Renaissance Middle School Control Submittal 05-20-2022
Renaissance Middle School Control Submittal 05-20-2022
Renaissance Middle School Control Submittal 05-20-2022
PH DAT
MOUNTED ON PANEL FACE
CONTROL VALVE, 2-WAY PREHEAT COIL DUCT MOUNTED TEMPERATURE
MOUNTED INSIDE PANEL C SENSOR
CONTROL VALVE, 3-WAY
3 CONTROL TUBE #3 C
PARALLEL BLADED DAMPER
PNEUMATIC TUBING COOLING COIL IS
OPPOSED BLADED DAMPER C
WIRING IMMERSION TYPE
RH TEMPERATURE SENSOR
6 TERMINAL BLOCK #6 AB SIGNAL LINE INSIDE PANEL
REHEAT COIL
SV C
DSD
SOLENOID VALVE H DUCT MOUNTED
SMOKE DETECTOR
HEATING COIL
C SPT
ABBREVIATIONS: STATIC PRESSURE
H L TRANSMITTER
DIRECT EXPANSION COIL
AFMS- AIR FLOW MEASURING STATION OA -OUTSIDE AIR
C- COMMON PORT OL'S- MOTOR STARTER OVERLOADS
SP
CCP- CENTRAL CONTROL PANEL PC- PRESSURE CONTROLLER STEAM PRESSURE SENSOR
FAN
CR- CONTROL RELAY PE- PRESSURE TOGGLE SWITCH
CS- CURRENT SWITCH PI- PRESSURE INDICATOR
DA-DAMPER ACTUATOR PL- PILOT LIGHT
MANUAL VALVE HUM
DPRO- DAMPER OUTPUT PR- PNEUMATIC RELAY DUCT MOUNTED
DPRS- DAMPER STATUS HUMIDITY SENSOR
PT- PRESSURE TRANSMITTER
DPS- DIFFERENTIAL PRESSURE SWITCH RC- RECEIVER CONTROLLER
DPT- DIFFERENTIAL PRESSURE TRANS RR- REVERSING RELAY ZONE CO2 SENSOR
EA- EXHAUST AIR RT- ROOM THERMOSTAT
ES- END SWITCH, POSITION SWITCH S- SWITCH
FS- FLOW SWITCH SD- SMOKE DETECTOR SPACE TEMPERATURE
FM
FSD- FIRE & SMOKE DAMPER S/W- SUMMER/ WINTER SIGNAL WATER FLOW METER
H- HUMIDISTAT T- THERMOSTAT
HC- MOTOR STARTER HOLDING COIL TS- TEMPERATURE SENSOR
HI- HUMIDITY INDICATOR TC- TIME CLOCK MAT
HL- HIGH LIMIT HUMIDISTAT TDR- TIME DELAY RELAY AVERAGING TYPE
OUTSIDE AIR CO2 SENSOR
HS- HIGH SIGNAL SELECTOR TEMPERATURE SENSOR
THL- TEMPERATURE HIGH LIMIT THERMOSTAT
HT- HUMIDITY TRANSMITTER TI- TEMPERATURE INDICATOR
LCP- LOCAL CONTROL PANEL TLL- TEMPERATURE LOW LIMIT THERMOSTAT
LS- LOW SIGNAL SELECTOR TR- TRANSDUCER
MA- MIXED AIR TT- TEMPERATURE TRANSMITTER FILTER AIR FLOW MEASURING STATION
MOD-MOTER OPERATED DAMPER TX- TRANSFORMER
NC- NORMALLY CLOSED V- VALVE
NCP- NETWORK CONTROL PANEL WB- WET BULB
NO- NORMALLY OPEN FIRE & SMOKE DAMPER
WU- WARM-UP SIGNAL
(BY OTHERS) CR-1
C
CONTROL RELAY
OAT
OUTSIDE AIR TEMPERATURE SENSOR
CS
CURRENT SENSOR
WIRING LEGEND
CAT5e Cable
CP-5
EOL
PUB6438SR
2ND FLOOR
CP-4 CP-3
1ST FLOOR
CP-1 CP-2
MS/TP TRUNK-1
WEB-8000
Module: 8000
TO DISTRICT IP Address: x.x.x.x
SERVER Subnet: 255.255.255.0
Gateway: 0.0.0.0
Device Instance:200000
Location: BOILER ROOM
GROUND FLOOR
FTR-1
UV-2
UV-3
UV-1
UV-4
HWS
AHU
AHU AHU
TRV-13 TRV-14
TRV-10 TRV-2
TRV-7 TRV-3
TRV-6
TRV-9
RWF-1
RWF-3 RWF-4
TRV-8
FTR-4 FTR-3 FTR-2 TRV-1
FTR-8 FTR-7
HWP-1
OA-T
OUTSIDE TEMPERATURE SENSOR
UI-5 C1
CS-1
AO-1
T3
T4
C1 UI-3
T+ UI-1
X
T- C1 2 1 3 DO-1 T
S/S
X
C1
*INSTALL SENSOR TO
HWS
THE NORTH SIDE OF LPS STARTER TS-1
V-#
OUTSIDE WALL HX-1 PANEL
CONDENSATE
UI-6
CS-2
SIO1
X
DO-2
S/S
X
C1
C1
STARTER
UI-4
PANEL
T
UI-2
C1 HWR
TS-2
SP
LPS TO
BUILDING
EQUIPMENTS
BLR-1 BLR-2
LPS LPS
X X
DI-1 X DO-3 DI-2 X DO-4
STS
STS
S/S
S/S
X X
C1 X C1 C1 X C1
DI-3 X DI-4 X
ALM
ALM
C1 X C1 X
BOILER-1 BOILER-2
PANEL PANEL
120 VAC
BY OTHERS 24VAC 24VAC
OUTPUT OUTPUT
CP-1 ø N
1 2 3 4 5 6 7 8 9
PSH-1 TR-1
H 24VAC
H N T1 T2 T3 T4 H T3
N
N COM
T4
COM
T2
24 VAC
T1
JACE-1
T1
24VAC/DC
WLAN
T2
-
ACC
24V DC
OFF
CLT
+
END
BIA
MID
DATA BUS SHIELDS: CONNECT TO
NS-1 THE ‘S’ TERMINAL AND GROUND
A-
BACNET MS/TP TO
RS485-A
WEB-8000
A+ FIELD CONTROLLERS
SH
PRI
B-
BACNET MS/TP TO
FIELD CONTROLLERS
RS485-B
B+
SH
SEC
FROM OWNER’S END
BIA
IT INFRASTRUCTURE MID
CP-1
C1
CS-2 42
HWP-2 STATUS
41 C4
CS-2
CS-1 40 40 UI-6 COM 20
HWP-1 STATUS
39 C4 C4 39 COM DO-8 19
38 CS-1
TS-2 38 UI-5 DO-7 18
T
S/S
34 C BLR-2 S/S
DO-5 15 WHT/BLU YEL
X PANEL
VOUT BLR-2 START/STOP
SP-1 SP-1 16
SP
COM 33 C2 34 UI-2
STEAM PRESSURE SENSOR COM 14 C5
V+
32 DC+ C2 BLR-2 S/S WHT/YEL
33 COM C5 15 FR-3 ORG
X
DO-4 13 BOILER BLR-1 S/S
S/S
C
WHT/BLU YEL PANEL BLR-1 START/STOP
OAT X
31 C2 32 UI-1 BLR-1 S/S 14
OAT DO-3 12
OUTSIDE AIR TEMPERATURE
30
DC+ 31 20VDC COM 11 C4 WHT/YEL FR-2 ORG
C4 13 X PUMP HWP-2 S/S
S/S
C
BLR-2 ALM HWP-2 S/S WHT/BLU YEL PANEL HWP-2 START/STOP
X 29 X
ALM
PUB6438S
28 C1 BLR-1 ALM HWP-1 S/S
Enhanced
Spyder™
29 DI-3 DO-1 9
WHT/YEL FR-1 ORG
27 C4 11 X PUMP HWP-1 S/S
S/S
BLR-1 ALM X
ALM
BOILER C
Sylk™
C1 28 COM WHT/BLU YEL PANEL HWP-1 START/STOP
BOILER-1 ALARM PANEL X X
26 C1 10
BLR-2 STS
27 DI-2
BLR-2 STS X 25 FROM
STS
BOILER
BOILER-2 STATUS PANEL X BLR-1 STS PREVIOUS
24 C1 26 DI-1
BACNET
BAC- 8
23 DEVICE
X
STS
24VAC 1 T3
D. ALARMS SHALL BE PROVIDED AS FOLLOWS, ONLY WHEN THE HEATING SYSTEM IS ENABLED:
1.LOW STEAM PRESSURE – IF LESS THAN 2 PSI (ADJUSTABLE) FOR MORE THAN 30 MINUTES.
