Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Electrical Load List - Module-2

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

EPC-COMMON SERVICES, VENTILATION AND PRPD

PROJECT
MECHANICAL EQUIPMENT PACKAGE OF KKNPP-5&6
ELECTRICAL LOAD LIST - DESALINATION PLANT (MODULE-2)
MODULE NO. MODULE 2 CHKD

DOCUMENT NO. AES- EE-EL-001

REVISION A APRD

TAG. NO.: DESALINATION PLANT LOAD CALCULATION CONSUMED LOAD

ABSORBED MOTOR OR LOAD FACTOR EFFICIENCY AT POWER

STARTER / FEEDER
kW = A/ D & kVAr = kW . tan Φ

CLASSIFICATION
LOAD EQUIPMENT LOAD FACTOR C FACTOR AT LOAD
RATING (IEC STD) A LOAD DUTY CONTINUOUS INTERMITTENT STAND-BY REMARKS REV

TYPE

LOAD
ITEM

FACTOR C :C/I/S
KKS / TAG NUMBER DESCRIPTION DATA BUS GROUP VOLTAGE A B B C D E F G

kW kW pu pu cosΦ kW kVAr kW kVAr kW kVAr

I DESALINATION PLANT FOR PHASE II

1 00UGX10AN005 COMPRESSOR MOTOR -5 ME A DOL N 3 6000 876.00 1000.00 0.88 0.97 0.80 C 907 680 _ _ _ _ A

2 00UGX10AN006 COMPRESSOR MOTOR -6 ME A DOL N 3 6000 876.00 1000.00 0.88 0.97 0.80 C 907 680 _ _ _ _ A

3 00UGX10AN007 COMPRESSOR MOTOR -7 ME A DOL N 3 6000 876.00 1000.00 0.88 0.97 0.80 C 907 680 _ _ _ _ A

4 00UGX50AP005 BRINE DISPOSAL PUMP MOTOR-2 ME A VSD N 3 415 48.00 75.00 0.64 0.95 0.80 C 50.5 37.9 _ _ _ _ A

5 00UGX50AP006 BRINE DISPOSAL PUMP MOTOR-3 ME B VSD N 3 415 48.00 75.00 0.64 0.95 0.80 C 50.5 37.9 _ _ _ _ A

6 00UGX50AP007 BRINE DISPOSAL PUMP MOTOR-4 ME A VSD N 3 415 48.00 75.00 0.64 0.95 0.80 C 50.5 37.9 _ _ _ _ A

7 00UGX60AP005 PRODUCT WATER PUMP MOTOR-2 ME B VSD N 3 415 26.00 37.00 0.70 0.93 0.80 C 28.0 21.0 _ _ _ _ A

8 00UGX60AP006 PRODUCT WATER PUMP MOTOR-3 ME A VSD N 3 415 26.00 37.00 0.70 0.93 0.80 C 28.0 21.0 _ _ _ _ A

9 00UGX60AP007 PRODUCT WATER PUMP MOTOR-4 ME B VSD N 3 415 26.00 37.00 0.70 0.93 0.80 C 28.0 21.0 _ _ _ _ A

10 00UGX12AP004 RECIRCULATION PUMP MOTOR-D ME A Soft Starter N 3 415 25.00 30.00 0.83 0.94 0.80 C 26.7 20.0 _ _ _ _ A

11 00UGX12AP005 RECIRCULATION PUMP MOTOR-E ME B Soft Starter N 3 415 25.00 30.00 0.83 0.94 0.80 C 26.7 20.0 _ _ _ _ A

12 00UGX12AP006 RECIRCULATION PUMP MOTOR-F ME A Soft Starter N 3 415 25.00 30.00 0.83 0.94 0.80 C 26.7 20.0 _ _ _ _ A

13 00UGX12AP007 RECIRCULATION PUMP MOTOR-G ME B Soft Starter N 3 415 25.00 30.00 0.83 0.94 0.80 C 26.7 20.0 _ _ _ _ A

14 00UGX12AP008 RECIRCULATION PUMP MOTOR-H ME A Soft Starter N 3 415 25.00 30.00 0.83 0.94 0.80 C 26.7 20.0 _ _ _ _ A

