PM150

DC-DC Converter

PM150-series 120 to 150 W


Input / Output Operation
• Wide input voltage ranges. • Operating temperature range -25 to +55 °C
• Input ranges from 10 to 270 Vd.c. and +70 ° with derating.
• Single outputs from 12 to 48 Vd.c. • High efficiency.
• Reverse input voltage protection. • Fully encapsulated, meets IP20 as standard.
• 2.5 kVa.c. isolation input/output, • Convection cooled.
input/case, output/case. • Output voltage adjustable on frontpanel.

Features EMC
• Overvoltage protection OVP. • EN/IEC 61000-6-3, Emission.
• Extra output with series diode. • EN/IEC 61000-6-2, Immunity.
• Over/Under voltage alarm relay. • EN/IEC 61000-4-4, 4 kV.
• EN/IEC 61000-4-5 level 2 & 3.

Input and outputs ratings


Nominal inputs Input range Code Output
12, 24 Vd.c. 10 - 30 V A Voltage Current Power
24, 28, 36, 48 Vd.c. 20 - 60 V B 12 V 10 - 12 A 120 - 150 W
72, 96, 110, 127 Vd.c. 50 - 150 V C 13.8 V 8.7 - 10.9 A 120 - 150 W
110, 127, 220 Vd.c. 90 - 270 V D 15 V 8 - 10 A 120 - 150 W
24V 5 - 6.25 A 120 - 150 W
Input voltages meeting train standard
EN 50155/IEC 60571, can be made on demand. 28 V 5.36 A 150 W
36 V 4.17 A 150 W
48 V 2.5 - 3.13 A 120 - 150 W
Output ratings and type code
Output Input
Voltage Current Power 10 - 30 V 20 - 60 V 50 - 150 V 90 - 270 V How to read our product code:
Example PM150B12
12 V 10.0 A 120 W PM150A12
PM150 = Family code
12 V 12.5 A 150 W PM150B12 PM150C12 PM150D12 B = input voltage code B
13.8 V 8.70 A 120 W PM150A13.8 12 = Output voltage 12V
13.8 V 10.9 A 150 W PM150B13.8 PM150C13.8 PM150D13.8
15 V 8.00 A 120 W PM150A15
15 V 10.0 A 150 W PM150B15 PM150C15 PM150D15
24 V 5.00 A 120 W PM150A24
24 V 6.25 A 150 W PM150B24 PM150C24 PM150D24
28 V 5.36 A 150 W PM150B28 PM150C28 PM150D28
36 V 4.17 A 150 W PM150B36
48 V 2.50 A 120 W PM150A48
48 V 3.13 A 150 W PM150B48 PM150C48 PM150D48

Features Optional Features

Overvoltage protection OVP Inrush current limit with NTC


The output voltage is limited to 15 % over Reduces the inrush current during start up.
nominal output voltage by an extra The input voltage range will be affected.
regulation circuit. Only available on C & D inputs.
Conformally coating
Extra output with series diode For environment with high non condensing
Use the series diode output when the output humidity max 98 % RH.
is connected in parallel with other power +70 °C operating temperature
supplies to archive redundancy. Contact factory for derating as it depends on
model. The alarm can not be used at +70 °C.
Over / Under voltage alarm Mounting brackets L214-1
The built in relay changes to alarm state if Se figure 3.
the converter output voltage is not within 19” Rack mounting set PL88-2
90 to 115 % of nominal output. To mount two PM150 together to form a
The user can select NO or NC relay full 19” rack unit, see figure 2.
function. The relay rating is 19” Rack mounting bracket PL88-3
30 V 0.5 A (d.c. or a.c.) To mount one PM150 to form a full 19” rack
unit, see figure 2.
EN/IEC 61000-4-5 level 4
External varistor + surge arrestor mounted from
pole to ground. With this filter the input meets
level 4 of EN/IEC 61000-4-5 (+/-2 kV line to
line, 4 kV line to ground)
DIN-rail clips
Clips to mount PM150 on a 35 mm DIN-rail.
(Used with PL88-1 & L-214 see figure 3)
Train input
Input voltage range according to train standard
EN 50155 and IEC 60571.

