AHU_Kit_MCM-D201N-Install-Manual
AHU_Kit_MCM-D201N-Install-Manual
AHU_Kit_MCM-D201N-Install-Manual
MCM-D201N
Air Conditioner
installation manual
2
Safety Information
When installing the product, the following safety precautions must be taken for the safety of an installer and user.
ENGLISH
product. Safety precautions must be taken when installing the refrigerant pipe.
fWhen charging mixed refrigerant, you should use liquid refrigerant (If you charge gaseous refrigerant, it may affect
the capacity and reliability of the product as a result of change in formation of the refrigerant.)
Disconnect all the power supplies before installation, service, and cleaning.
The installation must be done by the manufacturer or a qualified person.
fInstallation by an unqualified person may result in a water leakage, electric shock or fire.
Install the unit correctly according to the installation manual.
fAn incorrect installation may result in a water leakage, electric shock or fire.
Manufacturer of AHU KIT is not responsible for accidents due to incorrect installation by an unqualified person. Also,
you should use only supplied or designated parts and tools for installation.
fIf you don’t use the designated parts and tools, product fall, water leakage, electric shock, or fire may occur.
When adding refrigerant, use the R-410A refrigerant only.
fUsing other types of refrigerant may result in product malfunction, explosion etc.
Do not use the pipe for R-22 refrigerant or flare parts.
When there is refrigerant leakage during installation, you must ventilate the area.
fToxic gas may be generated when refrigerant gas contacts with fire.
If the power cable or cord is damaged, it should be replaced by manufacturer or qualified person. The electric work
must be done by a certified person according to code and standard about electric installation, regulation for indoor
wiring and installation manual. In addition, the electric work must be in compliance with rated electric specification.
fVoltage drop, shortage of supply voltage, incorrect power supply work and use of uncertified cables may result in electric
shock or fire.
Arrange the cables between the AHU-KIT and outdoor unit so that the cover of electric part does not rise and then fix
the cover of the electric box to the product firmly.
fIf the cover is attached incompletely, a heat generation, electric shock or fire of the terminal may occur.
The Power supply to the kit should be through dedicated MCCB/ELB or ELCB.
fIf dedicated MCCB/ELB or ELCB is not provided, electric shock or fire may occur because of overcurrent or leakage current.
Install the supplied cables firmly. Fix them securely so that external force is not applied to the terminal.
fIf the connection or fixing is incomplete, heat generation, spark and fire may occur.
Make sure that the power for AHU-KIT is under maximum, and over minimum voltage.
fFailure to do so may result in product malfunction due to electrical component damage and functional degradation of a
part.
Use rated copper wire for the power cable.
Make sure electric wiring is correctly connected.
fFailure to do so may result in fire with overheating.
Make sure there is no leakage of refrigerant gas after finishing installation.
fWhen leakage of refrigerant gas contacts with fire, toxic gas may be generated.
3
Safety Information
FOR INSTALLATION CAUTION
4
Name of each part and product dimension
Name of each part and product dimension
ASS'Y Control(Control part)
ENGLISH
(Unit : mm)
168
182
238
275
350
385
Terminal block(20P)
(53)
254 mm
185 mm
Filter
EEV coil(7 m)
IN/OUT Pipe Diameter :
79 mm
0 12.7mm
5
Parts
Accessories (supplied)
Pipe inlet/outlet Inlet sensor holder Outlet sensor holder
Name Sensor fixing spring
sensor(7 m) (OD Ø6.8 mm) (OD Ø7.8 mm)
Quantity 1 1 1 2
Shape
Shape
6
Checking before using an AHU KIT
Structure diagram of an AHU-KIT
Outdoor unit
ENGLISH
Communication cable: F1,F2
EEV Control
Liquid valve
Communication cable:
F3,F4
* Room Temperature
Sensor(mA or PT1000)
Gas pipe
Wired remote controller
OUT sensor
* Room temperature sensor is not provided. It should be provided additionally on the field.
7
Installing an AHU KIT
Installing ASS'Y Control
1. Check the installation location of ASS'Y Control.
fYou can choose either AHU attachment type or AHU separation type depending on the installation environment.
2. Check the length of connection cable of ASS'Y Control.
fThe length of provided connection cable is 7 m.
