g100-variable-speed-drive-manual
g100-variable-speed-drive-manual
g100-variable-speed-drive-manual
Contents
1 LS G100 Variable Speed Drive
2 Product Information
3 Product Usage Instructions
4 Configurations without VTS controls
5 PART LIST
6 CONFIGURATIONS WITHOUT VTS
CONTROLS
7 AHU WITH VTS CONTROLS TYPE uPC3
8 Documents / Resources
The LS G100 is a frequency converter that is used in conjunction with an Air Handling Unit (AHU). This manual
focuses on the control and communication circuits of the LS G100. The installation of the frequency converter and
mains and motor cables should be done according to the LS G100 Manual. The manual provides a list of
parameters and their corresponding values for configuring the LS G100. These parameters include ramp-up time,
ramp-down time, maximum frequency, U/f ratio, load type, overload protection, number of motor poles, rated slip,
rated current, idle run current, and P5 input function. There are different configurations provided in the manual,
including local control using the integrated control panel and remote control with three speeds. For each
configuration, additional parameters are specified to set the start/stop source, frequency source, and constant
speeds. The manual also includes information on exhaust units with VTS control systems and AHUs with VTS
control type uPC3. Parameters for these configurations are provided to set the start/stop source, frequency
source, address, communication protocol, communication speed, and communication parameters.
Use the P1/P3/P4/P5 inputs to set the desired drive function (1=on, 0=off). The corresponding input values are:
0000 = STOP, 1100 = START, 1ST SPEED, 1110 = START, 2ND SPEED, 1111 = START, 3RD SPEED.
Use the P1/P3/P4/P5 inputs to set the desired drive function (1=on, 0=off). The corresponding input values are:
0000 = STOP, 1100 = START, 1ST SPEED, 1110 = START, 2ND SPEED, 1111 = START, 3RD SPEED.
To allow control of the G100 frequency drivers, set the VFD type to G100 in uPC3 settings (HMI Advanced mask
I03).
Address CM-01 2
Use Modbus RS-485 as the communication protocol with a speed of 9600 bps and 8N1 parameters. To restore
G100 to default settings, set dr-93 = 1 and switch off the power supply. v1.01 (08.2023)
PART LIST
Local control using the integrated control panel Set additional parameters:
Use the RUN and STOP/RST buttons to control the drive Use buttons / potentiometer to set frequency
0000 = STOP
0000 = STOP
NOTE! To allow control of the G100 frequency drivers, set VFD type to G100 in uPC3 settings (HMI Advanced
mask I03).
Set additional parameters:
2 Supply 1
3 Exhaust 1
5 Supply 2/ redundant
7 Supply 3
9 Supply 4
8 Exhaust 3
10 Exhaust 4
NOTE! To restore G100 to default settings set dr-93 = 1 and switch off the power supply.
Documents / Resources
LS G100 Variable Speed Drive [pdf] User Manual
G100 Variable Speed Drive, G100, Variable Speed Drive, Speed Drive
Manuals+,