d60
d60
d60
Digital Energy
E83849
GE Digital Energy
LISTED
650 Markland Street
IND.CONT. EQ.
Markham, Ontario 52TL
GE Multilin's Quality Management
Canada L6C 0M1 System is registered to ISO
9001:2008
Tel: +1 905 927 7070 Fax: +1 905 927 5098 QMI # 005094
UL # A3775
Internet: http://www.GEDigitalEnergy.com
*1601-0089-Z2*
Copyright © 2013 GE Multilin Inc. All rights reserved.
D60 Line Distance Protection System UR Series Instruction Manual revision 7.1x.
FlexLogic, FlexElement, FlexCurve, FlexAnalog, FlexInteger, FlexState, EnerVista,
CyberSentry, HardFiber, Digital Energy, Multilin, and GE Multilin are trademarks
or registered trademarks of GE Multilin Inc.
The contents of this manual are the property of GE Multilin Inc. This
documentation is furnished on license and may not be reproduced in whole or
in part without the permission of GE Multilin. The content of this manual is for
informational use only and is subject to change without notice.
Part number: 1601-0089-Z2 (September 2013)
TABLE OF CONTENTS
INDEX
Before attempting to install or use the device, review all safety indicators in this document to help prevent injury, equipment
damage, or downtime.
The following safety and equipment symbols are used in this document.
Indicates a hazardous situation which, if not avoided, will result in death or serious injury.
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a hazardous situation which, if not avoided, could result in minor or moderate
injury.
Indicates practices not related to personal injury.
1 1. Open the relay packaging and inspect the unit for physical damage.
2. View the rear nameplate and verify that the correct model has been ordered and delivered.
GE DIGITAL ENERGY CONTACT INFORMATION AND CALL CENTER FOR PRODUCT SUPPORT:
GE Digital Energy
650 Markland Street
Markham, Ontario
Canada L6C 0M1
TELEPHONE: Worldwide +1 905 927 7070
Europe/Middle East/Africa +34 94 485 88 54
North America toll-free 1 800 547 8629
FAX: +1 905 927 5098
E-MAIL: Worldwide multilin.tech@ge.com
Europe multilin.tech.euro@ge.com
HOME PAGE: http://www.gedigitalenergy.com/multilin
For updates to the instruction manual, firmware, and software, visit the GE Digital Energy website.
The GE Universal Relay (UR) series is a new generation of digital, modular, and multifunction equipment that is easily
1
incorporated into automation systems, at both the station and enterprise levels.
a) UR BASIC DESIGN
The UR is a digital-based device containing a central processing unit (CPU) that handles multiple types of input and output
signals. The UR device can communicate over a local area network (LAN) with an operator interface, a programming
device, or another UR device.
b) UR SIGNAL TYPES
The contact inputs and outputs are digital signals associated with connections to hard-wired contacts. Both ‘wet’ and ‘dry’
contacts are supported.
The virtual inputs and outputs are digital signals associated with UR-series internal logic signals. Virtual inputs include
signals generated by the local user interface. The virtual outputs are outputs of FlexLogic™ equations used to customize
the device. Virtual outputs can also serve as virtual inputs to FlexLogic equations.
The analog inputs and outputs are signals that are associated with transducers, such as Resistance Temperature Detec-
tors (RTDs).
The CT and VT inputs refer to analog current transformer and voltage transformer signals used to monitor AC power lines.
The UR-series relays support 1 A and 5 A CTs.
The remote inputs and outputs provide a means of sharing digital point state information between remote UR-series
devices. The remote outputs interface to the remote inputs of other UR-series devices. Remote outputs are FlexLogic oper-
ands inserted into IEC 61850 GSSE and GOOSE messages.
The direct inputs and outputs provide a means of sharing digital point states between a number of UR-series IEDs over
1 dedicated fiber (single or multimode), RS422, or G.703 interface. No switching equipment is required as the IEDs are con-
nected directly in a ring or redundant (dual) ring configuration. This feature is optimized for speed and intended for pilot-
aided schemes, distributed logic applications, or the extension of the input/output capabilities of a single relay chassis.
c) UR SCAN OPERATION
The UR-series devices operate in a cyclic scan fashion. The device reads the inputs into an input status table, solves the
logic program (FlexLogic equation), and then sets each output to the appropriate state in an output status table. Any result-
ing task execution is priority interrupt-driven.
Firmware is the software embedded in the relay and is designed in functional modules that can be installed in any relay as
1
required. This is achieved with object-oriented design and programming (OOD/OOP) techniques.
Object-oriented techniques involve the use of objects and classes. An object is defined as “a logical entity that contains
both data and code that manipulates that data”. A class is the generalized form of similar objects. By using this concept,
one can create a protection class with the protection elements as objects of the class, such as time overcurrent, instanta-
neous overcurrent, current differential, undervoltage, overvoltage, underfrequency, and distance. These objects represent
completely self-contained software modules. The same object-class concept can be used for metering, input/output control,
software interface, communications, or any functional entity in the system.
Employing OOD/OOP in the software architecture of the D60 achieves the same features as the hardware architecture:
modularity, scalability, and flexibility. The application software for any UR-series device (for example, feeder protection,
transformer protection, distance protection) is constructed by combining objects from the various functional classes. This
results in a common interface across the UR series.
As described above, the architecture of the UR-series relays differ from previous devices. To achieve a general understand-
ing of this device, some sections of Chapter 5 are quite helpful. The most important functions of the relay are contained in
“elements”. A description of the UR-series elements can be found in the Introduction to elements section in chapter 5.
Examples of simple elements, and some of the organization of this manual, can be found in the Control elements section of
chapter 5. An explanation of the use of inputs from CTs and VTs is in the Introduction to AC sources section in chapter 5. A
description of how digital signals are used and routed within the relay is contained in the Introduction to FlexLogic section in
chapter 5.
1 The relay front panel or the EnerVista UR Setup software can be used to communicate with the relay. The EnerVista UR
Setup software interface is the preferred method to edit settings and view actual values because the computer monitor can
display more information.
The minimum system requirements for the EnerVista UR Setup software are as follows:
• Pentium 4 (Core Duo recommended)
• Windows XP with Service Pack 2 (Service Pack 3 recommended), Windows 7, or Windows Server 2008 Release 2
64-bit
• 1 GB of RAM (2 GB recommended)
• 500 MB free hard drive space (1 GB recommended)
• 1024 x 768 display (1280 x 800 recommended)
The following qualified modems have been tested to be compliant with the D60 and the EnerVista UR Setup software:
• US Robotics external 56K FaxModem 5686
• US Robotics external Sportster 56K X2
• PCTEL 2304WT V.92 MDC internal modem
1.3.2 INSTALLATION
After ensuring that the requirements for using EnerVista UR Setup are met (previous section), install the EnerVista UR
Setup software from the GE EnerVista DVD. Or download the UR EnerVista software from
http://www.gedigitalenergy.com/multilin and install it.
If you are upgrading from version 7.0 or 7.1 to 7.2 or later, some CPU modules require a new boot version. Update this first
in EnerVista under Maintenance > Update Firmware.
To install the UR EnerVista software from the DVD:
1. Insert the GE EnerVista DVD into the DVD drive of your computer.
2. Click the Install Now button and follow the instructions.
3. When installation is complete, start the EnerVista Launchpad application.
4. Click the IED Setup section of the Launch Pad window.
tion, then click the Add Now button to list software items for the product. EnerVista Launchpad then obtains the
software from the Internet or DVD and automatically starts the installation program.
1
a) OVERVIEW
You connect remotely to the D60 through the rear RS485 or Ethernet port with a computer running the EnerVista UR Setup
software. The D60 can also be accessed locally with a laptop computer through the front panel RS232 port or the rear
Ethernet port using the Quick Connect feature.
• To configure the D60 for remote access via the rear RS485 port, see the Configuring Serial Communications section.
• To configure the D60 for remote access via the rear Ethernet port, see the Configuring Ethernet Communications sec-
tion. An Ethernet module must be specified at the time of ordering.
• To configure the D60 for local access with a laptop through either the front RS232 port or rear Ethernet port, see the
Using the Quick Connect Feature section.
1 A GE Multilin F485 converter (or compatible RS232-to-RS485 converter) is required. See the F485 instruction manual for
details.
1. Connect a serial cable to the RS485 terminal on the back of the UR device.
2. In the EnerVista Launchpad software on the computer, select the UR device to start the software.
3. Click the Device Setup button to open the Device Setup window, and click the Add Site button to define a new site.
4. Enter a site name in the Site Name field. Optionally add a short description of the site along with the display order of
devices defined for the site. This example uses “Location 1” as the site name. When done, click the OK button. The
new site appears in the upper-left list in the EnerVista UR Setup window.
5. Click the Device Setup button, then select the new site to re-open the Device Setup window.
6. Click the Add Device button to define the new device.
7. Enter a name in the "Device Name” field and a description (optional) of the site.
8. Select “Serial” from the Interface drop-down list. This displays a number of interface parameters that must be entered
for serial communications.
20. Enter the relay slave address and Modbus port address values from the respective settings in the SETTINGS PROD-
UCT SETUP COMMUNICATIONS MODBUS PROTOCOL menu.
21. Click the Read Order Code button to connect to the D60 device and upload the order code. If an communications
error occurs, ensure that the three EnerVista UR Setup values entered in the previous steps correspond to the relay
setting values.
22. Click OK when the relay order code has been received. The new device is added to the Site List window (or Online
window) located in the top left corner of the main EnerVista UR Setup window.
The Site Device has now been configured for Ethernet communications. Proceed to the Connecting to the D60 section to
begin communications.
4. Select the Serial interface and the correct COM Port, then click Connect.
5. The EnerVista UR Setup software creates a site named “Quick Connect” with a corresponding device also named
“Quick Connect” and displays them at the upper-left of the screen. Expand the sections to view data directly from the
D60 device.
Each time that the EnerVista UR Setup software is initialized, click the Quick Connect button to establish direct communi-
cations to the D60 device. This ensures that configuration of the EnerVista UR Setup software matches the D60 model
number.
3 4 5 6
END 1 END 2
2 7 Pin Wire color Diagram Pin Wire color Diagram
1 8 1 White/orange 1 White/green
2 Orange 2 Green
3 White/green 3 White/orange
4 Blue 4 Blue
5 White/blue 5 White/blue
6 Green 6 Orange
7 White/brown 7 White/brown
8 Brown 8 Brown
842799A1.CDR
1. From the Windows desktop, right-click the My Network Places icon and select Properties to open the network con-
nections window.
1
3. Select the Internet Protocol (TCP/IP) item from the list, and click the Properties button.
5. Enter an IP address with the first three numbers the same as the IP address of the D60 relay and the last number dif-
1 6.
ferent (in this example, 1.1.1.2).
Enter a subnet mask equal to the one set in the D60 (in this example, 255.0.0.0).
7. Click the OK button to save the values.
Before continuing, test the Ethernet connection.
1. Open a Windows console window by selecting Start > Run from the Windows Start menu and typing “cmd”.
2. Type the following command, substituting the IP address of 1.1.1.1 with yours:
C:\WINNT>ping 1.1.1.1
3. If the connection is successful, the system returns four replies similar to the following:
Pinging 1.1.1.1 with 32 bytes of data:
Reply from 1.1.1.1: bytes=32 time<10ms TTL=255
Reply from 1.1.1.1: bytes=32 time<10ms TTL=255
Reply from 1.1.1.1: bytes=32 time<10ms TTL=255
Reply from 1.1.1.1: bytes=32 time<10ms TTL=255
Ping statistics for 1.1.1.1:
Packets: Sent = 4, Received = 4, Lost = 0 (0% loss),
Approximate round trip time in milliseconds:
Minimum = 0ms, Maximum = 0ms, Average = 0 ms
4. Note that the values for time and TTL vary depending on local network configuration.
5. If the following sequence of messages appears when entering the C:\WINNT>ping 1.1.1.1 command:
Pinging 1.1.1.1 with 32 bytes of data:
Request timed out.
Request timed out.
Request timed out.
Request timed out.
Ping statistics for 1.1.1.1:
Packets: Sent = 4, Received = 0, Lost = 4 (100% loss),
Approximate round trip time in milliseconds:
Minimum = 0ms, Maximum = 0ms, Average = 0 ms
Pinging 1.1.1.1 with 32 bytes of data:
verify the physical connection between the D60 and the laptop computer, and double-check the programmed IP
address in the PRODUCT SETUP COMMUNICATIONS NETWORK IP ADDRESS setting, then repeat step 2.
6. If the following sequence of messages appears when entering the C:\WINNT>ping 1.1.1.1 command:
Pinging 1.1.1.1 with 32 bytes of data:
Hardware error.
Hardware error.
Hardware error.
Hardware error.
Ping statistics for 1.1.1.1:
Packets: Sent = 4, Received = 0, Lost = 4 (100% loss),
Approximate round trip time in milliseconds:
Minimum = 0ms, Maximum = 0ms, Average = 0 ms
Pinging 1.1.1.1 with 32 bytes of data:
verify the physical connection between the D60 and the laptop computer, and double-check the programmed IP
address in the PRODUCT SETUP COMMUNICATIONS NETWORK IP ADDRESS setting, then repeat step 2.
7. If the following sequence of messages appears when entering the C:\WINNT>ping 1.1.1.1 command:
4. Ensure that the “Use a proxy server for your LAN” box is not checked.
If this computer is used to connect to the Internet, re-enable any proxy server settings after the laptop has been discon-
nected from the D60 relay.
1. Start the Internet Explorer software.
2. Select the “UR” device from the EnerVista Launchpad to start EnerVista UR Setup.
3. Click the Quick Connect button to open the Quick Connect dialog box.
4. Select the Ethernet interface and enter the IP address assigned to the D60, then click the Connect button. The
EnerVista UR Setup software creates a site named “Quick Connect” with a corresponding device also named “Quick
Connect” and displays them at the upper-left of the screen.
5. Expand the sections to view data directly from the D60 device.
Each time the EnerVista UR Setup software is initialized, click the Quick Connect button to establish direct communica-
tions to the D60. This ensures that configuration of the EnerVista UR Setup software matches the D60 model number.
When direct communications with the D60 via Ethernet is complete, make the following changes:
1. From the Windows desktop, right-click the My Network Places icon and select Properties to open the network con-
nections window.
2. Right-click the Local Area Connection icon and select the Properties item.
3. Select the Internet Protocol (TCP/IP) item from the list provided and click the Properties button.
4. Set the computer to “Obtain a relay address automatically” as shown.
If this computer is used to connect to the Internet, re-enable any proxy server settings after the computer has been discon-
nected from the D60 relay.
AUTOMATIC DISCOVERY OF ETHERNET DEVICES
The EnerVista UR Setup software can automatically discover and communicate to all UR-series IEDs located on an Ether-
net network.
Using the Quick Connect feature, a single click of the mouse triggers the software to automatically detect any UR-series
relays located on the network. The EnerVista UR Setup software then proceeds to configure all settings and order code
options in the Device Setup menu. This feature allows the user to identify and interrogate all UR-series devices at a loca-
tion.
1. Open the Display Properties window through the Site List tree as shown. The Display Properties window opens with a
1
status indicator on the lower left of the EnerVista UR Setup window.
842743A3.CDR
2. If the status indicator is red, verify that the Ethernet network cable is properly connected to the Ethernet port on the
back of the relay and that the relay has been properly setup for communications (steps A and B earlier).
If a relay icon appears in place of the status indicator, than a report (such as an oscillography or event record) is open.
Close the report to re-display the green status indicator.
3. The Display Properties settings can now be edited, printed, or changed.
See chapter 4 in this manual or the EnerVista UR Setup Help File for information about the using the EnerVista UR
Setup software interface.
NOTE
1 If and when first using CyberSentry security, use the following procedure for set up.
1. Log in to the relay as Administrator by using the Value keys on the front panel or through EnerVista connected serially
(so that no IP address is required). If logging in through EnerVista choose Device authentication. Enter the default
password "ChangeMe1#". Note that the "Lock relay" setting needs to be disabled in the Security > Supervisory
menu. When this setting is disabled, configuration and firmware upgrade are possible. By default, this setting is dis-
abled.
2. Enable the Supervisor role if you have a need for it.
3. Make any required changes in configuration, such as setting a valid IP address for communication over Ethernet.
4. Log out of the Administrator account by choosing None.
Next, device or server authentication can be chosen on the login screen, but the choice is available only in EnerVista. Use
device authentication to log in using the five pre-configured roles (Administrator, Supervisor, Engineer, Operator,
Observer). When using a serial connection, only device authentication is supported. When server authentication is
required, characteristics for communication with a RADIUS server must be configured on the UR. This is possible only
through the EnerVista software. The RADIUS server itself also must be configured. The appendix called RADIUS Server
gives an example of how to setup a simple RADIUS server. Once both the RADIUS server and the parameters for connect-
ing UR to the server have been configured, you can choose server authentication on the login screen of EnerVista.
Figure 1–10: LOGIN SCREEN FOR CYBERSENTRY
During the commissioning phase, you have the option to bypass the use of passwords. Do so by enabling the Bypass
Access setting under SETTINGS > PRODUCT SETUP > SECURITY > SUPERVISORY. Be sure to disable this bypass setting after
commissioning the device.
You can change the password for any role either from the front panel or through EnerVista.
If using EnerVista, navigate to Settings > Product Setup > Security. Change the Local Administrator Password, for
example. It is strongly recommended that the password for the Administrator be changed from the default. Changing the
passwords for the other three roles is optional. 1
Figure 1–11: CHANGING THE DEFAULT PASSWORD
1.4.2 COMMUNICATIONS
The EnerVista UR Setup software communicates to the relay via the faceplate RS232 port or the rear panel RS485 / Ether-
net ports. To communicate via the faceplate RS232 port, a standard straight-through serial cable is used. The DB-9 male
end is connected to the relay and the DB-9 or DB-25 female end is connected to the computer COM2 port as described in
the CPU communications ports section of chapter 3.
All messages are displayed on a backlit liquid crystal display (LCD) to make them visible under poor lighting conditions.
While the keypad and display are not actively being used, the display defaults to user-defined messages. Any high-priority
event-driven message automatically overrides the default message and appears on the display.
Display messages are organized into pages under the following headings: actual values, settings, commands, and targets.
1
The MENU key navigates through these pages. Each heading page is divided further into logical subgroups.
The MESSAGE keys navigate through the subgroups. The VALUE keys increment or decrement numerical setting values
when in programming mode. These keys also scroll through alphanumeric values in the text edit mode. Alternatively, val-
ues can be entered with the numeric keypad.
The decimal key initiates and advances to the next character in text edit mode or enters a decimal point.
The HELP key can be pressed at any time for context-sensitive help messages.
The ENTER key stores altered setting values.
Press the MENU key to select a header display page (top-level menu). The header title appears momentarily followed by a
header display page menu item. Each press of the MENU key advances through the following main heading pages:
• Actual values
• Settings
• Commands
• Targets
• User displays (when enabled)
The setting and actual value messages are arranged hierarchically. The header display pages are indicated by double
scroll bar characters (), while sub-header pages are indicated by single scroll bar characters (). The header display
pages represent the highest level of the hierarchy and the sub-header display pages fall below this level. The MESSAGE
UP and DOWN keys move within a group of headers, sub-headers, setting values, or actual values. Continually pressing
the MESSAGE RIGHT key from a header display displays specific information for the header category. Conversely, contin-
ually pressing the MESSAGE LEFT key from a setting value or actual value display returns to the header display.
SETTINGS
SYSTEM SETUP
The relay is in the default “Not Programmed” state when it leaves the factory. When powered up successfully, the Trouble
LED is on and the In Service LED off. The relay in the “Not Programmed” state blocks signaling of any output relay. These
conditions remain until the relay is explicitly put in the “Programmed” state.
Select the menu message SETTINGS PRODUCT SETUP INSTALLATION RELAY SETTINGS
RELAY SETTINGS:
Not Programmed
1. To put the relay in the “Programmed” state, press either of the VALUE keys once and then press ENTER. The face-
plate Trouble LED turns off and the In Service LED turns on.
The settings for the relay can be programmed manually (see Chapter 5) via the faceplate keypad or remotely via the
a) PASSWORD SECURITY
It is recommended that passwords be set for each security level and assigned to specific personnel. There are two user
security access levels, COMMAND and SETTING.
1. COMMAND
The COMMAND access level restricts the user from making any settings changes, but allows the user to perform the fol-
lowing operations:
• Operate breakers via faceplate keypad
• Change state of virtual inputs
• Clear event records
• Clear oscillography records
• Operate user-programmable pushbuttons
2. SETTING
The SETTING access level allows the user to make any changes to any of the setting values.