1.2 HEATING HOT WATER SYSTEM STEAM TO HOT WATER HEAT EXCHANGER:
A.THE HEATING HOT WATER SYSTEM CONSISTS OF A STEAM TO HOT WATER SHELL AND TUBE HEAT EXCHANGER WITH STEAM CONTROL VALVE AND HOT WATER CIRCULATION PUMPS.
* REUSE EXISTING SENSORS & END DEVICES WHEREVER POSSIBLE. EXISTING PIPE LINE SIZES ARE NOT AVAILABLE. FIELD TO COORDINATE THE LENGTH OF THE PROBE FOR IMMERSION SENSORS PRIOR TO ORDERING NEW.
CP-1
CP-1 1"
END
END
SH
SH
MID
MID
A+
B+
BIA
BIA
A-
B-
- +
24VAC/DC 24V DC RS485-A RS485-B
42
41
40
39
4.5"
38
WEB-8000
PRI SEC
ACC
OFF
CLT
WLAN
7"
1"
21 AO-1
22 COM
23 AO-2
24 AO-3
25 COM
26 DI-1
27 DI-2
28 COM
29 DI-3
30 DI-4
31 20VDC
32 UI-1
33 COM
34 UI-2
35 UI-3
36 COM
37 UI-4
38 UI-5
39 COM
40 UI-6
24" 22" 1" 1.5"
1"
5.5"
Spyder™
PUB6438S
Sylk™
Enhanced
SBUS1
SBUS2
24VAC
24VAC
EGND
SHLD
BAC+
BAC-
DO-1
DO-2 10
DO-3 12
DO-4 13
DO-5 15
DO-6 16
DO-7 18
DO-8 19
COM
COM 11
COM 14
COM 17
COM 20
1
2
3
4
5
6
7
8
9
7"
1"
13
12
3" 11
10
9
PSH 8
NS-1 7
4.5"
6
TR-1 5
4"
4
3
2 120VAC
1 N
ø (BY
OTHERS)
5.2"
2"
24" 22"
NOTES :
1. PANEL LAYOUTS ARE NOT TO THE SCALE.
UI-2 SEN+
C1 SEN-
UI-1 SET
C1 SET
ZN-T
ZONE TEMPERATURE SENSOR
AO-2
T1
T2
C1
FOR INTERLOCK. C1
DI-2
UI-3
3
2
1
FILTER STEAM COIL FRZ SUPPLY FAN DAT
OUTSIDE SUPPLY
NC
AIR AIR
C
OAD DI-1
X T1 C1
V-# X T2
X
X
AO-1 C1
S/S
X
DO-1
STARTER
COND. LPS PANEL
AHU SCHEDULE
ITEM# TAG FLOOR LOCATION
1 AHU GROUND FLOOR G-14 MECH
24 VAC
H N H T1
T2
T1 N COM
T2
C1
40 UI-6 COM 20
39 COM DO-8 19
38 UI-5 DO-7 18
37 UI-4
COM 17
DAT 28 C3
PUB6438S
DAT
SFTY
DO-3 12 C
FAN PANEL
23 C2 WHT/BLU YEL SF SAFETY
X
9
31 20VDC COM 11 C4
SF SFTY
30 DI-4 DO-2 10 WHT/YEL FR-1 ORG
C4 8 X SF- S/S
S/S
PUB6438S
22 WHT/BLU
C
YEL FAN PANEL
SF S/S
Enhanced
X SF START/STOP
Spyder™
29 DI-3 DO-1 9
FRZ
FRZ STAT 7
21 C1
FREEZESTAT ALARM
Sylk™
C1 28 COM
20 T1
FRZ STAT
19 27 DI-2
FROM
CS-1 26 DI-1 PREVIOUS
18 C1 BACNET
CS-1 BAC- 8 DEVICE
SUPPLY FAN STATUS 17 25 COM
BAC+ 7 TO NEXT
BACNET
24 AO-3 DEVICE
3 16 SBUS2 6
ECON DMPR CTRL ECON DMPR CTRL
2 23 AO-2
ECON DAMPER CONTROL 15 T2
1 SBUS1 5
14 22 COM
SHLD 4
STM VLV CTRL
21 AO-1
EGND 3
13
x 24VAC T2
12 T2 COM 2
STM VLV CTRL
x
STEAM VALVE CONTROL
x 11 24VAC 1 T1
NOTES :
1. VERIFY AND REUSE EXISTING FREEZSTAT INTERLOCK
WIRING, IF FOUND IN WORKING CONDITION.
A. SCHEDULING: THE SCHEDULE WILL BE COMMUNICATED TO THE UNIT’S BACNET MS/TP DDC CONTROLLER AS ESTABLISHED IN THE GUI. THE UNIT WILL REMAIN IN THE “UNOCCUPIED” MODE UNTIL THE
SUPPLY FAN CURRENT SWITCH (SFCS) HAS PROVEN THE SUPPLY FAN “ON”.
B. SPACE TEMPERATURE SENSOR (RMT):
THE SPACE TEMPERATURE SENSOR (RMT) WILL HAVE A LOCALLY ADJUSTABLE HEATING SETPOINT WITH AN OVERRIDE PUSHBUTTON; WHEN THE BUTTON IS DEPRESSED, THE LED WILL LIGHT & THE UNIT WILL BE
SCHEDULED INTO THE “OCCUPIED” MODE FOR UP TO 3 HOURS (ADJ.); UPON THE EXPIRATION OF THE OVERRIDE, THE UNIT WILL REVERT TO ITS SCHEDULED MODE. THE SPACE HEATING (HSP/UHSP)WILL BE CONTROLLED
FROM THE GUI. THE SETPOINTS WILL BE INITIALLY SET AT 72 °F (ADJ.) FOR HEATING (HSP) WITH A SETPOINT ADJUSTMENT SPAN SETTING OF ± 4 °F (ADJ.).
