Fire Product Catalogue 2008
Fire Product Catalogue 2008
Fire Product Catalogue 2008
Contents
Conventional
1-7 FX2200CF Range
Conventional panels Conventional detectors Ancillary devices
Analogue
13 CF3000 Range
Analogue panels
14
CF2000 Range
Analogue panels
8-12
FX2200BWCF Range
Bi wire panels Bi wire detectors Bi wire ancillary devices
15
CF1000 Range
Analogue panels
16
CF3000PRG
Analogue repeater panel
17-19 20
21-26
Ancillaries
Callpoints Sounders Audio visual units Beacons Interfaces PCBs
FX2200CF Range
Conventional panels
The FX2200CF range of conventional panels provide a simple yet effective installer and end user conventional fire detection system solution. Available as 2, 4 and 8-zone panels, with the 8-zone panel being configured for the provision of a repeater panel output as well as two additional alarm line outputs.
Features
> BOSEC 3rd party approved to EN54 pts. 2 and 4 > Choice of 2, 4 and 8-zone panels > Single 12 V DC battery requirement for 24-hour standby > Single keypad access code for end user and engineer use > Selectable fire/fault relay > Class change facility > Supports up to 32 detectors on each zone > Same style repeater panel available for 8-zone panel > Simple one shot end user test facility > Maintenance free poly switch circuit protection
Technical Specifications
Model Standards Number of zones Detectors per zone Number of alarm circuits Alarm circuit load End of line devices Auxiliary fire signal / fault output Auxiliary DC output Repeater port Mains input voltage System operating voltage Standby duration Battery (sealed lead acid) Recharge period Panel construction Cable entries Environmental rating Surface dimensions WxHxD (mm) FX2202CF FX2204CF FX2208CF EN54-2: 1998 & EN54-4: 1998 EN50130-4: 1996 EN500081-1: 1992 & EN61000-2-2: 1994 2 4 8 32 2 4 150mA per circuit 0.3A total 400mA per circuit 0.8A total 500mA per circuit 2A total Detection circuits: EOLM1 monitoring unit. Alarm lines: 6.8K resistor 5A 24V DC single pole changeover contacts 24V DC fused. 30mA No Yes 230V AC 10% +15% 24V DC 24 hours 1 x 3.2 AH 2 x 3.2 AH 24 hours Polycarbonate housing & back box Top: 12 x 20mm entries with blanking plugs Rear cable entry aperture IP30. -5C to +40C humidity 75% max (non condensing) 332 x 270 x 90mm
Product Codes
FX2202CF FX2204CF FX2208CF FXRP2200CF 2-Zone panel 4-Zone panel 8-Zone panel Repeater panel
FX2200CF Range
Conventional detectors
A comprehensive range of conventional detectors are available for the FX2200CF range of fire detection panels.
Features
> LPCB 3rd party approved > Low profile design > 360 viewable LED design > Removable detector chamber for cleaning > Common mounting base
CMT360
CPD321*
CPT341**
CFR330
CHT390
CDBB300
CIR301
Technical Specifications
Model Description Standards CPD321* Photoelectric Smoke Detector EN54 pt7:2000 and BSEN54 pt7:2001 CPT341** CFR330 Heat Detector (Fast Response) CMT360 Heat Detector (Medium Response) EN54 pt7:2000 and BSEN54 pt5:2001 CHT390 Heat Detector (High Temperature) Photo Thermal Smoke Detector EN54 pt7:2000, BSEN54 pt7:2002 and BSEN54 pt 5:2001 100m2 (subject to local standard)
Area coverage System wiring Indication Mounting Compatibility Detection mode Operating voltage Max stand-by current Max start up current Max alarm current Alarm temperature Heat class Environmental Application Temperature Humidity EMC Construction Material Colour Dimensions Excluding base Including base
50m2 (subject to local standard) 2 core 360 visibility pipe Surface mount using CDBB300 FX2200CF range of panels Light scatter principle Light scatter principle & Heat sensitive element heat sensitive element 15V to 30V DC 30 A 220 A 30 A 210 A 340 A NA 25 mA 20 mA 25 mA NA 60C 77C NA A2S A1R BS Indoor use IP40 -20C to 60C 0 - 95% non condensing CE marked PC/ABS White 100mm(Dia) x 43mm(H) 101mm(Dia) x 55mm(H)
