Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                
0% found this document useful (0 votes)
5 views40 pages

AHU_Kit_MCM-D201N-Install-Manual

Download as pdf or txt
Download as pdf or txt
Download as pdf or txt
You are on page 1/ 40

AHU KIT

MCM-D201N

Air Conditioner
installation manual

imagine the possibilities


Thank you for purchasing this Samsung product.
Contents
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Name of each part and product dimension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Checking before using an AHU KIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Installing an AHU KIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Setting an address and installation option of AHU KIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Trouble shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Installation check and test operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

2
Safety Information
When installing the product, the following safety precautions must be taken for the safety of an installer and user.

Use R-410A refrigerant.


fWhen using R-410A, the inflow of moisture or foreign substances may greatly affect the capacity and reliability of the

ENGLISH
product. Safety precautions must be taken when installing the refrigerant pipe.
fWhen charging mixed refrigerant, you should use liquid refrigerant (If you charge gaseous refrigerant, it may affect
the capacity and reliability of the product as a result of change in formation of the refrigerant.)

FOR INSTALLATION WARNING

Disconnect all the power supplies before installation, service, and cleaning.
The installation must be done by the manufacturer or a qualified person.
fInstallation by an unqualified person may result in a water leakage, electric shock or fire.
Install the unit correctly according to the installation manual.
fAn incorrect installation may result in a water leakage, electric shock or fire.
Manufacturer of AHU KIT is not responsible for accidents due to incorrect installation by an unqualified person. Also,
you should use only supplied or designated parts and tools for installation.
fIf you don’t use the designated parts and tools, product fall, water leakage, electric shock, or fire may occur.
When adding refrigerant, use the R-410A refrigerant only.
fUsing other types of refrigerant may result in product malfunction, explosion etc.
Do not use the pipe for R-22 refrigerant or flare parts.
When there is refrigerant leakage during installation, you must ventilate the area.
fToxic gas may be generated when refrigerant gas contacts with fire.
If the power cable or cord is damaged, it should be replaced by manufacturer or qualified person. The electric work
must be done by a certified person according to code and standard about electric installation, regulation for indoor
wiring and installation manual. In addition, the electric work must be in compliance with rated electric specification.
fVoltage drop, shortage of supply voltage, incorrect power supply work and use of uncertified cables may result in electric
shock or fire.
Arrange the cables between the AHU-KIT and outdoor unit so that the cover of electric part does not rise and then fix
the cover of the electric box to the product firmly.
fIf the cover is attached incompletely, a heat generation, electric shock or fire of the terminal may occur.
The Power supply to the kit should be through dedicated MCCB/ELB or ELCB.
fIf dedicated MCCB/ELB or ELCB is not provided, electric shock or fire may occur because of overcurrent or leakage current.
Install the supplied cables firmly. Fix them securely so that external force is not applied to the terminal.
fIf the connection or fixing is incomplete, heat generation, spark and fire may occur.
Make sure that the power for AHU-KIT is under maximum, and over minimum voltage.
fFailure to do so may result in product malfunction due to electrical component damage and functional degradation of a
part.
Use rated copper wire for the power cable.
Make sure electric wiring is correctly connected.
fFailure to do so may result in fire with overheating.
Make sure there is no leakage of refrigerant gas after finishing installation.
fWhen leakage of refrigerant gas contacts with fire, toxic gas may be generated.

3
Safety Information
FOR INSTALLATION CAUTION

Proper earthing should be done as per the rating.


fDo not connect the ground wire to the gas pipe, water pipe, lightning rod or a ground wire of a telephone.
fIf the grounding is incomplete, electric shock may occur.
Follow the instructions in this manual to make sure that the condensed water dripping from the drain hose runs out
properly and insulate the drain pipe so that dew condensation is not generated.
fIf the drain work is incomplete, property damage may occur due to water leakage.
Install the power cable and communication cable of the AHU-KIT at least 1 m away from other electric appliances and
2 m away from lightning conductor.
fHowever, even 1 m away from an electric appliance, noise may be heard depending on radio wave condition.
Do not install the AHU-KIT in following places.
fThe place where much mineral oil, arsenic acid or steam exist.
The resin parts may be burned, which can result in falling part or water leakage.
fThe place where corrosive gas such as sulfurous acid gas from an exhaust pipe or air outlet can be generated.
The copper pipe or connection part may corrode, which may result in refrigerant leakage.
fThe place where there is a machine that generates electromagnetic waves.
The control system may have a problem which can result in abnormal operation.
fThe place where inflammable gas can leak, carbon fiber or inflammable dust floats, or volatile flammables are
handled.
If the gas leaks and stays around the main valve of the product, fire may occur.
fThe place where indoor unit corrosion may occur such as seashore or spa.
fThe place where external environment such as sunlight, rain, temperature, humidity, dust can directly affect the
product.
❋ The manufacturer is not responsible for the damage occurred by not keeping standard of the installation. (The cost
of the service will be charged.)

4
Name of each part and product dimension
Name of each part and product dimension
ASS'Y Control(Control part)

ENGLISH
(Unit : mm)

Wire saddle Place for AHU KIT PBA insertion

168
182
238
275
350
385
Terminal block(20P)
(53)

ASS’Y EEV(Electronic Expansion Valve): Accessory (Ordered separately)


For detailed information of EEV installation, refer to the installation manual of ASS’Y EEV (MXD-A64K100E) which you
need to purchase additionally.

MXD-A64K100E (Unit : mm)


EEV

254 mm
185 mm

Filter

EEV coil(7 m)
IN/OUT Pipe Diameter :
79 mm
0 12.7mm

5
Parts
Accessories (supplied)
Pipe inlet/outlet Inlet sensor holder Outlet sensor holder
Name Sensor fixing spring
sensor(7 m) (OD Ø6.8 mm) (OD Ø7.8 mm)
Quantity 1 1 1 2

Shape

Name Aluminum tape Rubber tape Insulator Cable tie


Quantity 4 2 2 8

Shape

Additional accessory (not included)


* Wired remote controller
(MWR-WE10✴N)
1

❋ You need to purchase the wired remote controller additionally.


❋ Room temperature sensor is not provided. It should be provided additionally on the field.

