N-18800A_RS_5000_Q2157_RB_Overall SLD Rev. B
N-18800A_RS_5000_Q2157_RB_Overall SLD Rev. B
N-18800A_RS_5000_Q2157_RB_Overall SLD Rev. B
-Q15
-Q16
-Q25
-Q26
-Q17
-Q27
withstand voltage (1min)
-Q63,-Q64
Rated switching impulse withstand voltage 1050 kV
BB 1A BB 1A BB 1B BB 1B BB 1C BB 1C
Rated normal current
420kV, 4000A, 40°C, 63kA (1s) 4000 A
Busbar, Bus Section, Bus coupler -Q51, -Q52
Earthing Switch
BB 2A BB 2A BB 2B BB 2B BB 2C BB 2C Rated normal current at 40°C / 50°C -Q81,-Q82
4000/3762 A -Q83, -Q84 (Insulated)
OHL Feeder
420kV, 4000A, 40°C, 63kA (1s)
Rated normal current at 40°C / 50°C
4000/3762 A
-Q1 -Q2 -Q1 -Q2 -Q1 -Q2 -Q1 -Q2 -Q61 -Q62 -Q1 -Q2 -Q1 -Q2 -Q11 -Q12 -Q21 -Q22 -Q1 -Q2 -Q1 -Q2 -Q63 -Q64 -Q1 -Q2 -Q1 -Q2 -Q1 -Q2 -Q1 -Q2 -Q1 -Q2 -Q1 -Q2 -Q1 -Q2 -Q1 -Q2 -Q16 -Q26 -Q65 -Q66 -Q1 -Q2 -Q1 -Q2 Transformer Feeder
-Q8
Rated shorttime withstand current 1s 63 kA High speed Earthing Switch
-Q15,-Q16
-Q25,-Q26 (Insulated)
-Q1 -Q1 -Q2
Rated shortcircuit breaking current 63 kA
-Q51 -Q51 -Q51 -Q51 -Q81 -Q82 -Q1 -Q2 -Q51 -Q51 -Q51 -Q2 -Q83 -Q84 -Q51 -Q51 -Q51 -Q51 -Q51 -Q51 -Q85 -Q86 -Q51 -Q51
-Q51
Rated supply voltage 110 V DC
-T1,-T2,-T3 Current transformer
-Q51 -Q52 -Q51 -Q52 -Q51 -Q52 -Q51 -Q52
P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1
1 1 -Q51 -Q52 1 1 1 1 -Q51 -Q52 1 1
-Q51 -Q52 Rated supply voltage circuit breaker 110 V DC
-T1 -T1 -T1 2 -T1 2 -T1 2 -T1 2 -T1 2 -T1 2 -T1 2 -T1 2 -T1 -T1 -T1 -T1 -T1 -T1
3 3 3 3 3 3 3 3 -T5
P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 -T15,-T25 Voltage transformer
Rated supply voltage isolator/earthing switch 110 V DC
P1 P1 P1 P1 P1 P1 P1 P1 -T16,-T26
1 1 1 1
-Q0 -Q0 -Q0 -Q0 -Q0 -Q0 -T1 2 -T2 2 -T1 2 -T2 2
-Q0 -Q0 -Q0 -Q0 -Q0 -Q0 -T1 -T2 -T1 -T2 -Q0 -Q0 -Q0 -Q0 Heater voltage 400/230 V AC
P1 P1 3 3 3 3 P1 P1 P1 P1
Surge Arrester with removable link,
1 1 P2 P2 P2 P2 1 1 P2 P2 P2 P2 1 1 -F1 Metal Oxide type Gas Insulated,
-T1 2 -T2 2 -T1 2 -T2 2 -T1 2 -T2 2 Ur = 336 kV, Class 4, In= 20kA
3 3 3 3 3 3 Color Code of Switchgear RAL 7033
P2 P2 P2 P2 P2 P2
P2 P2 -T15 -T25 P2 P2 P2 P2 -T16 -T26 P2 P2 P2 P2 P2 P2 -T17 -T27 P2 P2
3 3 3 3 3 3 3 3
-Q0 -Q0 -Q0 -Q0
-T2 -T2 -T2 2 -T2 2 -T2 2 -T2 2 -T2 2 -T2 2 -T2 2 -T2 2 -T2 -T2 -T2 -T2 -T2 -T2 -Z1 SF6 air bushing
P1
1
P1
1
P1
1
P1
1
P1
1
P1
1
P1
1
P1
1
P1 P1 P1 P1 P1 P1
FILLING PRESSURE 400KV GIS
-Q52 -Q52 -Q52 -Q52
-Q0
-Q52 -Q52 -Q52 -Q52
-Q0
-Q52 -Q52 -Q52 -Q52 -Q52 -Q52
-Q0
-Q52 -Q52
(gauge pressure at 20°C)
-Z2 Transformer direct connection
Circuit breaker 5.6 bar 560 kPa
-Q9 -Q9 -Q9 -Q9 -Q9 -Q9 -Q9 -Q9 -Q9 -Q9 -Q9 -Q9 -Q9 -Q9 -Q9 -Q9
Switchgear 5.2 bar 520 kPa