3. Make sure the location has waterproof and fire prevention structure.
fMake sure that the ASS'Y Control is not exposed to sunlight by covering with a case which has waterproof and fire
prevention structure.
Main PBA
Terminal Block
8
fFor HP setting, refer to SEG20 of 05 series in installation option section. (Refer to p.26)
fConnect room temperature sensor and discharge temperature sensor(optional) as mA or PT1000Ω type.
- When using the mA type sensor, connect to the terminal block +/-(mA).
- When using the PT1000Ω sensor, connect to the terminal block A/B/C .
- Set the types of room temperature sensor and discharge temperature sensor in SEG24 of 05 series installation option.
The types of the sensors must be same.
ENGLISH
No. CONNECTOR FUNCTION NOTE
1 CN83/84/85 EEV EEV 1/2/3
2 CN86 EEV EEV 4
3 REM01 REMOCON RECEIVER OPTION INPUT
1/3 PIN : COMP CHECK OUT
4 CN82 EXTERNAL CHECK
6/8 PIN : ERROR CHECK OUT
1/2 PIN : EVA IN
5 CN43 SENSOR
3/4 PIN : EVA OUT
6 CN21 DOWNLOAD S/W UPGRADE
7 CN201 EEPROM PBA
8 CN311 2WIRE SUB PBA
9
Installing an AHU KIT
10
Working on power supply
Connecting power/communication cable
fTurn the power off before working on the power supply.
fMaximum cable length and the amount of voltage drop for AHU KIT power/communication cables should be within
10 %.
ENGLISH
fWhen installing the MCCB/ELB or ELCB, consider Power Rating of the AHU motor for correct capacity.
fConnect F3, F4 of AHU KIT terminal to Wired Remote Control.
fUse the appropriate tools for wiring and make sure the wiring is connected tightly within Tightening torque (kgf•cm)
the tightening torque to withstand the external pressure. Arrange the wires so that cover or
M4 12.0~14.7
other parts does not get loose. Otherwise, it may cause overheating, electric shock or fire.
fTo protect the product from external shock or water, put the power and communication cable into a power cable
protection box.
fConnect the power cable through MCCB/ELB or ELCB.
fMaintain more than 50 mm distance between the power cable and communication cable.
• The circuit diagram for wiring represents only an outline so the detailed information about actual installation
work is not described.
CAUTION
• In principle, AHU KIT power supply should be provided separately from an outdoor unit.
• Do not distribute the communication cable as communication error may occur.
• Do not distribute the power cable of terminal block for 2 AHU KITs from 1 AHU KIT.
• When peeling the sheath of power cable, use the appropriate tools to prevent damage inside the wire.
• Make sure that more than 20 mm of power and communication cable of AHU KIT is inside the electric parts.
• Communication cable should be installed separately from power cable or other communication cables.
11
Installing an AHU KIT
Specification of electronic wire
Power supply MCCB ELB Power cable Earth cable Communication cable
Max : 242V XA, 30 mmA 2 2
XA 2.5 mm 2.5 mm 0.75~1.5 mm2
Min : 198V 0.1 s
Defrost signal
12
Installation example 2) AHU KIT + contact signal for AHU fan ON
AHU MOTOR
POWER SOURE
ENGLISH
Contact signal for fan ON
Installation example 3) Setting a room temperature sensor for installing multiple AHU KITs
Room
temperature
sensor PT1000 Wired remote
controller
• For common AHU with multiple AHU KITS, sharing with 1 room temperature sensor is possible. The room
temperature sensor sharing uses the communication of wired remote controller, so Wired remote controller
CAUTION
should be installed. mA temperature sensor is the same as well. (Refer to SEG 24 of installation option 05 series
on page 26.)
• If one room temperature sensor is used for multiple AHU kits, MCM-D201N should only be used.
13
Installing an AHU KIT
Welding with nitrogen blowing
➀ Refrigerant pipe
➁ Location for welding
➂ Tape
➃ Hands valve
➄ Reducing valve
➅ Nitrogen gas
Insulator
Clamp
14
5. For checking EEV service, please attach a label sticker.
fAttach one label to upper middle part of ASS'Y EEV valve body and attach the same color of a lable sticker to valve wire
housing.