6
Checking before using an AHU KIT
Structure diagram of an AHU-KIT

Outdoor unit

ENGLISH
Communication cable: F1,F2

ASS'Y EEV(Electronic Expansion Valve)

EEV Control
Liquid valve

Communication cable:
F3,F4

Return air Exhaust Outdoor


air air Supply air
IN sensor

* Room Temperature
Sensor(mA or PT1000)

Gas pipe
Wired remote controller
OUT sensor

* Room temperature sensor is not provided. It should be provided additionally on the field.

7
Installing an AHU KIT
Installing ASS'Y Control
1. Check the installation location of ASS'Y Control.
fYou can choose either AHU attachment type or AHU separation type depending on the installation environment.
2. Check the length of connection cable of ASS'Y Control.
fThe length of provided connection cable is 7 m.
3. Make sure the location has waterproof and fire prevention structure.
fMake sure that the ASS'Y Control is not exposed to sunlight by covering with a case which has waterproof and fire
prevention structure.

Main PBA

Terminal Block

Functions of ASS'Y Control


fWhen using the ASS’Y Control alone, you can use EEV of 10~40 HP Capacity.
fASS'Y Control adjusts rate of flow for EEV refrigerant and performs control functions through communication with an
indoor unit or wired remote controller.
fThe contact signal for AHU fan operation is sent from ASS'Y Control. When AHU is in Cool/Heat/Fan mode, terminal block
No.1 and No.2 will output contact signal to turn the fan on. At this time, the output is contact signal and not be used for
power supply of motor. (Refer to p.12~13)
fThe terminal block No.3 and No.4 will receive the signal for fan operation status and the signal is the input signal which
AHU KIT control part receives. At this time, the input signal sholud be input as only OPEN/SHORT signal not the signal that
has separate voltage level. (Refer to p.10)
- When the fan operates normally: The terminal block No.3 and No.4 are SHORT status.
- When the fan does not operate: The terminal block No.3 and No.4 are OPEN status.
- Set SEG 21 of installation option 05 series to ‘1(Use)’ to use fan feedback for system protection. (Refer to p. 26)
fThe terminal block Vd/Vd is output defrost signal. (There exist some time delay.)
- When installing a defrost bypass valve, set SEG22 of 05 series installation option as “1”.
fConnect 220~240 V to the terminal block 1(L)/2(N).
fThe terminal block of communication cable (F1, F2) is connected with communication of Outdoor Unit. When installing
additional AHU KIT, the communication (F1, F2) should be connected with the communication (F1,F2) of AHU KIT which
is additionally installed. (Refer to p.12~13)
fThe communication cable(F3, F4) is the communication group of wired remote controller. (Refer to p.12~13)
fWhen installing 10 HP of ASS'Y Control, you shouldn't perform additional control of ASS'Y Control.

8
fFor HP setting, refer to SEG20 of 05 series in installation option section. (Refer to p.26)
fConnect room temperature sensor and discharge temperature sensor(optional) as mA or PT1000Ω type.
- When using the mA type sensor, connect to the terminal block +/-(mA).
- When using the PT1000Ω sensor, connect to the terminal block A/B/C .
- Set the types of room temperature sensor and discharge temperature sensor in SEG24 of 05 series installation option.
The types of the sensors must be same.

ENGLISH
No. CONNECTOR FUNCTION NOTE
1 CN83/84/85 EEV EEV 1/2/3
2 CN86 EEV EEV 4
3 REM01 REMOCON RECEIVER OPTION INPUT
1/3 PIN : COMP CHECK OUT
4 CN82 EXTERNAL CHECK
6/8 PIN : ERROR CHECK OUT
1/2 PIN : EVA IN
5 CN43 SENSOR
3/4 PIN : EVA OUT
6 CN21 DOWNLOAD S/W UPGRADE
7 CN201 EEPROM PBA
8 CN311 2WIRE SUB PBA

9
Installing an AHU KIT

Wiring diagram for ASS’Y Control

❋ AHU KIT sensor displays about 10 KΩ of resistance value at room temperature.

10
Working on power supply
Connecting power/communication cable
fTurn the power off before working on the power supply.
fMaximum cable length and the amount of voltage drop for AHU KIT power/communication cables should be within
10 %.

ENGLISH
fWhen installing the MCCB/ELB or ELCB, consider Power Rating of the AHU motor for correct capacity.
fConnect F3, F4 of AHU KIT terminal to Wired Remote Control.
fUse the appropriate tools for wiring and make sure the wiring is connected tightly within Tightening torque (kgf•cm)
the tightening torque to withstand the external pressure. Arrange the wires so that cover or
M4 12.0~14.7
other parts does not get loose. Otherwise, it may cause overheating, electric shock or fire.
fTo protect the product from external shock or water, put the power and communication cable into a power cable
protection box.
fConnect the power cable through MCCB/ELB or ELCB.
fMaintain more than 50 mm distance between the power cable and communication cable.

• The circuit diagram for wiring represents only an outline so the detailed information about actual installation
work is not described.
CAUTION
• In principle, AHU KIT power supply should be provided separately from an outdoor unit.
• Do not distribute the communication cable as communication error may occur.
• Do not distribute the power cable of terminal block for 2 AHU KITs from 1 AHU KIT.
• When peeling the sheath of power cable, use the appropriate tools to prevent damage inside the wire.
• Make sure that more than 20 mm of power and communication cable of AHU KIT is inside the electric parts.
• Communication cable should be installed separately from power cable or other communication cables.