15 00UGX12AP009 RECIRCULATION PUMP MOTOR-I ME B Soft Starter N 3 415 25.00 30.00 0.83 0.94 0.80 C 26.7 20.0 _ _ _ _ A

16 00UGX12AP010 RECIRCULATION PUMP MOTOR-J ME A Soft Starter N 3 415 25.00 30.00 0.83 0.94 0.80 C 26.7 20.0 _ _ _ _ A

17 00UGX12AP011 RECIRCULATION PUMP MOTOR-K ME B Soft Starter N 3 415 25.00 30.00 0.83 0.94 0.80 C 26.7 20.0 _ _ _ _ A

18 00UGX12AP012 RECIRCULATION PUMP MOTOR-L ME A Soft Starter N 3 415 25.00 30.00 0.83 0.94 0.80 C 26.7 20.0 _ _ _ _ A

19 00UGX40AP003 ANTI SCALE ADDITIVE DOSING PUMP MOTOR ME - DOL N 3 24 0.10 0.20 0.50 0.94 0.80 C 0.1 0.1 _ _ _ _ A

20 00UGX40AP004 ANTI SCALE ADDITIVE DOSING PUMP MOTOR ME - DOL N 3 24 0.10 0.20 0.50 0.94 0.80 S _ _ _ _ 0.1 0.1 A

21 00UGX40AP005 ANTI SCALE ADDITIVE DOSING PUMP MOTOR ME - DOL N 3 24 0.10 0.20 0.50 0.94 0.80 C 0.1 0.1 _ _ _ _ A

22 00UGX40AP006 ANTI SCALE ADDITIVE DOSING PUMP MOTOR ME - DOL N 3 24 0.10 0.20 0.50 0.94 0.80 S _ _ _ _ 0.1 0.1 A

23 00UGX40AP007 ANTI SCALE ADDITIVE DOSING PUMP MOTOR ME - DOL N 3 24 0.10 0.20 0.50 0.94 0.80 C 0.1 0.1 _ _ _ _ A

24 00UGX40AP008 ANTI SCALE ADDITIVE DOSING PUMP MOTOR ME - DOL N 3 24 0.10 0.20 0.50 0.94 0.80 S _ _ _ _ 0.1 0.1 A

1 of 6
EPC-COMMON SERVICES, VENTILATION AND PRPD
PROJECT
MECHANICAL EQUIPMENT PACKAGE OF KKNPP-5&6
ELECTRICAL LOAD LIST - DESALINATION PLANT (MODULE-2)
MODULE NO. MODULE 2 CHKD

DOCUMENT NO. AES- EE-EL-001

REVISION A APRD

TAG. NO.: DESALINATION PLANT LOAD CALCULATION CONSUMED LOAD

ABSORBED MOTOR OR LOAD FACTOR EFFICIENCY AT POWER

STARTER / FEEDER
kW = A/ D & kVAr = kW . tan Φ

CLASSIFICATION
LOAD EQUIPMENT LOAD FACTOR C FACTOR AT LOAD
RATING (IEC STD) A LOAD DUTY CONTINUOUS INTERMITTENT STAND-BY REMARKS REV