6. Connect the EEV termial block to exact places on PCB according to set HP.
fWhen the set HP of AHU KIT is set as 40 HP: Connect EEV-1, EEV-2, EEV-3 and EEV-4
fWhen the set HP of AHU KIT is set as 30 HP: Connect EEV-1, EEV-2, and EEV-3.
ENGLISH
fWhen the set HP of AHU KIT is set as 20 HP: Connect EEV-1 and EEV-2
❋ EEV connector connection should be fixed to the wire saddle as shown in the image.
• New AHU KIT (ACM-D201N) has a different way to set the number of the indoor unit installation from the
CAUTION previous AHU KIT (ACM-D201) and an outdoor unit.
• Be careful when setting the number of the indoor unit installation with an outdoor unit.
• When setting AHU KIT HP, refer to the SEG 20 of Installation option 05 series on page 26.
• Regardless of the AHU KIT HP setting, one indoor unit will be recognized.
15
Installing an AHU KIT
Installing IN/OUT sensor
1. Attach the EVA IN sensor after the distributor and on the lowest temperature pipe of a heat exchanger.
2. Install the EVA OUT sensor 200 mm after the header of AHU heat exchanger as shown in the picture.
3. Insulate the EVA IN and OUT sensor so that it is not affected by wind.
4. Install the ROOM temperature sensor on the RA(Return Air) path of AHU.
Cool mode
Distributor Heat mode
1 EVA IN sensor
Header 200
2 EVA OUT sensor
• In principle, the sensor holder of EVA IN/OUT sensor should be welded at the designated place and then the EVA
IN/OUT sensor should be fixed with a clip.
NOTE
• EVA IN/OUT sensor should be installed at the place where temperature of the heat exchanger air inlet or outlet
can be measured accurately.
16
Example of IN/OUT sensor installation 1
1. Chcek the sensor and sensor holder you will attach.
ENGLISH
OUT sensor(Red) ø7 ø 7.8
3. Insert the sensor and the clip into the sensor holder.
IN/OUT sensor
Insulator
17
Installing an AHU KIT
Example of IN/OUT sensor installation 2
1. Chcek the sensor and sensor holder you will attach.
Aluminum tape
Rubber tape
IN/OUT sensor
Cable tie
Insulator
18
Setting an address and installation option of AHU KIT
fSet the address of an AHU KIT and installation option with remote controller options. Set each option separately since
you cannot set the ADDRESS setting and indoor unit installation setting option at the same time. You need to set twice
when setting the address of an AHU KIT and installation option.
fThe reception part of a remote controller is built in the AHU KIT PBA.
ENGLISH
The procedure of option setting
Mode change
19
Setting an address and installation option of AHU KIT
Option setting Status
1. Setting SEG2, SEG3 option
Press Low Fan button( ) to enter SEG2 value.
Press High Fan button( ) to enter SEG3 value.
Each time you press the button, p p … p will be selected in rotation. SEG2 SEG3
20
Option setting Status
ENGLISH
Press Low Fan button( ) to enter SEG16 value.
Press High Fan button( ) to enter SEG17 value.
Each time you press the button, p p … p will be selected in rotation. SEG16 SEG17
→ → → → →
→ → → →
Remote
Controller
Display
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
No Main
0
Indication address
and Details Main Hundred's
0 A 0~9 0~9 Tens' digit 0~9 A unit digit
address digit
1
setting
mode
Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
Remote
Controller
Display
• When “A”~”F” is entered to SEG5~6, the main address of AHU KIT will not be changed.
CAUTION • If you set the SEG 3 as 0, the AHU KIT will maintain the existing MAIN ADDRESS even if you have entered the
option value of SEG5~6.
• If you set the SEG 9 as 0, the AHU KIT will maintain the existing RMC ADDRESS even if you have entered the
option value of SEG11~12.
22
Setting the installation option of an AHU KIT (suitable for the condition of each installation location)
1. Check whether power is supplied or not.
- When the AHU KIT is not plugged in, there should be additional power supply.
2. The reception part of a remote controller is built in the AHU KIT PBA.
3. Set the installation option of an AHU KIT according to installation conditions.
- The default setting of an AHU KIT installation option is “020010-100000-200000-300000”.
