Tta LT Panels

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 6

Sr. NO. ITEM DESCRIPTION QTY.

1 MAIN LT PANEL (TTA) 1


MAIN PANEL Fabrication, supply, erection, testing and commissioningof Type Tested Assembly (TTA) cubicle type (panel and all switch gears should be type tested and certification
should be submitted) as per IEC 61439 and internal arc test as per IEC 61641, dust and vermin proof, floor mounted, front operated MV Main panel board made out of 14 SWG thick
CRCA sheet (7 tank treatment) fully compartmentalised complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable
gland plates made out of 3mm thick sheet steel including all componentsas shown in the schematic drawing. All opening parts of the panel shall be sealable. This panel should include
Pluggable type surge arrester Class B & Class C / Class 1 & Class 2 as per IEC 61643 (IP 20) with potential free contact, completely assembled enclosure & provision for inbuilt
common remote indication for defective arresters 3 nos of encapsulated spark gap & 3 nos of single large block of MOV with series thermal fuse and cooling gel to connect between
Line and Neutral and one number arrester encapsulated spark gap type to connect between Neutral and Earth of following ratings including base element & pluggable arresters.
Nominal voltage - 230V 50Hz, Impulse current-150 KA (10/350µ sec) & 60KA (8/20µ sec) for Line to Neutral & 125 KA(10/350µ sec) for Neutral to Protective Earth, voltage
protection level <1.3 KV ( L to N) & <1.3 KV (N to E). Operating temp -40º to
+85ºC. Response time <100 nano secincluding necessary MCCB for protection of same. Providing all connectionsand interconnectionsas required and providing all assecories as 1
required for complete installation as instructed by engineer in charge/consultant and as shown in the schematic layout provided. Incomers EB Incomer 1 & 2 - 1000A, 50kA, FP, EDO
Microprocessor based ACB with 3 O/C and 1 E/F releases. Standby low set E/F relay with CT at neutral earthing conductor, O/V relay with primary trip - 2 Set. DG Feeder 1
& 2 - 1000A, 50kA, FP, EDO Microprocessor based ACB with overload and E/F release Standby low set E/F relay with CT at neutral earthing conductor - 2 Sets. 2000A 415V, 50kA
best conductivity Al TPN bus bar with SMC supports, heat shrinkable sleeves etc complete as required. Necessary interlocking arrangement. ( complete specification as detailed in
Part C - Schedule of Quantities)

2 DG SYNCHRONIZATION PANEL (TTA) 1


DG SYNCHRONIZATION PANEL Fabrication, supply, erection, testing and commissioning of Type Tested Assembly (TTA) cubicle type (panel and all switch gears should
be type tested and certification should be submitted) as per IEC 61439 and internal arc test as per IEC 61641, dust and vermin proof, floor mounted, front operated MV Main panel
board made out of 14 SWG thick CRCA sheet (7 tank treatment) fully compartmentalisedcomplete with hinged and earthed front doors with name plate, danger notice board, heavy
duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel includingall componentsas shown in the schematic drawing. All opening parts of the panel shall be
sealable. Incomers DG Incomer 1 & 2 - 800A, 50 kA, TP, EDO, ACB Microprocessor based with thermal O/L, voltage controlled O/C relay, over voltage, under voltage, negative
sequence, low set stand by earth fault relays and ref/differential relay + Neutral contactor - 2 Set; DG Incomer 3 - 400A, 50 kA, 4P, MCCB Microprocessor based with thermal O/L,
voltage controlled O/C relay, over voltage, under voltage, negative sequence, low set stand by earth fault relays and ref/differential relay + TP Power contactor + Neutral contactor
- 1 Set; 2000A 415V, 50kA best conductivity Al TPN bus bar with SMC supports, heat shrinkable sleeves etc complete as required. Necessary interlocking arrangement;
Multi function digital LED meters with accuracy class 1, with necessary CT and accessories for measuring Voltage,Current, Frequency, kW, KVA, kVAr, kWh, kVAh, kVArh, PF,
Runhr, Onhr, Interupts, Phase angle, THD, Neutral current, Max Demand (with RTC), Events (high-low) with time stamp, Individual Harmonics upto 31st, Meter with Ethernet port - 1
3 Set; Supply, erection, testing & commisioningof PLC based synchronising system for 4 Nos DG set with PLC and Synchronization Relay module of approve make - 3 Nos,
including necessary SMPS, AUX contactor or Relay, Relay Module, DIN Rail, Selector Switch, Push Button, Terminal, Indication lamp, Legs, End plate, Stopper, 1.5 Ferule, Screw,
Neutral link, 2.5 Sqmm wire, 1.5 Sqmm wire, Cable tie, Tie mount and all other accesories and componets as required for complete installation and as instructed by engineer in
charge/consultant.; RYB phase indicating LED lamps with control fuses and switches - 3 set.; 2000A, FP, 50kA, EDO Microprocessor based ACB as Buscoupler - 2 Nos. Outgoings
1000A, 50kA, FP, EDO Microprocessor Based ACB - 3 Nos; Supply, Installation, testing and commisioning