C. “UNOCCUPIED” MODE:
WHEN THE UNIT IS SCHEDULED IN THE “UNOCCUPIED” MODE; THE UNIT’S SUPPLY FAN (SFSS), THE OUTSIDE DAMPERS (OAD) WILL BE “CLOSED”; WHEN THE OUTSIDE AIR TEMPERATURE (OAT) IS > 45 °F, THE STEAM
CONTROL VALVE BE “CLOSED” TO THE COIL. WHEN THE OUTSIDE AIR TEMPERATURE (OAT) IS < 48 °F, THE STEAM CONTROL VALVE WILL MODULATE TO MAINTAIN A DISCHARGE AIR SETPOINT (DASP) OF 85 °F.
D. “UNOCCUPIED COOLING” MODE: NONE
E. “UNOCCUPIED HEATING” MODE:
WHEN ANY SPACE TEMPERATURE SENSOR (RMT) IS < THE “UNOCCUPIED HEATING” SETPOINT (UHSP) OF 60 °F (ADJ.), THE UNIT’S SUPPLY FAN (SFSS) WILL BE COMMANDED “ON”. WHEN THE SPACE TEMPERATURE (RMT)
IS > THE “UNOCCUPIED HEATING” SETPOINT (UHSP) HYSTERESIS, THE UNIT’S SUPPLY FAN (SFSS) WILL BE COMMANDED “OFF”.
F. “OCCUPIED” MODE:
WHEN THE UNIT IS SCHEDULED IN THE “OCCUPIED” MODE THE UNIT SUPPLY FAN (SFSS) WILL BE COMMANDED “ON” & RUN CONTINUOUSLY. THE OUTSIDE AIR (OAD) DAMPER WILL “OPEN” TO THE MINIMUM OUTSIDE AIR
SETTING (ADJ.) (OAMINSP). UPON THE TRANSITION OF THE UNIT TO “OCCUPIED” MODE, A 10 MINUTE RAMP WILL BE IMPLEMENTED BEFORE THE OUTSIDE DAMPERS (OAD) CAN GO FULLY OPEN.
G. “MORNING WARM-UP” MODE:
THE UNIT WILL BE PLACED IN “WARM-UP” MODE WHEN THE SPACE TEMPERATURE (RMT) IS > 5 °F (ADJ.) BELOW THE SPACE HEATING SETPOINT (HSP). WHEN THE UNIT IS PLACED IN WARM-UP MODE THE OUTSIDE AIR
(OAD) DAMPERS WILL BE “CLOSED”. THE STEAM CONTROL VALVE WILL BE MODULATED “OPEN” TO THE COIL TO MAINTAIN A DISCHARGE AIR SETPOINT (DASP) OF 85 °F (ADJ.). THE UNIT WILL BE RELEASED FROM
“WARM-UP” MODE WHEN THE SPACE TEMPERATURE (RMT) IS < 2 °F (ADJ.) BELOW THE SPACE HEATING SETPOINT (HSP). WHEN THE UNIT IS RELEASED FROM WARM-UP MODE THE OUTSIDE AIR (OAD), THE STEAM
CONTROL VALVE WILL REVERT TO THEIR SCHEDULED MODE.
H. MINIMUM OUTSIDE AIR CONTROL:
THE TESTING & BALANCING CONTRACTOR (TAB) WILL ADJUST & SET THE OUTSIDE AIR MINIMUM SETTING (OAMINSP). THE OUTSIDE AIR (OAD) DAMPERS WILL POSITION ACCORDING TO THE SEQUENCE OF OPERATIONS.
I. “HEATING” MODE:
THE STEAM CONTROL VALVE WILL MODULATE TO MAINTAIN THE SPACE TEMPERATURE (RMT) AT OR ABOVE THE SPACE HEATING SETPOINT (HSP). WHEN THE SPACE TEMPERATURE (RMT) IS < THE SPACE TEMPERATURE
(HSP) HEATING SETPOINT THE STEAM CONTROL VALVE WILL MODULATE “OPEN” TO THE COIL. WHEN THE SPACE TEMPERATURE (RMT) IS> THE SPACE HEATING SETPOINT (HSP) THE STEAM CONTROL VALVE WILL
MODULATE “CLOSED” TO THE COIL.
J. DISCHARGE AIR TEMPERATURE LOW-LIMIT:
THE STEAM CONTROL VALVE MODULATE TO MAINTAIN THE DISCHARGE AIR TEMPERATURE (DAT) AT OR ABOVE THE DISCHARGE AIR LOW LIMIT (DALL) OF 60 °F (ADJ.). WHEN THE DISCHARGE AIR TEMPERATURE (DAT)
FAILS TO INCREASE ABOVE 60 °F AFTER THE STEAM CONTROL VALVE IS FULLY OPEN, THE OUTSIDE DAMPER (OAD) WILL BE MODULATED “CLOSED” & AN ALARM WILL BE GENERATED. (DATLO).
K. ALARMS & SAFETIES MONITORING:
1. FAN FAILURE (FANFAIL): COMMANDED ON, BUT THE STATUS (CS) IS “OFF”.
2. FAN IN HAND (FANHAND): COMMANDED OFF, BUT THE STATUS (CS) IS ON.
3. HI/LOW SPACE AIR TEMP: WHEN THE SPACE TEMPERATURE (RMT) IS > 85 °F (ADJ.) < 55 °F (ADJ.).
4. HI/LOW DISCHARGE AIR TEMP: WHEN THE DISCHARGE AIR TEMPERATURE (DAT) IS > 120 °F (ADJ.) < 50 °F (ADJ.).
5. LOW TEMPERATURE LIMIT SWITCH (LLSTRIP): WHEN THE SENSOR TRIPS, UPON THE TEMPERATURE BELOW THE SETTING.
6. HEATING FAILURE: (HEATFAIL) AN ALARM WILL BE GENERATED WHEN THE DISCHARGE AIR TEMPERATURE (DAT) REMAINS WITHIN 4°F (ADJ.) OF THE HEATING SETPOINT (HSP) & THE HEATING SIGNAL
IS > 10% “OPEN” (FOR > 5 MINUTES) THIS ALARM WILL NOT BE ENABLED UNTIL THE ZONE HAS BEEN “ON” FOR 10 MINUTES (ADJ.).
* REUSE EXISTING SENSORS & END DEVICES WHEREVER POSSIBLE. EXISTING UNIT DUCT SIZES ARE NOT AVAILABLE. FIELD TO COORDINATE THE LENGTH FOR FREEZSTAT, MAT, DAT & RAT PRIOR TO ORDERING NEW.
