Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

belimodatasheet

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Technical data sheet TFB120

Basic Fail-Safe actuator for controlling dampers


in typical commercial HVAC applications.

• Torque motor 22 in-lb [2.5 Nm]


• Nominal voltage AC 100...240 V
• Control On/Off

Technical data

Electrical data Nominal voltage AC 100...240 V


Nominal voltage frequency 50/60 Hz
Nominal voltage range AC 85...265 V
Power consumption in operation 2.5 W
Power consumption in rest position 1.3 W
Transformer sizing 5 VA
Electrical Connection 18 GA appliance cable, 3 ft [1 m], with 1/2"
NPT conduit connector
Overload Protection electronic throughout 0...95° rotation
Electrical Protection actuators are double insulated

Functional data Torque motor 22 in-lb [2.5 Nm]


Direction of motion motor selectable by ccw/cw mounting
Direction of motion fail-safe reversible with cw/ccw mounting
Angle of rotation Max. 95°
Angle of rotation note adjustable with mechanical stop
Running Time (Motor) 75 s
Running time fail-safe <25 s @ -4...122°F [-20...50°C], <60 s @ -22°F
[-30°C]
Noise level, motor 50 dB(A)
Noise level, fail-safe 62 dB(A)
Position indication Mechanical

Safety data Degree of protection IEC/EN IP42


Degree of protection NEMA/UL NEMA 2
Enclosure UL Enclosure Type 2
Agency Listing cULus acc. to UL60730-1A/-2-14, CAN/CSA
E60730-1:02
CE acc. to 2014/30/EU and 2014/35/EU
Quality Standard ISO 9001
UL 2043 Compliant Suitable for use in air plenums per Section
300.22(C) of the NEC and Section 602 of the
IMC
Ambient humidity Max. 95% RH, non-condensing
Ambient temperature -22...122°F [-30...50°C]
Storage temperature -40...176°F [-40...80°C]
Servicing maintenance-free

Weight Weight 1.8 lb [0.83 kg]

www.belimo.com TFB120 • en-us • 2024-08-20 • Subject to change 1/4


Technical data sheet TFB120

Technical data

Materials Housing material UL94-5VA

Footnotes †Rated Impulse Voltage 4kV, Type of action 1.AA, Control Pollution Degree 3.

Product features

Application For On/Off, fail-safe control of dampers in HVAC systems. Actuator sizing should be done in
accordance with the damper manufacturer’s specifications. Control is On/Off from an auxiliary
contact, or a manual switch. The actuator is mounted directly to a damper shaft from 1/4” up
to 1/2” in diameter by means of its universal clamp, 1/2” shaft centered at delivery. A crank
arm and several mounting brackets are available for applications where the actuator cannot
be direct coupled to the damper shaft.

Operation The TF series actuators provide true spring return operation for reliable fail-safe application
and positive close off on air tight dampers. The spring return system provides consistent
torque to the damper with, and without, power applied to the actuator. The TF series provides
95° of rotation and is provided with a graduated position indicator showing 0° to 90°. The
actuator may be stalled anywhere in its normal rotation without the need of mechanical end
switches. Power consumption is reduced in holding mode. The actuator is double insulated so
an electrical ground connection is not necessary.
Safety Note: Screw a conduit fitting into the actuator’s bushing. Jacket the actuator’s input and
output wiring with suitable flexible conduit. Properly terminate the conduit in a suitable
junction box.

Typical specification On/Off spring return damper actuators shall be direct coupled type which require no crank
arm and linkage and be capable of direct mounting to a shaft up to a 1/2” diameter and
center a 1/2” shaft. The actuators must be designed so that they may be used for either
clockwise or counter clockwise fail-safe operation. Actuators shall be protected from overload
at all angles of rotation. If required, one SPDT auxiliary switch shall be provided having the
capability of being adjustable. Actuators with auxiliary switch must be constructed to meet the
requirements for Double Insulation so an electrical ground is not required to meet agency
listings. Actuators shall be cULus listed, have a 5 year warranty, and be manufactured under
ISO 9001 International Quality Control Standards. Actuators shall be as manufactured by
Belimo.

Accessories

Electrical accessories Description Type


Auxiliary switch, mercury-free P475
Auxiliary switch, mercury-free P475-1
Signal simulator, Power supply AC 120 V PS-100
Cable conduit connector 1/2" TF-CC US
Mechanical accessories Description Type
Shaft extension 170 mm ø10 mm for damper shaft ø6...16 mm AV6-20
Position indicator IND-TF
for TFB(X)
Shaft clamp K8 US
for TFB(X)
Ball joint suitable for damper crank arm KH8 / KH10 KG10A
Ball joint suitable for damper crank arm KH8 KG6
Ball joint suitable for damper crank arm KH8 KG8
Damper crank arm Slot width 8.2 mm, for ø1.05" KH12
Damper crank arm Slot width 6.2 mm, clamping range ø10...18 mm KH6
Damper crank arm Slot width 8.2 mm, clamping range ø10...18 mm KH8
TFB(X) crankarm with 5/16" slot. KH-TF US
TFB(X) crankarm with 1/4" slot. KH-TF-1 US
Screw fastening kit SB-TF

www.belimo.com TFB120 • en-us • 2024-08-20 • Subject to change 2/4


Technical data sheet TFB120

Accessories
Description Type
Push rod for KG10A ball joint L 36”, 3/8” diameter SH10
SH8
Anti-rotation bracket TF/NKQ/AM/NM/LM. TF-P
Wrench 0.32 in and 0.39 in [8 mm and 10 mm] TOOL-06
Angle of rotation limiter, with end stop ZDB-TF
Mounting bracket ZG-113
for TFB(X)
ZG-DC1
ZG-DC2
Shaft extension for 3/8" diameter shafts (4" L). ZG-LMSA-1
Shaft extension for 1/2" diameter shafts (5" L). ZG-LMSA-1/2-5
TFB(X) crankarm adaptor kit (includes ZG-113). ZG-TF112
TFB(X) crankarm adaptor kit (T bracket included). ZG-TF2
Mounting kit ZG-TF3
for TFB(X)
Weather shield 13x8x6" [330x203x152 mm] (LxWxH) ZS-100
Baseplate, for ZS-100 ZS-101
Weather shield 406x213x102 mm [16x8-3/8x4"] (LxWxH) ZS-150

Electrical installation

Warning! Live electrical components!


During installation, testing, servicing and troubleshooting of this product, it may be necessary
to work with live electrical components. Have a qualified licensed electrician or other individual
who has been properly trained in handling live electrical components perform these tasks.
Failure to follow all electrical safety precautions when exposed to live electrical components
could result in death or serious injury.
Meets cULus requirements without the need of an electrical ground connection.
Actuators with appliance cables are numbered.
Provide overload protection and disconnect as required.
Actuators may be connected in parallel if not mechanically linked. Power consumption and
input impedance must be observed.

On/Off

www.belimo.com TFB120 • en-us • 2024-08-20 • Subject to change 3/4


Technical data sheet TFB120

Dimensions

www.belimo.com TFB120 • en-us • 2024-08-20 • Subject to change 4/4

You might also like