Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

technical-leaflet-from-50-125kva-24-10-19

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

KIRLOSKAR ELECTRIC COMPANY LTD.

TECHNICAL PARTICULARS OF KIRLOSKAR ELECTRIC BLISS DG SETS - 50kVA-125kVA


Model KEC-T50- II KEC-T63-II KEC-T75 -II KEC-T82.5-II KEC-T100-II KEC-T125-II
Rating (kVA) 50 63 75 82.5 100 125
Rated kW 40 50 60 66 80 100
DG SET
Rated Current (Amps) 69.56 87.65 104.34 114.77 139.12 173.90
Length x Width x Height (mm) 2800X1100X1660 2800X1100X1660 3350x1200x1660 3350x1200x1660 3350x1200x1660 3600x1200x1715
Total Dry Weight (Kgs) 1500 1500 1800 1800 1800 2000
Engine Make TATA TATA TATA TATA TATA TATA
Model 497 TC75 497TC74 697-TC51 697-TC51 697-TC52 697-TC10
BHP 75.7 89.8 109.3 109.3 125.4 154.2
No. of Cylinders 4 4 6 6 6 6
RPM 1500 1500 1500 1500 1500 1500
Bore (mm) 97 97 97 97 97 97
Stroke (mm) 128 128 128 128 128 128
Displacement (ltrs) 3.8 3.8 5.678 5.678 5.678 5.678
Compression ratio 17.5:1 17.5:1 17.5±1:1 17.5±1:1 17.5±1:1 17.5±1:1
SFC (ltrs/hr) 12.4 15.3 15.3 20 23.9 29
Governor Mechanical Mechanical Electronic Electronic Electronic Mechanical
ENGINE Class of Governing A A G3 G3 G3 A
Aspiration TCIC TCIC TCIC TCIC TCIC TCIC
Air Filter Dry Type Dry Type Dry type Dry type Dry type Dry type
Fuel HSD-ASTM D2 HSD-ASTM D2 HSD HSD HSD HSD
Type of oil 10W40 C14+ 10W40 C14+ 10W40 C14+ 10W40 C14+ 10W40 C14+ 10W40 C14+
Oil sump capacity (ltrs) 9 9 14 14 14 14
Lube Oil consumption (gms/BHP-hr) < 0.3% of FC < 0.3% of FC < 0.09% of FC < 0.09% of FC < 0.09% of FC < 0.09% of FC
Cooling Liquid Cooled Liquid Cooled Liquid Cooled Liquid Cooled Liquid Cooled Liquid Cooled
Bare Radiator Coolant capacity (ltrs) 9 9 8.5 8.5 8.5 8.5
Coolant Capacity with engine Jacket (ltrs) 3 3 26 26 26 26
Engine Dry Weight (Kgs) 390 390 500 500 500 500
Electric Starting System 12V 12 V 12V 12V 12 V 12 V
Make KEC KEC KEC KEC KEC KEC
Model 4AB200S1 4AB200M1 4AB225S1 4AB225S1 4AB225S1 4AB225M1
Type Brushless Brushless Brushless Brushless Brushless Brushless
Rating (kVA) 50 63 75 82.5 100 125
Voltage (V) 415 415 415 415 415 415
No. of Phases 3 3 3 3 3 3
ALTERNATOR
Power Factor 0.8 0.8 0.8 0.8 0.8 0.8
Speed (rpm) / Frequency (Hz) 1500 / 50 1500 / 50 1500 / 50 1500 / 50 1500 / 50 1500 / 50
Voltage Regulation +/- 1% +/- 1% +/- 1% +/- 1% +/- 1% +/- 1%
Enclosure SPDP SPDP SPDP SPDP SPDP SPDP
Insulation class H H H H H H
Weight of ACG (Kgs) 222 282 286 286 337 387
Type ASAS \ AMF with microprocessor based BLISS EAR Monitor / Inbuilt
DG parameter monitoring display On BLISS EAR monitor - Volts line to line & line to neutral , Amps, Hz, Hour, KW, KWH, kVA, PF.
Engine parameter monitoring display On BLISS EAR monitor- Oil pressure,coolant temp.fuel level, battery voltage & charging status, engine speed .
CONTROL PANEL Functions Auto Start/Stop, Emergency Stop, Cooling time, LCD Display, acknowledgment & Fault Reset.
Protection Short Circuit, Over load MCCB, MCB's for control circuit.

Safeties Low Lube Oil Pressure, High Coolant Temperature, over load, under & over voltage, under & over frequency Auto Shut Down, Visual & Audio Alarm against Fault.

Make Exide Genplus /Reputed Exide Genplus Exide Genplus /Reputed Exide Genplus /Reputed Exide Genplus /Reputed Exide Genplus /Reputed
Type /Reputed MAINTENANCE FREE
Rating (AH) 90 90 90 90 90 90
BATTERY
Quantity (Nos.) 1 1 1 1 1 1
Charging Facility Charging Alternator
Battery metering Ammeter, Voltmeter built in BLISS EAR Monitor
Silencer type Residential
EXHAUST SYSTEM Location Hot Air Chamber
Exhaust pipe size in mm 90 90 115 115 115 115
Type Drag type in base frame
FUEL TANK
Capacity (Liters) 100 100 170 170 170 170
KEC/PGG/TD2-2/50-125/R1-24.10.2019

Type BOLTED
Sheet metal CRCA
CANOPY Draft Forced
Insulation Fire retardent FOAM
Noise level at 1 m 75 dB @ 1 Meter In line with CPCB norms
Base frame Pressed HR Channel
AVMs Qty (Nos.) 4 4 4 4 4 4
OTHER ITEMS
Emergency stop YES
Internal Lights YES
Engine Power Declared is at NTP.
In view of the continuous product development the format furnished is subject to revision and since published data is widely circulated, responsibility of seeking update rests with the user.