CP-2
CP-2
1"
24
23
21 AO-1
22 COM
23 AO-2
24 AO-3
25 COM
26 DI-1
27 DI-2
28 COM
29 DI-3
30 DI-4
31 20VDC
32 UI-1
33 COM
34 UI-2
35 UI-3
36 COM
37 UI-4
38 UI-5
39 COM
40 UI-6
22
21
5.5"
Spyder™
PUB6438S
Sylk™
Enhanced
SBUS1
SBUS2
24VAC
24VAC
EGND
SHLD
BAC+
BAC-
DO-1
DO-2 10
DO-3 12
DO-4 13
DO-5 15
DO-6 16
DO-7 18
DO-8 19
COM
COM 11
COM 14
COM 17
COM 20
1
2
3
4
5
6
7
8
9
7"
3"
TR-1
4" 10
9
8
7
6
5 PANEL
GROUND
4
3
2 N 120VAC
1
ø (BY OTHERS)
2"
18"
20"
NOTES :
1. PANEL LAYOUTS ARE NOT TO THE SCALE.
*NOTE-1
SYLK
SYLK
ZN-T/CO2
ZONE TEMPERATURE & CO2
C1 SENSOR
UI-4
RAT
RETURN
AIR
T1 2
T2 1 RAD
AO-2 3 C1
NO FOR INTERLOCK.
C1 C1 DI-2 C1
UI-2 UI-1 UI-3
OAT FILTER MAT STEAM COIL FRZ SUPPLY FAN DAT
OUTSIDE SUPPLY
NC
AIR AIR TO GYM
C
OAD DI-1
X T1 C1
V-# X T2
X
X
AO-1 C1
S/S
X
DO-1
STARTER
COND. LPS PANEL
AHU SCHEDULE
ITEM# TAG FLOOR LOCATION
1 AHU FIRST FLOOR 158-STORAGE
2 AHU FIRST FLOOR 156-STORAGE
NOTE:-
1. BOTH AHU SERVING SAME ZONES, SHARES COMMON ZONE TEMP & CO2 SENSOR.
1 2 3 4 5 6
TR-1
24 VAC
H N H T1
T2
T1 N COM
T2
C1
40 UI-6 COM 20
39 COM DO-8 19
RAT 30 C3
RAT
RETURN AIR
29 38 UI-5 DO-7 18
TEMPERATURE
RAT
37 UI-4
COM 17
DAT 28 C3
PUB6438S
DAT
OAT 34 UI-2
OUTSIDE AIR TEMPERATURE COM 14
25 C2
C2 33 COM
DO-4 13
24 MAT
MAT
SFTY
MIXED AIR TEMPERATURE DO-3 12 C
FAN PANEL
23 C2 WHT/BLU YEL SF SAFETY
X
9
31 20VDC COM 11 C4
SF SFTY
30 DI-4 DO-2 10 WHT/YEL FR-1 ORG
C4 8 X SF- S/S
S/S
PUB6438S
22 WHT/BLU
C
YEL FAN PANEL
SF S/S
Enhanced
X SF START/STOP
Spyder™
29 DI-3 DO-1 9
FRZ
FRZ STAT 7
21 C1
FREEZESTAT ALARM
Sylk™
C1 28 COM
20 T1
FRZ STAT
19 27 DI-2
FROM
CS-1 26 DI-1 PREVIOUS
18 C1 BACNET
CS-1 BAC- 8 DEVICE
SUPPLY FAN STATUS 17 25 COM
BAC+ 7 TO NEXT *NOTE-2
BACNET
24 AO-3 DEVICE
3 16 SBUS2 6
ECON DMPR CTRL ECON DMPR CTRL
1 23 AO-2
ECON DAMPER CONTROL 15 T2
2 SBUS1 5
14 22 COM
SHLD 4 ZN-T/CO2
STM VLV CTRL
21 AO-1
ZONE TEMPERATURE &
EGND 3 CO2 SENSOR
13
X 24VAC T2
12 T2 COM 2
STM VLV CTRL
X
STEAM VALVE CONTROL
X 11 24VAC 1 T1
NOTES :
1. VERIFY AND REUSE EXISTING FREEZSTAT INTERLOCK WIRING, IF FOUND
IN WORKING CONDITION.
2. ZN-T/CO2 APPLICABLE FOR ONLY ONE AHU, AS BOTH AHU SERVING SAME
ZONES, SHARES COMMON ZONE TEMP & CO2 SENSOR.
A. SCHEDULING: THE SCHEDULE WILL BE COMMUNICATED TO THE UNIT’S BACNET MS/TP DDC CONTROLLER AS ESTABLISHED IN THE GUI. THE UNIT WILL REMAIN IN THE “UNOCCUPIED” MODE UNTIL THE
SUPPLY FAN CURRENT SWITCH (SFCS) HAS PROVEN THE SUPPLY FAN “ON”.
B. SPACE TEMPERATURE SENSOR (RMT):
THE SPACE TEMPERATURE SENSOR (RMT) WILL HAVE A LOCALLY ADJUSTABLE HEATING SETPOINT WITH AN OVERRIDE PUSHBUTTON; WHEN THE BUTTON IS DEPRESSED, THE LED WILL LIGHT & THE UNIT WILL BE
SCHEDULED INTO THE “OCCUPIED” MODE FOR UP TO 3 HOURS (ADJ.); UPON THE EXPIRATION OF THE OVERRIDE, THE UNIT WILL REVERT TO ITS SCHEDULED MODE. THE SPACE HEATING (HSP/UHSP)WILL BE CONTROLLED
FROM THE GUI. THE SETPOINTS WILL BE INITIALLY SET AT 72 °F (ADJ.) FOR HEATING (HSP) WITH A SETPOINT ADJUSTMENT SPAN SETTING OF ± 4 °F (ADJ.).
C. “UNOCCUPIED” MODE:
WHEN THE UNIT IS SCHEDULED IN THE “UNOCCUPIED” MODE; THE UNIT’S SUPPLY FAN (SFSS), AND ANY ASSOCIATED EXHAUST FANS (EFSS) WILL BE COMMANDED “OFF”; THE OUTSIDE DAMPERS (OAD) WILL BE
“CLOSED” & THE RETURN DAMPER (RAD) WILL BE OPEN; WHEN THE OUTSIDE AIR TEMPERATURE (OAT) IS > 45 °F, THE STEAM CONTROL VALVE BE “CLOSED” TO THE COIL. WHEN THE OUTSIDE AIR TEMPERATURE (OAT) IS
< 48 °F, THE STEAM CONTROL VALVE WILL MODULATE TO MAINTAIN A DISCHARGE AIR SETPOINT (DASP) OF 85 °F.
D. “UNOCCUPIED COOLING” MODE: NONE
E. “UNOCCUPIED HEATING” MODE:
WHEN ANY SPACE TEMPERATURE SENSOR (RMT) IS < THE “UNOCCUPIED HEATING” SETPOINT (UHSP) OF 60 °F (ADJ.), THE UNIT’S SUPPLY FAN (SFSS) WILL BE COMMANDED “ON”. ANY ASSOCIATED EXHAUST FANS (EFSS)
WILL REMAIN “OFF”. WHEN THE SPACE TEMPERATURE (RMT) IS > THE “UNOCCUPIED HEATING” SETPOINT (UHSP) HYSTERESIS, THE UNIT’S SUPPLY FAN (SFSS) WILL BE COMMANDED “OFF”.
