K1) as indicated by the
EN 334 standard. Sizing available through Pietro Fiorentini's online sizing programme.

Flow rate coefficient

Orifice sizes 3/32” 1/8” 3/16” 1/4” 3/8” 1/2”

Cg 7.1 13 27.8 50 110 150

K1 110 110 110 110 110 110

Table 21 Flow rate coefficient

For sizing PRESS HERE or use the QR code:

Note: In case you do not have the proper credentials to access, feel free to contact your closest
Pietro Fiorentini representative.

In general the online sizing considers multiple variables as the regulator is installed in a system,
enabling a better and multiperspective approach to the sizing.

For different gases, and for natural gas with a different relative density other than 0.61 (compared to
air), the correction coefficients from the following formula shall be applied:

Fc = 175.8 Fc = 316.44

S x (273.16 + T) S x (459.67 + T)

S = relative density (refere to Table 22) S = relative density (refere to Table 22)
T = gas temperature ( °C ) T = gas temperature ( °F )

24
Correction Factor Fc

Gas Type Relative Density S Correction Factor Fc

Air 1.00 0.78

Propane 1.53 0.63

Butane 2.00 0.55

Nitrogen 0.97 0.79

Oxygen 1.14 0.73

Carbon Dioxide 1.52 0.63

Note: the table shows the Fc correction factors valid for Gas, calculated at a temperature of 15°C | 59 °F and at the
declared relative density.

Table 22 Correction Factor Fc

Nm3/h Reference conditions:


Flow rate conversion
T= 0 °C; P= 1 bar(a) | T= 32 °F; P= 14.5 psi(a)
Stm3/h Reference conditions:
Stm3/h x 0.94795 = Nm3/h
T= 15 °C; P= 1 bar(a) | T= 59 °F; P= 14.5 psi(a)

Table 23 Flow rate conversion

CAUTION:
In order to get optimal performance, to avoid premature erosion phenomena and to limit noise
emissions, it is recommended to check the gas speed and its compliance with local practice and
regulations. The gas speed at the outlet flange may be calculated by means of the following formula:

Q 1 - 0.002 x Pd Q 14.504 - 0.002 x Pd


V = 345.92 x x V = 0.0498 x x
DN2 1 + Pd DN2 14.504 + Pd

V = gas speed in m/s V = gas speed in ft/s


Q = gas flow rate in Stm3/h Q = gas flow rate in Scfh
DN = nominal size of regular in mm DN = nominal size of regular in inches
Pd = outlet pressure in barg Pd = outlet pressure in psi

25
High - Medium Pressure Gas Regulator

Flow capacity tables


FT 518 - 3/32 STD - LP - DN 3/4” | 20 mm
Inlet pressure: from 0.69 MPa [100 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.06 MPa [10 psig] to 0.86 MPa [125 psig]

FT 518 - 3/32 STD - LP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm /h


3
Scfh Stm /h
3
Scfh Stm /h
3
Scfh Stm /h
3
Scfh Stm3/h Scfh

0.69 100 28 1000 28 1000 28 1000 28 1000 - -

1.04 150 38 1400 38 1400 38 1400 38 1400 34 1200

1.39 200 49 1800 49 1800 50 1800 50 1800 49 1800

2.08 300 76 2700 76 2700 80 2900 76 2700 72 2600

3.47 500 120 4300 120 4300 125 4400 115 4100 115 4100

5.21 750 180 6400 180 6400 180 6400 180 6400 175 6200

6.94 1000 245 8700 250 8900 250 8900 250 8900 240 8500

Cg = 9 K1= 120

FT 518 - 3/32 STD - LP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

0.69 100 36 1300 36 1300 36 1300 34 1300 - -

1.04 150 52 1900 52 1900 52 1900 52 1900 38 1400

1.39 200 68 2500 68 2500 68 2500 68 2500 64 2300

2.08 300 100 3600 100 3600 100 3600 100 3600 100 3600

3.47 500 163 5800 163 5800 163 5800 163 5800 163 5800

5.21 750 242 8600 242 8600 242 8600 242 8600 242 8600

6.94 1000 322 11400 322 11400 322 11400 322 11400 322 11400

Cg = 9 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

26
FT 518 - 1/8 STD - LP - DN 3/4” | 20 mm
Inlet pressure: from 0.69 MPa [100 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.06 MPa [10 psig] to 0.86 MPa [125 psig]

FT 518 - 1/8 STD - LP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

0.69 100 50 1800 42 1500 48 1700 47 1700 - -

1.04 150 69 2500 69 2500 70 2500 69 2500 60 2200

1.39 200 90 3200 90 3200 95 3400 90 3200 89 3200

2.08 300 130 4600 130 4600 135 4800 125 4500 125 4500

3.47 500 220 7800 220 7800 225 8000 215 7600 210 7500

5.21 750 330 11700 330 11700 340 12000 320 11300 320 11300

6.94 1000 380 13500 410 14500 440 15600 380 13500 420 14900

Cg = 16 K1= 120

FT 518 - 1/8 STD - LP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm /h


3
Scfh Stm /h
3
Scfh Stm /h
3
Scfh Stm /h
3
Scfh Stm3/h Scfh

0.69 100 65 2300 65 2300 65 2300 61 2200 - -

1.04 150 93 3300 93 3300 93 3300 93 3300 68 2400

1.39 200 121 4300 121 4300 121 4300 121 4300 114 4100

2.08 300 177 6300 177 6300 177 6300 177 6300 177 6300

3.47 500 290 10300 290 10300 290 10300 290 10300 290 10300

5.21 750 431 15300 431 15300 431 15300 431 15300 431 15300

6.94 1000 572 20200 572 20200 572 20200 572 20200 572 20200

Cg = 16 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

27
High - Medium Pressure Gas Regulator

FT 518 - 3/16 STD - LP - DN 3/4” | 20 mm


Inlet pressure: from 0.69 MPa [100 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.06 MPa [10 psig] to 0.86 MPa [125 psig]

FT 518 - 3/16 STD - LP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

0.69 100 120 4300 105 3800 108 3900 100 3600 - -

1.04 150 150 5300 150 5300 160 5700 150 5300 140 5000

1.39 200 190 6800 200 7100 210 7500 200 7100 200 7100

2.08 300 250 8900 280 9900 300 10600 290 10300 290 10300

3.47 500 275 9800 350 12400 510 18100 480 17000 480 17000

5.21 750 300 10600 420 14900 540 19100 700 24800 720 25500

6.94 1000 - - 500 17700 550 19500 840 29700 930 32900

Cg = 34 K1= 120

FT 518 - 3/16 STD - LP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm /h3


Scfh Stm /h
3
Scfh Stm /h
3
Scfh Stm /h
3
Scfh Stm3/h Scfh

0.69 100 137 4900 137 4900 137 4900 130 4600 - -

1.04 150 197 7000 197 7000 197 7000 197 7000 144 5100

1.39 200 257 9100 257 9100 257 9100 257 9100 243 8600

2.08 300 377 13400 377 13400 377 13400 377 13400 377 13400

3.47 500 616 21800 616 21800 616 21800 616 21800 616 21800

5.21 750 916 32400 916 32400 916 32400 916 32400 916 32400

6.94 1000 - - 1215 42900 1215 42900 1215 42900 1215 42900

Cg = 34 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

28
FT 518 - 1/4 STD - LP - DN 3/4” | 20 mm
Inlet pressure: from 0.69 MPa [100 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.06 MPa [10 psig] to 0.86 MPa [125 psig]

FT 518 - 1/4 STD - LP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

0.69 100 180 6400 190 6800 175 6200 185 6600 - -

1.04 150 200 7100 280 9900 290 10300 280 9900 230 8200

1.39 200 210 7500 330 11700 360 12800 360 12800 350 12400

2.08 300 260 9200 350 12400 500 17700 540 19100 520 18400

3.47 500 280 9900 410 14500 750 26500 780 27600 850 30100

5.21 750 - - 440 15600 800 28300 830 29400 1330 47000

6.94 1000 - - 550 19500 850 30100 860 30400 1400 49500

Cg = 58 K1= 120

FT 518 - 1/4 STD - LP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm /h3


Scfh Stm /h
3
Scfh Stm /h
3
Scfh Stm /h
3
Scfh Stm3/h Scfh

0.69 100 234 8300 234 8300 234 8300 221 7900 - -

1.04 150 336 11900 336 11900 336 11900 336 11900 245 8700

1.39 200 438 15500 438 15500 438 15500 438 15500 414 14700

2.08 300 643 22700 643 22700 643 22700 643 22700 643 22700

3.47 500 967 34200 1051 37200 1051 37200 1051 37200 1051 37200

5.21 750 - - 1365 48300 1562 55200 1562 55200 1562 55200

6.94 1000 - - 1365 48300 1764 62400 2072 73200 2072 73200

Cg = 58 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

29
High - Medium Pressure Gas Regulator

FT 518 - 3/8 STD - LP - DN 3/4” | 20 mm


Inlet pressure: from 0.69 MPa [100 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.06 MPa [10 psig] to 0.86 MPa [125 psig]

FT 518 - 3/8 STD - LP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

0.69 100 210 7500 340 12100 350 12400 330 11700 - -

1.04 150 220 7800 390 13800 410 14500 500 17700 440 15600

1.39 200 300 10600 410 14500 440 15600 700 24800 600 21200

2.08 300 - - 460 16300 800 28300 750 26500 900 31800

3.47 500 - - 700 24800 900 31800 800 28300 1200 42400

5.21 750 - - - - 1000 35400 1000 35400 1400 49500

6.94 1000 - - - - - - 1100 38900 1500 53000

Cg = 115 K1= 120

FT 518 - 3/8 STD - LP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm /h 3


Scfh Stm /h3
Scfh Stm /h3
Scfh Stm /h
3
Scfh Stm3/h Scfh

0.69 100 464 16400 464 16400 464 16400 439 15500 - -

1.04 150 667 23600 667 23600 667 23600 667 23600 486 17200

1.39 200 869 30700 869 30700 869 30700 869 30700 821 29100

2.08 300 - - 1274 45000 1274 45000 1274 45000 1274 45000

3.47 500 - - 1365 48300 1764 62400 2084 73600 2084 73600

5.21 750 - - - - 1764 62400 2969 104900 3097 109400

6.94 1000 - - - - - - 2969 104900 4109 145100

Cg = 115 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

30
FT 518 - 1/2 STD - LP - DN 3/4” | 20 mm
Inlet pressure: from 0.69 MPa [100 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.06 MPa [10 psig] to 0.86 MPa [125 psig]

FT 518 - 1/2 STD - LP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

0.69 100 260 9200 550 19500 550 19500 500 17700 - -

1.04 150 280 9900 680 24100 700 24800 650 23000 520 18400

1.39 200 - - 750 26500 750 26500 750 26500 680 24100

2.08 300 - - 800 28300 850 30100 850 30100 1000 35400

3.47 500 - - - - 1000 35400 1000 35400 1450 51200

5.21 750 - - - - - - 1300 46000 1900 67100

6.94 1000 - - - - - - - - 2000 70700

Cg = 180 K1= 120

FT 518 - 1/2 STD - LP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm /h 3


Scfh Stm /h3
Scfh Stm /h3
Scfh Stm /h3
Scfh Stm3/h Scfh

0.69 100 726 25700 726 25700 726 25700 686 24300 - -

1.04 150 967 34200 1043 36900 1043 36900 1043 36900 760 26900

1.39 200 - - 1360 48100 1360 48100 1360 48100 1286 45500

2.08 300 - - 1365 48300 1764 62400 1994 70500 1994 70500

3.47 500 - - - - 1764 62400 2969 104900 3262 115200

5.21 750 - - - - - - 2969 104900 4847 171200

6.94 1000 - - - - - - - - 5614 198300

Cg = 180 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

31
High - Medium Pressure Gas Regulator

FT 518 - 3/32 STD - HP - DN 3/4” | 20 mm


Inlet pressure: from 1.04 MPa [150 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.76 MPa [110 psig] to 3.47 MPa [500 psig]

FT 518 - 3/32 STD - HP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

1.04 150 36 1300 - - - - - - - -

1.39 200 48 1700 41 1500 - - - - - -

2.08 300 70 2500 75 2700 75 2700 - - - -

2.78 400 105 3800 95 3400 100 3600 95 3400 - -

3.47 500 110 3900 115 4100 108 3900 120 4300 - -

5.21 750 165 5900 175 6200 170 6100 185 6600 185 6600

6.94 1000 212 7500 215 7600 230 8200 250 8900 252 8900

Cg = 9 K1= 120

FT 518 - 3/32 STD - HP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm /h


3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm3/h Scfh

1.04 150 45 1600 - - - - - - - -

1.39 200 66 2400 58 2100 - - - - - -

2.08 300 100 3600 99 3500 92 3300 - - - -

2.78 400 131 4700 131 4700 131 4700 113 4000 - -

3.47 500 163 5800 163 5800 163 5800 157 5600 - -

5.21 750 242 8600 242 8600 242 8600 242 8600 226 8000

6.94 1000 322 11400 322 11400 322 11400 322 11400 320 11300

Cg = 9 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

32
FT 518 - 1/8 STD - HP - DN 3/4” | 20 mm
Inlet pressure: from 1.04 MPa [150 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.76 MPa [110 psig] to 3.47 MPa [500 psig]