TYPE

LOAD
ITEM

FACTOR C :C/I/S
KKS / TAG NUMBER DESCRIPTION DATA BUS GROUP VOLTAGE A B B C D E F G

kW kW pu pu cosΦ kW kVAr kW kVAr kW kVAr

25 00UGX40AP009 ANTI FOAM ADDITIVE DOSING PUMP MOTOR ME - DOL N 3 24 0.10 0.20 0.50 0.94 0.80 C 0.1 0.1 _ _ _ _ A

26 00UGX40AP010 ANTI FOAM ADDITIVE DOSING PUMP MOTOR ME - DOL N 3 24 0.10 0.20 0.50 0.94 0.80 S _ _ _ _ 0.1 0.1 A

27 00UGX40AP011 ANTI FOAM ADDITIVE DOSING PUMP MOTOR ME - DOL N 3 24 0.10 0.20 0.50 0.94 0.80 C 0.1 0.1 _ _ _ _ A

28 00UGX40AP012 ANTI FOAM ADDITIVE DOSING PUMP MOTOR ME - DOL N 3 24 0.10 0.20 0.50 0.94 0.80 S _ _ _ _ 0.1 0.1 A

29 00UGX40AP013 ANTI FOAM ADDITIVE DOSING PUMP MOTOR ME - DOL N 3 24 0.10 0.20 0.50 0.94 0.80 C 0.1 0.1 _ _ _ _ A

30 00UGX40AP014 ANTI FOAM ADDITIVE DOSING PUMP MOTOR ME - DOL N 3 24 0.10 0.20 0.50 0.94 0.80 S _ _ _ _ 0.1 0.1 A

31 00UGX51AP001 SEA WATER BOOSTER PUMP MOTOR -2 ME A DOL N 3 415 18.00 30.00 0.60 0.94 0.80 C 19.2 14.4 _ _ _ _ A

32 00UGX61AP001 SEA WATER BOOSTER PUMP MOTOR -3 ME B DOL N 3 415 18.00 30.00 0.60 0.94 0.80 C 19.2 14.4 _ _ _ _ A

33 00UGX71AP001 SEA WATER BOOSTER PUMP MOTOR -4 ME A DOL N 3 415 18.00 30.00 0.60 0.94 0.80 C 19.2 14.4 _ _ _ _ A

34 00UGX*5AP006 VACUUM PUMP MOTOR-3 ME A VSD N 3 415 20.00 22.00 0.91 0.93 0.80 C 21.6 16.2 _ _ _ _ A

35 00UGX*5AP007 VACUUM PUMP MOTOR-4 ME B VSD N 3 415 20.00 22.00 0.91 0.93 0.80 S _ _ _ _ 21.6 16.2 A

36 00UGX*5AP008 VACUUM CIRCULATION PUMP MOTOR-2 ME A DOL N 3 415 0.20 0.37 0.54 0.93 0.80 C 0.2 0.2 _ _ _ _ A

37 00UGX*5AP009 CO2 CIRCULATION BOOSTER PUMP MOTOR-3 ME A VSD N 3 415 23.00 30.00 0.77 0.93 0.80 C 24.8 18.6 _ _ _ _ A

38 00UGX*5AP010 CO2 CIRCULATION BOOSTER PUMP MOTOR-4 ME B VSD N 3 415 23.00 30.00 0.77 0.93 0.80 S _ _ _ _ 24.8 18.6 A

39 00UGX*7AM001 ELECTRICAL AGITATOR ME A DOL N 3 415 0.30 0.37 0.81 0.93 0.80 I _ _ 0.32 0.24 _ _ A

40 00UGX*7AM001 ELECTRICAL AGITATOR ME A DOL N 3 415 0.30 0.37 0.81 0.93 0.80 I _ _ 0.32 0.24 _ _ A

41 00UGX*7AM001 ELECTRICAL AGITATOR ME A DOL N 3 415 0.30 0.37 0.81 0.93 0.80 I _ _ 0.32 0.24 _ _ A

42 00UGX*0AP002 OIL PUMP MOTOR -2 ME - DOL E 2 415 0.30 0.37 0.81 0.95 0.80 C 0.3 0.2 _ _ _ _ A

43 00UGX*0AP003 OIL PUMP MOTOR -3 ME DOL E 2 415 0.30 0.37 0.81 0.95 0.80 C 0.3 0.2 _ _ _ _ A

44 00UGX*0AP003 OIL PUMP MOTOR -4 ME DOL E 2 415 0.30 0.37 0.81 0.95 0.80 C 0.3 0.2 _ _ _ _ A

45 00UGX*0AH002 HEATER-2 ME MCCB N 3 415 1.50 1.50 1.00 1.00 0.80 C 1.5 1.1 _ _ _ _ A

46 00UGX*0AH003 HEATER-3 ME MCCB N 3 415 1.50 1.50 1.00 1.00 0.80 C 1.5 1.1 _ _ _ _ A

47 00UGX*0AH004 HEATER-4 ME MCCB N 3 415 1.50 1.50 1.00 1.00 0.80 C 1.5 1.1 _ _ _ _ A

48 00UGX*0EEXXX PLANT LIGHTING (NORMAL) EE MCB N 3 415 1.50 1.50 1.00 1.00 0.80 C 1.5 1.1 _ _ _ _ Photocell control A

