QUESTION 5: Designing single line diagram, control circuit for capacitor bank

at the transformer bus bar, with automatic and manual switching mode (with on /
off button on the outside of the cabinet or the board). Proposed smart
compensation and active or passive harmonic filtering methods for the above
project.
AC power system provides 2 types of energy:
+ P: active power (kW)
+ Q: reactive power (kVar)
According to statistics:
+ Induction 3-phase motor consumes 60  65% of the total reactive power of
the power system.
+ The transformer consumes about 20  25% of the total reactive power of the
power system.
+ Lines, reactance, and equipment consume about 10% of the total reactive
power of the power system.
Therefore, in order to avoid the loss of a large amount of reactive power, it is
necessary to equip Q generators (compensation capacitors) directly to the load. Should
be called reactive power compensation.
Advantages of using Q-capacitors compensation:
+ Reduce power loss for the power system
+ No excess compensation, ensuring the desired compensation coefficient
5.1. Design and calculate the reactive power of the compensation capacitor
We have an formula:
Qb=P tt ×(tan φ1−tan φ2 )
+ Qc : Compensation capacity
+ Ptt : Total active power of the calculated load (kW)
+ tan φ1: Before compensation
+ tan φ2: After compensation
Parameter of calculations for workshop:
+ Ptt = 730.8 kW
+ Qtt = 343.2 kVar
+ Stt = 807.4 kVA
Apply Power triangle and Power factor:

FIGURE 1: Formula of Power triangle and Power factor


Reference: https://emrecicek.net/en/blog-en/active-and-reactive-power/
Ptt 730.8
+cos φ1= = =0.905
S tt 807.4
According to EVN: cos φ>¿ 0.9 (EVN No.15/2014/TT-BCT)
=> Choose cos φ2=0.92
+ cos φ1=0.905 => sin φ 1=√ 1−(cos φ1 )2=0.425
2

+ cos φ2=0.92 => sin φ 2=√ 1−(cos φ2 )2=0.392


2

sin φ1 0.425
=> tan φ1= = =0.47
cos φ 1 0.905
sin φ 2 0.392
=> tan φ2= = =0.426
cos φ 2 0.92
Calculate:
Qc = Ptt × ( tan φ1−tan φ2 ) =730.2× ( 0.47−0.426 )=32.204 ≈ 32(kVar )
Choose compensation capacitor for compensation cabinet:
Mikro compensation capacitor
+ Code: MKC-445050KT
+ Size: 63 x 165 (mm)
+ Rated voltage: 440 V / 50Hz
+ Rated current: 39.4A
+ Phase: 3 phase
+ Nominal capacitance: 82.2 μF
+ Q0 = 5 kVar

FIGURE 2: Catalog of MKC-445050KT compensation capacitor


Reference: https://dien-congnghiep.com/upload/mikro/catalogue_tu_bu_mikro.pdf
Qc (kVA) 32
+ Number of compensation capacitors: n = = =6 , 4 ≈ 7
5(kVAR ) 5

+ Power compensation capacity: Qc =5 ×n=¿ 5 × 7 = 35 (kVar)


FIG
URE 3: Simulator graph download to machine part (24 hours)

8 121
08 10 12 13  16 16  18 18  23
10 3
P (kW) 50 120 125 80 125 120 50
Q (kVar) 32.3 77.51 80.74 51.67 80.74 77.51 32.3
Qb (kVar) 11 26.4 27.5 17.6 27.5 26.4 11
Number of
compensation 3 6 6 6 6 6 3
capacitor
Automatic 3 6 6 6 6 6 3

5.2. Choose APFC for compensation cabinet:


2 SK QR-X4 4 levels to controll compensation capacitor
+ Working limitation: +-15%
+ Voltage operation: 220VAC
+ Efficenicy: maximum 10VA
+ Frequency: 50Hz or 60Hz
+ Rated current: 5A
FIGURE 4: SK QR-X4 4 levels control compensation capacitorReference:
https://codienhaiau.com/product/bo-dieu-khien-tu-bu-sk-4-cap/
5.3. Choose MCCB, Contactor and protective current transformer for
compensation cabinet:
Calculate CB protect for one compensation capacitor
Qc 5
I đm= = =7.22 ( A )
√3 U đm √ 3× 0.4
I CB=I đm ×1.5 ×1.5=7.22× 1.5 ×1.5=16.245 ( A)
I cu ≥ S transformer × 1.5 ×25
¿> I cu ≥ 150 ×1.5 ×25=2812.5 ( A )=28.125 (k A )