92C CS
100mm(Dia) x 45mm(H)
Product Codes
CPD321* CFR330 CHT390 CIR301 Photoelectric smoke detector Heat detector fast response (A1R) Heat detector high temperature (CS) Remote indicator CPT341** CMT360 CDBB300 Photo thermal dual detector Heat detector medium response (BS) Common base
FX2200CF Range
Ancillary devices
Callpoints CX201 and CX203
> Design approved to EN54 -11 > Convenient clip fixed front cover > One key for test and cover removal > Available as flush, surface and weatherproof (IP65)
Technical Specifications
Model Configuration Rating Connection Operating method Test facility Construction IP Rating Temp Dimensions WxHxD (mm) Weight CX201 - Flush/Surface CX203 - Weatherproof Series resistor 680 24 V DC 4-way terminal block Glass element with safety film Unique key ABS IP42 -25C to +55C 86x86x20(S) 53(F) 0.19Kg 110x110x65 0.29Kg IP67
Product Codes
CX201 CX203 CXPC UBSG CXUK Flush/surface callpoint Weatherproof callpoint (IP67) Plastic front cover Pk of 10 Spare glasses Pk of 5 Call point keys Pk of 10
Bells
> High sound output > Low current > 4, 6 and 8-inch versions available
Technical Specifications
Model Operating voltage Sound output Current consumption Operating temperature Construction - Gong - Base Colour IP rating Dimensions (mm) Weight CFB4D24 84dB(A) at 12V DC 20mA at 24V DC CFB6D24 18 to 30V DC 93-95dB(A) at 24V DC 25mA at 24V DC -10C to +55C Steel Polycarbonate Red IP42 152 (Dia) x 63 (D) 0.85Kg
CFB4D24
CFB6D24
Product Codes
CFB4D24 CFB6D24 CFB8D24 4 Bell 6 Bell 8 Bell
FX2200CF Range
Ancillary devices
Electronic sounders
A comprehensive range of electronic sounders, beacons and sounder/beacons are available in the Cooper range.
Roshni ROLP
> Low current > High sound output > 32 selectable tones > IP65 version available > Lockable base
ROLP-R-S ROLP-R-D
Technical Specifications
Model Operating voltage Sound output (tone 3) Tones available Temperature Construction Colour IP rating Dimensions (mm) Weight ROLP-R-S 9 to 28V DC 102dB(A) at 24V DC 32 -25C to +70C ABS Red IP54 93 (Dia) x 63 (D) 0.24 Kg IP65 93 (Dia) x 93 (D) 0.3 Kg ROLP-R-D
Product Codes
ROLP-R-S ROLP-R-D Roshni sounder, shallow base Roshni sounder, deep base, IP65
Symphoni
> Ultra low current > High sound output > 3 Tones > Volume control > IP65 version available > Lockable base
SY-R SY-R-IP
Technical Specifications
Model Operating voltage Sound output Current consumption Operating temperature Colour IP rating Dimensions WxHxD (mm) Weight SY-R 12 to 30V DC 100dB(A) at 24V DC 5mA at 24V DC -25C to +70C Red IP42 110x110x95 0.58 Kg IP66 110x110x105 0.68 Kg SY-R-IP
Product Codes
SY-R SY-R-IP Symphoni sounder Symphoni sounder, IP66 4
FX2200CF Range
Ancillary devices
Askari
> Low current > High sound output > 32 tones > Volume control > Available in red (R) or white (W)
AC-W
Technical Specifications
Model Voltage Sound output Tones Temperature Construction Colour IP rating Dims WxHxD (mm) Weight AC-W (R) 9 to 28V DC 97dB(A) at 24V DC 32 -25C to +70C ABS Red or white IP54 (with backbox) 86x86x42 0.11Kg
Product Codes
AC-W AC-R Askari flush sounder - white Askari flush sounder - red
Squashni
> Low current > High sound output > 32 Tones > Volume control > Available in red (R) or white (W)
SQ-W
Technical Specifications
Model Operating voltage Sound output Current consumption Operating temperature Construction Colour IP rating Dimensions (mm) Weight SQ-W (R) 10 to 28V DC 93dB(A) at 24V DC 18mA at 24V DC -25C to +70C ABS White or red IP42 112 (Dia) x 30 (D) 0.15Kg
Product Codes
