2 www.3b-energy.com
MME 24 12 - 24 kV
630 - 1250 A
16 - 20 kA
Contents
Description 4
Unit Dimensions 6
Unit Types 7
Technical Data 8
Typical Units 9
Components 25
www.3b-energy.com
3
MME 24 12 - 24 kV
630 - 1250 A
16 - 20 kA
GENERAL
MME series Metal Enclosed units which are produced by our company,have been designed and tested to be used
for all energy distribution systems till 24 kV
Modular Metal Enclosed units appear as the optimal solution with their easiness of taking operation by means of
their modular structure and with their module apposition characteristic for companies
MME series Metal enclosed unit are manufactured according to IEC Standards
Optimal dimensions
Long term technical solutions for various applications
High level personal safety
APPLICATIONS
Manufacturing industry
Secondary electricy distribution networks
Shopping malls
MV / LV distribution transformer substations
Small size power plants
Wind power plants
Airports, hospitals, holiday village
Enclosure of cubicle is 2 mm galvanized steel sheet. If desired al-zinc is also possible.
No welding during the assembling of the structure.
SAFETY
There is a survelliance window on the front cover of the every cubicle to check inside the cubicle without open the
door / cover
The door / cover of the accessible compartments is mechanically interlocked with the earthing switches
High voltage indication system in each cubicle
STANDARDS
Compliance with standards IEC 62271 - 200
Classification; (according to IEC 62271 - 200 )
Classification of service contunity: LSC 2A
Classification of the partitions: ( Partition: Insulated or Metallic )
Classification of arc proofing: IAC A (FL), IAC A (FLR)
4 www.3b-energy.com
MME 24 12 - 24 kV
630 - 1250 A
16 - 20 kA
Busbar compartment
1 is located on the top of the cubicle. It contains the
1
main busbar which interconnect between cubicles.
And also: 2
Tool based accessible compartment with regard
to accessibility, (it means that is not possible to
open the covers without using any tools)
Withstand to internal arc
Having IP 3X protection degree
2
Cable comparment
3
compartmentCable compartment is located at the
bottom of the cubicle. It contains switching devices,
measuring transformers., HV fuses, earthing devices,
4
support insulators according to the functional type of
the cubicle. Incoming / outgoing MV cable connection
of the cubicle is made in this compartment. The door
has an inspection window. And also:
Procedure based accessible compartment with
regard to accessibility, (it means that it is possible to open the covers without using any tools)
Withstand to internal arc
IP 3X protection degree
www.3b-energy.com
5
MME 24 SERIES Unit dimension
1650 1650
1650 1650
6 www.3b-energy.com
MME 24 SERIES Unit types
Type MME 241 Type MME 242 Type MME 243 Type MME 243.R
Incoming Cable Unit Incoming Cable with Earthing Unit Line with Metering Unit Line with Metering and Riser Unit
Type MME 244 Type MME 245 Type MME 245.U Type MME 246
Metering Unit Bus Riser with Metering Unit Bus Riser with Metering Unit Bus Riser Unit
Type MME 247 Type MME 248 Type MME 249 Type MME 249.1
Line Switch Unit Transformer Protection Unit Circuit-Breaker Unit Circuit-Breaker with Bus Riser Unit
Type MME 249.2 Type MME 249.C Type MME 249.S1 Type MME 249.S2
Circuit-Breaker with Double switch Unit Circuit-Breaker Upside down Unit Circuit-Breaker with SINTER Circuit-Breaker with SINTER
SINTER
SINTER
www.3b-energy.com
7
MME 24 SERIES Technical data
8 www.3b-energy.com
MME 24
Incoming Cable Unit
1650
MME 241
375 1140
Standard equipment
1.Voltage indicator device
2.Busbars
3.Earthing bar
4.Heater
5.Interlocking unit
Technical data
Rated voltage [kV] 12 17,5 24
Rated current [A] 630/1250 630/1250 630/1250
Rated short-time withstand current [kA] 20 20 20
Maximum rated duration of short circuit [s] 1 1 1
Net Weight kg 110 110 110
Gross Weight kg 140 140 140
Width with pack mm 420 420 420
Depth with pack mm 1250 1250 1250
Height with pack mm 1750 1750 1750
www.3b-energy.com
9
MME 24
Incoming Cable with Earthing Unit
1650
MME 242
375 1140
Standard equipment
1.Earthing switch
2.Voltage indicator device
3.Busbars
4.Earthing bar