See the Changing Settings section in Chapter 4 for complete instructions on setting security-level passwords.
NOTE
b) CYBERSENTRY
When the CyberSentry option is purchased, advanced security services are available, using either device authentication or
server authentication using RADIUS. When this option is purchased, the basic password security is disabled automatically.
For more information, see the CyberSentry content in the Security section of the next chapter.
FlexLogic equation editing is required for setting user-defined logic for customizing the relay operations. See the FlexLogic
section in Chapter 5.
1.5.7 COMMISSIONING
The D60 requires minimal maintenance after it is commissioned into service. Since the D60 is a microprocessor-based
1
relay, its characteristics do not change over time. As such, no further functional tests are required.
The D60 performs a number of continual self-tests and takes the necessary action in case of any major errors (see the
Relay Self-tests section in chapter 7). However, it is recommended that D60 maintenance be scheduled with other system
maintenance. This maintenance can involve in-service, out-of-service, or unscheduled maintenance.
In-service maintenance:
1. Visual verification of the analog values integrity, such as voltage and current (in comparison to other devices on the
corresponding system).
2. Visual verification of active alarms, relay display messages, and LED indications.
3. LED test.
4. Visual inspection for any damage, corrosion, dust, or loose wires.
5. Event recorder file download with further events analysis.
Out-of-service maintenance:
1. Check wiring connections for firmness.
2. Analog values (currents, voltages, RTDs, analog inputs) injection test and metering accuracy verification. Calibrated
test equipment is required.
3. Protection elements setting verification (analog values injection or visual verification of setting file entries against relay
settings schedule).
4. Contact inputs and outputs verification. This test can be conducted by direct change of state forcing or as part of the
system functional testing.
5. Visual inspection for any damage, corrosion, or dust.
6. Event recorder file download with further events analysis.
7. LED Test and pushbutton continuity check.
Unscheduled maintenance, such as a disturbance causing system interruption:
1. View the event recorder and oscillography or fault report for correct operation of inputs, outputs, and elements.
If it is concluded that the relay or one of its modules is of concern, contact GE Multilin for service.
The D60 Line Distance Protection System is a microprocessor-based relay intended for use on transmission lines of any
voltage level, without, with, and in the vicinity of series compensation, in three-pole and single-pole tripping applications.
The primary function of the relay consists of five phase and ground distance zones of protection, either mho or quadrilateral
as per user selection, with built-in logic for the five common pilot-aided schemes. The distance elements are optimized to
provide good measurement accuracy with a fast operating time, even when used with capacitive voltage transformers
(CVTs), and can be supervised by detection of power swings. The relay also provides directional ground overcurrent ele-
ments, which are commonly used as part of an overall line protection system.
2
D60 phase distance zones can be configured to work with voltages and currents fed from VTs and CTs located indepen-
dently from one another on either side of a three-phase power transformer. The relay compensates accordingly to preserve
reach and correct target information regardless of the location and type of fault. This feature allows backup protection appli-
cations for generators and power transformers.
A close-into-fault (or switch-on-to-fault) function is performed by the line pickup element. Out-of-step tripping, three-pole/
single-pole dual-breaker autoreclosing, synchrocheck, fault location, and many other functions are also available. In addi-
tion, overcurrent and undervoltage protection, fault diagnostics, power metering, and RTU functions are provided. The D60
provides phase, neutral, and ground time overcurrent protection. The time overcurrent functions can be programmed with
multiple curve shapes or FlexCurve™ for optimum coordination.
Voltage, current, and power metering is built into the relay as a standard feature. Current parameters are available as total
waveform RMS magnitude, or as fundamental frequency only RMS magnitude and angle (phasor).
Diagnostic features include an event recorder capable of storing 1024 time-tagged events, oscillography capable of storing
up to 64 records with programmable trigger, content and sampling rate, and data logger acquisition of up to 16 channels,
with programmable content and sampling rate. The internal clock used for time-tagging can be synchronized with an IRIG-
B signal or via the SNTP protocol over the Ethernet port. This precise time stamping allows the sequence of events to be
determined throughout the system. Events can also be programmed (via FlexLogic™ equations) to trigger oscillography
data capture which may be set to record the measured parameters before and after the event for viewing on a personal
computer (PC). These tools significantly reduce troubleshooting time and simplify report generation in the event of a sys-
tem fault.
Several options are available for communication. A faceplate RS232 port can be used to connect to a computer for the pro-
gramming of settings and the monitoring of actual values. The RS232 port has a fixed baud rate of 19.2 kbps. The rear
RS485 port allows independent access by operating and engineering staff. It can be connected to system computers with
baud rates up to 115.2 kbps. All serial ports use the Modbus RTU protocol. The 100Base-FX Ethernet interface provides
fast, reliable communications in noisy environments. The Ethernet port supports IEC 61850, IEC 61850-90-5, Modbus/TCP,
and TFTP protocols, PTP (according to IEEE Std. 1588-2008 or IEC 61588), and allows access to the relay via any stan-
dard web browser (D60 web pages). The IEC 60870-5-104 protocol is supported on the Ethernet port, and DNP 3.0 and
IEC 60870-5-104 cannot be enabled at the same time. The Ethernet port also supports the Parallel Redundancy Protocol
(PRP) of IEC 62439-3 (clause 4, 2012) when purchased as a CPU module option.
The D60 IEDs use flash memory technology which allows field upgrading as new features are added. The following single
line diagram illustrates the relay functionality using ANSI (American National Standards Institute) device numbers.
&ORVH 7ULS
0RQLWRULQJ
; ;
3 B 3 B %) 3 3 B 1 1 1 *
'' & 1*
3
* *
1
'/LQH'LVWDQFH3URWHFWLRQ6\VWHP
$*&'5
2.1.2 SECURITY
b) PASSWORD SECURITY
Password security is a basic security feature present in the default offering of the product.
Two levels of password security are provided: command and setting.
The following operations are under command password supervision:
• Operating the breakers via faceplate keypad
• Changing the state of virtual inputs
• Clearing the event records
• Clearing the oscillography records
• Clearing fault reports
• Changing the date and time
• Clearing the breaker arcing current
2 The command and setting passwords are defaulted to “0” when the relay is shipped from the factory. When a password is
set to “0”, the password security feature is disabled. As shown in the figures, the window indicates when the password is at
the default and when the password has been set.
Figure 2–2: WINDOW INDICATES DEFAULT PASSWORD (LEFT) AND PASSWORD SET (RIGHT)
The D60 supports password entry from a local or remote connection. Local access is defined as any access to settings or
commands via the faceplate interface. This includes both keypad entry and the through the faceplate RS232 port. Remote
access is defined as any access to settings or commands via any rear communications port. This includes both Ethernet
and RS485 connections. Any changes to the local or remote passwords enables this functionality.
When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond-
ing connection password. If the connection is to the back of the D60, the remote password must be used. If the connection
is to the RS232 port of the faceplate, the local password applies.
Events are logged in the Event Recorder. The FlexLogic operands and events are updated every five seconds.
c) CYBERSENTRY SECURITY
CyberSentry Embedded Security is a software option that provides advanced security services. When this option is pur-
chased, the basic password security is disabled automatically.
CyberSentry provides security through the following features:
• An Authentication, Authorization, Accounting (AAA) Remote Authentication Dial-In User Service (RADIUS) client that
is centrally managed, enables user attribution, provides accounting of all user activities, and uses secure standards-
based strong cryptography for authentication and credential protection.
• A Role-Based Access Control (RBAC) system that provides a permission model that allows access to UR device oper-
ations and configurations based on specific roles and individual user accounts configured on the AAA server (that is,
Administrator, Supervisor, Engineer, Operator, Observer).
• Security event reporting through the Syslog protocol for supporting Security Information Event Management (SIEM)
systems for centralized cybersecurity monitoring.
• Strong encryption of all access and configuration network messages between the EnerVista software and UR devices
using the Secure Shell (SSH) protocol, the Advanced Encryption Standard (AES), and 128-bit keys in Galois Counter
Mode (GCM) as specified in the U.S. National Security Agency Suite B extension for SSH and approved by the
National Institute of Standards and Technology (NIST) FIPS-140-2 standards for cryptographic systems.
Example: Administrative functions can be segmented away from common operator functions, or engineering type
access, all of which are defined by separate roles, as shown in the following figure, so that access of UR devices by multi-
ple personnel within a substation is allowed. Permission for each role are outlined in the next section.
Figure 2–3: CYBERSENTRY USER ROLES
There are two types of authentication supported by CyberSentry that can be used to access the UR device:
• Device Authentication (local UR device authenticates)
• Server Authentication (RADIUS server authenticates)
The EnerVista software allows access to functionality that is determined by the user role, which comes either from the local
UR device or RADIUS server.
The EnerVista software has a device authentication option on the login screen for accessing the UR device. When the
"Device" button is selected, the UR uses its local authentication database and not the RADIUS server to authenticate the
user. In this case, it uses its built-in roles (Administrator, Engineer, Supervisor, Observer, Operator) as login names and the
associated passwords are stored on the UR device. As such, when using the local accounts, access is not user-attribut-
able.
In cases where user attributable access is required especially to facilitate auditable processes for compliance reasons, use
RADIUS authentication only.
When the "Server" Authentication Type option is selected, the UR uses the RADIUS server and not its local authentication
database to authenticate the user.
No password or security information are displayed in plain text by the EnerVista software or UR device, nor are they ever
transmitted without cryptographic protection.
CYBERSENTRY USER ROLES
CyberSentry user roles (Administrator, Engineer, Operator, Supervisor, Observer) limit the levels of access to various UR
device functions. This means that the EnerVista software allows for access to functionality based on the user’s logged in
role.
Example: Observer cannot write any settings.
The table lists the roles that are supported and their corresponding capabilities.
Table 2–3: PERMISSIONS BY USER ROLE FOR CYBERSENTRY
2 |--------------- Oscillography
|--------------- Data Logger
RW
RW
RW
RW
R
R
R
R
R
R
|--------------- Demand RW RW R R R
User Programmable
|--------------- LEDs RW RW R R R
User Programmable
|--------------- self test RW RW R R R
|--------------- Control Pushbuttons RW RW R R R
User programmable
|--------------- Pushbuttons RW RW R R R
|--------------- Flex states RW RW R R R
User definable dis-
|--------------- plays RW RW R R R
|--------------- Direct I/O RW RW R R R
|--------------- Tele-protection RW RW R R R
|--------------- Installation RW RW R R R
|------------ System Setup RW RW R R R
|------------ FlexLogic RW RW R R R
|------------ Grouped Elements RW RW R R R
|------------ Control Elements RW RW R R R
|------------ Inputs / Outputs RW RW R R R
|--------------- Contact Input RW RW R R R
Contact Input thresh-
|--------------- old RW RW R R R
|--------------- Virtual Inputs RW RW R R R
|--------------- Contact Output RW RW R R R
|--------------- Virtual Output RW RW R R R
|--------------- Remote Devices RW RW R R R
|--------------- Remote Inputs RW RW R R R
|--------------- Remote DPS input RW RW R R R
Remote Output DNA
|--------------- Bit Pair RW RW R R R
Remote Output user
|--------------- Bit Pair RW RW R R R
|--------------- Resetting RW RW R R R
|--------------- Direct Inputs RW RW R R R
|--------------- Direct Outputs RW RW R R R
|--------------- Teleprotection RW RW R R R
|--------------- Direct Analogs RW RW R R R
|--------------- Direct Integers RW RW R R R
IEC61850 GOOSE
|--------------- Analogs RW RW R R R
IEC61850 GOOSE
|--------------- Integers RW RW R R R
|------------ Transducer I/O RW RW R R R
|------------ Testing RW RW R R R
2.1.3 ORDERING
a) OVERVIEW
The D60 is available as a 19-inch rack horizontal mount or reduced-size (¾) vertical unit and consists of the following mod-
ules: power supply, CPU, CT/VT, digital input and output, transducer input and output, and inter-relay communications.
Each of these modules can be supplied in a number of configurations specified at the time of ordering. The information
required to completely specify the relay is provided in the following tables (see chapter 3 for full details of relay modules).
Order codes are subject to change without notice. See the ordering page at
http://www.gedigitalenergy.com/multilin/order.htm for the latest options.
NOTE
The order code structure is dependent on the mounting option (horizontal or vertical) and the type of CT/VT modules
(enhanced diagnostic CT/VT modules or HardFiberTM process bus modules). The order code options are described in the
following sub-sections.
2
SOFTWARE 00 | | | | | | | | | No software options
02 | | | | | | | | | Breaker-and-a-half software
03 | | | | | | | | | IEC 61850 communications
05 | | | | | | | | | Breaker-and-a-half software and IEC 61850 communications
06 | | | | | | | | | Phasor measurement unit (PMU)
07 | | | | | | | | | IEC 61850 communications and phasor measurement unit (PMU)
08 | | | | | | | | | Breaker-and-a-Half and phasor measurement unit (PMU)
09 | | | | | | | | | Breaker-and-a-Half, IEC 61850 communications, and phasor measurement unit (PMU)
A0 | | | | | | | | | CyberSentry Lvl 1
A2 | | | | | | | | | CyberSentry Lvl 1 and Breaker-and-a-half
A3 | | | | | | | | | CyberSentry Lvl 1 and IEC 61850
A5 | | | | | | | | | CyberSentry Lvl 1 and IEC 61850 and Breaker-and-a-half
A6 | | | | | | | | | CyberSentry Lvl 1 and phasor measurement unit (PMU)
A7 | | | | | | | | | CyberSentry Lvl 1 and IEC 61850 and phasor measurement unit (PMU)
A8 | | | | | | | | | CyberSentry Lvl 1 and phasor measurement unit (PMU) and Breaker-and-a-half
A9 | | | | | | | | | CyberSentry Lvl 1 and IEC 61850 and phasor measurement unit (PMU) and Breaker-and-a-half
B0 | | | | | | | | | IEEE 1588
B2 | | | | | | | | | IEEE 1588 and Breaker-and-a-half
B3 | | | | | | | | | IEEE 1588 and IEC 61850
B5 | | | | | | | | | IEEE 1588 and IEC 61850 and Breaker-and-a-half
B6 | | | | | | | | | IEEE 1588 and phasor measurement unit (PMU)
B7 | | | | | | | | | IEEE 1588 and IEC 61850 and phasor measurement unit (PMU)
B8 | | | | | | | | | IEEE 1588 and phasor measurement unit (PMU) and Breaker-and-a-half
B9 | | | | | | | | | IEEE 1588 and IEC 61850 and phasor measurement unit (PMU) and Breaker-and-a-half
C0 | | | | | | | | | Parallel Redundancy Protocol (PRP)
C2 | | | | | | | | | PRP and Breaker-and-a-half
C3 | | | | | | | | | PRP and IEC 61850
C5 | | | | | | | | | PRP, IEC 61850, and Breaker-and-a-half
C6 | | | | | | | | | PRP and PMU
C7 | | | | | | | | | PRP, IEC 61850, and PMU
C8 | | | | | | | | | PRP, Breaker-and-a-half, and PMU
C9 | | | | | | | | | PRP, IEC 61850, Breaker-and-a-half, and PMU
D0 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1
D2 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850
D3 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850
D5 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850
D6 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and phasor measurement unit (PMU)
D7 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850 and phasor measurement unit (PMU)
D8 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850 and phasor measurement unit (PMU)
D9 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850 + phasor measurement unit (PMU) + Breaker-and-a-half
E0 | | | | | | | | | IEEE 1588 and PRP
E2 | | | | | | | | | IEEE 1588, PRP, and Breaker-and-a-half
E3 | | | | | | | | | IEEE 1588, PRP, and IEC 61850
E5 | | | | | | | | | IEEE 1588, PRP, IEC 61850, and Breaker-and-a-half
E6 | | | | | | | | | IEEE 1588, PRP, and PMU
E7 | | | | | | | | | IEEE 1588, PRP, IEC 61850, and PMU
E8 | | | | | | | | | IEEE 1588, PRP, Breaker-and-a-half, and PMU
E9 | | | | | | | | | IEEE 1588, PRP, IEC 61850, Breaker-and-a-half, and PMU
F0 | | | | | | | | | PRP and CyberSentry Lvl 1
F2 | | | | | | | | | PRP, CyberSentry Lvl 1, and Breaker-and-a-half
F3 | | | | | | | | | PRP, CyberSentry Lvl 1, and IEC 61850
F5 | | | | | | | | | PRP CyberSentry Lvl 1, IEC 61850, and Breaker-and-a-half
F6 | | | | | | | | | PRP, CyberSentry Lvl 1, and PMU
F7 | | | | | | | | | PRP, CyberSentry Lvl 1, IEC 61850, and PMU
F8 | | | | | | | | | PRP, CyberSentry Lvl 1, Breaker-and-a-half, and PMU
F9 | | | | | | | | | PRP, CyberSentry Lvl 1, IEC 61850, Breaker-and-a-half, and PMU
G0 | | | | | | | | | IEEE 1588, PRP, and CyberSentry Lvl 1
G2 | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, Breaker-and-a-half
G3 | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, and IEC 61850
G5 | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, IEC 61850, and Breaker-and-a-half
G6 | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, and PMU
G7 | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, IEC 61850, and PMU
G8 | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, Breaker-and-a-half, and PMU
G9 | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, IEC 61850, Breaker-and-a-half, and PMU
The order codes for the reduced size vertical mount units are shown below.
