6164 Keypad Ademco
6164 Keypad Ademco
6164 Keypad Ademco
ZONESINPUTS
The four 2K EOLR zones have 300mS response. A local programming option allows selecting conventional EOLR type or double-balanced type for all zones as a group. Each double-balanced zone type supports up to 10 sensors. Four 2K EOL resistors are furnished, as well as four additional 2K resistors for use when double-balanced zones are used. Note: Do not use the zones on this keypad for commercial fire applications.
RELAY OUTPUTS
One Form-C relay provides contacts rated 1A, 24V AC/DC.
CASE TAMPER
An on-board tamper switch detects removal of case front from case back, and removal of the case back from its mounting surface. A local programming option allows you to disable the detection of a tamper condition. For tamper protection, an additional mounting screw must be used in the case back, as shown in Figure 2. When the 6164 keypad is used in the addressable mode, it will report a tamper condition to the control panel as a 4229 case tamper when the zone/relay feature is enabled, or as a general keypad tamper when the zone/relay feature is disabled. Note: The 6164 will not support general keypad tamper reporting when set to the non-addressable mode (keypad address 31). In the non-addressable mode, tamper will be reported as if it were a C function key/zone 96. Program this zone as a Type 5 Tamper Zone Type for proper reporting. Also, not all control panels support general keypad tamper reporting. Check with the control panels instructions.
On newer control panels (E.G: Vista-20P and Vista-12/48 series) the tamper will be reported using the ECP address assigned to the Zone Expander. Note that the tamper feature will function only if the zone expander has been enabled; Zone 96 can then be used as a keypad panic. Older control panels (E.G: Vista-20 SE) will not support general keypad tamper reporting when set to the nonaddressable mode (keypad address 31). In the nonaddressable mode, tamper will be reported as if it were a C function key/zone 96. Program this zone as a Type 5 Tamper Zone Type for proper reporting. Also, not all control panels support general keypad tamper reporting. Check with the control panels instructions. If the tamper is enabled Zone 96 cannot be used as a keypad panic.
these steps to mount and wire the keypad: 1. Detach the case back as follows: Push in one of the two case release snaps at the bottom of the keypad with the blade of a small screwdriver (this will push in the release snap), then pull that side of the case back away. Repeat for the other side. Refer to Figure 1 for location of the case back release snaps.
LG + MY
Wiring Table
Keypad Data Out GND +12VDC Data In Control Panel
Data In
Aux Pwr + Aux Pwr
Data Out
5. Connect the wires for the four 2K EOLR zones to the six screw terminals on keypad PC board as shown in Figure 3 and as follows: Keypad Z1 Wired Zone + Zone 1 - Zone 1 and Zone 2 return + Zone 2
ARMED
READY
NOTE: TO REMOVE REAR COVER PUSH IN THE TWO MOUNTING SNAPS LOCATED ALONG THE BOTTOM OF THE KEYPAD AND LIFT COVER UP.
Z2 Z3
+ Zone 3 - Zone 3 and Zone 4 return Z4 + Zone 4 Note: There is a common ground for zones 1 and 2, and one for zones 3 and 4. 6. Connect the zone contacts wires (door strike, etc.) to the three relay terminals marked NC, NO, and C as shown in Figure 3 and as follows: Keypad NO C NC Relay N.O. contact Pole contact (common) N.C. contact OPTIONAL
DOUBLE BALANCED 2K 2K [Y] DATA IN CONVENTIONAL EOLR
6164-003-V1
2K
TAMPER CONTACTS
N.O.
[+] +12VDC IN
2K
TAMPER CONTACTS
N.C.
N.O.
C. N.C.
6164-02-V0
Figure 2. Wiring Entry (Case Back) 4. Connect the power/data wires to the four screw terminals on the keypads PC board marked as shown in Figure 3 and as follows:
7. Reattach the keypad to the mounted case back. Attach the top of the keypad first, and then press the bottom section down until it snaps into place securely. 8. Peel off the protective film on the LED and keypad labels.
-2-
6164-005-V2
Y + Z1 Z2 Z4 Z3
Keypad address Tamper enable Zone expander enable Display option Zone expander address Sound option Zone type Language option These settings are maintained even when keypad power is removed.
The keypad options may only be programmed within 60 seconds of applying power. After that, they are not accessible for editing or viewing. The Address can still be viewed by holding down the 1 and 3 keys for approximately three (3) seconds. To re-enter programming mode, remove and reapply power and proceed as follows:
Perform the following steps to change the keypad options. 1. Enter the keypad's local program mode within 60 seconds of power-up by pressing and holding down the [1] and [3] keys at the same time for 3 seconds. The current keypad address will be displayed with the cursor under the "tens" digit.
CON ADDRESS = 31
2. If the current keypad address setting is acceptable (the default = 31), press the [] key to advance to the Zone Expander Enable field and go to step 3. To change the current keypad address, first reset the current address to 00 as follows: press [0] to clear the tens digits. The cursor will move to the ones digit position. Press [0] again to clear the ones digit. The cursor will move back to the tens digit position. Now set the desired keypad address as follows: Enter the proper tens digit for the keypads address. The cursor will move to the ones digit. Enter the proper ones digit for the keypads address. Press the [] key to store the displayed address and to advance to the Zone Expander Enable field. 3. By pressing the [1] key, you can toggle the Zone Expander Enable option (default = OFF).
9. For languages other than English enter [*]. For English language press [#]. This will also store the displayed settings and exit from the local programming mode.
EXP ADDRESS = 01
Consult the control panels installation guide to select the correct address (default = 01). Use the [] key to advance to the Zone Type option.
LANGUAGE? * = YES # = NO
Press [#] to advance to each of the listed languages. Place the cursor placed to the left of the selected language and press [] to continue with the selected language prompts.
In order to use the built-in zones and relay the panel must be programmed in the same way as for a 4229 zone.
5. By pressing the [1] key, you can toggle the Zone Type option.
SPECIFICATIONS
Dimensions: 5-3/8"H x 7-3/8"W x 1-1/4"D (137mm x 187mm x 32mm) Wiring Terminals: LG + MY Z4 Z3 Z2 Z1 NO C NC Data In to Control Panel Ground (12 VDC ) + 12 VDC Power Input Data Out from Control Panel + Wired Zone 4 - Wired Zone 3 and Zone 4 + Wired Zone 3 + Wired Zone 2 - Wired Zone 1 and Zone 2 + Wired Zone 1 Relay N.O. contact Relay Pole contact (common) Relay N.C. contact Display: 2 x 16 alphanumeric supertwist LCD, backlit. Sounder: Speaker (fire alarm sound is loud, temporal pattern pulsed tone; burglary alarm sound is loud, continuous, dual tone). Voltage: 12 VDC Current: Alarm rating: 190mA (LCD backlight on, sounder on, relay OFF) Standby rating: 115mA (LCD backlight on, sounder off, relay on); 55mA (LCD backlight off, sounder off, relay off) The control panel determines whether LCD backlighting is on or off. When determining the capacity of the control panels backup battery, use the following chart: If Backlighting is . . . On steadily Off when keypad is inactive Then . . . Use the 115 mA current rating. Use the 55mA current rating.
LEGEND = - (Ground/Common) NOTE: The keypad will display OPEN CKT and beep periodically when there is a fault that prevents data from reaching the keypad.
REFER TO THE INSTALLATION INSTRUCTIONS FOR THE CONTROL PANEL WITH WHICH THIS DEVICE IS USED FOR WARRANTY INFORMATION AND FOR LIMITATIONS OF THE ENTIRE ALARM SYSTEM.
K4842-1V2v