SINGLE-PHASE,230V,2WIRE+GROUND,60Hz.

PROPOSED SERVICE ENTRANCE


ELECTRICAL NOTES: 2- 14.0 mm 2 THW
1- 8.0 mm2 THW-GROUND
in 50MMØ RSC
CT
SPECIFICATION: KW-HR M
METER
1. ALL ELECTRICAL WORKS SHALL BE DONE IN ACCORDANCE WITH THE PROVISION OF THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE,
60AT,2P, ECB
EXISTING APPLICABLE ORDINANCES, RULES AND REGULATIONS OF THE LOCAL GOVERNMENT AND WITH THE REQUIREMENTS OF THE LOCAL POWER
COMPANY.
LEGEND & SYMBOL
2 - 5.5 mm² THHN BLACK WIRE
DESIGN CRITERIA: 1 - 3.5 mm² THW GROUND WHITE WIRE
1. THE TYPE OF SERVICE POWER SUPPLY TO BE USED SHALL BE SINGLE-PHASE, 2-WIRE, 230V, 60 HERTZ, A.C CIRCULAR LIGHT BULB WITH CASING
IN 25mm Ø UPVC
2. THE CONTRACTOR SHALL VERIFY AND ORIENT THE ACTUAL LOCATION OF SERVICE ENTRANCE FOR CONNECTION TO THE POWER COMPANY LIGHT BULB RECEPTACLE W/ INCADESCENT LED
35W EXHAUST FAN
SERVICE POINT.
FLOOD LIGH/LAMP POST 32 AT, 2P,240V,BOLT ON TYPE MCB
3. UNLESS OTHERWISE SPECIFIED, THE MINIMUM SIZES OF WIRE AND GALVANIZED RIGID STEEL CONDUIT OR UPVC PIPE CONDUIT TO BE USED
WALL LAMP
SHALL BE 2.0mm², THHN AND 15mm NOMINAL DIAMETER FOR RSC OR 20mm NOMINAL DIAMETER FOR UPVC, RESPECTIVELY LIKE WISE ALL ELECTRICAL DUPLEX CONVENIENCE OUTLET, NATIONAL
WP MODEL WEG15829-5 W/ WEATHER PROOF COVER
WIRES SHALL BE COLOR-CODED.
DUPLEX CONVENIENCE OUTLET L.O 1 2 L.O
4. GROUNDING FOR SERVICE ENTRANCE WOULD BE WHITE 5.5mm² THW NATIONAL. MODEL WEG15829-5 16AT 16AT
5. ALL GROUNDING FOR CONVENIENCE OUTLET WOULD BE GREEN 3.5mm² THHN M SERVICE METER
ECB ENCLOSED CIRCUIT BREAKER C.O 3 4 C.O
6. ALL LIGHTING CIRCUIT HOME RUNS SHALL BE WIRED WITH NOT LESS THAN 2.0mm² IN SIZE. 20AT 20AT
PP POWER PANELBOARD
7. ALL CONVENIENCE OUTLETS HOME RUNS SHALL BE WIRED WITH NOT LESS THAN 3.5mm² IN SIZE.
CIRCUIT HOMERUN TO PANEL REF 5 6 ACU1
CT CURRENT TRANSFORMER 20AT 20AT
CONSTRUCTION REQUIREMENTS: S1 NATIONAL ONE GANG SWITCH MODEL WEG6801W-1
1. WHEREVER REQUIRED AND NECESSARY, PULL OR JUNCTION BOXES SHALL BE INSTALLED AT CONVENIENT AND INCONSPICUOUS LOCATION,
ALTHOUGH SUCH BOXES ARE NOT SHOWN ON THE PLAN NOR MENTIONED IN THE SPECIFICATIONS.