49 00UGX*0EEXXX PLANT LIGHTING (EMERGENCY) EE MCB E 2 415 0.50 1.50 0.33 1.00 0.80 C 0.5 0.4 _ _ _ _ Photocell control A

2 of 6
EPC-COMMON SERVICES, VENTILATION AND PRPD
PROJECT
MECHANICAL EQUIPMENT PACKAGE OF KKNPP-5&6
ELECTRICAL LOAD LIST - DESALINATION PLANT (MODULE-2)
MODULE NO. MODULE 2 CHKD

DOCUMENT NO. AES- EE-EL-001

REVISION A APRD

TAG. NO.: DESALINATION PLANT LOAD CALCULATION CONSUMED LOAD

ABSORBED MOTOR OR LOAD FACTOR EFFICIENCY AT POWER

STARTER / FEEDER
kW = A/ D & kVAr = kW . tan Φ

CLASSIFICATION
LOAD EQUIPMENT LOAD FACTOR C FACTOR AT LOAD
RATING (IEC STD) A LOAD DUTY CONTINUOUS INTERMITTENT STAND-BY REMARKS REV

TYPE

LOAD
ITEM

FACTOR C :C/I/S
KKS / TAG NUMBER DESCRIPTION DATA BUS GROUP VOLTAGE A B B C D E F G

kW kW pu pu cosΦ kW kVAr kW kVAr kW kVAr

50 00UGX*0EEXXX WELDING SOCKETS EE MCB N 3 415 15.00 15.00 1.00 1.00 0.80 I _ _ 15.00 11.25 _ _ A

51 00UGX*0CIXXX PLC CABINET POWER SUPPLY I&C - MCB E 1 240 1.20 1.20 1.00 1.00 0.80 C 1.2 0.9

Total kW / kVAr 3310.2 2482.6 16.0 12.0 47.0 35.3


MAX DEMAND CONNECTED

GROUP-3 6KV LOAD SUMMARY (kW) 2720.50 3000.00 Total kVA 4137.7 20.0 58.8

GROUP-3 415V LV LOAD SUMMARY (kW) 587.04 824.88

GROUP-2 415V/240V LV LOAD SUMMARY (kW) 1.45 2.61

GROUP-1 240V AC UPS LOAD SUMMARY (kW) 1.20 1.20

3 of 6
EPC-COMMON SERVICES, VENTILATION AND PRPD
PROJECT
MECHANICAL EQUIPMENT PACKAGE OF KKNPP-5&6
ELECTRICAL LOAD LIST - DM PLANT (MODULE-2)
MODULE NO. MODULE 2 CHKD

DOCUMENT NO. AES- EE-EL-001

REVISION A APRD

TAG. NO.: DM PLANT LOAD CALCULATION CONSUMED LOAD

ABSORBED MOTOR OR LOAD FACTOR EFFICIENCY AT POWER

STARTER / FEEDER
kW = A/ D & kVAr = kW . tan Φ

CLASSIFICATION
LOAD EQUIPMENT LOAD FACTOR C FACTOR AT LOAD
RATING (IEC STD) A LOAD DUTY CONTINUOUS INTERMITTENT STAND-BY REMARKS REV

