ELP332_Lab Manual_
ELP332_Lab Manual_
LABORATORY MANUAL
List of Experiments
Cycle 1
1. Performance study and measurement of a DC shunt motor during braking operation with the
following methods (a) Dynamic braking and (b) Plugging (reverse current braking).Conduct
suitable tests to get the parameters of the DC machine.
Simulate the braking performance of the DC shunt motor in a digital computer.
2. Performance study of Voltage Source Inverter (VSI) fed induction motor drive with constant
V/f operation. Study current and Voltage waveforms at the AC output at different speed of the
motor along with their harmonic spectrum. Conduct suitable tests to get the parameters of the
Induction motor.
Simulate the VSI fed Induction motor drive in a digital computer.
3. Performance study and measurement of a three phase induction motor during braking with the
following methods (a) Dynamic braking (b) Plugging and (c) Capacitor braking. Conduct suitable
tests to get the parameters of the Induction motor.
Simulate the starting performance of the Induction motor in a digital computer.
4. Performance study and measurement of a DC motor with single phase and three phase diode
bridge rectifier inputs. Study current and Voltage waveforms in the AC as well as DC side at
different load conditions along with their harmonic spectrum. Conduct suitable tests to get the
parameters of the DC machine.
Simulate the DC motor drive with single phase and three phase diode bridge rectifier inputs in a
digital computer.
5. Study of PMBLDC motor including converter, control, sensors etc. Measure parameters of the
motor and inductance for different position of rotor.
Cycle 2
6. Performance study of slip ring induction motor with rotor resistance control. Study the variation
of torque and speed of the induction motor with various values of resistance and series combination
of resistance and capacitance. Conduct suitable tests to get the parameters of the Induction motor.
Simulate the rotor resistance controlled induction motor drive in a digital computer.
7. Performance study and measurement of a three-phase induction motor during starting with the
following methods (a) Direct on-line start (b) Autotransformer start (c) Star-Delta starter. Conduct
suitable tests to get the parameters of the Induction motor.
Simulate the starting performance of the Induction motor in a digital computer.
8. Performance study of 3 phase PMSM at variable frequency with constant torque and constant
power operation. Study of PMSM drive including converter, control, sensors etc. Measure
parameters of the PMSM like resistance, back emf etc. Conduct tests at different speeds.
Cycle 1
Experiment 1
Performance Study of a DC Shunt Motor during Braking Operation
Objective:
• Performance study and measurement of a DC shunt motor during braking operation
with the following methods (a) Dynamic braking and (b) Plugging (reverse current
braking).
• Conduct suitable tests to get the parameters of the DC machine.
• Simulate the braking performance of the DC shunt motor in a digital computer.
Apparatus Required:
Theory:
The braking of dc motor and its load can be done by using either (i) mechanical (friction)
braking or (ii) electric braking. In mechanical braking, the motor is stopped due to the friction
between the moving parts of the motor and the brake shoe i.e. kinetic energy of the motor is
dissipated as heat. Mechanical braking has several disadvantages including non-smooth stop and
greater stopping time.
In electric braking, the kinetic energy of the moving parts is converted into electrical energy
which is dissipated in a resistance as heat or alternatively, it is returned to the supply source. For
DC shunt as well as series motors, the following three methods of electric braking are normally
used:
(i) Rheostatic (or) Dynamic Braking: In this method, the armature of the running motor is
disconnected from the supply and is connected across a variable resistance Rb. However,
the field winding is left connected to the supply. The armature, while slowing down, rotates
in a strong magnetic field and, therefore, operates as a generator, sending a large current
through resistance Rb. This causes the energy possessed by the rotating armature to be
dissipated quickly as heat in the resistance. As a result, the motor is brought to standstill
quickly.
The braking torque can be controlled by varying the resistance Rb. If the value of
Rb is decreased as the motor speed decreases, the braking torque may be maintained at a
high value. At a low value of speed, the braking torque becomes small and the final
stopping of the motor is due to friction.