FT 518 - 1/8 STD - HP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

1.04 150 56 2000 - - - - - - - -

1.39 200 85 3100 87 3100 - - - - - -

2.08 300 110 3900 130 4600 130 4600 - - - -

2.78 400 153 5500 154 5500 170 6100 170 6100 - -

3.47 500 190 6800 210 7500 210 7500 210 7500 - -

5.21 750 270 9600 320 11300 320 11300 320 11300 336 11900

6.94 1000 345 12200 410 14500 430 15200 455 16100 455 16100

Cg = 16 K1= 120

FT 518 - 1/8 STD - HP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm /h


3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm3/h Scfh

1.04 150 80 2900 - - - - - - - -

1.39 200 118 4200 102 3700 - - - - - -

2.08 300 177 6300 176 6300 164 5800 - - - -

2.78 400 234 8300 234 8300 232 8200 200 7100 - -

3.47 500 290 10300 290 10300 290 10300 280 9900 - -

5.21 750 431 15300 431 15300 431 15300 431 15300 401 14200

6.94 1000 572 20200 572 20200 572 20200 572 20200 569 20100

Cg = 16 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

33
High - Medium Pressure Gas Regulator

FT 518 - 3/16 STD - HP - DN 3/4” | 20 mm


Inlet pressure: from 1.04 MPa [150 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.76 MPa [110 psig] to 3.47 MPa [500 psig]

FT 518 - 3/16 STD - HP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

1.04 150 135 4800 - - - - - - - -

1.39 200 190 6800 175 6200 - - - - - -

2.08 300 265 9400 300 10600 300 10600 - - - -

2.78 400 400 14200 400 14200 400 14200 380 13500 - -

3.47 500 460 16300 490 17400 490 17400 485 17200 - -

5.21 750 500 17700 730 25800 710 25100 750 26500 762 26900

6.94 1000 620 21900 1000 35400 960 33900 1000 35400 970 34300

Cg = 34 K1= 120

FT 518 - 3/16 STD - HP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm /h


3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm3/h Scfh

1.04 150 169 6000 - - - - - - - -

1.39 200 251 8900 218 7700 - - - - - -

2.08 300 377 13400 374 13200 348 12400 - - - -

2.78 400 496 17600 496 17600 493 17500 425 15100 - -

3.47 500 616 21800 616 21800 616 21800 595 21000 - -

5.21 750 916 32400 916 32400 916 32400 916 32400 853 30200

6.94 1000 1215 42900 1215 42900 1215 42900 1215 42900 1209 42700

Cg = 34 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

34
FT 518 - 1/4 STD - HP - DN 3/4” | 20 mm
Inlet pressure: from 1.04 MPa [150 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.76 MPa [110 psig] to 3.47 MPa [500 psig]

FT 518 - 1/4 STD - HP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

1.04 150 175 6200 - - - - - - - -

1.39 200 310 11000 310 11000 - - - - - -

2.08 300 450 15900 520 18400 520 18400 - - - -

2.78 400 620 21900 690 24400 680 24100 630 22300 - -

3.47 500 650 23000 790 27900 850 30100 850 30100 - -

5.21 750 800 28300 1150 40700 1300 46000 1380 48800 1372 48500

6.94 1000 1050 37100 1550 54800 1780 62900 1800 63600 1780 62900

Cg = 58 K1= 120

FT 518 - 1/4 STD - HP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm /h


3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm3/h Scfh

1.04 150 289 10200 - - - - - - - -

1.39 200 428 15200 371 13200 - - - - - -

2.08 300 643 22700 638 22600 594 21000 - - - -

2.78 400 847 30000 847 30000 841 29800 725 25700 - -

3.47 500 1051 37200 1051 37200 1051 37200 1014 35900 - -

5.21 750 1562 55200 1562 55200 1562 55200 1562 55200 1454 51400

6.94 1000 2072 73200 2072 73200 2072 73200 2072 73200 2062 72900

Cg = 58 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

35
High - Medium Pressure Gas Regulator

FT 518 - 3/8 STD - HP - DN 3/4” | 20 mm


Inlet pressure: from 1.04 MPa [150 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.76 MPa [110 psig] to 3.47 MPa [500 psig]

FT 518 - 3/8 STD - HP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

1.04 150 450 15900 - - - - - - - -

1.39 200 500 17700 550 19500 - - - - - -

2.08 300 600 21200 830 29400 1008 35600 - - - -

2.78 400 750 26500 1050 37100 1456 51500 1100 38900 - -

3.47 500 900 31800 1500 53000 1740 61500 1400 49500 - -

5.21 750 1100 38900 1600 56500 1900 67100 2400 84800 2400 84800

6.94 1000 1400 49500 1700 60100 2000 70700 2500 88300 3500 123600

Cg = 115 K1= 120

FT 518 - 3/8 STD - HP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm /h3


Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm3/h Scfh

1.04 150 572 20300 - - - - - - - -

1.39 200 849 30000 736 26100 - - - - - -

2.08 300 1274 45000 1264 44700 1178 41700 - - - -

2.78 400 1679 59300 1679 59300 1668 58900 1438 50800 - -

3.47 500 2084 73600 2084 73600 2084 73600 2011 71100 - -

5.21 750 3097 109400 3097 109400 3097 109400 3097 109400 2884 101900

6.94 1000 4109 145100 4109 145100 4109 145100 4109 145100 4088 144400

Cg = 115 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

36
FT 518 - 1/2 STD - HP - DN 3/4” | 20 mm
Inlet pressure: from 1.04 MPa [150 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.76 MPa [110 psig] to 3.47 MPa [500 psig]

FT 518 - 1/2 STD - HP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

1.04 150 415 14700 - - - - - - - -

1.39 200 570 20200 600 21200 - - - - - -

2.08 300 800 28300 1050 37100 1000 35400 - - - -

2.78 400 1150 40700 1300 46000 1500 53000 1400 49434 - -

3.47 500 1300 46000 1600 56500 2050 72400 2320 81919 - -

5.21 750 - - - - - - 2500 88275 3600 127200

6.94 1000 - - - - - - 2800 98868 3800 134200

Cg = 180 K1= 120

FT 518 - 1/2 STD - HP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm /h 3


Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm3/h Scfh

1.04 150 896 31700 - - - - - - - -

1.39 200 1329 47000 1153 40800 - - - - - -

2.08 300 1994 70500 1979 69900 1845 65200 - - - -

2.78 400 2628 92900 2628 92900 2611 92200 2251 79500 - -

3.47 500 3262 115200 3262 115200 3262 115200 3148 111200 - -

5.21 750 - - - - - - 4847 171200 4513 159400

6.94 1000 - - - - - - 6432 227200 6399 226000

Cg = 180 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

37
High - Medium Pressure Gas Regulator

FT 518 - 3/32 - PM518 LP - DN 3/4” | 20 mm


Inlet pressure: from 0.69 MPa [100 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.06 MPa [10 psig] to 0.86 MPa [125 psig]

FT 518 - 3/32 - PM518 LP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

0.69 100 27 1000 27 1000 28 1000 28 1000 - -

1.04 150 36 1300 37 1400 36 1300 37 1400 34 1200

1.39 200 46 1700 47 1700 45 1600 48 1700 48 1700

2.08 300 72 2600 74 2700 70 2500 70 2500 70 2500

3.47 500 - - 110 3900 115 4100 110 3900 110 3900

5.21 750 - - 165 5900 170 6100 170 6100 170 6100

6.94 1000 - - - - - - 235 8300 230 8200

Cg = 9 K1= 120

FT 518 - 3/32 - PM518 LP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm /h3


Scfh Stm /h3
Scfh Stm /h3
Scfh Stm /h
3
Scfh Stm3/h Scfh

0.69 100 36 1300 36 1300 36 1300 34 1300 - -

1.04 150 52 1900 52 1900 52 1900 52 1900 38 1400

1.39 200 68 2500 68 2500 68 2500 68 2500 64 2300

2.08 300 100 3600 100 3600 100 3600 100 3600 100 3600

3.47 500 - - 163 5800 163 5800 163 5800 163 5800

5.21 750 - - 242 8600 242 8600 242 8600 242 8600

6.94 1000 - - - - - - 322 11400 322 11400

Cg = 9 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

38
FT 518 - 1/8 - PM518 LP - DN 3/4” | 20 mm
Inlet pressure: from 0.69 MPa [100 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.06 MPa [10 psig] to 0.86 MPa [125 psig]

FT 518 - 1/8 - PM518 LP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

0.69 100 48 1700 42 1500 45 1600 47 1700 - -

1.04 150 66 2400 65 2300 67 2400 68 2500 60 2200

1.39 200 85 3100 85 3100 89 3200 88 3200 86 3100

2.08 300 120 4300 120 4300 130 4600 125 4500 120 4300

3.47 500 - - 200 7100 220 7800 215 7600 200 7100

5.21 750 - - 310 11000 320 11300 320 11300 290 10300

6.94 1000 - - - - - - 370 13100 390 13800

Cg = 16 K1= 120

FT 518 - 1/8 - PM518 LP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm /h3


Scfh Stm /h3
Scfh Stm /h3
Scfh Stm /h
3
Scfh Stm3/h Scfh

0.69 100 65 2300 65 2300 65 2300 61 2200 - -

1.04 150 93 3300 93 3300 93 3300 93 3300 68 2400

1.39 200 121 4300 121 4300 121 4300 121 4300 114 4100

2.08 300 177 6300 177 6300 177 6300 177 6300 177 6300

3.47 500 - - 290 10300 290 10300 290 10300 290 10300

5.21 750 - - 431 15300 431 15300 431 15300 431 15300

6.94 1000 - - - - - - 572 20200 572 20200

Cg = 16 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

39
High - Medium Pressure Gas Regulator

FT 518 - 3/16 - PM518 LP - DN 3/4” | 20 mm


Inlet pressure: from 0.69 MPa [100 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.06 MPa [10 psig] to 0.86 MPa [125 psig]

FT 518 - 3/16 - PM518 LP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

0.69 100 100 3600 105 3800 100 3600 90 3200 - -

1.04 150 130 4600 145 5200 155 5500 145 5200 130 4600

1.39 200 175 6200 190 6800 210 7500 190 6800 190 6800

2.08 300 240 8500 270 9600 280 9900 260 9200 275 9800

3.47 500 - - 330 11700 470 16600 470 16600 470 16600

5.21 750 - - 385 13600 520 18400 650 23000 680 24100

6.94 1000 - - - - - - 752 26600 860 30400

Cg = 34 K1= 120

FT 518 - 3/16 - PM518 LP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm /h3


Scfh Stm /h3
Scfh Stm /h3
Scfh Stm /h
3
Scfh Stm3/h Scfh

0.69 100 137 4900 137 4900 137 4900 130 4600 - -

1.04 150 197 7000 197 7000 197 7000 197 7000 144 5100

1.39 200 257 9100 257 9100 257 9100 257 9100 243 8600

2.08 300 377 13400 377 13400 377 13400 377 13400 377 13400

3.47 500 - - 616 21800 616 21800 616 21800 616 21800

5.21 750 - - 916 32400 916 32400 916 32400 916 32400

6.94 1000 - - - - - - 1215 42900 1215 42900

Cg = 34 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

40
FT 518 - 1/4 - PM518 LP - DN 3/4” | 20 mm
Inlet pressure: from 0.69 MPa [100 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.06 MPa [10 psig] to 0.86 MPa [125 psig]

FT 518 - 1/4 - PM518 LP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

0.69 100 150 5300 180 6400 170 6100 180 6400 - -

1.04 150 185 6600 260 9200 280 9900 270 9600 200 7100

1.39 200 200 7100 320 11300 345 12200 350 12400 330 11700

2.08 300 250 8900 320 11300 470 16600 510 18100 480 17000

3.47 500 - - 380 13500 700 24800 725 25600 800 28300

5.21 750 - - 410 14500 790 27900 715 25300 950 33600

6.94 1000 - - - - - - 800 28300 1000 35400

Cg = 58 K1= 120

FT 518 - 1/4 - PM518 LP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm /h3


Scfh Stm /h3
Scfh Stm /h3
Scfh Stm /h
3
Scfh Stm3/h Scfh

0.69 100 234 8300 234 8300 234 8300 221 7900 - -

1.04 150 336 11900 336 11900 336 11900 336 11900 245 8700

1.39 200 438 15500 438 15500 438 15500 438 15500 414 14700

2.08 300 643 22700 643 22700 643 22700 643 22700 643 22700

3.47 500 - - 1051 37200 1051 37200 1051 37200 1051 37200

5.21 750 - - 1365 48300 1562 55200 1562 55200 1562 55200

6.94 1000 - - - - - - 2072 73200 2072 73200

Cg = 58 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

41
High - Medium Pressure Gas Regulator

FT 518 - 3/8 - PM518 LP - DN 3/4” | 20 mm


Inlet pressure: from 0.69 MPa [100 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.06 MPa [10 psig] to 0.86 MPa [125 psig]

FT 518 - 3/8 - PM518 LP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

0.69 100 205 7300 250 8900 340 12100 250 8900 - -

1.04 150 215 7600 380 13500 390 13800 450 15900 400 14200

1.39 200 300 10600 390 13800 430 15200 600 21200 500 17700

2.08 300 - - 420 14900 720 25500 710 25100 650 23000

3.47 500 - - 630 22300 790 27900 750 26500 900 31800

5.21 750 - - - - 1000 35400 970 34300 1000 35400

6.94 1000 - - - - - - 1000 35400 1100 38900

Cg = 115 K1= 120

FT 518 - 3/8 - PM518 LP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm /h 3