SQ-W SQ-R Squashni base sounder - white Squashni base sounder - red
FX2200CF Range
Ancillary devices
CS200
> Low current > High sound output > 32 tones > Clip fit base > Available in red (R) or white (W) > Lockable base
CS200W
Technical Specifications
Model Operating voltage Current consumption Sound output Tones Volume control Operating temperature Construction Colour IP rating Dimensions (mm) Weight CS200W (R) 10 to 28V DC 16mA at 24V DC 100dB(A) at 24V DC 32 20dB range -10C to +55C ABS Red or white IP21C 112 (Dia) x 30 (D) mm 0.24Kg
Product Codes
CS200W CS200R Electronic sounder - white Electronic sounder - red
Sounder/Beacons Flashni
> High output sounder beacon > Volume control > Lockable base
FL-RL-R-D
Technical Specifications
Model Operating voltage Sound output Current consumption Operating temperature Construction Colour IP rating Dimensions (mm) Weight FL-RL-R-S 18 to 30V DC 101dB(A) at 24V DC 68mA at 24V DC -10C to +55C Lens - Polycarbonate, Base - ABS Red IP42 93 (Dia) x 92 (D) mm 0.29Kg IP66 93 (Dia) x 121 (D) mm 0.33Kg FL-RL-R-D
Product Codes
FL-RL-R-S FL-RL-R-D Flashni sounder beacon, shallow base Flashni sounder beacon, deep base
FX2200CF Range
Ancillary devices
Base AV unit
> Low profile design > High output LED beacon > Volume control > Can be standalone unit or with detector & base > Tamper-proof cover for standalone use
SQG3-AV-W
Technical Specifications
Model Operating voltage Current consumption Operating temperature Light output Flash rate Tones Construction Colour IP rating Dimensions (mm) Weight SQG3-AV-W 18 to 28V DC 10mA at 24V DC -10C to +55C >1Cd 1Hz 5 ABS FR White IP40 114 (Dia) x 35 0.11Kg
Product Codes
SQG3-AV-W-CAP SQG3-COV Base sounder beacon unit Base sounder beacon cover Pk of 5
FX2200BWCF Range
Bi wire panels
The Cooper range of Bi wire panels are designed in such a way that there is no requirement for alarm lines to be installed; detectors, sounders, beacons and relays all share the same zone wiring pair giving significant savings in both cable and installation costs. The 4 and 8-zone panels provide enhanced features accessed via dip switch settings; these include non latching zones, alarm line output delay, double knock and pulsed alarm output facilities.
Features
> Choice of 2, 4 and 8-zone panels > Detectors and sounders share same wiring > Single 12 VDC battery requirement for 24-hour standby > Single keypad access code for end user and engineer use > Selectable fire/fault relay > Class change facility > Supports up to 20 detectors and 20 sounders, beacons or relays on each zone > Enhanced features available on 4 and 8-zone panels > Maintenance-free poly switch circuit protection
Technical Specifications
Model Standards Number of zones Detectors per zone Alarm circuit load End of line devices Auxiliary fire signal / fault output Mains input voltage System operating voltage Standby duration Battery (sealed lead acid) Recharge period Panel construction Cable entries Environmental rating Surface dimensions WxHxD (mm) FX2202BWCF FX2204BWCF FX2208BWCF EN54-2: 1998 & EN54-4:1998 EN50130-4: 1996 EN500081-1: 1992 & EN61000-2-2: 1994 2 4 8 20 150mA per zone Active end of line monitoring unit 1A 24V DC single pole changeover contacts 230V AC 10% +15% 24V DC 24 hours 1 x 3.2 AH 12V 2 x 3.2 AH 12V 24 hours Polycarbonate housing & back box Top: 12 x 20mm entries with blanking plugs. Rear cable entry aperture. IP30. -5C to +40C Humidity 75% max (non condensing) 332 x 270 x 92
Product Codes
FX2202BWCF FX2204BWCF FX2208BWCF 2-Zone panel 4-Zone panel 8-Zone panel
FX2200BWCF Range
Bi wire detectors
A comprehensive range of conventional detectors are available for Bi wire range of fire detection panels.