5.Heater
6.Interlocking unit
Technical data
Rated voltage [kV] 12 17,5 24
Rated current [A] 630/1250 630/1250 630/1250
Rated short-time withstand current [kA] 20 20 20
Maximum rated duration of short circuit [s] 1 1 1
Net Weight kg 130 130 130
Gross Weight kg 150 150 150
Width with pack mm 420 420 420
Depth with pack mm 1250 1250 1250
Height with pack mm 1750 1750 1750
10 www.3b-energy.com
MME 24
Line and Metering Unit
1650
MME 243
750 1140
Technical data
Rated voltage [kV] 12 17,5 24
Rated current [A] 630/1250 630/1250 630/1250
Rated short-time withstand current [kA] 20 20 20
Maximum rated duration of short circuit [s] 1 1 1
Net Weight kg 405 405 405
Gross Weight kg 450 450 450
Width with pack mm
Depth with pack mm 1250 1250 1250
Height with pack mm 1750 1750 1750
www.3b-energy.com
11
MME 24
Line and Metering with Riser Unit
1650
MME 243.U
750 1140
Technical data
Rated voltage [kV] 12 17,5 24
Rated current [A] 630/1250 630/1250 630/1250
Rated short-time withstand current [kA] 20 20 20
Maximum rated duration of short circuit [s] 1 1 1
Net Weight kg 420 420 420
Gross Weight kg 465 465 465
Width with pack mm 800 800 800
Depth with pack mm 1250 1250 1250
Height with pack mm 1750 1750 1750
12 www.3b-energy.com
MME 24
Metering Unit
1650
MME 244
750 1140
Technical data
Rated voltage [kV] 12 17,5 24
Rated current [A] 630/1250 630/1250 630/1250
Rated short-time withstand current [kA] 20 20 20
Maximum rated duration of short circuit [s] 1 1 1
Net Weight kg 00
Gross Weight kg
Width with pack mm
Depth with pack mm 1250 1250 1250
Height with pack mm 1750 1750 1750
www.3b-energy.com
13
MME 24
Bus Riser with Metering Unit
1650
MME 245
750 1140
Technical data
Rated voltage [kV] 12 17,5 24
Rated current [A] 630/1250 630/1250 630/1250
Rated short-time withstand current [kA] 20 20 20
Maximum rated duration of short circuit [s] 1 1 1
Net Weight kg 370 370 370
Gross Weight kg 415 415 415
Width with pack mm 800 800 800
Depth with pack mm 1250 1250 1250
Height with pack mm 1750 1750 1750
14 www.3b-energy.com
MME 24
Bus Riser with Metering Unit
1650
MME 245.U
750 1140
Technical data
Rated voltage [kV] 12 17,5 24
Rated current [A] 630/1250 630/1250 630/1250
Rated short-time withstand current [kA] 20 20 20
Maximum rated duration of short circuit [s] 1 1 1
Net Weight kg 370 370 370
Gross Weight kg 415 415 415
Width with pack mm 800 800 800
Depth with pack mm 1250 1250 1250
Height with pack mm 1750 1750 1750
www.3b-energy.com
15
MME 24
Bus Riser Unit
1650
MME 246
375 1140
Standard equipment
1.Earthing switch
2.Voltage indicator device
3.Busbars
4.Earthing bar
5.Heater
6.Interlocking unit
Technical data
Rated voltage [kV] 12 17,5 24
Rated current [A] 630/1250 630/1250 630/1250
Rated short-time withstand current [kA] 20 20 20
Maximum rated duration of short circuit [s] 1 1 1
Net Weight kg 90 90 90
Gross Weight kg 120 120 120
Width with pack mm 420 420 420
Depth with pack mm 1250 1250 1250
Height with pack mm 1750 1750 1750
16 www.3b-energy.com
MME 24
Line Switch Unit
1650
MME 247
375 1140
Technical data
Rated voltage [kV] 12 17,5 24
Rated current [A] 630/1250 630/1250 630/1250
Rated short-time withstand current [kA] 20 20 20
Maximum rated duration of short circuit [s] 1 1 1
Net Weight kg 155 155 155
Gross Weight kg 185 185 185
Width with pack mm 420 420 420
Depth with pack mm 1250 1250 1250
Height with pack mm 1750 1750 1750
www.3b-energy.com
17
MME 24
Transformer Protection Unit
1650
MME 248
375 1140
Technical data
Rated voltage [kV] 12 17,5 24
Rated current [A] 200 200 200
Rated short-time withstand current [kA] 20 20 20
Maximum rated duration of short circuit [s] 1 1 1
Net Weight kg 170 170 170
Gross Weight kg 200 200 200
Width with pack mm 420 420 420
Depth with pack mm 1250 1250 1250
Height with pack mm 1750 1750 1750
18 www.3b-energy.com
MME 24
Circuit Breaker Unit
750 1140
1300
Technical data
Rated voltage [kV] 12 17,5 24
Rated current [A] 630/1250 630/1250 630/1250
Rated short-time withstand current [kA] 20 20 20
Maximum rated duration of short circuit [s] 1 1 1
Net Weight kg 360 360 360
Gross Weight kg 405 405 405
Width with pack mm 800 800 800
Depth with pack mm 1350 1350 1350