Scfh Stm /h3
Scfh Stm /h3
Scfh Stm /h
3
Scfh Stm3/h Scfh

0.69 100 464 16400 464 16400 464 16400 439 15500 - -

1.04 150 667 23600 667 23600 667 23600 667 23600 486 17200

1.39 200 869 30700 869 30700 869 30700 869 30700 821 29100

2.08 300 - - 1274 45000 1274 45000 1274 45000 1274 45000

3.47 500 - - 1365 48300 1764 62400 2084 73600 2084 73600

5.21 750 - - - - 1764 62400 2969 104900 3097 109400

6.94 1000 - - - - - - 2969 104900 4109 145100

Cg = 115 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

42
FT 518 - 1/2 - PM518 LP - DN 3/4” | 20 mm
Inlet pressure: from 0.69 MPa [100 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.06 MPa [10 psig] to 0.86 MPa [125 psig]

FT 518 - 1/2 - PM518 LP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

0.69 100 260 9200 350 12400 400 14200 340 12100 - -

1.04 150 300 10600 400 14200 500 17700 390 13800 420 14900

1.39 200 - - 420 14900 540 19100 450 15900 587 20800

2.08 300 - - 450 15900 750 26500 850 30100 650 23000

3.47 500 - - - - 850 30100 940 33200 1000 35400

5.21 750 - - - - - - 1150 40700 1100 38900

6.94 1000 - - - - - - - - 1200 42400

Cg = 180 K1= 120

FT 518 - 1/2 - PM518 LP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm /h3


Scfh Stm /h3
Scfh Stm /h3
Scfh Stm /h3
Scfh Stm3/h Scfh

0.69 100 726 25700 726 25700 726 25700 686 24300 - -

1.04 150 967 34200 1043 36900 1043 36900 1043 36900 760 26900

1.39 200 - - 1360 48100 1360 48100 1360 48100 1286 45500

2.08 300 - - 1365 48300 1764 62400 1994 70500 1994 70500

3.47 500 - - - - 1764 62400 2969 104900 3262 115200

5.21 750 - - - - - - 2969 104900 4847 171200

6.94 1000 - - - - - - - - 5614 198300

Cg = 180 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

43
High - Medium Pressure Gas Regulator

FT 518 - 3/32 - PM518 HP - DN 3/4” | 20 mm


Inlet pressure: from 1.04 MPa [150 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.76 MPa [110 psig] to 3.47 MPa [500 psig]

FT 518 - 3/32 - PM518 HP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

1.04 150 36 1300 - - - - - - - -

1.39 200 48 1700 41 1500 - - - - - -

2.08 300 70 2500 75 2700 75 2700 - - - -

2.78 400 105 3800 95 3400 100 3600 95 3400 - -

3.47 500 110 3900 115 4100 108 3900 120 4300 - -

5.21 750 165 5900 175 6200 170 6100 185 6600 185 6600

6.94 1000 212 7500 215 7600 230 8200 250 8900 252 8900

Cg = 9 K1= 120

FT 518 - 3/32 - PM518 HP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm /h


3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm3/h Scfh

1.04 150 45 1600 - - - - - - - -

1.39 200 66 2400 58 2100 - - - - - -

2.08 300 100 3600 99 3500 92 3300 - - - -

2.78 400 131 4700 131 4700 131 4700 113 4000 - -

3.47 500 163 5800 163 5800 163 5800 157 5600 - -

5.21 750 242 8600 242 8600 242 8600 242 8600 226 8000

6.94 1000 322 11400 322 11400 322 11400 322 11400 320 11300

Cg = 9 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

44
FT 518 - 1/8 - PM518 HP - DN 3/4” | 20 mm
Inlet pressure: from 1.04 MPa [150 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.76 MPa [110 psig] to 3.47 MPa [500 psig]

FT 518 - 1/8 - PM518 HP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

1.04 150 56 2000 - - - - - - - -

1.39 200 85 3100 87 3100 - - - - - -

2.08 300 110 3900 130 4600 130 4600 - - - -

2.78 400 153 5500 154 5500 170 6100 170 6100 - -

3.47 500 190 6800 210 7500 210 7500 210 7500 - -

5.21 750 270 9600 320 11300 320 11300 320 11300 336 11900

6.94 1000 345 12200 410 14500 430 15200 455 16100 455 16100

Cg = 16 K1= 120

FT 518 - 1/8 - PM518 HP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm /h


3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm3/h Scfh

1.04 150 80 2900 - - - - - - - -

1.39 200 118 4200 102 3700 - - - - - -

2.08 300 177 6300 176 6300 164 5800 - - - -

2.78 400 234 8300 234 8300 232 8200 200 7100 - -

3.47 500 290 10300 290 10300 290 10300 280 9900 - -

5.21 750 431 15300 431 15300 431 15300 431 15300 401 14200

6.94 1000 572 20200 572 20200 572 20200 572 20200 569 20100

Cg = 16 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

45
High - Medium Pressure Gas Regulator

FT 518 - 3/16 - PM518 HP - DN 3/4” | 20 mm


Inlet pressure: from 1.04 MPa [150 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.76 MPa [110 psig] to 3.47 MPa [500 psig]

FT 518 - 3/16 - PM518 HP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

1.04 150 135 4800 - - - - - - - -

1.39 200 190 6800 175 6200 - - - - - -

2.08 300 265 9400 300 10600 300 10600 - - - -

2.78 400 400 14200 400 14200 400 14200 380 13500 - -

3.47 500 460 16300 490 17400 490 17400 485 17200 - -

5.21 750 500 17700 730 25800 710 25100 750 26500 762 26900

6.94 1000 620 21900 1000 35400 960 33900 1000 35400 970 34300

Cg = 34 K1= 120

FT 518 - 3/16 - PM518 HP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm /h


3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm3/h Scfh

1.04 150 169 6000 - - - - - - - -

1.39 200 251 8900 218 7700 - - - - - -

2.08 300 377 13400 374 13200 348 12400 - - - -

2.78 400 496 17600 496 17600 493 17500 425 15100 - -

3.47 500 616 21800 616 21800 616 21800 595 21000 - -

5.21 750 916 32400 916 32400 916 32400 916 32400 853 30200

6.94 1000 1215 42900 1215 42900 1215 42900 1215 42900 1209 42700

Cg = 34 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

46
FT 518 - 1/4 - PM518 HP - DN 3/4” | 20 mm
Inlet pressure: from 1.04 MPa [150 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.76 MPa [110 psig] to 3.47 MPa [500 psig]

FT 518 - 1/4 - PM518 HP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

1.04 150 175 6200 - - - - - - - -

1.39 200 310 11000 310 11000 - - - - - -

2.08 300 450 15900 520 18400 520 18400 - - - -

2.78 400 620 21900 690 24400 680 24100 630 22300 - -

3.47 500 650 23000 790 27900 850 30100 850 30100 - -

5.21 750 800 28300 1150 40700 1300 46000 1250 44200 1200 42400

6.94 1000 1050 37100 1550 54800 1780 62900 1600 56500 1550 54800

Cg = 58 K1= 120

FT 518 - 1/4 - PM518 HP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm /h


3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm3/h Scfh

1.04 150 289 10200 - - - - - - - -

1.39 200 428 15200 371 13200 - - - - - -

2.08 300 643 22700 638 22600 594 21000 - - - -

2.78 400 847 30000 847 30000 841 29800 725 25700 - -

3.47 500 1051 37200 1051 37200 1051 37200 1014 35900 - -

5.21 750 1562 55200 1562 55200 1562 55200 1562 55200 1454 51400

6.94 1000 2072 73200 2072 73200 2072 73200 2072 73200 2062 72900

Cg = 58 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

47
High - Medium Pressure Gas Regulator

FT 518 - 3/8 - PM518 HP - DN 3/4” | 20 mm


Inlet pressure: from 1.04 MPa [150 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.76 MPa [110 psig] to 3.47 MPa [500 psig]

FT 518 - 3/8 - PM518 HP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

1.04 150 325 11500 - - - - - - - -

1.39 200 450 15900 510 18100 - - - - - -

2.08 300 580 20500 830 29400 870 30800 - - - -

2.78 400 750 26500 1050 37100 1300 46000 1100 38900 - -

3.47 500 900 31800 1500 53000 1580 55800 1400 49500 - -

5.21 750 1100 38900 1600 56500 1700 60100 2400 84800 2160 76300

6.94 1000 1400 49500 1700 60100 1800 63600 2500 88300 3000 106000

Cg = 115 K1= 120

FT 518 - 3/8 - PM518 HP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm /h3


Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm3/h Scfh

1.04 150 572 20300 - - - - - - - -

1.39 200 849 30000 736 26100 - - - - - -

2.08 300 1274 45000 1264 44700 1178 41700 - - - -

2.78 400 1679 59300 1679 59300 1668 58900 1438 50800 - -

3.47 500 2084 73600 2084 73600 2084 73600 2011 71100 - -

5.21 750 3097 109400 3097 109400 3097 109400 3097 109400 2884 101900

6.94 1000 4109 145100 4109 145100 4109 145100 4109 145100 4088 144400

Cg = 115 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

48
FT 518 - 1/2 - PM518 HP - DN 3/4” | 20 mm
Inlet pressure: from 1.04 MPa [150 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.76 MPa [110 psig] to 3.47 MPa [500 psig]

FT 518 - 1/2 - PM518 HP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

1.04 150 415 14700 - - - - - - - -

1.39 200 570 20200 600 21200 - - - - - -

2.08 300 800 28300 1050 37100 900 31800 - - - -

2.78 400 1150 40700 1250 44200 1380 48800 1150 49434 - -

3.47 500 1300 46000 1500 53000 1650 58300 1660 81919 - -

5.21 750 - - - - - - 2450 88275 2250 79500

6.94 1000 - - - - - - 2600 98868 3200 113000

Cg = 180 K1= 120

FT 518 - 1/2 - PM518 HP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm /h3


Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm3/h Scfh

1.04 150 896 31700 - - - - - - - -

1.39 200 1329 47000 1153 40800 - - - - - -

2.08 300 1994 70500 1979 69900 1845 65200 - - - -

2.78 400 2628 92900 2628 92900 2611 92200 2251 79500 - -

3.47 500 3262 115200 3262 115200 3262 115200 3148 111200 - -

5.21 750 - - - - - - 4847 171200 4513 159400

6.94 1000 - - - - - - 6432 227200 6399 226000

Cg = 180 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

49
High - Medium Pressure Gas Regulator

FT 518 - 3/32 STD - LP - DN 1” | 25 mm


Inlet pressure: from 0.69 MPa [100 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.06 MPa [10 psig] to 0.86 MPa [125 psig]

FT 518 - 3/32 STD recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

0.69 100 28 1000 28 1000 28 1000 28 1000 - -

1.04 150 38 1400 38 1400 38 1400 38 1400 34 1200

1.39 200 49 1800 49 1800 50 1800 50 1800 49 1800

2.08 300 76 2700 76 2700 80 2900 76 2700 72 2600

3.47 500 120 4300 120 4300 125 4400 115 4100 115 4100

5.21 750 150 5300 180 6400 180 6400 180 6400 175 6200

6.94 1000 180 6400 250 8900 250 8900 250 8900 240 8500

Cg = 9 K1= 120

FT 518 - 3/32 STD flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm /h


3
Scfh Stm /h
3
Scfh Stm /h
3
Scfh Stm /h
3
Scfh Stm3/h Scfh

0.69 100 36 1300 36 1300 36 1300 34 1300 - -

1.04 150 52 1900 52 1900 52 1900 52 1900 38 1400

1.39 200 68 2500 68 2500 68 2500 68 2500 64 2300

2.08 300 100 3600 100 3600 100 3600 100 3600 100 3600

3.47 500 163 5800 163 5800 163 5800 163 5800 163 5800

5.21 750 242 8600 242 8600 242 8600 242 8600 242 8600

6.94 1000 322 11400 322 11400 322 11400 322 11400 322 11400

Cg = 9 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

50
FT 518 - 1/8 STD - LP - DN 1” | 25 mm
Inlet pressure: from 0.69 MPa [100 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.06 MPa [10 psig] to 0.86 MPa [125 psig]

FT 518 - 1/8 STD recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

0.69 100 50 1800 42 1500 48 1700 47 1700 - -

1.04 150 69 2500 69 2500 70 2500 69 2500 60 2200

1.39 200 90 3200 90 3200 95 3400 90 3200 89 3200

2.08 300 130 4600 130 4600 135 4800 125 4500 125 4500

3.47 500 220 7800 220 7800 225 8000 215 7600 210 7500

5.21 750 330 11700 330 11700 340 12000 320 11300 320 11300

6.94 1000 380 13500 430 15200 440 15600 380 13500 420 14900

Cg = 16 K1= 120

FT 518 - 1/8 STD flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm /h


3
Scfh Stm /h
3
Scfh Stm /h
3
Scfh Stm /h
3
Scfh Stm3/h Scfh

0.69 100 65 2300 65 2300 65 2300 61 2200 - -

1.04 150 93 3300 93 3300 93 3300 93 3300 68 2400

1.39 200 121 4300 121 4300 121 4300 121 4300 114 4100

2.08 300 177 6300 177 6300 177 6300 177 6300 177 6300

3.47 500 290 10300 290 10300 290 10300 290 10300 290 10300

5.21 750 431 15300 431 15300 431 15300 431 15300 431 15300

6.94 1000 572 20200 572 20200 572 20200 572 20200 572 20200

Cg = 16 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

51
High - Medium Pressure Gas Regulator

FT 518 - 3/16 STD - LP - DN 1” | 25 mm


Inlet pressure: from 0.69 MPa [100 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.06 MPa [10 psig] to 0.86 MPa [125 psig]

FT 518 - 3/16 STD recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

0.69 100 120 4300 110 3900 108 3900 100 3600 - -

1.04 150 150 5300 150 5300 160 5700 150 5300 140 5000

1.39 200 200 7100 200 7100 210 7500 200 7100 200 7100

2.08 300 280 9900 280 9900 300 10600 290 10300 290 10300

3.47 500 410 14500 430 15200 510 18100 480 17000 480 17000

5.21 750 500 17700 600 21200 540 19100 700 24800 720 25500

6.94 1000 - - 750 26500 800 28300 950 33600 950 33600

Cg = 34 K1= 120

FT 518 - 3/16 STD flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm /h3


Scfh Stm /h
3
Scfh Stm /h
3
Scfh Stm /h
3
Scfh Stm3/h Scfh

0.69 100 137 4900 137 4900 137 4900 130 4600 - -

1.04 150 197 7000 197 7000 197 7000 197 7000 144 5100

1.39 200 257 9100 257 9100 257 9100 257 9100 243 8600

2.08 300 377 13400 377 13400 377 13400 377 13400 377 13400

3.47 500 616 21800 616 21800 616 21800 616 21800 616 21800

5.21 750 916 32400 916 32400 916 32400 916 32400 916 32400

6.94 1000 - - 1215 42900 1215 42900 1215 42900 1215 42900

Cg = 34 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

52
FT 518 - 1/4 STD - LP - DN 1” | 25 mm
Inlet pressure: from 0.69 MPa [100 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.06 MPa [10 psig] to 0.86 MPa [125 psig]

FT 518 - 1/4 STD recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

0.69 100 180 6400 190 6800 190 6800 185 6600 - -

1.04 150 270 9600 280 9900 290 10300 280 9900 240 8500

1.39 200 350 12400 350 12400 360 12800 360 12800 350 12400

2.08 300 480 17000 490 17400 500 17700 520 18400 520 18400

3.47 500 530 18800 750 26500 750 26500 850 30100 850 30100

5.21 750 - - 850 30100 850 30100 1160 41000 1300 46000

6.94 1000 - - 900 31800 900 31800 1400 49500 1700 60100

Cg = 58 K1= 120

FT 518 - 1/4 STD flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

0.69 100 234 8300 234 8300 234 8300 221 7900 - -

1.04 150 336 11900 336 11900 336 11900 336 11900 245 8700

1.39 200 438 15500 438 15500 438 15500 438 15500 414 14700

2.08 300 643 22700 643 22700 643 22700 643 22700 643 22700

3.47 500 1051 37200 1051 37200 1051 37200 1051 37200 1051 37200

5.21 750 - - 1562 55200 1562 55200 1562 55200 1562 55200

6.94 1000 - - 2072 73200 2072 73200 2072 73200 2072 73200

Cg = 58 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

53
High - Medium Pressure Gas Regulator

FT 518 - 3/8 STD - LP - DN 1” | 25 mm


Inlet pressure: from 0.69 MPa [100 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.06 MPa [10 psig] to 0.86 MPa [125 psig]

FT 518 - 3/8 STD recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

0.69 100 220 7800 340 12100 350 12400 340 12100 - -

1.04 150 400 14200 460 16300 410 14500 500 17700 440 15600

1.39 200 430 15200 700 24800 440 15600 650 23000 800 28300

2.08 300 - - 750 26500 800 28300 1050 37100 1110 39200

3.47 500 - - 800 28300 900 31800 1700 60100 1800 63600

5.21 750 - - - - 1000 35400 1750 61800 2700 95400

6.94 1000 - - - - - - 1800 63600 3400 120100

Cg = 115 K1= 120

FT 518 - 3/8 STD flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

0.69 100 464 16400 464 16400 464 16400 439 15500 - -

1.04 150 667 23600 667 23600 667 23600 667 23600 486 17200

1.39 200 869 30700 869 30700 869 30700 869 30700 821 29100

2.08 300 - - 1274 45000 1274 45000 1274 45000 1274 45000

3.47 500 - - 2084 73600 2084 73600 2084 73600 2084 73600

5.21 750 - - - - 2859 101000 3097 109400 3097 109400

6.94 1000 - - - - - - 4109 145100 4109 145100

Cg = 115 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

54
FT 518 - 1/2 STD - LP - DN 1” | 25 mm
Inlet pressure: from 0.69 MPa [100 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.06 MPa [10 psig] to 0.86 MPa [125 psig]

FT 518 - 1/2 STD recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

0.69 100 420 14900 550 19500 600 21200 550 19500 - -

1.04 150 460 16300 680 24100 800 28300 850 30100 600 21200

1.39 200 480 17000 750 26500 950 33600 1100 38900 880 31100

2.08 300 - - 800 28300 1000 35400 1500 53000 1550 54800

3.47 500 - - - - 1000 35400 1800 63600 2850 100700

5.21 750 - - - - - - 1900 67100 3900 137800

6.94 1000 - - - - - - - - 4000 141300

Cg = 160 K1= 120

FT 518 - 1/2 STD flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm /h3


Scfh Stm /h3
Scfh Stm /h3
Scfh Stm /h3
Scfh Stm3/h Scfh

0.69 100 646 22900 646 22900 646 22900 610 21600 - -

1.04 150 927 32800 927 32800 927 32800 927 32800 676 23900

1.39 200 1209 42700 1209 42700 1209 42700 1209 42700 1143 40400

2.08 300 - - 1773 62600 1773 62600 1773 62600 1773 62600

3.47 500 - - - - 2859 101000 2900 102400 2900 102400

5.21 750 - - - - - - 4308 152200 4308 152200

6.94 1000 - - - - - - - - 5717 201900

Cg = 160 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

55
High - Medium Pressure Gas Regulator

FT 518 - 3/32 STD - HP - DN 1” | 25 mm


Inlet pressure: from 1.04 MPa [150 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.76 MPa [110 psig] to 3.47 MPa [500 psig]

FT 518 - 3/32 STD - HP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

1.04 150 39 1400 - - - - - - - -

1.39 200 48 1700 48 1700 - - - - - -

2.08 300 70 2500 75 2700 75 2700 - - - -

2.78 400 105 3800 100 3600 100 3600 100 3600 - -

3.47 500 110 3900 120 4300 126 4500 128 4600 - -

5.21 750 165 5900 185 6600 180 6400 188 6700 185 6600

6.94 1000 240 8500 256 9100 250 8900 245 8700 245 8700

Cg = 9 K1= 120

FT 518 - 3/32 STD - HP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm /h


3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm3/h Scfh

1.04 150 45 1600 - - - - - - - -

1.39 200 66 2400 58 2100 - - - - - -

2.08 300 100 3600 99 3500 92 3300 - - - -

2.78 400 131 4700 131 4700 131 4700 113 4000 - -

3.47 500 163 5800 163 5800 163 5800 157 5600 - -

5.21 750 242 8600 242 8600 242 8600 242 8600 226 8000

6.94 1000 322 11400 322 11400 322 11400 322 11400 320 11300

Cg = 9 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

56
FT 518 - 1/8 STD - HP -DN 1” | 25 mm
Inlet pressure: from 1.04 MPa [150 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.76 MPa [110 psig] to 3.47 MPa [500 psig]

FT 518 - 1/8 STD - HP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

1.04 150 60 2200 - - - - - - - -

1.39 200 85 3100 90 3200 - - - - - -

2.08 300 110 3900 140 5000 140 5000 - - - -

2.78 400 153 5500 180 6400 185 6600 175 6200 - -

3.47 500 200 7100 220 7800 225 8000 228 8100 - -

5.21 750 300 10600 330 11700 340 12100 340 12100 330 11700

6.94 1000 450 15900 450 15900 450 15900 455 16100 430 15200

Cg = 16 K1= 120

FT 518 - 1/8 STD - HP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm /h


3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm3/h Scfh

1.04 150 80 2900 - - - - - - - -

1.39 200 118 4200 102 3700 - - - - - -

2.08 300 177 6300 176 6300 164 5800 - - - -

2.78 400 234 8300 234 8300 232 8200 200 7100 - -

3.47 500 290 10300 290 10300 290 10300 280 9900 - -

5.21 750 431 15300 431 15300 431 15300 431 15300 401 14200

6.94 1000 572 20200 572 20200 572 20200 572 20200 569 20100

Cg = 16 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

57
High - Medium Pressure Gas Regulator

FT 518 - 3/16 STD - HP - DN 1” | 25 mm


Inlet pressure: from 1.04 MPa [150 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.76 MPa [110 psig] to 3.47 MPa [500 psig]

FT 518 - 3/16 STD - HP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

1.04 150 137 4900 - - - - - - - -

1.39 200 190 6800 200 7100 - - - - - -

2.08 300 280 9900 310 11000 310 11000 - - - -

2.78 400 400 14200 405 14400 405 14400 380 13500 - -

3.47 500 460 16300 500 17700 490 17400 480 17000 - -

5.21 750 680 24100 750 26500 740 26200 740 26200 760 26900

6.94 1000 935 33100 970 34300 1010 35700 980 34700 980 34700

Cg = 34 K1= 120

FT 518 - 3/16 STD - HP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm /h


3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm3/h Scfh

1.04 150 169 6000 - - - - - - - -

1.39 200 251 8900 218 7700 - - - - - -

2.08 300 377 13400 374 13200 348 12400 - - - -

2.78 400 496 17600 496 17600 493 17500 425 15100 - -

3.47 500 616 21800 616 21800 616 21800 595 21000 - -

5.21 750 916 32400 916 32400 916 32400 916 32400 853 30200

6.94 1000 1215 42900 1215 42900 1215 42900 1215 42900 1209 42700

Cg = 34 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

58
FT 518 - 1/4 STD - HP - DN 1” | 25 mm
Inlet pressure: from 1.04 MPa [150 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.76 MPa [110 psig] to 3.47 MPa [500 psig]

FT 518 - 1/4 STD - HP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

1.04 150 220 7800 - - - - - - - -

1.39 200 320 11300 340 12100 - - - - - -

2.08 300 460 16300 530 18800 540 19100 - - - -

2.78 400 620 21900 700 24800 715 25300 670 23700 - -

3.47 500 750 26500 860 30400 920 32500 920 32500 - -

5.21 750 1000 35400 1350 47700 1360 48100 1360 48100 1370 48400

6.94 1000 1690 59700 1650 58300 1820 64300 1760 62200 1800 63600

Cg = 58 K1= 120

FT 518 - 1/4 STD - HP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm /h


3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm3/h Scfh

1.04 150 289 10200 - - - - - - - -

1.39 200 428 15200 371 13200 - - - - - -

2.08 300 643 22700 638 22600 594 21000 - - - -

2.78 400 847 30000 847 30000 841 29800 725 25700 - -

3.47 500 1051 37200 1051 37200 1051 37200 1014 35900 - -

5.21 750 1562 55200 1562 55200 1562 55200 1562 55200 1454 51400

6.94 1000 2072 73200 2072 73200 2072 73200 2072 73200 2062 72900

Cg = 58 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

59
High - Medium Pressure Gas Regulator

FT 518 - 3/8 STD - HP - DN 1” | 25 mm


Inlet pressure: from 1.04 MPa [150 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.76 MPa [110 psig] to 3.47 MPa [500 psig]

FT 518 - 3/8 STD - HP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

1.04 150 390 13800 - - - - - - - -

1.39 200 550 19500 630 22300 - - - - - -

2.08 300 700 24800 840 29700 1000 35400 - - - -

2.78 400 1110 39200 1100 38900 1400 49500 1200 42400 - -

3.47 500 1400 49500 1450 51200 1760 62200 1550 54800 - -

5.21 750 1800 63600 1600 56500 1900 67100 2300 81300 2450 86600

6.94 1000 2400 84800 1800 63600 2000 70700 3600 127200 3650 128900

Cg = 115 K1= 120

FT 518 - 3/8 STD - HP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm /h3


Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm3/h Scfh

1.04 150 572 20300 - - - - - - - -

1.39 200 849 30000 736 26100 - - - - - -

2.08 300 1274 45000 1264 44700 1178 41700 - - - -

2.78 400 1679 59300 1679 59300 1668 58900 1438 50800 - -

3.47 500 2084 73600 2084 73600 2084 73600 2011 71100 - -

5.21 750 3097 109400 3097 109400 3097 109400 3097 109400 2884 101900

6.94 1000 4109 145100 4109 145100 4109 145100 4109 145100 4088 144400

Cg = 115 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

60
FT 518 - 1/2 STD - HP - DN 1” | 25 mm
Inlet pressure: from 1.04 MPa [150 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.76 MPa [110 psig] to 3.47 MPa [500 psig]

FT 518 - 1/2 STD HP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

1.04 150 550 19500 - - - - - - - -

1.39 200 750 26500 900 31800 - - - - - -

2.08 300 1230 43500 1350 47700 1450 51200 - - - -

2.78 400 1400 49500 1450 51200 1900 67100 1550 49434 - -

3.47 500 1680 59400 1900 67100 2500 88300 2400 81919 - -

5.21 750 - - - - - - 3000 88275 4000 141300

6.94 1000 - - - - - - 4500 98868 4600 162500

Cg = 180 K1= 120

FT 518 - 1/2 STD - HP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm /h3


Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm3/h Scfh

1.04 150 896 31700 - - - - - - - -

1.39 200 1329 47000 1153 40800 - - - - - -

2.08 300 1994 70500 1979 69900 1845 65200 - - - -

2.78 400 2628 92900 2628 92900 2611 92200 2251 79500 - -

3.47 500 3262 115200 3262 115200 3262 115200 3148 111200 - -

5.21 750 - - - - - - 4847 171200 4513 159400

6.94 1000 - - - - - - 6432 227200 6399 226000

Cg = 180 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

61
High - Medium Pressure Gas Regulator

FT 518 - 3/32 - PM518 LP - DN 1” | 25 mm


Inlet pressure: from 0.69 MPa [100 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.06 MPa [10 psig] to 0.86 MPa [125 psig]

FT 518 - 3/32 STD - PM518 LP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

0.69 100 27 1000 27 1000 28 1000 28 1000 - -

1.04 150 36 1300 37 1400 36 1300 37 1400 34 1200

1.39 200 46 1700 47 1700 45 1600 48 1700 48 1700

2.08 300 72 2600 74 2700 70 2500 70 2500 70 2500

3.47 500 - - 110 3900 116 4100 110 3900 110 3900

5.21 750 - - 165 5900 168 6000 170 6100 170 6100

6.94 1000 - - - - - - 235 8300 230 8200

Cg = 9 K1= 120

FT 518 - 3/32 - PM518 LP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm /h3


Scfh Stm /h3
Scfh Stm /h3
Scfh Stm /h
3
Scfh Stm3/h Scfh

0.69 100 36 1300 36 1300 36 1300 34 1300 - -

1.04 150 52 1900 52 1900 52 1900 52 1900 38 1400

1.39 200 68 2500 68 2500 68 2500 68 2500 64 2300

2.08 300 100 3600 100 3600 100 3600 100 3600 100 3600

3.47 500 - - 163 5800 163 5800 163 5800 163 5800

5.21 750 - - 242 8600 242 8600 242 8600 242 8600

6.94 1000 - - - - - - 322 11400 322 11400

Cg = 9 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

62
FT 518 - 1/8 - PM518 LP - DN 1” | 25 mm
Inlet pressure: from 0.69 MPa [100 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.06 MPa [10 psig] to 0.86 MPa [125 psig]

FT 518 - 1/8 - PM518 LP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

0.69 100 48 1700 42 1500 45 1600 47 1700 - -

1.04 150 66 2400 65 2300 67 2400 68 2500 60 2200

1.39 200 85 3100 85 3100 89 3200 88 3200 86 3100

2.08 300 120 4300 120 4300 130 4600 125 4500 120 4300

3.47 500 - - 200 7100 218 7700 215 7600 200 7100

5.21 750 - - 300 10600 320 11300 320 11300 290 10300

6.94 1000 - - - - - - 370 13100 390 13800

Cg = 16 K1= 120

FT 518 - 1/8 - PM518 LP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm /h3


Scfh Stm /h3
Scfh Stm /h3
Scfh Stm /h
3
Scfh Stm3/h Scfh

0.69 100 65 2300 65 2300 65 2300 61 2200 - -

1.04 150 93 3300 93 3300 93 3300 93 3300 68 2400

1.39 200 121 4300 121 4300 121 4300 121 4300 114 4100

2.08 300 177 6300 177 6300 177 6300 177 6300 177 6300

3.47 500 - - 290 10300 290 10300 290 10300 290 10300

5.21 750 - - 431 15300 431 15300 431 15300 431 15300

6.94 1000 - - - - - - 572 20200 572 20200

Cg = 16 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

63
High - Medium Pressure Gas Regulator

FT 518 - 3/16 - PM518 LP - DN 1” | 25 mm


Inlet pressure: from 0.69 MPa [100 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.06 MPa [10 psig] to 0.86 MPa [125 psig]

FT 518 - 3/16 - PM518 LP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

0.69 100 100 3600 100 3600 105 3800 90 3200 - -

1.04 150 130 4600 145 5200 155 5500 145 5200 130 4600

1.39 200 180 6400 190 6800 210 7500 190 6800 190 6800

2.08 300 260 9200 267 9500 280 9900 260 9200 275 9800

3.47 500 - - 400 14200 470 16600 470 16600 470 16600

5.21 750 - - 550 19500 550 19500 650 23000 680 24100

6.94 1000 - - - - - - 850 30100 880 31100

Cg = 34 K1= 120

FT 518 - 3/16 - PM518 LP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm /h3


Scfh Stm /h3
Scfh Stm /h3
Scfh Stm /h
3
Scfh Stm3/h Scfh

0.69 100 137 4900 137 4900 137 4900 130 4600 - -

1.04 150 197 7000 197 7000 197 7000 197 7000 144 5100

1.39 200 257 9100 257 9100 257 9100 257 9100 243 8600

2.08 300 377 13400 377 13400 377 13400 377 13400 377 13400

3.47 500 - - 616 21800 616 21800 616 21800 616 21800

5.21 750 - - 916 32400 916 32400 916 32400 916 32400

6.94 1000 - - - - - - 1215 42900 1215 42900

Cg = 34 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

64
FT 518 - 1/4 - PM518 LP - DN 1” | 25 mm
Inlet pressure: from 0.69 MPa [100 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.06 MPa [10 psig] to 0.86 MPa [125 psig]

FT 518 - 1/4 - PM518 LP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

0.69 100 160 5700 180 6400 180 6400 180 6400 - -

1.04 150 250 8900 260 9200 280 9900 270 9600 220 7800

1.39 200 330 11700 320 11300 345 12200 350 12400 330 11700

2.08 300 450 15900 450 15900 470 16600 495 17500 480 17000

3.47 500 490 17400 690 24400 700 24800 790 27900 800 28300

5.21 750 - - 790 27900 790 27900 1000 35400 1150 40700

6.94 1000 - - - - - - 1300 46000 1500 53000

Cg = 58 K1= 120

FT 518 - 1/4 - PM518 LP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm /h3


Scfh Stm /h3
Scfh Stm /h3
Scfh Stm /h
3
Scfh Stm3/h Scfh

0.69 100 234 8300 234 8300 234 8300 221 7900 - -

1.04 150 336 11900 336 11900 336 11900 336 11900 245 8700

1.39 200 438 15500 438 15500 438 15500 438 15500 414 14700

2.08 300 643 22700 643 22700 643 22700 643 22700 643 22700

3.47 500 1051 37200 1051 37200 1051 37200 1051 37200 1051 37200

5.21 750 - - 1562 55200 1562 55200 1562 55200 1562 55200

6.94 1000 - - - - - - 2072 73200 2072 73200

Cg = 58 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

65
High - Medium Pressure Gas Regulator

FT 518 - 3/8 - PM518 LP - DN 1” | 25 mm


Inlet pressure: from 0.69 MPa [100 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.06 MPa [10 psig] to 0.86 MPa [125 psig]

FT 518 - 3/8 - PM518 LP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

0.69 100 220 7800 250 8900 340 12100 300 10600 - -

1.04 150 390 13800 380 13500 390 13800 450 15900 400 14200

1.39 200 400 14200 480 17000 430 15200 600 21200 710 25100

2.08 300 - - 600 21200 720 25500 1000 35400 1080 38200

3.47 500 - - 700 24800 790 27900 1600 56500 1700 60100

5.21 750 - - - - 1000 35400 1700 60100 2500 88300

6.94 1000 - - - - - - 1800 63600 3300 116600

Cg = 115 K1= 120

FT 518 - 3/8 - PM518 LP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm /h 3


Scfh Stm /h3
Scfh Stm /h3
Scfh Stm /h
3
Scfh Stm3/h Scfh

0.69 100 464 16400 464 16400 464 16400 439 15500 - -

1.04 150 667 23600 667 23600 667 23600 667 23600 486 17200

1.39 200 869 30700 869 30700 869 30700 869 30700 821 29100

2.08 300 - - 1274 45000 1274 45000 1274 45000 1274 45000

3.47 500 - - 2084 73600 2084 73600 2084 73600 2084 73600

5.21 750 - - - - 2859 101000 3097 109400 3097 109400

6.94 1000 - - - - - - 4109 145100 4109 145100

Cg = 115 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

66
FT 518 - 1/2 - PM518 LP - DN 1” | 25 mm
Inlet pressure: from 0.69 MPa [100 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.06 MPa [10 psig] to 0.86 MPa [125 psig]

FT 518 - 1/2 - PM518 LP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

0.69 100 360 12800 350 12400 450 15900 360 12800 - -

1.04 150 400 14200 540 19100 800 28300 500 17700 580 20500

1.39 200 - - 550 19500 650 23000 630 22300 760 26900

2.08 300 - - 690 24400 800 28300 1100 38900 1100 38900

3.47 500 - - - - 850 30100 1700 60100 2300 81300

5.21 750 - - - - - - 1700 60100 2500 88300

6.94 1000 - - - - - - - - 2600 91900

Cg = 160 K1= 120

FT 518 - 1/2 - PM518 LP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm /h3


Scfh Stm /h3
Scfh Stm /h3
Scfh Stm /h3
Scfh Stm3/h Scfh

0.69 100 646 22900 646 22900 646 22900 610 21600 - -

1.04 150 927 32800 927 32800 927 32800 927 32800 676 23900

1.39 200 - - 1209 42700 1209 42700 1209 42700 1143 40400

2.08 300 - - 1773 62600 1773 62600 1773 62600 1773 62600

3.47 500 - - - - 2859 101000 2900 102400 2900 102400

5.21 750 - - - - - - 4308 152200 4308 152200

6.94 1000 - - - - - - - - 5717 201900

Cg = 160 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

67
High - Medium Pressure Gas Regulator

FT 518 - 3/32 - PM518 HP - DN 1” | 25 mm


Inlet pressure: from 1.04 MPa [150 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.76 MPa [110 psig] to 3.47 MPa [500 psig]

FT 518 - 3/32 - PM518 HP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

1.04 150 39 1400 - - - - - - - -

1.39 200 48 1700 48 1700 - - - - - -

2.08 300 70 2500 75 2700 75 2700 - - - -

2.78 400 105 3800 100 3600 100 3600 100 3600 - -

3.47 500 110 3900 120 4300 126 4500 128 4600 - -

5.21 750 165 5900 185 6600 180 6400 188 6700 185 6600

6.94 1000 240 8500 256 9100 250 8900 245 8700 245 8700

Cg = 9 K1= 120

FT 518 - 3/32 - PM518 HP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm /h


3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm3/h Scfh

1.04 150 45 1600 - - - - - - - -

1.39 200 66 2400 58 2100 - - - - - -

2.08 300 100 3600 99 3500 92 3300 - - - -

2.78 400 131 4700 131 4700 131 4700 113 4000 - -

3.47 500 163 5800 163 5800 163 5800 157 5600 - -

5.21 750 242 8600 242 8600 242 8600 242 8600 226 8000

6.94 1000 322 11400 322 11400 322 11400 322 11400 320 11300

Cg = 9 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

68
FT 518 - 1/8 - PM518 HP - DN 1” | 25 mm
Inlet pressure: from 1.04 MPa [150 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.76 MPa [110 psig] to 3.47 MPa [500 psig]

FT 518 - 1/8 - PM518 HP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

1.04 150 60 2200 - - - - - - - -

1.39 200 85 3100 90 3200 - - - - - -

2.08 300 110 3900 140 5000 140 5000 - - - -

2.78 400 153 5500 180 6400 185 6600 175 6200 - -

3.47 500 200 7100 220 7800 225 8000 228 8100 - -

5.21 750 300 10600 330 11700 340 12100 340 12100 330 11700

6.94 1000 450 15900 450 15900 450 15900 455 16100 430 15200

Cg = 16 K1= 120

FT 518 - 1/8 - PM518 HP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm /h


3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm3/h Scfh

1.04 150 80 2900 - - - - - - - -

1.39 200 118 4200 102 3700 - - - - - -

2.08 300 177 6300 176 6300 164 5800 - - - -

2.78 400 234 8300 234 8300 232 8200 200 7100 - -

3.47 500 290 10300 290 10300 290 10300 280 9900 - -

5.21 750 431 15300 431 15300 431 15300 431 15300 401 14200

6.94 1000 572 20200 572 20200 572 20200 572 20200 569 20100

Cg = 16 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

69
High - Medium Pressure Gas Regulator

FT 518 - 3/16 - PM518 HP - DN 1” | 25 mm


Inlet pressure: from 1.04 MPa [150 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.76 MPa [110 psig] to 3.47 MPa [500 psig]

FT 518 - 3/16 - PM518 HP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

1.04 150 137 4900 - - - - - - - -

1.39 200 190 6800 200 7100 - - - - - -

2.08 300 280 9900 310 11000 310 11000 - - - -

2.78 400 400 14200 405 14400 405 14400 380 13500 - -

3.47 500 460 16300 500 17700 490 17400 480 17000 - -

5.21 750 680 24100 750 26500 740 26200 740 26200 760 26900

6.94 1000 935 33100 970 34300 1010 35700 980 34700 980 34700

Cg = 34 K1= 120

FT 518 - 3/16 - PM518 HP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm /h


3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm3/h Scfh

1.04 150 169 6000 - - - - - - - -

1.39 200 251 8900 218 7700 - - - - - -

2.08 300 377 13400 374 13200 348 12400 - - - -

2.78 400 496 17600 496 17600 493 17500 425 15100 - -

3.47 500 616 21800 616 21800 616 21800 595 21000 - -

5.21 750 916 32400 916 32400 916 32400 916 32400 853 30200

6.94 1000 1215 42900 1215 42900 1215 42900 1215 42900 1209 42700

Cg = 34 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

70
FT 518 - 1/4 - PM518 HP - DN 1” | 25 mm
Inlet pressure: from 1.04 MPa [150 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.76 MPa [110 psig] to 3.47 MPa [500 psig]

