BX 11
BX 11
BX 11
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 1 of 92
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 2 of 92
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 3 of 92
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 4 of 92
We;
BAYKON ENDÜSTRİYEL KONTROL SİSTEMLERİ SAN. VE TİC. A.Ş.
Kimya Sanayicileri Organize Sanayi Bölgesi Organik Cad. No:31
34956 Tepeören Tuzla/İSTANBUL
to which this declaration relates, is in conformity with the following standard(s) or other normative
document(s).
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 5 of 92
2.1 Overview
BX11 family instruments are economic and powerful state-of-the-art technology indicators for weighing and
force measurements. These instruments convert the low level strain gage load cell analog signal to digital
signal in high resolution and accuracy to transmit digital data to PLC or PC. With a wide variety of interface,
BX11 instruments are used for any type of weighing processes and force measurement including tank and
silo weighing, dynamic weighing, check weighing, filling, tension /compression force measurement etc.
BX11 MB
BX11 CO
BX11 AN
BX11 PN
BX11 EN
BX11 PB
BX11
1 000 to 999 999 display resolution Yes Yes Yes Yes Yes Yes Yes
High internal resolution up to 16 000 000 counts Yes Yes Yes Yes Yes Yes Yes
Up to 1600 conversion per second Yes Yes Yes Yes Yes Yes Yes
Serial interface RS 232C Yes Yes Yes Yes Yes Yes Yes
Serial interface RS 485 Yes Yes Yes Yes Yes Yes Yes
Analogue output - Yes - - - - -
Profibus DPV1 interface - - - Yes - - -
Profinet interface - - - - Yes - -
Ethernet interface - - - - - Yes -
CANopen interface - - - - - - Yes
Continuous data output Yes Yes Yes Yes Yes Yes Yes
Fast Continuous data output Yes Yes Yes Yes Yes Yes Yes
BSI data interface Yes Yes Yes Yes Yes Yes Yes
Modbus RTU - Yes Yes Yes Yes Yes Yes
Modbus TCP - - - - - Yes -
1 digital input and 3 relay contact output - - - Yes Yes - Yes
2 digital input and 4 relay contact output Yes Yes Yes - - Yes -
Peak function Yes Yes Yes Yes Yes Yes Yes
Hold function Yes Yes Yes Yes Yes Yes Yes
Auto-zero tracking and auto-zero at power-up Yes Yes Yes Yes Yes Yes Yes
Motion detection Yes Yes Yes Yes Yes Yes Yes
Zeroing and Taring by field bus command Yes Yes Yes Yes Yes Yes Yes
Adaptive digital filter for fast and stable reading Yes Yes Yes Yes Yes Yes Yes
Electronic calibration (eCal) without test weights Yes Yes Yes Yes Yes Yes Yes
Electronic calibration (eCal) over field bus Yes Yes Yes Yes Yes Yes Yes
Zero and Span calibrations over field bus Yes Yes Yes Yes Yes Yes Yes
Zero adjustment Yes Yes Yes Yes Yes Yes Yes
Span adjustment with test weights Yes Yes Yes Yes Yes Yes Yes
Span adjustment for filled tanks Yes Yes Yes Yes Yes Yes Yes
3 point calibration ( linearity correction ) Yes Yes Yes Yes Yes Yes Yes
Programming by BAYKON IndFace1X PC software Yes Yes Yes Yes Yes Yes Yes
8 load cells 350 Ω or 18 load cells 1100 Ω Yes Yes Yes Yes Yes Yes Yes
12 to 28 VDC power supply range Yes Yes Yes Yes Yes Yes Yes
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 6 of 92
Common Specifications
A/D Converter:
A/D converter type: 24 bit Delta-Sigma radiometric with integral analog and digital filters
Conversion rate: Up to 1600 measurement values per second
Input sensitivity: 0.1 μV/e (non approved)
Analog input range: 0 mV to +18 mV ( unipolar ) ; - 18 mV to +18 mV ( bipolar )
Internal resolution: up to 16 000 000
External Resolution:
Display resolution up to 999 999 increment
Scale Calibration and Functions:
Calibration: Calibration is performed with or without test weights ( eCal )
Digital filter: 10 steps programmable adaptive filter
Taring, zeroing, auto zero tracking, motion detection, auto zero at power up, net
Weighing functions:
indication at power on, increased resolution
Linearity:
Within 0.0015% FS, ≤ 2 ppm/°C
Load cells:
Excitation: 5 VDC max. 300 mA
Number of load cells: Up to 8 load cells 350 Ω or 18 load cells 1100 Ω in parallel
4- or 6-wire technique.
Connection:
Cable length: maximum 250 m/mm² for 6-wire connection
Digital Inputs and Outputs:
1 optoisolated digital input at BX11 PB, BX11 PN, BX11 CO,
Digital Inputs 2 optoisolated digital inputs at BX11, BX11 AN, BX11 MB, BX11 EN,
12 to 28 VDC, 10mA
3 free relay contact at BX11 PB, BX11 PN, BX11 CO,
Digital Outputs 4 free relay contact at BX11, BX11 AN, BX11 MB, BX11 EN,
250 VAC or 30 VDC , 1A
DC Power supply:
12 to 28 VDC max. 300 mA
Environment and Enclosure:
Operation temp.: -10 °C to +40 °C; 85% RH max, non-condensing
Panel type, front panel and rear panel are stainless steel;
Enclosure
Aluminum body.
Protection Front panel IP67
BX11 AN Analogue
Communication:
Voltage output: 0-5 VDC, 0-10 VDC
Current output: 4-20mA, 0-20mA
D/A Converter: 16 bit
Max. cable length: 300 meter
Max. load resistance:
500 Ω
(current output )
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 7 of 92
BX11 PN Profinet
Communication:
Data rate: 100 Mbit/s, full duplex
GSDML file: Generic GSDML-file provided
DHCP or manual IP assign over EtherX PC Software.
TCP/IP settings:
Device identity customization
Topology: Line, Bus, Star or Tree topology depending on physical media
Switched Ethernet transmission with shielded twisted pair cables and RJ-45
Installation:
connectors.
Web client: Available
Isolation: Galvonically isolated bus electronics
Response speed: Up to 4 ms response delay after read/write commands
BX11 EN Ethernet
Communication:
Transmission rate: 10 Mbit/s, half duplex
TCP/IP settings: Manual IP assign over EtherX PC Software
Switched Ethernet transmission with shielded twisted pair cables and RJ-45
Installation:
connectors.
Web client: Available
Response speed: Up to 4 ms response delay after read/write commands
BX11 CO CANopen
Communication:
Data rate: 10 kbit/s – 1 Mbit/s (selectable) kbit/s
ESD file Generic EDS-file provided
Line with Trunkline, Dropline structure and Termination at both Ends
Topology:
Line length depending on baudrate 25 – 500 meter.
2 wire shielded twisted pair cable
Installation:
Alternatively 4 wire with 24 Volt power over the bus
Max. Stations: Up to 127 stations per network
Isolation Galvonically isolated bus electronics
Response speed: Up to 4 ms response delay after read/write commands
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 8 of 92
3.1 Display
The weight display of BX11 is seven segments LED. At the right side of the display there are two LED’s for
indicating the net and the unit ( standard kg ), also the left side of the display for indicating the gross, center
of zero and unstable.
Units g, kg, t, lb, klb, N, kN units are located on the right of the display.
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 9 of 92
GN / Set Point : Pressing this key indicates the Gross weight temporarily. To enter the set
point menu, long press this key.
Tare / Clear : Pressing this key tares the scale and get into the Net mode.
