56OP 00544 7001 Electrical Load List - Rev 3
56OP 00544 7001 Electrical Load List - Rev 3
56OP 00544 7001 Electrical Load List - Rev 3
DISTRIBUTION
CLIENT : SIAM MITSUI PTA CO.,LTD. 1 PDF
2 Hard Copy
PROJECT : ANAEROBIC PROJECT
PURPOSE
P Information (FI)
Review (FR)
Approval (FA)
Construction (FC)
Final (FF)
As Built (AB)
ITEM NO. (1) EQUIPMENT NAME Q'TY(2) RATING SPECIFICATION CONSTRUCTION RESTART(10) REMARKS
Degree of Protection
Rotation Direction
Temperature Rise
Area classification
Number of Phase
MCC Assignment
Insulation Class
Speed Control
Type of Motor
Stand-by use
Speed (pole)
Normal use
Enclosure
EDG Load
Unit type
Voltage
restart
Status
Rated
Unit
N S kV (3) (4) (5) (6) (7) (8) (9) N 1 2 >2 (11) (12)
FROM 3MCC-08
2PM-577A/B Ca(OH)2 FEED PUMPS 1 1 o 7.5 kW 4 0.38 3 C CCW C N IM TEFC N IP55 H F B N 3MCC-08 M
2PM-578A/B KCI FEED PUMPS 1 1 o 0.25 kW 4 0.38 3 C CCW C N IM TEFC N IP55 V F B N 3MCC-08 M
2PM-571C UREA FEED PUMP 1 o 0.4 kW 4 0.38 3 C CCW C N IM TEFC N IP55 V F B N 3MCC-08 M
2PM-572C 85% PO4 FEED PUMP 1 o 0.2 kW 4 0.38 3 C CCW C N IM TEFC N IP55 V F B N 3MCC-08 M
VARIABLE FREQUENCY SPEED DRIVE-
3VSD-01-1/2/3 2 1 o 45 kW - 0.38 3 C - C N - - N IP41 - - - - - - - - 3MCC-08 F 160AT, 3ph, 380V
No.1/2/3
VARIABLE FREQUENCY SPEED DRIVE-
3VSD-01-4 1 o 0.25 kW - 0.38 3 C - C N - - N IP41 - - - - - - - - 3MCC-08 F 10AT, 3ph, 380V
No.4
800AT, 3ph, 3W,
3PC-02 POWER CAPACITOR (LV SYSTEM) 1 o 400 kVar 0.38 3 C N - - - - - - - - - - - - 3MCC-08 F
380V
PM-442B/C 32% NaOH FEED PUMPS 2 o 9.1 kW 4 0.38 3 C CCW C N CANNED TEFC N IP55 H F B N TBA M
FROM 3VSD-01
VVVF installed in
2PM-532A/B/C RECYCLE PUMPS 2 1 o 45 kW 8 0.38 3 - CCW VVVF N IM TEFC N IP55 H F B N 3VSD-01 VVVF
VSD Panel
VVVF installed in
2ZM-576B Ca(OH)2 VOLUMETRIC FEEDER ( SCREW ) 1 o 0.25 kW 4 0.38 3 - CW VVVF N IM TEFC N IP55 H F B N 3VSD-01 VVVF
VSD Panel
PROCESS EQUIPMENT UTILITY AND CONTROL SYSTEM FEEDER
30AT, 3ph, 4W,
3LDB-02 (G-Zone) NORMAL LIGHTING 1 o 15.8 kVA 0.38 3 C N 3LP-01-2 F
380/220V
125AT, 3ph,4W,
3PJB-01 (G-Zone) POWER PLUG 125A, 380Vac 2 o 65.8 kVA 0.38 3 C N 3DP-01-2 F
380/220V
EMERGENCY LIGHTING & SMALL POWER 30AT, 3ph, 4W,
3LDB-03 (G-Zone) 1 o 15.8 kVA 0.38 3 C N 3LP-01-3 F
SOCKETS 380/220V
ITEM NO. (1) EQUIPMENT NAME Q'TY(2) RATING SPECIFICATION CONSTRUCTION RESTART(10) REMARKS
Degree of Protection
Rotation Direction
Temperature Rise
Area classification
Number of Phase
MCC Assignment
Insulation Class
Speed Control
Type of Motor
Stand-by use
Speed (pole)
Normal use
Enclosure
EDG Load
Unit type
Voltage
restart
Status
Rated
Unit
N S kV (3) (4) (5) (6) (7) (8) (9) N 1 2 >2 (11) (12)
Example, 3TCM-301A means a motor to dive 3 TC-301A Circulation Blower H : Horizontal type
2. Q'ty N : Normal use, S : Strand-by use 10. Restart N : No time delay restart after power restored
CCW : Counter clockwise 11. EDG load Quantity of cirtical loads backed up by Emergency Disel Generator in case of normal power failure
DCM : DC motor
IM : Induction motor
SM : Synchronous motor