YUANDONG 1.8-3kV 3x95mm2
YUANDONG 1.8-3kV 3x95mm2
YUANDONG 1.8-3kV 3x95mm2
TECHNICAL SPECIFICATION
For Low-Votage Cables
1. SCOPE
This specification covers the minimum requirements for Power cables, including the structure,
performance, test and packing information of cables as manufactured by Far East Cable. Matters
not mentioned in this technical specification shall be negotiated by purchaser & supplier.
2. STANDARDS
The cable which Far East Cable offered shall be designed, manufactured and tested according to
international standards as follows:
Cable Standards
IEC 60228 Conductors of insulated cables
Power cables with extruded insulation and their accessories for rated
IEC 60502-1 voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1:
Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV)
3. Application
Maximum sustained conductor temperature during operation: 90℃
Maximum conductor temperature during short circuit(5s): 250℃
Lowest allowable temperature during installation(ambient and cable): 0℃
Lowest allowable temperature during operation(ambient): -15℃
Mouse proof and termite-proof
1) STRUCTURE
2. Insulation XLPE
2) DATA SHEET
Structure Parameter
Approx. Approx.
Core No. × Conductor Insulation Armouring Outer sheath
diameter weight
Cross section
No. Approx. Dia. of Nom./min. Nom. Nom./min.
(mm2)
Conductor Thickness Thickness Thickness (mm) (kg/km)
(mm) (mm) (mm) (mm)
12xDia.
1. 3×95 0.193 265 175 215 3.5/5
of cable
Cable drum shall be of wood or iron provided with wooden battens or sheet iron to protect the
cable from damage. After factory tests, cable ends should be sealed reliably, cable ends
spreading out of drum should be given protection cover, which is not less than 300mm. Cable
should be protected from moisture, kept away from high temperature and fire sparks, protected
from over bending and crushing, and protected from mechanical stress and damage during
transportation and installation.
Each drum of cable adheres to eligibility certification of production quality inspection. In
addition, purchaser’s and manufacturer’s information, cable information and drum information
shall be stuck on or marked at outside face of drum.