Zeroing: In Gross mode, if the scale doesn’t show zero while there is no load on the pan,
you can zero the scale by pressing this key.
Print: By pressing this key weight data and other information depending on the setup
parameters sent to a printer or a PC via serial port.
You can activate or deactivate this function by long pressing <F> key, press <Tare/Clear> and <Print>
keys sequentially. [ Lock ] prompt appear for a short while to indicate the pressed key is locked.
3.4 Housing
BX11 housings are panel type with stainless steel front and back parts, and aluminum body.
92 mm ( 3,62" )
47 mm
( 1,85" )
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 10 of 92
55 mm 46 mm
( 2.16" ) ( 1.81" )
BX11 AN Panel type rear view BX11 & BX11 MB Panel type rear view
BX11 PB Panel type rear view BX11 PN Panel type rear view
BX11 EN Panel type rear view BX11 CO Panel type rear view
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 11 of 92
BX11 MB
BX11 CO
BX11 AN
BX11 PN
BX11 EN
BX11 PB
BX11
3-pos and 3,81 mm pitch green plug for
1 2 1 1 1 1 1
power supply and analogue output
7-pos and 3,81 mm pitch black plug for load
1 1 1 1 1 1 1
cell cable
6-pos and 3,81 mm pitch black plug for
1 1 1 1 2 2 2
RS 232C&RS 485 and I/O
8-pos and 3,81 mm pitch green plug for I/O 1 1 1 1 - - -
User manual 1 1 1 1 1 1 1
Installation CD (IndFace1X setup, user manual
1 1 1 1 1 1 1
and technical documents)
BX11 CO
BX11 AN
BX11 PN
BX11 EN
BX11 PB
BX11
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 12 of 92
4.1 Recommendations
4.1.1 Control Cabinet Design
Warning: Please care the following warnings for designing the control cabinet which will increase your
system reliability.
The control cabinet should be designed so that Analog Digitizer can operate safely. The panel should be
placed clean area, not getting direct sun light if possible, with a temperature between -10 ºC and +40 ºC,
humidity not exceeding 85% non-condensing. All external cables should be installed safely to avoid
mechanical damages.
BX11 instruments are very low level signal measuring instruments. To avoid electrical noise, BX11 should be
separated from the equipments that produce electrical noise. Preferable use metal cabinet against radio
frequency interference and the cabinet shall be connected to ground against the electromagnetic
disturbances. Load cell cable trays must be separated from others, if possible. If there are noise-generating
equipments such as heavy load switches, motor control equipments, inductive loads etc., please be careful
against the EMC interference in the cabinet. If possible protect BX11 instruments with the faraday cage or
install them in separate section or install them far a way from this kind of equipments. Connect parallel
reverse diodes to the DC inductive loads like relays, solenoids etc. to minimize voltage peaks on the DC
power lines.
4.1.2 Cabling
All cables coming to the control cabinet shall be shielded. Please use separate cable tray for these low
signal level cables. Distance from load cell cables, interface cables and DC power supply cables to power
line cables shall be minimum 50 cm.
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 13 of 92
( rear view )
0V 24V
The quality of the instrument’s ground will determine the accuracy and the safety of your measuring system.
A proper ground connection is needed to minimize extraneous electrical noise affects on the measurement.
A poor ground can result in an unsafe and unstable operation. It is important that the instrument should not
share power lines with noise-generating parts such as heavy load switching relays, motor control
equipments, inductive loads, etc. If the condition of the power line in the plant is poor, prepare a special
power line and grounding.
Before interfering the instrument, turn off the power and wait at least for 30 seconds.
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 14 of 92
Warning: Always connect Sense pins to Excitation pins for 4 wire connection. Non-connected sense pins
may cause the wrong Excitation voltage measurement and create an accuracy problem.
Warning: Connect the load cell cable shield to the reference ground or shield pin of the load cell connector.
RS 232C serial connection is done with three wire as indicated below in Figure 4.4
Warning: Connecting the shield to the reference ground will protect your weighing system against EMC
disturbances.
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 15 of 92
RS 485 serial connection is done with three wire as indicated below in Figure 4.5. Line termination resistors
( 110 ohm ) are needed both ends of the RS 485 line.
Analogue connections are done as indicated below in Figure 4.6 and Figure 4.7.
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 16 of 92
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 17 of 92
The PC connection cabling will be done via cross cable as shown below. IP address blocks and gateway
address of BX11 and PC should be the same in cross connection.
Warning: Connect the shield to the reference ground or shield pin of the power connector.
Warning: Disconnect IndFace1X PC software before starting Profinet interfacing.
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 18 of 92
The PC connection cabling will be done via cross cable as shown below. IP address blocks and gateway
address of BX11 and PC should be the same in cross connection.
Warning: Connect the shield to the reference ground or shield pin of the power connector.
Warning: Disconnect IndFace1X PC software before starting Ethernet interfacing.
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 19 of 92
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 20 of 92
Digital Outputs:
BX11 instruments digital outputs are can be used as a standard, threshold and window. Threshold and
window outputs are also programmable positive or negative polarity. Digital outputs of BX11 are also
programmable as a fieldbus port to control them with a fieldbus commands. Refer to parameter [ 130 ] on
Page 42 and [ 70- ] on Page 49 . Outputs are 250 VAC or 30 VDC, 1A.
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 21 of 92
Standard Output:
Only one set point value is entered. The
output state is forced active high when the
weight is higher than SP1, else the output is
passive.
Refer to parameter [ 131 ] on Page 42.
Threshold Output:
2 set point values are entered. SP1 is the
point that the output goes active when the
weight increased from SP1_H. SP1_L is the
point that the output drops to passive state
when the weight decreased to SP1_L.
Inverse function is available.
Refer to parameter [ 7-- ] on Page 49.
Window Output:
2 set point values are entered. The output is
active when the weight is between SP1_L
and SP1_H. Inverse function is available.
Refer to parameter [ 7-- ] on Page 49.
4.4 Commissioning
PRECAUTION: Please read this manual carefully before energizing the instrument. Perform the
commissioning operation according the procedure given in this section. Only trained person is allowed for
cleaning, commissioning, checking and servicing of the instrument. The interference of untrained person
may cause some unwanted damages or injuries.
Before power on the instrument, please make the required mechanical and electrical installations. After
power on, you have to program your BX11 before field bus interfacing.
Install IndFace1X to your PC. IndFace1X software is used for easy programming, calibration and testing of
BX11 instruments.
After checking the performance of instruments with IndFace1X, you can begin to use BX11 in your
application.
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 22 of 92
The including of the status bytes STA, STB and STC are ;
Definition Table for Status A ( STA )
Bits 0, 1 and 2 Bits 3 and 4 Bit 5 Bit 6 Bit 7
0 1 2 Decimal point 3 4 Increment size
0 0 0 XXXXOO 1 0 X1
1 0 0 XXXXXO 0 1 X2
0 1 0 XXXXXX 1 1 X5
Always 1
Always 1
1 1 0 XXXXX.X X
0 0 1 XXXX.XX
1 0 1 XXX.XXX
0 1 1 XX.XXXX
1 1 1 X.XXXXX
Error Messages: UNDER, OVER, A.OUT, L-VOLT, H-VOLT, are represented in Indicated data fields.
Note: The weight data is represented with right aligned and the error messages are represented with left
aligned.
Note: The continuous data is started to send after 20 seconds after power-on. This property helps to
connect IndFace1X on RS 485 bus.
