Performance Report

TH Selborn 2024 - 330


Carrier China Sales Office
Date: 10/09/2024 11:39 PM Prepared By: PACK PING HENG

19MV-21N21N259E39
Chiller
Starter Type Unit Mounted Standard Tier VFD
Refrigerant Type R-134a
Liquid Bypass Not Installed
Operation Type Cooling Mode
Manufacturing Source Shanghai, China
Compressor Type Two Stage, Back-to-Back with Magnetic Bearings
Economizer Economizer
Isolation Valve Installed

Configuration Cooler Condenser


Size 21N 21N
Waterbox Type Nozzle-in-Head, 150 psi (Standard) Nozzle-in-Head, 150 psi (Standard)
Passes 2 2
Nozzle Arrangement C - 2 Pass, Inlet on 2nd Stage End R - 2 Pass, Inlet on 2nd Stage End
Tubing Super B5 ¾´OD(SUPB5), .025 in., Copper(Opt ) Spike 3 (SPK3) , .025 in., Copper(Std)
Fluid Type Fresh Water Fresh Water
Fouling Factor 0.000100 h·ft2·°F/Btu 0.000250 h·ft2·°F/Btu
Tube Quantity 309 361

Compressor
Size 259
Weights
Total Rigging Weight 12222 lb
Total Operating Weight 15034 lb
Refrigerant Weight 1240 lb
Motor and Starter
Motor Size J3H
Line Voltage-Phase-Hertz 400-3-50
VFD Code -
VFD Size DD480

Applied Chillers Asia Builder Version 2.19.0.0 Page 1 of 3


Performance Report
TH Selborn 2024 - 330
Carrier China Sales Office
Date: 10/09/2024 11:39 PM Prepared By: PACK PING HENG

Load Line
Load Line Unit Percent Load
Operating Mode Mechanical Cooling

Chiller
Percent Load 100.00 90.00 80.00 70.00 60.00 50.00 40.00 30.00 20.00 10.00
Capacity WRQߢ 300.0 270.0 240.0 210.0 180.0 150.0 120.0 90.00 60.00 30.00
Input kW kW 172.7 150.0 131.6 114.9 101.5 89.71 80.01 68.53 55.56 38.13
Cooling kW/tonR N:WRQߢ 0.5756 0.5556 0.5482 0.5469 0.5641 0.5981 0.6668 0.7614 0.9261 1.271
IPLV.IP kW/Ton 0.3349 NA NA NA NA NA NA NA NA NA
,3/9,3&23ߢ W/W 10.50 NA NA NA NA NA NA NA NA NA
NPLV.IP kW/Ton 0.3382 NA NA NA NA NA NA NA NA NA
13/9,3&23ߢ W/W 10.40 NA NA NA NA NA NA NA NA NA
Cooler
Entering Temperature °F 54.00 53.00 52.00 51.00 50.00 49.00 48.00 47.00 46.00 45.00
Leaving Temperature °F 44.00 44.00 44.00 44.00 44.00 44.00 44.00 44.00 44.00 44.00
Flow Rate gpm 717.6 717.6 717.6 717.6 717.6 717.6 717.6 717.6 717.6 717.6
Pressure Drop ft HརO 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1
Condenser
Heat Rejection MBtu/h 4.188 3.751 3.328 2.911 2.505 2.105 1.712 1.313 0.9084 0.4889
Leaving Temperature °F 96.36 95.38 94.43 93.50 92.60 91.70 90.82 89.93 89.03 88.09
Entering Temperature °F 87.00 87.00 87.00 87.00 87.00 87.00 87.00 87.00 87.00 87.00
Flow Rate gpm 900.0 900.0 900.0 900.0 900.0 900.0 900.0 900.0 900.0 900.0
Pressure Drop ft HརO 11.6 11.6 11.6 11.7 11.7 11.7 11.7 11.7 11.7 11.7
Motor and Starter
Motor Amps 304 270 242 215 196 179 165 148 123 101
Motor OLTA 328 NA NA NA NA NA NA NA NA NA
Chiller line Amps 279 248 224 207 192 177 164 148 127 97
Chiller Inrush Amps 279 NA NA NA NA NA NA NA NA NA
Max Fuse/ CB Amps 600 NA NA NA NA NA NA NA NA NA
Min Circuit Ampacity 350 NA NA NA NA NA NA NA NA NA
Heat Exchangers
Condensing Temp °F 98.0 96.8 95.6 94.5 93.5 92.4 91.4 90.4 89.4 88.3
Cooler Wall Temp °F 43.3 43.4 43.4 43.5 43.6 43.6 43.7 43.8 43.8 43.9
Suction Temp °F 43.0 43.1 43.2 43.4 43.5 43.5 43.6 43.7 43.8 43.8
Cooler Freeze Temp °F 34.0 34.0 34.0 34.0 34.0 34.0 34.0 34.0 34.0 34.0
Cooler Tube Vel ft/s 4.52 4.52 4.52 4.52 4.52 4.52 4.52 4.52 4.52 4.52
Cond Tube Vel ft/s 5.11 5.11 5.11 5.11 5.11 5.11 5.11 5.11 5.11 5.11

Applied Chillers Asia Builder Version 2.19.0.0 Page 2 of 3


Performance Report
TH Selborn 2024 - 330
Carrier China Sales Office
Date: 10/09/2024 11:39 PM Prepared By: PACK PING HENG

Certified in accordance with the AHRI Water-Cooled Water-Chilling and Heat Pump Water-Heating Packages
Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI).
Certified units may be found in the AHRI Directory at www.ahridirectory.org

http://www.ahridirectory.org

Applied Chillers Asia Builder Version 2.19.0.0 Page 3 of 3