TYPE

LOAD
ITEM

FACTOR C :C/I/S
KKS / TAG NUMBER DESCRIPTION DATA BUS GROUP VOLTAGE A B B C D E F G

kW kW pu pu cosΦ kW kVAr kW kVAr kW kVAr

I DM PLANT FOR PHASE II

1 00UGX20AP004 LSF FEED PUMP ME A DOL N 3 415 18.56 22.00 0.84 0.95 0.80 C 19.5 14.7 _ _ _ _ 00UGD A

2 00UGX20AP005 LSF FEED PUMP ME A DOL N 3 415 18.56 22.00 0.84 0.95 0.80 S _ _ _ _ 19.5 14.7 00UGD A

3 00UGD10AP004 PW TRANSFER PUMP ME A DOL N 3 415 39.77 45.00 0.88 0.93 0.80 C 42.9 32.2 _ _ _ _ 00UGD A

4 00UGD10AP005 PW TRANSFER PUMP ME A DOL N 3 415 39.77 45.00 0.88 0.93 0.80 S _ _ _ _ 42.9 32.2 00UGD A

5 00UGD20AP003 NAOCL DOSING PUMP ME A DOL N 3 415 0.01 0.37 0.03 0.93 0.80 C 0.0 0.0 _ _ _ _ 00UGD A

6 00UGD40AP003 NA2CO3 DOSING PUMP ME A DOL N 3 415 0.01 0.37 0.03 0.94 0.80 C 0.0 0.0 _ _ _ _ 00UGD A

7 00UGX10AP004 MB FEED PUMP ME A DOL N 3 415 13.40 15.00 0.89 0.94 0.80 C 14.3 10.7 _ _ _ _ 00UGD A

8 00UGX10AP005 MB FEED PUMP ME A DOL N 3 415 13.40 15.00 0.89 0.94 0.80 S _ _ _ _ 14.3 10.7 00UGD A

9 00GCF10AP004 DM TRANSFER PUMP ME A DOL N 3 415 36.31 45.00 0.81 0.94 0.80 C 38.8 29.1 _ _ _ _ 00UGD A

10 00GCF10AP005 DM TRANSFER PUMP ME A DOL N 3 415 36.31 45.00 0.81 0.94 0.80 C 38.8 29.1 _ _ _ _ 00UGD A

11 00GCF10AP006 DM TRANSFER PUMP ME A DOL N 3 415 36.31 45.00 0.81 0.94 0.80 S _ _ _ _ 38.8 29.1 00UGD A

12 00GCF20AP003 MB REGENERATION PUMP ME A DOL N 3 415 4.15 5.50 0.75 0.94 0.80 C 4.4 3.3 _ _ _ _ 00UGD A

13 00GCF30AP003 MORPHOLINE DOSING PUMP ME A DOL N 3 415 0.01 0.37 0.03 0.94 0.80 C 0.0 0.0 _ _ _ _ 00UGD A

14 00GCF50AP003 NAOH(CAUSTIC) DOSING PUMP ME A DOL N 3 415 0.52 0.75 0.69 0.94 0.80 C 0.6 0.4 _ _ _ _ 00UGD A

15 00GCF60AP003 H2SO4(ACID) DOSING PUMP ME A DOL N 3 415 0.26 0.37 0.70 0.94 0.80 C 0.3 0.2 _ _ _ _ 00UGD A

16 00UGX*0EEXXX WELDING SOCKETS EE MCB N 3 415 15.00 15.00 1.00 1.00 0.80 I _ _ 15.00 11.25 _ _ 00UGD A

17 00UGX*0EEXXX PLANT LIGHTING (NORMAL) EE MCB N 3 415 1.00 1.00 1.00 1.00 0.80 C 1.0 0.8 _ _ _ _ IF REQUIRED A

18 00UGX*0EEXXX PLANT LIGHTING (EMERGENCY) EE MCB E 2 240 0.75 0.75 1.00 1.00 0.80 C 0.8 0.6 _ _ _ _ IF REQUIRED A

19 00UGX*0CIXXX DM LOCAL CONTROL PANEL I&C - MCB E 1 240 1.20 1.20 1.00 1.00 0.80 C 1.2 0.9 00UGD A

Total kW / kVAr 162.6 121.9 15.0 11.3 115.5 86.7


MAX DEMAND CONNECTED

GROUP-3 415V LV LOAD SUMMARY (kW) 160.64 322.73 Total kVA 203.2 18.8 144.4

GROUP-2 415V/240V LV LOAD SUMMARY (kW) 0.75 0.75

GROUP-1 240V AC UPS LOAD SUMMARY (kW) 1.20 1.20

4 of 6
EPC-COMMON SERVICES, VENTILATION AND PRPD
PROJECT
MECHANICAL EQUIPMENT PACKAGE OF KKNPP-5&6
ELECTRICAL LOAD LIST - COMPRESSED AIR PLANT (MODULE-2)
MODULE NO. MODULE 2 CHKD