ENGLISH
4. Set the AHU KIT option with a remote controller.
Remote
Controller
Display
Indication Details Indication Details Indication Details Indication Details Indication Details
Use of
Minimizing fan
External room
operation when
0 Disuse temperature 0 Disuse
thermostat is off
sensor
0 Disuse Disuse
Indication and 1 Use Disuse
Details 0 2 2 Disuse Heating Use
3 Use Heating Use
4 Disuse Cooling Use 1 Use
5 Use Cooling Use
6 Disuse All Use
7 Use All Use
23
Setting an address and installation option of AHU KIT
Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
Explanation PAGE Use of drain pump Use of hot water heater Use of electronic heater EEV Step when heating stops Master / Slave
Remote
Controller
Display
Indication Details Indication Details
Indication and 0 Default value
Details 1 Noise decreasing
1
setting
24
(*1)
Minimizing fan operation when thermostat is off
- Fan operates for 20 seconds at an interval of 5 minutes in heating mode.
- Fan stops when thermostat is off in cooling mode.
- Make sure to connect the wired remote controller or the external room temperature sensor if you use the function of
external room temperature sensor or minimizing fan operation. (In order to implement the functions the option of
using temperature sensor inside the wired remote controller must be set. Refer to the installation manual of the wired
remote controller.
ENGLISH
■ 05 series installation option
SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
(When setting SEG3)
Use of Auto Change (When setting SEG3) (When setting SEG3)
Standard for mode
0 5 Over for HR only in Standard heating temp. Standard cooling
change Heating →
Auto mode Offset temp. Offset
Cooling
SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
(When setting SEG3) Compensation option
(When setting SEG3)
Standard for mode for Long pipe or height
1 Time required for - -
change Cooling → difference between
mode change
Heating indoor units
SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
Temperature control
2 - - - -
by using simple BMS
SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
Skip the prevention
3 HP setting Fan Feedback Defrost signal Sensor
of cold air
Remote
Controller
Display
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
Follow
0 product 0 0 0 0 0 1
options
1 0.5 1 0.5 1 1.5
Indication 2 1 2 1 2 2
and Details 0 5 3 1.5 3 1.5 3 2.5
Use Auto
1 Change Over 4 2 4 2 4 3
for HR only 5 2.5 5 2.5 5 3.5
6 3 6 3 6 4
7 3.5 7 3.5 7 4.5
25
Setting an address and installation option of AHU KIT
Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
(When setting SEG3) (When setting SEG3) Compensation option for Long
Explanation PAGE Standard for mode change Time required for mode pipe or height diffference between
Cooling → Heating mode change indoor units
Remote
Controller
Display
Explanation 2
Indication Details
0 Room
temperature
1 Discharge
temperature
Option SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
Explanation PAGE HP setting Fan Feedback Defrost signal Skip the prevention of cold air Sensor
Remote
Controller
Display
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
Default Sharing the room and discharge
0 0 Disuse 0 Disuse 0 Disuse 0 temperature value of a master
(10 HP) indoor unit
Master indoor unit
1 10 HP 1 Use 1 Use 1 Use 1 - Room temperature : PT1000 Ω
- Discharge temperature :
4~20 mA
Indication Master indoor unit
and Details
3) - Room temperature : 4~20 mA
2 20 HP 2
- Discharge temperature :
PT1000 Ω
3 30 HP Master indoor unit
- Room temperature : a wired
3 remote controller’s sensor
4 40 HP
- Discharge temperature :
4~20 mA
1) Height difference : The difference of the height between the corresponding indoor uint and the indoor unit installed at the lowest place.
For example, When the indoor unit is installed 40 m(131.23 ft) higher than the indoor unit installed at the lowest place, select the option "1".
2) Distance : The difference between the pipe length of the indoor unit istalled at the farthest place from an outdoor unit and the pipe length of the corresponding indoor unit from an outdoor
unit. For example, when the farthest pipe length is 100 m(328 ft) and the corresponding indoor unit is 40 m(131.23 ft) away from an outdoor unit, select the option "2". (100 m(328 ft) -
40 m(131.23 ft) = 60 m(196.85 ft))
3) Regardless of the AHU KIT HP setting, one indoor unit will be recognized. Therefore, be careful when setting the number of the indoor unit installation with an outdoor unit.
26
Additional information for SEG 3,4,5,6,8,9
When the SEG 3 is set as "1" and follow Auto Change Over for HR only operation, it will operate as follows.