3 HVAC MAIN PANEL 1


HVAC MAIN PANEL Fabrication, supply, erection testing and commissionin of Type Tested Assembly (TTA)
cubicle type (panel and all switch gears should be type tested and certification should be submitted) as per IEC 61439 and internal arc test as per IEC 61641, dust and vermin proof,
floor mounted, front operated MV panel board made out of 14 SWG thick CRCA sheet (7 tank treatment) fully compartmentalised complete with hinged and earthed front doors
with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel includingall componentsas shown in the schematic
drawing. All opening parts of the panel shall be sealable. This panel should include pluggable type surge arrester in suitable enclosure Class B+C / Class 1+2 as per IEC 61643 (IP
20) with potential free contact, thermal dis connector & provision for inbuilt common remote indication for defective arresters to connect between Line and Neutral and one
number arrester Spark Gap type to connect between Neutral and Earth of following ratings including base element & pluggable arresters. Nominal voltage -230V 50Hz, type single
MOV with built in thermal fuse and cooling gel(L to N) & spark gap encapsulated / non exhausting (N to E)
. Lightning Impulse Current - 21 kA (10/350µ sec) for Line to Neutral & 25 kA(10/350µ sec) for Neutral to Earth,Nominal discharge current-30 kA (8/20µ sec) for Line to
Neutral & 40 kA(8/20µ sec) for Neutral to Earth, max discharge current 150 kA (8/20µ sec) for Line to Neutral & 50 kA(8/20µ sec) for Neutral to Earth. Voltage protection level
1300V (L to N) & 1200V (N to E). Operating temp -40º to +80ºC. Response time <25 nano sec (L to N), < 100 nano sec (N to E) DIN rail mountingtype etc complete with back up
1
fuse as required and as directed. Incomer - 630 A, TPN, MCCB Isolator - 1 No. 630A 433V, 50kA best conductivityextensible Al TPN bus bar with SMC supports, heat shrinkable
sleeves etc complete as required. Necessary interlocking arrangement. Multi function digital LED meters with accuracy class 1, with necessary CT and accessories for measuring
Voltage, current, Frequency, Power Factor, kW, kVA, Old energy, On hours, site selectable kWh/kVAh. Class B+C / Class 1 + 2 Surge arrestor device with necessary MCCB for
protection of same - 1 No. RYB phase indicating LED lamps with control fuses and switches - 1 set. Outgoings : 250A, 25kA, TP Termal Magnetic Based MCCB - 5 Nos.
Supply, Installation, testing and
commisionin

