Nuovo Pignone CLIENTE – CUSTOMER

RAS GAS COMPANY LIMITED

FIRENZE LOCALITA’ - PLANT LOCATION


RAS LAFFAN - QATAR
COMMESSA - JOB
160.6570-72-73 IMPIANTO – PLANT
110. 2703-04-05 BARZAN Residue Gas Compressor

TITOLO – TITLE

MS6001B GAS TURBINE + 3MCL807 + BCL806 + GB


+ HELPER MOTOR
ELECTRIC LOAD LIST
PROJECT NAME: BARZAN ONSHORE PROJECT SHEET 1 OF 15

JOB CODE: 0-5858-20

PLANT LOCATION: Ras Laffan, Qatar

OWNER’S NAME: RasGas Company Limited

P.O. NO.: BAR-ON-LLE-003 / 0-5858-P-2158-501-A

B99-KT001/002/003 + B99-K001/003/005 + B99-K002/004/006 +


ITEM NO.
B99-KX001/002/003 + B99-KM001/002/003

ITEM NAME: MS6001B GAS TURBINE + 3MCL807 + BCL806 + GB + HELPER MOTOR

Electronically approved draw. GE NuovoPignone Internal DT-'N'


DOCUMENT TITLE: ELECTRIC LOAD LIST

VENDOR’S DOC NO.: SOM6628545

ISSUE PURPOSE : FC
RESULT CODE : A, B, R, F, ( )
NEXT STATUS : FA, FI, FC, AB, ( )
RESUBMISSION DATE : ( )
Approval or review hereunder shall not be construed to
relieve Vendor / Subcontractor of his responsibilities and
liability under the Contract.
PJ DEPT. ( )
RES DEPT. ( )
RELATED ( )
DEPT. ( )
( )
DATE
JOB NO. 0-5858-20
OWNER
B-V-BAR-ON-LLE-003-006
DOC. NO.

ORIG. PURCHASE ORDER NO. SERIAL REV.


DOC. NO.
V- 2158-501-A 006 5

REVISED CUSTOMER LABEL AND SHEETS


5 4,6,7,10÷13, AND 15 WHERE SHOWN <5>. SIME Gorini F. Ricci A. 07/11/2011
REVISED CUSTOMER LABEL AND SHEETS 2÷5,14
4 WHERE SHOWN <4>. SIME Gorini F. Ricci A. 23/09/2011
REVISED CUSTOMER LABEL AND SHEETS 2,4÷13 ITEM
3 WHERE SHOWN <3>. SIME Gorini F. Ricci A. 15/07/2011
2 REVISED CUSTOMER LABEL AND ALL SHEETS. SIME Gorini F. Ricci A. 11/05/2011
1 ADDED CUSTOMER LABEL AND REVISED ALL SHEETS. SIME Gorini F. Ricci A. 16/03/2011 N. SOM 6628545/4
0 ISSUE SIME Gorini F. Ricci A. 23/12/2010 LINGUA-LANG. PAGINA-SHEET
REV. DESCRIZIONE - DESCRIPTION PREP'D CONT-CHK'D APP-APPR'D DATA-DATE A 1 / 2
© 2008 Nuovo Pignone S.p.A, all rights reserved SOSTITUISCE IL - REPLACES
Drawing is furnished under license from NP to the Customer as per the above-specified Job
Number. Drawings not warranted by NP to third parties. SOSTITUITO DA - REPLACED BY
Nuovo Pignone ELECTRIC LOAD LIST
FIRENZE

GENERAL NOTES:

- ALL LOADS LISTED IN THIS DOCUMENT ARE RELEVANT TO ONE (n°1) TRAIN ONLY AND TO
REDUNDANT VFD TRAIN (Note 8) <2>

EQUIPMENT TAGGING RULE:

CUSTOMER Tag
GE-NP
Service Redundant VFD
Tag Train 1 Train 2 Train 3
Train <2>
23QT-1A Lube oil tank heater B99-KT001-H001A B99-KT002-H001A B99-KT003-H001A N/A
23QT-1B Lube oil tank heater B99-KT001-H001B B99-KT002-H001B B99-KT003-H001B N/A
88QE-1 <4> Emergency pump motor B99-KT001-PM003 B99-KT002-PM003 B99-KT003-PM003 N/A
23QA-1 Auxiliary pump motor space heater N/A N/A N/A N/A
88QA-1 Auxiliary pump motor B99-KT001-PM002 B99-KT002-PM002 B99-KT003-PM002 N/A
88QV-1 Fan extractor drive B99-KT001-KM001A B99-KT002-KM001A B99-KT003-KM001A N/A
88QV-2 Fan extractor drive B99-KT001-KM001B B99-KT002-KM001B B99-KT003-KM001B N/A
88HQ-1 Hydraulic oil Auxiliary pump motor B99-KT001-PM005 B99-KT002-PM005 B99-KT003-PM005 N/A
23TK-1 GT Exhaust stream fan motor space heater N/A N/A N/A N/A
23TK-2 GT Exhaust stream fan motor space heater N/A N/A N/A N/A
88TK-1 GT Exhaust frame cooling fan motor B99-KT001-KM002A B99-KT002-KM002A B99-KT003-KM002A N/A
88TK-2 GT Exhaust frame cooling fan motor B99-KT001-KM002B B99-KT002-KM002B B99-KT003-KM002B N/A
88CR Starting system motor B99-KT001-XM004 B99-KT002-XM004 B99-KT003-XM004 N/A
23CR Starting motor space heater N/A N/A N/A N/A
88HR-1 Hydraulic ratchet pump motor B99-KT001-PM006 B99-KT002-PM006 B99-KT003-PM006 N/A
23TW-1 Washing solution heater B99-KT001-H002 B99-KT002-H002 B99-KT003-H002 N/A
88TW-1 Washing solution pump motor B99-KT001-PM007 B99-KT002-PM007 B99-KT003-PM007 N/A
88EH-1 Electrical hoist motor <4> B99-KT001-XM005 B99-KT002-XM005 B99-KT003-XM005 N/A
88BA-1 Ventilation fan motor B99-KT001-KM003A B99-KT002-KM003A B99-KT003-KM003A N/A
88BA-2 Ventilation fan motor B99-KT001-KM003B B99-KT002-KM003B B99-KT003-KM003B N/A
23BA-1 Ventilation fan motor space heater N/A N/A N/A N/A
23BA-2 Ventilation fan motor space heater N/A N/A N/A N/A
88RC-1 CO2 compressor motor B99-KT001-KM004A B99-KT002-KM004A B99-KT003-KM004A N/A
88RC-2 CO2 compressor motor B99-KT001-KM004B B99-KT002-KM004B B99-KT003-KM004B N/A
23HM-1 VSDS motor space heater N/A N/A N/A N/A
23HM-2 VSDS motor main TB space heater N/A N/A N/A N/A
23HM-3 VSDS motor exciter space heater N/A N/A N/A N/A
88QS-1 Jacking oil main pump motor B99-KT001-PM008 B99-KT002-PM008 B99-KT003-PM008 N/A
88QS-2 Jacking oil emergency pump motor B99-KT001-PM009 B99-KT002-PM009 B99-KT003-PM009 N/A
88CA-1 Motor Cooling Fan Motor B99-KM001-KM001A B99-KM002-KM001A B99-KM003-KM001A N/A
88CA-2 Motor Cooling Fan Motor B99-KM001-KM001B B99-KM002-KM001B B99-KM003-KM001B N/A
23SG-1 Seal gas electric heater B99-K001-H001 B99-K003-H001 B99-K005-H001 N/A
23SG-2 Seal gas electric heater B99-K002-H001 B99-K004-H001 B99-K006-H001 N/A
88QP-1 Oil purifier pump motor B99-KT001-PM010 B99-KT002-PM010 B99-KT003-PM010 N/A
95TR-1 Gas Turbine Ignition Transfomer B99-KT001-AUX01 B99-KT002-AUX01 B99-KT003-AUX01 N/A
95TR-10 Gas Turbine Ignition Transfomer B99-KT001-AUX10 B99-KT002-AUX10 B99-KT003-AUX10 N/A
- VFD Transfomer TR-10641 TR-10642 TR-10643 TR-10645
- VFD Swithchgear 36kV SB-10621 SB-10622 SB-10623 SB-10625
- VFD Swithchgear 12kV (output) SB-10641Y/D SB-10642Y/D SB-10643Y/D SB-10645Y/D
- VFD Swithchgear 7.2kV (input) SB-10641 SB-10642 SB-10643 SB-10645
- VFD Excitation Unit <3> AF-10641-EXU <3> AF-10642-EXU <3> AF-10643-EXU <3> AF-10645-EXU <3>
- VFD WCU Control Unit <3> AF-10641-AX-SB <3> AF-10642-AX-SB <3> AF-10643-AX-SB <3> AF-10645-AX-SB <3>
- VFD Master Controller <3> N/A <3> N/A <3> N/A <3> AF-1064-MC <3>
- VFD Excitation Switchover <3> N/A <3> N/A <3> N/A <3> AF-1064-ES <3>
M1 <3> Cooling water pump motor <2> AF-10641-PM001A <2> AF-10642-PM001A <2> AF-10643-PM001A <2> AF-10645-PM001A
M2 <3> Cooling water emergency pump motor <2> AF-10641-PM001B <2> AF-10642-PM001B <2> AF-10643-PM001B <2> AF-10645-PM001B
M3 <3> WCU Cooling Fan Motor <3> AF-10641-EM002A <3> AF-10642-EM002A <3> AF-10643-EM002A <3> AF-10645-EM002A <3>
M4 <3> WCU Cooling Fan Emergency Motor <3> AF-10641-EM002B <3> AF-10642-EM002B <3> AF-10643-EM002B <3> AF-10645-EM002B <3>
E5 <3> Enclosure Electric Heater <3> AF-10641-H001 <3> AF-10642-H001 <3> AF-10643-H001 <3> AF-10645-H001 <3>

ITEM

4 REVISED WHERE SHOWN <4>


3 REVISED WHERE SHOWN <3> N. SOM 6628545/4
2 REVISED WHERE SHOWN <2> LINGUA-LANG. PAGINA-SHEET

1 ADDED CUSTOMER EQUIPMENT TAGGING RULE A 2 / 3


SOSTITUISCE IL - REPLACES
© 2 0 0 8 N u o v o P i g n o n e S . p . A , a l l r i g h t s r e se r ve d SOSTITUITO DA - REPLACED BY
Nuovo Pignone ELECTRIC LOAD LIST
FIRENZE

SECTION 1

Feeding panel: 6.6 kVac 3Ph. 50Hz (Supplied by Customer) <1>

CUSTOMER TAG Absorbed power


Rated Rated
(NP TAG) Description Voltage Power Stand-by Starting Running Cool Down Emergency
<1> (V) (kW) (kW) (kW) (kW) (kW)
(kW)

B99-KT001-XM004
Electric Starting Motor 6600 530 - 530 - - -
(88CR)

