135 STK2 Mechanical Specification T1
135 STK2 Mechanical Specification T1
135 STK2 Mechanical Specification T1
PART 1 GENERAL
This section of the specification covers the mechanical services works associated with this
project.
A suitably qualified and registered Mechanical Contractor shall carry out the whole of
mechanical installation.
This section shall be read in conjunction with the Engineers drawings 1596 M0-M1
The Mechanical Contractor shall ensure they are familiar with the existing condition of the site
and existing services, prior to submitting the tender price.
The price shall be deemed to include the provision of all materials, fittings and performance of
all works, which is necessary for the satisfactory and efficient functions of the installation, and
which is provided in accordance with accepted trade practice, even though such works may
not be explicitly mentioned in the specification or not.
Appropriate instructions shall be given in writing. Oral amendments and instructions shall not
be recognised.
103 Alternatives & Substitutions
The contractor shall allow in their tender price all the equipment.
“As Specified”. Alternatives and substitutions of ‘approved equal’ shall only be offered as a
deduction and/or alternative to the Tender Price, and any discussions will be entered into
after the close of Tender.
The contractor shall thoroughly inspect the existing conditions during the tender period and
ensure that they have a complete understanding of the existing conditions and allow for all
temporary works necessary to ensure services are maintained.
Provision of all temporary lighting, power, water and other services required by the
Mechanical Contractor
Provision of tundishes for condensate drains where shown on the mechanical drawings.
501 General
All items of driven equipment shall be mounted on vibration bases.
They shall be equipped with spring or rubber vibration mounts to give sufficient deflection to
provide not less than 95% vibration isolation.
502 Equipment
All rotating equipment when complete as a fully assembly shall be statically and dynamically
balanced.
All ductwork shall be manufactured from best quality galvanised sheet metal.
As a minimum requirement, the ductwork shall be supplied and installed in accordance with
the "Low Pressure Duct Construction Standards", (5th Edition -1976), as published by the
SMACNA Association.
Ductwork to comply with the fire hazard properties of AS4254.
Suitable balancing devices shall be provided to all grilles and registers to achieve the
specified air quantities.
Ceiling diffusers shall be of the louvred-face type with removable covers. The style shall
match the ceiling type, as applicable unless noted on the drawings. Opposed blade dampers
shall be included.
Side wall, supply-air registers unless noted, shall have individually adjustable horizontal and
vertical blades unless noted on the drawings. Opposed blade dampers shall be included
unless otherwise noted.
Ceiling, return-air grilles shall be of the 15mm square pattern, egg-crate type.
All air outlets and grilles shall be provided with acoustically lined cushion head boxes.
All air outlets and grilles shall be either anodised aluminium or baked enamel to the required
colour, or prime coated, as selected by the Engineer or Superintendent. All visible surfaces
behind outlets and grilles shall be painted matt black.
All air grilles shall be balanced to with +- 10% of the supply specified air quantity. Air
quantities in the main supply air ducts shall also be measured. All air balancing shall include
a N.E.B.B. or N.A.T.A. certification.
These procedures shall be performed under the inspection of the Engineer, and shall be
completed to his satisfaction.
The systems shall be set in operation and left to operate under Automatic Control for a period
of two weeks, prior to practical completion.
St Teresa of Kolkata Primary School Stage 2 Project No: 135
It is the intention that the systems shall be fully tested and commissioned prior to this, the two
week period being used to demonstrate the correct operation of the system under normal
automatic control.
Failure to comply with this Clause will result in Practical Completion being delayed, until this is
achieved.
Prior to Practical Completion, three sets of the Mechanical Services Maintenance Manuals
shall be provided in hard copy and in digital copy (PDF). (No draft copies will be accepted
for approval.) These shall be in vinyl-covered, hard-backed folders, appropriately labelled.
Digital copies (PDF) of the Mechanical Services manuals are to be provided as one combined
manual for review. A link containing folders with information will not be reviewed.
Manuals will be reviewed by the Consultant a maximum of two times. Any further review will
incur a cost to the Contractor at the Consultant’s hourly rate.
The fan coil units shall be controlled via a wall mounted wired controllers, supplied by the
manufacturer and installed generally as indicated on the drawings, with consultation on site
with the Architect.
The building to be provided with wall mounted central controller as denoted on the
drawings.
903 Ductwork Connections
Flexible connections shall be provided between the unit and the supply and return air
ductwork, complete with weatherproof covers on the top and two sides where located on roof.
904 Condensate Drain
Provide a trapped condensate drain from the unit to the nearest waste.
905 Mountings
The unit shall be mounted on rubber in shear anti-vibration eliminators to prevent the
transmission of noise or vibration to the building.
PART 10 FANS
1001 General
Provide all fans, as shown on the Drawings
These shall include all associated wiring and controls.
Where shown on the drawings, the system shall be complete with all ductwork and registers.
The static pressures, as scheduled, are for tendering purposes only. The Contractor shall
calculate the actual static pressures.
1002 Fans
Fans shall be of the axial or centrifugal type, as scheduled.
Vermin-proof mesh shall be provided on all fans that are mounted out of doors.
Roof mounted fans shall incorporate a moulded base that forms a weatherproof skirt and is
suitable for mounting on a kerb proved by the Builder. An integral wiring conduit shall be
provided from the motor compartment to under the weatherproof skirt.