Features
> LPCB 3rd party approved > Low profile design > 360 viewable LED design > Removable detector chamber for cleaning > Common mounting base
CXN624
CXN623
CXN622
CXN625
CXN626
CDBB300
CIR301
Technical Specifications
Model Description Standards CXN623 Photoelectric Smoke Detector EN54 pt7:2000 & BSEN54 pt7:2001 CXN622 CXN625 Heat Detector (Fast Response) CXN624 Heat Detector (Medium Response) EN54 pt7:2000 & BSEN54 pt5:2001 CXN626 Heat Detector (High Temperature) Photo Thermal Smoke Detector EN54 pt7:2000, BSEN54 pt7:2002 & BSEN54 pt 5:2001 100m2 (subject to local standard)
Area coverage System wiring Indication Mounting Compatibility Detection mode Operating voltage Max stand-by current Max start up current Max alarm current Alarm temperature Heat class Environmental Application Temperature Humidity EMC Construction Material Colour Dimensions Including Base (mm)
50m2 (subject to local standard) 2 core 360 Visibility pipe Surface mount using CDBB300 FX2200BWCF range of panels Light scatter principle Light scatter principle & Heat sensitive element heat sensitive element 15V to 30V DC 30 A 70 A 30 A 210 A 340 A NA 25 mA 20 mA 25mA NA 60C 77C NA A2S A1R BS Indoor use IP40 -20C to 60C 0 - 95% non condensing CE marked PC/ABS White 104 (Dia) x 47 (H) 101 (Dia) x 56 (H)
92C CS
Product Codes
CXN623 CXN625 CXN626 CIR301 Photoelectric smoke detector Heat detector fast response Heat detector high temperature Remote indicator CXN622 CXN624 CDBB300 Photo thermal dual detector Heat detector medium response Common base
FX2200BWCF Range
Technical Specifications
Model Configuration Rating Connection Operating method Test facility Construction IP Rating Temp Dimensions WxHxD (mm) Weight CX201 - Flush/Surface CX203 - Weatherproof Series resistor 680 24 V DC 4-way terminal block Glass element with safety film Unique key ABS IP42 -25C to +55C 86x86x20(S) 53(F) 0.19Kg 110x110x65 0.29Kg IP67
Product Codes
CX201 CX203 CXPC UBSG CXUK Flush/surface callpoint Weatherproof callpoint (IP67) Plastic front cover Pk of 10 Spare glasses Pk of 5 Call point keys Pk of 10
Electronic sounder
> Ultra low current > High sound output > Volume control > Lockable base
CX009
Technical Specifications
Model Operating voltage Sound output Current consumption Operating temperature Colour IP rating Dimensions WxHxD (mm) Weight CX009 12 to 30V DC 100dB(A) at 24V DC 5mA at 24V DC -25C to +70C Red IP42 105x105x95 0.28 Kg
Product Codes
CX009 Electronic sounder
10
FX2200BWCF Range
Technical Specifications
Model Operating voltage Sound output Current consumption Operating temperature Construction Colour IP rating Dimensions (mm) Weight CXN520BWS 25 to 32V DC 90dB(A) at 1 metre 8mA -10C to +55C ABS White IP40 102 (Dia) x 40 (D) 0.2Kg
CXN520BWS
Product Codes
CXN520BWS Base sounder
LED Beacon
> High output LED beacon > Low current
Technical Specifications
CXN004BW
Model Operating voltage Current consumption Operating temperature Construction Colour IP rating Dimensions (mm) Weight
CXN004BW 18 to 30V DC 68mA at 24V DC -10C to +55C Lens - Polycarbonate, Base - ABS Red IP42 95 (Dia) x 53 (D) 0.1Kg
Product Codes
CXN004BW LED beacon
11
FX2200BWCF Range
Technical Specifications
Model Sets of contacts Contact rating Colour IP rating Dimensions WxHxD (mm) Weight CXN01124V 1 set of change over contacts 1A (24V DC) White IP40 150x89x58 0.2Kg 3A (230V DC) CXN011230
Product Codes
CXN01124V CXN011230 Relay module 24V DC switching Relay module 230V AC switching
12
CF3000 Range
Analogue panels
The Cooper CF3000 range of panels offer a high-specification, analogue fire detection panel solution which is available in a 1, 2 or 4-loop configuration. It combines sophisticated functionality, yet simple panel operation with a very aesthetically-pleasing design. The large capacity, ability to support complex cause and effect programming and wide range of user-controllable functions make this panel suitable for a wide range of projects from sheltered housing to large office developments as well as many industrial applications. The CF3000 range of panels provide a large (120mm x 90mm) touch screen display as the main user element, eliminating the need for dedicated system push buttons. The user interface is menu-driven, automatically reconfiguring to suit the chosen menu option. To enable text updates directly at the panel, the display converts to a full QWERTY keyboard, enabling comprehensive text insertion. The panel also has 96 zone fire LEDs providing additional information about the extent of any fire activation as well as a comprehensive set of system status LEDs providing additional visual information for the end user. The panels use spur tolerant soft addressing to minimise installation time and remove the potential for error normally associated with manual addressing. All of the CF3000 fire detection system components have been specifically designed to operate as part of an integrated system; this provides an assurance that the panel, sensors, interfaces and other ancillaries are all fully compatible with each other and that the full range of system functionality is supported by each device.