Table 2–5: D60 ORDER CODES FOR REDUCED SIZE VERTICAL UNITS
D60 - * ** - * * * - F ** - H ** - M ** - P/R ** Reduced Size Vertical Mount (see note regarding P/R slot below)
BASE UNIT D60 | | | | | | | | | Base Unit
CPU T | | | | | | | | RS485 and Three Multi-mode fiber 100Base-FX (SFP with LC)
U | | | | | | | | RS485 and Two Multi-mode fiber 100Base-FX (SFP with LC), One 10/100Base-T (SFP with RJ45)
V | | | | | | | | RS485 and Three 10/100Base-T (SFP with RJ45)
SOFTWARE 00 | | | | | | | No software options
02 | | | | | | | Breaker-and-a-half software
03 | | | | | | | IEC 61850 communications
05 | | | | | | | Breaker-and-a-half software and IEC 61850 communications
06 | | | | | | | Phasor measurement unit (PMU)
07 | | | | | | | IEC 61850 communications and phasor measurement unit (PMU)
08 | | | | | | | Breaker-and-a-Half and phasor measurement unit (PMU)
09 | | | | | | | Breaker-and-a-Half, IEC 61850 communications, and phasor measurement unit (PMU)
A0 | | | | | | | CyberSentry Lvl 1
A2 | | | | | | | CyberSentry Lvl 1 and Breaker-and-a-half
A3 | | | | | | | CyberSentry Lvl 1 and IEC 61850
A5 | | | | | | | CyberSentry Lvl 1 and IEC 61850 and Breaker-and-a-half
A6 | | | | | | | CyberSentry Lvl 1 and phasor measurement unit (PMU)
A7 | | | | | | | CyberSentry Lvl 1 and IEC 61850 and phasor measurement unit (PMU)
A8 | | | | | | | CyberSentry Lvl 1 and phasor measurement unit (PMU) and Breaker-and-a-half
A9 | | | | | | | CyberSentry Lvl 1 and IEC 61850 and phasor measurement unit (PMU) and Breaker-and-a-half
B0 | | | | | | | IEEE 1588
B2 | | | | | | | IEEE 1588 and Breaker-and-a-half
B3 | | | | | | | IEEE 1588 and IEC 61850
B5 | | | | | | | IEEE 1588 and IEC 61850 and Breaker-and-a-half
B6 | | | | | | | IEEE 1588 and phasor measurement unit (PMU)
B7 | | | | | | | IEEE 1588 and IEC 61850 and phasor measurement unit (PMU)
B8 | | | | | | | IEEE 1588 and phasor measurement unit (PMU) and Breaker-and-a-half
B9 | | | | | | | IEEE 1588 and IEC 61850 and phasor measurement unit (PMU) and Breaker-and-a-half
C0 | | | | | | | Parallel Redundancy Protocol (PRP)
Table 2–5: D60 ORDER CODES FOR REDUCED SIZE VERTICAL UNITS
C2 | | | | | | | PRP and Breaker-and-a-half
C3 | | | | | | | PRP and IEC 61850
C5 | | | | | | | PRP, IEC 61850, and Breaker-and-a-half
C6 | | | | | | | PRP and PMU
C7 | | | | | | | PRP, IEC 61850, and PMU
C8 | | | | | | | PRP, Breaker-and-a-half, and PMU
C9 | | | | | | | PRP, IEC 61850, Breaker-and-a-half, and PMU
D0 | | | | | | | IEEE 1588 and CyberSentry Lvl 1
D2 | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850
D3 | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850
D5 | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850
D6 | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and phasor measurement unit (PMU)
D7 | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850 and phasor measurement unit (PMU)
D8 | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850 and phasor measurement unit (PMU)
2 D9
E0
E2
E3
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
IEEE 1588 and CyberSentry Lvl 1 and IEC 61850 + phasor measurement unit (PMU) + Breaker-and-a-half
IEEE 1588 and PRP
IEEE 1588, PRP, and Breaker-and-a-half
IEEE 1588, PRP, and IEC 61850
E5 | | | | | | | IEEE 1588, PRP, IEC 61850, and Breaker-and-a-half
E6 | | | | | | | IEEE 1588, PRP, and PMU
E7 | | | | | | | IEEE 1588, PRP, IEC 61850, and PMU
E8 | | | | | | | IEEE 1588, PRP, Breaker-and-a-half, and PMU
E9 | | | | | | | IEEE 1588, PRP, IEC 61850, Breaker-and-a-half, and PMU
F0 | | | | | | | PRP and CyberSentry Lvl 1
F2 | | | | | | | PRP, CyberSentry Lvl 1, and Breaker-and-a-half
F3 | | | | | | | PRP, CyberSentry Lvl 1, and IEC 61850
F5 | | | | | | | PRP CyberSentry Lvl 1, IEC 61850, and Breaker-and-a-half
F6 | | | | | | | PRP, CyberSentry Lvl 1, and PMU
F7 | | | | | | | PRP, CyberSentry Lvl 1, IEC 61850, and PMU
F8 | | | | | | | PRP, CyberSentry Lvl 1, Breaker-and-a-half, and PMU
F9 | | | | | | | PRP, CyberSentry Lvl 1, IEC 61850, Breaker-and-a-half, and PMU
G0 | | | | | | | IEEE 1588, PRP, and CyberSentry Lvl 1
G2 | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, Breaker-and-a-half
G3 | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, and IEC 61850
G5 | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, IEC 61850, and Breaker-and-a-half
G6 | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, and PMU
G7 | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, IEC 61850, and PMU
G8 | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, Breaker-and-a-half, and PMU
G9 | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, IEC 61850, Breaker-and-a-half, and PMU
MOUNT/COATING V | | | | | | Vertical (3/4 rack)
B | | | | | | Vertical (3/4 rack) with harsh environmental coating
FACEPLATE/ DISPLAY F | | | | | English display
D | | | | | French display
R | | | | | Russian display
A | | | | | Chinese display
K | | | | | Enhanced front panel with English display
M | | | | | Enhanced front panel with French display
Q | | | | | Enhanced front panel with Russian display
U | | | | | Enhanced front panel with Chinese display
L | | | | | Enhanced front panel with English display and user-programmable pushbuttons
N | | | | | Enhanced front panel with French display and user-programmable pushbuttons
T | | | | | Enhanced front panel with Russian display and user-programmable pushbuttons
V | | | | | Enhanced front panel with Chinese display and user-programmable pushbuttons
W | | | | | Enhanced front panel with Turkish display
Y | | | | | Enhanced front panel with Turkish display and user-programmable pushbuttons
POWER SUPPLY H | | | | 125 / 250 V AC/DC power supply
L | | | | 24 to 48 V (DC only) power supply
ENHANCED DIAGNOSTICS CT/VT DSP 8L | 8L | Standard 4CT/4VT with enhanced diagnostics
(requires all DSP to be enhanced diagnostic) 8M | 8M | Sensitive Ground 4CT/4VT with enhanced diagnostics
DIGITAL INPUTS/OUTPUTS XX | XX No Module
4A 4A 4A 4 Solid-State (no monitoring) MOSFET outputs
4B 4B 4B 4 Solid-State (voltage with optional current) MOSFET outputs
4C 4C 4C 4 Solid-State (current with optional voltage) MOSFET outputs
4D 4D 4D 16 digital inputs with Auto-Burnishing
4L 4L 4L 14 Form-A (no monitoring) Latching outputs
67 67 67 8 Form-A (no monitoring) outputs
6A 6A 6A 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 digital inputs
6B 6B 6B 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 digital inputs
6C 6C 6C 8 Form-C outputs
6D 6D 6D 16 digital inputs
6E 6E 6E 4 Form-C outputs, 8 digital inputs
6F 6F 6F 8 Fast Form-C outputs
6G 6G 6G 4 Form-A (voltage with optional current) outputs, 8 digital inputs
6H 6H 6H 6 Form-A (voltage with optional current) outputs, 4 digital inputs
6K 6K 6K 4 Form-C and 4 Fast Form-C outputs
6L 6L 6L 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 digital inputs
6M 6M 6M 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 digital inputs
6N 6N 6N 4 Form-A (current with optional voltage) outputs, 8 digital inputs
6P 6P 6P 6 Form-A (current with optional voltage) outputs, 4 digital inputs
6R 6R 6R 2 Form-A (no monitoring) and 2 Form-C outputs, 8 digital inputs
6S 6S 6S 2 Form-A (no monitoring) and 4 Form-C outputs, 4 digital inputs
6T 6T 6T 4 Form-A (no monitoring) outputs, 8 digital inputs
6U 6U 6U 6 Form-A (no monitoring) outputs, 4 digital inputs
6V 6V 6V 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 digital inputs
TRANSDUCER 5A 5A 5A 4 dcmA inputs, 4 dcmA outputs (only one 5A module is allowed)
INPUTS/OUTPUTS 5C 5C 5C 8 RTD inputs
(select a maximum of 3 per unit) 5D 5D 5D 4 RTD inputs, 4 dcmA outputs (only one 5D module is allowed)
5E 5E 5E 4 RTD inputs, 4 dcmA inputs
5F 5F 5F 8 dcmA inputs
INTER-RELAY 2A C37.94SM, 1300nm single-mode, ELED, 1 channel single-mode
COMMUNICATIONS 2B C37.94SM, 1300nm single-mode, ELED, 2 channel single-mode
(select a maximum of 1 per unit) 2E Bi-phase, single channel
For the last module, slot P is used for digital and transducer 2F Bi-phase, dual channel
2G IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel
input/output modules; slot R is used for inter-relay
2H IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
communications modules. 72 1550 nm, single-mode, LASER, 1 Channel
73 1550 nm, single-mode, LASER, 2 Channel
74 Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, LASER
75 Channel 1 - G.703; Channel 2 - 1550 nm, Single-mode LASER
76 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel
77 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels
7A 820 nm, multi-mode, LED, 1 Channel
7B 1300 nm, multi-mode, LED, 1 Channel
7C 1300 nm, single-mode, ELED, 1 Channel
7D 1300 nm, single-mode, LASER, 1 Channel
7E Channel 1 - G.703; Channel 2 - 820 nm, multi-mode
7F Channel 1 - G.703; Channel 2 - 1300 nm, multi-mode
7G Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
7H 820 nm, multi-mode, LED, 2 Channels
7I 1300 nm, multi-mode, LED, 2 Channels
7J 1300 nm, single-mode, ELED, 2 Channels
7K 1300 nm, single-mode, LASER, 2 Channels
7L Channel 1 - RS422; Channel 2 - 820 nm, multi-mode, LED
7M Channel 1 - RS422; Channel 2 - 1300 nm, multi-mode, LED
7N Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
7P Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER
7Q Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER
7R G.703, 1 Channel
7S G.703, 2 Channels
7T RS422, 1 Channel
7W RS422, 2 Channels
Table 2–6: D60 ORDER CODES FOR HORIZONTAL UNITS WITH PROCESS BUS (SHEET 1 OF 2)
D60 - * ** - * * * - F ** - H ** - M ** - P ** - U ** - W/X ** Full Size Horizontal Mount
BASE UNIT D60 | | | | | | | | | | | Base Unit
CPU T | | | | | | | | | | RS485 and Three Multi-mode fiber 100Base-FX (SFP with LC)
U | | | | | | | | | | RS485 and Two Multi-mode fiber 100Base-FX (SFP with LC), One 10/100Base-T (SFP with RJ45)
V | | | | | | | | | | RS485 and Three 10/100Base-T (SFP with RJ45)
2
SOFTWARE 00 | | | | | | | | | No software options
03 | | | | | | | | | IEC 61850 communications
06 | | | | | | | | | Phasor measurement unit (PMU)
07 | | | | | | | | | IEC 61850 communications and phasor measurement unit (PMU)
A0 | | | | | | | | | CyberSentry Lvl 1
A2 | | | | | | | | | CyberSentry Lvl 1 and Breaker-and-a-half
A3 | | | | | | | | | CyberSentry Lvl 1 and IEC 61850
A5 | | | | | | | | | CyberSentry Lvl 1 and IEC 61850 and Breaker-and-a-half
A6 | | | | | | | | | CyberSentry Lvl 1 and phasor measurement unit (PMU)
A7 | | | | | | | | | CyberSentry Lvl 1 and IEC 61850 and phasor measurement unit (PMU)
A8 | | | | | | | | | CyberSentry Lvl 1 and phasor measurement unit (PMU) and Breaker-and-a-half
A9 | | | | | | | | | CyberSentry Lvl 1 and IEC 61850 and phasor measurement unit (PMU) and Breaker-and-a-half
B0 | | | | | | | | | IEEE 1588
B2 | | | | | | | | | IEEE 1588 and Breaker-and-a-half
B3 | | | | | | | | | IEEE 1588 and IEC 61850
B5 | | | | | | | | | IEEE 1588 and IEC 61850 and Breaker-and-a-half
B6 | | | | | | | | | IEEE 1588 and phasor measurement unit (PMU)
B7 | | | | | | | | | IEEE 1588 and IEC 61850 and phasor measurement unit (PMU)
B8 | | | | | | | | | IEEE 1588 and phasor measurement unit (PMU) and Breaker-and-a-half
B9 | | | | | | | | | IEEE 1588 and IEC 61850 and phasor measurement unit (PMU) and Breaker-and-a-half
C0 | | | | | | | | | Parallel Redundancy Protocol (PRP)
C2 | | | | | | | | | PRP and Breaker-and-a-half
C3 | | | | | | | | | PRP and IEC 61850
C5 | | | | | | | | | PRP, IEC 61850, and Breaker-and-a-half
C6 | | | | | | | | | PRP and PMU
C7 | | | | | | | | | PRP, IEC 61850, and PMU
C8 | | | | | | | | | PRP, Breaker-and-a-half, and PMU
C9 | | | | | | | | | PRP, IEC 61850, Breaker-and-a-half, and PMU
D0 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1
D2 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850
D3 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850
D5 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850
D6 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and phasor measurement unit (PMU)
D7 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850 and phasor measurement unit (PMU)
D8 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850 and phasor measurement unit (PMU)
D9 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850 + phasor measurement unit (PMU) + Breaker-and-a-half
E0 | | | | | | | | | IEEE 1588 and PRP
E2 | | | | | | | | | IEEE 1588, PRP, and Breaker-and-a-half
E3 | | | | | | | | | IEEE 1588, PRP, and IEC 61850
E5 | | | | | | | | | IEEE 1588, PRP, IEC 61850, and Breaker-and-a-half
E6 | | | | | | | | | IEEE 1588, PRP, and PMU
E7 | | | | | | | | | IEEE 1588, PRP, IEC 61850, and PMU
E8 | | | | | | | | | IEEE 1588, PRP, Breaker-and-a-half, and PMU
E9 | | | | | | | | | IEEE 1588, PRP, IEC 61850, Breaker-and-a-half, and PMU
F0 | | | | | | | | | PRP and CyberSentry Lvl 1
F2 | | | | | | | | | PRP, CyberSentry Lvl 1, and Breaker-and-a-half
F3 | | | | | | | | | PRP, CyberSentry Lvl 1, and IEC 61850
F5 | | | | | | | | | PRP CyberSentry Lvl 1, IEC 61850, and Breaker-and-a-half
F6 | | | | | | | | | PRP, CyberSentry Lvl 1, and PMU
F7 | | | | | | | | | PRP, CyberSentry Lvl 1, IEC 61850, and PMU
F8 | | | | | | | | | PRP, CyberSentry Lvl 1, Breaker-and-a-half, and PMU
F9 | | | | | | | | | PRP, CyberSentry Lvl 1, IEC 61850, Breaker-and-a-half, and PMU
G0 | | | | | | | | | IEEE 1588, PRP, and CyberSentry Lvl 1
G2 | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, Breaker-and-a-half
G3 | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, and IEC 61850
G5 | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, IEC 61850, and Breaker-and-a-half
G6 | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, and PMU
G7 | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, IEC 61850, and PMU
G8 | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, Breaker-and-a-half, and PMU
G9 | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, IEC 61850, Breaker-and-a-half, and PMU
MOUNT/COATING H | | | | | | | | Horizontal (19” rack)
A | | | | | | | | Horizontal (19” rack) with harsh environmental coating
FACEPLATE/ DISPLAY C | | | | | | | English display
D | | | | | | | French display
R | | | | | | | Russian display
A | | | | | | | Chinese display
P | | | | | | | English display with 4 small and 12 large programmable pushbuttons
G | | | | | | | French display with 4 small and 12 large programmable pushbuttons
S | | | | | | | Russian display with 4 small and 12 large programmable pushbuttons
B | | | | | | | Chinese display with 4 small and 12 large programmable pushbuttons
K | | | | | | | Enhanced front panel with English display
M | | | | | | | Enhanced front panel with French display
Q | | | | | | | Enhanced front panel with Russian display
U | | | | | | | Enhanced front panel with Chinese display
L | | | | | | | Enhanced front panel with English display and user-programmable pushbuttons
N | | | | | | | Enhanced front panel with French display and user-programmable pushbuttons
T | | | | | | | Enhanced front panel with Russian display and user-programmable pushbuttons
V | | | | | | | Enhanced front panel with Chinese display and user-programmable pushbuttons
W | | | | | | | Enhanced front panel with Turkish display
Y | | | | | | | Enhanced front panel with Turkish display and user-programmable pushbuttons
POWER SUPPLY H | | | | | | 125 / 250 V AC/DC power supply
(redundant supply must H | | | | | RH 125 / 250 V AC/DC with redundant 125 / 250 V AC/DC power supply
be same type as main supply) L | | | | | | 24 to 48 V (DC only) power supply
L | | | | | RL 24 to 48 V (DC only) with redundant 24 to 48 V DC power supply
PROCESS BUS MODULE | 81 | | | | Eight-port digital process bus module
DIGITAL INPUTS/OUTPUTS XX XX XX XX XX No Module
4A 4A | 4 Solid-State (no monitoring) MOSFET outputs
4B 4B | 4 Solid-State (voltage with optional current) MOSFET outputs
4C 4C | 4 Solid-State (current with optional voltage) MOSFET outputs
4D 4D | 16 digital inputs with Auto-Burnishing
4L 4L | 14 Form-A (no monitoring) Latching outputs
67 67 | 8 Form-A (no monitoring) outputs
6A 6A | 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 digital inputs
6B 6B | 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 digital inputs
6C 6C | 8 Form-C outputs
6D 6D | 16 digital inputs
6E 6E | 4 Form-C outputs, 8 digital inputs
6F 6F | 8 Fast Form-C outputs
6G 6G | 4 Form-A (voltage with optional current) outputs, 8 digital inputs
6H 6H | 6 Form-A (voltage with optional current) outputs, 4 digital inputs
6K 6K | 4 Form-C and 4 Fast Form-C outputs
6L 6L | 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 digital inputs
6M 6M | 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 digital inputs
6N 6N | 4 Form-A (current with optional voltage) outputs, 8 digital inputs
6P 6P | 6 Form-A (current with optional voltage) outputs, 4 digital inputs
6R 6R | 2 Form-A (no monitoring) and 2 Form-C outputs, 8 digital inputs
6S 6S | 2 Form-A (no monitoring) and 4 Form-C outputs, 4 digital inputs
6T 6T | 4 Form-A (no monitoring) outputs, 8 digital inputs
6U 6U | 6 Form-A (no monitoring) outputs, 4 digital inputs
6V 6V | 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 digital inputs
INTER-RELAY 2A C37.94SM, 1300nm single-mode, ELED, 1 channel single-mode
COMMUNICATIONS 2B C37.94SM, 1300nm single-mode, ELED, 2 channel single-mode
(select a maximum of 1 per unit) 2E Bi-phase, single channel
2F Bi-phase, dual channel
2G IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel
2H IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
Table 2–6: D60 ORDER CODES FOR HORIZONTAL UNITS WITH PROCESS BUS (SHEET 2 OF 2)
D60 - * ** - * * * - F ** - H ** - M ** - P ** - U ** - W/X ** Full Size Horizontal Mount
BASE UNIT D60 | | | | | | | | | | | Base Unit
72 1550 nm, single-mode, LASER, 1 Channel
73 1550 nm, single-mode, LASER, 2 Channel
74 Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, LASER
75 Channel 1 - G.703; Channel 2 - 1550 nm, Single-mode LASER
76 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel
77 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels
7A 820 nm, multi-mode, LED, 1 Channel
7B 1300 nm, multi-mode, LED, 1 Channel
7C 1300 nm, single-mode, ELED, 1 Channel
7D 1300 nm, single-mode, LASER, 1 Channel
7E Channel 1 - G.703; Channel 2 - 820 nm, multi-mode
7F Channel 1 - G.703; Channel 2 - 1300 nm, multi-mode
2 7G
7H
7I
7J
Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
820 nm, multi-mode, LED, 2 Channels
1300 nm, multi-mode, LED, 2 Channels
1300 nm, single-mode, ELED, 2 Channels
7K 1300 nm, single-mode, LASER, 2 Channels
7L Channel 1 - RS422; Channel 2 - 820 nm, multi-mode, LED
7M Channel 1 - RS422; Channel 2 - 1300 nm, multi-mode, LED
7N Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
7P Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER
7Q Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER
7R G.703, 1 Channel
7S G.703, 2 Channels
7T RS422, 1 Channel
7W RS422, 2 Channels
The order codes for the reduced size vertical mount units with the process bus module are shown below.