Examples :
S+000123.4 (weight is stable and 123.4)
D+000123.4 (weight is dynamic and 123.4)
+ (Over load)
- (Under load)
O (ADC out error)
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 24 of 92
M L S M L S M L S M L L C
S S P S S P S S P S S F R
D D D D D D D D
9 3 13 3 13 3 13 1 1
Multi Line
You can send the data in multiple lines as seen in the label given below by pressing < Enter > key.
The data output structure can be programmed with printer parameters.
General Rules:
Command format:
A general description of the command is the following:
[ADR][COMMAND][CHK][CR][LF]
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 25 of 92
Status Table:
Note: CHK, CR and LF will not be shown in below data format descriptions in this section.
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 26 of 92
Command : [ADR][A]
Response : [ADR][A][STATUS][SIGN][NET W][SIGN][TARE W][SIGN][GROSS W]
Example :
Command : 01A
Response : 01AS+000123.4+000111.1+000234.5
01AD+000123.4+000111.1+000234.5
01AO ( ADC out error )
Comments :
The response is net, tare and gross weight values or error status.
All weight data is transmitted immediately after receiving the command.
Command : [ADR][B]
Response : [ADR][B][STATUS][SIGN][WEIGHT VALUE]
Example :
Command : 01B
Response : 01BS+000123.4 (gross weight is stable and 123.4)
01BD+000123.4 (gross weight is dynamic and 123.4)
01B− (under load)
Comments :
The response is the gross weight value (stable or dynamic) or error status.
Gross weight data is transmitted immediately after receiving command.
Command : [ADR][C]
Response : [ADR][C][A] (Cleared and the scale is in gross mode)
Comments :
The response status is always Ack in weighing or force mode.
Command : [ADR][G]
Response : [ADR][G][STATUS][VOLTAGE VALUE]
Example :
Command : 01G
Response : 01GA234 (Power supply is 23.4 VDC)
01GA150 (Power supply is 15.0 VDC)
01GA090 (Power supply is 9.0 VDC)
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 27 of 92
Command : [ADR][I]
Response : [ADR][I][STATUS][SIGN][WEIGHT VALUE]
Example :
Command : 01I
Response : 01IS+000123.4 (weight is stable and 123.4)
01ID+000123.4 (weight is dynamic and 123.4)
01I+ (overload)
Comments :
Indicated weight value (stable or dynamic) is transmitted immediately.
The weight value may be in gross or net.
Command : [ADR][P]
Response : [ADR][P][STATUS][SIGN][WEIGHT VALUE]
Example :
Command : 01P
Response : 01PS+000123.4 (weight is stable and 123.4) or
01PN (could not print)
Comments :
Checks status and it must be stable. Else Nack status is send.
Status can be Stable or Nack.
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 28 of 92
S Read Status
Command : [ADR][S]
Response : [ADR][S][STATUS-1][STATUS-2][STATUS-3]
Example :
Command : 01S
Response : 01SSGI (Stable, Gross, In Range)
01SDGL (Dynamic, Gross, Low voltage error)
Comments :
The response includes 3 status information.
STATUS-1 can be Stable or Dynamic.
STATUS-2 can be Gross or Net.
STATUS-3 can be ‘In range’, ‘Out of range’, ‘+ Over’, ‘- Under’, ‘Low voltage’, ‘High voltage’ or ‘Errors’.
T Tare
Command : [ADR][T]
Response : [ADR][T][A] (Taring is done successfully and scale is in net)
[ADR][T][N] (Taring could not executed)
[ADR][T][X] (Taring is disabled)
Comments :
The tare value is overwritten by the new tare weight value.
Status must be stable in 2 seconds time out delay. If so, Ack is send.
If it can not be stable in time out delay, Nack is send.
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 29 of 92
Command : [ADR][U]
Response : [ADR][U][STATUS][Inputs]
Example :
Command : 01U
Response : 01UA03 (Input 2 and Input 1 are active)
01UA4296 (Input 15,10,8,5,3,2 are active)
01UAFF (All 8 inputs are active)
01UN (Could not read inputs)
Comments :
Data length change according to number of digital inputs.
Inputs are implemented to ASCII char of 4-bit. ‘1111’ inputs are implemented to char ‘F’.
INPUTS
IN-16
IN-15
IN-14
IN-13
IN-12
IN-11
IN-10
IN-9
IN-8
IN-7
IN-6
IN-5
IN-4
IN-3
IN-2
IN-1
Bit wise 0 1 0 0 0 0 1 0 1 0 0 1 0 1 1 0
ASCII 4 2 9 6
Command : [ADR][V]
Response : [ADR][V][STATUS][Outputs]
Example :
Command : 01V
Response : 01VA03 (Output 2 and Output 1 are active)
01VA4296 (Output 15,10,8,5,3,2 are active)
01VAFF (All 8 outputs are active)
01VN (Could not read outputs)
Comments :
Data length change according to number of digital outputs.
Outputs are implemented to ASCII char of 4-bit. ‘1111’ is implemented to char ‘F’.
OUT-16
OUT-15
OUT-14
OUT-13
OUT-12
OUT-11
OUT-10
OUT-9
OUT-8
OUT-7
OUT-6
OUT-5
OUT-4
OUT-3
OUT-2
OUT-1
OUTPUTS
Bit wise 0 1 0 0 0 0 1 0 1 0 0 1 0 1 1 0
ASCII 4 2 9 6
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 30 of 92
Command : [ADR][W][Outputs]
Response : [ADR][W][STATUS]
Example :
Command : 01W4296
Response : 01WA (Outputs 15,10,8,5,3,2 are activated)
01WN (Outputs could not be activated)
Comments :
Data length change according to number of digital outputs.
Outputs are implemented to ASCII char of 4-bit. ‘1111’ outputs are implemented to char F’.
OUT-16
OUT-15
OUT-14
OUT-13
OUT-12
OUT-11
OUT-10
OUT-9
OUT-8
OUT-7
OUT-6
OUT-5
OUT-4
OUT-3
OUT-2
OUT-1
OUTPUTS
Bit wise 0 1 0 0 0 0 1 0 1 0 0 1 0 1 1 0
ASCII 4 2 9 6
Command : [ADR][X]
Response : [ADR][X][STATUS][SIGN][WEIGHT VALUE]
Example :
Command : 01X
Response : 01XS+00123.41 (weight is stable and 123.41) or
01XD+00123.41 (weight is dynamic and 123.41) or
01XE (Error)
Comments :
The response includes weight data with divided the increment to 10.
Z Zero
Command : [ADR][Z]
Response : [ADR][Z][A] (Zeroed)
[ADR][Z][N] (Zeroing could not be operated)
[ADR][Z][X] (Zeroing is disabled)
Comments :
Zero command can not work in net weighing.
Weight must be in zeroing range for all operating modes.
Status must be stable in 2 seconds time out delay. If so, Ack is send.
If it can not be stable in time out delay, Nack is send.
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 31 of 92
Command: 01P[CHK][CR][LF]
Response: 01PS+000123.4[CHK][CR][LF]
Checksum = 0 − (0x30 + 0x31 + 0x50 + 0x53 + 0x2B + 0x30 + 0x30 + 0x30 + 0x31+ 0x32 + 0x33 +
0x2E + 0x34)
= 0 − 0x02B7
= 0x49
= Char ‘4’ and Char ‘9’
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 32 of 92
Exit without saving Advancing next Select the digit will be Changing parameter Enter
parameter changed value or increasing the
blanking digit
Display Operation
Programming and Calibration menu consist of main blocks which are shown as [X-- ] and sub-blocks.