Transformer 400/220kV
-Q8 -Q8 -Q8 -Q8 -Q8 -Q8 -Q8 -Q8 -Q8 -Q8 -Q8 -Q8 -Q8 -Q8 -Q8 -Q8 Voltage transformer 5.6 bar 560 kPa
P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 220kV Legend
-T3 -T3 -T3 1 -T3 1 -T3 1 -T3 1 -T3 -T3 -T3 -T3 -T3 -T3
220kV Technical Data of Switchgear
P1 P1 P1 P1 P1 P1 P1 P1 P1 P1
Symbol Designation Description
-F1 -F1 -F1 -F1 -F1 -F1 -F1 -F1 -F1 -F1 -F1 -F1 Type of switchgear 8DN9
-Q0 Circuit breaker
Rated voltage 245 kV
-Q1, -Q2
Rated frequency 50 Hz -Q9
-Q11, -Q12 Disconnector
Rated lightning impulse withstand voltage 1050 kV -Q21, -Q22
-Z2 -Z2 -Z2 -Z2 -Q61, -Q62
Rated short-duration power frequency 460 kV -Q63, -Q64
-T8 -T3 -T4 -T8 -T3 -T4 -T8 -T3 -T4 -T8 -T3 -T4 withstand voltage >1 (min)
-Z1 -Z1 -Z1 -Z1 -Z1 -Z1 -Z1 -Z1 -Z1 -Z1 -Z1 -Q51, -Q52
P2 P1 P2 P1 P1 P2 -Z1 P2 P1 P2 P1 P1 P2 P2 P1 P2 P1 P1 P2 P2 P1
-Q81, -Q82 Earthing Switch (Insulated)
Rated normal current Busbar @ 40°C 3150 A -Q83, -Q84
-LA IBT - 01 -LA IBT - 02 -LA IBT - 03 -LA IBT - 04 (Future) Bus Couplers & Bus Section
P2 P2 P2 P2
-T6 T110 -T6 T120 -T6 T130 -T6 T140 -Q8
P1 P1 P1 P1
Rated normal current @ 40°C 3150 A High Speed Earthing Switch
500/500/125MVA 500/500/125MVA 500/500/125MVA 500/500/125MVA -Q15, -Q25
OHL Feeder @ 50°C 2500 A -Q16, -Q26 (Insulated)
400/230/34.5kV 400/230/34.5kV 400/230/34.5kV 400/230/34.5kV
YNa0d11 Rated normal current @ 40°C 3150 A
YNa0d11 YNa0d11 YNa0d11
ONAN / ONAF/ODAF ONAN / ONAF/ODAF Cable Feeder @ 50°C 2500 A
ONAN / ONAF/ODAF ONAN / ONAF/ODAF -T1, -T2, -T3 Current transformer
%Z-18% %Z-18% %Z-18% %Z-18% Rated normal current @ 40°C 3150 A
Taps +15-15 Taps +15-15 Taps +15-15 IBT Feeder @ 50°C 2500 A
Taps +15-15
-T5
Rated short-time withstand current 1 s 50 kA -T15, -T16 Voltage transformer
-T25, -T26
3phx1Cx240sqmm 1x1Cx1600 sqmm / PHASE 1x1Cx1600 sqmm / PHASE 3phx1Cx240sqmm 1x1Cx1600 sqmm / PHASE 1x1Cx1600 sqmm / PHASE Rated short-circuit breaking current 50 kA
33kV XLPE CABLE 220kV XLPE CABLE 220kV XLPE CABLE 33kV XLPE CABLE 220kV XLPE CABLE 220kV XLPE CABLE
Rated supply voltage 110V DC Surge Arrester with removable link,
-F1 Metal Oxide type Gas Insulated,
Ur = 192 kV, Class 4, In= 20kA
Rated supply voltage circuit breaker 110V DC
Rated supply voltage isolator / earthing switch 110V DC -Z1 Cable Sealing end
Heater voltage 400/230V AC
Disconnecting link
FILLING PRESSURE 220KV GIS
(gauge pressure at 20°C) LEGENDS: Transformer Tertiary
-T5 -T5 Surge Arrestor details
3 3 Circuit breaker 6.9 bar 690 kPa
-LA Surge Arrester, Metal Oxide,
Switchgear 6.1 bar 610 kPa Ur = 45 kV, Class 4, In= 20kA
2xS2
2xS2