F. “OCCUPIED” MODE:
WHEN THE UNIT IS SCHEDULED IN THE “OCCUPIED” MODE THE UNIT SUPPLY FAN (SFSS) AND ANY ASSOCIATED EXHAUST FANS (EFSS) WILL BE COMMANDED “ON” & RUN CONTINUOUSLY. THE OUTSIDE AIR (OAD),
EXHAUST AIR (EAD) & RETURN AIR (RAD) DAMPERS WILL “OPEN” TO THE MINIMUM OUTSIDE AIR SETTING (ADJ.) (OAMINSP). UPON THE TRANSITION OF THE UNIT TO “OCCUPIED” MODE, A 10 MINUTE RAMP WILL BE
IMPLEMENTED BEFORE THE OUTSIDE DAMPERS (OAD) CAN GO FULLY OPEN.
G. “MORNING WARM-UP” MODE:
THE UNIT WILL BE PLACED IN “WARM-UP” MODE WHEN THE SPACE TEMPERATURE (RMT) IS > 5 °F (ADJ.) BELOW THE SPACE HEATING SETPOINT (HSP) OR THE RETURN AIR TEMPERATURE (RAT) IS < THE “WARM-UP”
SETPOINT (WUSP) OF 66 °F (ADJ.) (WUSP). WHEN THE UNIT IS PLACED IN WARM-UP MODE ALL ASSOCIATED EXHAUST FANS (EFSS) WILL BE COMMANDED “OFF”; THE OUTSIDE AIR (OAD) & EXHAUST AIR (EAD) DAMPERS
WILL BE “CLOSED”. THE RETURN DAMPER (RAD) WILL BE OPENED, THE HOT WATER CONTROL VALVE WILL BE MODULATED “OPEN” TO THE COIL TO MAINTAIN A DISCHARGE AIR SETPOINT (DASP) OF 85 °F (ADJ.). THE
UNIT WILL BE RELEASED FROM “WARM-UP” MODE WHEN THE RETURN AIR TEMPERATURE (RAT) > THE “WARM-UP” SETPOINT (WASP) HYSTERESIS OR THE SPACE TEMPERATURE (RMT) IS < 2 °F (ADJ.) BELOW THE SPACE
HEATING SETPOINT (HSP). WHEN THE UNIT IS RELEASED FROM WARM-UP MODE THE OUTSIDE AIR (OAD), EXHAUST AIR (EAD) & RETURN AIR (RAD) DAMPERS, THE STEAM CONTROL VALVE WILL REVERT TO THEIR
SCHEDULED MODE.
H. MINIMUM OUTSIDE AIR CONTROL:
THE TESTING & BALANCING CONTRACTOR (TAB) WILL ADJUST & SET THE OUTSIDE AIR MINIMUM SETTING (OAMINSP). THE OUTSIDE AIR (OAD) & RETURN AIR (RAD) DAMPERS WILL POSITION ACCORDING TO THE
SEQUENCE OF OPERATIONS.
I. “HEATING” MODE:
THE STEAM CONTROL VALVE WILL MODULATE TO MAINTAIN THE SPACE TEMPERATURE (RMT) AT OR ABOVE THE SPACE HEATING SETPOINT (HSP). WHEN THE SPACE TEMPERATURE (RMT) IS < THE SPACE TEMPERATURE
(HSP) HEATING SETPOINT THE STEAM CONTROL VALVE WILL MODULATE “OPEN” TO THE COIL. WHEN THE SPACE TEMPERATURE (RMT) IS> THE SPACE HEATING SETPOINT (HSP) THE STEAM CONTROL VALVE WILL
MODULATE “CLOSED” TO THE COIL.
J. FREE COOLING ECONOMIZER:
WHEN THE OUTSIDE AIR TEMPERATURE (OAT) IS < THE SPACE TEMPERATURE (RMT) BY > 8 °F (ADJ.) THE USE OF THE FREE COOLING ECONOMIZER WILL BE USED TO COOL THE SPACE TEMPERATURE (RMT) AS REQUIRED.
THE OUTSIDE AIR (OAD) & RETURN AIR (RAD) DAMPERS WILL MODULATE TO MAINTAIN MIXED AIR TEMPERATURE SETPOINT (MASP) - 10°F TO THE SPACE COOLING SETPOINT (CSP). WHEN THE SPACE TEMPERATURE (RMT)
IS > THE SPACE COOLING SETPOINT (CSP) THE OUTSIDE AIR (OAD) WILL BE MODULATED OPEN; THE RETURN AIR (RAD) DAMPERS MODULATED CLOSED. WHEN THE SPACE TEMPERATURE (RMT) IS < THE SPACE COOLING
SETPOINT (CSP) THE OUTSIDE AIR (OAD) DAMPERS WILL BE MODULATED CLOSED; THE RETURN AIR (RAD) DAMPER MODULATED OPEN.
L. DISCHARGE AIR TEMPERATURE LOW-LIMIT:
THE HOT WATER CONTROL VALVE MODULATE TO MAINTAIN THE DISCHARGE AIR TEMPERATURE (DAT) AT OR ABOVE THE DISCHARGE AIR LOW LIMIT (DALL) OF 60 °F (ADJ.). WHEN THE DISCHARGE AIR TEMPERATURE
(DAT) FAILS TO INCREASE ABOVE 60 °F AFTER THE STEAM CONTROL VALVE IS FULLY OPEN, THE OUTSIDE DAMPER (OAD) WILL BE MODULATED “CLOSED” & AN ALARM WILL BE GENERATED. (DATLO).
M. DCV:
THE BMS SHALL MONITOR CO2 LEVELS. THE BMS SHALL MODULATE THE OUTSIDE AIR DAMPER FROM ITS MINIMUM OUTSIDE AIR POSITION TO THE MAXIMUM OUTSIDE AIR POSITION TO MAINTAIN CO2
CONCENTRATION SET-POINT. CONTROLLER SHALL NOT ALLOW MIXED AIR TEMPERATURE TO DROP BELOW 50°F OR GOES ABOVE 85°F DURING HIGH CO2 CONDITION.
* REUSE EXISTING SENSORS & END DEVICES WHEREVER POSSIBLE. EXISTING UNIT DUCT SIZES ARE NOT AVAILABLE. FIELD TO COORDINATE THE LENGTH FOR FREEZSTAT, MAT, DAT & RAT PRIOR TO ORDERING NEW.