(ii) Plugging: In this method, connections to the armature are reversed so that motor tends to
rotate in the opposite direction, thus providing the necessary braking effect. When the
motor comes to rest, the supply must be cut off otherwise the motor will start rotating in
the opposite direction.
Note that armature connections are reversed while the connections of the field winding are
kept the same. As a result the current in the armature reverses. During the normal running
of the motor, the back e.m.f. Eb opposes the applied voltage V. However, when armature
connections are reversed, back e.m.f. Eb and V act in the same direction around the circuit.
Therefore, a voltage equal to V + Eb is impressed across the armature circuit. In order to
limit the current to safe value, a variable resistance Rb is inserted in the circuit at the time
of changing armature connections.
(iii) Regenerative Braking: In the regenerative braking, the motor is run as a generator. Here
back e.m.f Eb becomes greater than the supply voltage. As a result, the kinetic energy of
the motor is converted into electrical energy and returned to the supply.
Circuit Diagrams:
1. Dynamic Braking:
+ _ _ 1 2 + _
A + _A A
+
Rext
220 V + Z A +
ZZ Rb
DC SUPPLY v V
- -
Shunt AA
_ Regulator
1' 2'
Fig 4. Circuit diagram for dynamic braking
2. Plugging:
+ _ _ 1 2 _
A + _A + A
+
Rext
220 V + Z ZZ A +
DC SUPPLY v
Rb
V _
- - 220 V
Shunt AA AC Supply
+
_ Regulator 1-Φ
Rectifier Variac
1' 2'
Fig 5. Circuit diagram for plugging
3. Swinburne’s Test:
+ _ + _
A _A
+
Rext
+ A
220 V Z ZZ
DC SUPPLY v
-
Shunt AA
_ Regulator
A
A
220 V
AC Supply
V
Single phase AA
Variac
Procedure:
(b) Plugging:
S.No Braking Resistance (Ω) Braking Time (sec) Peak Armature Current (A)
2. Plugging:
Braking Resistance =
S.No Plugging Voltage (V) Braking Time (sec) Peak Armature Current (A)
3. Swinburne’s Test:
Armature Resistance Ra =
Field Resistance Rf =
Calculations:
1. From Swinburne’s Test find out the constant losses of the dc motor.
2. To find the inertia (J) of the rotor from retardation test, use the constant losses obtained
from the Swinburne’s test.
3. The armature inductance can be found as we know the armature impedance and resistance.
Simulation:
Simulation of the plugging can be done as follows:
1. Initial armature current, motor speed and field current are known.
dI
2. Ra I a + La a + Rb I a = Eb + V ------------- (1)
dt
Where Eb = K I f
d (I 2 R )
TL = J = − a b = − KI f I a --------------------- (2)
dt
Solve the above two simultaneous equations and obtain and Ia vs. Time.
Compare the braking time with the experimental value and comment on the discrepancies.
Quiz:
Precautions:
1. Make sure that there are no loose connections.
2. Always the external resistance in the armature circuit should be in maximum position at
the starting of the motor.
References:
1. “Fundamentals of Electric Drives” by G.K. Dubey, Narosa Publication House, 2nd Edition
2001.
2. “A First Course on Electric Drives” by S.K. Pillai, New Age International Limited
Publishers, 2nd Edition.
Experiment 2
APPARATUS REQUIRED:
S.No Apparatus Rating Quantity
1 3-phase Induction Machine
2 Variable voltage- variable frequency AC drive
3 Power Analyser
MOTIVATION:
In many industrial applications, the speed control is required to be varied either in steps or smoothly. In
certain special applications such as textile and mining industry a group of motors is required to be run at
different speeds with extremely good accuracy. In such applications d.c. shunt motor is being used because
of its characteristics and easy speed control. However, the use of squirrel cage induction motor is desirable
due to its well-known advantages over all other motors namely, rugged construction, low maintenance and
high efficiency. The problem however, is that the speed of induction motor cannot be controlled easily. It
requires additional expensive equipment. The knowledge of a system whereby speed is controlled by
varying the frequency is important for applied engineers. The system is best suited for applications such as
mining, chemical industries and textiles.
