Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

0300 Hager General Catalogue 17 256 257

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Miniature Circuit Breakers

Torque Settings, Electrical Characteristics

Torque Settings
Cables >1.5mm2 Cables ≤1.5mm2
Cable Stripping (mm)
Tightening torque (N.m) Tightening torque (N.m)

Pz No. (mm) Single Cable Multi Cables Single Cable Multi Cable
Consumer unit terminals
Earth and neutral terminal bars 2 6.5 2 2 1.5 1.5 10
Isolation
SB switch disconnectors 2 6.5 3.6 3.6 3.6 3.6 15
Circuit protection
MTN MCB 2 6.5 2.8 2.8 2.8 2.8 13
NBN/NCN/NDN MCB 2 6.5 2.8 2.8 2.8 2.8 13
RCBO 2 5.5 2.1 2.1 2.1 2.1 13
RCCB 2 5.5 2.8 2.8 2.8 2.8 13

MTN Electrical Characteristics.

Poles Rated Nominal Breaking Breaking Rated Rated Impulse Electrical Connection of
Operational Current Capacity (Icn ) Capacity (Ics ) Insulation Voltage Endurace Auxiliaries
Voltage Ue (V) to BS EN 60898 to BS EN 60898 Voltage Uimp (kV)
Ul (V)
Single Pole 230 6 - 63A 6kA 6kA 500V 4kV 10,000 No
cycles

Power Loss
The power loss of MCB’s is closely controlled by the standards and is calculated on the basis of the voltage drop across the main
terminals measured at rated current. The power loss of hager circuit breakers is very much lower than that required by the British Standard, so in consequences
run cooler and are less affected when mounted together.

The table below gives the watts loss per pole at rated current.

MCB Rated current (A) 0.5 1 2 3 4 6 10 13 16 20 25 32 40 50 63


Watts loss per pole 1.2 1.3 1.5 2.0 1.8 1.4 1.9 2.1 2.5 2.8 3.2 3.8 4.0 4.5 5.1
Distribution
Residential

4.17 Data is subject to errors and technical modifications.


Miniature Circuit Breakers
Technical Information

Connection
The circuit breaker can have the line\load connected to either the top or bottom terminals

Temperature Derating
MCBs are designed and calibrated to carry their rated current and to operate within their designated thermal time/current zone at 30ºC. Testing is carried out with
the breaker mounted singly in a vertical plane in a controlled environment. Therefore if the circuit breaker is required to operate in conditions which differ from the
reference conditions, certain factors have to be applied to the standard data.

In (A) -25ºC -20ºC -15ºC -10ºC -5ºC 0ºC 5ºC 10ºC 15ºC 20ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC 55ºC 60ºC
6 8.64 8.4 8.16 7.92 7.68 7.44 7.2 6.96 6.72 6.48 6.24 6 5.76 5.52 5.28 5.04 4.8 4.56
10 14.4 14 13.6 13.2 12.8 12.4 12 11.6 11.2 10.8 10.4 10 9.6 9.2 8.8 8.4 8 7.6
16 23 22.4 21.8 21.1 20.5 19.8 19.2 18.6 17.9 17.3 16.6 16 15.4 14.7 14.1 13.4 12.8 12.2
20 28.8 28 27.2 26.4 25.6 24.8 24 23.2 22.4 21.6 20.8 20 19.2 18.4 17.6 16.8 16 15.2
25 36 35 34 33 32 31 30 29 28 27 26 25 24 23 22 21 20 19
32 46.1 44.8 43.5 42.2 41 39.7 38.4 37.1 35.8 34.6 33.3 32 30.7 29.4 28.2 26.9 25.6 24.3
40 57.6 56 54.4 52.8 51.2 49.6 48 46.4 44.8 43.2 41.6 40 38.4 36.8 35.2 33.6 32 30.4
50 - - - - - 62 60 58 56 54 52 50 48 46 44 42 40 38
63 - - - - - - - - - - - 63 60.5 58 55.4 52.9 50.4 47.9

Distribution
Residential

Data is subject to errors and technical modifications. 4.18

You might also like