Selecting a solderless terminal


1. Select a solderless terminal on the basis of nominal sectional area for a connecting power cable.
2. Insulate the solderless terminal and connection part of the connecting power cable with sheath.
Nominal sectional area for cables
1.5 2.5 4
(mm2)
Nominal diameter for screws (mm) 4 4 4 4 4
Standard dimension (mm) 6.6 8 6.6 8.5 9.5
B
Allowance (mm) ±0.2 ±0.2 ±0.2
Standard dimension (mm) 3.4 4.2 5.6
+0.3 +0.3 +0.3 Silver soldering
D
Allowance (mm)
-0.2 -0.2 -0.2
Standard dimension (mm) 1.7 2.3 3.4
d1
Allowance (mm) ±0.2 ±0.2 ±0.2
E Min. 4.1 6 6
F Min. 6 6 5
L Max. 16 17.5 20
Standard dimension (mm) 4.3 4.3 4.3
d2 +0.2 +0.2 +0.2
Allowance (mm)
0 0 0
t Min. 0.7 0.8 0.9

11
Installing an AHU KIT
Specification of electronic wire
Power supply MCCB ELB Power cable Earth cable Communication cable
Max : 242V XA, 30 mmA 2 2
XA 2.5 mm 2.5 mm 0.75~1.5 mm2
Min : 198V 0.1 s

fDecide the capacity of ELB and MCCB by below formula.

The capacity of ELB, MCCB X [A] = 1.25 X 1.1 X ∑Ai

❋ X : The capacity of ELB, MCCB


❋ ∑Ai : Sum of Rating currents of each indoor unit.
❋ Refer to each installation manual about the rating current of indoor unit.
❋ Rating current

Unit Model Rating current


AHU KIT MCM-D201N 0.5A

Connection diagram of ASS'Y Control


Installation example 1) Connection diagram of 1 outdoor unit + 1 AHU

Wired remote controller Outdoor Unit

Defrost signal

Contact signal for AHU


Sensor fan ON
220~240 V (mA)
Supply
power Sensor
(PT1000) F4: Wired remote controller communication cable
F3: Wired remote controller communication cable
F2: Outdoor unit communication cable
F1: Outdoor unit communication cable
Input contact signal for fan operation
status and off power.

12
Installation example 2) AHU KIT + contact signal for AHU fan ON

AHU MOTOR
POWER SOURE

ENGLISH
Contact signal for fan ON

AHU AHU MOTOR


controller

❋ AHU KIT outputs only contact signals for FAN output.


Use the FAN output signal from the AHU controller to control the AHU FAN motor.
(Do not connect the FAN oupt signal directly to driving part.)

Installation example 3) Setting a room temperature sensor for installing multiple AHU KITs

SLAVE AHU Kit 3 SLAVE AHU Kit 2

MASTER AHU Kit SLAVE AHU Kit 1

Room
temperature
sensor PT1000 Wired remote
controller

• For common AHU with multiple AHU KITS, sharing with 1 room temperature sensor is possible. The room
temperature sensor sharing uses the communication of wired remote controller, so Wired remote controller
CAUTION
should be installed. mA temperature sensor is the same as well. (Refer to SEG 24 of installation option 05 series
on page 26.)
• If one room temperature sensor is used for multiple AHU kits, MCM-D201N should only be used.

13
Installing an AHU KIT
Welding with nitrogen blowing
➀ Refrigerant pipe
➁ Location for welding
➂ Tape
➃ Hands valve
➄ Reducing valve
➅ Nitrogen gas

1. When welding a pipe, perform nitrozen blowing work.


- If you didn't blow the nitrogen for pipe welding, many oxides would be accumulated inside the pipe, which may cause
the valve of refrigerant system and compressor to operate abnormally.
2. When inputting the nitrogen gas, the rate of flow for nitrogen gas should be less than 0.02 MPa using the reducing
valve. (You should be able to feel the degree on your skin.)

Installing ASS'Y EEV(Not provided)


1. Check that ASS'Y EEV is installed inside the AHU.
- Since dew condensation may occur around the ASS'Y EEV pipe, install the ASS'Y EEV at a place where condensate water
can be drained.
2. Check whether IN and OUT pipe connection is correct.
3. Essential to check the ASS'Y EEV main body is installed vertically.
- ASS'Y EEV main body should be installed within the range of +/- 15˚ of standard for vertical installation. Otherwise, the
reliability of ASS'Y EEV cannot be guranteed.
4. Fix the EEV to AHU fixing groove firmly as shown in the image A below.

Standard for vertical Standard for vertical


installation installation
30° 30°
A

Insulator
Clamp

Clamp(Work area for AHU


manufacturer)
Insulator(Work area for AHU
manufacturer)

A: High pressure pipe from outdoor unit(IN)


- Diameter : Ø12.7 mm
B: Low pressure pipe to AHU heat exchanger(OUT)
- Diameter : Ø12.7 mm

14
5. For checking EEV service, please attach a label sticker.
fAttach one label to upper middle part of ASS'Y EEV valve body and attach the same color of a lable sticker to valve wire
housing.
6. Connect the EEV termial block to exact places on PCB according to set HP.
fWhen the set HP of AHU KIT is set as 40 HP: Connect EEV-1, EEV-2, EEV-3 and EEV-4
fWhen the set HP of AHU KIT is set as 30 HP: Connect EEV-1, EEV-2, and EEV-3.

ENGLISH
fWhen the set HP of AHU KIT is set as 20 HP: Connect EEV-1 and EEV-2

EEV-1 EEV-2 EEV-3

Wire saddle EEV-4

❋ EEV connector connection should be fixed to the wire saddle as shown in the image.

• New AHU KIT (ACM-D201N) has a different way to set the number of the indoor unit installation from the
CAUTION previous AHU KIT (ACM-D201) and an outdoor unit.
• Be careful when setting the number of the indoor unit installation with an outdoor unit.
• When setting AHU KIT HP, refer to the SEG 20 of Installation option 05 series on page 26.
• Regardless of the AHU KIT HP setting, one indoor unit will be recognized.

15
Installing an AHU KIT
Installing IN/OUT sensor

1. Attach the EVA IN sensor after the distributor and on the lowest temperature pipe of a heat exchanger.
2. Install the EVA OUT sensor 200 mm after the header of AHU heat exchanger as shown in the picture.
3. Insulate the EVA IN and OUT sensor so that it is not affected by wind.
4. Install the ROOM temperature sensor on the RA(Return Air) path of AHU.

Selecting the location of EVA_IN/OUT sensor


❋ Refrigerant flow

Cool mode
Distributor Heat mode

1 EVA IN sensor
Header 200 ”
”
2 EVA OUT sensor

Example of ROOM temperature sensor installation

Return air Exhaust air Supply air


Outdoor air

Location of room temperature sensor

• In principle, the sensor holder of EVA IN/OUT sensor should be welded at the designated place and then the EVA
IN/OUT sensor should be fixed with a clip.
NOTE
• EVA IN/OUT sensor should be installed at the place where temperature of the heat exchanger air inlet or outlet
can be measured accurately.