By using < ↑ > key you can reach next main blocks. After reaching the desired main block, you can get in
by pressing < Enter > key. As you enter the block you will reach the first sub-block in that main block. The
sub-block address will be seen on the display as [X0- ]. You can also search between the sub-blocks by
using < ↑ > key and reach the first parameter of the sub-block seen on the display by pressing < Enter >
key. The number of the parameter comes on display as [XY0 ]. Again you can search between parameters
by < ↑ > key. For entering numerical value in the parameters, press the < Tare > key to select the digit
and press the < Zero > key the change the value.
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 33 of 92
Display Operation
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 34 of 92
008 007
RESP. Speed LF
018 017
RESP. Speed LF
05 _ 050 051
PROFIBUS FORMAT ADR
06 _ 060
PROFINET FORMAT
07 _ 070 071
CANopen FORMAT ADR
14 _ 142
ADJUSTMENT CN
4_ _ 40 _ 400 401
ANALOGUE S.SELECT. MODE SET to RANGE
Changeable with calibration
jumper
41 _ 410 411
ZERO CAL. COARSE FINE
42 _ 420 421
SPAN ADJ.. COARSE FINE
8_ _ 80 _ 800
M.LOGIC REC. RECORDS CAL. COUNT.
99 _ 990 991
PRMT. PRT ALL PRMT. DEFAULT
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 35 of 92
You can reach the parameters about serial interface of BX11 indicator in this section. The data output modes
can be used once except continuous data output.
0 : No data transfer.
1 : Continuous data output ( * ) ( Page 23 )
2 : Print mode ( Parameter [ 040 ] on Page 39 )
3 : BSI command set ( Page 25 )
4 : Modbus RTU High-Low ( Page 53 )
5 : Modbus RTU Low-High ( Page 53 )
6 : Fast continuous mode ( Page 24 )
( * ) Warning : Use for Baykon remote displays interfacing. CR and LF should be enabled.
You can define a device address between 1 and 99 by this parameter. If you enter 0, indicator will
operate without an address.
[005 0] Checksum
You can enable or disable for continuous data format and BSI command set.
0 : No CR 1 : CR enables
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 36 of 92
0 : No LF 1 : LF enables
0 : No data transfer.
1 : Continuous data output ( * ) ( Page 23 )
2 : Print mode ( Parameter [ 040 ] on Page 39 )
3 : BSI command set ( Page 25 )
4 : Modbus RTU High-Low ( Page 53 )
5 : Modbus RTU Low-High ( Page 53 )
6 : Fast continuous mode ( Page 24 )
( * ) Warning : Use for Baykon remote displays interfacing. CR and LF should be enabled.
You can define a device address between 1 and 99 by this parameter. If you enter 0, indicator will
operate without an address.
[015 0] Checksum
You can enable or disable for continuous data format and BSI command set.
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 37 of 92
0 : No CR 1 : CR enables
0 : No LF 1 : LF enables
0 : No data transfer.
1 : Continuous data output ( Page 23 )
2 : Print mode ( Parameter [ 040 ] on Page 39 )
3 : BSI command set ( Page 25 )
4 : Modbus TCP High-Low ( Page 76 )
5 : Modbus TCP Low-High ( Page 76 )
6 : Fast continuous mode ( Page 24 )
[032 ] IP Address
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 38 of 92
The local port will be entered between 00001 to 65535. Default is “502”.
[04-] Printer
If one of the serial interfaces is selected as printer, the label settings will be made in his sub-block.
[ XXXXXX] If the weight is less than the value entered here, the data will not be printed.
Explanation: If this parameter selected as auto print, the data will automatically be printed when
the data exceeds minimum print value and become stable. The weight value should decrease under
minimum print value to reprint. If this parameter selected as print interlock, after printing the weight
must be changed to reprint.
X=0,1 : 0 means the forward feeding and 1 means the backward feeding.
Y=0,1,2….9 : Enter the number of the feed lines before data printing
X=0,1 : 0 means the forward feeding and 1 means the backward feeding.
Y=0,1,2….9 : Enter the number of the feed lines after data printing
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 39 of 92
0 : No Form Feed
1 : After printing, the printer will go to next page automatically.
Here you can enter the number to shift the printout to the right on the paper.
Available values are from 0 to 9.
The Profibus rack address of BX11 will be entered via keypad between 001 to 126.
The CANopen rack address of BX11 will be entered via keypad between 001 to 126.
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 40 of 92
[11-] Start Up
Note: The parameter [ 202 ] must be selected as 0 to store Tare at power off.
[ ABCDE] When the key lock function is activated, the key(s) programmed as 1 in this parameter
is(are) locked (Page 10).
0 : No any
1 : Increased Indication
2 : Total
3 : Tare value indication
4 : CN value indication
5 : Hold function
6 : Peak function
Explanation: If this parameter selected as total, To clear the weight total, you need to press
< Clear > key while the total value is seen on the display and [ All C ] will appear on the display.
You can confirm deletion by pressing < Enter > key or cancel by pressing < F > key.
[12-] Filter
In this block the proper filter values according to the operating conditions can be entered. One of the most
important features of BX series is viewing filter characteristic on the display and with the help of this option,
you can select the most suitable filter without exiting the programming mode.
[120 7 ] Filter
The filter value can be selected from 0 to 9 ( The minimum value of the filter at least 7 in normal
weighing applications). As you enter this parameter and press < Enter > key while [120 X] seen
on the display, the weight variation can be seen on the display. The value of the filter can be
changed by using < ↑ > key and the weight variation for every value can be seen on the display.
After finishing the filter selection you can go to next step by pressing the < F > key.
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 41 of 92
[130 0 ] Outputs
The outputs operate with respect to the weight value seen on the display.
At BX11 PB, BX11 PN and BX11 CO the outputs are programmed as;
0 : No.
1 : ( Output1 = Sp1 ), (Output2 = Sp2 ), (Output3 = Sp3 )
2 : ( Output1 = Sp1 ), (Output2 = Sp2 ), (Output3 = Stable )
3 : ( Output1 = Sp1 ), (Output2 = Sp2 ), (Output3 = Error )
4 : Not used
5 : Functional outputs ( Refer to [ 7-- ] parameter group on Page 49 )
At BX11, BX11 AN, BX11 MB and BX11 EN the outputs are programmed as;
0 : No.
1 : ( Output1 = Sp1 ), (Output2 = Sp2 ), (Output3 = Sp3 ), (Output4 = Sp4 )
2 : ( Output1 = Sp1 ), (Output2 = Sp2 ), (Output3 = Sp3 ), (Output4 = Stable )
3 : ( Output1 = Sp1 ), (Output2 = Sp2 ), (Output3 = Sp3 ), (Output4 = Error )
4 : Not used
5 : Functional outputs ( Refer to [ 7-- ] parameter group on Page 49 )
[131 0] Input 1
[14-] Entries
In this block you can enter the initial CN.
[142 ] Label No ( CN )
[ XXXXXX ]
The desired value is entered via < Tare > and < Zero > keys and saved by pressing < Enter > key.
If the number exceeds 65535, it will automatically reset and begin from 1 again.
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 42 of 92
[20-] Set Up
The parameters about weighing operation are being entered here.
[200 0] Approved
0 : No 1 : OIML
According to the selection below, during power on, if the weight is in the percentage of the capacity,
the scale will automatically be zeroed. If the weight is not in zeroing range, the display will show
[E E E ] message until pressing < Enter > key.
0 : Disable 1 : ± 2% 2 : ± 10%
AZT automatically readjusts the scale to zero for compensating selected small deviation per second
around centre of zero.