Table 2–7: D60 ORDER CODES FOR REDUCED SIZE VERTICAL UNITS WITH PROCESS BUS (SHEET 1 OF 2)
D60 - * ** - * * * - F ** - H ** - M ** - P/R ** Reduced Size Vertical Mount (see note regarding P/R slot below)
BASE UNIT D60 | | | | | | | | | Base Unit
CPU T | | | | | | | | RS485 and Three Multi-mode fiber 100Base-FX (SFP with LC)
U | | | | | | | | RS485 and Two Multi-mode fiber 100Base-FX (SFP with LC), One 10/100Base-T (SFP with RJ45)
V | | | | | | | | RS485 and Three 10/100Base-T (SFP with RJ45)
SOFTWARE 00 | | | | | | | No software options
03 | | | | | | | IEC 61850 communications
06 | | | | | | | Phasor measurement unit (PMU)
07 | | | | | | | IEC 61850 communications and phasor measurement unit (PMU)
A0 | | | | | | | CyberSentry Lvl 1
A2 | | | | | | | CyberSentry Lvl 1 and Breaker-and-a-half
A3 | | | | | | | CyberSentry Lvl 1 and IEC 61850
A5 | | | | | | | CyberSentry Lvl 1 and IEC 61850 and Breaker-and-a-half
A6 | | | | | | | CyberSentry Lvl 1 and phasor measurement unit (PMU)
A7 | | | | | | | CyberSentry Lvl 1 and IEC 61850 and phasor measurement unit (PMU)
A8 | | | | | | | CyberSentry Lvl 1 and phasor measurement unit (PMU) and Breaker-and-a-half
A9 | | | | | | | CyberSentry Lvl 1 and IEC 61850 and phasor measurement unit (PMU) and Breaker-and-a-half
B0 | | | | | | | IEEE 1588
B2 | | | | | | | IEEE 1588 and Breaker-and-a-half
B3 | | | | | | | IEEE 1588 and IEC 61850
B5 | | | | | | | IEEE 1588 and IEC 61850 and Breaker-and-a-half
B6 | | | | | | | IEEE 1588 and phasor measurement unit (PMU)
B7 | | | | | | | IEEE 1588 and IEC 61850 and phasor measurement unit (PMU)
B8 | | | | | | | IEEE 1588 and phasor measurement unit (PMU) and Breaker-and-a-half
B9 | | | | | | | IEEE 1588 and IEC 61850 and phasor measurement unit (PMU) and Breaker-and-a-half
C0 | | | | | | | Parallel Redundancy Protocol (PRP)
C2 | | | | | | | PRP and Breaker-and-a-half
C3 | | | | | | | PRP and IEC 61850
C5 | | | | | | | PRP, IEC 61850, and Breaker-and-a-half
C6 | | | | | | | PRP and PMU
C7 | | | | | | | PRP, IEC 61850, and PMU
C8 | | | | | | | PRP, Breaker-and-a-half, and PMU
C9 | | | | | | | PRP, IEC 61850, Breaker-and-a-half, and PMU
D0 | | | | | | | IEEE 1588 and CyberSentry Lvl 1
D2 | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850
D3 | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850
D5 | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850
D6 | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and phasor measurement unit (PMU)
D7 | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850 and phasor measurement unit (PMU)
D8 | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850 and phasor measurement unit (PMU)
D9 | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850 + phasor measurement unit (PMU) + Breaker-and-a-half
E0 | | | | | | | IEEE 1588 and PRP
E2 | | | | | | | IEEE 1588, PRP, and Breaker-and-a-half
E3 | | | | | | | IEEE 1588, PRP, and IEC 61850
E5 | | | | | | | IEEE 1588, PRP, IEC 61850, and Breaker-and-a-half
E6 | | | | | | | IEEE 1588, PRP, and PMU
E7 | | | | | | | IEEE 1588, PRP, IEC 61850, and PMU
E8 | | | | | | | IEEE 1588, PRP, Breaker-and-a-half, and PMU
E9 | | | | | | | IEEE 1588, PRP, IEC 61850, Breaker-and-a-half, and PMU
F0 | | | | | | | PRP and CyberSentry Lvl 1
F2 | | | | | | | PRP, CyberSentry Lvl 1, and Breaker-and-a-half
F3 | | | | | | | PRP, CyberSentry Lvl 1, and IEC 61850
F5 | | | | | | | PRP CyberSentry Lvl 1, IEC 61850, and Breaker-and-a-half
F6 | | | | | | | PRP, CyberSentry Lvl 1, and PMU
F7 | | | | | | | PRP, CyberSentry Lvl 1, IEC 61850, and PMU
F8 | | | | | | | PRP, CyberSentry Lvl 1, Breaker-and-a-half, and PMU
F9 | | | | | | | PRP, CyberSentry Lvl 1, IEC 61850, Breaker-and-a-half, and PMU
G0 | | | | | | | IEEE 1588, PRP, and CyberSentry Lvl 1
G2 | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, Breaker-and-a-half
G3 | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, and IEC 61850
G5 | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, IEC 61850, and Breaker-and-a-half
G6 | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, and PMU
G7 | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, IEC 61850, and PMU
G8 | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, Breaker-and-a-half, and PMU
G9 | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, IEC 61850, Breaker-and-a-half, and PMU
MOUNT/COATING V | | | | | | Vertical (3/4 rack)
B | | | | | | Vertical (3/4 rack) with harsh environmental coating
FACEPLATE/ DISPLAY F | | | | | English display
D | | | | | French display
R | | | | | Russian display
A | | | | | Chinese display
K | | | | | Enhanced front panel with English display
M | | | | | Enhanced front panel with French display
Q | | | | | Enhanced front panel with Russian display
U | | | | | Enhanced front panel with Chinese display
L | | | | | Enhanced front panel with English display and user-programmable pushbuttons
N | | | | | Enhanced front panel with French display and user-programmable pushbuttons
T | | | | | Enhanced front panel with Russian display and user-programmable pushbuttons
V | | | | | Enhanced front panel with Chinese display and user-programmable pushbuttons
W | | | | | Enhanced front panel with Turkish display
Y | | | | | Enhanced front panel with Turkish display and user-programmable pushbuttons
Table 2–7: D60 ORDER CODES FOR REDUCED SIZE VERTICAL UNITS WITH PROCESS BUS (SHEET 2 OF 2)
POWER SUPPLY H | | | | 125 / 250 V AC/DC power supply
L | | | | 24 to 48 V (DC only) power supply
PROCESS BUS MODULE | 81 | Eight-port digital process bus module
DIGITAL INPUTS/OUTPUTS XX XX XX No Module
4A 4 Solid-State (no monitoring) MOSFET outputs
4B 4 Solid-State (voltage with optional current) MOSFET outputs
4C 4 Solid-State (current with optional voltage) MOSFET outputs
4D 16 digital inputs with Auto-Burnishing
4L 14 Form-A (no monitoring) Latching outputs
67 8 Form-A (no monitoring) outputs
6A 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 digital inputs
6B 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 digital inputs
6C 8 Form-C outputs
6D 16 digital inputs
6E
6F
6G
6H
4 Form-C outputs, 8 digital inputs
8 Fast Form-C outputs
4 Form-A (voltage with optional current) outputs, 8 digital inputs
6 Form-A (voltage with optional current) outputs, 4 digital inputs
2
6K 4 Form-C and 4 Fast Form-C outputs
6L 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 digital inputs
6M 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 digital inputs
6N 4 Form-A (current with optional voltage) outputs, 8 digital inputs
6P 6 Form-A (current with optional voltage) outputs, 4 digital inputs
6R 2 Form-A (no monitoring) and 2 Form-C outputs, 8 digital inputs
6S 2 Form-A (no monitoring) and 4 Form-C outputs, 4 digital inputs
6T 4 Form-A (no monitoring) outputs, 8 digital inputs
6U 6 Form-A (no monitoring) outputs, 4 digital inputs
6V 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 digital inputs
INTER-RELAY 2A C37.94SM, 1300nm single-mode, ELED, 1 channel single-mode
COMMUNICATIONS 2B C37.94SM, 1300nm single-mode, ELED, 2 channel single-mode
(select a maximum of 1 per unit) 2E Bi-phase, single channel
For the last module, slot P is used for digital 2F Bi-phase, dual channel
2G IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel
input/output modules; slot R is used for inter-relay
2H IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
communications modules. 72 1550 nm, single-mode, LASER, 1 Channel
73 1550 nm, single-mode, LASER, 2 Channel
74 Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, LASER
75 Channel 1 - G.703; Channel 2 - 1550 nm, Single-mode LASER
76 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel
77 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels
7A 820 nm, multi-mode, LED, 1 Channel
7B 1300 nm, multi-mode, LED, 1 Channel
7C 1300 nm, single-mode, ELED, 1 Channel
7D 1300 nm, single-mode, LASER, 1 Channel
7E Channel 1 - G.703; Channel 2 - 820 nm, multi-mode
7F Channel 1 - G.703; Channel 2 - 1300 nm, multi-mode
7G Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
7H 820 nm, multi-mode, LED, 2 Channels
7I 1300 nm, multi-mode, LED, 2 Channels
7J 1300 nm, single-mode, ELED, 2 Channels
7K 1300 nm, single-mode, LASER, 2 Channels
7L Channel 1 - RS422; Channel 2 - 820 nm, multi-mode, LED
7M Channel 1 - RS422; Channel 2 - 1300 nm, multi-mode, LED
7N Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
7P Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER
7Q Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER
7R G.703, 1 Channel
7S G.703, 2 Channels
7T RS422, 1 Channel
7W RS422, 2 Channels
Replacement modules can be ordered separately. When ordering a replacement CPU module or faceplate, provide the
serial number of your existing unit.
Not all replacement modules may be applicable to the D60 relay. Only the modules specified in the order codes are
available as replacement modules.
NOTE
2 Replacement module codes are subject to change without notice. See the ordering page at
http://www.gedigitalenergy.com/multilin/order.htm for the latest D60 ordering options.
NOTE
The replacement module order codes for the horizontal mount units are shown below.
The replacement module order codes for the reduced-size vertical mount units are shown below.
The operating times include the activation time of a trip rated form-A output contact unless otherwise indicated.
FlexLogic operands of a given element are 4 ms faster. Take this into account when using FlexLogic to interconnect
NOTE with other protection or control elements of the relay, building FlexLogic equations, or interfacing with other IEDs or
2 power system devices via communications or different output contacts. If not specified, operate times are given
here for a 60 Hz system at nominal system frequency. Operate times for a 50 Hz system are 1.2 times longer.
PHASE DISTANCE PHASE DISTANCE OPERATING TIME CURVES
Characteristic: mho (memory polarized or offset) or The operating times are response times of a microprocessor part
quad (memory polarized or non-direc- of the relay. See output contacts specifications for estimation of
tional), selectable individually per zone the total response time for a particular application. The operating
Number of zones: 5 times are average times including variables such as fault inception
Directionality: forward, reverse, or non-directional per angle or type of a voltage source (magnetic VTs and CVTs).
zone
Reach (secondary ): 0.02 to 500.00 in steps of 0.01 Phase Element (21P)
Zero-sequence compensation 0% 10% 20% 30% 40% 50% 60% 70% 80%
Fault Location [%]
Z0/Z1 magnitude: 0.00 to 10.00 in steps of 0.01
837718A1.CDR
2 Overreach:
Pickup delay:
<2%
0.00 to 600.00 s in steps of 0.01
Current sensitivity threshold: 0.05 pu
Characteristic angle: 0 to 359° in steps of 1
Angle accuracy: ±2°
Reset delay: 0.00 to 600.00 s in steps of 0.01
Operation time (FlexLogic operands):
Operate time: <16 ms at 3 pickup at 60 Hz
(Phase/Ground IOC) Tripping (reverse load, forward fault):
12 ms, typically
<20 ms at 3 pickup at 60 Hz
Blocking (forward load, reverse fault):
(Neutral IOC)
8 ms, typically
Timer accuracy: ±3% of operate time or ±1/4 cycle
(whichever is greater) NEUTRAL DIRECTIONAL OVERCURRENT
Directionality: Co-existing forward and reverse
NEGATIVE SEQUENCE TOC
Polarizing: Voltage, Current, Dual, Dual-V, Dual-I
Pickup level: 0.000 to 30.000 pu in steps of 0.001
Polarizing voltage: V_0 or VX
Dropout level: 97% to 98% of pickup
Polarizing current: IG
Level accuracy: ±0.5% of reading or ±0.4% of rated
(whichever is greater) Operating current: I_0
from 0.1 to 2.0 x CT rating Level sensing: 3 (|I_0| – K |I_1|), IG
±1.5% of reading > 2.0 x CT rating Restraint, K: 0.000 to 0.500 in steps of 0.001
Curve shapes: IEEE Moderately/Very/Extremely Characteristic angle: –90 to 90° in steps of 1
Inverse; IEC (and BS) A/B/C and Short Limit angle: 40 to 90° in steps of 1, independent for
Inverse; GE IAC Inverse, Short/Very/
forward and reverse
Extremely Inverse; I2t; FlexCurves™
Angle accuracy: ±2°
(programmable); Definite Time (0.01 s
base curve) Offset impedance: 0.00 to 250.00 in steps of 0.01
Curve multiplier (Time dial): 0.00 to 600.00 in steps of 0.01 Pickup level: 0.002 to 30.000 pu in steps of 0.01
Reset type: Instantaneous/Timed (per IEEE) and Lin- Dropout level: 97 to 98%
ear Operation time: <16 ms at 3 pickup at 60 Hz
Curve timing accuracy NEGATIVE SEQUENCE DIRECTIONAL OC
at 1.03 to 20 x pickup: ±3.5% of operate time or ±½ cycle Directionality: Co-existing forward and reverse
(whichever is greater) from pickup to Polarizing: Voltage
operate
Polarizing voltage: V_2
NEGATIVE SEQUENCE IOC Operating current: I_2
Pickup level: 0.000 to 30.000 pu in steps of 0.001 Level sensing:
Dropout level: 97 to 98% of pickup Zero-sequence:|I_0| – K |I_1|
Level accuracy: 0.1 to 2.0 CT rating: ±0.5% of reading Negative-sequence:|I_2| – K |I_1|
or ±0.4% of rated (whichever is greater); Restraint, K: 0.000 to 0.500 in steps of 0.001
2.0 CT rating: ±1.5% of reading
Characteristic angle: 0 to 90° in steps of 1
Overreach: 2%
Limit angle: 40 to 90° in steps of 1, independent for
Pickup delay: 0.00 to 600.00 s in steps of 0.01 forward and reverse
Reset delay: 0.00 to 600.00 s in steps of 0.01 Angle accuracy: ±2°
Operate time: <20 ms at 3 pickup at 60 Hz Offset impedance: 0.00 to 250.00 in steps of 0.01
Timer accuracy: ±3% of operate time or ±1/4 cycle Pickup level: 0.015 to 30.000 pu in steps of 0.01
(whichever is greater) Dropout level: 97 to 98%
Operation time: <16 ms at 3 pickup at 60 Hz
Typical times are average operate times including variables such BREAKER RESTRIKE
as frequency change instance, test method, etc., and may vary by Principle: detection of high-frequency overcurrent
±0.5 cycles. condition ¼ cycle after breaker opens
RATE OF CHANGE OF FREQUENCY Availability: one per CT/VT module (not including 8Z
df/dt trend: increasing, decreasing, bi-directional modules)
df/dt pickup level: 0.10 to 15.00 Hz/s in steps of 0.01 Pickup level: 0.1 to 2.00 pu in steps of 0.01
df/dt dropout level: 96% of pickup Reset delay: 0.000 to 65.535 s in steps of 0.001
FLEXLOGIC FLEXELEMENTS™
Programming language: Reverse Polish Notation with graphical Number of elements: 8
visualization (keypad programmable) Operating signal: any analog actual value, or two values in
Lines of code: 512 differential mode
Internal variables: 64 Operating signal mode: signed or absolute value
Supported operations: NOT, XOR, OR (2 to 16 inputs), AND (2 Operating mode: level, delta
to 16 inputs), NOR (2 to 16 inputs), Comparator direction: over, under
NAND (2 to 16 inputs), latch (reset-domi- Pickup Level: –90.000 to 90.000 pu in steps of 0.001
nant), edge detectors, timers
Hysteresis: 0.1 to 50.0% in steps of 0.1
Inputs: any logical variable, contact, or virtual
Delta dt: 20 ms to 60 days
input
Pickup & dropout delay: 0.000 to 65.535 s in steps of 0.001
Number of timers: 32
Pickup delay: 0 to 60000 (ms, sec., min.) in steps of 1 NON-VOLATILE LATCHES
Dropout delay: 0 to 60000 (ms, sec., min.) in steps of 1 Type: set-dominant or reset-dominant
Number: 16 (individually programmed)
FLEXCURVES™
Number: 4 (A through D) Output: stored in non-volatile memory
Reset points: 40 (0 through 1 of pickup) Execution sequence: as input prior to protection, control, and
FlexLogic
Operate points: 80 (1 through 20 of pickup)
Time delay: 0 to 65535 ms in steps of 1 USER-PROGRAMMABLE LEDs
Number: 48 plus trip and alarm
FLEX STATES Programmability: from any logical variable, contact, or vir-
Number: up to 256 logical variables grouped tual input
under 16 Modbus addresses
Reset mode: self-reset or latched
Programmability: any logical variable, contact, or virtual
input LED TEST
Initiation: from any digital input or user-program-
mable condition
Number of tests: 3, interruptible at any time
Duration of full test: approximately 3 minutes
Test sequence 1: all LEDs on
Test sequence 2: all LEDs off, one LED at a time on for 1 s
Test sequence 3: all LEDs on, one LED at a time off for 1 s
2.2.3 MONITORING
2.2.4 METERING
RMS CURRENT: PHASE, NEUTRAL, AND GROUND WATT-HOURS (POSITIVE AND NEGATIVE)
Accuracy at Accuracy: ±2.0% of reading
0.1 to 2.0 CT rating: ±0.25% of reading or ±0.1% of rated Range: ±0 to 1 106 MWh
(whichever is greater) Parameters: three-phase only
2.0 CT rating: ±1.0% of reading
Update rate: 50 ms
RMS VOLTAGE
Accuracy: ±0.5% of reading from 10 to 208 V
VAR-HOURS (POSITIVE AND NEGATIVE)
Accuracy: ±2.0% of reading
REAL POWER (WATTS) Range: ±0 to 1 106 Mvarh
Accuracy at 0.1 to 1.5 x
Parameters: three-phase only
CT rating and 0.8 to
Update rate: 50 ms
1.2 x VT rating: ±1.0% of reading at –1.0 PF< –0.8 and
0.8 < PF 10 FREQUENCY
Accuracy at
REACTIVE POWER (VARS) V = 0.8 to 1.2 pu: ±0.01 Hz (when voltage signal is used
Accuracy at 0.1 to 1.5 x for frequency measurement)
CT rating and 0.8 to I = 0.1 to 0.25 pu: ±0.05 Hz
1.2 x VT rating: ±1.0% of reading at –0.2 PF 0.2 I > 0.25 pu: ±0.02 Hz (when current signal is used for
frequency measurement)
APPARENT POWER (VA)
Accuracy at 0.1 to 1.5 x
CT rating and 0.8 to
1.2 x VT rating: ±1.0% of reading
2.2.5 INPUTS
2 FREQUENCY
Nominal frequency setting:25 to 60 Hz
IRIG-B INPUT
Amplitude modulation: 1 to 10 V pk-pk
Sampling frequency: 64 samples per power cycle DC shift: TTL–Compatible
Tracking frequency range:20 to 65 Hz Input impedance: 50 k
CONTACT INPUTS Isolation: 2 kV
Dry contacts: 1000 maximum REMOTE INPUTS (IEC 61850 GSSE/GOOSE)
Wet contacts: 300 V DC maximum Input points: 32, configured from 64 incoming bit pairs
Selectable thresholds: 17 V, 33 V, 84 V, 166 V Remote devices: 16
Tolerance: ±10% Default states on loss of comms.: On, Off, Latest/Off, Latest/On
Contacts per common return: 4 Remote DPS inputs: 5
Recognition time: < 1 ms
DIRECT INPUTS
Debounce time: 0.0 to 16.0 ms in steps of 0.5
Input points: 32
Continuous current draw:3 mA (when energized)
Remote devices: 16
CONTACT INPUTS WITH AUTO-BURNISHING Default states on loss of comms.: On, Off, Latest/Off, Latest/On
Dry contacts: 1000 maximum Ring configuration: Yes, No
Wet contacts: 300 V DC maximum Data rate: 64 or 128 kbps
Selectable thresholds: 17 V, 33 V, 84 V, 166 V CRC: 32-bit
Tolerance: ±10% CRC alarm:
Contacts per common return: 2 Responding to: Rate of messages failing the CRC
Recognition time: < 1 ms Monitoring message count: 10 to 10000 in steps of 1
Alarm threshold: 1 to 1000 in steps of 1
Debounce time: 0.0 to 16.0 ms in steps of 0.5
Unreturned message alarm:
Continuous current draw:3 mA (when energized)
Responding to: Rate of unreturned messages in the ring
Auto-burnish impulse current: 50 to 70 mA configuration
Duration of auto-burnish impulse: 25 to 50 ms Monitoring message count: 10 to 10000 in steps of 1
DCMA INPUTS Alarm threshold: 1 to 1000 in steps of 1
Current input (mA DC): 0 to –1, 0 to +1, –1 to +1, 0 to 5, 0 to 10, TELEPROTECTION
0 to 20, 4 to 20 (programmable) Input points: 16
Input impedance: 379 ±10% Remote devices: 3
Conversion range: –1 to + 20 mA DC Default states on loss of comms.: On, Off, Latest/Off, Latest/On
Accuracy: ±0.2% of full scale Ring configuration: No
Type: Passive Data rate: 64 or 128 kbps
CRC: 32-bit
2.2.7 OUTPUTS 2
FORM-A RELAY FAST FORM-C RELAY
Make and carry for 0.2 s: 30 A as per ANSI C37.90 Make and carry: 0.1 A max. (resistive load)
24 V 1A 250 V DC 20 K 50 K
48 V 0.5 A 120 V DC 5 K 2 K
125 V 0.3 A 48 V DC 2 K 2 K
250 V 0.2 A 24 V DC 2 K 2 K
Operate time: < 4 ms Note: values for 24 V and 48 V are the same due to a
required 95% voltage drop across the load impedance.