16
Example of IN/OUT sensor installation 1
1. Chcek the sensor and sensor holder you will attach.

Diameter of a Diameter of a sensor


Type
NOTE
sensor (mm) holder (mm) Clip for sensor fixing Sensor holder
IN sensor(Blue) ø6 ø 6.8

ENGLISH
OUT sensor(Red) ø7 ø 7.8

Insulator IN/OUT sensor

2. Attach the sensor holder to the selected location of a pipe.

Attaching a sensor Pipe


NOTE
• Attach the sensor at the place where temperature
detection is easily available. (Refer to p.16)
• Attach the sensor holder as closely as possible on the
Sensor holder
surface of the pipe.
• Check whether the sensor you will attach is IN or OUT
sensor. (The size of IN/OUT sensor is different.)

3. Insert the sensor and the clip into the sensor holder.
IN/OUT sensor

Clip for sensor fixing

4. Bend the clip to fix it.

5. Attach the insulator around the attached sensor.

Insulator

17
Installing an AHU KIT
Example of IN/OUT sensor installation 2
1. Chcek the sensor and sensor holder you will attach.

Diameter of a Diameter of a sensor IN/OUT


Type
NOTE sensor (mm) holder (mm) sensor
Insulator Cable tie
IN sensor(Blue) ø6 ø 6.8
OUT sensor(Red) ø7 ø 7.8

Aluminum tape Rubber tape

2. Attach the sensor closely to the pipe.


Attaching a sensor
• Attach the sensor at the place where temperature Pipe
NOTE
detection is easily available. (Refer to p.16)
• Attach the sensor as closely as possible on the surface of
Sensor
the pipe.
• Do not use a sensor holder.

3. After attaching the sensor on the pipe, cover it with aluminum


tape.
IN/OUT sensor

Aluminum tape

4. Cover the sensor with rubber tape.

Rubber tape

IN/OUT sensor

5. Fix the sensor with cable ties.

Cable tie

6. Attach the insulator around the attached sensor.

Insulator

18
Setting an address and installation option of AHU KIT
fSet the address of an AHU KIT and installation option with remote controller options. Set each option separately since
you cannot set the ADDRESS setting and indoor unit installation setting option at the same time. You need to set twice
when setting the address of an AHU KIT and installation option.
fThe reception part of a remote controller is built in the AHU KIT PBA.

ENGLISH
The procedure of option setting

Entering mode for Option setting mode


option setting

Mode change

High Temp Button High Fan Button

Low Temp Button Low Fan Button

Step 1. Entering mode for option setting


1. Remove batteries from the remote controller.
2. While pressing the button of high temp and low temp at the same time, insert the batteries.

3. Check if you have entered the option setting status.

Step 2. The procedure of option setting


After entering the option setting status, select the option as listed below.

• Option setting is available from SEG1 to SEG 24


CAUTION • SEG1, SEG7, SEG13, and SEG19 are not set as page option.
• Set the SEG2~SEG6, and SEG8~SEG12 as ON status and SEG14~18, and SEG20~24 as OFF status.
SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 On(SEG1~12) Off(SEG13~24)
0 X X X X X 1 X X X X X
SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
2 X X X X X 3 X X X X X

19
Setting an address and installation option of AHU KIT
Option setting Status
1. Setting SEG2, SEG3 option
Press Low Fan button( ) to enter SEG2 value.
Press High Fan button( ) to enter SEG3 value.
Each time you press the button, p p … p will be selected in rotation. SEG2 SEG3

2. Setting Cool mode


Press button to be changed to Cool mode in the ON status.

3. Setting SEG4, SEG5 option


Press Low Fan button( ) to enter SEG4 value.
Press High Fan button( ) to enter SEG5 value.
Each time you press the button, p p … p will be selected in rotation. SEG4 SEG5

4. Setting Dry mode


Press button to be changed to DRY mode in the ON status.

5. Setting SEG6, SEG8 option


Press Low Fan button( ) to enter SEG6 value.
Press High Fan button( ) to enter SEG8 value.
Each time you press the button, p p … p will be selected in rotation. SEG6 SEG8

6. Setting Fan mode


Press button to be changed to FAN mode in the ON status.

7. Setting SEG9, SEG10 option


Press Low Fan button( ) to enter SEG9 value.
Press High Fan button( ) to enter SEG10 value.
Each time you press the button, p p … p will be selected in rotation. SEG9 SEG10

8. Setting Heat mode


Press button to be changed to HEAT mode in the ON status.

9. Setting SEG11, SEG12 option


Press Low Fan button( ) to enter SEG11 value.
Press High Fan button( ) to enter SEG12 value.
Each time you press the button, p p … p will be selected in rotation. SEG11 SEG12

10. Setting Auto mode


Press button to be changed to AUTO mode in the OFF status.

11. Setting SEG14, SEG15 option


Press Low Fan button( ) to enter SEG14 value.
Press High Fan button( ) to enter SEG15 value.
Each time you press the button, p p … p will be selected in rotation. SEG14 SEG15

20
Option setting Status

12. Setting Cool mode


Press button to be change to Cool mode in the OFF status.

13. Setting SEG16, SEG17 option

ENGLISH
Press Low Fan button( ) to enter SEG16 value.
Press High Fan button( ) to enter SEG17 value.
Each time you press the button, p p … p will be selected in rotation. SEG16 SEG17

14. Setting Dry mode


Press button to be change to Dry mode in the OFF status.

15. Setting SEG18, SEG20 option


Press Low Fan button( ) to enter SEG18 value.
Press High Fan button( ) to enter SEG20 value.
Each time you press the button, p p … p will be selected in rotation. SEG18 SEG20

16. Setting Fan mode


Press button to be change to Fan mode in the OFF status.

