7 LIFT PANEL-2 1
LIFT PANEL 2 Fabrication, supply, erection, testing and commissioning of Type Tested Assembly (TTA) cubicle type (panel and all switch gears should be type tested and
certification should be submitted) as per IEC 61439 and internal arc test as per IEC 61641, dust and vermin proof, floor mounted, front operated MV panel board made out of 16
SWG thick CRCA sheet (7 tank treatment) fully compartmentalisedcomplete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets,
removable gland plates made out of 3mm thick sheet steel including all componentsas shown in the schematic drawing. All opening parts of the panel shall be sealable. This panel
should include pluggable type surge arrester in suitable enclosure Class B+C/ Class 1+2 as per IEC 61643 (IP 20) with potential free contact, thermal dis connector & provision for
inbuilt common remote indication for defective arresters to connect between Line and Neutral and one number arrester Spark Gap type to connect between Neutral and Earth of
following ratings including base element & pluggable arresters. Nominal voltage -230V 50Hz, type single MOV with built in thermal fuse and cooling gel(L to N) & spark
gap encapsulated / non exhausting (N to E) . Lightning Impulse Current - 21 kA (10/350µ sec) for Line to Neutral & 25 kA(10/350µ sec) for Neutral to Earth,Nominal
discharge current-30 kA (8/20µ sec) for Line to Neutral & 40 kA(8/20µ sec) for Neutral to Earth, max discharge current 150 kA (8/20µ sec) for Line to Neutral & 50 kA(8/20µ sec) for
Neutral to Earth. Voltage protection level 1300V (L to N) & 1200V (N to E). Operating temp -40º to +80ºC. Response time <25 nano sec (L to N), < 100 nano sec (N to E) DIN rail 1
mountingtype etc complete with back up fuse as required and as directed. Incomer - 160A, FP, MCCB Isolator - 1No. 160A, 415V, 25 kA best conductivity Al TPN bus
barwith SMC supports, heat shrinkable sleeves etc complete as required. Multi function digital LED meters with accuracy class 1, with necessary CT and accessories for measuring
Voltage, current, Frequency, Power Factor, kW, kVA, Old energy, On hours, site selectable kWh/kVAh - 1Set; Class B+C / Class 1+2 Surge arrestor device with necessary MCCB
for protection of same - 1 No.; RYB phase indicating LED lamps with control fuses and switches - 1 set. Outgoing 63A, 16kA, TP, Thermal Magnetic Releas MCCB - 4 Nos.; 25A
DP MCB - 3 Nos.; Supply, Installation, testing and commisioning
8 LIFT PANEL-3 1
LIFT PANEL 3 Fabrication, supply, erection, testing and commissioning of Type Tested Assembly (TTA) cubicle type (panel and all switch gears should be type tested and
certification should be submitted) as per IEC 61439 and internal arc test as per IEC 61641, dust and vermin proof, floor mounted/wallmounted, front operated MV panel board made
out of 16 SWG thick CRCA sheet (7 tank treatment) fully compartmentalisedcomplete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber
gaskets, removable gland plates made out of 3mm thick sheet steel including all components as shown in the schematic drawing. All opening parts of the panel shall be sealable. This
panel should include pluggable type surge arrester in suitable enclosure Class B+C/ Class 1+2 as per IEC 61643 (IP 20) with potential free contact, thermal dis connector & provision
for inbuilt common remote indication for defective arresters to connect between Line and Neutral and one number arrester Spark Gap type to connect between Neutral and Earth of
following ratings including base element & pluggable arresters. Nominal voltage -230V 50Hz, type single MOV with built in thermal fuse and cooling gel(L to N) & spark gap
encapsulated / non exhausting (N to E)
. Lightning Impulse Current - 21 kA (10/350µ sec) for Line to Neutral & 25 kA(10/350µ sec) for Neutral to Earth,Nominal discharge current-30 kA (8/20µ sec) for Line to
Neutral & 40 kA(8/20µ sec) for Neutral to Earth, max discharge current 150 kA (8/20µ sec) for Line to Neutral & 50 kA(8/20µ sec) for Neutral to Earth. Voltage protection level
1300V (L to N) & 1200V (N to E). Operating temp -40º to +80ºC. Response time <25 nano sec (L to N), < 100 nano sec (N to E) DIN rail mounting type etc complete with back up 1
fuse as required and as directed. Incomer - 80A, FP MCCB Isolator - 1No. 80A, 415V, 25 kA best conductivity Al TPN bus bar with SMC supports, heat shrinkable sleeves etc
complete as required. Multi function digital LED meters with accuracy class 1, with necessary CT and accessories for measuring Voltage, current, Frequency, Power Factor, kW,
kVA, Old energy, On hours, site selectable kWh/kVAh - 1Set. Class B+C/ Class 1+2 Surge arrestor device with necessary MCCB for protection of same - 1 No. ; RYB phase
indicating LED lamps with control fuses and switches - 1 set. Outgoing 63A, 16kA, TP, Thermal
Magnetic Releas MCCB - 1 Nos.; 25A DP MCB - 1 No.; Supply, Installation, testing and commisioning
9 PLUMBING PANEL 1
PLUMBING PANEL - Fabrication, supply, erection, testing and commissionin of Type Tested Assembly (TTA)
cubicle type (panel and all switch gears should be type tested and certification should be submitted) as per IEC 61439 and internal arc test as per IEC 61641, dust and vermin proof,
floor mounted, front operated MV panel board made out of 16 SWG thick CRCA sheet (7 tank treatment) fully compartmentalised complete with hinged and earthed front doors
with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel includingall componentsas shown in the schematic
drawing. All opening parts of the panel shall be sealable. Incomer - 125 A FP MCCB Isolator - 1 No. 125A, 433V, 25kA, best conductivity extensible Al TPN bus bar with SMC
supports, heat shrinkable sleeves etc complete as required. Necessary interlocking arrangement. Multi function digital LED meters with accuracy class 1, with necessary CT and
accessories for measuring Voltage, current, Frequency, Power Factor, kW, kVA, Old energy, On hours, site selectable kWh/kVAh. RYB phase indicating LED lamps with control 1
fuses and switches - 1 set. Outgoings 63A, 16kA, TP MPCB - 2 Nos. ; 50A, 16kA, TP MPCB - 1 No.; 32A, 16kA, TP MPCB - 2 Nos.; 16A, 16kA, TP MPCB - 3 Nos.;
Supply, Installation, testing and
commisionin
Each
Each
Each
Each
Each
Each
Each
Each
Each
Each
Each