4 MEDICAL EQUIPMENT PANEL 1


MEDICAL EQUIPMENT PANEL Fabrication, supply, erection, testing and commissioning of Type Tested Assembly (TTA) cubicle type (panel and all switch gears should
be type tested and certification should be submitted) as per IEC 61439 and internal arc test as per IEC 61641, dust and vermin proof, floor mounted, front operated MV panel board
made out of 14 SWG thick CRCA sheet (7 tank treatment) fully compartmentalised complete with hinged and earthed front doors with name plate, danger notice board, heavy duty
rubber gaskets, removable gland plates made out of 3mm thick sheet steel including all components as shown in the schematic drawing. All opening parts of the panel shall be sealable.
This panel should include pluggable type surge arrester in suitable enclosure Class B+C / Class 1+2 as per IEC 61643 (IP 20) with potential free contact, thermal dis connector &
provision for inbuilt common remote indication for defective arresters to connect between Line and Neutral and one number arrester Spark Gap type to connect between Neutral
and Earth of following ratings including base element& pluggable arresters. Nominal voltage 230V 50Hz, type single MOV with built in thermal fuse and cooling gel(L to N) &
spark gap encapsulated / non exhausting (N to E) . Lightning Impulse Current - 21 kA (10/350µ sec) for Line to Neutral & 25 kA(10/350µ sec) for Neutral to Earth,Nominal
discharge current-30 kA (8/20µ sec) for Line to Neutral & 40 kA(8/20µ sec) for Neutral to Earth, max discharge current 150 kA (8/20µ sec) for Line to Neutral & 50 kA(8/20µ sec) for
Neutral to Earth. Voltage protection level 1300V (L to N) & 1200V (N to E). Operating temp -40º to +80ºC. Response time <25 nano sec (L to N), < 100 nano sec (N to E) DIN 1
rail mounting type etc complete with back up fuse as required and as directed. Incomer - 500 A, TPN, MCCB Isolator - 1 No. 500A 433V, 50kA best conductivity extensible Al
TPN bus bar with SMC supports, heat shrinkable sleeves etc complete as required. Necessary interlocking arrangement. Multi function digital LED meters with accuracy class 1,
with necessary CT and accessories for measuring Voltage, current, Frequency, Power Factor, kW, kVA, Old energy, On hours, site selectable kWh/kVAh. Class B+C / Class 1 +
2 Surge arrestor device with necessary MCCB for protection of same - 1 No. RYB phase indicating LED lamps with control fuses and switches - 1 set. Outgoings 250A, 25kA, TP
Termal Magnetic Based MCCB - 2 Nos.; 100A, 25kA, TP Termal Magnetic Based MCCB - 2 Nos.; Supply, Installation, testing and commisioning