17. Setting SEG21, SEG22 option


Press Low Fan button( ) to enter SEG21 value.
Press High Fan button( ) to enter SEG22 value.
Each time you press the button, p p … p will be selected in rotation. SEG21 SEG22

18. Setting Heat mode


Press button to be change to HEAT mode in the OFF status.

19. Setting SEG23, SEG24 mode


Press Low Fan button( ) to enter SEG23 value.
Press High Fan button( ) to enter SEG24 value.
Each time you press the button, p p … p will be selected in rotation. SEG23 SEG24

Step 3. Checking the option you have set


After setting option, press button to check whether the option code you have entered is correct or not.

→ → → → →

→ → → →

Step 4. Entering an option


Press the operation button with the direction of a remote controller to set.
For the correct option setting, you must enter the option twice.
Step 5. Checking operation
1) Press the power reset button or the reset button of an outdoor unit to reset the settings.
2) Take the batteries out of the remote controller and insert them again and then press the button.
21
Setting an address and installation option of AHU KIT
Setting an AHU KIT address (MAIN/RMC)
1. Check whether power is supplied or not.
- When the AHU KIT is not plugged in, there should be additional power supply.
2. The reception part of a remote controller is built in the AHU KIT PBA.
3. Each address of AHU KIT(MAIN/RMC) should be set according to installation conditions.
4. Assign each AHU KIT address(MAIN/RMC) with a remote controller.
- The default setting value of an AHU KIT address(MAIN/RMC) is “0A0000-100000-200000-300000”.

Option No. : 0AXXXX-1XXXXX-2XXXXX-3XXXXX

Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6


Hundreds' digit of an
Explanation PAGE MODE Setting Main address Tens' digit of an address Unit digit of an address
address

Remote
Controller
Display

Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
No Main
0
Indication address
and Details Main Hundred's
0 A 0~9 0~9 Tens' digit 0~9 A unit digit
address digit
1
setting
mode
Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12

Explanation PAGE Setting RMC address Group channel(*16) Group address

Remote
Controller
Display

Indication Details - Indication Details - Indication Details Indication Details


No RMC
0
Indication address
and Details 1 RMC RMC1 0~2 RMC2 0~F
address
1
setting
mode

• When “A”~”F” is entered to SEG5~6, the main address of AHU KIT will not be changed.
CAUTION • If you set the SEG 3 as 0, the AHU KIT will maintain the existing MAIN ADDRESS even if you have entered the
option value of SEG5~6.
• If you set the SEG 9 as 0, the AHU KIT will maintain the existing RMC ADDRESS even if you have entered the
option value of SEG11~12.

22
Setting the installation option of an AHU KIT (suitable for the condition of each installation location)
1. Check whether power is supplied or not.
- When the AHU KIT is not plugged in, there should be additional power supply.
2. The reception part of a remote controller is built in the AHU KIT PBA.
3. Set the installation option of an AHU KIT according to installation conditions.
- The default setting of an AHU KIT installation option is “020010-100000-200000-300000”.

ENGLISH
4. Set the AHU KIT option with a remote controller.

■ 02 series installation option


SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
External room
temperature sensor/
0 2 - Central control -
Minimizing fan operation
when thermostat is off
SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
EEV Step when
1 - - - -
heating stops
SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
External control
2 External control - Buzzer -
output
SEG19 SEG20 SE21 SEG22 SEG23 SEG24
Oil return/EEV step
Compensation of
3 - of stopped defrost - -
heating setting
mode
fSEG5 central control option is basically set as 1 (Use), so you don’t need to set the central control option additionally.
When you exclude the indoor unit control from central control, change the setting as 0(Disuse).
fWhen you set the value other than the SEG setting values, it will be set as "0".

Option No. : 02XXXX-1XXXXX-2XXXXX-3XXXXX

Option SEG1 SEG2 SEG3 SEG4(*1) SEG5 SEG6

Use of external room temperature sensor/Minimizing


Explanation PAGE MODE Use of robot cleaning Use of central control FAN RPM compensation
fan operation when thermostat is off

Remote
Controller
Display
Indication Details Indication Details Indication Details Indication Details Indication Details
Use of
Minimizing fan
External room
operation when
0 Disuse temperature 0 Disuse
thermostat is off
sensor
0 Disuse Disuse
Indication and 1 Use Disuse
Details 0 2 2 Disuse Heating Use
3 Use Heating Use
4 Disuse Cooling Use 1 Use
5 Use Cooling Use
6 Disuse All Use
7 Use All Use

23
Setting an address and installation option of AHU KIT
Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12

Explanation PAGE Use of drain pump Use of hot water heater Use of electronic heater EEV Step when heating stops Master / Slave

Remote
Controller
Display
Indication Details Indication Details
Indication and 0 Default value
Details 1 Noise decreasing
1
setting

Option SEG13 SEG14 SEG15 SEG16 SEG17 SEG18


Setting the output of external Number of hours using
Explanation PAGE Use of external control S-Plasma ion Buzzer control
control filter
Remote
Controller
Display
Indication Details Indication Details Indication Details Indication Details
0 Disuse 0 Thermo on 0 Use buzzer
Indication and
Details ON/OFF
2 1
control 1 Operation on 1 Disuse buzzer
2 OFF control
Option SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
Offset of compensation for Oil return/EEV step of
Explanation PAGE -
heating installation stopped defrost mode
Remote
Controller
Display
Indication Details Indication Details Indication Details Indication Details
0 Default
Default
0 0 -
Indication and 1 2°C(35.6°F) value
Details 3
Noise
2 5°C(41°F) 1 decreasing
setting

24
(*1)
Minimizing fan operation when thermostat is off
- Fan operates for 20 seconds at an interval of 5 minutes in heating mode.
- Fan stops when thermostat is off in cooling mode.
- Make sure to connect the wired remote controller or the external room temperature sensor if you use the function of
external room temperature sensor or minimizing fan operation. (In order to implement the functions the option of
using temperature sensor inside the wired remote controller must be set. Refer to the installation manual of the wired
remote controller.