Features
> LPCB 3rd party approved to EN54 pts. 2 and 4 > Choice of 1, 2 and 4-loop panel options > Large multi functional touch screen > Spur tolerant soft addressing > Short circuit isolators incorporated into each loop device > Up to 200 addresses per loop > Fully network capable up to 127 panels > Network compatible with CF1000 range and CF2000 range of panels > Optional integral printer
Product Codes
CF30001G CF30002G CF30004G CF30001GP CF30002GP CF30004GP 13 1-Loop panel 2-Loop panel 4-Loop panel 1-Loop panel c/w integral printer 2-Loop panel c/w integral printer 4-Loop panel c/w integral printer CF30001GNC CF30002GNC CF30004GNC CF30001GPNC CF30002GPNC CF30004GPNC 1-Loop panel c/w network card 2-Loop panel c/w network card 4-Loop panel c/w network card 1-Loop panel c/w integral printer and network card 2-Loop panel c/w integral printer and network card 4-Loop panel c/w integral printer and network car
CF2000 Range
Analogue panels
The Cooper CF2000 panel is an entry level two-loop analogue fire detection panel which can be configured for 1 or 2-loop operation. The panel has a 126mm x 64mm graphic display which provides a simple yet comprehensive, menu-driven, end user interface. With the panels ability to support complex cause and effect programming and a wide range of user controllable functions it makes the panel suitable for a varied range of projects from small warehouses to small/medium office developments as well as many small industrial applications. As with all Cooper analogue addressable panels, the CF2000 uses spur tolerant soft addressing to minimise installation time and remove the potential for errors often associated with many forms of manual addressing. All of the CF2000 fire detection system components have been specifically designed to operate as part of an integrated system; this provides an assurance that the panel, sensors, interfaces and other ancillaries are all fully compatible with each other and that the full range of system functionality is supported by each device.
Features
> BOSEC 3rd party approved to EN54 pts. 2 and 4 > Choice of 1 or 2-loop panel operation > Menu-driven graphic screen > Spur tolerant soft addressing > Short circuit isolators incorporated into each loop device > Up to 200 addresses per loop > Network compatible with CF1000 and CF3000 range of panels
Product Codes
CF2000G CF2000GNC 2-Loop panel 2-Loop panel c/w network card
14
CF1000 Range
Analogue panels
The Cooper CF1000 range of analogue fire detection panels are available as 1 and 2-loop configured panels. They provide sophisticated touch screen functionality yet achieve a simple end user interface operation within a compact panel design. The CF1000 range of panels provide a large (120mm x 90mm) touch screen display as the main user element, eliminating the need for dedicated system push buttons. The user interface is menu-driven, automatically reconfiguring to suit the chosen menu option. To enable text updates directly at the panel, the display converts to a full QWERTY keyboard, enabling comprehensive text insertion. The panel also has 16 zone fire LEDs providing additional information about the extent of any fire activation as well as a comprehensive set of system status LEDs providing additional visual information for the end user. The CF1000 range supports a complex cause and effect programming ability which, together with a wide range of user controllable functions, makes the panel suitable for a wide range of projects. As with all Cooper analogue panels the CF1000 range uses spur tolerant soft addressing thereby minimising installation time and removing the potential for errors often associated with other forms of system addressing. As with the entire range of Cooper analogue panels, the CF1000 range of panel system components have been specifically designed to operate as part of an integrated system; this provides an assurance that the panel, sensors, interfaces and other ancillaries are all fully compatible with each other and that the full range of system functionality is supported by each device.
Features
> Large versatile touch screen display > 1 and 2-loop panel versions > Spur tolerant soft addressing > Short circuit isolators incorporated into every loop device > Up to 200 addresses per loop > Network capable with CF3000 and CF2000 range of panels > Integral power supply > Large selection of compatible ancillaries
Product Codes
CF1100 CF1100NC CF1200 CF1200NC 1-Loop panel 1-Loop panel c/w network card 2-Loop panel 2-Loop panel c/w network card
15
CF3000PRG Range
Features
> 2x40 backlit LCD display > Loop or network connected > Silence alarm, evacuate and reset commands from repeater
Product Codes
CF3000PRG CF3000PRGNC Loop-connected repeater panel Network-connected repeater panel
Loop connected
Network connected
Mains Supply
Mains Supply
Mains Supply
16
System Configuration
System configuration
The Cooper analogue control panel system architecture has been designed in such a way that future system expansion, within a single-panel solution or as part of a multi-panel network, can be achieved with a minimum amount of system downtime.
Interfaces
An extensive range of interfaces are available for the Cooper range of analogue panels providing solutions for most design requirements.