5 COMMON SERVICE PANEL 1


COMMON SERVICE PANEL Fabrication, supply, erection, testing and commissionin of Type Tested Assembly
(TTA) cubicle type (panel and all switch gears should be type tested and certification should be submitted) as per IEC 61439 and internal arc test as per IEC 61641, dust and
vermin proof, floor mounted, front operated MV common Service panel board made out of 14 SWG thick CRCA sheet (7 tank treatment) fully compartmentalisedcomplete with
hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel includingall
componentsas shown in the schematic drawing. All opening parts of the panel shall be sealable. Incomer - 500 A FP MCCB Isolator - 1 No. 500A 433V, 36kA, best
conductivity extensible TPN Al bus bar with SMC supports, heat shrinkable sleeves etc complete as required with necessary interlocking arrangement. Multi function digital
LED meters with accuracy class 1, with necessary CT and accessories for measuring Voltage, current, Frequency, Power Factor, kW, kVA, Old energy, On hours, site selectable 1
kWh/kVAh 1Set. RYB phase indicating LED lamps with control fuses and switches - 1 set. Outgoings 250A 25kA TP Termal Magnetic Based MCCB - 2 Nos.; 125A 25kA TP
Termal Magnetic Based MCCB - 2 Nos.; 100A 25kA TP Termal Magnetic Based MCCB - 1 No., 40A 25kA TP Termal Magnetic Based MCCB - 1 No., Supply, Installation,
testing
and commisionin
6 LIFT PANEL-1 1
LIFT PANEL 1 Fabrication, supply, erection, testing and commissioning of Type Tested Assembly (TTA) cubicle type (panel and all switch gears should be type tested and
certification should be submitted) as per IEC 61439 and internal arc test as per IEC 61641, dust and vermin proof, floor mounted, front operated MV panel board made out of 16
SWG thick CRCA sheet (7 tank treatment) fully compartmentalisedcomplete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets,
removable gland plates made out of 3mm thick sheet steel including all componentsas shown in the schematic drawing. All opening parts of the panel shall be sealable. This panel
should include pluggable type surge arrester in suitable enclosure Class B+C/ Class 1+2 as per IEC 61643 (IP 20) with potential free contact, thermal dis connector & provision for
inbuilt common remote indication for defective arresters to connect between Line and Neutral and one number arrester Spark Gap type to connect between Neutral and Earth of
following ratings including base element & pluggable arresters. Nominal voltage -230V 50Hz, type single MOV with built in thermal fuse and cooling gel(L to N) & spark
gap encapsulated / non exhausting (N to E) . Lightning Impulse Current - 21 kA (10/350µ sec) for Line to Neutral & 25 kA(10/350µ sec) for Neutral to Earth,Nominal
discharge current-30 kA (8/20µ sec) for Line to Neutral & 40 kA(8/20µ sec) for Neutral to Earth, max discharge current 150 kA (8/20µ sec) for Line to Neutral & 50 kA(8/20µ sec) for
Neutral to Earth. Voltage protection level 1300V (L to N) & 1200V (N to E). Operating temp -40º to +80ºC. Response time <25 nano sec (L to N), < 100 nano sec (N to E) DIN rail 1
mountingtype etc complete with back up fuse as required and as directed. Incomer - 125A, FP MCCB Isolator - 1No. 125A, 415V, 25 kA best conductivity Al TPN bus barwith
SMC supports, heat shrinkable sleeves etc complete as required. Multi function digital LED meters with accuracy class 1, with necessary CT and accessories for measuring
Voltage, current, Frequency, Power Factor, kW, kVA, Old energy, On hours, site selectable kWh/kVAh - 1Set; Class B+C / Class 1+2 Surge arrestor device with necessary MCCB for
protection of same - 1 No.; RYB phase indicating LED lamps with control fuses and switches - 1 set.; Outgoing 63A, 16kA, TP, Thermal Magnetic Releas MCCB - 3 Nos.;
25A DP MCB - 2 Nos. Supply, Installation, testing and commisioning

7 LIFT PANEL-2 1
LIFT PANEL 2 Fabrication, supply, erection, testing and commissioning of Type Tested Assembly (TTA) cubicle type (panel and all switch gears should be type tested and
certification should be submitted) as per IEC 61439 and internal arc test as per IEC 61641, dust and vermin proof, floor mounted, front operated MV panel board made out of 16
SWG thick CRCA sheet (7 tank treatment) fully compartmentalisedcomplete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets,
removable gland plates made out of 3mm thick sheet steel including all componentsas shown in the schematic drawing. All opening parts of the panel shall be sealable. This panel
should include pluggable type surge arrester in suitable enclosure Class B+C/ Class 1+2 as per IEC 61643 (IP 20) with potential free contact, thermal dis connector & provision for
inbuilt common remote indication for defective arresters to connect between Line and Neutral and one number arrester Spark Gap type to connect between Neutral and Earth of
following ratings including base element & pluggable arresters. Nominal voltage -230V 50Hz, type single MOV with built in thermal fuse and cooling gel(L to N) & spark
gap encapsulated / non exhausting (N to E) . Lightning Impulse Current - 21 kA (10/350µ sec) for Line to Neutral & 25 kA(10/350µ sec) for Neutral to Earth,Nominal
discharge current-30 kA (8/20µ sec) for Line to Neutral & 40 kA(8/20µ sec) for Neutral to Earth, max discharge current 150 kA (8/20µ sec) for Line to Neutral & 50 kA(8/20µ sec) for
Neutral to Earth. Voltage protection level 1300V (L to N) & 1200V (N to E). Operating temp -40º to +80ºC. Response time <25 nano sec (L to N), < 100 nano sec (N to E) DIN rail 1
mountingtype etc complete with back up fuse as required and as directed. Incomer - 160A, FP, MCCB Isolator - 1No. 160A, 415V, 25 kA best conductivity Al TPN bus
barwith SMC supports, heat shrinkable sleeves etc complete as required. Multi function digital LED meters with accuracy class 1, with necessary CT and accessories for measuring
Voltage, current, Frequency, Power Factor, kW, kVA, Old energy, On hours, site selectable kWh/kVAh - 1Set; Class B+C / Class 1+2 Surge arrestor device with necessary MCCB
for protection of same - 1 No.; RYB phase indicating LED lamps with control fuses and switches - 1 set. Outgoing 63A, 16kA, TP, Thermal Magnetic Releas MCCB - 4 Nos.; 25A
DP MCB - 3 Nos.; Supply, Installation, testing and commisioning