0 : Disable 1 : ± 0,5e 2 : ± 1e 3 : ± 3e
[205 1] Tare
0 : Disabled
1 : Multi tare via key
2 : Tare via key if scale is in gross mode
This parameter defines the sensitivity level which will determine what is considered as stable.
If the scale is stabile during this time, the scale is accepted as a stabile to process zeroing, tare,
print etc. commands. It can be entered up to 9.9 sec.
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 43 of 92
0 : Weighing ( unipolar )
5 : Force ( bipolar )
You will reach the next parameter by pressing the < Enter > key.
[212 ] Capacity
[CAP ]
[ XXXXXX ]
Enter the capacity of the scale via < Tare > and < Zero > keys and confirms the value with
pressing < Enter >.
[d ]
[ XXXXXX ]
Display resolution will be selected by < Zero > key and confirmed with < Enter > key.
[214 1] Unit
0 : g (Gram)
1 : kg (Kilogram)
2 : t (Ton)
3 : lb (Libre)
4 : klb (Kilolibre)
5 : N (Newton)
6 : kN (Kilonewton)
[30-] Calibration
[300 ] Gravity
This parameter should be used in the scale that will be verified in two stages by gravity adjustment
(in legal metrologic applications). This parameter should not be touched in other applications.
If you enter a value in this parameter before calibration ( as six decimal digits. Enter 798564 for
9.798564), this value will be assumed as the reference gravity acceleration where the first stage of
the calibration performed. After calibration this parameter will be zeroed. If value of this parameter
is zero, that means no gravity adjustment had been performed after calibration.
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 44 of 92
[301 ] Calibration
Calibration involves emptying the scale then placing a known test weight on an empty platform and
allowing the BX11 indicator to capture values for zero and span. Calibration is performed as;
1. Press < Enter > at the [ 301 ] prompt to start the calibration.
2. At the [ ZEro.CA ] prompt, remove any weight on the platform, then press < Enter >.
3. The terminal automatically starts to capture zero and the [ WAıt ] message indicating the
operation is in progress.
4. After the [ Load ] prompt, the test weight value will be used for the calibration seen on the
display as [ XXXXXX ] . If the value of the test weights that will be used is different from
the value shown on the display, type the new value via < Tare > and < Zero > keys.
A minimum of 20% of scale capacity is necessary for calibration; BAYKON recommends 50
to 100%. A calibration error will result if insufficient weight is used.
5. Place the test weights or another practical weight on the scale.
6. Press < Enter > to start span calibration. [ WAıt ] message will shown on the display 10
seconds while span calibration is being performed.
7. At the [ SAvE ] prompt press < Enter > key to continue to the next parameter or press
< F > key to exit without saving the calibration.
Because of the load cell non linearity or mechanical scale hardware, you may see non linearity on
the scale performance. Three step scale calibration in this parameter improves the scale
performance.
1. Press < Enter > at the [ 302 ] prompt to start the calibration.
2. At the [ ZEro.CA ] prompt, remove any weight on the platform, then press < Enter >.
3. The terminal automatically starts to capture zero and the [ WAıt ] message indicating the
operation is in progress.
4. At the [ Load 1 ] prompt, the test weight value will be used for the first step calibration
seen on the display as [ XXXXXX ] . If the value of the test weights that will be used is
different from the value shown on the display, type the new value via < Tare > and
< Zero > keys. This load value equaling between 35% and 65% of the scale’s capacity.
5. Place the test weights or another practical weight on the scale.
6. Press < Enter > to start span calibration. [ WAıt ] message will shown on the display 10
seconds while the first span calibration is being performed.
7. At the [ Load 2 ] prompt, the test weight value will be used for the second step calibration
seen on the display as [ XXXXXX ] . If the value of the test weights that will be used is
different from the value shown on the display, type the new value via < Tare > and
< Zero > keys. Place weight on the platform equaling at least 90% of scale capacity,
preferable at scale capacity as much as is practical.
8. Place the test weights or another practical weight on the scale.
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 45 of 92
[31-] Adjustment
In this sub-block you can only perform zero adjustment or span adjustment without full calibration
operation.
This parameter is only being used for refreshing the zero level of the scale to prevent wrong
weightings from zero drifts.
1. Press < Enter > at the [ 310 ] prompt to start the zero adjustment.
2. At the [ ZEro.CA ] prompt, remove any weight on the platform, then press < Enter >.
3. The terminal automatically starts to capture zero and the [ WAıt ] message indicating the
operation is in progress.
4. At the [ SAvE ] prompt press < Enter > key to continue to the next parameter or press
< F > key to exit without saving the calibration.
1. Press < Enter > at the [ 311 ] prompt to start the span adjustment.
2. At the [ XXXXXX ] prompt, the test weight value will be used for the calibration seen on
the display. If the value of the test weights that will be used is different from the value
shown on the display, type the new value via tare and zero keys. A minimum of 20% of
scale capacity is necessary for calibration; BAYKON recommends 50 to 100%. A calibration
error will result if insufficient weight is used.
3. Place the test weights or another practical weight on the scale.
4. Press < Enter > to start span calibration. [ WAıt ] message will shown on the display 10
seconds while span calibration is being performed.
5. At the [ SAvE ] prompt press < Enter > key to continue to the next parameter or press
< F > key to exit without saving the calibration.
This parameter is being used to perform span adjustment of a scale without lifting the load on it.
This operation especially used for span adjustment for filled tanks. You can make span adjustment
without emptying the tank.
1. Press < Enter > at the [ 312 ] prompt to start the span adjustment under load.
2. [ P.ZEro ] prompt appears on the display to indicate the scale load will be determined as
temporary zero.
3. Press < Enter > key and the display will show [ WAıt ] message during temporary zero
adjustment.
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 46 of 92
Warning: The scale capacity and increment shall be entered before performing eCal.
This parameter lets you to perform calibration without using any test weights. BX11 A/D coefficients
are adjusted in production for increasing eCal accuracy. The calibration coefficients are calculated
by scale capacity, total load cell capacity, load cell full scale output, and estimated dead load. If the
conditions are convenient for zero calibration, you may perform automatic zero adjustment instead
of entering estimated preload. Press < Tare > key to start eCal.
[LC.CAP ]
[XXXXXX]
Enter total load cell capacity via < Tare > and < Zero > keys and press < Enter > key to go to the
next step.
Example : If the weighing system has 4 pcs 1000 kg load cell, enter 4000.
[LC.oUt ]
[XXXXXX]
Enter load cell output in mV/V via < Tare > and < Zero > keys. If the weighing system has more
than one load cell, calculate the mean value of load cells outputs mV/V indicated on the certificates
of the load cells. Press < Enter > key to go to the next step.
Example: If load cell outputs are LC1: 2.0010, LC2: 1.9998, LC3:1.9986 and LC4:2.0002, the mean
value will be
Mean of LC outputs = ( 2.0010 + 1.9998 + 1.9986 + 2.0002 ) ÷ 4 = 1.9999 mV/V.
[ZEr.AdJ]
[XXXXXX]
If the scale is empty and you want to make automatic zero adjustment instead of entering estimated
dead load ( look next step ), press < Enter > key appears [ Zero.CA ] and press < Enter > key for
starting zero calibration. The display will show [ WAıt ] message during zero adjustment. In this
while the scale must be unloaded and stable. Approximately 10 seconds later display will prompt
you to save the calibration by [ SAvE ] message below.
If the scale is not empty or you prefer to enter estimated preload value, press the up < G/N > key.
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 47 of 92
[ SAvE ]
Save your eCal calibration by pressing < Enter > key or press < F > key to go out without saving
your eCal calibration.