Voltage transformer 6.1 bar 610 kPa
-Q69 / 69E -Q69 / 69E
P2
6
P2
6
33kV LEGEND 33kV Technical data of switchgear
5 5
-T1
4
3 -T1
4
3
Symbol Designation Equipments Type of Switchgear 8DB10
2 2
Motorlized Rated Voltage 36kV
1 1 -Q0
P1 P1
-Z1 -Z1 -Z1 -Z1 M Circuit Breaker
Operating Voltage 33kV
VT BUS1A VT BUS1B
CAPDIS S2+ CAPDIS S2+ Motorlized Rated Frequency 50Hz
M
-Q1, -Q5 3-Position Switch
-T15 -A51 -A51 -T16
3 3
Rated lightning impulse withstand voltage 170kV
Line VT disconnector/earting
-Q69/69E Rated short-duration power-frequency withstand voltage 70kV
-F1 Switch
-Q0 1250A -Q0 1250A
-Q61E -Q63E -F1 -F1 -F1 Rated short-time withstand current 31.5kA(3sec)
-Q63 -Q63 3
1250A 1250A -T1, -T2 Current Transformer
Rated current at 40°C Busbar 2000A
Line/Busbar Voltage Rated current at 40°C feeder 1250A
-T5, Transformer
-Q1 -Q1 -Q5
33kV, 3 ~ 50 Hz, 2000A, 40°C, 31.5kA (3s), BUS - 1A -Q5 33kV, 3 ~ 50 Hz, 2000A, 40°C, 31.5kA (3s), BUS - 1B Maximum permissible busbar current at 40°C 2000A
Capacitive Voltage indication
-A51
CAPDIS system (CAPDIS S2+)
-Q5 -Q16 -Q15 -Q5 Maximum permissible busbar current at 50°C -
-Q5 -Q1 =H03 =H06 -Q1 -Q5 Plug-in Type cable
-Q11 -Q12 -Q1
-Q1 Terminator Rated supply voltage DC 110V
INCOMER-1 INCOMER-2
-T5 -T5 -T5 -T5 Cable Termination Rated supply voltage motor, Circuit breaker DC 110V
P1
-T2 1
Rated supply voltage motor, 3-Pos. switch DC 110V
-Q0 -Q0 1250A P2 -Q0 1250A -Q0
-Q0 2000A P1
-Q8 -Q8 -Q8 -Q8 Environmental Factors Rated heater voltage AC 240V
1
2
min. -5 °C
-T1 Ambient temperature (indoor)
max. +40 °C
-A51 -A51
-A51
3
4
-A51 -A51 -Q9 -Q9 -Q9 -Q9
Phase Assignment
CAPDIS S2+
P2
CAPDIS S2+
min. -5 °C
Ambient temperature (outdoor)
CAPDIS S2+ max. +50 °C R = I = A
P1 P1 P1 P1 Altitude Above Mean Sea Level < 1000m
1 1 Y = II = B
-T1 -T1
2
-T1
2 -T1 P1 1 P1 1 P1 1 P1 1
3 3
-T2 2 -T2 2 -T2 2 -T2 2 B = III = C
P2 4 4 P2
3 3 3 3
P2 P2 P2 P2 P2 P2
=H04 =H05
-Q52 -Q52 -Q52 -Q52
2xS2
BUS SECTION BUS RISER 2xS2 Auto-Transformer CT data
Identification Designation Rated Power Ratio Class resistance Knee IMAG at Vk Function
-Q0 -Q0 -Q0 -Q0 ( VA ) (ohm) point voltage(V) (mA)
T3U,T3V,T3W 2UN,2VN,2WN NA 3200-1600/1 PX <10-5 > 600 - 400 <20-30 CIRC.CURRENT DIFF
3phx1Cx240sqmm 3phx1Cx240sqmm
T4 2N NA 1500-1000/1 PX <3-2 >300 - 200 <20-30 STANDBY EF
P2 P2 P2 P2
=H01 =H02 =H07 =H08 4
3
4
3
4
3
4
3 T8U,T8V,T8W 3U,3V,3W NA 1500-1000/1 PX <3.4-2.7 > 600 - 400 <20-30 SHORT ZONE PROTN
-T2 2
-T2 2
-T2 2
-T2 2
FUTURE FDR AUX. TR -1 AUX. TR -2 FUTURE FDR 1 1 1 1 T6U,T6V,T6W 2U,2V,2W NA 3200-1600/1 PX <10-5 > 600 - 400 <20-30 CABLE DIFF
P1 P1 P1 P1
REFERENCE DRG.