Height with pack mm 1750 1750 1750
www.3b-energy.com
19
MME 24
Circuit-Breaker with Bus Riser Unit
MME 249.1
1650
750 1140
1300
Technical data
Rated voltage [kV] 12 17,5 24
Rated current [A] 630/1250 630/1250 630/1250
Rated short-time withstand current [kA] 20 20 20
Maximum rated duration of short circuit [s] 1 1 1
Net Weight kg 380 380 380
Gross Weight kg 420 420 420
Width with pack mm 800 800 800
Depth with pack mm 1350 1350 1350
Height with pack mm 1750 1750 1750
20 www.3b-energy.com
MME 24
Circuit-Breaker Double switch Unit
MME 249.2
1650
750 1140
1300
Standard equipment
Standard equipment Optional equipments
1.Earthing switch
1.3 Position SF6 load break switch Optional equipments
2.Voltage indicator device
(open - closed - earthed) 1.Remote control with cable
3.Busbars
2.Operating mechanism with mechanical position (Opening and closing)
4.Earthing bar
indication 2.Remote control without cable
5.Heater
3.Voltage indicator
unit device (Opening and closing)3
6.Interlocking
4.Heater .Gas density indication
5.Earthing bar 4.Gas density indication with alarm contact
6.Busbars 5.Motor operation device
7.Interlocking unit 6.Cable fault indication device
8.Auxiliary contacts for close 7.Surge arresters
(2NO+2NC) and earth (2NO+2NC) position 8.Current transformers
9.Cable entry with cable support 9.Arc-gas channel
Technical data
Rated voltage [kV] 12 17,5 24
Rated current [A] 630/1250 630/1250 630/1250
Rated short-time withstand current [kA] 20 20 20
Maximum rated duration of short circuit [s] 1 1 1
Net Weight kg 400 400 400
Gross Weight kg 450 450 450
Width with pack mm 800 800 800
Depth with pack mm 1350 1350 1350
Height with pack mm 1750 1750 1750
www.3b-energy.com
21
MME 24
Circuit Breaker Upside down Unit
1650 o
MME 249.C o
o
o
o
o
o
750 1140
1300
Technical data
Rated voltage [kV] 12 17,5 24
Rated current [A] 630/1250 630/1250 630/1250
Rated short-time withstand current [kA] 20 20 20
Maximum rated duration of short circuit [s] 1 1 1
Net Weight kg 360 360 360
Gross Weight kg 405 405 405
Width with pack mm 800 800 800
Depth with pack mm 1350 1350 1350
Height with pack mm 1750 1750 1750
22 www.3b-energy.com
MME 24
Circuit Breaker with SINTER Unit
SINTER
1650
MME 249.S1
500 1140
1300
Technical data
Rated voltage [kV] 12 17,5 24
Rated current [A] 630/1250 630/1250 630/1250
Rated short-time withstand current [kA] 20 20 20
Maximum rated duration of short circuit [s] 1 1 1
Net Weight kg 320 320 320
Gross Weight kg 350 350 350
Width with pack mm 550 550 550
Depth with pack mm 1350 1350 1350
Height with pack mm 1750 1750 1750
www.3b-energy.com
www.3b-energy.com
23
MME 24
Circuit Breaker with SINTER Unit
SERIES Type MME 249.S2
MME 249.S2
SINTER
1650
500 1140
1300
Standard equipment Optional equipments
1.SINTER SF6 disconnector 1.Remote control with cable
2.Operating mechanism withmechanical position (Opening and closing)
indication 2.Remote control without cable
3.SINTER Circuit breaker vacuum type (Opening and closing)
4.Current transformers (toroidal orstandard type ) 3.Gas density indication
5.Over current protection relay 4.Gas density indication with alarm contact
6.Earthing switch 16 kA 5.Voltage Transformers
7.Voltage indicator device 6.Cable fault indication device
8.Heater 7.Surge arresters
9.Earthing bar 8.Arc-gas channel
10.Busbars
11.Interlocking unit
12.Auxiliary contacts for close
(2NO+2NC) and earth (2NO+2NC) position
13.Cable entry with cable support
Technical data
Rated voltage [kV] 12 17,5 24
Rated current [A] 630/1250 630/1250 630/1250
Rated short-time withstand current [kA] 20 20 20
Maximum rated duration of short circuit [s] 1 1 1
Net Weight kg 320 320 320
Gross Weight kg 350 350 350
Width with pack mm 550 550 550
Depth with pack mm 1350 1350 1350
Height with pack mm 1750 1750 1750
24 www.3b-energy.com
MME 24 SF6 LOAD BREAK SWITCH & DISCONNECTOR
SERIES MS
Functioning concept
MS switches are made of an epoxy cast resin housing
filled with SF6 gas at the pressure of 150 kPa abs.,
operative life sealed.(Standard IEC 62271-103)
The moving contact are fixed on the insulated rotary shaft
inside the cast resin body, while the fi-xed contacts are
mounted directly on the cast resin body.