UI-3 SEN+
C1 SEN-
RETURN UI-2 SET
AIR C1 SET
ZN-T
ZONE TEMPERATURE SENSOR
C1
FOR INTERLOCK. UI-1
DI-1
C1
FILTER HOT WATER COIL DX COIL SUPPLY FAN DAT
FRZ
H
OUTSIDE SUPPLY
AIR OA/RA AIR
DAMPER
C
C1 C1
X T2
3 2 1 DO-2 DI-2
V-# X T1
X *120VAC
AO-2
AO-1 WHT/YEL FR-# ORG
T1
T2
C1 N
C
BY OTHERS
WHT/BLU YEL
DO-1 L
HWS HWR
FTR-1
DO-3
C1
HWS HWR
V-#
UV SCHEDULE
ITEM# TAG FLOOR LOCATION NEARBY FTR
1 UV-1 GROUND FLOOR G6-MUSIC
2 UV-2 GROUND FLOOR G2-MULTIPURPOSE ROOM 3
3 UV-3 GROUND FLOOR G2-MULTIPURPOSE ROOM 2 FTR-1
4 UV-4 GROUND FLOOR G2-CLASSROOM
5 UV-5 GROUND FLOOR G17-CLASSROOM
6 UV-6 GROUND FLOOR G16-CLASSROOM
7 UV-7 GROUND FLOOR G10-CLASSROOM
NOTE:-
1. FOR UV-3 & FTR- 1 SERVING SAME ZONES, SHARES COMMON ZONE TEMP SENSOR.
2. FTR-1 VLV APPLICABLE FOR ONLY UV-3.
TR-1
24 VAC
H T1
N COM
T2
C1
T2
40 UI-6 COM 20
39 COM DO-8 19
38 UI-5 DO-7 18
37 UI-4
COM 17 *NOTE-5
PUB6438S
C3 36 COM WHT/YEL FR-3 BLK FTR-1 VLV CMD
DO-6 16 C5
ZNT-1 WHT/BLU
C
BLK FTR-1 VALVE
SEN- C3 35 UI-3 COMMAND
ZNT-1 DO-5 15
SEN+ T1
ZONE TEMPERATURE SENSOR ZNT-1 SP 34 UI-2
WITH SETPOINT SET COM 14 C5
T2
SET C2
C2 33 COM
DO-4 13
DAT
32 UI-1 FTR-1 CMD WHT/YEL ORG
DAT
STG
C
DISCHARGE AIR TEMPERATURE WHT/BLU YEL DX STG
C2 X DX STAGE COMMAND
31 20VDC COM 11 C4
PUB6438S
C
WHT/BLU YEL
SF S/S
Enhanced
Spyder™
SF STS 29 DI-3 DO-1 9
C1
SA FAN STATUS
Sylk™
C1 28 COM L N
SF STS
FRZ
24VAC T2
COM 2
24VAC 1 T1
NOTE:-
1. CONTROLLERS TO BE DIRECTLY INSTALLED IN UV CABINET.
2. REFER TO UV SCHEDULE FOR DETAILS OF RESPECTIVE DETAILS.
3. VERIFY AND REUSE EXISTING FREEZSTAT INTERLOCK WIRING, IF FOUND IN WORKING CONDITION.
4. FOR UV-3 & FTR- 1 SERVING SAME ZONES, SHARES COMMON ZONE TEMP SENSOR.
5. FTR-1 VLV CMD APPLICABLE FOR ONLY UV-3.
C. FREEZE PROTECTION:
THE UNIT SHALL SHUT DOWN, HOT WATER WATER VALVE WILL OPEN 100% AND GENERATE AN ALARM UPON RECEIVING A FREEZESTAT STATUS. OUTSIDE AIR DAMPER WILL CLOSE AND RETURN AIR DAMPER WILL OPEN.
E. SUPPLY FAN:
1. THE SUPPLY FAN SHALL RUN ANYTIME THE UNIT IS COMMANDED TO RUN, UNLESS SHUTDOWN ON SAFETIES. TO PREVENT SHORT CYCLING, THE SUPPLY FAN SHALL HAVE A USER DEFINABLE (ADJ.) MINIMUM RUNTIME.
2. ALARMS SHALL BE PROVIDED AS FOLLOWS:
• SUPPLY FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.
• SUPPLY FAN IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.
• SUPPLY FAN RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT (ADJ.).
* REUSE EXISTING SENSORS & END DEVICES WHEREVER POSSIBLE. EXISTING UNIT DUCT SIZES ARE NOT AVAILABLE. FIELD TO COORDINATE THE LENGTH FOR FREEZSTAT, MAT, DAT & RAT PRIOR TO ORDERING NEW.