Choose 6 MCB of Schneider EasyPact EZC100B3015 3P

FIGURE 5: Catalog of EZC100B3015 Schneider


Reference: https://www.se.com/vn/vi/product/EZC100B3015/circuit-breaker-
easypact-ezc100b-tmd-15a-3-poles-3d/
Calculate CB protect for compensation cabinet
I đm=6 × I đm of 1 capacitor=6 ×7.22=43.32 ( A )
I CB=I đm ×1.5 ×1.5=43.32 ×1.5=64.98( A)
I cu ≥ S transformer × 1.5 ×25
¿> I cu ≥ 150 ×1.5 ×25=5625 ( A )=5.625( k A )

Choose 2 MCCB of Schneider EasyPact EZC100F3015 3P

FIGURE 6: Catalog of EZC100F3100 Schneider


Reference: https://www.se.com/vn/vi/product/EZC100F3100/circuit-breakereasypact-
ezc100f-tmd-100a-3-poles-3d/
Calculate MCCB protect for transformer to bus bar
MBA
In =S MBA × 1.5=75 ×1.5=112.5(A )
I sc =I n ×25=112.5× 25=28.125 ( kA )

Choose 4 MCCB of Schneider EasyPact EZC250H3125 3P


FIGURE 7: Catalog of EZC250H3125 Schneider
Reference:https://www.se.com/vn/vi/product/EZC250H3125/circuit-breaker-easypact-
ezc250h-tmd-125a-3-poles-3d/?range=997-easypact-ezc&parent-subcategory-
id=23859433&filter=business-4-low-voltage-products-and-
systems&selectedNodeId=12144303882

Calculate Contactor for compensation capacitor working automatic


Qc 5
I đm= = =7.22 ( A )
√3 U đm √ 3× 0.4
I MC =I đm ×1.5=7.22× 1.5=10.83( A)
Choose 6 contactor of Contactor Schneider LC1D12M7 20A/220V 4P

FIGURE 8: Catalog of contactor 20A/220V


Reference:https://www.se.com/vn/en/product/LC1DT25M7/contactor-tesys-deca-4p4-
no-ac1-440v-25a-220vac-50-60hz-coil-screw-clamp-terminal/
Calculate bus bar
Qc ×1000 126.9 ×1000
I= = =183.16 ( A )
√3 U đm √ 3 ×400
I n=I × 1.5=183.16 × 1.5=274.74 ( A )

➔ Choose busbar 4 x 40 x 4000mm, cross-section 185mm2

Reference: https://www.busbar-vn.com/2019/10/lua-chon-busbar-day-dan.html
 Choose KP-CT 250/5A-35mm
+ Current transformer ratio: 250/5A
+ Inner diameter: 35mm
+ Capacity: 5VA
+ Accuracy level 0.5
+ Rated voltage: 600V

FIGURE 7: KP-CT 250/5A


Reference: https://codienhaiau.com/product/bien-dong-kp-ct-250-5a-35mm/
5.4. Calculate wiring for compensation capacitor board
-Wire connect from capacitor to MCB is 5kVar Voltage is 400V, so I choose 2.5mm2
Copper cross-section cores. (3*1C*2.5mm2)
-Wire connect with 3 capacitors to MCCB is 15kVar Voltage is 400V, so I choose
4mm2 Copper cross-section cores. (3*1C*4mm2)
FIGURE 9: Electrical Installation Guide 2018 cross section of
each compensation capacitor

5.5. Effective harmonic filtering solution for workshops


Because the workshop is mainly motor loads and is controlled and started by
DOL type, Start/Delta, Soft Starter and Variable Speed. Because many motors use
type starter Soft Starter and Variable Speed drives have significantly increased the
problem of internal harmonics factory supply system.
So I choose low voltage reactor with 7% harmonic filter for 10kVAR 440V 50Hz
capacitor: NSR- L7.442015
FIGURE 10 :Nuintek capacitor NSR- L7.442015
Reference: https://ple.vn/cuon-khang/cuon-khang-nuintek/nsr-l7-442010-detail.html

5.6 CAD drawing