8 LIFT PANEL-3 1
LIFT PANEL 3 Fabrication, supply, erection, testing and commissioning of Type Tested Assembly (TTA) cubicle type (panel and all switch gears should be type tested and
certification should be submitted) as per IEC 61439 and internal arc test as per IEC 61641, dust and vermin proof, floor mounted/wallmounted, front operated MV panel board made
out of 16 SWG thick CRCA sheet (7 tank treatment) fully compartmentalisedcomplete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber
gaskets, removable gland plates made out of 3mm thick sheet steel including all components as shown in the schematic drawing. All opening parts of the panel shall be sealable. This
panel should include pluggable type surge arrester in suitable enclosure Class B+C/ Class 1+2 as per IEC 61643 (IP 20) with potential free contact, thermal dis connector & provision
for inbuilt common remote indication for defective arresters to connect between Line and Neutral and one number arrester Spark Gap type to connect between Neutral and Earth of
following ratings including base element & pluggable arresters. Nominal voltage -230V 50Hz, type single MOV with built in thermal fuse and cooling gel(L to N) & spark gap
encapsulated / non exhausting (N to E)
. Lightning Impulse Current - 21 kA (10/350µ sec) for Line to Neutral & 25 kA(10/350µ sec) for Neutral to Earth,Nominal discharge current-30 kA (8/20µ sec) for Line to
Neutral & 40 kA(8/20µ sec) for Neutral to Earth, max discharge current 150 kA (8/20µ sec) for Line to Neutral & 50 kA(8/20µ sec) for Neutral to Earth. Voltage protection level
1300V (L to N) & 1200V (N to E). Operating temp -40º to +80ºC. Response time <25 nano sec (L to N), < 100 nano sec (N to E) DIN rail mounting type etc complete with back up 1
fuse as required and as directed. Incomer - 80A, FP MCCB Isolator - 1No. 80A, 415V, 25 kA best conductivity Al TPN bus bar with SMC supports, heat shrinkable sleeves etc
complete as required. Multi function digital LED meters with accuracy class 1, with necessary CT and accessories for measuring Voltage, current, Frequency, Power Factor, kW,
kVA, Old energy, On hours, site selectable kWh/kVAh - 1Set. Class B+C/ Class 1+2 Surge arrestor device with necessary MCCB for protection of same - 1 No. ; RYB phase
indicating LED lamps with control fuses and switches - 1 set. Outgoing 63A, 16kA, TP, Thermal
Magnetic Releas MCCB - 1 Nos.; 25A DP MCB - 1 No.; Supply, Installation, testing and commisioning