-Q0 -Q0 -Q0 -Q0 -Q0 -Q0 -Q0 -Q0 -Q0 -Q0 -Q0 -Q0 -Q0
N-18800A-RS-7410-H-2703 400/230/34.5kV,500MVA POWER TRANSFORMER RATING B
-Q0 -Q0 -Q0
-Q52 -Q52 -Q52 -Q52 -Q52 -Q52
-Q0
-Q52 -Q52 -Q52 -Q52 -Q52 -Q52 -Q52 N-18800A-RS-7140-R-2454 33kV GIS-SINGLE LINE DIAGRAM C
-Q52 -T15 -T25 -T16 -T26 -Q52
N-18800A-RS-7130-R-2366 220kV GIS-SINGLE LINE DIAGRAM C
P2 P2 P2 =D06 P2 =D10 =D11 P2 P2
=D15 P2 P2
N-18800A-RS-7130-R-2217 400kV GIS-SINGLE LINE DIAGRAM **
-T2
4 4
-T2
3
2 BUS COUPLER -1A-2A -T2
3
2 BUS BUS -T2
3
2 -T2
3
2 METERING BAY 1B/2B
4 4
-T2 -T2 -T2
C
-T2 -T2 3
-T2 3
-T2 3
-T2 3
2 2 P1 1 P1 1 P1 1 P1 1 2 2
/ METERING BAY 1A/2A SECTION -1A-1B SECTION -2A-2B / BUS COUPLER 1B-2B REV. STATUS
P1
1
P1
1
P1
1
P1
1
DRG. NO. TITLE
-Q9 -Q9 -Q9 -Q9 -Q9 -Q9 -Q9 -Q9 -Q9 -Q9 -Q9 -Q9 -Q9
-Q8 -Q8 -Q8 -Q8 -Q8 -Q8 -Q8 -Q8 -Q8 -Q8 -Q8 -Q8 -Q8
REVISIONS
-T5 -T5 -T5 -T5 -T5 -T5 -T5 -T5 -T5
-T5 -T5 -T5 -T5
B 22.04.2024 REVISED AS PER COMMENTS ON DTS-446 (RET STATUS) SC AKG NK
-T3
P2
-T3 1 -T3
P2
1 -T3
P2
1 -T3
P2
1 -T3
DTS NO. REV. DATE DESCRIPTION PREP CHD APPR
P1 P1 P1 P1
CONTRACTOR STAMP
-F1 -F1 -F1 -F1 -F1 -F1 -F1 -F1 -F1 -F1 -F1 -F1 -F1 FOR APPROVAL
This Document is Checked and Verified by Concerned Engineer In Charge Date: 18.10.2023
-Z2 -Z1 -Z2 -Z2 -Z1 -Z1 -Z1 -Z1 -Z2 -Z2 -Z1 -Z2 -Z1
OWNER:
=D01
FUTURE OHL
=D02
FUTURE TR
=D03
SPARE
OHL
=D04
SPARE
OHL
=D05
CABLE
FEEDER -3
=D08
CABLE
FEEDER-DP01
CABLE
=D12
FEEDER-DP02
=D14
CABLE
FEEDER-4
=D17
SPARE
OHL -3
=D18
SPARE
OHL -4
=D19
FUTURE TR
=D20
FUTURE OHL
=D21
FUTURE TR TRANSCO P.O. BOX 173
ABU DHABI - U.A.E.
Tel : +971 2 416 4000
Abu Dhabi Transmission & Despatch Company Fax : +971 2 416 4444
CONSULTANT: