STRUCTURES − MANHOLES SPEC 10

Straight − Precast Sheet 1 of 2


6’−0” x 14’−0” x 7’−0”

TOP VIEW
15’−0”
14’−0”
4’−0” 6’−0” 4’−0” 36” x 20” x 4” THIN
WALL KNOCKOUT
8 PLACES AS SHOWN
1” THREADED INSERTS

1’−6” 2’−1”
7’−0” 6’−0”
4’−7”

5’−0 1/4”
4”
36” CLEAR OPENING
12” SUMP HOLE INSERT

END VIEWS
(12) 5” DIA. (12) 5” DIA.
18” TERMINATORS 8” TERMINATORS

12”
10 1/2”
48 1/2” 9”
*118” 40 1/2”
9”
6”
100” 6 1/2” 84” CLEAR HEAD ROOM
9”
51 1/2” 43 1/2” 9”
13”

1” HOLE 8” 1” HOLE
3” ABOVE FLOOR 8” 3” ABOVE FLOOR
SIDE VIEW
* SETTING DEPTH FINAL GRADE
FRAME & COVER
18” 2 − 3” COLLARS
1 − 6” COLLAR

18” 36”

20”

8”
20”
18” CRUSHED ROCK or
FLOWABLE FILL

8”
6” MIN.

COLLAR CONFIGURATION * SETTING DEPTHS WEIGHTS


PREFERED − 1−6” & 2−3” COORDINATE W/AMEREN REP. TOP SECTION 19,798 lbs.
3” NECKS ARE REQUIRED ON ALL MANHOLES PREFERRED − 18” (AS SHOWN) BASE SECTION 20,526 lbs.
AND SHALL BE TOP COLLARS MINIMUM − 12” TO FINAL GRADE TOTAL 40,324 lbs.
MAXIMUM − 60” TO FINAL GRADE TRAFFIC RATED DESIGN
(DERIVED FROM CONSTRUCTION STANDARD 32 21 03 **)

UNDERGROUND DISTR. ENG:JLH


CONCRETE ENCASED SPEC. REV. NO: 7