Contact material: silver alloy
Operate time: < 0.6 ms
LATCHING RELAY Internal Limiting Resistor: 100 , 2 W
Make and carry for 0.2 s: 30 A as per ANSI C37.90
Carry continuous: 6 A as per IEEE C37.90 SOLID-STATE OUTPUT RELAY
Operate and release time: <100 s
Break (DC resistive as per IEC61810-1):
Maximum voltage: 265 V DC
VOLTAGE CURRENT
Maximum continuous current: 5 A at 45°C; 4 A at 65°C
24 V 6A
Make and carry:
48 V 1.6 A
for 0.2 s: 30 A as per ANSI C37.90
125 V 0.4 A for 0.03 s 300 A
250 V 0.2 A Breaking capacity:
Operate time: < 4 ms UL508 Utility Industrial
application application
Contact material: silver alloy (autoreclose
Control: separate operate and reset inputs scheme)
Control mode: operate-dominant or reset-dominant Operations/ 5000 ops / 5 ops /
interval 1 s-On, 9 s-Off 0.2 s-On, 10000 ops /
FORM-A VOLTAGE MONITOR 0.2 s-Off 0.2 s-On,
Applicable voltage: approx. 15 to 250 V DC 1000 ops / within 1 30 s-Off
0.5 s-On, 0.5 s-Off minute
Trickle current: approx. 1 to 2.5 mA
Break 3.2 A
FORM-A CURRENT MONITOR capability L/R = 10 ms
(0 to 250 V
Threshold current: approx. 80 to 100 mA DC) 1.6 A 10 A 10 A
L/R = 20 ms L/R = 40 ms L/R = 40 ms
FORM-C AND CRITICAL FAILURE RELAY 0.8 A
Make and carry for 0.2 s: 30 A as per ANSI C37.90 L/R = 40 ms
Carry continuous: 8A
CONTROL POWER EXTERNAL OUTPUT
Break (DC inductive, L/R = 40 ms):
(FOR DRY CONTACT INPUT)
VOLTAGE CURRENT Capacity: 100 mA DC at 48 V DC
24 V 1A Isolation: ±300 Vpk
48 V 0.5 A
REMOTE OUTPUTS (IEC 61850 GSSE/GOOSE)
125 V 0.3 A
Standard output points: 32
250 V 0.2 A
User output points: 32
Operate time: < 8 ms
DIRECT OUTPUTS
Contact material: silver alloy
Output points: 32
DCMA OUTPUTS
Range: –1 to 1 mA, 0 to 1 mA, 4 to 20 mA
Max. load resistance: 12 k for –1 to 1 mA range
12 k for 0 to 1 mA range
600 for 4 to 20 mA range
Accuracy: ±0.75% of full-scale for 0 to 1 mA range
±0.5% of full-scale for –1 to 1 mA range
±0.75% of full-scale for 0 to 20 mA range
2 99% Settling time to a step change: 100 ms
Isolation: 1.5 kV
Driving signal: any FlexAnalog quantity
Upper and lower limit for the driving signal: –90 to 90 pu in steps of
0.001
2.2.8 COMMUNICATIONS
RS232
Front port: 19.2 kbps, Modbus RTU
PRECISION TIME PROTOCOL (PTP)
RS485 PTP IEEE Std 1588 2008 (version 2)
1 rear port: Up to 115 kbps, Modbus RTU, isolated Power Profile (PP) per IEEE Standard PC37.238TM2011
together at 36 Vpk
Slave-only ordinary clock
Typical distance: 1200 m
Peer delay measurement mechanism
Isolation: 2 kV
PARALLEL REDUNDANCY PROTOCOL (PRP)
ETHERNET (FIBER) (IEC 62439-3 CLAUSE 4, 2012)
PARAMETER FIBER TYPE Ethernet ports used: 2 and 3
100MB MULTI- Networks supported: 10/100 MB Ethernet
MODE
Wavelength 1310 nm
Connector LC
Transmit power –20 dBm
Receiver sensitivity –30 dBm
Power budget 10 dB
Maximum input –14 dBm
power
Typical distance 2 km
Duplex full/half
Redundancy yes
2.2.10 ENVIRONMENTAL
2 Damped oscillatory
Electrostatic discharge
IEC61000-4-18 / IEC60255-22-1
EN61000-4-2 / IEC60255-22-2
2.5 kV CM, 1 kV DM
Level 3
RF immunity EN61000-4-3 / IEC60255-22-3 Level 3
Fast transient disturbance EN61000-4-4 / IEC60255-22-4 Class A and B
Surge immunity EN61000-4-5 / IEC60255-22-5 Level 3 and 4
Conducted RF immunity EN61000-4-6 / IEC60255-22-6 Level 3
Power frequency immunity EN61000-4-7 / IEC60255-22-7 Class A and B
Voltage interruption and ripple DC IEC60255-11 12% ripple, 200 ms interrupts
Radiated and conducted emissions CISPR11 / CISPR22 / IEC60255-25 Class A
Sinusoidal vibration IEC60255-21-1 Class 1
Shock and bump IEC60255-21-2 Class 1
Seismic IEC60255-21-3 Class 1
Power magnetic immunity IEC61000-4-8 Level 5
Pulse magnetic immunity IEC61000-4-9 Level 4
Damped magnetic immunity IEC61000-4-10 Level 4
Voltage dip and interruption IEC61000-4-11 0, 40, 70, 80% dips; 250 / 300 cycle interrupts
Damped oscillatory IEC61000-4-12 2.5 kV CM, 1 kV DM
Conducted RF immunity, 0 to 150 kHz IEC61000-4-16 Level 4
Voltage ripple IEC61000-4-17 15% ripple
Ingress protection IEC60529 IP40 front, IP10 back
Cold IEC60068-2-1 –40°C for 16 hours
Hot IEC60068-2-2 85°C for 16 hours
Humidity IEC60068-2-30 6 days, variant 1
Damped oscillatory IEEE/ANSI C37.90.1 2.5 kV, 1 MHz
RF immunity IEEE/ANSI C37.90.2 20 V/m, 80 MHz to 1 GHz
Safety UL508 e83849 NKCR
Safety UL C22.2-14 e83849 NKCR7
Safety UL1053 e83849 NKCR
THERMAL
Products go through an environmental test based upon an
Accepted Quality Level (AQL) sampling process.
2.2.13 APPROVALS
APPROVALS
COMPLIANCE APPLICABLE ACCORDING TO
COUNCIL DIRECTIVE
CE Low voltage directive EN 60255-5
EMC directive EN 60255-26 / EN 50263
EN 61000-6-5 2
C-UL-US --- UL 508
UL 1053
C22.2 No. 14
2.2.14 MAINTENANCE
MOUNTING CLEANING
Attach mounting brackets using 20 inch-pounds (±2 inch-pounds) Normally, cleaning is not required; but for situations where dust
of torque. has accumulated on the faceplate display, a dry cloth can be used.
To avoid deterioration of electrolytic
capacitors, power up units that are stored
in a de-energized state once per year, for
one hour continuously.
a) HORIZONTAL UNITS
The D60 Line Distance Protection System is available as a 19-inch rack horizontal mount unit with a removable faceplate.
The faceplate can be specified as either standard or enhanced at the time of ordering. The enhanced faceplate contains
additional user-programmable pushbuttons and LED indicators.
The modular design allows the relay to be easily upgraded or repaired by a qualified service person. The faceplate is
hinged to allow easy access to the removable modules, and is itself removable to allow mounting on doors with limited rear
depth.
The case dimensions are shown below, along with panel cutout details for panel mounting. When planning the location of
your panel cutout, ensure that provision is made for the faceplate to swing open without interference to or from adjacent
equipment.
The relay must be mounted such that the faceplate sits semi-flush with the panel or switchgear door, allowing the operator 3
access to the keypad and the RS232 communications port. The relay is secured to the panel with the use of four screws
supplied with the relay.
11.016”
[279,81 mm]
9.687”
[246,05 mm]
17.56”
[446,02 mm]
7.460”
[189,48 mm]
6.995” 6.960”
[177,67 mm] [176,78 mm]
19.040”
[483,62 mm]
842807A1.CDR
18.370”
[466,60 mm]
0.280”
[7,11 mm]
Typ. x 4
CUT-OUT
4.000”
[101,60 mm]
17.750”
3
[450,85 mm] 842808A1.CDR
b) VERTICAL UNITS
The D60 Line Distance Protection System is available as a reduced size (¾) vertical mount unit, with a removable face-
plate. The faceplate can be specified as either standard or enhanced at the time of ordering. The enhanced faceplate con-
tains additional user-programmable pushbuttons and LED indicators.
The modular design allows the relay to be easily upgraded or repaired by a qualified service person. The faceplate is
hinged to allow easy access to the removable modules, and is itself removable to allow mounting on doors with limited rear
depth.
The case dimensions are shown below, along with panel cutout details for panel mounting. When planning the location of
your panel cutout, ensure that provision is made for the faceplate to swing open without interference to or from adjacent
equipment.
The relay must be mounted such that the faceplate sits semi-flush with the panel or switchgear door, allowing the operator
access to the keypad and the RS232 communications port. The relay is secured to the panel with the use of four screws
supplied with the relay.
7.482” 11.015”
1.329”
13.560”
3
15.000” 14.025”
4.000”
9.780”
843809A1.CDR
Figure 3–7: D60 VERTICAL SIDE MOUNTING REAR DIMENSIONS (STANDARD PANEL)
The small form-factor pluggable ports (SFPs) are pluggable transceivers. Do not use non-validated
transceivers or install validated transceivers in the wrong Ethernet slot, else damage can occur.
The relay follows a convention with respect to terminal number assignments which are three characters long assigned in
order by module slot position, row number, and column letter. Two-slot wide modules take their slot designation from the
first slot position (nearest to CPU module) which is indicated by an arrow marker on the terminal block. See the following
figure for an example of rear terminal assignments.
The dielectric strength of the UR-series module hardware is shown in the following table:
Table 3–1: DIELECTRIC STRENGTH OF UR-SERIES MODULE HARDWARE
MODULE MODULE FUNCTION TERMINALS DIELECTRIC STRENGTH
TYPE (AC)
FROM TO
1 Power supply High (+); Low (+); (–) Chassis 2000 V AC for 1 minute
1 Power supply 48 V DC (+) and (–) Chassis 2000 V AC for 1 minute
1 Power supply Relay terminals Chassis 2000 V AC for 1 minute
2 Reserved N/A N/A N/A
3 Reserved N/A N/A N/A
4
5
Reserved
Analog inputs/outputs
N/A
All except 8b
N/A
Chassis
N/A
< 50 V DC
3
6 Digital inputs/outputs All Chassis 2000 V AC for 1 minute
G.703 All except 2b, 3a, 7b, 8a Chassis 2000 V AC for 1 minute
7
RS422 All except 6a, 7b, 8a Chassis < 50 V DC
8 CT/VT All Chassis 2000 V AC for 1 minute
9 CPU All Chassis 2000 V AC for 1 minute
Filter networks and transient protection clamps are used in the hardware to prevent damage caused
by high peak voltage transients, radio frequency interference (RFI), and electromagnetic interference
(EMI). These protective components can be damaged by application of the ANSI/IEEE C37.90 spec-
ified test voltage for a period longer than the specified one minute.
Control power supplied to the relay must be connected to the matching power supply range of the
relay. If the voltage is applied to the wrong terminals, damage can occur.
The D60 relay, like almost all electronic relays, contains electrolytic capacitors. These capacitors are
well known to be subject to deterioration over time if voltage is not applied periodically. Deterioration
can be avoided by powering the relays up once a year.
The power supply module can be ordered for two possible voltage ranges, with or without a redundant power option. Each
range has a dedicated input connection for proper operation. The ranges are as shown below (see the Technical specifica-
tions section of chapter 2 for additional details):
• Low (LO) range: 24 to 48 V (DC only) nominal.
• High (HI) range: 125 to 250 V nominal.
The power supply module provides power to the relay and supplies power for dry contact input connections.
The power supply module provides 48 V DC power for dry contact input connections and a critical failure relay (see the
Typical wiring diagram earlier). The critical failure relay is a form-C device that is energized once control power is applied
and the relay has successfully booted up with no critical self-test failures. If on-going self-test diagnostic checks detect a
critical failure (see the Self-test errors section in chapter 7) or control power is lost, the relay is de-energize.
For high reliability systems, the D60 has a redundant option in which two D60 power supplies are placed in parallel on the
bus. If one of the power supplies become faulted, the second power supply assumes the full load of the relay without any
interruptions. Each power supply has a green LED on the front of the module to indicate it is functional. The critical fail relay
of the module also indicates a faulted power supply.
An LED on the front of the control power module shows the status of the power supply:
LED INDICATION POWER SUPPLY
CONTINUOUS ON OK
ON / OFF CYCLING Failure
OFF Failure
A CT/VT module can have voltage inputs on channels 1 through 4 inclusive, or channels 5 through 8 inclusive. Channels 1
and 5 are intended for connection to phase A, and are labeled as such in the relay. Likewise, channels 2 and 6 are intended
for connection to phase B, and channels 3 and 7 are intended for connection to phase C.
Channels 4 and 8 are intended for connection to a single-phase source. For voltage inputs, these channel are labelled as
auxiliary voltage (VX). For current inputs, these channels are intended for connection to a CT between system neutral and
ground, and are labelled as ground current (IG).
Verify that the connection made to the relay nominal current of 1 A or 5 A matches the secondary rat-
ing of the connected CTs. Unmatched CTs may result in equipment damage or inadequate protec-
tion.
CT/VT modules can be ordered with a standard ground current input that is the same as the phase current input. Each AC
current input has an isolating transformer and an automatic shorting mechanism that shorts the input when the module is
withdrawn from the chassis. There are no internal ground connections on the current inputs. Current transformers with 1 to
50000 A primaries and 1 A or 5 A secondaries may be used.
CT/VT modules with a sensitive ground input are also available. The ground CT input of the sensitive ground modules is
ten times more sensitive than the ground CT input of standard CT/VT modules. However, the phase CT inputs and phase
VT inputs are the same as those of regular CT/VT modules.
The above modules are available with enhanced diagnostics. These modules can automatically detect CT/VT hardware
failure and take the relay out of service.
CT connections for both ABC and ACB phase rotations are identical as shown in the Typical wiring diagram.
The exact placement of a zero-sequence core balance CT to detect ground fault current is shown below. Twisted-pair
cabling on the zero-sequence CT is recommended.
NOTE
The D60 can be ordered with a process bus interface module. This module is designed to interface with the GE Multilin
HardFiber system, allowing bidirectional IEC 61850 fiber optic communications with up to eight HardFiber merging units,
known as Bricks. The HardFiber system has been designed to integrate seamlessly with the existing UR-series applica-
tions, including protection functions, FlexLogic, metering, and communications.
The IEC 61850 process bus system offers the following benefits:
• Reduces labor associated with design, installation, and testing of protection and control applications using the D60 by
reducing the number of individual copper terminations
• Integrates seamlessly with existing D60 applications, since the IEC 61850 process bus interface module replaces the
traditional CT/VT modules
• Communicates using open standard IEC 61850 messaging
For additional details on the HardFiber system, see GE publication GEK-113658: HardFiber Process Bus System Instruc-
tion Manual.
Every contact input/output module has 24 terminal connections. They are arranged as three terminals per row, with eight
rows in total. A given row of three terminals can be used for the outputs of one relay. For example, for form-C relay outputs,
the terminals connect to the normally open (NO), normally closed (NC), and common contacts of the relay. For a form-A
output, there are options of using current or voltage detection for feature supervision, depending on the module ordered.
The terminal configuration for contact inputs is different for the two applications.
The contact inputs are grouped with a common return. The D60 has two versions of grouping: four inputs per common
return and two inputs per common return. When a contact input/output module is ordered, four inputs per common is used.
The four inputs per common allows for high-density inputs in combination with outputs, with a compromise of four inputs
sharing one common. If the inputs must be isolated per row, then two inputs per common return should be selected (4D
module).
3 The tables and diagrams on the following pages illustrate the module types (6A, etc.) and contact arrangements that can be
ordered for the relay. Since an entire row is used for a single contact output, the name is assigned using the module slot
position and row number. However, since there are two contact inputs per row, these names are assigned by module slot
position, row number, and column position.
Some form-A / solid-state relay outputs include circuits to monitor the DC voltage across the output contact when it is open,
and the DC current through the output contact when it is closed. Each of the monitors contains a level detector whose out-
put is set to logic “On = 1” when the current in the circuit is above the threshold setting. The voltage monitor is set to “On =
1” when the current is above about 1 to 2.5 mA, and the current monitor is set to “On = 1” when the current exceeds about
80 to 100 mA. The voltage monitor is intended to check the health of the overall trip circuit, and the current monitor can be
used to seal-in the output contact until an external contact has interrupted current flow.
Block diagrams are shown as follows for form-A and solid-state relay outputs with optional voltage monitor, optional current
monitor, and with no monitoring. The actual values shown for contact output 1 are the same for all contact outputs.
,I,GFP$&RQW2S ´,2Qµ
aD aD RWKHUZLVH&RQW2S ´,2IIµ
, , ,I,GFP$&RQW2S ´92Qµ
RWKHUZLVH&RQW2S ´92IIµ
,I,GFP$&RQW2S ´92Qµ
aE aE /RDG
RWKHUZLVH&RQW2S ´92IIµ
9 /RDG 9
aF aF
D 9ROWDJHZLWKRSWLRQDO
9ROWDJHPRQLWRULQJRQO\ %RWKYROWDJHDQGFXUUHQWPRQLWRULQJ
FXUUHQWPRQLWRULQJ
,I,GFP$&RQW2S ´,2Qµ
aD aD RWKHUZLVH&RQW2S ´,2IIµ
9 9 ,I,GFP$&RQW2S ´92Qµ
RWKHUZLVH&RQW2S ´92IIµ
,I,GFP$&RQW2S ´,2Qµ
, aE , aE /RDG
RWKHUZLVH&RQW2S ´,2IIµ
/RDG
aF aF
E &XUUHQWZLWKRSWLRQDO
&XUUHQWPRQLWRULQJRQO\ %RWKYROWDJHDQGFXUUHQWPRQLWRULQJ
YROWDJHPRQLWRULQJ
H[WHUQDOMXPSHUDELVUHTXLUHG
aD
aE
/RDG
aF
F 1RPRQLWRULQJ $&'5
Figure 3–14: FORM-A AND SOLID-STATE CONTACT OUTPUTS WITH VOLTAGE AND CURRENT MONITORING
The operation of voltage and current monitors is reflected with the corresponding FlexLogic operands (CONT OP # VON,
CONT OP # VOFF, and CONT OP # ION) which can be used in protection, control, and alarm logic. The typical application of
the voltage monitor is breaker trip circuit integrity monitoring; a typical application of the current monitor is seal-in of the
control command.
Refer to the Digital elements section of chapter 5 for an example of how form-A and solid-state relay contacts can be
applied for breaker trip circuit integrity monitoring.
Consider relay contacts unsafe to touch when the unit is energized. If the relay contacts need
to be used for low voltage accessible applications, ensure proper insulation levels.
NOTE For form-A and solid-state relay output contacts internally equipped with a voltage measuring circuit across the con-
tact, the circuit has an impedance that can cause a problem when used in conjunction with external high input
impedance monitoring equipment such as modern relay test set trigger circuits. These monitoring circuits may con-
3
tinue to read the form-A contact as being closed after it has closed and subsequently opened, when measured as
an impedance.
The solution is to use the voltage measuring trigger input of the relay test set, and connect the form-A contact
through a voltage-dropping resistor to a DC voltage source. If the 48 V DC output of the power supply is used as a
source, a 500 , 10 W resistor is appropriate. In this configuration, the voltage across either the form-A contact or
the resistor can be used to monitor the state of the output.
Wherever a tilde “~” symbol appears, substitute with the slot position of the module; wherever a number sign “#”
appears, substitute the contact number
NOTE
When current monitoring is used to seal-in the form-A and solid-state relay contact outputs, the Flex-
Logic operand driving the contact output should be given a reset delay of 10 ms to prevent damage
of the output contact (in situations when the element initiating the contact output is bouncing, at val-
ues in the region of the pickup value).