THEORY:
From Faraday’s law, the air gap component of the armature voltage in an AC machine is proportional to
the peak flux density in the machine and electrical frequency. Thus, neglecting the voltage drop across the
armature resistance and leakage reactance, the stator voltage can be written as,
f B peak
Va = e Vrated (1)
f rated Brated
where Va is the amplitude of the armature voltage; f e is the operating frequency;
B peak is the peak flux density; f rated , Brated , Vrated are the corresponding rated values.
The speed of induction motors can be precisely controlled by frequency control and can be made
independent of variation in supply voltage, field current and load. Therefore, keeping V =V , Eq.(1) can
a rated
be rewritten as
f
Bpeak = rated Brated (2)
fe
This demonstrates the constant voltage, variable frequency operation. In this mode, a machine operating in
saturation at rated voltage and frequency, any reduction in frequency will lead to further increase in flux
density. Higher flux density will result in increased core loss and higher machine currents. Therefore, for
frequencies less than or equal to rated frequency, the machine is operated at constant flux density, i.e.
B =B . This makes the Eq. (1) as
peak rated
f Va Vrated
Va = e Vrated = (3)
f rated fe f rated
This is constant voltage per hertz (V/f) operation. It is typically maintained from rated frequency to the low
frequency at which armature resistance drop becomes significant component of the applied voltage. For
frequencies higher than the rated with the voltage at its rated value, the air-gap flux density will drop below
its rated value {referring Eq (1)}. Thus, to maintain the rated flux density the voltage has to be increased,
which may result in insulation failure. Therefore, for frequencies above the rated frequency the terminal
voltage is kept at rated value. Assuming that machine cooling is not affected by rotor speed, the maximum
permissible terminal current will remain constant at its rated value Irated. Therefore, for the frequencies
below rated frequency the machine power will be proportional to feVratedIrated. Fig. 1 shows the typical
torque-speed characteristics with variable frequency drive.
T
Vs= Constant
-n nb n
-T
Power
Torque
Speed
CIRCUIT DIAGRAM:
fe Ve
E1 +
A1 s1 La
s3 s'1 s'3 s'5 A
E2
Three
Phase
VDC Lb B Induction
Three
Phase A2 Variac
Motor
E3 Lc
415V C
Supply -
IC
A3 s6 s'4 s'6 s'2
Rectifier Inverter
+ V
A
220V DC DC
supply Generator
Resistive
- Load
VOLTAGE
PROBE
R
0-10A MI
VOLTAGE
PROBE
0-500V MI
V
Y
CURRENT PROBE
B
POST-EXPERIMENTAL QUIZ
1. What will be the change in torque speed characteristics of the induction motor if there is change in
V/f ratio
2. Can higher starting torque be obtained at very low frequencies? Comment on the basis of the
observations.
3. Can constant torque speed characteristics be achieved at different frequencies?
4. What are the advantages and disadvantages of this method of speed control?
5. How are the equivalent circuit parameters affected by frequency?
6. What is the effect of variation of frequency on maximum torque, starting torque, slip at maximum
torque, if V/f is kept constant?
7. At constant V/f, is the developed power at all frequency same at rated input current?
REFERENCES:
[1] S K Bhattacharya “Electrical machines” New Delhi: Tata McGraw-Hill Pub. Co. Ltd.,©2009.
[2] Arthur Eugene Fitzgerald, Charles Kingsley, Stephen D. Umans “Electrical Machinery” Tata
McGraw-Hill publishing company Limited, New Delhi, India,2009
[3] Mohamed Abdus Salam “Fundamentals of electrical machines” Oxford Alpha Science 2005
[4] Say, M.G. "Alternating Current Machines" Fifth Edition. London: Pitman (1983).