Note: If you want to make zero adjustment after entering estimated preload value, empty the scale,
change the preload value as (estimated value + display value at empty scale ) or enter parameter
[ 310 ] for zero adjustment.
0 : 4 – 20 mA
1 : 0 – 20 mA
2 : 0 – 5 VDC
3 : 0 – 10 VDC
Press Enter key. [ Ld dEf ] message appears on the display. Press < Tare > key for loading default
values or press < F > key to go next sub block.
The coarse zero adjustment is being performed by pressing < Zero > key one after another to
increase the analogue signal level or < Tare > key to decrease the analogue signal level.
The fine zero adjustment is being performed by pressing < Zero > key continuously one after
another to increase the analogue signal level or < Tare > key to decrease the analogue signal level.
Coarse span adjustment is being performed by pressing < Zero > key continuously one after
another to increase the analogue signal level or < Tare > key to decrease the analogue signal level
by taking the full capacity value as reference without placing any weight.
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 48 of 92
Fine span adjustment is being performed by pressing < Zero > key one after another to increase
the analogue signal level or < Tare > key to decrease the analogue signal level by taking the full
capacity value as reference without placing any weight.
Threshold Output :
2 set point values are entered. SP1 is the
point that the output goes active when the
weight increased from SP1_H. SP1_L is the
point that the output drops to passive state
when the weight decreased to SP1_L.
Inverse function is available.
Window Output:
2 set point values are entered. The output is
active when the weight is between SP1_L
and SP1_H. Inverse function is available.
[700 0] Output 1
0 : No function on output 1
1 : Threshold (Active High)
2 : Threshold (Active Low)
3 : Window (Active High)
4 : Window (Active Low)
5 : Fieldbus output
[701 0] Output 2
0 : No function on output 2
1 : Threshold (Active High)
2 : Threshold (Active Low)
3 : Window (Active High)
4 : Window (Active Low)
5 : Fieldbus output
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 49 of 92
0 : No function on output 3
1 : Threshold (Active High)
2 : Threshold (Active Low)
3 : Window (Active High)
4 : Window (Active Low)
5 : Fieldbus output
0 : No function on output 4
1 : Threshold (Active High)
2 : Threshold (Active Low)
3 : Window (Active High)
4 : Window (Active Low)
5 : Fieldbus output
This counter increases by 1 automatically after entering the programming mode with calibration DIP
switch. This counter cannot be changed manually.
[9--] Diagnostics
The operations about checking and testing BX11 can be made here.
[90-] Tests
In this step every keys ASCII code will be shown on the display as you press the related key. By this
way you can test if all the keys are functional or not. Pressing < ↑ > key will take you to the next
parameter.
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 50 of 92
The characters in the alphabet will sequentially be transferred from RS 232C serial interface port by
pressing < Zero > key one after another. Received numerical data is seen on display.
The characters in the alphabet will sequentially be transferred from RS 485 serial interface port by
pressing < Zero > key one after another. Received numerical data is seen on display.
[905 ] mV Indication
As you press < Enter > key the output voltage of the load cell will be shown on the display. This
uncalibrated value is only for test / service purposes.
By pressing < Enter > key the whole parameters can be printed.
Press < Enter > key. [ Ld dEf ] message appears on the display. Press < Tare > key for loading
default parameter values or press < F > key to go [ 9- ] sub block.
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 51 of 92
The analogue output is related with the gross load of the scale. The analog output signal operates as
described next.
When the gross indication drops below zero, the analog output reduces
Under Zero the analog output to 0mA or - 4 V to indicate error on the analog output.
The analog output will reflect the gross value to the programmed analog
Normal Range output 4 – 20 mA, 0 – 20 mA, 0 – 5 V or 0 – 10 V.
When the gross value exceeds the high limit, the analog signal increase to
Over High Limit approximately 24 mA or 11 V and remains there until the weight display is
no longer blanked or the analog signal returns to within range.
The following table indicates the analog output value when the gross indication is out of the range and if
there is any error indication on the display.
The error data indicated above can be used to follow the errors at PLC.
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 52 of 92
Parameter’s set-up:
Set the RS 485 / RS 232C Data Format : Modbus RTU High-Low or Modbus RTU Low-High
RS-485 Data Length & Parity : 8 none 1,
RS-485 Address : 01 to 31
Make the RS-485 / RS 232C parameter settings as defined on Page 36.
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 53 of 92
Dec Description
0 None
188 Adjust Zero Calibration
220 Adjust Span Calibration ( 1 )
40030 R/W 1 Calibration
236 Total Load Cell Capacity ( 1 )
250 Average mV/V ( 1 ) eCal
171 Dead Load ( 1 ) Coefficients
23205 Save the coefficients of eCal
40031 R/W 2 Span Calibration Value / LC capacity / mV value / Dead load value
Dec Description
D0 .. D7 1 Ready for calibration
3 Zero calibration in process …
Calibration 4 Span calibration in process …
Process
Status 9 Error (Refer to D8 ... D15 )
Calibration Timeout
1
- Restart calibration
ADC Error
2 - Re-energize the instrument
- If seen again, change the board.
Instrument can not be calibrating
3 - Check load cell cable
Calibration - Re-energize the instrument
40033 R 1 Instrument can not be calibrating
Status
34
D8 .. D15 - Load cell signal is very low or too high
Calibration Error
Calibration - Calibration loading is not enough
35
Errors - Check test weight loading
- Check load cell connections
Calibration load value entry Error
36 - Test weight is too small. Increase the test
weight
Scale unstable
37 - Wait until scale become stable
- Check grounding wiring
The Calibration DIP switch is not ON position.
38
- Check the calibration DIP switch.
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 54 of 92
D0 Input-1
40200 R 1 Status of Inputs
D1 Input-2
D0 Output-1
D1 Output-2
40201 R/W 1 Status of Outputs
D2 Output-3
D3 Output-4
40202 R/W 2 Setpoint 1 Low (2)
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 55 of 92
EXPLANATION:
Attention: For hardware connection details, please refer to the related hardware descriptions in this manual.
Exception codes:
1: Function code is not supported.
2: Out of beginning and ending address range.
3: Invalid value entrance or wrong byte number.
4: Operation error.
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 56 of 92
Performing Read and Write operations according (Modbus RTU High-Low) to hex system with the instrument
set to address “0x01”.
Description Hex
Request weight data 01,03,00,00,00,02,C4,0B
Answer of request weight 01,03,04,00,01,86,A0,38,4A
(weight value is 100000 )
Request status data 01,03,00,02,00,01,25,CA
Taring 01,10,00,08,00,01,02,00,02,26,D9
Request tare data 01,03,00,03,00,02,34,0B
Answer of request tare 01,03,04,00,00,27,10,E0,0F
(tare value is 10000 )
Zero Command 01,10,00,08,00,01,02,00,01,66,D8
Request Calibration Status 01,03,00,20,00,01,85,C0
Answer of request Calibration Status 01,03,02,00,01,79,84
(Instrument is ready for calibration)
Zero Calibration 01,10,00,1D,00,01,02,00,BC,A4,6C
Span Calibration Command with Span 01,10,00,1D,00,03,06,00,DC,00,00,C3,50,F7,F0
value 50000
Total LC capacity Command with Total 01,10,00,1D,00,03,06,00,EC,00,01,86,A0,D4,E0
LC capacity value 100000
Average mV/V Command with Average 01,10,00,1D,00,03,06,00,FA,00,00,4E,1F,DA,93
mV/V value 1.9999
Dead load Command with Dead load 01,10,00,1D,00,03,06,00,AB,00,00,30,39,87,25
value 12345
Save the coefficients of eCal 01,10,00,1D,00,01,02,5A,A5,5F,06
Command
Read Voltage of Power Supply value 01,03,00,63,00,01,74,14
Answer of Voltage of Power Supply 01,03,02,00,EB,F8,0B
(Voltage of Power Supply is 23,5 V)
Read digital inputs 01,03,00,C7,00,01,35,F7
Answer of digital inputs 01,03,02,00,02,39,85
(Input-2 is active)
Read digital outputs 01,03,00,C8,00,01,05,F4
Answer of digital outputs 01,03,02,00,04,B9,87
(Output-3 is Active)
Read Setpoint-1 Low 01,03,00,C9,00,02,14,35
Answer of Setpoint-1 Low 01,03,04,00,00,03,E8,FA,8D
Load Set point 1 Low = 5000 01,10,00,C9,00,02,04,00,00,13,88,32,C3
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 57 of 92
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 58 of 92
There are two LED’s near the Profibus connector which are ;
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 59 of 92
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 60 of 92
Bitwise of a Dword:
D31 D30 D29 D28 D27 D26 D25 D24 D23 D22 D21 D20 D19 D18 D17 D16
Dword
(Only read)
D15 D14 D13 D12 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 62 of 92
Bitwise of a Dword:
D31 D30 D29 D28 D27 D26 D25 D24 D23 D22 D21 D20 D19 D18 D17 D16
Dword
(R/W)
D15 D14 D13 D12 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0
1st
Next Dword defines the usage of this Dword.
Dword
01011 11
Not used
01110 14
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 63 of 92
(1) Write this command after writing values to 1st Dword , then apply this command with New CMD
(2) Only set point low addresses are used if the set point is programmed as standard.
Bit No Description
Bin Dec Commands
Voltage of Voltage of power supply is
00000000 0 R indicated with 0.1 VDC
Power Supply increment.
00000001 1
Not in use
00111111 63
01000000 64 RW Filter (1) Refer to par. [120] on page 41
01000001 65 RW Power On Zero (1) Refer to par. [202] on page 43
01000010 66 RW Zeroing Range (1) Refer to par. [203] on page 43
01000011 67 RW Auto Zero Tracking (1) Refer to par. [204] on page 43
01000100 68 RW Tare (1) Refer to par. [205] on page 43
Expanded 01000101 69 RW Motion Detector (1) Refer to par. [206] on page 43
D23…D16 Commands 01000110 70 RW Stability Period (1) Refer to par. [207] on page 43
List
01000111 71 RW Operation mode (1) Refer to par. [210] on page 44
01001000 72 RW Capacity (1) Refer to par. [212] on page 44
0 XXXXOO
1 XXXXXO
2 XXXXXX
01001001 73 RW Decimal point (1)
3 XXXXX.X
4 XXXX.XX
5 XXX.XXX
1 X1
01001010 74 RW Increment (1) 2 X2
3 X5
Table 9.2 - Expanded Command List
(1) Write this command after writing values to 1st Dword then apply this command with New CMD
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 64 of 92
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 65 of 92
LINK/Activity LED
DHCP
Dynamic Host Configuration Protocol automates network parameters if it is enabled.
Default is ‘Disable’.
IP Address
If DHCP is disabled, obtain IP address manually.
Default is ‘192.168.16.250’.
Subnet Mask
If DHCP is disabled, obtain subnet mask manually.
Default is ‘255.255.255.0’.
Default Gateway
If DHCP is disabled, obtain default gateway manually.
Default is ‘192.168.16.253’.
Primary DNS
If DHCP is disabled, obtain primary DNS manually.
Default is ‘208.67.222.222’.
Secondary DNS
If DHCP is disabled, obtain secondary DNS manually.
Default is ‘208.67.220.220’.
Host Name
Enter a unique host name to the instrument.
Default is ‘ ’.
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 67 of 92
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 68 of 92
Bitwise of a Dword:
D31 D30 D29 D28 D27 D26 D25 D24 D23 D22 D21 D20 D19 D18 D17 D16
Dword
(Only read)
D15 D14 D13 D12 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 70 of 92
Bitwise of a Dword:
D31 D30 D29 D28 D27 D26 D25 D24 D23 D22 D21 D20 D19 D18 D17 D16
Dword
(R/W)
D15 D14 D13 D12 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0
1st
Next Dword defines the usage of this Dword.
Dword
01011 11
Not used
01110 14
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 71 of 92
(1) Write this command after writing values to 1st Dword, then apply this command with New CMD
(2) Only set point low addresses are used if the set point is programmed as standard.
Bit No Description
Bin Dec Commands
Voltage of Voltage of power supply is indicated
00000000 0 R
Power Supply with 0.1 VDC increment.
00000001 1
Not in use
00111111 63
01000000 64 RW Filter (1) Refer to par. [120] on page 41
01000001 65 RW Power On Zero (1)
Refer to par. [202] on page 43
01000010 66 RW Zeroing Range (1) Refer to par. [203] on page 43
01000011 67 RW Auto Zero Tracking (1) Refer to par. [204] on page 43
01000100 68 RW Tare (1) Refer to par. [205] on page 43
Expanded 01000101 69 RW Motion Detector (1) Refer to par. [206] on page 43
D23…D16 Commands 01000110 70 RW Stability Period (1) Refer to par. [207] on page 43
List 01000111 71 RW Operation mode (1) Refer to par. [210] on page 44
01001000 72 RW Capacity (1) Refer to par. [212] on page 44
0 XXXXOO
1 XXXXXO
2 XXXXXX
01001001 73 RW Decimal point (1)
3 XXXXX.X
4 XXXX.XX
5 XXX.XXX
1 X1
01001010 74 RW Increment (1)
2 X2
3 X5
Table 10.2 - Expanded Command List
(1) Write this command after writing values to 1st Dword then apply this command with New CMD.
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 72 of 92
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 73 of 92
You can communicate with the indicator after programming Ethernet TCP/IP and Modbus TCP related
parameters [ 03- ] on Page 38.
Host Name
Device name of the instrument.
Default is ‘ ’.
IP Address
Obtain IP address manually.
Default is ‘192.168.16.250’.
Local Port
Ethernet connection port of the instrument.
Default is ‘502’.
Gateway
Network point that acts as an entrance to another network.
Default is ‘192.168.16.253’.
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 74 of 92
Primary DNS
Obtain primary DNS manually.
Default is ‘208.67.222.222’.
Secondary DNS
Obtain secondary DNS manually.
Default is ‘208.67.220.220’.
Remote Connection
Automatic connection to any device on the network.
Default is ‘Disabled’.
Remote IP : IP address of the PC or Device to be connected automatically.
Remote Port : Ethernet connection point of PC or Device to be connected automatically.
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 75 of 92
Parameter’s set-up:
Set Ethernet Data Format : Modbus TCP/IP High-Low or Modbus TCP/IP Low-High
Ethernet Address : 01 to 255
Make the Ethernet parameter settings as defined on Page 38.
Please find Modbus information in the web site of http://www.modbus.org
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 76 of 92
D0 Input-1
40200 R 1 Status of Inputs
D1 Input-2
D0 Output-1
D1 Output-2
40201 R/W 1 Status of Outputs
D2 Output-3
D3 Output-4
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 77 of 92
EXPLANATION:
Attention: For hardware connection details, please refer to the related hardware descriptions in this manual.
Exception codes:
1: Function code is not supported.
2: Out of beginning and ending address range.
3: Invalid value entrance or wrong byte number.