Feeding panel: 33 kVac 3Ph. 50Hz (Supplied by Customer) <1>

Absorbed power
CUSTOMER TAG Rated Rated
(NP TAG) Description Power Stand-by Starting Running Cool Down Emergency
Voltage
<1> (kVA) (kVA) (kVA) (kVA) (kVA) (kVA)
(V)
<4> <4> <4> <4> <4>
<4>
VFD Step Down Transformer 24450
TR-10641 33000 24500 - - - -
(VSDS) <2>
VFD Step Down Transformer
TR-10645
(VSDS) 33000 24500 - - 24450 - -
<2>
Redundant Train

ITEM

4 REVISED WHERE SHOWN <4> N. SOM 6628545/4


2 REVISED WHERE SHOWN <2> LINGUA-LANG. PAGINA-SHEET

1 ADDED CUSTOMER EQUIPMENT TAGS AND REVISED WHERE SHOWN <1> A 3 / 4


SOSTITUISCE IL - REPLACES
© 2 0 0 8 N u o v o P i g n o n e S . p . A , a l l r i g h t s r e se r ve d SOSTITUITO DA - REPLACED BY
Nuovo Pignone ELECTRIC LOAD LIST
FIRENZE

SECTION 2A <5>
Feeding panel: MCC UNIT Panel 415Vac; 3Ph; 50Hz (Supplied by Customer)

CUSTOMER TAG Absorbed power


Rated Rated
(NP TAG) Description Voltage Power Stand-by Starting Running Cool Down Emergency
<1> (V) (kW) (kW) (kW) (kW) (kW)
(kW)
B99-KT001-PM002 Auxiliary Lube Oil Pump
415 37 - 30 - 30 -
(88QA-1) Motor
B99-KT001-PM005
Hydraulic Oil Auxiliary Pump 415 15 - 13 - - -
(88HQ-1)
B99-KT001-H001A
Lube Oil Tank Heater 415 10 10 10 - - -
(23QT-1A)
B99-KT001-H001B
Lube Oil Tank Heater 415 10 10 10 - - -
(23QT-1B)
B99-KT001-KM003A Turbine Enclosure Ventilation 149 135 135 135
415 - -
(88BA-1) Fan Motor (Main) <4> <4> <4> <4>
B99-KT001-KM003B Turbine Enclosure Ventilation 149 135
415 - - - -
(88BA-2) Fan Motor (Stand-by) <4> <4>
B99-KT001-KM002A Turbine Exhaust Frame
415 45 - 30 30 30 -
(88TK-1) Cooling Fan Motor <4>
B99-KT001-KM002B Turbine Exhaust Frame
415 45 - 30 30 30 -
(88TK-2) Cooling Fan Motor <4>
B99-KT001-KM001A Lube Oil Fan Separator Motor 3 2.5 2.5 2.5
415 - -
(88QV-1) (Main) <1> <1> <1> <1>
B99-KT001-KM001B Lube Oil Fan Separator Motor 3 2.5
415 - - - -
(88QV-2) (Stand-by) <1> <1>

<5>

<5>
17.2
B99-KT001-H002
Washing water skid 18 (14
(23TW-1)
(14 heater heater +
+ heater + pump motor 415 - - - -
+ 4 pump 3.2
B99-KT001-PM007 <2> motor) pump
(88TW-1)
motor)
B99-KT001-PM010 Oil purifier pump motor 1.1 1.1
415 - - - -
(88QP-1) <1> <5> <5>
B99-KT001-
CO2 FF Chilling Motor (Loop 4 - 2 2 2
KM004A/B (88RC- 415 -
1-2, Note 6) <1> <1> <1> <1> <1> <1>
1/2) <1>
B99-KT001-XM005
Electrical Hoist Motor 415 1.5 1.2 - - - -
(88EH-1)

B99-K001-H001 10 10 10 10
3MCL 807 Seal gas heater 415 - -
(23SG-1) <2> <5> <2> <5> <2> <5> <2> <5>

B99-K002-H001 10 10 10 10
BCL 806 Seal gas heater 415 - -
(23SG-2) <2> <5> <2> <5> <2> <5> <2> <5>

5 REVISED WHERE SHOWN <5> ITEM

4 REVISED WHERE SHOWN <4>


3 REVISED WHERE SHOWN <3> N. SOM 6628545/4
2 REVISED WHERE SHOWN <2> LINGUA-LANG. PAGINA-SHEET

1 ADDED CUSTOMER EQUIPMENT TAGS AND REVISED WHERE SHOWN <1> A 4 / 5


SOSTITUISCE IL - REPLACES
© 2 0 0 8 N u o v o P i g n o n e S . p . A , a l l r i g h t s r e se r ve d SOSTITUITO DA - REPLACED BY
Nuovo Pignone ELECTRIC LOAD LIST
FIRENZE

CUSTOMER TAG Absorbed power


Rated Rated
(NP TAG) Description Voltage Power Stand-by Starting Running Cool Down Emergency
<1> (V) (kW) (kW) (kW) (kW) (kW)
(kW)