EXPERIMENT NO. – 3
Performance study and measurement of a three phase induction motor during braking with the
following methods
• Dynamic braking
• Plugging and
• Capacitor braking.
Conduct suitable tests to get the parameters of the Induction motor.
Simulate the braking performance of the Induction motor in a digital computer.
APPARATUS REQUIRED:
2) TPDT switches.
3) Diode rectifier.
4) Capacitor bank.
5) Tachometer
6) Multi-meter
7) AC Ammeter.
8) 1-phase Wattmeter.
9) 3-Phase Induction
Motor.
Motor Rating:
THEORY:
In this experiment, braking of a 3‐phase induction motor will be implemented using the following
three methods:
For all these methods of braking, please refer to the book [1].
CAPACITIVE BRAKING:
• When three-phase balanced capacitors of suitable value are connected across the terminals
of a three-phase induction machine driven externally at constant speed, voltages are
induced in the machine windings, assuming residual flux exists in the magnetic circuit of
the machine (see Fig 3). Excitation is sustained by the terminal capacitors, while magnetic
saturation limits the induced voltages. This phenomenon, referred to as capacitor self-
excitation, can also be observed if only one capacitor of suitable value is connected across
two of the three terminals of the machine with the third kept open.
• Capacitor self-excitation may be exploited for purposes of dynamic braking of induction
motors following disconnection of the supply. As the motor is still running, high transient
currents can flow in the machine windings producing a braking torque. Kinetic energy in
the motor is dissipated as copper losses in the machine windings. Self-excitation process
under no-load condition is explained through Fig.3. The intersection point shifts
downwards as speed decreases.
• The value of the capacitance required to cause self-excitation is shown to decrease with
increased speed (Fig. 1). Further, at any particular speed the induced self-excited voltage
increases with the capacitance [3].
Fig. 1. Fig. 2
Fig. 3
DC DYNAMIC BRAKING:
In this form of braking, the AC supply to the stator winding is switched off and an appropriate DC
voltage is applied across any two out of the three stator terminals. This creates a stationary flux in
the air gap. The rotor is rotating at a given speed at this time and is very likely to have a residual
magnetism. Motion of the rotor in this field induces voltage in the rotor winding. Machine
therefore works as a generator. Generated energy is dissipated in the rotor circuit resistance, thus
giving dynamic braking. Fig. 5 shows the speed-torque characteristics of an IM, with the slip scale
reversed (Since equivalent Slip = 1 - s). Slip at which maximum braking torque occurs is at
SmT = 1 – smT and smT is the point of maximum torque for induction motor. For a given load torque
TL , operating point shift from A during normal operation to B when DC dynamic braking is
applied. With external resistance the initial braking torque can be increased and speed
corresponding to maximum braking torque can be increased.
Fig. 5
PLUGGING:
Plugging is one of the electrical braking methods applicable in induction motor. The principle of
traditional plug braking, is that changing the direction of revolving magnetic field to oppose the
direction of former magnetic field by changing the phase sequence of three-phase voltages supply
to the stator windings, and then the motor will be brought to a halt by opposing torque in a short
time. As the rotor always tries to catch up with the rotating field, it can be reversed rapidly simply
by interchanging any two of the supply leads. If the leads on the stator windings are reversed
suddenly, the direction of rotation of the stator field is reversed. The resulting slip is larger than
one. The motor will come to an abrupt stop. Very rapid reversal is possible using plugging but
large cage motors can only be plugged if the supply can withstand the very high currents involved,
which are even larger than when starting from rest. Moreover, there is a possibility of reversing
the rotation of motor if it fails to remove the braking as soon as the motor speed reached to zero
rpm. As shown in Fig. 6, operating point shifts from motoring mode shown by cross to a new point
in plugging region. With addition of external resistance initial braking toque can be increased.