> Spur isolator available to allow loop spurs of analogue addressable devices > 3-way 24V rated input / output unit suitable for switching low voltage control equipment > Zone monitor unit, to connect zones of suitable conventional detectors or loop-powered beam detectors > Mains rated Input / output unit for switching mains operated equipment > Sounder circuit controller provides four additional, programmable, conventional sounder circuits remote from the main control panel > Shop unit isolator allows the connection of a conventional detection zone along with two conventional sounder circuits, ideal for linking small self-contained units onto a main addressable panel. The interface requires a 24 vdc power supply.
Soft Addressing
The system auto learn facility, once activated on initial panel start up, will scan each loop and allocate an address number to each loop device thus providing a simple yet efficient setup procedure which alleviates the need for time consuming manual device addressing and minimises potential problems due to dual addressing. Each loop device has integral short circuit isolators ensuring maximum loop integrity should a short-circuit fault occur on the loop wiring.
Detection Capacity
Up to 200 addresses per loop can be installed, which can be a mixture of callpoints, sensors, beam detectors, interfaces, loop sounders or repeater panels. It should be noted that, to comply with EN54 requirements no more than 512 addresses should be connected to a single panel.
System Networking
The full range of Cooper analogue panels can be networked together. When fitted with a network card, up to 126 panels and repeaters can be networked to form a single co-ordinated system. With larger networked systems, where long distances are found, it is possible to connect networks using LON boosters, fibre optic interfaces or IP routers. When operating as a network system fire, fault and pre-alarm information is transmitted across the network, as well as text information, with evacuate, silence alarm and reset control functions also permitted across the network. Network configuration of the system, to permit or inhibit each signal or facility, is achieved using the engineering menu on each panel.
Alarm Capacity
Up to 80 loop-powered sounders, beacons, sounder beacons or interfaces can be connected per loop. With a full range of conventional sounders and beacons, up to a total load of 1.5A can be connected via the control panels four alarm line outputs. Alternatively additional conventional sounders can be connected via a CSC354 loop mounted 4-way sounder controller unit remotely from the panel.
Site Monitor/Graphics
Cooper Site Graphic is a versatile alarm management system providing a comprehensive site monitoring and control package of the installed fire detection system that interfaces to the network of the Cooper range of analogue panels using a network manager driver program. The site graphics dedicated PC is connected to the network via an EC0232 board.
17
System Configuration
Mains Supply
CSC354
Repeater
CMIO353
CIO351
CSI350
CSUM355
CZMU352
18
System Configuration
Technical Specifications
Panel type Standards Number of loops CF3000 CF30001 1 loop CF30002 2 loops CF30004 4 loops CF2000 CF1100 CF1200 EN-54:2 1998 & EN54:4 1998 EN-501304 2 1 2
Addresses per loop Panel sounder circuits Class change facility Auxiliary relay Auxiliary fire routing equipment output Auxiliary fire protection equipment output Auxiliary fault routing equipment output Output ports Mains input voltage System operating voltage Battery Standby duration Cable entries
200 4 outputs (programmed in pairs - outputs 1&2, 3&4) 2 Operated by external, normally open, volt free contacts One set of change over contacts, operated in the event of fire activation Monitored 24 V DC, 30 mA (max) Monitored 24 V DC, 30 mA (max) Monitored 12 V DC, 30 mA (max) RS485 and RS232 (for connection of repeaters etc) 230 V AC +10% / -15% 24 V DC 2 x 12 V 12Ah 2x 12 V 7Ah 2x12 V 7Ah 24 hours (dependant on loop loading) 31 top entry cable knockouts 20 top entry cable knockouts 11 top entry cable knockouts (20mm) (20mm) & 12 rear cable entry (20mm) & 7 rear cable entry plus rear entry cable aperture cable knockouts (20mm) cable knockouts (20mm) IP30, -5C to +40C, 75% RH (non condensing) Graphite 395x495x125 400x320x170 375x357x50 18Kg 15Kg 8Kg