ENGLISH
■ 05 series installation option
SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
(When setting SEG3)
Use of Auto Change (When setting SEG3) (When setting SEG3)
Standard for mode
0 5 Over for HR only in Standard heating temp. Standard cooling
change Heating →
Auto mode Offset temp. Offset
Cooling
SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
(When setting SEG3) Compensation option
(When setting SEG3)
Standard for mode for Long pipe or height
1 Time required for - -
change Cooling → difference between
mode change
Heating indoor units
SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
Temperature control
2 - - - -
by using simple BMS
SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
Skip the prevention
3 HP setting Fan Feedback Defrost signal Sensor
of cold air

■ 05 series installation option(Detailed)


Option No. : 05XXXX-1XXXXX-2XXXXX-3XXXXX

Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6


Use of Auto Change Over (When setting SEG3) (When setting SEG3) (When setting SEG3)
Explanation PAGE MODE
for HR only in Auto mode Standard heating temp. Offset Standard cooling temp. Offset Standard for mode change Heating → Cooling

Remote
Controller
Display

Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
Follow
0 product 0 0 0 0 0 1
options
1 0.5 1 0.5 1 1.5
Indication 2 1 2 1 2 2
and Details 0 5 3 1.5 3 1.5 3 2.5
Use Auto
1 Change Over 4 2 4 2 4 3
for HR only 5 2.5 5 2.5 5 3.5
6 3 6 3 6 4
7 3.5 7 3.5 7 4.5

25
Setting an address and installation option of AHU KIT
Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
(When setting SEG3) (When setting SEG3) Compensation option for Long
Explanation PAGE Standard for mode change Time required for mode pipe or height diffference between
Cooling → Heating mode change indoor units

Remote
Controller
Display

Indication Details Indication Details Indication Details Indication Details


0 1 0 5 min. 0 Use default value
1 1.5 1 7 min. 1) Height difference1) is
2 2 2 9 min. more than 30 m or
1
Indication 2) Distance2) is longer
and Details 3 2.5 3 11 min. than 110 m
1
4 3 4 13 min. 1) Height difference1) is
5 3.5 5 15 min. 15~30 m or
2
6 4 6 20 min. 2) Distance2) is
7 4.5 7 30 min. 50~110 m
Option SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
- - - Simple BMS temperature -
control

Explanation 2
Indication Details
0 Room
temperature
1 Discharge
temperature
Option SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
Explanation PAGE HP setting Fan Feedback Defrost signal Skip the prevention of cold air Sensor

Remote
Controller
Display

Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
Default Sharing the room and discharge
0 0 Disuse 0 Disuse 0 Disuse 0 temperature value of a master
(10 HP) indoor unit
Master indoor unit
1 10 HP 1 Use 1 Use 1 Use 1 - Room temperature : PT1000 Ω
- Discharge temperature :
4~20 mA
Indication Master indoor unit
and Details
3) - Room temperature : 4~20 mA
2 20 HP 2
- Discharge temperature :
PT1000 Ω
3 30 HP Master indoor unit
- Room temperature : a wired
3 remote controller’s sensor
4 40 HP
- Discharge temperature :
4~20 mA
1) Height difference : The difference of the height between the corresponding indoor uint and the indoor unit installed at the lowest place.
For example, When the indoor unit is installed 40 m(131.23 ft) higher than the indoor unit installed at the lowest place, select the option "1".
2) Distance : The difference between the pipe length of the indoor unit istalled at the farthest place from an outdoor unit and the pipe length of the corresponding indoor unit from an outdoor
unit. For example, when the farthest pipe length is 100 m(328 ft) and the corresponding indoor unit is 40 m(131.23 ft) away from an outdoor unit, select the option "2". (100 m(328 ft) -
40 m(131.23 ft) = 60 m(196.85 ft))
3) Regardless of the AHU KIT HP setting, one indoor unit will be recognized. Therefore, be careful when setting the number of the indoor unit installation with an outdoor unit.

26
Additional information for SEG 3,4,5,6,8,9

When the SEG 3 is set as "1" and follow Auto Change Over for HR only operation, it will operate as follows.

Thermo Off

Thermo Off
Thermo On

Thermo On
Heating

Heating
Cooling

Cooling

ENGLISH
Standard temp. for Heating
Temp. → Cooling
c

Standard temp. for B C


Cooling
Ts
A D
Set temp. for Auto
mode a

Standard temp. for Heating


d

Standard temp.
A : Set with SEG4(˚C)
for Cooling →
Heating B : Set with SEG5(˚C)
C : Set with SEG6(˚C)
D : Set with SEG8(˚C)

Cooling/Heating mode can be changed when Thermo Off status is maintained during the time with SEG9.

27
Changing a particular option
You can change each digit of set option.
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Tens' digit of an Unit digit of an
Option mode to
Explanation PAGE MODE option SEG to option SEG to Changed value
change
change change
Remote
Controller
Display
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
Indication
and Tens’ Unit
Option Changed
Details 0 D 0~F digit of 0~9 digit of 0~9 0~9
mode value
SEG SEG

• When changing a digit of an AHU KIT address setting option, set the SEG3 as ‘A’.
NOTE • When changing a digit of an AHU KIT installation option, set the SEG3 as ‘2’.
Ex) When setting the ‘buzzer control’ into disuse status.
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Tens' digit of Unit digit of an
Option mode
Explanation PAGE MODE an option SEG option SEG to Changed value
to change
to change change
Indication 0 D 2 1 7 1

Setting discharge temperature control


1. In service mode of a wired remote control, you can set whether to use “Discharge temperature control” or not and also
can set targeted temperature of heating and cooling. Refer to “Installation/service setting mode” in a wired remote
controller’s installation manual.
2. If you set to use “Discharge temperature control”, a thermostat of a product is turned on or off according to room set
temperature and room temperature. Discharge temperature control is carried out while thermostat is on.
❋ The discharge temperature control can be set using DMS, also.
❋ Discharge temperature may not meet the desired temperature(set value) depending on conditions of the external air.
3. When the discharge temperature control is used, SEG21 of 01 series installation option must be set as “1”.

28
Trouble shooting
Initial check-up
1. Check the connection status between an outdoor unit and the AHU-KIT.
fCheck that you have followed wiring method according to the circuit diagram or installation manual.

ENGLISH
fCheck that AHU-KIT PBA is installed in a place where there is no influence from outdoor humidity, dust and temperature.