Fig. 6
CIRCUIT DIAGRAMS:
Fig. 7
Fig. 8
Fig. 9
Fig. 10
Fig. 11
PROCEDURE:
RETARDATION TEST:
1. Make the connections as per the circuit diagram of no load test given by Fig. 7.
2. Run the machine under no load condition by applying rated voltage through VARIAC, and
note down the readings of no load voltage and no load speed of the machine.
3. Switch off the supply, note down the time for the speed of the machine to drop to zero.
CAPCITIVE BRAKING:
1. Make the as per the circuit diagram given in Fig. 9. Run the machine under no load
condition by applying voltage around 100V through VARIAC, and note down the readings
of no load voltage and no load speed of the machine.
2. At steady state, switch over the TPDT switch to connect the motor terminal across capacitor
bank.
3. Note the time required and capacitor value in the form of table.
4. Repeat the same procedure for other combinations of capacitor available i.e 10 µF,440 V.
DC DYNAMIC BRAKING:
1. Make the as per the circuit diagram given in Fig. 10.
2. Run the machine under no load condition by applying rated voltage through VARIAC, and
note down the readings of no load voltage and no load speed of the machine.
3. At steady state, switch over the TPDT switch to connect the motor terminal to DC supply
(about 30 V) across any two terminals.
4. Note the time required and DC Voltage value in the form of table.
5. Repeat the procedure above for different DC voltages i.e 10 V and 20 V also.
6. Removed the switch from DC Supply as soon as the motor comes to rest.
PLUGGING:
1. Make the as per the circuit diagram given in Fig. 11.
2. Run the machine under no load condition by applying rated voltage through VARIAC, and
note down the readings of no load voltage and no load speed of the machine.
3. At steady state, switch over the TPDT switch to connect the motor terminal such that any
two terminals are interchanged.
4. Note the time required and AC supply voltage value in the form of table.
5. Remove the switch from the plugging connection as soon as the motor comes to rest.
6. Repeat the procedure above with different values of reduced voltages i.e. 300V and 200V.
DC DYNAMIC BRAKING:
Sl.no DC Supply Speed(RPM) Braking Time to
Voltage(V) Voltage Current (A) stop(sec.)
(V)
PLUGGING:
Sl.no AC Voltage(V) Braking Speed(RPM) Time to stop(sec.)
Current
(A)
CALCULATION:
• No-load test and Block rotor test results is used to determine Induction motor equivalent
circuit parameter.
• Reduced voltage test results is used to calculate friction and windage loss in the Induction
Motor.
• Retardation test results is used to calculate the time required for the motor to come to
standstill from no-load speed.
• Moment of inertia (J) of Induction Motor is calculated using Reduced and Retardation test.
SIMULATION:
The simulation can be done by using the model of induction motor available in the SIMULINK.
The parameters needed to be entered in the SIMULINK model could be found out by carrying out
five test as mentioned above in the procedure section. For plugging operation, only the forcing
function has to be changed from ABC to BAC and rest of the things remain the same. In the
simulation, Speed vs Torque, Current vs Time, Speed vs Time are to be obtained.
QUIZ:
(1) Is regenerative braking feasible in an induction m/c?
(2) Analyse DC dynamic braking for the two cases:
(a) one phase open
(b) two stator phases started and DC supply applied between the other terminal and short‐circuited
terminal.
REFERENCES:
1. Dubey,G.K., Fundamentals of Electrical Drives, Narosa Publication,2nd edition,2001.
2. S. Sreenivasa Murthy, Gunnar J. Berg, Chandra S. Jha, and Ajay K. Tandon, A Novel
Method of Multistage Dynamic Braking of three phase induction motor, IEEE Transaction
on Industrial Applications, Vol. Ia-20, No. 2, March/April 1984.
Experiment 4
STUDY OF DC SHUNT MOTOR WITH SINGLE PHASE AND THREE
PHASE DIODE BRIDGE RECTIFIER
OBJECTIVE:
a) Performance study and measurement of a DC shunt motor with single phase and three phase
diode bridge rectifier inputs. Study current and voltage waveforms in the AC as well as DC
side at different load conditions along with their harmonic spectrum.
c) Simulate the DC shunt motor with single phase and three phase diode bridge rectifier inputs in
a digital computer.