Repeater Panel
Panel type Display System indicators System controls Input ports Mains input voltage System operating voltage Battery Standby duration Mechanical Environmental rating Colour Size WxHxD (mm) Weight Compatibility CF3000PRG and CF3000PRGNC 2x40 Character Backbit LCD Power on, fire, fault, test, disable and scroll Silence alarms, evacuate and reset RS232 (for connection of programmer) 230 V AC +10% / -15% 24 V DC 1 x 12 V 3.2Ah 24 hours (dependant on loop loading) PC/ABS, rating - UL94V0 IP30, 0C to 25C, 75% RH (non condensing) Light grey 332x270x92 3.6Kg CF3000, CF2000, CF1100 and CF1200
19
Detection
Analogue sensors
A comprehensive range of analogue sensors are available to operate with the Cooper analogue addressable panel range with the following :-
Features
> Stylish low profile design > 360 viewable LED design > Removable detector chamber
Product Codes
CAP320 CAPT340 CAH330 CAB300 CIR301 Optical sensor Photo thermal Dual sensor Heat sensor Analogue sensor base Remote indicator
CAB300 Common base CIR301 Remote indicator
Technical Specifications
Model Specification CAP320 EN54 pt7:2000 and BSEN54 pt7:2001 CAPT340 CAH330 EN54 pt5:2000 and BSEN54 pt5:2001 50m (subject to local standard) EN54 pt7:2000 and EN54 pt5:2000BS, BSEN54 pt7:2001 and BSEN54 pt 5:2001 100m (subject to local standard) Min. 1.5mm, 2 core loop or spur 360 visibility light pipe Surface mount CAB300 base CF range of analogue panels Auto address 18 to 30V DC 220A 5mA A1S na na 60C na na Indoor use IP 40 -20C to 50C 0 to 95% non condensing PC/ABS White 101 (Dia) x 33 (H) 104 (Dia) x 45 (H) 101 (Dia) x 43 (H) 104 (Dia) x 55 (H) 76g (without base) 101 (Dia) x 43 (H) 104 (Dia) x 55 (H)
Area coverage System wiring Indication Mounting Compatibility Addressing mode Operating voltage Max standby current Max alarm current Heat class Rate of rise Fixed 60C Fixed 90C Alarm temperature (static) AIR BS CS Environmental Application Temperature Humidity Construction Material Colour Dimensions (excl.base) (mm) (incl.base) (mm) Weight
na na na na na na
-20C to 60C
-20C to 60C
20
Ancillaries
Addressable callpoints
The Cooper range of addressable callpoints are available as surface, flush and weatherproof versions. All callpoints have integral short circuit isolators and have a status LED fitted as standard. To simplify replacement of glass element callpoints are fitted with fast fit clip on front covers.
Technical Specifications
Model Type Configuration Rating Connections Operating method Test/reset facility Construction Colour IP rating Temp. range Dimensions HxWxD (mm) Weight CBG370 Flush
CBG370 Flush
CBG370-S Surface
CBG370-WP Weatherproof
CBG370-S
CBG370-WP
Surface Weatherproof Addressable 24V DC 4-way terminal block Glass element with plastic safety film or resetable plastic element with integral alarm indicator Unique key ABS Red to EN54-11 IP42 IP67 -10C to +55C 87x87x20 87x87x53 110x110x65 0.15Kg 0.2Kg 0.3Kg
Product Codes
CBG370 CBG370-S CBG370-WP CXPC UBSG CXUK Callpoint-flush Callpoint-surface Callpoint-weather resistant Polycarbonate cover (pk of 10) Spare glass (pk of 5) Spare callpoint key (pk of 10)
21
Ancillaries
Addressable sounders
Base sounder
The CAS380 is a loop-powered integrated sounder and sensor mounting base. It can be used with any analogue sensor or as a standalone sounder with the optional CASC cover plate.
CAS380
Wall sounder
The CAS381 range of loop-powered addressable wall sounders offers a highly efficient, low current sounder option. Sounder volume and tone are set at the analogue panel avoiding the need to access each sounder individually to alter settings.