3
~6P MODULE ~6R MODULE ~6S MODULE ~6T MODULE
TERMINAL OUTPUT OR TERMINAL OUTPUT OR TERMINAL OUTPUT OR TERMINAL OUTPUT OR
ASSIGNMENT INPUT ASSIGNMENT INPUT ASSIGNMENT INPUT ASSIGNMENT INPUT
~1 Form-A ~1 Form-A ~1 Form-A ~1 Form-A
~2 Form-A ~2 Form-A ~2 Form-A ~2 Form-A
~3 Form-A ~3 Form-C ~3 Form-C ~3 Form-A
~4 Form-A ~4 Form-C ~4 Form-C ~4 Form-A
~5 Form-A ~5a, ~5c 2 Inputs ~5 Form-C ~5a, ~5c 2 Inputs
~6 Form-A ~6a, ~6c 2 Inputs ~6 Form-C ~6a, ~6c 2 Inputs
~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs
~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs
6K
I I
~ 1b ~1 ~ 5c CONTACT IN ~ 5c ~1 ~ 1b ~ 7c CONTACT IN ~ 7c ~1 ~ 1b
~ 1c ~ 6a CONTACT IN ~ 6a ~ 1c ~ 8a CONTACT IN ~ 8a ~ 1c
~ 2a ~ 6c CONTACT IN ~ 6c V ~ 2a ~ 8c CONTACT IN ~ 8c V ~ 2a
I I
~ 2b ~2 ~ 5b COMMON ~ 5b ~2 ~ 2b ~ 7b COMMON ~ 7b ~2 ~ 2b
~ 2c ~ 2c ~ 2c
~ 7a CONTACT IN ~ 7a ~ 8b SURGE
~ 3a ~ 3a ~ 3a
~ 7c CONTACT IN ~ 7c
~ 3b ~3 ~3 ~ 3b ~3 ~ 3b
~ 8a CONTACT IN ~ 8a
~ 3c ~ 3c ~ 3c
~ 8c CONTACT IN ~ 8c
~ 4a ~ 4a ~ 4a
~ 7b COMMON ~ 7b
~ 4b ~4 ~4 ~ 4b ~4 ~ 4b
~ 4c ~ 8b SURGE ~ 4c ~ 4c
~ 5a ~ 5a
~ 5b ~5 ~5 ~ 5b
~ 5c ~ 5c
~ 6a ~ 6a
~ 6b ~6 ~6 ~ 6b
~ 6c ~ 6c
3
~ 7a
DIGITAL I/O
~ 7b ~7
~ 7c
~ 8a
~ 8b ~8
~ 8c
842763A2.CDR
CONTACT INPUTS
A dry contact has one side connected to terminal B3b. This is the positive 48 V DC voltage rail supplied by the power sup-
ply module. The other side of the dry contact is connected to the required contact input terminal. Each contact input group
has its own common (negative) terminal which must be connected to the DC negative terminal (B3a) of the power supply
module. When a dry contact closes, a current of 1 to 3 mA flows through the associated circuit.
A wet contact has one side connected to the positive terminal of an external DC power supply. The other side of this contact
is connected to the required contact input terminal. If a wet contact is used, then the negative side of the external source
must be connected to the relay common (negative) terminal of each contact group. The maximum external source voltage
for this arrangement is 300 V DC.
The voltage threshold at which each group of four contact inputs detects a closed contact input is programmable as
17 V DC for 24 V sources, 33 V DC for 48 V sources, 84 V DC for 110 to 125 V sources, and 166 V DC for 250 V sources.
NOTE
Contact outputs can be ordered as form-A or form-C. The form-A contacts can be connected for external circuit supervi-
sion. These contacts are provided with voltage and current monitoring circuits used to detect the loss of DC voltage in the
circuit, and the presence of DC current flowing through the contacts when the form-A contact closes. If enabled, the current
monitoring can be used as a seal-in signal to ensure that the form-A contact does not attempt to break the energized induc-
tive coil circuit and weld the output contacts.
There is no provision in the relay to detect a DC ground fault on 48 V DC control power external output. We recom-
mend using an external DC supply.
NOTE
50 to 70 mA
3 mA
time
25 to 50 ms 842749A1.CDR
842751A1.CDR
The auto-burnish circuitry has an internal fuse for safety purposes. During regular maintenance, check the auto-
burnish functionality using an oscilloscope.
NOTE
Transducer input modules can receive input signals from external dcmA output transducers (dcmA In) or resistance tem-
perature detectors (RTD). Hardware and software is provided to receive signals from these external transducers and con-
vert these signals into a digital format for use as required.
Transducer output modules provide DC current outputs in several standard dcmA ranges. Software is provided to configure
virtually any analog quantity used in the relay to drive the analog outputs.
Every transducer input/output module has a total of 24 terminal connections. These connections are arranged as three ter-
minals per row with a total of eight rows. A given row can be used for either inputs or outputs, with terminals in column "a"
having positive polarity and terminals in column "c" having negative polarity. Since an entire row is used for a single input/
output channel, the name of the channel is assigned using the module slot position and row number.
Each module also requires that a connection from an external ground bus be made to terminal 8b. The current outputs
3 require a twisted-pair shielded cable, where the shield is grounded at one end only. The figure below illustrates the trans-
ducer module types (5A, 5C, 5D, 5E, and 5F) and channel arrangements that can be ordered for the relay.
Wherever a tilde “~” symbol appears, substitute with the slot position of the module.
NOTE
A 9-pin RS232C serial port is located on the D60 faceplate for programming with a computer. All that is required to use this
interface is a computer running the EnerVista UR Setup software provided with the relay. Cabling for the RS232 port is
shown in the following figure for both 9-pin and 25-pin connectors.
The baud rate for this port is fixed at 19200 bps.
NOTE
a) OPTIONS
In addition to the faceplate RS232 port, the D60 provides a rear RS485 communication port.
The CPU modules do not require a surge ground connection.
NOTE
b) RS485 PORTS
RS485 data transmission and reception are accomplished over a single twisted pair with transmit and receive data alternat-
ing over the same two wires. Through the use of the port, continuous monitoring and control from a remote computer,
SCADA system, or PLC is possible.
To minimize errors from noise, the use of shielded twisted pair wire is recommended. Correct polarity must also be
observed. For instance, the relays must be connected with all RS485 “+” terminals connected together, and all RS485 “–”
terminals connected together. Though data is transmitted over a two-wire twisted pair, all RS485 devices require a shared
reference, or common voltage. This common voltage is implied to be a power supply common. Some systems allow the
shield (drain wire) to be used as common wire and to connect directly to the D60 COM terminal (#3); others function cor-
rectly only if the common wire is connected to the D60 COM terminal, but insulated from the shield.
To avoid loop currents, ground the shield at only one point. If other system considerations require the shield to be grounded
at more than one point, install resistors (typically 100 ohms) between the shield and ground at each grounding point. Each
relay needs to be daisy-chained to the next one in the link. A maximum of 32 relays can be connected in this manner with-
out exceeding driver capability. For larger systems, additional serial channels must be added. It is also possible to use com-
mercially available repeaters to have more than 32 relays on a single channel. Avoid star or stub connections entirely.
Lightning strikes and ground surge currents can cause large momentary voltage differences between remote ends of the
communication link. For this reason, surge protection devices are internally provided at both communication ports. An iso-
lated power supply with an optocoupled data interface also acts to reduce noise coupling. To ensure maximum reliability, all
equipment should have similar transient protection devices installed.
Terminate both ends of the RS485 circuit with an impedance as shown below.
The fiber optic communication ports allow for fast and efficient communications between relays at 100 Mbps. Optical fiber
can be connected to the relay supporting a wavelength of 1310 nm in multi-mode.
The fiber optic port is designed such that the response times do not vary for any core that is 100 µm or less in diameter,
62.5 µm for 100 Mbps. For optical power budgeting, splices are required every 1 km for the transmitter/receiver pair. When
splicing optical fibers, the diameter and numerical aperture of each fiber must be the same.
3.2.10 IRIG-B
IRIG-B is a standard time code format that allows stamping of events to be synchronized among connected devices within
1 millisecond. The IRIG time code formats are serial, width-modulated codes that can be either DC level shifted or ampli-
tude modulated (AM). Third party equipment is available for generating the IRIG-B signal; this equipment can use a GPS
satellite system to obtain the time reference so that devices at different geographic locations can be synchronized.
NOTE
Using an amplitude modulated receiver also causes errors of up to 1 ms in metered synchrophasor values.
NOTE
The D60 direct inputs and outputs feature makes use of the type 7 series of communications modules, which allow direct
messaging between devices.
The communications channels are normally connected in a ring configuration as shown in the following figure. The trans-
mitter of one module is connected to the receiver of the next module. The transmitter of this second module is then con-
nected to the receiver of the next module in the ring. This is continued to form a communications ring. The figure illustrates
a ring of four UR-series relays with the following connections: UR1-Tx to UR2-Rx, UR2-Tx to UR3-Rx, UR3-Tx to UR4-Rx,
and UR4-Tx to UR1-Rx. A maximum of sixteen (16) UR-series relays can be connected in a single ring
3
Figure 3–27: DIRECT INPUT AND OUTPUT SINGLE/DUAL CHANNEL COMBINATION CONNECTION
The interconnection requirements are described in further detail in this section for each specific variation of type 7 commu-
nications module. These modules are listed in the following table. All fiber modules use ST type connectors.
Not all the direct input and output communications modules may be applicable to the D60 relay. Only the modules
specified in the order codes are available as direct input and output communications modules.
NOTE
The following figure shows the configuration for the 7A, 7B, 7C, 7H, 7I, and 7J fiber-only modules.
3
The following figure shows the configuration for the 72, 73, 7D, and 7K fiber-laser module.
a) DESCRIPTION
The following figure shows the 64K ITU G.703 co-directional interface configuration.
The G.703 module is fixed at 64 kbps. The SETTINGS > PRODUCT SETUP > DIRECT I/O > DIRECT I/O DATA
RATE setting is not applicable to this module.
NOTE
AWG 24 twisted shielded pair is recommended for external connections, with the shield grounded only at one end. Con-
necting the shield to pin X1a or X6a grounds the shield since these pins are internally connected to ground. Thus, if pin X1a
or X6a is used, do not ground at the other end. This interface module is protected by surge suppression devices.
7. Re-insert the G.703 module. Take care to ensure that the correct module type is inserted into the correct slot position.
The ejector/inserter clips located at the top and at the bottom of each module must be in the disengaged position as
the module is smoothly inserted into the slot. Once the clips have cleared the raised edge of the chassis, engage the
clips simultaneously. When the clips have locked into position, the module is fully inserted.
The switch settings for the internal and loop timing modes are shown below:
DMX G7R
842774A1.CDR
DMX G7R
842775A1.CDR
a) DESCRIPTION
There are two RS422 inter-relay communications modules available: single-channel RS422 (module 7T) and dual-channel
RS422 (module 7W). The modules can be configured to run at 64 kbps or 128 kbps. AWG 20-24 twisted shielded pair cable
is recommended for external connections. These modules are protected by optically-isolated surge suppression devices.
The shield pins (6a and 7b) are internally connected to the ground pin (8a). Proper shield termination is as follows:
• Site 1: Terminate shield to pins 6a or 7b or both.
• Site 2: Terminate shield to COM pin 2b.
Match the clock terminating impedance with the impedance of the line.
Single-channel RS422 module Dual-channel RS422 module
~ 3b ~ 3b 3
7W
Tx – Tx –
7T
~ 3a Rx – ~ 3a Rx –
RS422
~ 2a Tx + RS422 ~ 2a Tx +
channel 1
Inter-relay comms.
~ 4b Rx + ~ 4b Rx +
~ 6a Shield ~ 6a Shield
Inter-relay communications
~ 7a ~ 5b Tx –
Clock
~ 8b ~ 5a Rx –
RS422
~ 2b COM ~ 4a Tx +
channel 2
~ 8a Surge ~ 6b Rx +
~ 7b Shield
~ 7a
Clock
~ 8b
~ 2b COM
Data module 1
Signal name
Tx1(+) W 2a SD(A) - Send data
7W
Tx1(-) W 3b SD(B) - Send data
RS422
CHANNEL 1
Rx1(+) W 4b RD(A) - Received data
Rx1(-) W 3a RD(B) - Received data
Shld. W 6a RS(A) - Request to send (RTS)
INTER-RELAY COMMUNICATIONS
+ W 7a RS(B) - Request to send (RTS)
CLOCK
– W 8b RT(A) - Receive timing
Tx2(+) W 4a RT(B) - Receive timing
Tx2(-) W 5b CS(A) - Clear To send
RS422
CHANNEL 2
Rx2(+) W 6b CS(B) - Clear To send
Rx2(-) W 5a Local loopback
Shld. W 7b Remote loopback
com W 2b Signal ground
SURGE W 8a ST(A) - Send timing
3
ST(B) - Send timing
Data module 2
Signal name
TT(A) - Terminal timing
TT(B) - Terminal timing
SD(A) - Send data
SD(B) - Send data
RD(A) - Received data
RD(B) - Received data
RS(A) - Request to send (RTS)
RS(B) - Request to send (RTS)
CS(A) - Clear To send
CS(B) - Clear To send
Local loopback
Remote loopback
Signal ground
ST(A) - Send timing
ST(B) - Send timing
831022A3.CDR
c) TRANSMIT TIMING
The RS422 interface accepts one clock input for transmit timing. It is important that the rising edge of the 64 kHz transmit
timing clock of the multiplexer interface is sampling the data in the center of the transmit data window. Therefore, it is impor-
tant to confirm clock and data transitions to ensure proper system operation. For example, the following figure shows the
positive edge of the Tx clock in the center of the Tx data bit.
Tx Clock
Tx Data
831733A1.CDR
d) RECEIVE TIMING
The RS422 interface utilizes NRZI-MARK modulation code and; therefore, does not rely on an Rx clock to recapture data.
NRZI-MARK is an edge-type, invertible, self-clocking code.
To recover the Rx clock from the data-stream, an integrated DPLL (digital phase lock loop) circuit is utilized. The DPLL is
driven by an internal clock, which is 16-times over-sampled, and uses this clock along with the data-stream to generate a
data clock that can be used as the SCC (serial communication controller) receive clock.
The following figure shows the combined RS422 plus fiberoptic interface configuration at 64K baud. The 7L, 7M, 7N, 7P,
and 74 modules are used in two-terminal with a redundant channel or three-terminal configurations where channel 1 is
employed via the RS422 interface (possibly with a multiplexer) and channel 2 via direct fiber.
AWG 20-24 twisted shielded pair is recommended for external RS422 connections and ground the shield only at one end. 3
For the direct fiber channel, address power budget issues properly.
When using a LASER Interface, attenuators can be necessary to ensure that you do not exceed
maximum optical input power to the receiver.
The figure below shows the combined G.703 plus fiberoptic interface configuration at 64 kbps. The 7E, 7F, 7G, 7Q, and 75
modules are used in configurations where channel 1 is employed via the G.703 interface (possibly with a multiplexer) and
channel 2 via direct fiber. AWG 24 twisted shielded pair is recommended for external G.703 connections connecting the
shield to pin 1a at one end only. For the direct fiber channel, address power budget issues properly. See previous sections
for additional details on the G.703 and fiber interfaces.
When using a laser Interface, attenuators can be necessary to ensure that you do not exceed the
maximum optical input power to the receiver.
The UR-series IEEE C37.94 communication modules (modules types 2G, 2H, 76, and 77) are designed to interface with
IEEE C37.94 compliant digital multiplexers or an IEEE C37.94 compliant interface converter for use with direct input and
output applications. The IEEE C37.94 standard defines a point-to-point optical link for synchronous data between a multi-
plexer and a teleprotection device. This data is typically 64 kbps, but the standard provides for speeds up to 64n kbps,
where n = 1, 2,…, 12. The UR-series C37.94 communication modules are either 64 kbps (with n fixed at 1) for 128 kbps
(with n fixed at 2). The frame is a valid International Telecommunications Union (ITU-T) recommended G.704 pattern from
the standpoint of framing and data rate. The frame is 256 bits and is repeated at a frame rate of 8000 Hz, with a resultant bit
rate of 2048 kbps.
The specifications for the module are as follows:.
• IEEE standard: C37.94 for 1 128 kbps optical fiber interface (for 2G and 2H modules) or C37.94 for 2 64 kbps opti-
cal fiber interface (for 76 and 77 modules)
• Fiber optic cable type: 50 mm or 62.5 mm core diameter optical fiber
• Fiber optic mode: multi-mode
• Fiber optic cable length: up to 2 km
• Fiber optic connector: type ST
• Wavelength: 830 ±40 nm
• Connection: as per all fiber optic connections, a Tx to Rx connection is required
The UR-series C37.94 communication module can be connected directly to any compliant digital multiplexer that supports
the IEEE C37.94 standard as shown below.
The UR-series C37.94 communication module can be connected to the electrical interface (G.703, RS422, or X.21) of a
non-compliant digital multiplexer via an optical-to-electrical interface converter that supports the IEEE C37.94 standard, as
shown below.
The UR-series C37.94 communication module has six switches that are used to set the clock configuration. The functions
of these control switches are shown below.
3
For the internal timing mode, the system clock is generated internally. Therefore, the timing switch selection should be
internal timing for relay 1 and loop timed for relay 2. There must be only one timing source configured.
For the looped timing mode, the system clock is derived from the received line signal. Therefore, the timing selection
should be in loop timing mode for connections to higher order systems.
The IEEE C37.94 communications module cover removal procedure is as follows:
1. With power to the relay off, remove the IEEE C37.94 module (type 2G, 2H, 76 or 77 module) as follows. Record the
original location of the module to help ensure that the same or replacement module is inserted into the correct slot.
2. Simultaneously pull the ejector/inserter clips located at the top and at the bottom of each module in order to release the
module for removal.
3. Remove the module cover screw.
4. Remove the top cover by sliding it towards the rear and then lift it upwards.
5. Set the timing selection switches (channel 1, channel 2) to the desired timing modes (see description above).
6. Replace the top cover and the cover screw.
7. Re-insert the IEEE C37.94 module. Take care to ensure that the correct module type is inserted into the correct slot
position. The ejector/inserter clips located at the top and at the bottom of each module must be in the disengaged posi-
tion as the module is smoothly inserted into the slot. Once the clips have cleared the raised edge of the chassis,
engage the clips simultaneously. When the clips have locked into position, the module is fully inserted.
Modules shipped since January 2012 have status LEDs that indicate the status of the DIP switches, as shown in the follow-
ing figure.
The UR-series C37.94SM communication modules (2A and 2B) are designed to interface with modified IEEE C37.94 com-
pliant digital multiplexers or IEEE C37.94 compliant interface converters that have been converted from 820 nm multi-mode
fiber optics to 1300 nm ELED single-mode fiber optics. The IEEE C37.94 standard defines a point-to-point optical link for
synchronous data between a multiplexer and a teleprotection device. This data is typically 64 kbps, but the standard pro-
vides for speeds up to 64n kbps, where n = 1, 2,…, 12. The UR-series C37.94SM communication module is 64 kbps only
with n fixed at 1. The frame is a valid International Telecommunications Union (ITU-T) recommended G.704 pattern from
the standpoint of framing and data rate. The frame is 256 bits and is repeated at a frame rate of 8000 Hz, with a resultant bit
rate of 2048 kbps.
The specifications for the module are as follows:
• Emulated IEEE standard: emulates C37.94 for 1 64 kbps optical fiber interface (modules set to n = 1 or 64 kbps)
3 • Fiber optic cable type: 9/125 m core diameter optical fiber
• Fiber optic mode: single-mode, ELED compatible with HP HFBR-1315T transmitter and HP HFBR-2316T receiver
• Fiber optic cable length: up to 11.4 km
• Fiber optic connector: type ST
• Wavelength: 1300 ±40 nm
• Connection: as per all fiber optic connections, a Tx to Rx connection is required
The UR-series C37.94SM communication module can be connected directly to any compliant digital multiplexer that sup-
ports C37.94SM as shown below.
It can also can be connected directly to any other UR-series relay with a C37.94SM module as shown below.
The UR-series C37.94SM communication module has six switches that are used to set the clock configuration. The func-
tions of these control switches are shown below.
For the internal timing mode, the system clock is generated internally. Therefore, the timing switch selection should be
internal timing for relay 1 and loop timed for relay 2. There must be only one timing source configured.
For the looped timing mode, the system clock is derived from the received line signal. Therefore, the timing selection
should be in loop timing mode for connections to higher order systems.
The C37.94SM communications module cover removal procedure is as follows:
1. With power to the relay off, remove the C37.94SM module (modules 2A or 2B) as follows. Record the original location
of the module to help ensure that the same or replacement module is inserted into the correct slot.
2. Simultaneously pull the ejector/inserter clips located at the top and at the bottom of each module in order to release the
module for removal.
3. Remove the module cover screw.
4. Remove the top cover by sliding it towards the rear and then lift it upwards.
5. Set the timing selection switches (channel 1, channel 2) to the desired timing modes (see description above).
6.
7.
Replace the top cover and the cover screw.
Re-insert the C37.94SM module. Take care to ensure that the correct module type is inserted into the correct slot
3
position. The ejector/inserter clips located at the top and at the bottom of each module must be in the disengaged posi-
tion as the module is smoothly inserted into the slot. Once the clips have cleared the raised edge of the chassis,
engage the clips simultaneously. When the clips have locked into position, the module is fully inserted.