APPARATUS REQUIRED:
Variac
Power Analyser
Multimeter
Tachometer
Ammeter
Rectifier board
THEORY:
PROCEDURE:
Retardation Test:
1. Make the connections as per the circuit diagram of no load test fig1.
2. Run the machine under no load condition by applying rated voltage through VARIAC, and
note down the readings of no load speed of the machine.
3. Switch off the supply, note down the time for the speed of the machine to drop to zero.
EXPERIMENTAL OBSERVATIONS:
Armature resistance:………ohms
SWINBURNE’S TEST:
PRECAUTIONS:
1. Care must be taken while loading the machine, i.e., current should not exceed the rated
value of either of the machines.
2. Machine should be given voltage through a VARIAC slowly to avoid high starting current.
EXPERIMENTAL QUIZ:
REFERENCES:
PRINCIPLE OF OPERATION:
Fig.2. Hall sensor output compared with back EMF for three-phase BLDC motor. Switching of Hall sensor
output coincides with the respective coil’s back EMF crossing the zero point in a sensorless motor (3)
Fig.2. shows an example of Hall sensor signals with respect to back EMF and the phase current.
Fig.3. shows the switching sequence that should be followed with respect to the Hall sensors. Every 60
electrical degrees of rotation, one of the Hall sensors changes the state. Given this, it takes six steps to
complete an electrical cycle. In synchronism, with every 60 electrical degrees, the phase current
switching should be updated, thus following the six-step commutation. However, one electrical cycle
may not correspond to a complete mechanical revolution of the rotor. The number of electrical cycles to
be repeated to complete a mechanical rotation is determined by the rotor pole pairs. For each rotor pole
pairs, one electrical cycle is completed. So, the number of electrical cycles/rotations equals the rotor pole
pairs. Each commutation sequence has one of the windings energized to positive power (current enters
into the winding), the second winding is negative (current exits the winding) and the third is in a non-
energized condition. Torque is produced because of the interaction between the magnetic field generated
by the stator coils and the permanent magnets. Ideally, the peak torque occurs when these two fields are
at 90° to each other and falls off as the fields move together. In order to keep the motor running, the
magnetic field produced by the windings should shift position, as the rotor moves to catch up with the
stator field.
The inverter is usually responsible for the electronic commutation and current regulation. For the
six-step current control, if the motor windings are Y-connected without the neutral connection, only two
of the three phase currents flow through the inverter in series. This results in the amplitude of the DC
link current always being equal to that of the phase currents. The PWM current controllers are typically
used to regulate the actual machine currents in order to match the rectangular current reference
waveforms.
0 0 1 0 -1 +1
1 0 1 +1 -1 0
1 0 0 +1 0 -1
1 1 0 0 +1 -1
0 1 0 -1 +1 0
0 1 1 -1 0 +1
CIRCUIT DIAGRAMS:
1-ph DC
Controlled V PMBLDC
Motor
AC Supply DSO
Diode
Rectifier
220 V
1-ph
Controlled
AC Supply V PMBLDC
Diode
Rectifier
A
1-ph
Controlled
PMBLDC
AC Supply
PROCEDURE:
b) RESISTANCE MEASUREMENT
1. The circuit is to be connected as shown in the Fig. 5.
2. A small DC voltage is to be applied.
3. Readings of voltage and current are to be recorded to calculate resistance for all three
phases of BLDC.
c) INDUCTANCE MEASUREMENT
1. The circuit is to be connected as per the circuit diagram in Fig. 6.
2. AC input voltage is to be applied.
3. Readings of voltage and current are to be recorded to calculate impedence for all three
phases of BLDC.
4. Inductance is calculated using Formula 2) in Appendix A.
Three hall sensor outputs should be connected to the oscilloscope. Make a table and check the
authenticity of hall sensor outputs and the working of BLDC Motor. Hall sensor is a very sensitive
device. Please do this experiment under supervision.