DOCUMENT NO. AES- EE-EL-001

REVISION A APRD

TAG. NO.: COMPRESSED AIR PLANT LOAD CALCULATION CONSUMED LOAD

ABSORBED MOTOR OR LOAD FACTOR EFFICIENCY AT POWER

STARTER / FEEDER
kW = A/ D & kVAr = kW . tan Φ

CLASSIFICATION
LOAD EQUIPMENT LOAD FACTOR C FACTOR AT LOAD
RATING (IEC STD) A LOAD DUTY CONTINUOUS INTERMITTENT STAND-BY REMARKS REV

TYPE
FACTOR C

LOAD
ITEM

KKS / TAG NUMBER DESCRIPTION DATA BUS GROUP VOLTAGE A B B :C/I/S


C D E F G

kW kW pu pu cosΦ kW kVAr kW kVAr kW kVAr

I COMPRESSED AIR PLANT

1 SCA11AN001 LP RECIPROCATING COMPRESSOR -A ME A DOL N 3 415 30.00 37.00 0.81 0.95 0.80 C 31.6 23.7 _ _ _ _ 00UTF A

2 SCA11AN002 LP RECIPROCATING COMPRESSOR -B ME A DOL N 3 415 30.00 37.00 0.81 0.95 0.80 C 31.6 23.7 _ _ _ _ 00UTF A

3 SCA11AN003 LP RECIPROCATING COMPRESSOR -C ME A DOL N 3 415 30.00 37.00 0.81 0.95 0.80 S _ _ _ _ 31.6 23.7 00UTF A

DOL /
4 SCA12AN001 CENTRIFUGAL COMPRESSOR ME A N 3 415 132.00 160.00 0.83 0.95 0.80 C 138.9 104.2 _ _ _ _ 00UTF A
SOFT STARTER