Modules shipped since January 2012 have status LEDs that indicate the status of the DIP switches, as shown in the follow-
ing figure.
The EnerVista UR Setup software provides a graphical user interface (GUI) as one of two human interfaces to a UR device.
The alternate human interface is implemented via the device’s faceplate keypad and display (see the Faceplate interface
section in this chapter).
The EnerVista UR Setup software provides a single facility to configure, monitor, maintain, and troubleshoot the operation
of relay functions, connected over local or wide area communication networks. It can be used while disconnected (offline)
or connected (online) to a UR device. In offline mode, settings files can be created for eventual downloading to the device.
In online mode, you can communicate with the device in real-time.
The EnerVista UR Setup software is provided with every D60 relay and runs on Microsoft Windows XP, 7, and Server 2008.
This chapter provides a summary of the basic EnerVista UR Setup software interface features. The EnerVista UR Setup
Help File provides details for getting started and using the EnerVista UR Setup software interface.
To start using the EnerVista UR Setup software, site and device definition are required. See the EnerVista UR Setup Help
File or refer to the Connecting EnerVista UR Setup with the D60 section in Chapter 1 for details.
IP Address
IP Subnet Mask
IEC61850 Config GOOSE ConfRev
IP Routing
When a settings file is loaded to a D60 that is in-service, the following sequence occurs:
1. The D60 takes itself out of service.
2. The D60 issues a UNIT NOT PROGRAMMED major self-test error.
3. The D60 closes the critical fail contact.
f) FILE SUPPORT
• Execution: Any EnerVista UR Setup file that is opened launches the application or provides focus to the already
opened application. If the file was a settings file (has a URS extension) that had been removed from the Settings List
tree menu, it is added back to the Settings List tree menu.
• Drag and Drop: The Site List and Settings List control bar windows are each mutually a drag source and a drop target
for device-order-code-compatible files or individual menu items. Also, the Settings List control bar window and any
Windows Explorer directory folder are each mutually a file drag source and drop target.
New files that are dropped into the Settings List window are added to the tree, which is automatically sorted alphabeti-
cally with respect to settings file names. Files or individual menu items that are dropped in the selected device menu in
the Site List window are automatically sent to the online communicating device.
g) FIRMWARE UPGRADES
The firmware of a D60 device can be upgraded, locally or remotely, via the EnerVista UR Setup software. The correspond-
ing instructions are provided by the EnerVista UR Setup Help file under the topic “Upgrading Firmware”.
Modbus addresses assigned to firmware modules, features, settings, and corresponding data items (that is, default
values, minimum/maximum values, data type, and item size) can change slightly from version to version of firm-
NOTE
ware. The addresses are rearranged when new features are added or existing features are enhanced or modified.
The EEPROM DATA ERROR message displayed after upgrading/downgrading the firmware is a resettable, self-test
message intended to inform users that the Modbus addresses have changed with the upgraded firmware. This
message does not signal any problems when appearing after firmware upgrades.
The EnerVista UR Setup software main window supports the following primary display components:
1. Title bar that shows the pathname of the active data view
2. Main window menu bar
3. Main window tool bar
4. Site list control bar window
5. Settings list control bar window
6. Device data view windows, with common tool bar
7. Settings file data view windows, with common tool bar
8. Workspace area with data view tabs
9. Status bar
10. Quick action hot links
2 1 6 7 4
10
4
9 8 842786A2.CDR
Setting file templates simplify the configuration and commissioning of multiple relays that protect similar assets. An exam-
ple of this is a substation that has ten similar feeders protected by ten UR-series F60 relays.
In these situations, typically 90% or greater of the settings are identical between all devices. The templates feature allows
engineers to configure and test these common settings, then lock them so that they are not available to users. For exam-
ple, these locked down settings can be hidden from view for field engineers, allowing them to quickly identify and concen-
trate on the specific settings.
The remaining settings (typically 10% or less) can be specified as editable and be made available to field engineers install-
ing the devices. These are settings such as protection element pickup values and CT and VT ratios.
The settings template mode allows the user to define which settings are visible in EnerVista UR Setup. Settings templates
can be applied to both settings files (settings file templates) and online devices (online settings templates). The functionality
is identical for both purposes.
Settings files conversion from previous firmware versions is supported.
The software prompts for a template password. This password is required to use the template feature and must be at
least four characters in length.
3. Enter and re-enter the new password, then click OK to continue.
The online settings template is now enabled. The device is now in template editing mode.
By default, all settings are specified as locked and displayed against a grey background. The icon on the upper right of
the settings window also indicates that EnerVista UR Setup is in EDIT mode. The following example shows the phase
time overcurrent settings window in edit mode.
The software prompts for a template password. This password must be at least four characters in length.
Figure 4–4: APPLYING TEMPLATES VIA THE VIEW IN TEMPLATE MODE COMMAND
Viewing the settings in template mode also modifies the settings tree, showing only the settings categories that contain
editable settings. The effect of applying the template to a typical settings tree view is shown below.
Typical settings tree view without template applied. Typical settings tree view with template applied via
the Template Mode > View In Template Mode
command.
842860A1.CDR
Figure 4–5: APPLYING TEMPLATES VIA THE VIEW IN TEMPLATE MODE SETTINGS COMMAND
Use the following procedure to display settings available for editing and settings locked by the template. 4
1. Select an installed device or a settings file from the tree menu on the left of the EnerVista UR Setup main screen.
2. Apply the template by selecting the Template Mode > View All Settings option.
3. Enter the template password then click OK to apply the template.
Once the template has been applied, users are limited to edit the settings specified by the template, but all settings are
shown. The effect of applying the template to the phase time overcurrent settings is shown below.
Phase time overcurrent settings window without template applied. Phase time overcurrent window with template applied via
the Template Mode > View All Settings command.
The template specifies that only the Pickup and Curve
settings be available.
842859A1.CDR
Figure 4–6: APPLYING TEMPLATES VIA THE VIEW ALL SETTINGS COMMAND
4. Verify one more time that you want to remove the template by clicking Yes.
The EnerVista software removes all template information and all settings are available.
The UR allows users to secure parts or all of a FlexLogic equation, preventing unauthorized viewing or modification of criti-
cal FlexLogic applications. This is accomplished using the settings template feature to lock individual entries within Flex-
Logic equations.
Secured FlexLogic equations remain secure when files are sent to and retrieved from any UR-series device.
4 The following procedure describes how to lock individual entries of a FlexLogic equation.
1. Right-click the settings file or online device and select the Template Mode > Create Template item to enable the set-
tings template feature.
2. Select the FlexLogic > FlexLogic Equation Editor settings menu item.
By default, all FlexLogic entries are specified as viewable and displayed against a yellow background. The icon on the
upper right of the window also indicates that EnerVista UR Setup is in EDIT mode.
3. Specify which entries to lock by clicking on them.
The locked entries are displayed against a grey background as shown in the example below.
Once the template has been applied, users are limited to view and edit the FlexLogic entries not locked by the template.
The effect of applying the template to the FlexLogic entries in the above procedure is shown below.
Typical FlexLogic™ entries without template applied. Typical FlexLogic™ entries locked with template via
the Template Mode > View In Template Mode command.
842861A1.CDR
4 3. Enter the serial number of the D60 device to lock to the settings file in the Serial # Lock field.
The settings file and corresponding secure FlexLogic equations are now locked to the D60 device specified by the serial
number.
A traceability feature for settings files allows the user to quickly determine if the settings in a D60 device have been
changed since the time of installation from a settings file. When a settings file is transferred to a D60 device, the date, time,
and serial number of the D60 are sent back to EnerVista UR Setup and added to the settings file on the local PC. This infor-
mation can be compared with the D60 actual values at any later date to determine if security has been compromised.
The traceability information is only included in the settings file if a complete settings file is either transferred to the D60
device or obtained from the D60 device. Any partial settings transfers by way of drag and drop do not add the traceability
information to the settings file.
1. The transfer date of a setting file written to a D60 is logged in the relay and can be viewed via EnerVista UR Setup or
the front panel display. Likewise, the transfer date of a setting file saved to a local PC is logged in EnerVista UR Setup.
2. Comparing the dates stored in the relay and on the settings file at any time in the future indicates if any changes have
been made to the relay configuration since the settings file was saved.
4
842863A1.CDR
Traceability data
in settings report
842862A1.CDR
842865A1.CDR
a) ENHANCED FACEPLATE
The front panel interface is one of two supported interfaces, the other interface being EnerVista UR Setup software. The
front panel interface consists of LED panels, an RS232 port, keypad, LCD display, control pushbuttons, and optional user-
programmable pushbuttons.
The faceplate is hinged to allow easy access to the removable modules.
Display
Keypad
4
Front panel
RS232 port
b) STANDARD FACEPLATE
There are two interfaces: the front panel and the EnerVista UR Setup software. The front panel interface consists of LED
panels, an RS232 port, keypad, LCD display, control pushbuttons, and optional user-programmable pushbuttons.
The faceplate is hinged to allow easy access to the removable modules. There is also a removable dust cover that fits over
the faceplate that must be removed in order to access the keypad panel. The following figure shows the horizontal arrange-
ment of the faceplate panels.
Display
Front panel
RS232 port
The following figure shows the vertical arrangement of the faceplate panels for relays ordered with the vertical option.
a) ENHANCED FACEPLATE
The enhanced front panel display provides five columns of LED indicators. The first column contains 14 status and event
cause LEDs, and the next four columns contain the 48 user-programmable LEDs.
The RESET key is used to reset any latched LED indicator or target message, once the condition has been cleared (these
latched conditions can also be reset via the SETTINGS INPUT/OUTPUTS RESETTING menu). The RS232 port is
intended for connection to a portable PC.
The USER keys are used by the breaker control feature.
842811A1.CDR
• TROUBLE: This LED indicates that the relay has detected an internal problem.
• TEST MODE: This LED indicates that the relay is in test mode.
• TRIP: This LED indicates that the FlexLogic operand serving as a trip switch has operated. This indicator always
latches; as such, a reset command must be initiated to allow the latch to be reset.
• ALARM: This LED indicates that the FlexLogic operand serving as an alarm switch has operated. This indicator is
never latched.
• PICKUP: This LED indicates that an element is picked up. This indicator is never latched.
The event cause indicators in the first column are described below.
Events cause LEDs are turned on or off by protection elements that have their respective target setting selected as either
“Enabled” or “Latched”. If a protection element target setting is “Enabled”, then the corresponding event cause LEDs
remain on as long as operate operand associated with the element remains asserted. If a protection element target setting
is “Latched”, then the corresponding event cause LEDs turn on when the operate operand associated with the element is
asserted and remain on until the RESET button on the front panel is pressed after the operand is reset.
All elements that are able to discriminate faulted phases can independently turn off or on the phase A, B or C LEDs. This
includes phase instantaneous overcurrent, phase undervoltage, etc. This means that the phase A, B, and C operate oper-
ands for individual protection elements are ORed to turn on or off the phase A, B or C LEDs.
• VOLTAGE: This LED indicates voltage was involved. 4
• CURRENT: This LED indicates current was involved.
• FREQUENCY: This LED indicates frequency was involved.
• OTHER: This LED indicates a composite function was involved.
• PHASE A: This LED indicates phase A was involved.
• PHASE B: This LED indicates phase B was involved.
• PHASE C: This LED indicates phase C was involved.
• NEUTRAL/GROUND: This LED indicates that neutral or ground was involved.
The user-programmable LEDs consist of 48 amber LED indicators in four columns. The operation of these LEDs is user-
defined. Support for applying a customized label beside every LED is provided. Default labels are shipped in the label pack-
age of every D60, together with custom templates. The default labels can be replaced by user-printed labels.
User customization of LED operation is of maximum benefit in installations where languages other than English are used to
communicate with operators. Refer to the User-programmable LEDs section in chapter 5 for the settings used to program
the operation of the LEDs on these panels.
b) STANDARD FACEPLATE
The standard faceplate consists of three panels with LED indicators, keys, and a communications port. The RESET key is
used to reset any latched LED indicator or target message, once the condition has been cleared (these latched conditions
can also be reset via the SETTINGS INPUT/OUTPUTS RESETTING menu). The RS232 port is for connection to a com-
puter.
The USER keys are used by the breaker control feature.
842781A1.CDR
STATUS INDICATORS:
• IN SERVICE: Indicates that control power is applied; all monitored inputs/outputs and internal systems are OK; the
relay has been programmed.
• TROUBLE: Indicates that the relay has detected an internal problem.
• TEST MODE: Indicates that the relay is in test mode.
• TRIP: Indicates that the selected FlexLogic operand serving as a Trip switch has operated. This indicator always
latches; the reset command must be initiated to allow the latch to be reset.
• ALARM: Indicates that the selected FlexLogic operand serving as an Alarm switch has operated. This indicator is
never latched.
• PICKUP: Indicates that an element is picked up. This indicator is never latched.
EVENT CAUSE INDICATORS:
Events cause LEDs are turned on or off by protection elements that have their respective target setting selected as either
“Enabled” or “Latched”. If a protection element target setting is “Enabled”, then the corresponding event cause LEDs
remain on as long as operate operand associated with the element remains asserted. If a protection element target setting
is “Latched”, then the corresponding event cause LEDs turn on when the operate operand associated with the element is
asserted and remain on until the RESET button on the front panel is pressed after the operand is reset.
4 All elements that are able to discriminate faulted phases can independently turn off or on the phase A, B or C LEDs. This
includes phase instantaneous overcurrent, phase undervoltage, etc. This means that the phase A, B, and C operate oper-
ands for individual protection elements are ORed to turn on or off the phase A, B or C LEDs.
• VOLTAGE: Indicates voltage was involved.
• CURRENT: Indicates current was involved.
• FREQUENCY: Indicates frequency was involved.
• OTHER: Indicates a composite function was involved.
• PHASE A: Indicates phase A was involved.
• PHASE B: Indicates phase B was involved.
• PHASE C: Indicates phase C was involved.
• NEUTRAL/GROUND: Indicates that neutral or ground was involved.
USER-PROGRAMMABLE INDICATORS:
The second and third provide 48 amber LED indicators whose operation is controlled by the user. Support for applying a
customized label beside every LED is provided.
User customization of LED operation is of maximum benefit in installations where languages other than English are used to
communicate with operators. Refer to the User-programmable LEDs section in chapter 5 for the settings used to program
the operation of the LEDs on these panels.
842782A1.CDR
842784A1.CDR
a) ENHANCED FACEPLATE
The following procedure requires these pre-requisites:
• EnerVista UR Setup software is installed and operational
• The D60 settings have been saved to a settings file
• The D60 front panel label cutout sheet (GE Multilin part number 1006-0047) has been downloaded from
http://www.gedigitalenergy.com/products/support/ur/URLEDenhanced.doc and printed
• Small-bladed knife
To create custom LED labels for the enhanced front panel display:
1. Start the EnerVista UR Setup software.
2. Select the Front Panel Report item at the bottom of the menu tree for the settings file. The front panel report window
displays.
4
Figure 4–22: FRONT PANEL REPORT WINDOW
3. Enter the text to appear next to each LED and above each user-programmable pushbuttons in the fields provided.
4. Feed the D60 front panel label cutout sheet into a printer and press the Print button in the front panel report window.
5. When printing is complete, fold the sheet along the perforated lines and punch out the labels.
6. Remove the D60 label insert tool from the package and bend the tabs as described in the following procedures. These
tabs are used for removal of the default and custom LED labels.
It is important that the tool be used EXACTLY as shown below, with the printed side containing the GE part number
facing the user.
NOTE
The label package shipped with every D60 contains the three default labels shown below, the custom label template sheet,
and the label removal tool.
If the default labels are suitable for your application, insert them in the appropriate slots and program the LEDs to match
them. If you require custom labels, follow the procedures below to remove the original labels and insert the new ones.
The following procedure describes how to setup and use the label removal tool.
1. Bend the tabs at the left end of the tool upwards as shown below.
2. Bend the tab at the center of the tool tail as shown below.
The following procedure describes how to remove the LED labels from the D60 enhanced front panel and insert the custom
labels.
1. Use the knife to lift the LED label and slide the label tool underneath. Make sure the bent tabs are pointing away from
the relay.
4
2. Slide the label tool under the LED label until the tabs snap out as shown below. This attaches the label tool to the LED
label.
4. Slide the new LED label inside the pocket until the text is properly aligned with the LEDs, as shown below.
The following procedure describes how to remove the user-programmable pushbutton labels from the D60 enhanced front
panel and insert the custom labels.
1. Use the knife to lift the pushbutton label and slide the tail of the label tool underneath, as shown below. Make sure the
bent tab is pointing away from the relay.
2. Slide the label tool under the user-programmable pushbutton label until the tabs snap out as shown below. This
attaches the label tool to the user-programmable pushbutton label.
3. Remove the tool and attached user-programmable pushbutton label as shown below.
4
4. Slide the new user-programmable pushbutton label inside the pocket until the text is properly aligned with the buttons,
as shown below.
b) STANDARD FACEPLATE
Custom labeling of an LED-only panel is facilitated through a Microsoft Word file available from the following URL:
http://www.gedigitalenergy.com/products/support/ur/GET-8494A.doc
This file provides templates and instructions for creating appropriate labeling for the LED panel. The following procedures
are contained in the downloadable file. The panel templates provide relative LED locations and located example text (x)
edit boxes. The following procedure demonstrates how to install/uninstall the custom panel labeling.
1. Remove the clear Lexan Front Cover (GE Multilin part number: 1501-0014).
Push in
and gently lift
up the cover.
842771A1.CDR
2. Pop out the LED module and/or the blank module with a screwdriver as shown below. Be careful not to damage the
plastic covers.
F60
R
842722A1.CDR
3. Place the left side of the customized module back to the front panel frame, then snap back the right side.
4. Put the clear Lexan front cover back into place.
The following items are required to customize the D60 display module:
• Black and white or color printer (color preferred)
• Microsoft Word 97 or later software for editing the template
• 1 each of: 8.5" x 11" white paper, exacto knife, ruler, custom display module (GE Multilin Part Number: 1516-0069),
and a custom module cover (GE Multilin Part Number: 1502-0015)
The following procedure describes how to customize the D60 display module:
1. Open the LED panel customization template with Microsoft Word. Add text in places of the LED x text placeholders on
the template(s). Delete unused place holders as required.
2. When complete, save the Word file to your computer for future use.
3. Print the template(s) to a local printer.
4. From the printout, cut-out the Background Template from the three windows, using the cropmarks as a guide.
5. Put the Background Template on top of the custom display module (GE Multilin Part Number: 1513-0069) and snap the
clear custom module cover (GE Multilin Part Number: 1502-0015) over it and the templates.
4.3.4 DISPLAY
All messages are displayed on a backlit liquid crystal display (LCD) to make them visible under poor lighting conditions.
4
While the keypad and display are not actively being used, the display defaults to user-defined messages. Any high-priority
event-driven message automatically overrides the default message and appears on the display.
4.3.5 KEYPAD
Display messages are organized into pages under the following headings: actual values, settings, commands, and targets.
The MENU key navigates through these pages. Each heading page is divided further into logical subgroups.
The MESSAGE keys navigate through the subgroups. The VALUE keys increment or decrement numerical setting values
when in programming mode. These keys also scroll through alphanumeric values in the text edit mode. Alternatively, val-
ues can be entered with the numeric keypad.
The decimal key initiates and advances to the next character in text edit mode or enters a decimal point.
The HELP key can be pressed at any time for context-sensitive help messages.
The ENTER key stores altered setting values.
a) INTRODUCTION
The D60 can interface with associated circuit breakers. In many cases the application monitors the state of the breaker, that
can be presented on faceplate LEDs, along with a breaker trouble indication. Breaker operations can be manually initiated
from faceplate keypad or automatically initiated from a FlexLogic operand. A setting is provided to assign names to each
breaker; this user-assigned name is used for the display of related flash messages. These features are provided for two
breakers; the user can use only those portions of the design relevant to a single breaker, which must be breaker 1.
For the following discussion it is assumed the SETTINGS SYSTEM SETUP BREAKERS BREAKER 1(2) BREAKER
FUNCTION setting is "Enabled" for each breaker.
The D60 has features required for single-pole operation. Inputs that trip individual breaker poles and cause a breaker
reclose are passed directly to this element.
ENTER COMMAND This message appears when the USER 1, USER 2, or USER 3 key is pressed and a
PASSWORD COMMAND PASSWORD is required; i.e. if COMMAND PASSWORD is enabled and no com-
mands have been issued within the last 30 minutes.