FT 518 - 1/4 - PM518 HP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

1.04 150 195 6900 - - - - - - - -

1.39 200 295 10500 320 11300 - - - - - -

2.08 300 440 15600 500 17700 535 18900 - - - -

2.78 400 600 21200 650 23000 710 25100 670 23700 - -

3.47 500 720 25500 830 29400 910 32200 920 32500 - -

5.21 750 980 34700 1300 46000 1340 47400 1360 48100 1350 47700

6.94 1000 1700 60100 1560 55100 1800 63600 1760 62200 1780 62900

Cg = 58 K1= 120

FT 518 - 1/4 - PM518 HP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm /h


3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm3/h Scfh

1.04 150 289 10200 - - - - - - - -

1.39 200 428 15200 371 13200 - - - - - -

2.08 300 643 22700 638 22600 594 21000 - - - -

2.78 400 847 30000 847 30000 841 29800 725 25700 - -

3.47 500 1051 37200 1051 37200 1051 37200 1014 35900 - -

5.21 750 1562 55200 1562 55200 1562 55200 1562 55200 1454 51400

6.94 1000 2072 73200 2072 73200 2072 73200 2072 73200 2062 72900

Cg = 58 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

71
High - Medium Pressure Gas Regulator

FT 518 - 3/8 - PM518 HP - DN 1” | 25 mm


Inlet pressure: from 1.04 MPa [150 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.76 MPa [110 psig] to 3.47 MPa [500 psig]

FT 518 - 3/8 - PM518 HP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

1.04 150 330 11700 - - - - - - - -

1.39 200 500 17700 590 20900 - - - - - -

2.08 300 640 22600 815 28800 910 32200 - - - -

2.78 400 1080 38200 1030 36400 1290 45600 1200 42400 - -

3.47 500 1360 48100 1400 49500 1650 58300 1550 54800 - -

5.21 750 1775 62700 1950 68900 1860 65700 2300 81300 2100 74200

6.94 1000 2340 82700 2900 102400 3160 111600 3150 111300 3340 118000

Cg = 115 K1= 120

FT 518 - 3/8 - PM518 HP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm /h3


Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm3/h Scfh

1.04 150 572 20300 - - - - - - - -

1.39 200 849 30000 736 26100 - - - - - -

2.08 300 1274 45000 1264 44700 1178 41700 - - - -

2.78 400 1679 59300 1679 59300 1668 58900 1438 50800 - -

3.47 500 2084 73600 2084 73600 2084 73600 2011 71100 - -

5.21 750 3097 109400 3097 109400 3097 109400 3097 109400 2884 101900

6.94 1000 4109 145100 4109 145100 4109 145100 4109 145100 4088 144400

Cg = 115 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

72
FT 518 - 1/2 - PM518 HP - DN 1” | 25 mm
Inlet pressure: from 1.04 MPa [150 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.76 MPa [110 psig] to 3.47 MPa [500 psig]

FT 518 - 1/2 - PM518 HP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

1.04 150 450 15900 - - - - - - - -

1.39 200 700 24800 670 23700 - - - - - -

2.08 300 830 29400 930 32900 1050 37100 - - - -

2.78 400 1220 43100 1150 40700 1400 49500 1360 49434 - -

3.47 500 1440 50900 1510 53400 1780 62900 1880 81919 - -

5.21 750 - - - - - - 2560 88275 2300 81300

6.94 1000 - - - - - - 3450 98868 3500 123600

Cg = 58 K1= 120

FT 518 - 1/2 - PM518 HP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm /h 3


Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm3/h Scfh

1.04 150 896 31700 - - - - - - - -

1.39 200 1329 47000 1153 40800 - - - - - -

2.08 300 1994 70500 1979 69900 1845 65200 - - - -

2.78 400 2628 92900 2628 92900 2611 92200 2251 79500 - -

3.47 500 3262 115200 3262 115200 3262 115200 3148 111200 - -

5.21 750 - - - - - - 4847 171200 4513 159400

6.94 1000 - - - - - - 6432 227200 6399 226000

Cg = 58 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

73
High - Medium Pressure Gas Regulator

FT 518 - 3/32 STD - LP - DN 2” | 50 mm


Inlet pressure: from 0.69 MPa [100 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.06 MPa [10 psig] to 0.86 MPa [125 psig]

FT 518 - 3/32 STD - LP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

0.69 100 28 1000 28 1000 28 1000 28 1000 - -

1.04 150 38 1400 38 1400 38 1400 38 1400 34 1200

1.39 200 49 1800 49 1800 50 1800 50 1800 49 1800

2.08 300 76 2700 76 2700 80 2900 76 2700 72 2600

3.47 500 120 4300 120 4300 125 4400 115 4100 115 4100

5.21 750 190 6800 190 6800 190 6800 190 6800 185 6600

6.94 1000 270 9600 280 9900 280 9900 280 9900 270 9600

Cg = 9 K1= 120

FT 518 - 3/32 STD - LP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm /h


3
Scfh Stm /h
3
Scfh Stm /h
3
Scfh Stm /h
3
Scfh Stm3/h Scfh

0.69 100 36 1300 36 1300 36 1300 34 1300 - -

1.04 150 52 1900 52 1900 52 1900 52 1900 38 1400

1.39 200 68 2500 68 2500 68 2500 68 2500 64 2300

2.08 300 100 3600 100 3600 100 3600 100 3600 100 3600

3.47 500 163 5800 163 5800 163 5800 163 5800 163 5800

5.21 750 242 8600 242 8600 242 8600 242 8600 242 8600

6.94 1000 322 11400 322 11400 322 11400 322 11400 322 11400

Cg = 9 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

74
FT 518 - 1/8 STD - LP - DN 2” | 50 mm
Inlet pressure: from 0.69 MPa [100 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.06 MPa [10 psig] to 0.86 MPa [125 psig]

FT 518 - 1/8 STD - LP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

0.69 100 50 1800 42 1500 48 1700 47 1700 - -

1.04 150 69 2500 69 2500 70 2500 69 2500 60 2200

1.39 200 90 3200 90 3200 95 3400 90 3200 89 3200

2.08 300 130 4600 130 4600 135 4800 125 4500 125 4500

3.47 500 220 7800 220 7800 225 8000 215 7600 210 7500

5.21 750 350 12400 350 12400 340 12000 330 11700 320 11300

6.94 1000 460 16300 460 16300 460 16300 450 15900 440 15600

Cg = 16 K1= 120

FT 518 - 1/8 STD - LP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm /h


3
Scfh Stm /h
3
Scfh Stm /h
3
Scfh Stm /h
3
Scfh Stm3/h Scfh

0.69 100 65 2300 65 2300 65 2300 61 2200 - -

1.04 150 93 3300 93 3300 93 3300 93 3300 68 2400

1.39 200 121 4300 121 4300 121 4300 121 4300 114 4100

2.08 300 177 6300 177 6300 177 6300 177 6300 177 6300

3.47 500 290 10300 290 10300 290 10300 290 10300 290 10300

5.21 750 431 15300 431 15300 431 15300 431 15300 431 15300

6.94 1000 572 20200 572 20200 572 20200 572 20200 572 20200

Cg = 16 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

75
High - Medium Pressure Gas Regulator

FT 518 - 3/16 STD - LP - DN 2” | 50 mm


Inlet pressure: from 0.69 MPa [100 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.06 MPa [10 psig] to 0.86 MPa [125 psig]

FT 518 - 3/16 STD - LP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

0.69 100 120 4300 110 3900 108 3900 100 3600 - -

1.04 150 150 5300 150 5300 160 5700 150 5300 140 5000

1.39 200 200 7100 200 7100 210 7500 200 7100 200 7100

2.08 300 300 10600 280 9900 300 10600 290 10300 290 10300

3.47 500 450 15900 430 15200 510 18100 480 17000 480 17000

5.21 750 - - 750 26500 650 23000 700 24800 720 25500

6.94 1000 - - 950 33600 900 31800 1000 35400 1000 35400

Cg = 34 K1= 120

FT 518 - 3/16 STD - LP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm /h3


Scfh Stm /h
3
Scfh Stm /h
3
Scfh Stm /h
3
Scfh Stm3/h Scfh

0.69 100 137 4900 137 4900 137 4900 130 4600 - -

1.04 150 197 7000 197 7000 197 7000 197 7000 144 5100

1.39 200 257 9100 257 9100 257 9100 257 9100 243 8600

2.08 300 377 13400 377 13400 377 13400 377 13400 377 13400

3.47 500 616 21800 616 21800 616 21800 616 21800 616 21800

5.21 750 - - 916 32400 916 32400 916 32400 916 32400

6.94 1000 - - 1215 42900 1215 42900 1215 42900 1215 42900

Cg = 34 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

76
FT 518 - 1/4 STD - LP - DN 2” | 50 mm
Inlet pressure: from 0.69 MPa [100 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.06 MPa [10 psig] to 0.86 MPa [125 psig]

FT 518 - 1/4 STD - LP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

0.69 100 180 6400 190 6800 190 6800 185 6600 - -

1.04 150 270 9600 280 9900 290 10300 280 9900 240 8500

1.39 200 350 12400 350 12400 360 12800 360 12800 350 12400

2.08 300 550 19500 490 17400 500 17700 520 18400 550 19500

3.47 500 600 21200 850 30100 750 26500 850 30100 880 31100

5.21 750 - - 1100 38900 850 30100 1200 42400 1350 47700

6.94 1000 - - - - - - 1700 60100 1750 61800

Cg = 58 K1= 120

FT 518 - 1/4 STD - LP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm /h3


Scfh Stm /h3
Scfh Stm /h3
Scfh Stm /h
3
Scfh Stm3/h Scfh

0.69 100 234 8,300 234 8,300 234 8,300 221 7,900 - -

1.04 150 336 11,900 336 11,900 336 11,900 336 11,900 245 8,700

1.39 200 438 15,500 438 15,500 438 15,500 438 15,500 414 14,700

2.08 300 643 22,700 643 22,700 643 22,700 643 22,700 643 22,700

3.47 500 1,051 37,200 1,051 37,200 1,051 37,200 1,051 37,200 1,051 37,200

5.21 750 - - 1,562 55,200 1,562 55,200 1,562 55,200 1,562 55,200

6.94 1000 - - - - - - 2,072 73,200 2,072 73,200

Cg = 58 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

77
High - Medium Pressure Gas Regulator

FT 518 - 3/8 STD - LP - DN 2” | 50 mm


Inlet pressure: from 0.69 MPa [100 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.06 MPa [10 psig] to 0.86 MPa [125 psig]

FT 518 - 3/8 STD - LP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

0.69 100 250 8900 500 17700 450 15900 400 14200 - -

1.04 150 630 22300 550 19500 650 23000 600 21200 440 15600

1.39 200 820 29000 750 26500 820 29000 780 27600 800 28300

2.08 300 - - 1100 38900 1200 42400 1100 38900 1150 40700

3.47 500 - - - - - - 1700 60100 2000 70700

5.21 750 - - - - - - 2000 70700 3050 107700

6.94 1000 - - - - - - 2500 88300 4000 141300

Cg = 115 K1= 120

FT 518 - 3/8 STD - LP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm /h 3


Scfh Stm /h3
Scfh Stm /h3
Scfh Stm /h
3
Scfh Stm3/h Scfh

0.69 100 464 16400 464 16400 464 16400 439 15500 - -

1.04 150 667 23600 667 23600 667 23600 667 23600 486 17200

1.39 200 869 30700 869 30700 869 30700 869 30700 821 29100

2.08 300 - - 1274 45000 1274 45000 1274 45000 1274 45000

3.47 500 - - - - - - 2084 73600 2084 73600

5.21 750 - - - - - - 3097 109400 3097 109400

6.94 1000 - - - - - - 4109 145100 4109 145100

Cg = 115 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

78
FT 518 - 1/2 STD - LP - DN 2” | 50 mm
Inlet pressure: from 0.69 MPa [100 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.06 MPa [10 psig] to 0.86 MPa [125 psig]

FT 518 - 1/2 STD - LP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

0.69 100 440 15600 650 23000 600 21200 590 20900 - -

1.04 150 700 24800 750 26500 800 28300 850 30100 620 21900

1.39 200 - - 1100 38900 1100 38900 1100 38900 880 31100

2.08 300 - - 1550 54800 1500 53000 1500 53000 1500 53000

3.47 500 - - - - - - 2100 74200 3500 123600

5.21 750 - - - - - - 3400 120100 4200 148400

6.94 1000 - - - - - - - - 5100 180100

Cg = 180 K1= 120

FT 518 - 1/2 STD - LP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm /h 3


Scfh Stm /h3
Scfh Stm /h3
Scfh Stm /h3
Scfh Stm3/h Scfh

0.69 100 726 25700 726 25700 726 25700 686 24300 - -

1.04 150 1043 36900 1043 36900 1043 36900 1043 36900 760 26900

1.39 200 - - 1360 48100 1360 48100 1360 48100 1286 45500

2.08 300 - - 1994 70500 1994 70500 1994 70500 1994 70500

3.47 500 - - - - - - 3262 115200 3262 115200

5.21 750 - - - - - - 4847 171200 4847 171200

6.94 1000 - - - - - - - - 6432 227200

Cg = 180 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

79
High - Medium Pressure Gas Regulator

FT 518 - 3/32 STD - HP - DN 2” | 50 mm


Inlet pressure: from 1.04 MPa [150 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.76 MPa [110 psig] to 3.47 MPa [500 psig]