9 PLUMBING PANEL 1
PLUMBING PANEL - Fabrication, supply, erection, testing and commissionin of Type Tested Assembly (TTA)
cubicle type (panel and all switch gears should be type tested and certification should be submitted) as per IEC 61439 and internal arc test as per IEC 61641, dust and vermin proof,
floor mounted, front operated MV panel board made out of 16 SWG thick CRCA sheet (7 tank treatment) fully compartmentalised complete with hinged and earthed front doors
with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel includingall componentsas shown in the schematic
drawing. All opening parts of the panel shall be sealable. Incomer - 125 A FP MCCB Isolator - 1 No. 125A, 433V, 25kA, best conductivity extensible Al TPN bus bar with SMC
supports, heat shrinkable sleeves etc complete as required. Necessary interlocking arrangement. Multi function digital LED meters with accuracy class 1, with necessary CT and
accessories for measuring Voltage, current, Frequency, Power Factor, kW, kVA, Old energy, On hours, site selectable kWh/kVAh. RYB phase indicating LED lamps with control 1
fuses and switches - 1 set. Outgoings 63A, 16kA, TP MPCB - 2 Nos. ; 50A, 16kA, TP MPCB - 1 No.; 32A, 16kA, TP MPCB - 2 Nos.; 16A, 16kA, TP MPCB - 3 Nos.;
Supply, Installation, testing and
commisionin

10 UPS INPUT PANEL 1


UPS INPUT PANEL Fabrication, supply, erection, testing and commissioning of Type Tested Assembly (TTA) cubicle type (panel and all switch gears should be type tested
and certification should be submitted) as per IEC 61439 and internal arc test as per IEC 61641, dust and vermin proof, floor mounted, front operated MV panel board made out of 16
SWG thick CRCA sheet (7 tank treatment) fully compartmentalised complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets,
removable gland plates made out of 3mm thick sheet steel including all components as required. All opening parts of the panel shall be sealable.This panel should include pluggable
type surge arrester in suitable enclosure Class B+C/ Class 1+2 as per IEC 61643 (IP 20) with potential free contact, thermal dis connector & provision for inbuilt common remote
indication for defective arresters to connect between Line and Neutral and one number arrester Spark Gap type to connect between Neutral and Earth of following ratings including
base element & pluggable arresters. Nominal voltage -230V 50Hz, type single MOV with built in thermal fuse and cooling gel(L to N) & spark gap encapsulated / non exhausting (N
to E) . Lightning Impulse Current - 21 kA (10/350µ sec) for Line to Neutral & 25 kA(10/350µ sec) for Neutral to Earth,Nominal discharge current-30 kA (8/20µ sec) for Line to
Neutral & 40 kA(8/20µ sec) for Neutral to Earth, max discharge current 150 kA (8/20µ sec) for Line to Neutral & 50 kA(8/20µ sec) for Neutral to Earth. Voltage protection level 1
1300V (L to N) & 1200V (N to E). Operating temp -40º to +80ºC. Response time <25 nano sec (L to N), < 100 nano sec (N to E) DIN rail mounting type etc complete with back up
fuse as required and as directed. Incomer - 400A, 36kA, FP TM Based MCCB - 1No. 400A 433V, 36kA best conductivity Al TPN bus bar with SMC supports, heat shrinkable
sleeves etc complete as required. RYB phase indicating LED lamps with control fuses and switches - 1 set. Outgoing 250A, 36kA, TP, MCCB - 3 Nos. Supply, Installation,
testing and commisioning

11 UPS OUTPUT PANEL 1


UPS OUTPUT PANEL Fabrication, supply, erection, testing and commissioning of Type Tested Assembly (TTA) cubicle type (panel and all switch gears should be type tested and
certification should be submitted) as per IEC 61439 and internal arc test as per IEC 61641, dust and vermin proof, floor mounted, front operated MV panel board made out of 16
SWG thick CRCA sheet (7 tank treatment) fully compartmentalised complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets,
removable gland plates made out of 3mm thick sheet steel including all components as required. All opening parts of the panel shall be sealable. Incomer - 400A, 36kA, FP TM
1
Based MCCB - 2No. 400A 433V, 36kA best conductivity Al TPN bus bar with SMC supports, heat shrinkable sleeves etc complete as required. RYB phase indicating LED lamps
with control fuses and switches - 1 set. Outgoing 200A FP 36kA TM Based MCCB - 3 Nos. Supply, Installation, testing and commisioning
UNIT

Each

Each

Each

Each

Each
Each

Each

Each

Each

Each
Each