5 SCA13AN001 HP RECIPROCATING COMPRESSOR -A ME A DOL N 3 415 11.00 15.00 0.73 0.95 0.80 C 11.6 8.7 _ _ _ _ 00UTF A

6 SCA13AN002 HP RECIPROCATING COMPRESSOR -B ME A DOL N 3 415 11.00 15.00 0.73 0.95 0.80 C 11.6 8.7 _ _ _ _ 00UTF A

7 SCA13AN003 HP RECIPROCATING COMPRESSOR -C ME A DOL N 3 415 11.00 15.00 0.73 0.95 0.80 S _ _ _ _ 11.6 8.7 00UTF A

AIR DRYER PLANT FOR LP RECIPROCATING


8 SCA14AT001 ME A DOL N 3 415 30.00 37.00 0.81 0.95 0.80 C 31.6 23.7 _ _ _ _ 00UTF A
COMPRESSOR (REFRIGERATION TYPE)

AIR DRYER PLANT FOR LP RECIPROCATING


9 SCA14AT002 ME A DOL N 3 415 30.00 37.00 0.81 0.95 0.80 C 31.6 23.7 _ _ _ _ 00UTF A
COMPRESSOR (REFRIGERATION TYPE)

AIR DRYER PLANT FOR LP RECIPROCATING


10 SCA14AT003 ME A DOL N 3 415 30.00 37.00 0.81 0.95 0.80 S _ _ _ _ 31.6 23.7 00UTF A
COMPRESSOR (REFRIGERATION TYPE)

AIR DRYER PLANT FOR CENTRIFUGAL COMPRESSOR DOL /


11 SCA15AT001 ME A N 3 415 132.00 160.00 0.83 0.95 0.80 C 138.9 104.2 _ _ _ _ 00UTF A
(REFRIGERATION TYPE) SOFT STARTER

AIR DRYER PLANT FOR HP RECIPROCATING


12 SCA16AT001 ME A DOL N 3 415 11.00 15.00 0.73 0.95 0.80 C 11.6 8.7 _ _ _ _ 00UTF A
COMPRESSOR (REFRIGERATION TYPE)

AIR DRYER PLANT FOR HP RECIPROCATING


13 SCA16AT002 ME A DOL N 3 415 11.00 15.00 0.73 0.95 0.80 C 11.6 8.7 _ _ _ _ 00UTF A
COMPRESSOR (REFRIGERATION TYPE)

AIR DRYER PLANT FOR HP RECIPROCATING


14 SCA16AT003 ME A DOL N 3 415 11.00 15.00 0.73 0.95 0.80 S _ _ _ _ 11.6 8.7 00UTF A
COMPRESSOR (REFRIGERATION TYPE)

15 00GUD35AP001 VERTICAL SUBMERSIBLE PUMP ME A DOL N 3 415 2.00 2.20 0.91 0.95 0.80 C 2.1 1.6 _ _ _ _ 00UTF A

16 00SGCXXXX MOTORIZED GATE VALVE I&C A DOL N 3 415 1.20 1.50 0.80 0.95 0.80 I _ _ 1.26 0.95 _ _ 00UTF A

17 SGC76AA003 MOTORIZED GATE VALVE I&C A DOL N 3 415 1.20 1.50 0.80 0.95 0.80 I _ _ 1.26 0.95 _ _ 00UTF A

18 SGC76AA004 MOTORIZED GATE VALVE I&C A DOL N 3 415 1.20 1.50 0.80 0.95 0.80 I _ _ 1.26 0.95 _ _ 00UTF A

19 0SAS28AN001 EXHAUST AIR CENTRIFUGAL FAN -A HVAC A DOL N 3 415 2.74 3.00 0.91 0.95 0.80 C 2.9 2.2 _ _ _ _ 00UTF A

20 0SAS28AN002 EXHAUST AIR CENTRIFUGAL FAN -B HVAC A DOL N 3 415 2.74 3.00 0.91 0.95 0.80 C 2.9 2.2 _ _ _ _ 00UTF A

21 0SAS27AN001 EXHAUST AIR CENTRIFUGAL FAN -A HVAC A DOL N 3 415 1.35 1.50 0.90 0.95 0.80 C 1.4 1.1 _ _ _ _ 00UTF A

22 0SAS27AN002 EXHAUST AIR CENTRIFUGAL FAN -B HVAC A DOL N 3 415 1.35 1.50 0.90 0.95 0.80 C 1.4 1.1 _ _ _ _ 00UTF A

23 0SAZ20AN001 EXHAUST AIR CENTRIFUGAL FAN -A HVAC A DOL N 3 415 0.89 1.10 0.81 0.95 0.80 C 0.9 0.7 _ _ _ _ 00UTF A

24 0SAZ20AN002 EXHAUST AIR CENTRIFUGAL FAN -B HVAC A DOL N 3 415 0.89 1.10 0.81 0.95 0.80 C 0.9 0.7 _ _ _ _ 00UTF A

5 of 6
EPC-COMMON SERVICES, VENTILATION AND PRPD
PROJECT
MECHANICAL EQUIPMENT PACKAGE OF KKNPP-5&6
ELECTRICAL LOAD LIST - COMPRESSED AIR PLANT (MODULE-2)
MODULE NO. MODULE 2 CHKD

DOCUMENT NO. AES- EE-EL-001

REVISION A APRD

TAG. NO.: COMPRESSED AIR PLANT LOAD CALCULATION CONSUMED LOAD

ABSORBED MOTOR OR LOAD FACTOR EFFICIENCY AT POWER

STARTER / FEEDER
kW = A/ D & kVAr = kW . tan Φ

CLASSIFICATION
LOAD EQUIPMENT LOAD FACTOR C FACTOR AT LOAD
RATING (IEC STD) A LOAD DUTY CONTINUOUS INTERMITTENT STAND-BY REMARKS REV