DC panel battery charger & 15 15 15 15


(DCP) 415 - -
DC distribution panel <3> <3> <3> <3>
AF-10641-PM001A VSDS cooling unit Main
(M1) motor Pump
+ +
AF-10641-PM001B VSDS cooling unit
(M2) Emergency motor Pump
+ + 40,15 40,15 40,15 40,15
AF-10641-EM002A WCU cooling Fan Main
415 <1> - <1> <1> <1> -
(M3) motor
<3> <3> <3> <3>
+ +
<4> <4> <4> <4>
AF-10641-EM002B WCU cooling Fan Emergency
motor
(M4)
+ +
B99MOV-1590 WCU cooling MOV raw water
<2> <3> <4> <3> <4>
VSDS cooling unit Main
AF-10645-PM001A motor Pump
(M1) +
+ VSDS cooling unit
AF-10645-PM001B Emergency motor Pump
(M2) +
+ WCU cooling Fan Main 40,15 40,15 40,15 40,15
AF-10645-EM002A motor 415 <3> - <3> <3> <3> -
(M3) + <4> <4> <4> <4>
+ WCU cooling Fan Emergency
AF-10645-EM002B motor
(M4) +
+ WCU cooling MOV raw water
B99MOV-5590 Redundant Train
<2> <3> <4>
<3> <4>
Motor Exciter Unit + COU
charging transformer + VSDS
47.2 47.2 47.2 47.2
- cooling unit Air to Air cooling 415 - -
fans motors <1><2> <1><2> <1><2> <1><2>
(Note 5) <2>
Motor Exciter Unit + COU
charging transformer + VSDS
cooling unit Air to Air cooling
- fans motors 415 47.2 - 47.2 47.2 47.2 -
(Note 5)
Redundant Train <2>
VSDS Motor Auxiliary supply
- 415 32.3 - 32.3 32.3 - -
for motor excitation <2>
VSDS Motor Auxiliary supply
- for motor excitation 415 32.3 - 32.3 32.3 - -
Redundant Train <2>
B99-KM001-KM001A Helper motor Air cooling fan
415 15 - 15 15 15 -
(88CA-1)<2><3> motor A <1>
B99-KM001-KM001B Helper motor Air cooling fan
415 15 - 15 15 15 -
(88CA-2)<2><3> motor B <1>

ITEM

4 REVISED WHERE SHOWN <4>


3 REVISED WHERE SHOWN <3> N. SOM 6628545/4
2 REVISED WHERE SHOWN <2> LINGUA-LANG. PAGINA-SHEET

1 ADDED CUSTOMER EQUIPMENT TAGS AND REVISED WHERE SHOWN <1> A 5 / 6


SOSTITUISCE IL - REPLACES
© 2 0 0 8 N u o v o P i g n o n e S . p . A , a l l r i g h t s r e se r ve d SOSTITUITO DA - REPLACED BY
Nuovo Pignone ELECTRIC LOAD LIST
FIRENZE

SECTION 2B
Feeding panel: 415Vac; 3Ph; 50Hz from UPS (Supplied by Customer)

Absorbed power
CUSTOMER TAG Rated Rated
(NP TAG)
Description Voltage Power Stand-by Starting Running Cool Down Emergency
(V) (kW) (kW) (kW) (kW) (kW) (kW)

B99-KT001-PM008
Jacking Oil Main Pump Motor 415 4 - 4 4 4 4
(88QS-1)

B99-KT001-PM009 Jacking Oil Stand-by Pump


415 4 4 - - - -
(88QS-2) Motor

ITEM

5 GENERAL REVISION
3 REVISED WHERE SHOWN <3> N. SOM 6628545/4
2 REVISED WHERE SHOWN <2> LINGUA-LANG. PAGINA-SHEET

1 ADDED CUSTOMER EQUIPMENT TAGS AND REVISED WHERE SHOWN <1> A 6 / 7


SOSTITUISCE IL - REPLACES
© 2 0 0 8 N u o v o P i g n o n e S . p . A , a l l r i g h t s r e se r ve d SOSTITUITO DA - REPLACED BY
Nuovo Pignone ELECTRIC LOAD LIST
FIRENZE

SECTION 3
Feeding panel: MCC UNIT Panel 240Vac; 1Ph; 50Hz (Supplied by Customer)

CUSTOMER TAG Absorbed power


Rated Rated
(NP TAG) Description Voltage Power Stand-by Starting Running Cool Down Emergency
<1> (V) (kW) (kW) (kW) (kW) (kW)
(kW)
Accessory/ Gas Turbine
3 3
(AL1) compartment normal lighting 240 - - - -
<1> <1>
<1>
3 3
(FHL) Filter house normal lighting 240 - - - -
<1> <1>

(GT-SK-1) 4 4
GT enclosure sockets 240 - - - -
<1> <1> <1>

(GT-SK-2) GT enclosure sockets 240 4 4


- - - -
<1> <1> <1> <1> <1>

<5>

B99-KT001-AUX01
(95TR-1)
Gas Turbine ignition
+ 240 0.9 - 0.9 - - -
transformers
B99-KT001-AUX10
(95TR-10)

(DCP-H) DCP panel heater 240 0.5 0.5 0.5 0.5 0.5 -

Filter house pulse jet control


(PS-CP) 240 1 - 1 1 1 -
panel

Auxiliary lube oil pump motor


(23QA-1) 240 0.2 0.2 - 0.2 - -
space heater
Turbine Enclosure Ventilation
(23BA-1) Fan Motor (Main) space 240 0.2 0.2 - - - -
heater
Turbine Enclosure Ventilation
(23BA-2) Fan Motor (Stand-by) space 240 0.2 - 0.2 0.2 0.2 -
heater
Turbine exhaust frame
(23TK-1) ventilation fan motor space 240 0.2 0.2 - - - -
heater
Turbine exhaust frame
(23TK-2) ventilation fan motor space 240 0.2 0.2 - - - -
heater
0.15 0.15 0.15 0.15
(23CR) Starting motor space heater 240 - -
<3> <3> <3> <3>

