Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Annex 1 - DX FAHU With (Opt 1)

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

OPTION 1: DX FAHU SCHEDULE

PROJECT : G+1+R VILLA, PLOT NO. 13, BANIYAS, ABU DHABI, UAE
CLIENT : Mr. ALMALIK ADEL SALEH OMAR SALEH ALHUWAIT
CONSULTANT : M/s. MASTER ENGINEERING CONSULTANCY
CONTRACTOR : N/A

AIR FLOW COOLING COIL SIDE

AIR ON AIR OFF


VRF CU
UNIT UNIT DIMENSION UNIT Weight SUPPLY FAN COOLING COIL COOLING COIL COOLING COIL CAPACITY SUPPLY FAN ESP
# SCH. UNIT TYPE/MODEL Rated Elec. VFD QTY
REF NO. L*W*H (mm) (kg) °C °C PI (Kw) (PA)
(Kw)
TOTAL SENSIBLE
L/S DBT/WBT DBT/WBT
KW KW

1 SPECIFIED FAHU-1 FAHU - - - - - 31.65 - - - - - 1

FAHU
OFFERED FAHU-1 1858*961*538 138.0 600 46.1/29.4 22.0/19.3 29.40 18.00 1.5 - 300 YES 1
(MODEL: NIA-S 5)
VRF CU WxDxH
OFFERED CU-FAHU-1 177.0 - - - 33.50 - - 9.20 - - 1
GMV-H335WL/A-X (940*460*1615)

Proposed Specifications, Exclusions:


1. Building Data, 1. Electrostatic Filter
* Panel Thickness 40 mm 2. Control Panels & External Isolator Switch.
* External Material Pre-coated sp. 0.8 3. Electrical Power cables & Control Wiring.
* Internal Material Galvanized steel sp. 0.8 4. Sound Attenuators/Silencers, Insect Screen, Dampers & Damper Actuators.
* Insulation Material Polyurethane 42 kg/m³ 5. Air Flow Monitors.
* Blanks Off Material Galvanized steel sp.1.5 6. Control valves, thermostats, any kind of DDC or electric control, starters.
* Drain Tray Material used - Stainless steel 7. Unloading, installation, storage and maintenance of equipment at site.
* Roof Canopy Pre-coated - 0.8 8. External Vibration Isolators.
2. Fan-motor section: Plug Fan - Direct Driven & VFD. 9. BMS connectivity and so forth.
3. Fan Motor: Variable speed with IP55 Protection & Class ‘F’ Insulation 10. No spares included in our offer.
4. Fan Motor assembly mounted on Anti Vibration Isolators.
5. Cooling coil section with refrigerant based cooling coil made of Copper tubes & aluminum fins.
6. Proposed Condensing unit for FAHU is VRF ODU & Compressors are DC Inverter Type
7. Condensing unit is selected at Amp temp. 46⁰C/29⁰C
8. Refrigerant used - R410a
9. Filters Section :
* Coarse 80% (ISO16890) - Pre Filter
* ePM2,5 65% (ISO16890) - Soft Bag Filter
10. Make & Country of origin,
FAHU - Nia, UAE
CU - Gree, China
11. Intake Damper Section (GI).
12. Power Supply - FAHU & VRF ODU - 380-415V/3Ph/50Hz

Annexure-01 1 of 1 NIA/QTN/HS-0272/02-22