The rotary motion of the shaft is made by an ope-rating
mechanism placed on the front. The switch has three
different positions: closed, open and eart-hed, which
naturally prevent any wrong operations.
Charateristics
MS switches use sulphur hexafluoride gas (SF6) for
insulation and breaking.
The active parts are placed in an insulating enclosure in
accordance with the IEC standards for sealed pressure
systems.
SF6 products offer remarkable characteristics:
Long service life - Maintenance-free active parts - Opera-
ting safety - Very low over-voltage level
www.3b-energy.com
25
MME 24 DISCONNECTOR AND VACUUM CIRCUIT-BREAKER
SERIES SINTER
General Features
Electric arc breaking
The combined medium voltage circuit breaker of the
SINTER Series is the result of recognised technology
synergy for production of vacuum bottles and
manufacturing re-known know-how of Italian companies.
SINTER circuit breakers are indeed a combined system
of breaking and switching, inside a single SF6 insulated
enclosure, with pressure lower than 0.5 bar at 45 °C.
As regards the breaking, vacuum bottles are used.
As well known, the reduced necessary energy for vacuum
arc extinguishment enables to reach a long-lasting
electrical life (10.000 rated breaking current operations).
Apparatus structure
The whole active elements complex (circuit breaker and
main switch) are inside an heavy metallic stainless steel Main Components
structure filled with a high dielectric SF6 gas. Vacuum Interrupter
The structure is life-sealed and is holding 6 bushings
with operating mechanism. 1 Fixed contact terminal
The heavy structure grants stoutness and time-life 2 Ceramic insulator
reliability. 3 Mobile contact terminal
Reference Standards
IEC 62271 - 1, IEC 62271 - 100, IEC 62271 - 102, IEC 60529 - CEI EN 60447
26 www.3b-energy.com
MME 24 SERIES COMPONENTS
Earthing switch:
Rated voltage 12 kV - 17.5 kV - 24 kV
Voltage transformers
The resin insulated voltage transformers are used for the feeding of
measuring instruments and protection. They are suitable either for
fixed installation or mounted on withdrawable trucks. They comply
with IEC 60044 - 2 Standards. The dimensions of the fixed version
comply with DIN standards 42600 Narrow Type. The withdrawable
version equipped with fuses is custom made. The voltage transformers
can be fitted either with one or two poles. Their performances and
precision classes comply with the functional requirements of the appa-
ratus they are connected to. The withdrawable version is equipped
with medium voltage protection fuses, their replacement can be carri-
ed out while the switchboard is in service.
Current transformers
The current transformers are resin insulated and suitable for the
feeding of measuring instruments and protections. These transfor-
mers can have a wound core or bushing bar with one or more cores.
Their performances and precision classes comply with the apparatus
requirements. The current transformers comply with IEC 60044 - 1
Standard. Their dimensions meet the requirements of DIN 42600
Standards. The current transformers can be equipped also with a
capacitive socket for being connected to voltage indicator lambs.
Protection relay
MME Series switchboards can be equipped with different brand relay:
THYTRONIC, SEB, MS, ABB, SIEMENS, SCHNEIDER or others.
www.3b-energy.com
27