S2 NATIONAL TWO GANG COVER WEG 6802W-1 ACU2 7 8 ACU 3
S3 THREE-WAY SWITCH-NATIONAL MODEL WEG5002K
20AT 20AT
2. ALL NON-CURRENT CARRYING METAL PARTS OF ELECTRICAL EQUIPMENT SHALL BE PROPERLY GROUNDED IN ACCORDANCE WITH THE
CIRCUIT BREAKER
PROVISIONS IN ARTICLE 2.50 "GROUNDING" PHILIPPINE ELECTRICAL CODE, VOLUME 1, 2000 EDITION. GB
REFRIGERATOR OUTLET, GROUNDING TYPE
3. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND OF THE APPROVED TYPE FOR LOCATION AND PURPOSE. REF NATIONAL WEG1101, PLATE COVER WEG6801W-1
SPECIAL-PURPOSE OUTLET (AIR-CONDITIONER UNIT) PB
4. STANDARD TYPE OF ACCESSORIES, SPLICING DEVICES, TERMINATIONS AND OTHER APPURTENANCES FOR THE ENTIRE ELECTRICAL ACU
RANGE OUTLET, GROUNDING TYPE
INSTALLATION SHALL BE USED. R TWIST-LOCK TYPE, 30A CAPACITY
RANGEHOOD OUTLET, GROUNDING TYPE
1 - 3.5 mm² THW WHITE WIRE Cu.
5. ALL WALL OUTLETS SHALL BE INSTALLED AT THE FOLLOWING HEIGHTS ABOVE THE FINISHED FLOOR LEVEL UNLESS NOTED IN THE PLANS. RH NATIONAL WEG1101, PLATE COVER WEG6801W-1
A) WALL SWITCHES @ 1400mm WATER HEATER OUTLET, GROUNDING TYPE
WH TWIST-LOCK TYPE, 30A CAPACITY
B) WALL CONVENIENCE OUTLET @ 300mm OR 150mm ABOVE WORK TABLE/COUNTER HEATER OUTLET, GROUNDING TYPE
HTR TWIST-LOCK TYPE, 30A CAPACITY
C) PANEL BOARD @ 1800mm
GROUND-FAULT INTERRUPTER OUTLET - NATIONAL
GFCI
6. ALL ELECTRICAL WORKS SHALL BE DONE UNDER THE DIRECT AND IMMEDIATE SUPERVISION OF A DULY REGISTERED ELECTRICAL ENGINEER.
E 1 SINGLE LINE DIAGRAM
2 SCALE NTS
PANELBOARD (PB):
DEVICES LOAD DESCRIPTIONS AMPS. BREAKER RATING WIRE GROUND COND.
CKT
VOLT PER mm² mm² mmØ
NO.
CKT THHN THHN PVC
LO SW CO OTHERS AT AF P Kaic
1 8 6" DL 2-15W, 4" DL 6-5W, 230 0.26 16 63 2 6 2-3.5 1-3.5 20
2 6 6" DL 1-15W, 4" DL 5-5W, 230 0.17 16 63 2 6 2-3.5 1-3.5 20
3 5 5-180VA DUPLEX RECEPTACLE 230 3.91 20 63 2 6 2-3.5 1-3.5 20
4 5 5-180VA DUPLEX RECEPTACLE 230 3.91 20 63 2 6 2-3.5 1-3.5 20
5 800VA,1Ø,230V,60Hz REFRIGERATOR OUTLET 230 3.48 20 63 2 6 2-3.5 1-3.5 20
6 1Hp,1Ø,230V,60Hz ACU (LIVING ROOM) 230 5.50 20 63 2 6 2-3.5 1-3.5 20
MPB
M 7 1Hp,1Ø,230V,60Hz ACU (BEDROOM-1) 230 5.50 20 63 2 6 2-3.5 1-3.5 25
8 1Hp,1Ø,230V,60Hz ACU (BEDROOM-2) 230 5.50 20 63 2 6 2-3.5 1-3.5 25
14 10 TOTAL CONNECTED LOAD 28.23
COMPUTATIONS : SERVICE FEEDER CONDUCTOR: ENCLOSURE : NEMA-1
I = [11.73A] @ 50% D.F. + [16.5A] @ 75% D.F. MOUNTING : FLUSH
2-5.5mm² THHN
+ 0.25 (5.5A) = 19.615 amps. 1-3.5mm² THHN-GROUND MAIN : 32AT,63AF,6Kaic,2POLE,230V,MCB
MINIMUM AMPACITY OF MAIN FEEDER CONDUCTOR: in 25MMØ PVC BREAKER : MCB
I = 1.25 x 19.615A = 24.52 amps.
E 1 RISER DIAGRAM
1 SCALE NTS
SHEET NO.
13
ELECTRICAL NOTES
RISER DIAGRAM
PROPOSED TWO-STOREY RESIDENCE
LEGEND AND SYMBOL E-1
ELECTRICAL ENGINEER
ABEGAIL D. TABLADA
OWNER
SINGLE LINE DIAGRAM
SCHEDULE OF LOAD AND COMPUTATION