REFERENCES:
Formula Used:
1) Back Emf Constant, Ke
Volts[v]
Ke =
speed[rad / sec]
With a BLDC motor, line-to-line voltage is measured. So to convert to the phase voltage value,
the line-to-line voltage is divided by √3 =1.73.
Ke(line − to − line)
Ke( phase) =
1.73
2) Inductance, L
Z 2 − R2
L=
2 * * f
Cycle 2
EXPERIMENT 6
STUDY OF SLIP RING INDUCTION MOTOR WITH ROTOR
RESISTANCE CONTROL
OBJECTIVE:
a) Performance study of slip ring induction motor with rotor resistance control. Study the variation of
torque and speed of the induction motor with various values of resistance.
b) Conduct suitable tests to get the parameters of the Induction motor.
c) Simulate the rotor resistance controlled induction motor drive in a digital computer.
APPARATUS REQUIRED:
Variac
Multimeter
Wattmeter
Ammeter
Tachometer
THEORY:
Starting performance and speed of Slip ring induction motor can be controlled by adding external
resistance to its rotor terminal through slip rings.
Typical applications are in cranes and hoist where motor is started at heavy load.
In this method of speed control of three phase induction motor external resistance are added on rotor side.
The equation of torque for three phase induction motor is
2
sE 2 R2
T
R2 + (sX 2 ) 2
2
The three phase induction motor operates in low slip region .In low slip region term (sX2) 2 become very
very small as compared to R2. So, it can be neglected and also E2 is constant. So the equation of torque
after simplification becomes,
2
sE 2
T
f R2
Now if we increase rotor resistance R2 , torque decreases but to supply the same load torque must remain
constant. So, we increase slip, which will further results in decrease in rotor speed. Thus by adding
additional resistance in rotor circuit we can decrease the speed of three phase induction motor. The main
advantage of this method is that with addition of external resistance starting torque increases and power
factor improves. But this method of speed control of three phase induction motor also suffers from some
disadvantages:
1. The speed above the normal value is not possible.
2. Large speed change requires large value of resistance and if such large value of resistance is added
in the circuit it will cause large copper loss and hence reduction in efficiency.
3. This method cannot be used for squirrel cage induction motor.
TEST:
Following test are performed on the given motor:
1. No load test
2. Blocked rotor test
3. Retardation test
4. Rotor resistance speed control test
CIRCUIT DIAGRAMS:
PROCEDURE:
Retardation Test:
4. Make the connections as per the circuit diagram of no load test fig1.
5. Run the machine under no load condition by applying rated voltage through VARIAC, and note
down the readings of no load speed of the machine.
6. Switch off the supply, note down the time for the speed of the machine to drop to zero.
RETARDATION TEST:
PRECAUTIONS:
3. Care must be taken while loading the machine, i.e., current should not exceed the rated value of
either of the machines.
4. Machine should be given voltage through a VARIAC slowly to avoid high starting current.
EXPERIMENTAL QUIZ:
REFERENCES:
2. Fundamentals of Electric Drives by Gopal K. Dubey, Narosa publication, 2nd edition, 2001.
Experiment 7
STUDY OF 3-PHASE INDUCTION MOTOR STARTING TRANSIENTS
OBJECTIVE:
d) Study of 3-phase Induction Motor Starting Transients with the following Starting methods and
record current transients and compare the following:
i. DOL starting
ii. Y - starting
iii. Autotransformer starting
e) Measure the parameters of the induction machine by conducting no-load and blocked rotor
tests at rated voltage and at rated current.
f) Simulate Squirrel Cage Induction Motor in software with the above starting methods.