TYPE
FACTOR C

LOAD
ITEM

KKS / TAG NUMBER DESCRIPTION DATA BUS GROUP VOLTAGE A B B :C/I/S


C D E F G

kW kW pu pu cosΦ kW kVAr kW kVAr kW kVAr

25 0SAS24AN001 EXHAUST AIR CENTRIFUGAL FAN -A HVAC A DOL N 3 415 6.42 7.50 0.86 0.95 0.80 C 6.8 5.1 _ _ _ _ 00UTF A

26 0SAS24AN002 EXHAUST AIR CENTRIFUGAL FAN -B HVAC A DOL N 3 415 6.42 7.50 0.86 0.95 0.80 C 6.8 5.1 _ _ _ _ 00UTF A

27 0SAS45 AN001 SPLIT AC-1 HVAC A DOL N 3 415 3.60 4.00 0.90 0.95 0.80 C 3.8 2.8 _ _ _ _ 00UTF A

28 0SAS45 AN002 SPLIT AC-2 HVAC A DOL N 3 415 3.60 4.00 0.90 0.95 0.80 C 3.8 2.8 _ _ _ _ 00UTF A

29 0SAS45 AN003 SPLIT AC-3 HVAC A DOL N 3 415 3.60 4.00 0.90 0.95 0.80 C 3.8 2.8 _ _ _ _ 00UTF A

30 0SAS44AN001 SUPPLY AIR HANDLING UNIT-DRY AHU -A HVAC A DOL N 3 415 11.76 15.00 0.78 0.95 0.80 C 12.4 9.3 _ _ _ _ 00UTF A

31 0SAS44AN002 SUPPLY AIR HANDLING UNIT-DRY AHU -B HVAC A DOL N 3 415 11.76 15.00 0.78 0.95 0.80 C 12.4 9.3 _ _ _ _ 00UTF A

32 0SAS46AN001 SUPPLY AIR HANDLING UNIT-DRY AHU-A HVAC A DOL N 3 415 2.53 3.00 0.84 0.95 0.80 C 2.7 2.0 _ _ _ _ 00UTF A

33 0SAS46AN002 SUPPLY AIR HANDLING UNIT-DRY AHU-B HVAC A DOL N 3 415 2.53 3.00 0.84 0.95 0.80 C 2.7 2.0 _ _ _ _ 00UTF A

34 0SAS47AN001 SUPPLY AIR HANDLING UNIT-DRY AHU-A HVAC A DOL N 3 415 4.94 5.50 0.90 0.95 0.80 C 5.2 3.9 _ _ _ _ 00UTF A

35 0SAS47AN002 SUPPLY AIR HANDLING UNIT-DRY AHU-B HVAC A DOL N 3 415 4.94 5.50 0.90 0.95 0.80 C 5.2 3.9 _ _ _ _ 00UTF A

36 0SAZ40AN001 SUPPLY AIR HANDLING UNIT-DRY AHU-A HVAC A DOL N 3 415 1.49 2.20 0.68 0.95 0.80 C 1.6 1.2 _ _ _ _ 00UTF A

37 0SAZ40AN002 SUPPLY AIR HANDLING UNIT-DRY AHU-B HVAC A DOL N 3 415 1.49 2.20 0.68 0.95 0.80 C 1.6 1.2 _ _ _ _ 00UTF A

38 00UTF*0XX MOTORISED FIRE DAMPER HVAC A MCB N 3 240 1.50 2.00 0.75 0.95 0.80 I _ _ 1.58 1.18 _ _ 00UTF, (20nos. ) A

39 SMT20AE001 EOT CRANE ME A DOL N 3 415 7.20 11.00 0.65 0.95 0.80 C 7.6 5.7 _ _ _ _ 00UTF A

40 00UTF*0EEXXX WELDING SOCKETS EE MCB N 3 415 15.00 15.00 1.00 1.00 0.80 I _ _ 15.00 11.25 _ _ 00UGD A

41 00UTF*0EEXXX LIGHTING & SMALL POWER (NORMAL) EE MCB N 3 415 4.00 5.00 0.80 1.00 0.80 C 4.0 3.0 _ _ _ _ IF REQUIRED A

42 00UTF*0EEXXX PLANT LIGHTING (EMERGENCY) EE MCB E 2 240 1.00 1.00 1.00 1.00 0.80 C 1.0 0.8 _ _ _ _ IF REQUIRED A

43 00UTF*0CIXXX COMPRESSOR CONTROL PANELS I&C - MCB E 1 240 2.00 2.00 1.00 1.00 0.80 C 2.0 1.5 00UGD A

Total kW / kVAr 546.2 409.7 20.4 15.3 86.3 64.7


MAX DEMAND CONNECTED

GROUP-3 415V LV LOAD SUMMARY (kW) 543.20 761.30 Total kVA 682.8 25.5 107.9

GROUP-2 415V/240V LV LOAD SUMMARY (kW) 1.00 1.00

GROUP-1 240V AC UPS LOAD SUMMARY (kW) 2.00 2.00

6 of 6

You might also like