FT 518 - 3/32 STD - HP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

1.04 150 36 1300 - - - - - - - -

1.39 200 48 1700 48 1700 - - - - - -

2.08 300 70 2500 75 2700 75 2700 - - - -

2.78 400 105 3800 100 3600 100 3600 100 3600 - -

3.47 500 110 3900 120 4300 126 4500 128 4600 - -

5.21 750 165 5900 185 6600 180 6400 188 6700 185 6600

6.94 1000 212 7500 256 9100 250 8900 245 8700 245 8700

Cg = 9 K1= 120

FT 518 - 3/32 STD - HP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm /h


3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm3/h Scfh

1.04 150 45 1600 - - - - - - - -

1.39 200 66 2400 58 2100 - - - - - -

2.08 300 100 3600 99 3500 92 3300 - - - -

2.78 400 131 4700 131 4700 131 4700 113 4000 - -

3.47 500 163 5800 163 5800 163 5800 157 5600 - -

5.21 750 242 8600 242 8600 242 8600 242 8600 226 8000

6.94 1000 322 11400 322 11400 322 11400 322 11400 320 11300

Cg = 9 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

80
FT 518 - 1/8 STD - HP - DN 2” | 50 mm
Inlet pressure: from 1.04 MPa [150 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.76 MPa [110 psig] to 3.47 MPa [500 psig]

FT 518 - 1/8 STD - HP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

1.04 150 60 2200 - - - - - - - -

1.39 200 85 3100 90 3200 - - - - - -

2.08 300 110 3900 140 5000 140 5000 - - - -

2.78 400 153 5500 180 6400 185 6600 175 6200 - -

3.47 500 200 7100 220 7800 225 8000 228 8100 - -

5.21 750 300 10600 330 11700 340 12100 340 12100 330 11700

6.94 1000 450 15900 450 15900 450 15900 455 16100 430 15200

Cg = 16 K1= 120

FT 518 - 1/8 STD - HP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm /h


3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm3/h Scfh

1.04 150 80 2900 - - - - - - - -

1.39 200 118 4200 102 3700 - - - - - -

2.08 300 177 6300 176 6300 164 5800 - - - -

2.78 400 234 8300 234 8300 232 8200 200 7100 - -

3.47 500 290 10300 290 10300 290 10300 280 9900 - -

5.21 750 431 15300 431 15300 431 15300 431 15300 401 14200

6.94 1000 572 20200 572 20200 572 20200 572 20200 569 20100

Cg = 16 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

81
High - Medium Pressure Gas Regulator

FT 518 - 3/16 STD - HP - DN 2” | 50 mm


Inlet pressure: from 1.04 MPa [150 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.76 MPa [110 psig] to 3.47 MPa [500 psig]

FT 518 - 3/16 STD - HP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

1.04 150 137 4900 - - - - - - - -

1.39 200 190 6800 200 7100 - - - - - -

2.08 300 280 9900 310 11000 310 11000 - - - -

2.78 400 400 14200 405 14400 405 14400 380 13500 - -

3.47 500 460 16300 500 17700 490 17400 480 17000 - -

5.21 750 680 24100 750 26500 740 26200 740 26200 760 26900

6.94 1000 935 33100 970 34300 1010 35700 980 34700 980 34700

Cg = 34 K1= 120

FT 518 - 3/16 STD - HP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm /h


3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm3/h Scfh

1.04 150 169 6000 - - - - - - - -

1.39 200 251 8900 218 7700 - - - - - -

2.08 300 377 13400 374 13200 348 12400 - - - -

2.78 400 496 17600 496 17600 493 17500 425 15100 - -

3.47 500 616 21800 616 21800 616 21800 595 21000 - -

5.21 750 916 32400 916 32400 916 32400 916 32400 853 30200

6.94 1000 1215 42900 1215 42900 1215 42900 1215 42900 1209 42700

Cg = 34 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

82
FT 518 - 1/4 STD - HP - DN 2” | 50 mm
Inlet pressure: from 1.04 MPa [150 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.76 MPa [110 psig] to 3.47 MPa [500 psig]

FT 518 - 1/4 STD - HP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

1.04 150 220 7800 - - - - - - - -

1.39 200 320 11300 340 12100 - - - - - -

2.08 300 460 16300 530 18800 540 19100 - - - -

2.78 400 620 21900 700 24800 715 25300 670 23700 - -

3.47 500 800 28300 860 30400 920 32500 920 32500 - -

5.21 750 1000 35400 1350 47700 1360 48100 1360 48100 1370 48400

6.94 1000 1700 60100 1650 58300 1820 64300 1760 62200 1800 63600

Cg = 58 K1= 120

FT 518 - 1/4 STD - HP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm /h


3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm3/h Scfh

1.04 150 289 10200 - - - - - - - -

1.39 200 428 15200 371 13200 - - - - - -

2.08 300 643 22700 638 22600 594 21000 - - - -

2.78 400 847 30000 847 30000 841 29800 725 25700 - -

3.47 500 1051 37200 1051 37200 1051 37200 1014 35900 - -

5.21 750 1562 55200 1562 55200 1562 55200 1562 55200 1454 51400

6.94 1000 2072 73200 2072 73200 2072 73200 2072 73200 2062 72900

Cg = 58 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

83
High - Medium Pressure Gas Regulator

FT 518 - 3/8 STD - HP - DN 2” | 50 mm


Inlet pressure: from 1.04 MPa [150 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.76 MPa [110 psig] to 3.47 MPa [500 psig]

FT 518 - 3/8 STD - HP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

1.04 150 390 13800 - - - - - - - -

1.39 200 550 19500 630 22300 - - - - - -

2.08 300 700 24800 840 29700 1000 35400 - - - -

2.78 400 1110 39200 1100 38900 1400 49500 1200 42400 - -

3.47 500 1500 53000 1450 51200 1760 62200 1550 54800 - -

5.21 750 2100 74200 2000 70700 1900 67100 2300 81300 2450 86600

6.94 1000 3200 113000 3000 106000 3200 113000 3600 127200 3650 128900

Cg = 115 K1= 120

FT 518 - 3/8 STD - HP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm /h3


Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm3/h Scfh

1.04 150 572 20300 - - - - - - - -

1.39 200 849 30000 736 26100 - - - - - -

2.08 300 1274 45000 1264 44700 1178 41700 - - - -

2.78 400 1679 59300 1679 59300 1668 58900 1438 50800 - -

3.47 500 2084 73600 2084 73600 2084 73600 2011 71100 - -

5.21 750 3097 109400 3097 109400 3097 109400 3097 109400 2884 101900

6.94 1000 4109 145100 4109 145100 4109 145100 4109 145100 4088 144400

Cg = 115 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

84
FT 518 - 1/2 STD - HP - DN 2” | 50 mm
Inlet pressure: from 1.04 MPa [150 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.76 MPa [110 psig] to 3.47 MPa [500 psig]

FT 518 - 1/2 STD - HP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

1.04 150 550 19500 - - - - - - - -

1.39 200 750 26500 900 31800 - - - - - -

2.08 300 1230 43500 1400 49500 1450 51200 - - - -

2.78 400 1500 53000 1800 63600 1900 67100 1550 49434 - -

3.47 500 2000 70700 2500 88300 2500 88300 2400 81919 - -

5.21 750 - - - - - - 3000 88275 4000 141300

6.94 1000 - - - - - - 4500 98868 4600 162500

Cg = 180 K1= 120

FT 518 - 1/2 STD - HP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm /h 3


Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm3/h Scfh

1.04 150 896 31700 - - - - - - - -

1.39 200 1329 47000 1153 40800 - - - - - -

2.08 300 1994 70500 1979 69900 1845 65200 - - - -

2.78 400 2628 92900 2628 92900 2611 92200 2251 79500 - -

3.47 500 3262 115200 3262 115200 3262 115200 3148 111200 - -

5.21 750 - - - - - - 4847 171200 4513 159400

6.94 1000 - - - - - - 6432 227200 6399 226000

Cg = 180 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

85
High - Medium Pressure Gas Regulator

FT 518 - 3/32 - PM518 LP - DN 2” | 50 mm


Inlet pressure: from 0.69 MPa [100 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.06 MPa [10 psig] to 0.86 MPa [125 psig]

FT 518 - 3/32 STD - PM518 LP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

0.69 100 27 1000 27 1000 28 1000 28 1000 - -

1.04 150 36 1300 37 1400 36 1300 37 1400 34 1200

1.39 200 46 1700 47 1700 45 1600 48 1700 48 1700

2.08 300 72 2600 74 2700 70 2500 70 2500 70 2500

3.47 500 - - 110 3900 116 4100 110 3900 110 3900

5.21 750 - - 175 6200 175 6200 180 6400 170 6100

6.94 1000 - - - - - - 250 8900 250 8900

Cg = 9 K1= 120

FT 518 - 3/32 - PM518 LP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm /h3


Scfh Stm /h3
Scfh Stm /h3
Scfh Stm /h
3
Scfh Stm3/h Scfh

0.69 100 36 1300 36 1300 36 1300 28 1000 - -

1.04 150 52 1900 52 1900 52 1900 52 1900 34 1200

1.39 200 68 2500 68 2500 68 2500 68 2500 48 1700

2.08 300 100 3600 100 3600 100 3600 100 3600 100 3600

3.47 500 - - 163 5800 163 5800 163 5800 163 5800

5.21 750 - - 242 8600 242 8600 242 8600 242 8600

6.94 1000 - - - - - - 322 11400 322 11400

Cg = 9 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

86
FT 518 - 1/8 - PM518 LP - DN 2” | 50 mm
Inlet pressure: from 0.69 MPa [100 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.06 MPa [10 psig] to 0.86 MPa [125 psig]

FT 518 - 1/8 STD - PM518 LP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

0.69 100 48 1700 42 1500 45 1600 47 1700 - -

1.04 150 66 2400 65 2300 67 2400 68 2500 60 2200

1.39 200 85 3100 85 3100 89 3200 88 3200 86 3100

2.08 300 120 4300 120 4300 130 4600 125 4500 120 4300

3.47 500 - - 200 7100 218 7700 215 7600 200 7100

5.21 750 - - 330 11700 320 11300 320 11300 290 10300

6.94 1000 - - - - - - 390 13800 410 14500

Cg = 16 K1= 120

FT 518 - 1/8 - PM518 LP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm /h3


Scfh Stm /h3
Scfh Stm /h3
Scfh Stm /h
3
Scfh Stm3/h Scfh

0.69 100 65 2300 65 2300 65 2300 47 1700 - -

1.04 150 93 3300 93 3300 93 3300 93 3300 60 2200

1.39 200 121 4300 121 4300 121 4300 121 4300 86 3100

2.08 300 177 6300 177 6300 177 6300 177 6300 177 6300

3.47 500 - - 290 10300 290 10300 290 10300 290 10300

5.21 750 - - 431 15300 431 15300 431 15300 431 15300

6.94 1000 - - - - - - 572 20200 572 20200

Cg = 16 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

87
High - Medium Pressure Gas Regulator

FT 518 - 3/16 - PM518 LP - DN 2” | 50 mm


Inlet pressure: from 0.69 MPa [100 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.06 MPa [10 psig] to 0.86 MPa [125 psig]

FT 518 - 3/16 STD - PM518 LP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

0.69 100 100 3600 100 3600 105 3800 90 3200 - -

1.04 150 130 4600 145 5200 155 5500 145 5200 130 4600

1.39 200 180 6400 190 6800 210 7500 190 6800 190 6800

2.08 300 260 9200 267 9500 280 9900 260 9200 275 9800

3.47 500 - - 400 14200 470 16600 470 16600 470 16600

5.21 750 - - 650 23000 580 20500 650 23000 680 24100

6.94 1000 - - - - - - 870 30800 920 32500

Cg = 34 K1= 120

FT 518 - 3/16 - PM518 LP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm /h3


Scfh Stm /h3
Scfh Stm /h3
Scfh Stm /h
3
Scfh Stm3/h Scfh

0.69 100 137 4900 137 4900 137 4900 90 3200 - -

1.04 150 197 7000 197 7000 197 7000 197 7000 130 4600

1.39 200 257 9100 257 9100 257 9100 257 9100 190 6800

2.08 300 377 13400 377 13400 377 13400 377 13400 377 13400

3.47 500 - - 616 21800 616 21800 616 21800 616 21800

5.21 750 - - 916 32400 916 32400 916 32400 916 32400

6.94 1000 - - - - - - 1215 42900 1215 42900

Cg = 34 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

88
FT 518 - 1/4 - PM518 LP - DN 2” | 50 mm
Inlet pressure: from 0.69 MPa [100 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.06 MPa [10 psig] to 0.86 MPa [125 psig]

FT 518 - 1/4 STD - PM518 LP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

0.69 100 160 5700 180 6400 180 6400 180 6400 - -

1.04 150 250 8900 260 9200 280 9900 270 9600 220 7800

1.39 200 330 11700 320 11300 345 12200 350 12400 330 11700

2.08 300 450 15900 450 15900 470 16600 495 17500 490 17400

3.47 500 490 17400 770 27200 700 24800 790 27900 800 28300

5.21 750 - - 950 33600 790 27900 1000 35400 1200 42400

6.94 1000 - - - - - - 1450 51200 1550 54800

Cg = 16 K1= 120

FT 518 - 1/4 - PM518 LP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm /h3