APPARATUS REQUIRED:
Variac
Multimeter
Wattmeter
Ammeter
TPDT switch
Tachometer
Star Delta Starter
THEORY:
2. Star-Delta starters
This is applicable for a delta connected motor. To reduce the starting current of the motor,
it is however, configured in a star connection during starting. The voltage applied to the individual
motor windings is therefore reduced by a factor of 1/√3 (= 0.58) while the starting line current is
reduced to one third of the direct on line starting current. During running condition, the motor is
switched over to a delta connection thereby applying full voltage across the motor.
Due to the reduced starting torque, the star-delta-connection is suitable for drives with a high
inertia mass with a load torque which is low or only increases with increased speed. It is preferably
used for applications where the drive is subjected to a lower load torque at starting i.e. fans,
centrifuges, pumps, ventilators, etc.
3. Autotransformer-starting
An autotransformer starter enables the start of squirrel-cage motors using a reduced starting
current, since the voltage is reduced during start. Contrary to a star-delta starter, only three motor
connections are required.
TEST:
PROCEDURE:
No Load Test:
8. Make the connections as per the circuit diagram in fig1.
9. Apply rated voltage to the induction motor through the three-phase VARIAC.
10. Note down the readings of power, input voltage, input current, speed.
Blocked Rotor Test:
Retardation Test:
7. Make the connections as per the circuit diagram of no load test fig1.
8. Run the machine under no load condition by applying rated voltage through VARIAC, and
note down the readings of no load speed of the machine.
9. Switch off the supply, note down the time for the speed of the machine to drop to zero.
STARTING METHODS:
DOL STARTING:
1. Connect the Induction motor as per the circuit diagram in fig3
2. Make auto transformer voltage to machine rated value.
3. Note down the values of starting current in ammeter.
STAR-DELTA STARTING:
1. Connect the Induction motor as per the circuit diagram in fig4
2. Connect the star delta starter kit in between supply and motor.
3. Make auto transformer voltage to machine rated value and press the green button in the
kit.
4. Note down the values of starting current in ammeter.
EXPERIMENTAL OBSERVATIONS:
NO LOAD TEST:
RETARDATION TEST:
STARTING METHODS:
Turns ratio input Line starting Line current DOL / starting Line current Υ-Δ
voltage (V) auto transformer (A) (A)
40
57.7
60
70
80
90
100
PRECAUTIONS:
5. Care must be taken while loading the machine, i.e., current should not exceed the rated
value of either of the machines.
6. Machine should be given voltage through a VARIAC slowly to avoid high starting current.
EXPERIMENTAL QUIZ:
REFERENCES:
APPARATUS REQUIRED:
Motor Rating:
PM MACHINE
A
A
V
AA (0-300) V 1-ph AC Supply
F FF DIODE RECTIFIER
FLUKE
A
+
-
220 V DC
Fig. 1. Circuit diagram for PMSM drive coupled with DC motor
b) RESISTANCE MEASUREMENT
1. The circuit is to be connected as shown in the Fig. 3.
2. A small DC voltage is to be applied.
3. Readings of voltage and current are to be recorded to calculate resistance for all three phases of
PMSM.
c) INDUCTANCE PROFILE
1. The circuit is to be connected as per the circuit diagram in Fig. 4.
2. AC input voltage is to be applied.
3. Rotor of PMSM is rotated manually and for different angles of rotation ranging from 0 to 360
degree, readings of voltage and current are to be recorded to calculate impedence at each position.
4. Inductance is calculated using Formula 2) in Appendix A.
5. Inductance profile (Inductance vs Angle of rotation) is drawn.
REFERENCES:
1. R.Krishnan, Permanent magnet and brushless DC motors, Prentice Hall Publications.
2. T.J.E. Miller, Brushless Permanent Magnet and Reluctance Motor Drives, Oxford Science
Publications.
APPENDIX A
Formulae Used:
With a BLDC motor, line-to-line voltage is measured. So to convert to the phase voltage value, the line-
to-line voltage is divided by √3 =1.73.
Ke(line − to − line)
Ke( phase) =
1.73
2) Inductance, L
Z 2 − R2
L=
2 * * f