2. Check the power voltage is AC198 V~AC264 V.

3. Check the voltage of each part has a problem.


f5 V-GND both terminals: DC 4.5~5.5 V
f12 V-GND both terminals: DC 11~13 V

Error on EEPROM
Outdoor unit display
Description Communication problem between EEPROM of AHU KIT and micom.
- EEPROM PBA OF AHU KIT ERROR(Physical problem of parts/circuit)
Reason
- Replace EEPROM PBA

• Wired remote controller will display the same error shown in the outdoor unit.
NOTE

Error on the option of a remote controller


Outdoor unit display
Description The remote controller option of AHU KIT is not the same.
Reason Enter the remote controller option again.

29
Trouble shooting
Error on a sensor
Error on the detachment of AHU-KIT heat exchanger EVA IN sensor

Outdoor unit display xxx


 (xxx: Address of an indoor unit with an error)
Description Refer to the description below.
Reason Detachment of indoor heat exchanger EVA IN piping sensor

1. Description
- In Cool mode

Tcond, out-Tair, out > 3°C OK


Tair, in-TEVA, in > 4°C NO
Tair, in-TEVA, out > 4°C NO
Indoor unit operation or thermo ON during
OK
operation of a compressor
Error message Error on the detachment of indoor unit heat exchanger EVA IN sensor

2. Checking method
- After checking the detachment status of AHU KIT heat exchanger EVA IN sensor, assemble the sensor.

Error on the detachment of AHU KIT heat exchanger EVA OUT sensor

Outdoor unit display xxx


 (xxx: Address of an indoor unit with an error)
Description Refer to the description below.
Reason Detachment of indoor heat exchanger EVA OUT piping sensor

1. Description
- In Cool mode

Tcond, out-Tair, out > 3°C OK


Tair, in-TEVA, in > 4°C OK
Tair, in-TEVA, out > 4°C NO
Indoor unit operation or thermo ON during operation
OK
of a compressor
Error on detachment of indoor unit heat exchanger EVA OUT
Error message
sensor

2. Checking method
- After checking the detachment status of AHU KIT heat exchanger EVA OUT sensor, assemble the sensor.

• Wired remote controller will display the same error shown in the outdoor unit.
NOTE

30
Error on AHU KIT temperature sensor OPEN/SHORT
1. Checking method

(Room temperature sensor OPEN/SHORT)


Outdoor unit display
(Discharge temperature sensor OPEN/SHORT)

ENGLISH
Description When the temperature sensor part of AHU KIT is detected as OPEN/SHORT
Reason Incorrect installation of PT1000 temperature sensor or mA thermometer

Temperature feature table of PT1000


fAfter detaching the connector(CN41), measure the electric resistance between terminal A and terminal C, and
between terminal B and terminal C and then compare the table below. If the resistance is out of -30 °C ~ +50 °C
section, it will be displayed as error indication area.
Feature of PT1000 sensor

PT1000
Resistance

Temperature

Feature table of mA thermometer


fAfter measuring the DC voltage of mA+/- terminal in connector(CN41) connection status, compare the voltage with
the table below. If the voltage is out of -50 °C ~ +50 °C section, it will be displayed as error indication area.
fThe range of 4 ~ 20 mA current temperature sensor : -50 ~ +50 °C
Feature of mA thermometer

Voltage
Therminal voltage

Temperature

• Wired remote controller will display the same error shown in the outdoor unit.
NOTE

31
Trouble shooting
Error on AHU KIT temperature senor OPEN/SHORT
1. Checking method

Outdoor unit display (EVA IN sensor OPEN/SHORT)


(EVA OUT sensor OPEN/SHORT)
Description When the temperature sensor part of AHU KIT is OPEN/SHORT
Reason Loose contact between a sensor and PBA and defective sensor

Is the temperature sensor Yes


connector of AHU KIT EVA IN/OUT
detached from PBA?

No After connecting the connector to PBA, operate


it again.

Temperature(°C) Resistance(kΩ)
After detaching the temperature sensor connector
70 2.2
of AHU KIT EVA IN/OUT from the PBA, measure the
electrical resistance between both terminals. 60 3.0
50 4.2
40 5.8
Yes 30 8.3
20 12.1
10 18.0
0 27.3
-10 43.0
At this time, does the resistance value Yes
largely get out of the right table?

No
Since the temperature sensor of AHU KIT EVA IN/OUT
itself is defective, replace it.

After replacing the PBA, operate the product again.

• Wired remote controller will display the same error shown in the outdoor unit.
NOTE

32
Error on a fan
Outdoor unit display
When the feedback signal is maintained as OPEN status for 10 seconds after outputting the
Description
fan operation signal from ASS’Y Control ( For AHU KIT)
• Fan operation of AHU KIT is abnormal.

ENGLISH
Reason • The circuit to detect the fan feedback signal of AHU KIT is not formed or
misconnected.
1. Checking method

Set the 05 series SEG21 of AHU PBA installation option as “0”.


Have you configured the system (It will not detect the fan feedback signal.)
to receive the fan feedback signal?
(Refer to p.12~13)

No
No
Do you need the fan feedback?

Yes
Yes

Connect the feedback signal to fan check terminal of


ASS’Y control.
(It consist of contact signal)
Check the 05 series SEG21 in installation option of ASS’Y
control is set as “1”.

No
Is the fan operating? Check the fan control of AHU.

Yes

When the AHU KIT fan is in operation, No Form the control circuit so that the proper fan feedback
does the fan feedback signal provide signal is output depending on fan operation status.
the contact signal in SHORT status?

Yes

Replace the ASS’Y Control PBA.

• Only the contact signal without power supply should be entered to detecting terminal of fan feedback signal. If
voltage or current is connected other than the contact signal without power supply, the ASS’Y Control may be
NOTE
damaged.