Technical Specifications
Model Number Model Operating voltage Tones (set by panels) CAS380 Base sounder Continuous 910Hz Pulsed 910 / 0Hz @ 1Hz Two tone 610 / 910Hz @ 1Hz cycle Slow whoop Low volume: 84 dB Medium volume: 92 dB High volume: 95 dB CAS381 Wall sounder 17 to 32 V DC CAS381/WP Wall sounder - weatherproof
Standby current Operating temperature Construction Colour IP rating Dimensions HxWxD (mm) Weight
Continuous 910Hz Pulsed 910 / 0Hz @ 1Hz Two tone 644 / 984Hz @ 1Hz cycle Slow whoop 500-1200Hz in 3.5 sec / 0.5 sec gap Low volume: 87 dB Medium volume: 93 dB High volume: 100 dB Low volume: <2mA Medium volume: <3mA High volume: <6mA <320A -10C to +55C (95% RH) ABS Red Red IP42 IP66 105x105x95 108x108x103 0.25Kg 0.57Kg
Product Codes
CAS380 CAS381 CAS381-WP CASC Base sounder Addressable wall sounder Addressable wall sounder - weatherproof Pk of 5 base sounder covers
22
Ancillaries
Technical Specifications
Model Operating voltage Tones (set by panels) CASBB384 CASB383 17 to 32V DC Continuous 910Hz Pulsed 910 / 0Hz @ 1Hz Two tone 644 / 984Hz @ 1Hz cycle Slow whoop 500-1200Hz in 3.5 sec / 0.5 sec gap Low volume: 87 dB Medium volume: 93 dB High volume: 100 dB Low volume: <7mA Medium volume: <8mA High volume: <9mA <320A -10C to +55C (95% RH) PC ABS Red IP42 IP66 105x105x95 108x108x103 0.25Kg 0.57Kg CASB383-WP
Continuous 910Hz Pulsed 910 / 0Hz @ 1Hz Two tone 610 / 910Hz @ 1Hz cycle Slow whoop Sound output (set by panel) +/- 3 dB Low volume: 77 dB +/- 3 dB Medium volume: 89 dB High volume: 90 dB Current consumption
Standby current Operating temperature Construction Colour IP rating Dimensions HxWxD (mm) Weight
Product Codes
CASBB384 CASB383 CAS383-WP CASC Base sounder beacon Wall sounder beacon Wall sounder beacon - weatherproof Pk of 5 base sounder beacon covers
23
Ancillaries
Beacons
LED beacon
The CAS382 loop-powered addressable beacon offers high efficiency LED technology together with a low profile design for a discreet installation. The beacon is designed to provide a visual indication in areas of high ambient noise or where people may be hard of hearing.
Technical Specifications
Model Operating voltage Standby current Current consumption Operating temperature Flash frequency Construction Colour IP rating Dimensions (mm) Weight CAB382 17- 32V DC <250A <4.1mA -10C to +55C 1/2 Hz Lens - polycarbonate, base - ABS Red IP54 95 (Dia) x 53 (D) 0.15Kg
Product Codes
CAS382 LED beacon
24
Ancillaries
Interfaces
An extensive range of interfaces are available for the Cooper range of analogue panels providing solutions for most design requirements.
> CSI350 spur isolator available to allow loop spurs of analogue addressable devices > CIO351 3-channel 24V-rated input / output unit suitable for switching low voltage control equipment > CZMU352 zone monitor unit, to connect zones of suitable conventional detectors or loop powered beam detectors > CMIO353 mains-rated input / output unit for switching mains operated equipment > CSC354 Sounder circuit controller provides four additional, programmable, conventional sounder circuits remote from the main control panel > CSUM355 shop unit isolator allows the connection of a conventional detection zone along with two conventional sounder circuits, ideal for linking small self contained units onto a main addressable panel. The interface requires a 24 vdc power supply
MCIM MCOM
25
Ancillaries
PCBs
Mimic PCB
> Available as master or slave. Each has 32 outputs > 96 outputs (1 master + 2 slaves) > Ideal for mimic panel provision > Two types available:- LED or relay output > Each output can be programmed as fire or fault > Each output can be operated by address, zone or panel activation
4 to 20mA Interface
> Addressable interface with built in isolator > Ideal interface for gas detectors > Uses one address > Program 3 level of sensitivity using dip switch > 3 volt free outputs for each of the three alarm levels > Tracking/enabling facility (in tracking mode CF3000 will display pre-alarm 1, pre-alarm 2 & alarm). In alarm condition,CF3000 cause & effect programming is enabled > Requires external power supply (PSU is opto isolated from CF3000 loop) > The supply to the gas detector is taken directly from the interface
4 to 20mA Interface
26
Notes
27
Conditions of sale
All goods supplied are subject to the companys general conditions of sale which are available on request.
Trade Descriptions
All descriptions represent only particulars of the goods to which they apply and do not form part of any contract. The company reserves the right to change specification without prior notification or public announcement. 2008 Cooper All rights reserved.
Cooper Lighting and Safety Ltd. Wheatley Hall Road, Doncaster, South Yorkshire DN2 4NB www.cooper-ls.com
Sales T: +44 (0)1302 303 303 (Option 2) F: +44 (0)1302 367 155 E: sales@cooper-ls.com
CLSF042008 All Cooper logos are valuable trademarks of Cooper Industries in the U.S. and other countries. You are not permitted to use Cooper trademarks without the prior written consent of Cooper Industries.
Technical T: +44 (0)1302 303 350 F: +44 (0)1302 303 340 E: technical@cooper-ls.com
Export T: +44 (0)1302 303 250 F: +44 (0)1302 303 251 E: export@cooper-ls.com