C1 SEN-
UI-# SEN+
C1 SET
UI-# SET
FTR-# ZN-T
ZONE TEMPERATURE SENSOR
FTR-#
DO-#
C1
LPS COND
V-#
RADIATOR SCHEDULE
ITEM# TAG FLOOR LOCATION NEARBY UV/RAD TYPE
1 FTR-1 GROUND FLOOR G5 MULTIPURPOSE ROOM UV-3
2 FTR-2 FIRST FLOOR 107 TEACHERS LOUNGE
3 FTR-3 FIRST FLOOR 106 MAIN OFFICE
4 FTR-4 FIRST FLOOR 103 PRINCIPAL TYPE-1
5 FTR-5 FIRST FLOOR 111 CLASSROOM
6 FTR-6 FIRST FLOOR 115 NURSE
7 FTR-7 SECOND FLOOR 205 GUIDANCE
TYPE-2
8 FTR-8 SECOND FLOOR 215 RESOURCE
NOTE:-
1. FOR FTR-1 REFER UV-3 WIRING DETAILS.
C1 SEN-
UI-# SEN+
C1 SET
UI-# SET
RWF-# ZN-T
ZONE TEMPERATURE SENSOR
BLK
BLK
LPS
NO
COND
ORG
FR-#
DO-# WHT/YEL YEL
WHT/BLU
C PRP
C-X
BRN
L N
*120V BY OTHERS
RWF-#
120 VAC
BY OTHERS 24VAC 24VAC
CP-3 ø N OUTPUT OUTPUT
1 2 3 4 5 6 7 8 9
TR-1 TR-2
T1 T3 24 VAC 24 VAC
H N H T1 H T3
T2 T4
N COM N COM
T2 T4
T4
T3
C1 BLK
BLK RWF-1 CMD
ORG
WHT/YEL FR-6 RAD WITH FAN-1
21 YEL
WHT/BLU
C COMMAND
SEN- 33 PRP
FTR-4 ZNT FTR-4 ZNT 20
40
20
FTR-4 ZONE SEN+ UI-6 DO-B4 BRN
32 C3
TEMPERATURE SENSOR SET
39
19
31 C3 COM DO-B3 L N
SET
FTR-4 ZNT SP RWF-1 CMD *120VAC
30 C3
38
18
UI-5 DO-B2 BY OTHERS
37
17
UI-4 DO-B1
FTR-3 ZNT
SEN- 29 PUB6438SR FTR-5 CMD
36
C2
16
FTR-3 ZONE SEN+ COM DO-A3 19 WHT/YEL BLK FTR-6 VLV CMD
28 C2 FR-5 ORG
TEMPERATURE SENSOR SET C FTR-6 VALVE
FTR-3 ZNT SP FTR-4 CMD 18 WHT/BLU YEL BLK
35
15
SET 27 UI-3 DO-A2 COMMAND
34
14
UI-2 DO-A1 17 WHT/YEL FR-4 ORG BLK
C
FTR-5 VLV CMD
FTR-2 CMD WHT/BLU YEL BLK FTR-5 VALVE
33
16
13
C1 COM DO-C1
SEN- 25 COMMAND
FTR-2 ZNT FTR-2 ZNT SP
32
12
FTR-2 ZONE SEN+ UI-1 COM-C 15
24 C1 WHT/YEL FR-3 ORG BLK FTR-4 VLV CMD
TEMPERATURE SENSOR SET C FTR-4 VALVE
WHT/BLU YEL BLK
14
31
11
SET 23 20VDC COM-B COMMAND
C1
30
22
10
Sylk™ Enhanced
DI-4 COM-A
13 WHT/YEL FR-2 ORG BLK
C
FTR-3 VLV CMD
WHT/BLU YEL BLK
29
PUB6438SR
DI-3 24 VAC OUT T3 12 FTR-3 VALVE
9
COMMAND
Spyder™
28
COM
11 WHT/YEL FR-1 ORG BLK
C
FTR-2 VLV CMD
27
DI-2 FROM PREVIOUS 10 WHT/BLU YEL BLK
FTR-2 VALVE
BAC-
8
26 BACNET DEVICE COMMAND
DI-1
BAC+ TO NEXT
7
BACNET DEVICE
25
COM
SBUS2
6
24
5
23
AO-2
SHLD
4
22
COM
EGND
3
21
AO-1
24VAC COM T2
2
24VAC T1
1
PANEL CONTINUED ON NEXT PAGE
CP-3
SIO-1
SIO12000
FTR-6 ZNT
UI-4 12
C5 41 SEN-
FTR-6 ZNT
COM 11 C5 SEN+ FTR-6 ZONE
40
SET TEMPERATURE SENSOR
SEN- 45 FTR-6 ZNT SP
RWF-1 ZNT RWF-1 ZNT UI-3 10 C5 39 SET
SEN+ 24 UI-5
RWF-1 ZONE 44 C6
FTR-5 ZNT 38
TEMPERATURE SENSOR SET UI-2 9
23 COM
SIO12000
43 C6
SET
C4
Sylk I/O
RWF-1 ZNT SP COM 8
42 C6 22 UI-6 C4 37 SEN-
FTR-5 ZNT SP FTR-5 ZNT
UI-1 7 SEN+ FTR-5 ZONE
21 UI-7 36
SET TEMPERATURE SENSOR
7
C4 35 SET
ON
6
ADDRESSING
20 COM 5
SYLK IO
4
3
34
19 UI-8 2
1
18 UI-9 SBUS2 6
16 UI-10
15 UI-11 EGND 3
24VAC T2
14 COM COM 2
13 UI-12 24VAC 1 T1
120 VAC
BY OTHERS 24VAC 24VAC
CP-5 ø N OUTPUT OUTPUT
1 2 3 4 5 6 7 8 9
TR-1 TR-2
T4
T1 T3 24 VAC 24 VAC
H N H T1 H T3 T3
T2 T4
N COM N COM
T2 T4
BLK
ORG BLK RWF-10 CMD
WHT/YEL FR-8
25 C YEL RAD WITH FAN-10
WHT/BLU COMMAND
PRP
24
BRN
L N
C1 *120VAC BY OTHERS
BLK
ORG BLK RWF-9 CMD
WHT/YEL FR-7
23 C YEL RAD WITH FAN-9
SEN- 37 WHT/BLU COMMAND
RWF-5 ZNT RWF-5 ZNT PRP
RWF-10 CMD 22
40
20
RWF-5 ZONE SEN+ UI-6 DO-B4
36 C3 BRN
TEMPERATURE SENSOR SET
RWF-9 CMD
39
19
35 C3 COM DO-B3 L N
SET
*120VAC BY OTHERS
RWF-5 ZNT SP RWF-8 CMD
34 C3
38
18
UI-5 DO-B2 BLK
37
17
UI-4 DO-B1 21 YEL RAD WITH FAN-8
FTR-8 ZNT
SEN- 33 PUB6438SR RWF-6 CMD 20
WHT/BLU
C
PRP COMMAND
36
C2
16
FTR-8 ZONE SEN+ COM DO-A3 BRN
32 C2
TEMPERATURE SENSOR SET
FTR-8 ZNT SP RWF-5 CMD
35
15
UI-3 DO-A2 L N
SET 31
*120VAC BY OTHERS
34
14
UI-2 DO-A1 BLK
ORG BLK RWF-7 CMD
FTR-7 CMD WHT/YEL FR-5
19
33
13
C1 COM DO-C1 C YEL RAD WITH FAN-7
WHT/BLU
SEN- 29 PRP COMMAND
FTR-7 ZNT FTR-7 ZNT SP 18
32
12
FTR-7 ZONE SEN+ UI-1 COM-C BRN
28 C1
TEMPERATURE SENSOR SET L N
31
11
SET 27 20VDC COM-B
*120VAC BY OTHERS
C1 BLK
30
26
10
Sylk™ Enhanced
DI-4 COM-A
ORG BLK RWF-6 CMD
WHT/YEL FR-4
17 RAD WITH FAN-6
29
PUB6438SR
DI-3 24 VAC OUT T3 YEL
9
C
WHT/BLU COMMAND
PRP
Spyder™
28 16
COM BRN
L N
27
8
BACNET DEVICE
BLK
26
7
WHT/YEL FR-3 RAD WITH FAN-5
BACNET DEVICE 15
25
6
14
24
5
L N
23
4
22
COM
EGND
3
13 WHT/YEL FR-2 ORG BLK FTR-8 VLV CMD
FTR-8 VALVE
21
C
AO-1 WHT/BLU YEL BLK
24VAC COM T2 12 COMMAND
2