B99-MOV-1401
IBH motor drain valve 240 0.25 - 0.25 - - -
<2>
Helper Motor space heater
(23HM-1) +
+ Helper Motor main TB space
(23HM-2) heater 2.4 2.4 2.4 2.4
240 - -
+ + <3> <3> <3> <3>
(23HM-3) Helper Motor exciter space
<3> heater
<3>
VSDS Converter/Exciter Unit
0.6 0.6 0.6 0.6
- space heater 240 - -
<1><2> <1><2> <1><2> <1><2>
<2>

ITEM

5 REVISED WHERE SHOWN <5>


3 REVISED WHERE SHOWN <3> N. SOM 6628545/4
2 REVISED WHERE SHOWN <2> LINGUA-LANG. PAGINA-SHEET

1 ADDED CUSTOMER EQUIPMENT TAGS AND REVISED WHERE SHOWN <1> A 7 / 8


SOSTITUISCE IL - REPLACES
© 2 0 0 8 N u o v o P i g n o n e S . p . A , a l l r i g h t s r e se r ve d SOSTITUITO DA - REPLACED BY
Nuovo Pignone ELECTRIC LOAD LIST
FIRENZE

Absorbed power
CUSTOMER TAG Rated Rated
(NP TAG)
Description Voltage Power Stand-by Starting Running Cool Down Emergency
(V) (kW) (kW) (kW) (kW) (kW) (kW)

VSDS Converter/Exciter Unit


- space heater 240 0.6 - 0.6 0.6 0.6 -
Redundant Train <2>
AF-10641-H001 VSDS Cooling Unit Enclosure
0.5 0.5 0.5 0.5
(E5) space heater 240 - -
<3> <3> <3> <3>
<3> <1><3>
AF-10645-H001 VSDS Cooling Unit Enclosure
0.5 0.5 0.5 0.5
(E5) space heater 240 - -
<3> <3> <3> <3>
<3> Redundant Train <2><3>
VSDS Cooling Unit Control
0.5 0.5 0.5 0.5
- panel space heater 240 - -
<3> <3> <3> <3>
<3>
VSDS Cooling Unit Control
0.5 0.5 0.5 0.5
- panel space heater 240 - -
<3> <3> <3> <3>
Redundant Train <3>
VSDS Switchgear 7.2 kV
0.15 0.15 0.15 0.15
- space heaters-U1 240 - -
<2> <2> <2> <2>
<1> <2>
VSDS Switchgear 7.2 kV
0.15 0.15 0.15 0.15
- space heaters-V1 240 - -
<2> <2> <2> <2>
<1> <2>
VSDS Switchgear 7.2 kV
0.15 0.15 0.15 0.15
- space heaters-W1 240 - -
<2> <2> <2> <2>
<1> <2>
VSDS Switchgear 7.2 kV
0.15 0.15 0.15 0.15
- space heaters-U2 240 - -
<2> <2> <2> <2>
<1> <2>
VSDS Switchgear 7.2 kV
0.15 0.15 0.15 0.15
- space heaters-V2 240 - -
<2> <2> <2> <2>
<1> <2>
VSDS Switchgear 7.2 kV
0.15 0.15 0.15 0.15
- space heaters-W2 240 - -
<2> <2> <2> <2>
<1> <2>
VSDS Switchgear 7.2 kV
- space heaters-U1 240 0.15 - 0.15 0.15 0.15 -
Redundant Train <2>
VSDS Switchgear 7.2 kV
- space heaters-V1 240 0.15 - 0.15 0.15 0.15 -
Redundant Train <2>
VSDS Switchgear 7.2 kV
- space heaters-W1 240 0.15 - 0.15 0.15 0.15 -
Redundant Train <2>
VSDS Switchgear 7.2 kV
- space heaters-U2 240 0.15 - 0.15 0.15 0.15 -
Redundant Train <2>
VSDS Switchgear 7.2 kV
- space heaters-V2 240 0.15 - 0.15 0.15 0.15 -
Redundant Train <2>
VSDS Switchgear 7.2 kV
- space heaters-W2 240 0.15 - 0.15 0.15 0.15 -
Redundant Train <2>

VSDS Switchgear 12 kV 0.45 0.45 0.45 0.45


- 240 - -
space heaters-1 <3> <3> <3> <3>

VSDS Switchgear 12 kV 0.45 0.45 0.45 0.45


- 240 - -
space heaters-2 <3> <3> <3> <3>

ITEM

3 REVISED WHERE SHOWN <3> N. SOM 6628545/4


2 REVISED WHERE SHOWN <2> LINGUA-LANG. PAGINA-SHEET

1 REVISED WHERE SHOWN <1> A 8 / 9


SOSTITUISCE IL - REPLACES
© 2 0 0 8 N u o v o P i g n o n e S . p . A , a l l r i g h t s r e se r ve d SOSTITUITO DA - REPLACED BY
Nuovo Pignone ELECTRIC LOAD LIST
FIRENZE