Thermo Off
Thermo Off
Thermo On
Thermo On
Heating
Heating
Cooling
Cooling
ENGLISH
Standard temp. for Heating
Temp. → Cooling
c
Standard temp.
A : Set with SEG4(˚C)
for Cooling →
Heating B : Set with SEG5(˚C)
C : Set with SEG6(˚C)
D : Set with SEG8(˚C)
Cooling/Heating mode can be changed when Thermo Off status is maintained during the time with SEG9.
27
Changing a particular option
You can change each digit of set option.
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Tens' digit of an Unit digit of an
Option mode to
Explanation PAGE MODE option SEG to option SEG to Changed value
change
change change
Remote
Controller
Display
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
Indication
and Tens’ Unit
Option Changed
Details 0 D 0~F digit of 0~9 digit of 0~9 0~9
mode value
SEG SEG
• When changing a digit of an AHU KIT address setting option, set the SEG3 as ‘A’.
NOTE • When changing a digit of an AHU KIT installation option, set the SEG3 as ‘2’.
Ex) When setting the ‘buzzer control’ into disuse status.
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Tens' digit of Unit digit of an
Option mode
Explanation PAGE MODE an option SEG option SEG to Changed value
to change
to change change
Indication 0 D 2 1 7 1
28
Trouble shooting
Initial check-up
1. Check the connection status between an outdoor unit and the AHU-KIT.
fCheck that you have followed wiring method according to the circuit diagram or installation manual.
ENGLISH
fCheck that AHU-KIT PBA is installed in a place where there is no influence from outdoor humidity, dust and temperature.
Error on EEPROM
Outdoor unit display
Description Communication problem between EEPROM of AHU KIT and micom.
- EEPROM PBA OF AHU KIT ERROR(Physical problem of parts/circuit)
Reason
- Replace EEPROM PBA
• Wired remote controller will display the same error shown in the outdoor unit.
NOTE
29
Trouble shooting
Error on a sensor
Error on the detachment of AHU-KIT heat exchanger EVA IN sensor
1. Description
- In Cool mode
2. Checking method
- After checking the detachment status of AHU KIT heat exchanger EVA IN sensor, assemble the sensor.
Error on the detachment of AHU KIT heat exchanger EVA OUT sensor
1. Description
- In Cool mode
2. Checking method
- After checking the detachment status of AHU KIT heat exchanger EVA OUT sensor, assemble the sensor.
• Wired remote controller will display the same error shown in the outdoor unit.
NOTE
30
Error on AHU KIT temperature sensor OPEN/SHORT
1. Checking method
ENGLISH
Description When the temperature sensor part of AHU KIT is detected as OPEN/SHORT
Reason Incorrect installation of PT1000 temperature sensor or mA thermometer
PT1000
Resistance
Temperature
Voltage
Therminal voltage
Temperature
• Wired remote controller will display the same error shown in the outdoor unit.
NOTE
31
Trouble shooting
Error on AHU KIT temperature senor OPEN/SHORT
1. Checking method
Temperature(°C) Resistance(kΩ)
After detaching the temperature sensor connector
70 2.2
of AHU KIT EVA IN/OUT from the PBA, measure the
electrical resistance between both terminals. 60 3.0
50 4.2
40 5.8
Yes 30 8.3
20 12.1
10 18.0
0 27.3
-10 43.0
At this time, does the resistance value Yes
largely get out of the right table?
No
Since the temperature sensor of AHU KIT EVA IN/OUT
itself is defective, replace it.
• Wired remote controller will display the same error shown in the outdoor unit.
NOTE
32
Error on a fan
Outdoor unit display
When the feedback signal is maintained as OPEN status for 10 seconds after outputting the
Description
fan operation signal from ASS’Y Control ( For AHU KIT)
• Fan operation of AHU KIT is abnormal.
ENGLISH
Reason • The circuit to detect the fan feedback signal of AHU KIT is not formed or
misconnected.
1. Checking method
No
No
Do you need the fan feedback?
Yes
Yes
No
Is the fan operating? Check the fan control of AHU.
Yes
When the AHU KIT fan is in operation, No Form the control circuit so that the proper fan feedback
does the fan feedback signal provide signal is output depending on fan operation status.
the contact signal in SHORT status?
