Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Sub Duct Mid 220 47.8K

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

SUBMITTAL DATA

TVR Ultra - Medium Static Pressure Duct


47.8kBtu/h – 220-240V/1Ph/50-60Hz DC Motor
.
Model: 4TVD0048EF000AA

Job Name: Date:

Reference: Location:

Commercial Air Conditioner > TVR ULTRA > Indoor Unit > Medium Static Pressure Duct

 Overall Dimensions

© 2020 Trane All rights reserved Page 1 of 3 SUB-DUCT-MID-220-47.8K-2020-R00


SUBMITTAL DATA
TVR Ultra - Medium Static Pressure Duct
47.8kBtu/h – 220-240V/1Ph/50-60Hz DC Motor
.
Model: 4TVD0048EF000AA

 Installation Space Requirements

© 2020 Trane All rights reserved Page 2 of 3 SUB-DUCT-MID-220-47.8K-2020-R00


SUBMITTAL DATA
TVR Ultra - Medium Static Pressure Duct
47.8kBtu/h – 220-240V/1Ph/50-60Hz DC Motor
.
Model: 4TVD0048EF000AA

 Specifications

Model nam e 4TVD0048EF000AA


Pow er supply 1-phase, 220-240V, 50/60Hz
kW 14
Capacity
Cooling1 kBut/h 47.8
Input W 250
kW 15.5
Capacity
Heating2 kBut/h 52.9
Input W 250
Model ZKFP-240-8-1
Type DC
Fan motor
Brand Nidec/Welling/Match-Well
Speed (H/M/L) r/min 1060/1010/960/910/860/810/760
Number of row s 4
Tube pitch × row pitch mm 21×13.37
Fin spacing mm 1.5
Coil Fin type Hydrophilic aluminum
Tube OD and type mm Ф7 Inner groove
Dimensions (L×H ×W) mm 1030×378×58
Number of circuits 8
Airflow rate3 m3/h 1960/1860/1760/1660/1560/1460/1360
External static pressure4 Pa 40 (30~150)
Sound pressure level5 dB(A) 41/39/38/37/36/35/33
Net dimensions 6 (W×H×D) mm 1290x300x865
Unit Packed dimensions (W×H×D) mm 1400x375x925
Net/Gross w eight kg 46.5/55.5
Refrigerant type R410A
Type Electronic expansion valve
Throttle
Model D20MISZ-1R(L)
Design pressure (H/L) MPa 4.4/2.6
Liquid/Gas pipe mm Ф9.53/Ф15.9
Pipe connections
Drain pipe mm OD Ф25

Notes:

1. Indoor air temperature 27°C DB, 19°C WB; outdoor air temperature 35°C DB; equivalent refrigerant piping length
7.5m with zero level difference.
2. Indoor air temperature 20°C DB; outdoor air temperature 7°C DB, 6°C WB; equivalent refrigerant piping length
7.5m with zero level difference.
3. Diameters given are those of the unit's stop valve.
4. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic
chamber.

Trane optimizes the performance of homes and buildings around the world.
The leader in creating and sustaining safe, comfortable and energy efficient environments.
Broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts.

For more information, visit www.trane.com.

© 2020 Trane All rights reserved Page 3 of 3 SUB-DUCT-MID-220-47.8K-2020-R00