Rated Rated Absorbed power


CUSTOMER TAG
(NP TAG)
Description Voltage Power Stand-by Starting Runnin Cool Down Emergency
(V) (kW) (kW) (kW) g (kW) (kW) (kW)
VSDS Switchgear 12 kV
0.75 0.75 0.75 0.75
- space heaters-1 240 - -
<3> <3> <3> <3>
Redundant Train <2>
VSDS Switchgear 12 kV
0.75 0.75 0.75 0.75
- space heaters-2 240 - -
<3> <3> <3> <3>
Redundant Train <2>
VSDS Switchgear 36 kV
- 240 0.05 - 0.05 0.05 0.05 -
space heaters-1
VSDS Switchgear 36 kV
- space heaters-1 240 0.05 - 0.05 0.05 0.05 -
Redundant Train <2>
0.3
VSDS Transformer space 0.3 0.3 0.3
- 240 - <2> -
heater <2> <3> <2> <3> <2> <3>
<3>
VSDS Transformer space 0.3
0.3 0.3 0.3
- heater 240 - <2> -
<2> <3> <2> <3> <2> <3>
Redundant Train <3> <3>
VSDS Bus Duct space
0.15 0.15 0.15 0.15 0.15 0.15
- heater-U1 240
<2> <2> <2> <2> <2> <2>
<2>
VSDS Bus Duct space
0.15 0.15 0.15 0.15 0.15 0.15
- heater-V1 240
<2> <2> <2> <2> <2> <2>
<2>
VSDS Bus Duct space
0.15 0.15 0.15 0.15 0.15 0.15
- heater-W1 240
<2> <2> <2> <2> <2> <2>
<2>
VSDS Bus Duct space
0.15 0.15 0.15 0.15 0.15 0.15
- heater-U2 240
<2> <2> <2> <2> <2> <2>
<2>
VSDS Bus Duct space
0.15 0.15 0.15 0.15 0.15 0.15
- heater-V2 240
<2> <2> <2> <2> <2> <2>
<2>
VSDS Bus Duct space
0.15 0.15 0.15 0.15 0.15 0.15
- heater-W2 240
<2> <2> <2> <2> <2> <2>
<2>
VSDS Bus Duct space
0.15 0.15 0.15 0.15 0.15 0.15
- heater-U1 240
<2> <2> <2> <2> <2> <2>
Redundant Train <2>
VSDS Bus Duct space
0.15 0.15 0.15 0.15 0.15 0.15
- heater-V1 240
<2> <2> <2> <2> <2> <2>
Redundant Train <2>
VSDS Bus Duct space
0.15 0.15 0.15 0.15 0.15 0.15
- heater-W1 240
<2> <2> <2> <2> <2> <2>
Redundant Train <2>
VSDS Bus Duct space
0.15 0.15 0.15 0.15 0.15 0.15
- heater-U2 240
<2> <2> <2> <2> <2> <2>
Redundant Train <2>
VSDS Bus Duct space
0.15 0.15 0.15 0.15 0.15 0.15
- heater-V2 240
<2> <2> <2> <2> <2> <2>
Redundant Train <2>
VSDS Bus Duct space
0.15 0.15 0.15 0.15 0.15 0.15
- heater-W2 240
<2> <2> <2> <2> <2> <2>
Redundant Train <2>
Motor Excitation Switch
- Over space heater 240 0.15 0.15 0.15 0.15 0.15 0.15
<2>
VSDS Master Controller
- space heater 240 0.15 - 015 0.15 0.15 -
<2>

ITEM

3 REVISED WHERE SHOWN <3> N. SOM 6628545/4


2 REVISED WHERE SHOWN <2> LINGUA-LANG. PAGINA-SHEET

1 GENERAL REVISION A 9 / 10
SOSTITUISCE IL - REPLACES
© 2 0 0 8 N u o v o P i g n o n e S . p . A , a l l r i g h t s r e se r ve d SOSTITUITO DA - REPLACED BY
Nuovo Pignone ELECTRIC LOAD LIST
FIRENZE

Rated Rated Absorbed power


CUSTOMER TAG
(NP TAG)
Description Voltage Power Stand-by Starting Runnin Cool Down Emergency
(V) (kW) (kW) (kW) g (kW) (kW) (kW)

Helper Motor humidity


- detector (B99AT-1562) 240 0.05 0.05 --- --- --- ---
(note 9)

Helper Motor position


- encoder optical interface #1 240 0.01 --- 0.01 0.01 0.01 ---
(B99ZT-1560)

Helper Motor position


- encoder optical interface #2 240 0.01 --- 0.01 0.01 0.01 ---
(B99ZT-1561)

ITEM

5 GENERAL REVISION
3 REVISED WHERE SHOWN <3> N. SOM 6628545/4
2 REVISED WHERE SHOWN <2> LINGUA-LANG. PAGINA-SHEET

1 REVISED WHERE SHOWN <1> A 10 / 11


SOSTITUISCE IL - REPLACES
© 2 0 0 8 N u o v o P i g n o n e S . p . A , a l l r i g h t s r e se r ve d SOSTITUITO DA - REPLACED BY
Nuovo Pignone ELECTRIC LOAD LIST
FIRENZE

SECTION 4
Feeding panel: 240Vac; 1Ph; 50Hz from UPS (Supplied by Customer)

Absorbed power
CUSTOMER TAG Rated Rated
(NP TAG)
Description Voltage Power Stand-by Starting Running Cool Down Emergency
(V) (kW) (kW) (kW) (kW) (kW) (kW)