Polyamp AB PM150 DC-DC Converters Page 2


General data / input data Output data

Design topology Push-Pull Source regulation 0.1 %


Switching frequency 30 kHz Load regulation (0 to 100 % load) 0.3 %
Emission / Immunity See page 4 Transient recovery time for
Safety EN/IEC 60950 Class I 10 to 90 % load step to within 3 % of
nominal output voltage. <3 ms
Max. accepted input ripple1
50-400 Hz 2 % of nominal voltage Output ripple (60 kHz) 2
30 mV p-p

Input power at no load Max. 9 W Input ripple attenuation to output


(50 to 400 Hz) 150:1
Inrush current limit No
Emission / Immunity See page 4
Reverse input voltage protection
Temperature coefficient 0.02 %/°C
A, B inpute code Parallel diode
Min output adjustment range
C, D input code Series diode adjustable with a 15 turn
Dimensions (D x W x H) 160 x 214 x 88 mm potentiometer 95 - 110 %
Weight 2.5 kg Current limit, rectangular. 105 %

1. Higher ripple affects the input, contact factory Remote sense No


Soft start Yes
Start-up time 1s
Hold-up time, contact factory 2 - 25 ms
2. The output ripple might increase to 0.5 % RMS of Vout,
Efficiency 3
80 - 88 %
when EN/IEC 61000-4-3, 10 V/m test is applied
3. Lowest efficiency measured within the whole input Operating temperature range
voltage range at 100 % load. at 100 % load. -25 to +55 °C
(Convection cooling) with derating4 +70 °C
4. Contact factory for derating as it depends on model.
The alarm relay can not be used at +70 °C. Storage temperature range -40 to +85 °C

Mechanical drawing 88 mm

214 mm mm
160

Figure 1. Dimensions Weight: 2.5 kg

2 units PM150/240 mounted PM150/240 wall mounted. PM150/240 wall mounted.


side by side forming one 19” unit Using mounting brackets Using standard brackets
using standard bracket PL88-1 and (Optional) L214-1 PL88-1
PL88-2 (Optional).
4 units PM150/240 mounted
verticaly using standard PL88-1
brackets and L480-2 (Optional).
Single unit PM150/240
mounted as one 19” unit using
PL88-3 brackets (Optional).

Figure 3. Wall and chassis mounting


Figure 2. 19”-rack mounting
Polyamp AB PM150 DC-DC Converters Page 3
Safety and EMC Safety standard EN/IEC 60950

PM150 meets the requirements defined by Isolation testable levels Test voltage
CE mark as apparatus. Input / Output 2.5 kVa.c. / 4 kVd.c.
PM150 meets requirements of EMC directive Input / Case 2.5 kVa.c. / 4 kVd.c.
and low voltage directive (LVD). Output / Case all outputs 2.5 kVa.c. / 4 kVd.c.
Thus a PM150 can be used as free standing unit Input / Alarm 2.5 kVa.c. / 4kVd.c.
or in installations as well as systems designed Output / Alarm 2.5 kVa.c. / 4 kVd.c.
according to ”The modular approach”. PM150 case / Alarm 2.5 kVa.c. / 4 kVd.c.
can be used in installation without further EMC
We use the product standard Low voltage
tests, if our installation instructions are followed.
power supplies, DC outputs EN/IEC 61204-3
Please note that product standards can demand
and the generic EMC standards:
different levels or other basic standard tests. We
EN/IEC 61000-6-2 (Immunity)
test according to levels below. For higher levels
EN/IEC 61000-6-3 (Emission)
or other tests, contact factory.

EMC
EMC-standards EMC-performance
Emission standards Input Output Remarks
EN 55011/EN 55022 (0.15-30 MHz) Level B Level B
EN 55011/EN 55022 (30-1000 MHz) Level B Enclosure test
Immunity standards EN/IEC 61000-6-2
EN/IEC 61000-4-2 8 kV / 15 kV Contact / air, Enclosure test
EN/IEC 61000-4-3 10 V/m AM-Modulated Output ripple can increase to
0.5 % of Vout Enclosure test
EN/IEC 61000-4-4 4 kV 4 kV
EN/IEC 61000-4-5, Input code A, B 0.5 kV / 1 kV 0.5 kV / 1 kV Line-line 2 Ω / Line-case 12 Ω
EN/IEC 61000-4-5, Input code C, D 1 kV / 2 kV1 0.5 kV / 1 kV
EN 50121-3-2/IEC 62236-3-2 1 kV / 2 kV 1 kV / 2 kV Line-line 42 Ω / Line-case 42 Ω
EN/IEC 61000-4-6 10 VRMS 10 VRMS AM-Modulated
EN/IEC 61000-4-8 Not sensitive Enclosure test
EN/IEC 61000-4-10 Not sensitive Enclosure test
1 Higher level 2 kV / 4 kV with external filters, contact factory.

Contact

For updates on this datasheet we refer to www.polyamp.com