CATERPILLAR - Diesel Generator Chart

Load Fuel Usage-GPH Tank Dimensions (Inches) Dimensions with WP Enclosure


Cap.
Gals Wt. Pad Wt. Pad
KW 50% 75% 100% L W H L W H
Lbs Sf Lbs Sf

40 1.90 2.50 3.20 146 76 44 46 1,970 33 108 44 76 3,000 46

50 1.30 2.10 2.90 146 76 44 46 2,220 33 108 44 76 3,320 46

60 3.20 4.20 4.90 146 76 44 46 2,250 33 108 44 76 3,430 46

80 2.30 3.50 4.80 209 93 44 51 2,500 40 136 44 89 4,200 56

100 4.30 5.80 7.20 209 93 44 51 2,670 40 136 44 89 4,300 56

125 5.30 7.20 9.10 402 120 44 58 3,310 50 159 44 95 5,000 66

150 6.10 8.30 10.40 402 120 44 58 3,650 50 159 44 95 5,650 66

175 7.30 10.00 12.60 402 120 44 58 3,750 50 159 44 95 5,750 66

200 9.20 12.30 15.40 402 120 44 58 4,100 50 159 44 95 5,900 66

250 11.60 15.50 19.40 654 113 64 81 4,643 65 160 81 96 9,350 90

300 13.60 17.60 22.70 654 113 64 81 4,806 65 160 81 96 9,510 90

350 17.50 23.10 28.60 1,041 132 59 84 7,400 75 226 81 140 13,300 153

400 19.00 25.80 31.90 1,041 132 59 84 7,500 75 226 81 140 13,400 153

450 20.90 28.10 34.90 1,041 132 59 84 7,800 75 226 81 140 13,800 153

500 23.30 28.0 36.60 1,041 132 59 84 8,100 75 226 81 140 14,100 153

600 24.20 34.30 42.70 1,041 132 62 82 8,600 75 226 81 140 14,600 153

750 30.70 42.90 53.60 1,380 167 72 87 15,000 90 230 98 144 22,000 184

800 32.30 45.40 57.30 1,380 167 72 87 16,000 90 230 98 144 22,500 184

1000 38.20 56.40 71.90 1,728 167 79 87 17,000 112 240 98 144 24,400 272

1500 58.10 82.1 104.8 2,530 232 100 108 31,131 189 336 120 154 58,000 318

2000 77.70 107.80 139.90 3,312 253 100 115 38,155 205 360 144 154 65,000 402

NOTE: This chart is solely for estimating purposes.

1. The purpose of the generator chart is for estimating fuel consumption for testing, concrete equipment pads, and rigging requirements.
2. Pad size is six inches larger on all sides than the dimensions of the generator. Most equipment pads are approximately 12 inches thick.
3. Tank sizes are from manufacturer’s standard sizes or are sized for a min 24 hour run time. Job specifications may require larger tank
size for longer run times. Review specifications.
4. Dimensions and weights of outdoor enclosures are standard. Acoustical enclosures with some manufacturers are larger and weigh more
than a standard enclosure.
5. Fuel consumption is based on prime usage.

© Don Kiper – 2017, All rights reserved