Unit Control Panel 1.9


(UCP-1) 240 2.4 1.9 1.9 1.9 1.9
(Main power supply) (Note 7)
<5> <5> <1><5> <1><5> <1><5> <1><5> <1><5>
<1><5> <5>
3
Unit Control Panel 4 4 4 4 4
(UCP-2) 240 (Note 7)
from UPS#1 <1> <1> <1> <1> <1>
<1>
3
Unit Control Panel 4 4 4 4 4
(UCP-HMI) 240 (Note 7)
from UPS#2 <1> <1> <1> <1> <1>
<1>
VSDS converter Control
2.9
Unit control power and 2.9 2.9 2.9 2.9 2.9
- 240 (Note 7)
Miscellaneous supply <1><2> <3> <1><2> <1><2> <1><2>
<1><2><3>
<1><2>
VSDS converter Control
Unit control power and 2.9
- 240 2.9 2.9 2.9 2.9 2.9
Miscellaneous supply (Note 7)
Redundant Train <3>
UCS
0.8
CCC Trainview & Master
- 240 0.8 - 0.8 0.8 0.8 (Note 7)
Controller
<3>
from UPS#1
UCS
CCC Trainview & Master
- 240 0.8 0.8 - - - -
Controller
from UPS#2
UCS
1
Remote HMI and
- 240 1 - 1 1 1 (Note 7)
BN System One
<3>
from UPS#1
UCS
Remote HMI and
- 240 1 1 - - - -
BN System One
from UPS#2
UCS
Remote HMI, 1.2
- CCC Trainview, 240 1.2 - 1.2 1.2 1.2 (Note 7)
and BN System One <3>
from UPS#1
UCS
Remote HMI,
- CCC Trainview, 240 1.2 1.2 - - - -
and BN System One
from UPS#2
Remote Control System
Remote HMI, 0.9
- CCC Trainview, 240 0.9 - 0.9 0.9 0.9 (Note 7)
and BN System One <3>
from UPS#1
Remote Control System
HMI,
- CCC Trainview, 240 0.9 0.9 - - - -
and BN System One
from UPS#2

ITEM

5 REVISED WHERE SHOWN <5>


3 REVISED WHERE SHOWN <3> N. SOM 6628545/4
2 REVISED WHERE SHOWN <2> LINGUA-LANG. PAGINA-SHEET

1 REVISED WHERE SHOWN <1> A 11 / 12


SOSTITUISCE IL - REPLACES
© 2 0 0 8 N u o v o P i g n o n e S . p . A , a l l r i g h t s r e se r ve d SOSTITUITO DA - REPLACED BY
Nuovo Pignone ELECTRIC LOAD LIST
FIRENZE

Rated Rated Absorbed power


CUSTOMER TAG
(NP TAG)
Description Voltage Power
Stand-by Starting Running Cool Down Emergency
(V) (kW)
(kW) (kW) (kW) (kW) (kW)
Remote HMI,
CCC Trainview,
0.4
and BN System One
- 240 0.4 - 0.4 0.4 0.4 (Note 7)
Monitors
<3>
from UPS#1
(required for 2 hours)
Remote HMI,
CCC Trainview,
and BN System One
- 240 0.4 0.4 - - - -
Monitors
from UPS#2 <3>
(required for 2 hours)
Remote HMI,
CCC Trainview,
0.4
and BN System One
- 240 0.4 - 0.4 0.4 0.4 (Note 7)
Monitors
<3>
from UPS#1
(required for 1 hours)
Remote HMI,
CCC Trainview,
and BN System One
- 240 0.4 0.4 - - - -
Monitors
from UPS#2
(required for 1 hours)
Remote HMI,
CCC Trainview,
0.4
and BN System One
- 240 0.4 - 0.4 0.4 0.4 (Note 7)
Monitors
<3>
from UPS#1
(required for 2 hours)
Remote HMI,
CCC Trainview,
and BN System One
- 240 0.4 0.4 - - - -
Monitors
from UPS#2
(required for 2 hours)
Motor Excitation Switch Over 1.2
1.2 1.2 1.2 1.2 1.2
- control power-1 240 (Note 7)
<3><5> <3><5> <3><5> <3><5> <3><5>
<2> <3><5>
Motor Excitation Switch Over 1.2
1.2 1.2 1.2 1.2 1.2
- control power-2 240 (Note 7)
<3><5> <3><5> <3><5> <3><5> <3><5>
<2> <3><5>
Water Cooling Unit 1.35
1.35 1.35 1.35 1.35 1.35
- control power-1 240 (Note 7)
<3><5> <3><5> <3><5> <3><5> <3><5>
<2> <3><5>
Water Cooling Unit 1.35
1.35 1.35 1.35 1.35 1.35
- control power-2 240 (Note 7)
<3><5> <3><5> <3><5> <3><5> <3><5>
<2> <3><5>
Water Cooling Unit 1.35
1.35 1.35 1.35 1.35 1.35
- control power-1 240 (Note 7)
<3><5> <3><5> <3><5> <3><5> <3><5>
Redundant Train <3> <3><5>
Water Cooling Unit 1.35
1.35 1.35 1.35 1.35 1.35
- control power-2 240 (Note 7)
<3><5> <3><5> <3><5> <3><5> <3><5>
Redundant Train <3> <3><5>

ITEM

5 REVISED WHERE SHOWN <5>


3 REVISED WHERE SHOWN <3> N. SOM 6628545/4
2 REVISED WHERE SHOWN <2> LINGUA-LANG. PAGINA-SHEET

1 GENERAL REVISION A 12 / 13
SOSTITUISCE IL - REPLACES
© 2 0 0 8 N u o v o P i g n o n e S . p . A , a l l r i g h t s r e se r ve d SOSTITUITO DA - REPLACED BY
Nuovo Pignone ELECTRIC LOAD LIST
FIRENZE