33
Trouble shooting
Error on EEV step control
Outdoor unit display N/A
In cool mode, EEV step is controlled to minimum 230 steps and maximum 1700 steps. In
Description
heat mode, the EEV step is controlled to minimum 1000 steps.
• The location of EVA IN/OUT sensor is not correct.
• EEV coil is reversed.
Reason
• All or part of EEV coil is detached.
• Refrigerant is overcharged.
1. Checking method

Attach the EVA IN sensor to the branched pipe


No between the distributor and the heat exchanger and to
Is the location of EVA IN sensor correct?
the close part of the heat exchanger.
Check the status of sensor attachment. (Refer to p.16)

Yes

No Attach the EVA OUT sensor to the rear part of the


Is the location of EVA OUT sensor correct? heat exchanger header. Check the status of sensor
attachment. (Refer to p.16)

Yes

No Check that the EEV wire is firmly connected to the PBA


Is the EEV wire connected to PBA?
connector.

Yes

No
Is the amount of added refrigerant enough? Charge the appropriate amount of refrigerant.

Yes

Replace the ASS’Y control PBA.

34
Error on tracking
Communication error between AHU KIT and an outdoor unit during the tracking (During initial operation)

Outdoor unit display


Description Communication error between AHU KIT and an outdoor unit

ENGLISH
Reason Refer to the diagram below.

1. Checking method

Compare and check the setting value for the number of AHU
KIT installation with outdoor unit PBA and the real number of ❈ Regardless of setting HP capacity, the number of AHU Kit
AHU KIT installation. installation is recognized as one indoor unit.

Is the actual number of AHU KIT installation the No


same as the setting value for the number of
AHU-KIT installation?

Yes After setting the switch for the number of AHU KIT
installation set up on the outdoor unit correctly, press
the reset key(k3) of outdoor unit PBA to restart the
Press the reset key(K3) of outdoor unit PBA and view the
tracking.
display part to check the number of AHU KIT which responds
to the tracking.

Yes
Is there a response from AHU KIT on the display
part during the tracking?
After 2 minutes, check whether the PBA address setting
is repeated by finding the AHU KIT that displays the
No communication error.
− When the AHU KIT address is repeated, communication
After removing the communication cable which is connected error may occur. In this case, the communication error
to AHU KIT from an outdoor unit, measure the 2 wires on the may occur with all the AHU KITs(more than 2) whose
outdoor unit with SCOPE. address setting is incorrectly set.

Yes
If there is no problem with the address, check the
communication cable and replace the AHU KIT PBA.

Is the voltage between 2 wires square wave


No
that is more than DC±0.7?

After checking the communication cable or the


Yes connector of outdoor unit PBA, replace the PBA.
− Check the communication cable connection between an
outdoor unit and AHU KIT and between indoor units.
− When there is no problem, check the AHU KIT by • Wired remote controller will display the
connecting one by one. NOTE same error shown in the outdoor unit.
− Replace the PBA of AHU KIT for the problem.

35
Trouble shooting
Error on communication between AHU KIT and an outdoor unit after the tracking (During operation)

Outdoor unit display


Description When the communication between the AHU KIT and an outdoor unit is not available for 2 minutes during operation. (All rooms)
Reason The communication error between AHU KIT and an outdoor unit or the problem with the setting switch for the number of AHU KIT installation.

1. Checking method

Press the reset key(K3) of outdoor unit PBA and check the
display part.

Yes
Is there a response from AHU KIT on the display
part during the tracking?
After 2 minutes, check whether the PBA address setting
is repeated by finding the AHU KIT that displays the
No communication error.
− When the AHU KIT address is repeated, communication
error may occur. In this case, the communication error may
After removing the communication cable which is connected occur with all the AHU KITs(more than 2) whose address
to AHU KIT from an outdoor unvit, measure the 2 wires on the setting is incorrectly set.
outdoor unit with SCOPE.

Yes If there is no problem with the address, check the


communication cable and replace the AHU KIT PBA.

Is the voltage between 2 wires square wave No


that is more than DC±0.7 as shown in the
image below?

After checking the communication cable or the


Yes connector of outdoor unit PBA, replace the PBA.

− Check the communication cable connection between an


outdoor unit and AHU KIT and between indoor units.
− When there is no problem, check the AHU KIT by
connecting one by one.
− Replace the PBA of AHU KIT with a problem.

• Wired remote controller will display the same error shown in the outdoor unit.
NOTE

Good Bad

+0.7V

-0.7V

36
Installation check and test operation
Checking AHU KIT installation
1. Check that ASS’Y Control is correctly installed.
- You can choose either AHU attachment type or AHU separation type.

ENGLISH
- Check the length of connection cable of ASS'Y Control is correct.
- Check that the connection of ASS’Y Control connecting cable is correct.
- Make sure the location has waterproof and fire prevention structure with a specially designed case. ( For the separation
type, it is essential.)
- Make sure the ASS’Y Control is not exposed to sunlight or rain.

2. Check that the ASS’Y EEV is correctly installed.


- Check that ASS'Y EEV is installed inside the AHU.
- Check whether IN and OUT pipe connection is correct.
- Must check the ASS'Y EEV main body is installed vertically.
- Check that the ASS'Y EEV is installed at the place where condensate water can be drained.

3. Check that the EVA IN/OUT sensor is correctly installed.


- After attaching the EVA IN sensor after the distributor and on the lowest temperature pipe of a heat exchanger, check
that you have insulated the attached sensor.
- After installing the EVA OUT sensor 200 mm after the header of AHU heat exchanger, check that you have insulated the
attached sensor.

• ASS’Y Control should be installed with the CASE that has water proof and fire prevention function.
CAUTION

Test operation
1. Before supplying power, measure the grounding between the power terminal(1phase: L, N) and AHU KIT using the
DC 500 V insulation-resistance tester.
- Measured value should be more than 30 MΩ.

• Do not measure the communication terminal as the communication circuit may get damaged.
CAUTION • For the communication terminal, check the short circuit using a general circuit tester.

2. Before supplying power, check the voltage of the power(L, N), and turn the switch on.

N
220-240 V
L
<MCCB/ELB or ELCB>

3. After finishing and checking installation and the items below, check that the AHU KIT operates correctly.
- The firmness of AHU KIT installation environment and safety
- Thermal resistance of insulator for refrigerant pipe
- Leakage of refrigerant gas
- Drainage status
- Power connection status
- Connection status with a circuit breaker and grounding status
- Correct operation for each operation mode

37
MEMO

38
ENGLISH

39
MEMO

You might also like