4: Operation error.
Command Examples:
Performing Read and Write operations according (Modbus TCP/IP High-Low) to hex system with the
instrument set to address “0x01”. MBAP (Modbus Application Protocol) Header is not included to the below
Modbus TCP/IP application data units.
Description Hex
Request weight data 01,03,00,00,00,02
Answer of request weight 01,03,04,00,01,86,A0
(weight value is 100000 )
Request status data 01,03,00,02,00,01
Taring 01,10,00,08,00,01,02,00,02
Request tare data 01,03,00,03,00,02
Answer of request tare 01,03,04,00,00,27,10
(tare value is 10000 )
Zero Command 01,10,00,08,00,01,02,00,01
Request Calibration Status 01,03,00,20,00,01
Answer of request Calibration Status 01,03,02,00,01
(Instrument is ready for calibration)
Zero Calibration 01,10,00,1D,00,01,02,00,BC
Span Calibration Command with Span 01,10,00,1D,00,03,06,00,DC,00,00,C3,50
value 50000
Total LC capacity Command with Total 01,10,00,1D,00,03,06,00,EC,00,01,86,A0
LC capacity value 100000
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 79 of 92
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 80 of 92
1 Run LED
2 Error LED
3 CANopen interface
Run LED
Error LED
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 81 of 92
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 82 of 92
D63 D62 D61 D60 D59 D58 D57 D56 D55 D54 D53 D52 D51 D50 D49 D48
Unsigned D47 D46 D45 D44 D43 D42 D41 D40 D39 D38 D37 D36 D35 D34 D33 D32
Long
(Only read) D31 D30 D29 D28 D27 D26 D25 D24 D23 D22 D21 D20 D19 D18 D17 D16
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 83 of 92
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 84 of 92
Bitwise of a Ulong:
D63 D62 D61 D60 D59 D58 D57 D56 D55 D54 D53 D52 D51 D50 D49 D48
Unsigned D47 D46 D45 D44 D43 D42 D41 D40 D39 D38 D37 D36 D35 D34 D33 D32
Long
(R/W) D31 D30 D29 D28 D27 D26 D25 D24 D23 D22 D21 D20 D19 D18 D17 D16
(1) Write this command with writing values to D0…D33 bits then apply New CMD.
(2) Only set point low addresses are used if the set point is programmed as standard.
Bit No Description
Bin Dec Commands
Voltage of Voltage of power supply is
00000000 0 R
Power Supply indicated with 0.1 VDC increment.
00000001 1
Not in use
00111111 63
01000000 64 RW Filter (1) Refer to par. [120] on page 41
01000001 65 RW Power On Zero (1)
Refer to par. [202] on page 43
01000010 66 RW Zeroing Range (1) Refer to par. [203] on page 43
01000011 67 RW Auto Zero Tracking (1) Refer to par. [204] on page 43
01000100 68 RW Tare (1) Refer to par. [205] on page 43
Expanded 01000101 69 RW Motion Detector (1) Refer to par. [206] on page 43
D48…D55 Commands 01000110 70 RW Stability Period (1) Refer to par. [207] on page 43
List 01000111 71 RW Operation mode (1) Refer to par. [210] on page 44
01001000 72 RW Capacity (1) Refer to par. [212] on page 44
0 XXXXOO
1 XXXXXO
2 XXXXXX
01001001 73 RW Decimal point (1)
3 XXXXX.X
4 XXXX.XX
5 XXX.XXX
1 X1
01001010 74 RW Increment (1) 2 X2
3 X5
Table 12.2 - Expanded Command List
(1) Write this command with writing values to D0~D33 bits then apply New CMD.
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 86 of 92
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 87 of 92
Error Table
ERROR
DESCRIBTION THINGS TO DO
CODE
- Check the load
Under Weight is too low
- Load cell or instrument could be broken.
- Check the load
Over Over Load
- Load cell or instrument could be broken.
- Check the load
ADC Out Load exceeds the operation range - Check the calibration
- Load cell or instrument could be broken.
- Re-energize indicator
Err 1 ADC error
- Call BAYKON
- Re-energize indicator
Err 2 ADC error
- Call BAYKON
- Check load cell cable and load then start
Err 3 Indicator can not be calibrating
calibration again
- Configure the instrument
Err 10 EEPROM error
- EEPROM broken
Err 20 Calibration error - Calibrate the indicator..
Err 21 Configuration error - Configure the indicator.
Tare, CN, Total weight and the SP in - Check SP, PT and ID entries.
Err 22
use error - Check Tare, CN and Total weight
Err 26 Set point error - Reload Set points.
Err 27 Indicator is not calibrated - Calibrate the indicator
Err 30 Processor Error - Call BAYKON
- Load cell signal is negative , very low or
Err 34 Indicator can not be calibrating
too high
- Calibration loading is not enough.
Err 35 Calibration Error
- Check test weight loading.
- Test weight is too small. Increase the test
Err 36 Calibration load value entry Error
weight.
- Wait until scale become stable.
Err 37 Scale unstable
- Check grounding wiring.
Err 47 Main pcb info error - Call BAYKON
Err 61 Eeprom is not installed or broken - Call BAYKON
E XXXX Hardware error - Call BAYKON
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 88 of 92
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 89 of 92
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 90 of 92
Question : My PC could not interface with BX11. How can I check the com port?
Answer : − Connect the instrument to the PC and run Hyper Terminal.
− Check com ports as described in The Diagnostic Test section on Page 50.
Question : IndFace1X installation needs restart every time. How can I install it?
Answer : − Read and follow the installation notes in the installation directory.
− Update your computer (visit http://update.microsoft.com).
Question : IndFace1X could not connect to instrument. What can I do?
Answer : − Check the power, data cabling and LED status of the BX11 instrument.
− Check PC port setting.
− Remove other connections. Re-energize the BX11 instrument and then make connection.
Question : My PC doesn’t have any COM port. How can I connect instrument to my PC?
Answer : You can use RS-232 / USB converter for serial interfacing via USB port. And select com port
with Connection Settings menu.
Question : My PC have a COM port but I couldn’t see COM port in Connection Setting menu. How can I
solve that problem?
Answer : Another software may be connected to that COM port. Close all applications before running
IndFace1X.
Question : My PC could not interface with BX11. How can I check the com ports?
Answer : Short circuit your com port RXD and TXD pins. Check if the sending data is received or not
by using any terminal software. You may test also BX11 com ports as described in The
Diagnostic Tests section on Page 50 by short circuiting RXD and TXD terminals.
Question : I need very fast interfacing. What is the response delay time of BX11?
Answer : BX11 response delay is max. 4 milliseconds for weight data. Extremely fast interfacing.
Question : What is the external conversion rate of BX11?
Answer : Only continuous data output rate might be called as an external conversion rate which is
depend on the baud rate and data length and up to 65 conversion/second.
Question : How can I check Ethernet connection?
Answer : − BX11EN has a dummy web page. You can easily open web page with any browser
installed on any PC in network.
Question : EtherX is searching but it could not find any instrument over Local Network Area.
Answer : − Check the Exceptions tap in Windows firewall settings. EtherX should be marked.
− Check the firewall of Anti-virus program, If you have.
Question : I done crossover connection with BX11 EN but EtherX could not find it.
Answer : − Check the Internet Protocol (TCP/IP) Properties in Local Area Connection of Windows.
IP address blocks and gateway address of BX11 and PC should be the same in cross
connection.
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 91 of 92
BX11 Smart Process Indicator, Technical Manual, Rev. 1.2, May 2013 Page 92 of 92