24VAC T1
1
11 WHT/YEL FR-1 ORG BLK FTR-7 VLV CMD
WHT/BLU
C
YEL BLK FTR-7 VALVE
10 COMMAND
CP-5
SIO-1
SIO12000
RWF-7 ZNT
UI-4 12
C5 45 SEN-
RWF-7 ZNT
COM 11 C5 SEN+ RWF-7 ZONE
44
SEN- 57 SET TEMPERATURE SENSOR
RWF-8 ZNT RWF-7 ZNT SP
SEN+ RWF-8 ZNT UI-3 10 C5 43 SET
RWF-8 ZONE 56 C6 24 UI-5
TEMPERATURE SENSOR SET RWF-6 ZNT
UI-2 9 42
SET 55 23 COM
SIO12000
C6
C4
Sylk I/O
54 C6 RWF-8 ZNT SP COM 8
22 UI-6 C4 41 SEN-
RWF-6 ZNT SP RWF-6 ZNT
RWF-9 ZNT UI-1 7 SEN+ RWF-6 ZONE
21 UI-7 40
53 SET TEMPERATURE SENSOR
SEN-
RWF-9 ZNT 7
C4 39 SET
ON
SEN+ 6
ADDRESSING
RWF-9 ZONE C7 C7 20 COM
52 5
SYLK IO
TEMPERATURE SENSOR SET 4
38
RWF-9 ZNT SP 3
SET 51 19 UI-8 2
1
50 C7 RWF-10 ZNT
18 UI-9 SBUS2 6
46 C8 24VAC T2
14 COM COM 2
13 UI-12 24VAC 1 T1
120 VAC
BY OTHERS 24VAC
OUTPUT
CP-4 ø N
1 2 3 4 5 6 TR-1
24 VAC
H T1
H N
T2 N COM
T2
T1
T2
C1 T1
RWF-4 ZNT
40 UI-6 COM 20 BLK
SEN- 24 ORG BLK RWF-4 CMD
RWF-4 ZNT C3 39 COM DO-8 19 WHT/YEL FR-3
C5 12 RAD WITH FAN-4
RWF-4 ZONE SEN+ WHT/BLU
C YEL
23 C3
RWF-4 ZNT SP COMMAND
TEMPERATURE SENSOR SET PRP
38 UI-5 DO-7 18 11
22 BRN
SET
RWF-3 ZNT
37 UI-4 L N
21 C3 COM 17
C2
PUB6438S *120VAC BY OTHERS
36 COM
DO-6 16 BLK
RWF-3 ZNT SP BLK RWF-3 CMD
35 UI-3 ORG
WHT/YEL FR-2
DO-5 15 C4 10 RAD WITH FAN-3
C YEL
RWF-2 ZNT WHT/BLU COMMAND
SEN- 20 34 UI-2 PRP
COM 14 C5 9
RWF-3 ZNT SEN+ BRN
RWF-3 ZONE 19 C2 C1 33 COM
SET DO-4 13 L N
TEMPERATURE SENSOR
SET 18 RWF-2 ZNT SP *120VAC BY OTHERS
32 UI-1 RWF-4 CMD
DO-3 12 BLK
17 C2
ORG BLK RWF-2 CMD
31 20VDC COM 11 C4 WHT/YEL FR-1
C4 8 C YEL RAD WITH FAN-2
WHT/BLU COMMAND
RWF-3 CMD PRP
SEN- 16 30 DI-4 DO-2 10 7
RWF-2 ZNT BRN
PUB6438S
SEN+ RWF-2 CMD
Enhanced
RWF-2 ZONE C1
Spyder™
15 29 DI-3 DO-1 9
SET L N
TEMPERATURE SENSOR
SET 14 *120VAC BY OTHERS
Sylk™
28 COM
13 C1
27 DI-2
FROM
26 DI-1 PREVIOUS
BACNET
BAC- 8 DEVICE
25 COM TO NEXT
BAC+ 7
BACNET
24 AO-3 DEVICE
SBUS2 6
23 AO-2
SBUS1 5
22 COM
SHLD 4
21 AO-1
EGND 3
24VAC T2
COM 2
24VAC 1 T1
CP-3&5
CP-3&5 1"
21 AO-1
22 COM
23 AO-2
24 AO-3
25 COM
26 DI-1
27 DI-2
28 COM
29 DI-3
30 DI-4
31 20VDC
32 UI-1
33 COM
34 UI-2
35 UI-3
36 COM
37 UI-4
38 UI-5
39 COM
40 UI-6
57
56
55
54
5.45"
53
Spyder™
PUB6438SR
Sylk™ C1
Enhanced
24VAC COM
24VAC OUT
COM A 10
COM B 11
COM C 12
24VAC
DO-A1 14
DO-A2 15
DO-A3 16
DO-B1 17
DO-B2 18
DO-B3 19
DO-B4 20
DO-C1 13
SBUS1
SBUS2
EGND
BAC+
SHLD
BAC-
1
2
3
4
5
6
7
8
9
6.85"
1"
13
14
17
16
15
18
19
20
23
22
21
24
UI-10
UI-11
UI-12
COM
COM
COM
COM
UI-5
UI-6
UI-7
UI-8
UI-9
24" 22" 1" SIO1 1.5"
1"
6.27"
SIO12000
Sylk I/O
SIO-12000
24VAC
SBUS1
SBUS2
EGND
COM
COM
COM
UI-1
UI-2
UI-3
UI-4
12
11
10
5
6
1
9
7
4.75"
1"
13
12
3" 3" 11
10
9
8
7
6
5
4
TR-1 TR-2
4"
4"
3
2 120VAC
1 N
ø (BY
OTHERS)
2"
24" 22"
NOTES :
1. PANEL LAYOUTS ARE NOT TO THE SCALE.
CP-4
CP-4
1"
24
23
21 AO-1
22 COM
23 AO-2
24 AO-3
25 COM
26 DI-1
27 DI-2
28 COM
29 DI-3
30 DI-4
31 20VDC
32 UI-1
33 COM
34 UI-2
35 UI-3
36 COM
37 UI-4
38 UI-5
39 COM
40 UI-6
22
21
5.5"
Spyder™
PUB6438S
Sylk™
Enhanced
SBUS1
SBUS2
24VAC
24VAC
EGND
SHLD
BAC+
BAC-
DO-1
DO-2 10
DO-3 12
DO-4 13
DO-5 15
DO-6 16
DO-7 18
DO-8 19
COM
COM 11
COM 14
COM 17
COM 20
1
2
3
4
5
6
7
8
9
7"
3"
TR-1
4" 10
9
8
7
6
5 PANEL
GROUND
4
3
2 N 120VAC
1
ø (BY OTHERS)
2"
18"
20"
NOTES :
1. PANEL LAYOUTS ARE NOT TO THE SCALE.
CONVECTOR-#
LPS COND.
TRV
TRV SCHEDULE
ITEM# TAG FLOOR LOCATION
1 TRV-1 FIRST FLOOR FIRST FLOOR ROOM
2 TRV-2 FIRST FLOOR 102 HALLWAY
3 TRV-3 FIRST FLOOR 102 HALLWAY
4 TRV-4 FIRST FLOOR SW3 STAIRWELL (FIRST FLOOR)
5 TRV-5 FIRST FLOOR SW2 STAIRWELL (FIRST FLOOR)
6 TRV-6 FIRST FLOOR MAIN ENTRANCE 1
7 TRV-7 FIRST FLOOR MAIN ENTRANCE 2
8 TRV-8 FIRST FLOOR FIRST FLOOR ROOM
9 TRV-9 FIRST FLOOR SW4 STAIRWELL
10 TRV-10 FIRST FLOOR SW1 STAIRWELL
11 TRV-11 FIRST FLOOR 117 OFFICE
12 TRV-12 FIRST FLOOR 118 CLASSROOM BATHROOM
13 TRV-13 FIRST FLOOR 150 MULTIPURPOSE ROOM
14 TRV-14 FIRST FLOOR 150 MULTIPURPOSE ROOM
15 TRV-15 SECOND FLOOR 213 CLASSROOM
16 TRV-16 SECOND FLOOR 206 CLASSROOM
17 TRV-17 SECOND FLOOR GT212 WOMENS RESTROOM
* REUSE EXISTING SENSORS & END DEVICES WHEREVER POSSIBLE. EXISTING UNIT DUCT SIZES ARE NOT AVAILABLE. FIELD TO COORDINATE THE LENGTH FOR FREEZSTAT, MAT, DAT & RAT PRIOR TO ORDERING NEW.