Rated Rated Absorbed power


CUSTOMER TAG
(NP TAG)
Description Voltage Power
Stand-by Starting Running Cool Down Emergency
(V) (kW)
(kW) (kW) (kW) (kW) (kW)
1.3
VSDS Master controller 1.3 1.3 1.3 1.3 1.3
- 240 (Note 7)
Control power supply-1 <5> <5> <5> <5> <5>
<5>
1.3
VSDS Master controller 1.3 1.3 1.3 1.3 1.3
- 240 (Note 7)
Control power supply-2 <5> <5> <5> <5> <5>
<5>

ITEM

5 REVISED WHERE SHOWN <5>


3 GENERAL REVISION N. SOM 6628545/4
2 REVISED WHERE SHOWN <2> LINGUA-LANG. PAGINA-SHEET

1 ADDED CUSTOMER EQUIPMENT TAGS AND REVISED WHERE SHOWN <1> A 13 / 14


SOSTITUISCE IL - REPLACES
© 2 0 0 8 N u o v o P i g n o n e S . p . A , a l l r i g h t s r e se r ve d SOSTITUITO DA - REPLACED BY
Nuovo Pignone ELECTRIC LOAD LIST
FIRENZE

SECTION 5
Feeding panel: Distribution Panel 125 Vdc (Supplied by NP)

Rated Rated Absorbed power


CUSTOMER TAG
(NP TAG)
Description Voltage Power Stand-by Starting Running Cool Down Emergency
(V) (kW) (kW) (kW) (kW) (kW) (kW)
B99-KT001-PM003 Emergency lube oil pump
(88QE-1) motor 125 9.2 - - - - 7.5
<3><4> (Note 1)
B99-KT001-PM006 Hydraulic ratchet pump motor
125 1.7 - - - 1.5 1.5
(88HR-1) (Note 2)
Accessory/ Turbine
compartment emergency 1.5 1.5
(EL-1) 125 - - - -
lighting <1> <1>
(Note 3) <1>
Filter house emergency
2 2
(EL-3) lighting 125 - - - -
<1> <1>
(Note 3) <4>
VSDS Switchgear 7.2 kV - -
SB-10641 0.5 0.5 0.5 0.5
Control Power Supply 125 <1> <3> <1> <3>
<1> <1> <3> <1> <3> <1> <3> <1> <3>
(Note 4) <1> <4> <4>
VSDS Switchgear 7.2 kV
-
SB-10645 Control Power Supply 0.5 0.5 0.5 0.5 -
125 <1> <3>
<2> Redundant Train <3> <3> <3> <3> <3> <4>
<4>
(Note 4)
VSDS Switchgear 12 kV - -
SB-10641Y/D 0.5 0.5 0.5 0.5
Control Power Supply 125 <1> <3> <1> <3>
<1> <1> <3> <1> <3> <1> <3> <1> <3>
(Note 4) <1> <4> <4>
VSDS Switchgear 12 kV
SB-10645Y/D Control Power Supply 0.5 0.5 0.5 0.5 - -
125
<2> Redundant Train <3> <3> <3> <3> <3> <4> <3> <4>
(Note 4)
VSDS Switchgear 36 kV
SB-10621 0.5 0.5 0.5 0.5 0.5 0.5
Control Power Supply 125
<1> <1> <3> <1> <3> <1> <3> <1> <3> <1> <3> <1> <3>
(Note 4) <1>
VSDS Switchgear 36 kV
SB-10625 Control Power Supply 0.5 0.5 0.5 0.5 0.5 0.5
125
<2> Redundant Train <3> <3> <3> <3> <3> <3>
(Note 4)

ITEM

4 REVISED WHERE SHOWN <4>


3 REVISED WHERE SHOWN <3> N. SOM 6628545/4
2 REVISED WHERE SHOWN <2> LINGUA-LANG. PAGINA-SHEET

1 ADDED CUSTOMER EQUIPMENT TAGS AND REVISED WHERE SHOWN <1> A 14 / 15


SOSTITUISCE IL - REPLACES
© 2 0 0 8 N u o v o P i g n o n e S . p . A , a l l r i g h t s r e se r ve d SOSTITUITO DA - REPLACED BY
Nuovo Pignone ELECTRIC LOAD LIST
FIRENZE

st
Note 1 1 phase (GT run-down) – Emergency pump 15 minutes ON
nd
2 phase (GT cool-down) – Emergency pump 30 seconds ON; 3 minutes OFF
st nd
Cool down total time (1 phase + 2 phase): 12 HOURS
Note 2 Ratchet pump activated after 60s from Cool down sequence start
Sequence: Ratchet pump 30 seconds ON + 180 seconds (3 minutes) OFF
Sequence is repeated during all Cool Down total time: 12 hours.
Note 3 Required for 30 minutes.
Note 4 Absorbed power peak value during energization.
Note 5 Absorbed power peak value for 60 seconds at converter start-up.
Note 6 Controlled & feeded by local control panel. <1>
Note 7 Emergency diesel generators provides at least 12 hours of 240 Vac power supply, and 240 Vac is maintained by UPS during
diesel generator start-up. <1> <3>
Note 8 Redundant VSDS Train is one and it will be available for all 3 Trains. <2>
Note 9 Humidity detector available on helper motor, but not connected. Power load provision. <5>

ITEM

5 REVISED WHERE SHOWN <5>


3 REVISED WHERE SHOWN <3> N. SOM 6628545/4
2 REVISED WHERE SHOWN <2> LINGUA-LANG. PAGINA-SHEET

1 REVISED WHERE SHOWN <1> A 15 / 15


SOSTITUISCE IL - REPLACES
© 2 0 0 8 N u o v o P i g n o n e S . p . A , a l l r i g h t s r e se r ve d SOSTITUITO DA - REPLACED BY