Yes
• Only the contact signal without power supply should be entered to detecting terminal of fan feedback signal. If
voltage or current is connected other than the contact signal without power supply, the ASS’Y Control may be
NOTE
damaged.
33
Trouble shooting
Error on EEV step control
Outdoor unit display N/A
In cool mode, EEV step is controlled to minimum 230 steps and maximum 1700 steps. In
Description
heat mode, the EEV step is controlled to minimum 1000 steps.
• The location of EVA IN/OUT sensor is not correct.
• EEV coil is reversed.
Reason
• All or part of EEV coil is detached.
• Refrigerant is overcharged.
1. Checking method
Yes
Yes
Yes
No
Is the amount of added refrigerant enough? Charge the appropriate amount of refrigerant.
Yes
34
Error on tracking
Communication error between AHU KIT and an outdoor unit during the tracking (During initial operation)
ENGLISH
Reason Refer to the diagram below.
1. Checking method
Compare and check the setting value for the number of AHU
KIT installation with outdoor unit PBA and the real number of ❈ Regardless of setting HP capacity, the number of AHU Kit
AHU KIT installation. installation is recognized as one indoor unit.
Yes After setting the switch for the number of AHU KIT
installation set up on the outdoor unit correctly, press
the reset key(k3) of outdoor unit PBA to restart the
Press the reset key(K3) of outdoor unit PBA and view the
tracking.
display part to check the number of AHU KIT which responds
to the tracking.
Yes
Is there a response from AHU KIT on the display
part during the tracking?
After 2 minutes, check whether the PBA address setting
is repeated by finding the AHU KIT that displays the
No communication error.
− When the AHU KIT address is repeated, communication
After removing the communication cable which is connected error may occur. In this case, the communication error
to AHU KIT from an outdoor unit, measure the 2 wires on the may occur with all the AHU KITs(more than 2) whose
outdoor unit with SCOPE. address setting is incorrectly set.
Yes
If there is no problem with the address, check the
communication cable and replace the AHU KIT PBA.
35
Trouble shooting
Error on communication between AHU KIT and an outdoor unit after the tracking (During operation)
1. Checking method
Press the reset key(K3) of outdoor unit PBA and check the
display part.
Yes
Is there a response from AHU KIT on the display
part during the tracking?
After 2 minutes, check whether the PBA address setting
is repeated by finding the AHU KIT that displays the
No communication error.
− When the AHU KIT address is repeated, communication
error may occur. In this case, the communication error may
After removing the communication cable which is connected occur with all the AHU KITs(more than 2) whose address
to AHU KIT from an outdoor unvit, measure the 2 wires on the setting is incorrectly set.
outdoor unit with SCOPE.
• Wired remote controller will display the same error shown in the outdoor unit.
NOTE
Good Bad
+0.7V
-0.7V
36
Installation check and test operation
Checking AHU KIT installation
1. Check that ASS’Y Control is correctly installed.
- You can choose either AHU attachment type or AHU separation type.
ENGLISH
- Check the length of connection cable of ASS'Y Control is correct.
- Check that the connection of ASS’Y Control connecting cable is correct.
- Make sure the location has waterproof and fire prevention structure with a specially designed case. ( For the separation
type, it is essential.)
- Make sure the ASS’Y Control is not exposed to sunlight or rain.
• ASS’Y Control should be installed with the CASE that has water proof and fire prevention function.
CAUTION
Test operation
1. Before supplying power, measure the grounding between the power terminal(1phase: L, N) and AHU KIT using the
DC 500 V insulation-resistance tester.
- Measured value should be more than 30 MΩ.
• Do not measure the communication terminal as the communication circuit may get damaged.
CAUTION • For the communication terminal, check the short circuit using a general circuit tester.
2. Before supplying power, check the voltage of the power(L, N), and turn the switch on.
N
220-240 V
L
<MCCB/ELB or ELCB>
3. After finishing and checking installation and the items below, check that the AHU KIT operates correctly.
- The firmness of AHU KIT installation environment and safety
- Thermal resistance of insulator for refrigerant pipe
- Leakage of refrigerant gas
- Drainage status
- Power connection status
- Connection status with a circuit breaker and grounding status
- Correct operation for each operation mode
37
MEMO
38
ENGLISH
39
MEMO