Scfh Stm /h3
Scfh Stm /h3
Scfh Stm /h
3
Scfh Stm3/h Scfh

0.69 100 234 8300 234 8300 234 8300 180 6400 - -

1.04 150 336 11900 336 11900 336 11900 336 11900 220 7800

1.39 200 438 15500 438 15500 438 15500 438 15500 330 11700

2.08 300 643 22700 643 22700 643 22700 643 22700 643 22700

3.47 500 - - 1051 37200 1051 37200 1051 37200 1051 37200

5.21 750 - - 1365 48300 1562 55200 1562 55200 1562 55200

6.94 1000 - - - - - - 2072 73200 2072 73200

Cg = 58 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

89
High - Medium Pressure Gas Regulator

FT 518 - 3/8 - PM518 LP - DN 2” | 50 mm


Inlet pressure: from 0.69 MPa [100 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.06 MPa [10 psig] to 0.86 MPa [125 psig]

FT 518 - 3/8 STD - PM518 LP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

0.69 100 220 7800 350 12400 400 14200 340 12100 - -

1.04 150 390 13800 400 14200 580 20500 500 17700 410 14500

1.39 200 400 14200 650 23000 750 26500 650 23000 730 25800

2.08 300 - - 1000 35400 1050 37100 1150 40700 1080 38200

3.47 500 - - - - - - 1500 53000 1850 65400

5.21 750 - - - - - - 1800 63600 2600 91900

6.94 1000 - - - - - - 2100 74200 3300 116600

Cg = 115 K1= 120

FT 518 - 3/8 - PM518 LP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm /h 3


Scfh Stm /h3
Scfh Stm /h3
Scfh Stm /h
3
Scfh Stm3/h Scfh

0.69 100 464 16400 464 16400 464 16400 340 12100 - -

1.04 150 667 23600 667 23600 667 23600 667 23600 410 14500

1.39 200 869 30700 869 30700 869 30700 869 30700 730 25800

2.08 300 - - 1274 45000 1274 45000 1274 45000 1274 45000

3.47 500 - - 1365 48300 1764 62400 2084 73600 2084 73600

5.21 750 - - - - 1764 62400 2969 104900 3097 109400

6.94 1000 - - - - - - 2969 104900 4109 145100

Cg = 115 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

90
FT 518 - 1/2 - PM518 LP - DN 2” | 50 mm
Inlet pressure: from 0.69 MPa [100 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.06 MPa [10 psig] to 0.86 MPa [125 psig]

FT 518 - 1/2 STD - PM518 LP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

0.69 100 360 12800 400 14200 450 15900 380 13500 - -

1.04 150 400 14200 450 15900 550 19500 580 20500 630 22300

1.39 200 - - 700 24800 1000 35400 750 26500 860 30400

2.08 300 - - 1100 38900 1300 46000 1280 45200 1390 49100

3.47 500 - - - - - - 1550 54800 1950 68900

5.21 750 - - - - - - 1900 67100 2700 95400

6.94 1000 - - - - - - - - 3500 123600

Cg = 180 K1= 120

FT 518 - 1/2 - PM518 LP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.06 Mpa / 10 psig 0.13 Mpa / 20 psig 0.2 Mpa / 30 psig 0.41 Mpa / 60 psig 0.86 Mpa / 125 psig

MPa psig Stm /h3


Scfh Stm /h3
Scfh Stm /h3
Scfh Stm /h3
Scfh Stm3/h Scfh

0.69 100 726 25700 726 25700 726 25700 380 13500 - -

1.04 150 967 34200 1043 36900 1043 36900 1043 36900 630 22300

1.39 200 - - 1360 48100 1360 48100 1360 48100 860 30400

2.08 300 - - 1365 48300 1764 62400 1994 70500 1994 70500

3.47 500 - - - - 1764 62400 2969 104900 3262 115200

5.21 750 - - - - - - 2969 104900 4847 171200

6.94 1000 - - - - - - - - 5614 198300

Cg = 180 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

91
High - Medium Pressure Gas Regulator

FT 518 - 3/32 - PM518 HP - DN 2” | 50 mm


Inlet pressure: from 1.04 MPa [150 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.76 MPa [110 psig] to 3.47 MPa [500 psig]

FT 518 - 3/32 - PM518 HP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

1.04 150 39 1400 - - - - - - - -

1.39 200 48 1700 48 1700 - - - - - -

2.08 300 70 2500 75 2700 75 2700 - - - -

2.78 400 105 3800 100 3600 100 3600 100 3600 - -

3.47 500 110 3900 120 4300 126 4500 128 4600 - -

5.21 750 165 5900 185 6600 180 6400 188 6700 185 6600

6.94 1000 240 8500 256 9100 250 8900 245 8700 245 8700

Cg = 9 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

92
FT 518 - 1/8 - PM518 HP - DN 2” | 50 mm
Inlet pressure: from 1.04 MPa [150 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.76 MPa [110 psig] to 3.47 MPa [500 psig]

FT 518 - 1/8 - PM518 HP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

1.04 150 60 2200 - - - - - - - -

1.39 200 85 3100 90 3200 - - - - - -

2.08 300 110 3900 140 5000 140 5000 - - - -

2.78 400 153 5500 180 6400 185 6600 175 6200 - -

3.47 500 200 7100 220 7800 225 8000 228 8100 - -

5.21 750 300 10600 330 11700 340 12100 340 12100 330 11700

6.94 1000 450 15900 450 15900 450 15900 455 16100 430 15200

Cg = 16 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

93
High - Medium Pressure Gas Regulator

FT 518 - 3/16 - PM518 HP - DN 2” | 50 mm


Inlet pressure: from 1.04 MPa [150 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.76 MPa [110 psig] to 3.47 MPa [500 psig]

FT 518 - 3/16 - PM518 HP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

1.04 150 137 4900 - - - - - - - -

1.39 200 190 6800 200 7100 - - - - - -

2.08 300 280 9900 310 11000 310 11000 - - - -

2.78 400 400 14200 405 14400 405 14400 380 13500 - -

3.47 500 460 16300 500 17700 490 17400 480 17000 - -

5.21 750 680 24100 750 26500 740 26200 740 26200 760 26900

6.94 1000 935 33100 970 34300 1010 35700 980 34700 980 34700

Cg = 34 K1= 120

FT 518 - 3/16 - PM518 HP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm /h


3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm3/h Scfh

1.04 150 169 6000 - - - - - - - -

1.39 200 251 8900 218 7700 - - - - - -

2.08 300 377 13400 374 13200 348 12400 - - - -

2.78 400 496 17600 496 17600 493 17500 425 15100 - -

3.47 500 616 21800 616 21800 616 21800 595 21000 - -

5.21 750 916 32400 916 32400 916 32400 916 32400 853 30200

6.94 1000 1215 42900 1215 42900 1215 42900 1215 42900 1209 42700

Cg = 34 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

94
FT 518 - 1/4 - PM518 HP - DN 2” | 50 mm
Inlet pressure: from 1.04 MPa [150 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.76 MPa [110 psig] to 3.47 MPa [500 psig]

FT 518 - 1/4 - PM518 HP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

1.04 150 195 6900 - - - - - - - -

1.39 200 295 10500 320 11300 - - - - - -

2.08 300 440 15600 500 17700 535 18900 - - - -

2.78 400 600 21200 650 23000 710 25100 670 23700 - -

3.47 500 760 26900 830 29400 910 32200 920 32500 - -

5.21 750 980 34700 1300 46000 1340 47400 1360 48100 1350 47700

6.94 1000 1700 60100 1560 55100 1800 63600 1760 62200 1780 62900

Cg = 58 K1= 120

FT 518 - 1/4 - PM518 HP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm /h


3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm3/h Scfh

1.04 150 289 10200 - - - - - - - -

1.39 200 428 15200 371 13200 - - - - - -

2.08 300 643 22700 638 22600 594 21000 - - - -

2.78 400 847 30000 847 30000 841 29800 725 25700 - -

3.47 500 1051 37200 1051 37200 1051 37200 1014 35900 - -

5.21 750 1562 55200 1562 55200 1562 55200 1562 55200 1454 51400

6.94 1000 2072 73200 2072 73200 2072 73200 2072 73200 2062 72900

Cg = 58 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

95
High - Medium Pressure Gas Regulator

FT 518 - 3/8 - PM518 HP - DN 2” | 50 mm


Inlet pressure: from 1.04 MPa [150 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.76 MPa [110 psig] to 3.47 MPa [500 psig]

FT 518 - 3/8 - PM518 HP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

1.04 150 330 11700 - - - - - - - -

1.39 200 500 17700 590 20900 - - - - - -

2.08 300 640 22600 815 28800 910 32200 - - - -

2.78 400 1080 38200 1030 36400 1290 45600 1200 42400 - -

3.47 500 1410 49800 1400 49500 1650 58300 1550 54800 - -

5.21 750 1980 70000 1950 68900 1860 65700 2300 81300 2100 74200

6.94 1000 3000 106000 2900 102400 3160 111600 3150 111300 3340 118000

Cg = 115 K1= 120

FT 518 - 3/8 - PM518 HP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm /h3


Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm3/h Scfh

1.04 150 572 20300 - - - - - - - -

1.39 200 849 30000 736 26100 - - - - - -

2.08 300 1274 45000 1264 44700 1178 41700 - - - -

2.78 400 1679 59300 1679 59300 1668 58900 1438 50800 - -

3.47 500 2084 73600 2084 73600 2084 73600 2011 71100 - -

5.21 750 3097 109400 3097 109400 3097 109400 3097 109400 2884 101900

6.94 1000 4109 145100 4109 145100 4109 145100 4109 145100 4088 144400

Cg = 115 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

96
FT 518 - 1/2 - PM518 HP - DN 2” | 50 mm
Inlet pressure: from 1.04 MPa [150 psig] to 6.94 MPa [1000 psig]
Outlet pressure: from 0.76 MPa [110 psig] to 3.47 MPa [500 psig]

FT 518 - 1/2 - PM518 HP recommended max flow rate for optimal performance
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh Stm3/h Scfh

1.04 150 450 15900 - - - - - - - -

1.39 200 700 24800 670 23700 - - - - - -

2.08 300 890 31500 1320 46700 1050 37100 - - - -

2.78 400 1400 49500 1700 60100 1400 49500 1360 49434 - -

3.47 500 1930 68200 2400 84800 1780 62900 1880 81919 - -

5.21 750 - - - - - - 2560 88275 2300 81300

6.94 1000 - - - - - - 3450 98868 3500 123600

Cg = 180 K1= 120

FT 518 - 1/2 - PM518 HP flow rate with wide open regulator (100% capacity)
Outlet pressure
Inlet pressure
0.75 Mpa / 110 psig 1.03 Mpa / 150 psig 1.37 Mpa / 200 psig 2.06 Mpa / 300 psig 3.44 Mpa / 500 psig

MPa psig Stm /h3


Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm /h 3
Scfh Stm3/h Scfh

1.04 150 896 31700 - - - - - - - -

1.39 200 1329 47000 1153 40800 - - - - - -

2.08 300 1994 70500 1979 69900 1845 65200 - - - -

2.78 400 2628 92900 2628 92900 2611 92200 2251 79500 - -

3.47 500 3262 115200 3262 115200 3262 115200 3148 111200 - -

5.21 750 - - - - - - 4847 171200 4513 159400

6.94 1000 - - - - - - 6432 227200 6399 226000

Cg = 180 K1= 120

Note: Recommended max flow rate are considering multiple factors such as: extend the regulator’s life, mitigate the
erosion/vibrations for high velocity and to minimize the noise emission.
Remark: all capacity stated are considering a stand alone regulator. In case of incorporated accessories a reduction of
flow shall be considered.

97
High - Medium Pressure Gas Regulator

Customer Centricity
Customer centricity is a way of running your business — implementing a perfect customer experience
at each stage of the pipeline. Pietro Fiorentini is one of the main Italian international company with
high focus on product and service quality.

The main strategy is to create a stable, long-term relationship, putting the customer’s needs first.
Lean management and customer centricity are used to improve and maintain the highest level of
customer experience.

Support
Pietro Fiorentini’s top priority is to provide support to the client in all phases of project
development, during installation, start up and operation. Pietro Fiorentini has developed a
highly standardized Intervention-Management-System (IMS), which helps to facilitate the
entire process and putting the customer at the forefront of every decision in our process
while manufacturing or developing a product to help improve the product and service.
With our IMS business model many services are available remotely, avoiding long waiting
times, improving service, and avoiding unnecessary expenses.

Training
Pietro Fiorentini offers training services available for both experienced operators and new
customers. The training is offered for all levels of our customers which can include one or
all of the following: sizing of equipment, application, installation, operation, maintenance
and is prepared according to the level of use and the customer’s need.

Customer Relation Management (CRM)


The service and care of our customers are one of the main missions and vision of Pietro
Fiorentini. For this reason, Pietro Fiorentini has enhanced the customer relation management
system. This enables us to track every opportunity and request from our customers into
one single information point and allows us to coordinate information allowing us to give
the customer improved service.

98
Sustainability
Here at Pietro Fiorentini, we believe in a world capable of improvement through technology and
solutions that can shape a more sustainable future. That is why respect for people, society and the
environment form the cornerstones of our strategy.

Our commitment
to the world of tomorrow
While in the past we limited ourselves to providing products, systems and services for the oil & gas
sector, today we want to broaden our horizons and create technologies and solutions for a digital and
sustainable world. We have a particular focus on renewable energy projects to help make the most
of our planet’s resources and create a future in which the younger generations can grow and prosper.

The time has come to understand how and why we operate now.

99
TB0051USA

The data is not binding. We reserve the right


to make changes without prior notice.