InteliMains

510
Mains supervision controller

SW version 1.1.0
1 General information 2
2 Changes in the version 1.1.0 3
3 Notes 6

Copyright © 2024 ComAp a.s.


Written by Michal Slavata
Prague, Czech Republic
ComAp a.s., U Uranie 1612/14a,
170 00 Prague 7, Czech Republic
Tel: +420 246 012 111
E-mail: info@comap-control.com, www.comap-control.com New Features List
1 General information
1.1 Version information
Major version with new functions like Universal hours counters, SNMP improvement, support of 8C and 16C
communication modes, support of power management in kVA mode and several bugfixes.
IMPORTANT: Due to the new user access management, FW version of integrated color display
(ICD) 2.3.0.8 or newer is required.

1.2 Clarification of Notation


Note: This type of paragraph calls the reader’s attention to a notice or related theme.

IMPORTANT: This type of paragraph highlights a procedure, adjustment etc., which can cause a
damage or improper function of the equipment if not performed correctly and may not be clear at
first sight.

WARNING: This type of paragraph highlights a procedure, adjustment etc., which can cause a
damage or improper function of the equipment if not performed correctly and may not be clear at
first sight.

Example: This type of paragraph contains information that is used to illustrate how a specific function
works.

InteliMains 510 1.1.0 New Features List 2


2 Changes in the version 1.1.0
2.1 New features
LBI GROUP LINK in BTB application
In case the LBI is not configured, BTB controller makes automatically Group link function between
adjusted groups through closing the BTB breaker.
In case the LBI is configured, the group link is provided when BTB breaker is closed (BTB feedback -
active) and LBI GROUP LINK is closed.
Universal hours counter
This counter increments its value when appropriate LBI is active. Actual value of timer is visible in
statistics.
4 counters available
ROCOF and Vector shift protections
These protections trip breakers also in MAN mode
Function force value was added for following setpoints:
BTB control subgroup in BTB application
MGCB Parallel Close setpoint in MCB application
Min Power PTM setpoint in MCB application
Range of setpoint Nominal Mains Import was increased to 32 000 kW
SNMP improvement
Support of SNMP v3
SNMP v3 is supported on plug-in module CM3-Ethernet and on on-board ethernet
FW 1.1.0.7 or newer of CM3-Ethernet plug-in module is required
Universal values for modbus interface added
4x RemoteControl 2B
2x RemoteControl 4B
1x RemoteControl Bin
Actual values of exercise timers are visible
Default value of setpoint MCB Close Delay
New default value is 5s
Support of 8C and 16C communication modes on CAN2 line - setpoint CAN Intercontroller Comm Mode
Default value of setpoint MCB Open Window
New default value is 1%
LBO HISTORY RECORD INDICATION PULSE added - This LBO triggers 1s pulse when new history record is
created in history log.
Remote alarm messaging improvement
There are setpoints for each type of alarm in controller - these setpoint can enable or disable remote
alarm messaging for each alarm type

InteliMains 510 1.1.0 New Features List 3


New setpoint Bus Meas Error Delay
This setpoint adjust delay for bus measurement error protection.
It is possible to rename default names of existing objects in the configuration, for instance:
Universal Hours Counters
Remote Controls
Pulse Counters
User Buttons
Setpoint Nominal Frequency has 1 decimal place
A user defined groups and subgroups of setpoints within User Setpoints management
2 groups, 5 subgroups
Voltage protections can be evaluated based on the phase-phase, phase-neutral or both voltages using
new setpoint Evaluated Voltage Protections
Adjustment of access rules
all setpoint can be edited by all roles in controller
LBI MGCB OPEN
When this LBI is active, it is not possible to close MGCB. When MGCB is already closed and this LBI
is activated, MGCB is opened immediately.
Support of power management in kVA mode
Modification of PLC block Comp Hyst
Input Enable added - input is used for enabling of output of comparator. When input is not configured,
output is enabled all the time.
Subgroup Load Transfer was moved to Process Control setpoint group
Logical analog inputs for external control:
PF CONTROL: ANEXT BASE PF
Q CONTROL: ANEXT BASE Q
Q CONTROL: ANEXT IMP/EXP Q
Setpoint Time Stamp Act added
Use this setpoint for periodical records in history log
Improvement of PLC blocks Ramp and Up/Down
New parameter for setting a time units for ramping (s/min)
Modification of setpoint MGCB Parallel Close
New option No+Reserve - MGCB is closed to parallel operation when SYSTEM RESERVE OK = 1
It is possible to close MGCB in MAN mode when LBO SYSTEM START/STOP is not active
Improved user access management - access level based was replaced by a role-based system
Individual user accounts can be assigned to individual roles
Role 0: administrator

Role 1-7: configurable roles

Role 8: Modbus

Role 9: SNMP

InteliMains 510 1.1.0 New Features List 4


LBI DARK MODE
When active the status LED and backlight of a controller are turned off (application and controller
keep running)

2.2 Bug fixes


Airgate status value is correctly displayed
Setpoint Generator Unload MGCB Open Level
setpoint was renamed to Generator Unload Level
setpoint is used also in MCB application
MGCB is opened when system stop protection is activated
Correct evaluation of BTB closing conditions
BTB cannot close to dead BusL (Bus R - OK) If there is Genset Loaded (on the L side)
Evaluation of ROCOF/Vector Shift protections in MCB application when option Parallel only is selected
correct evaluation of protections
Close transfer to bus without ComAp genset controller
If there is voltage on the bus, but no ComAp controller connected to the bus, the Close Transfer ends
in a loop of MGCB closing/opening
Open transfer procedure when setpoint Open Transfer Min Break > 3s
The transfer does not happen as expected, MGCB keeps closing/opening forever.
MCB Fail To Open alarm stays active until MCB is opened
Change of regulation parameters of Load loop where not applied when regulation loop was active
Mains Return Delay timer was always applied when mains fail occurs - even when mains returned before
start of genset

InteliMains 510 1.1.0 New Features List 5


3 Notes
Revision number Related sw. version Date Author
1 1.1.0 6.5.2024 Michal Slavata

InteliMains 510 1.1.0 New Features List 6