Press USER 1 This message appears if the correct password is entered or if none is required. This mes-
4 To Select Breaker sage displays for 30 seconds or until the USER 1 key is pressed again.
BKR1-(Name) SELECTED This message is displayed after the USER 1 key is pressed for the second time. Three
USER 2=CLS/USER 3=OP possible actions can be performed from this state within 30 seconds as per items (1), (2)
and (3) below:
(1)
USER 2 OFF/ON If the USER 2 key is pressed, this message appears for 20 seconds. If the USER 2 key is
To Close BKR1-(Name) pressed again within that time, a signal is created that can be programmed to operate an
output relay to close breaker 1.
(2)
USER 3 OFF/ON If the USER 3 key is pressed, this message appears for 20 seconds. If the USER 3 key is
To Open BKR1-(Name) pressed again within that time, a signal is created that can be programmed to operate an
output relay to open breaker 1.
(3)
BKR2-(Name) SELECTED If the USER 1 key is pressed at this step, this message appears showing that a different
USER 2=CLS/USER 3=OP breaker is selected. Three possible actions can be performed from this state as per (1),
(2) and (3). Repeatedly pressing the USER 1 key alternates between available breakers.
Pressing keys other than USER 1, 2, or 3 at any time aborts the breaker control function.
4.3.7 MENUS
a) NAVIGATION
Press the MENU key to select a header display page (top-level menu). The header title appears momentarily followed by a
header display page menu item. Each press of the MENU key advances through the following main heading pages:
• Actual values
• Settings
• Commands
• Targets
• User displays (when enabled)
b) HIERARCHY
The setting and actual value messages are arranged hierarchically. The header display pages are indicated by double
scroll bar characters (), while sub-header pages are indicated by single scroll bar characters (). The header display
pages represent the highest level of the hierarchy and the sub-header display pages fall below this level. The MESSAGE
UP and DOWN keys move within a group of headers, sub-headers, setting values, or actual values. Continually pressing
the MESSAGE RIGHT key from a header display displays specific information for the header category. Conversely, contin-
ually pressing the MESSAGE LEFT key from a setting value or actual value display returns to the header display.
SETTINGS
SYSTEM SETUP
SETTINGS Press the MESSAGE DOWN key to move to the next Settings page. This page con-
SYSTEM SETUP tains settings for System Setup. Repeatedly press the MESSAGE UP and DOWN
keys to display the other setting headers and then back to the first Settings page
header.
PASSWORD From the Settings page one header (Product Setup), press the MESSAGE RIGHT
SECURITY key once to display the first sub-header (Password Security).
ACCESS LEVEL: Press the MESSAGE RIGHT key once more and this will display the first setting for
Restricted Password Security. Pressing the MESSAGE DOWN key repeatedly will display the
remaining setting messages for this sub-header.
PASSWORD Press the MESSAGE LEFT key once to move back to the first sub-header message.
SECURITY
DISPLAY Pressing the MESSAGE DOWN key displays the second setting sub-header associ-
PROPERTIES ated with the Product Setup header.
FLASH MESSAGE Press the MESSAGE RIGHT key once more to display the first setting for Display
TIME: 1.0 s Properties.
DEFAULT MESSAGE To view the remaining settings associated with the Display Properties subheader,
INTENSITY: 25% repeatedly press the MESSAGE DOWN key. The last message appears as shown.
FLASH MESSAGE For example, select the SETTINGS PRODUCT SETUP DISPLAY PROPERTIES FLASH
TIME: 1.0 s MESSAGE TIME setting.
MINIMUM: 0.5 Press the HELP key to view the minimum and maximum values. Press the HELP key
MAXIMUM: 10.0 again to view the next context sensitive help message.
Two methods of editing and storing a numerical setting value are available.
• 0 to 9 and decimal point: The relay numeric keypad works the same as that of any electronic calculator. A number is
entered one digit at a time. The leftmost digit is entered first and the rightmost digit is entered last. Pressing the MES-
SAGE LEFT key or pressing the ESCAPE key, returns the original value to the display.
• VALUE keys: The VALUE UP key increments the displayed value by the step value, up to the maximum value allowed.
4 While at the maximum value, pressing the VALUE UP key again allows the setting selection to continue upward from
the minimum value. The VALUE DOWN key decrements the displayed value by the step value, down to the minimum
value. While at the minimum value, pressing the VALUE DOWN key again allows the setting selection to continue
downward from the maximum value.
FLASH MESSAGE As an example, set the flash message time setting to 2.5 seconds. Press the appropriate
TIME: 2.5 s numeric keys in the sequence “2 . 5". The display message changes as the digits are
being entered.
NEW SETTING Until ENTER is pressed, editing changes are not registered by the relay. Therefore, press
HAS BEEN STORED ENTER to store the new value in memory. This flash message momentarily appears as
confirmation of the storing process. Numerical values which contain decimal places are
rounded-off if more decimal place digits are entered than specified by the step value.
ACCESS LEVEL: For example, the selections available for ACCESS LEVEL are "Restricted", "Command",
Restricted "Setting", and "Factory Service".
Enumeration type values are changed using the VALUE keys. The VALUE UP key displays the next selection while the
VALUE DOWN key displays the previous selection.
ACCESS LEVEL: If the ACCESS LEVEL needs to be "Setting", press the VALUE keys until the proper selec-
Setting tion is displayed. Press HELP at any time for the context sensitive help messages.
NEW SETTING Changes are not registered by the relay until the ENTER key is pressed. Pressing
HAS BEEN STORED ENTER stores the new value in memory. This flash message momentarily appears as
confirmation of the storing process.
There are several places where text messages can be programmed to allow the relay to be customized for specific applica-
tions. One example is the Message Scratchpad. Use the following procedure to enter alphanumeric text messages.
For example: to enter the text, “Breaker #1”.
1. Press the decimal point to enter text edit mode.
2. Press the VALUE keys until the character 'B' appears; press the decimal key to advance the cursor to the next position.
3. Repeat step 2 for the remaining characters: r,e,a,k,e,r, ,#,1.
4. Press ENTER to store the text.
5. If you have any problem, press HELP to view context sensitive help. Flash messages appear sequentially for several
seconds each. For the case of a text setting message, pressing HELP displays how to edit and store new values.
RELAY SETTINGS: When the relay is powered up, the Trouble LED is on, the In Service LED off, and this
Not Programmed message displayed, indicating the relay is in the "Not Programmed" state and is safe-
guarding (output relays blocked) against the installation of a relay whose settings have
not been entered. This message remains until the relay is explicitly put in the "Pro-
grammed" state.
4
To change the RELAY SETTINGS: "Not Programmed" mode to "Programmed", proceed as follows:
1. Press the MENU key until the SETTINGS header flashes momentarily and the PRODUCT SETUP message appears on the
display.
2. Press the MESSAGE RIGHT key until the PASSWORD SECURITY message appears on the display.
3. Press the MESSAGE DOWN key until the INSTALLATION message appears on the display.
4. Press the MESSAGE RIGHT key until the RELAY SETTINGS: Not Programmed message is displayed.
SETTINGS
SETTINGS PASSWORD
PRODUCT SETUP SECURITY
DISPLAY
PROPERTIES
5. After the RELAY SETTINGS: Not Programmed message appears on the display, press the VALUE keys change the
selection to "Programmed".
6. Press the ENTER key.
7. When the "NEW SETTING HAS BEEN STORED" message appears, the relay is in "Programmed" state and the In
Service LED turns on.
5. After the CHANGE...PASSWORD message appears on the display, press the VALUE UP or DOWN key to change the
selection to “Yes”.
6. Press the ENTER key and the display prompts you to ENTER NEW PASSWORD.
7. Type in a numerical password (up to 10 characters) and press the ENTER key.
8. When the VERIFY NEW PASSWORD is displayed, re-type in the same password and press ENTER.
CHANGE SETTING
PASSWORD: No
NEW PASSWORD
HAS BEEN STORED
9. When the NEW PASSWORD HAS BEEN STORED message appears, your new Setting (or Command) Password will be
active.
In the event that an incorrect Command or Setting password has been entered via the any external communications inter-
face three times within a three-minute time span, the REMOTE ACCESS DENIED FlexLogic operand is set to “On” and the
D60 does not allow Settings or Command access via the any external communications interface for the next ten minutes.
The REMOTE ACCESS DENIED FlexLogic operand is set to “Off” after the expiration of the ten-minute timeout.
SETTINGS SECURITY
See page 5-8.
PRODUCT SETUP
DISPLAY
See page 5-23.
PROPERTIES
CLEAR RELAY
See page 5-25.
RECORDS
COMMUNICATIONS
See page 5-26.
MODBUS USER MAP
See page 5-55.
REAL TIME
See page 5-56.
CLOCK
FAULT REPORTS
See page 5-60.
OSCILLOGRAPHY
See page 5-62.
DATA LOGGER
See page 5-64.
5
USER-PROGRAMMABLE
See page 5-66.
LEDS
USER-PROGRAMMABLE
See page 5-69.
SELF TESTS
CONTROL
See page 5-69.
PUSHBUTTONS
USER-PROGRAMMABLE
See page 5-71.
PUSHBUTTONS
FLEX STATE
See page 5-76.
PARAMETERS
USER-DEFINABLE
See page 5-77.
DISPLAYS
DIRECT I/O
See page 5-79.
TELEPROTECTION
See page 5-87.
INSTALLATION
See page 5-87.
SETTINGS AC INPUTS
See page 5-90.
SYSTEM SETUP
POWER SYSTEM
See page 5-91.
SIGNAL SOURCES
See page 5-92.
BREAKERS
See page 5-95.
SWITCHES
See page 5-99.
FLEXCURVES
See page 5-102.
PHASOR MEASUREMENT
See page 5-109.
UNIT
SETTINGS FLEXLOGIC
See page 5-149.
FLEXLOGIC EQUATION EDITOR
FLEXLOGIC
See page 5-149.
TIMERS
FLEXELEMENTS
See page 5-150.
NON-VOLATILE
See page 5-154.
LATCHES
SETTING GROUP 6
DIGITAL ELEMENTS
See page 5-277.
DIGITAL COUNTERS
See page 5-280.
MONITORING
See page 5-282.
ELEMENTS
PILOT SCHEMES
See page 5-302.
DCMA OUTPUTS
See page 5-346.
In the design of UR relays, the term element is used to describe a feature that is based around a comparator. The compar-
ator is provided with an input (or set of inputs) that is tested against a programmed setting (or group of settings) to deter-
mine if the input is within the defined range that will set the output to logic 1, also referred to as setting the flag. A single
comparator may make multiple tests and provide multiple outputs; for example, the time overcurrent comparator sets a
pickup flag when the current input is above the setting and sets an operate flag when the input current has been at a level
5 above the pickup setting for the time specified by the time-current curve settings. All comparators use analog parameter
actual values as the input.
The exception to the above rule are the digital elements, which use logic states as inputs.
NOTE
Elements are arranged into two classes, grouped and control. Each element classed as a grouped element is provided with
six alternate sets of settings, in setting groups numbered 1 through 6. The performance of a grouped element is defined by
the setting group that is active at a given time. The performance of a control element is independent of the selected active
setting group.
The main characteristics of an element are shown on the element logic diagram. This includes the inputs, settings, fixed
logic, and the output operands generated (abbreviations used on scheme logic diagrams are defined in Appendix F).
Some settings for current and voltage elements are specified in per-unit (pu) calculated quantities:
pu quantity = (actual quantity) / (base quantity)
For current elements, the base quantity is the nominal secondary or primary current of the CT.
Where the current source is the sum of two CTs with different ratios, the base quantity will be the common secondary or pri-
mary current to which the sum is scaled (that is, normalized to the larger of the two rated CT inputs). For example, if CT1 =
300 / 5 A and CT2 = 100 / 5 A, then in order to sum these, CT2 is scaled to the CT1 ratio. In this case, the base quantity will
be 5 A secondary or 300 A primary.
For voltage elements the base quantity is the nominal primary voltage of the protected system which corresponds (based
on VT ratio and connection) to secondary VT voltage applied to the relay.
For example, on a system with a 13.8 kV nominal primary voltage and with 14400:120 V delta-connected VTs, the second-
ary nominal voltage (1 pu) would be:
13800
---------------- 120 = 115 V (EQ 5.1)
14400
For wye-connected VTs, the secondary nominal voltage (1 pu) would be:
13800
---------------- 120
---------- = 66.4 V (EQ 5.2)
14400 3
Many settings are common to most elements and are discussed below:
• FUNCTION setting: This setting programs the element to be operational when selected as “Enabled”. The factory
default is “Disabled”. Once programmed to “Enabled”, any element associated with the function becomes active and all
options become available.
• NAME setting: This setting is used to uniquely identify the element.
• SOURCE setting: This setting is used to select the parameter or set of parameters to be monitored.
• PICKUP setting: For simple elements, this setting is used to program the level of the measured parameter above or
below which the pickup state is established. In more complex elements, a set of settings may be provided to define the
range of the measured parameters which will cause the element to pickup.
• PICKUP DELAY setting: This setting sets a time-delay-on-pickup, or on-delay, for the duration between the pickup
and operate output states.
• RESET DELAY setting: This setting is used to set a time-delay-on-dropout, or off-delay, for the duration between the
Operate output state and the return to logic 0 after the input transits outside the defined pickup range.
• BLOCK setting: The default output operand state of all comparators is a logic 0 or “flag not set”. The comparator
remains in this default state until a logic 1 is asserted at the RUN input, allowing the test to be performed. If the RUN
input changes to logic 0 at any time, the comparator returns to the default state. The RUN input is used to supervise
the comparator. The BLOCK input is used as one of the inputs to RUN control.
• TARGET setting: This setting is used to define the operation of an element target message. When set to “Disabled”,
no target message or illumination of a faceplate LED indicator is issued upon operation of the element. When set to
“Self-Reset”, the target message and LED indication follow the operate state of the element, and self-resets once the
operate element condition clears. When set to “Latched”, the target message and LED indication will remain visible
after the element output returns to logic 0 until a RESET command is received by the relay.
• EVENTS setting: This setting is used to control whether the pickup, dropout or operate states are recorded by the 5
event recorder. When set to “Disabled”, element pickup, dropout or operate are not recorded as events. When set to
“Enabled”, events are created for:
(Element) PKP (pickup)
(Element) DPO (dropout)
(Element) OP (operate)
The DPO event is created when the measure and decide comparator output transits from the pickup state (logic 1) to
the dropout state (logic 0). This could happen when the element is in the operate state if the reset delay time is not 0.
a) BACKGROUND
The D60 may be used on systems with breaker-and-a-half or ring bus configurations. In these applications, each of the two
three-phase sets of individual phase currents (one associated with each breaker) can be used as an input to a breaker fail-
ure element. The sum of both breaker phase currents and 3I_0 residual currents may be required for the circuit relaying
and metering functions. For a three-winding transformer application, it may be required to calculate watts and vars for each
of three windings, using voltage from different sets of VTs. These requirements can be satisfied with a single UR, equipped
with sufficient CT and VT input channels, by selecting the parameter to measure. A mechanism is provided to specify the
AC parameter (or group of parameters) used as the input to protection/control comparators and some metering elements.
Selection of the parameter(s) to measure is partially performed by the design of a measuring element or protection/control
comparator by identifying the type of parameter (fundamental frequency phasor, harmonic phasor, symmetrical component,
total waveform RMS magnitude, phase-phase or phase-ground voltage, etc.) to measure. The user completes the process
by selecting the instrument transformer input channels to use and some of the parameters calculated from these channels.
The input parameters available include the summation of currents from multiple input channels. For the summed currents of
phase, 3I_0, and ground current, current from CTs with different ratios are adjusted to a single ratio before summation.
A mechanism called a source configures the routing of CT and VT input channels to measurement sub-systems. Sources,
in the context of UR series relays, refer to the logical grouping of current and voltage signals such that one source contains
all the signals required to measure the load or fault in a particular power apparatus. A given source may contain all or some
of the following signals: three-phase currents, single-phase ground current, three-phase voltages and an auxiliary voltage
from a single VT for checking for synchronism.
To illustrate the concept of sources, as applied to current inputs only, consider the breaker-and-a-half scheme below. In this
application, the current flows as shown by the arrows. Some current flows through the upper bus bar to some other location
or power equipment, and some current flows into transformer winding 1. The current into winding 1 is the phasor sum (or
difference) of the currents in CT1 and CT2 (whether the sum or difference is used depends on the relative polarity of the CT
connections). The same considerations apply to transformer winding 2. The protection elements require access to the net
current for transformer protection, but some elements may need access to the individual currents from CT1 and CT2.
Winding 1
current
Winding 1
UR-series
relay Power
transformer
Winding 2
CT3 CT4
827791A3.CDR
Banks are ordered sequentially from the block of lower-numbered channels to the block of higher-numbered channels, and
from the CT/VT module with the lowest slot position letter to the module with the highest slot position letter, as follows:
INCREASING SLOT POSITION LETTER -->
CT/VT MODULE 1 CT/VT MODULE 2 CT/VT MODULE 3
< bank 1 > < bank 3 > < bank 5 >
< bank 2 > < bank 4 > < bank 6 >
The UR platform allows for a maximum of three sets of three-phase voltages and six sets of three-phase currents. The
result of these restrictions leads to the maximum number of CT/VT modules in a chassis to three. The maximum number of
sources is six. A summary of CT/VT module configurations is shown below.
ITEM MAXIMUM NUMBER
CT/VT Module 2
CT Bank (3 phase channels, 1 ground channel) 4
VT Bank (3 phase channels, 1 auxiliary channel) 2
a) SECURITY OVERVIEW
The following security features are available:
• Password security — Basic security present in the default offering of the product
• EnerVista security — Role-based access to various EnerVista software screens and configuration elements. The fea-
ture is available in the default offering of the product and only in the EnerVista software.
• CyberSentry security — Advanced security options available as a software option. When purchased, the options are
automatically enabled, and the default Password security and EnerVista security are disabled.
b) LOST PASSWORD
If all passwords are lost, recovery is possible by resetting the unit to default values.
To reset the unit after a lost password:
1. Email GE customer service at multilin.tech@ge.com with the serial number and using a recognizable corporate email
account. Customer service provides a code to reset the relay to the factory defaults.
2. Enter the reset code on the front panel, under Commands > Commands Relay Maintenance > Service Command.
3. Change the default password of ChangeMe1# as outlined in the Set Up CyberSentry and Change Default Password
section in the first chapter.
c) PASSWORD REQUIREMENTS
For password security and CyberSentry security, a user account requires an alpha-numeric password that meets the follow-
5 ing requirements:
• Password is case-sensitive
• Password cannot contain the user account name or parts of the user account that exceed two consecutive characters
• Password must be 6 to 20 characters in length
• Password must contain characters from three of the following four categories:
- English uppercase characters (A through Z)
- English lowercase characters (a through z)
- Base 10 digits (0 through 9)
- Non-alphabetic characters (for example, ~, !, @, #, $,%, &)
d) PASSWORD SECURITY
PATH: SETTINGS PRODUCT SETUP SECURITY
CHANGE LOCAL
MESSAGE See page 5–9.
PASSWORDS
ACCESS
MESSAGE See page 5–10.
SUPERVISION
DUAL PERMISSION
MESSAGE See page 5–11.
SECURITY ACCESS
PASSWORD ACCESS Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled
Local access is defined as any access to settings or commands via the faceplate interface. This includes both keypad entry
and the through the faceplate RS232 port. Remote access is defined as any access to settings or commands via any rear
communications port. This includes both Ethernet and RS485 connections. Any changes to the local or remote passwords
enables this functionality.
When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond-
ing connection password. If the connection is to the back of the D60, the remote password must be used. If the connection
is to the RS232 port of the faceplate, the local password must be used.
The PASSWORD ACCESS EVENTS settings allows recording of password access events in the event recorder.
The local setting and command sessions are initiated by the user through the front panel display and are disabled either by
the user or by timeout (via the setting and command level access timeout settings). The remote setting and command ses-
sions are initiated by the user through the EnerVista UR Setup software and are disabled either by the user or by timeout.
The state of the session (local or remote, setting or command) determines the state of the following FlexLogic operands.
• ACCESS LOC SETG OFF: Asserted when local setting access is disabled
• ACCESS LOC SETG ON: Asserted when local setting access is enabled
• ACCESS LOC CMND OFF: Asserted when local command access is disabled
• ACCESS LOC CMND ON: Asserted when local command access is enabled
• ACCESS REM SETG OFF: Asserted when remote setting access is disabled
• ACCESS REM SETG ON: Asserted when remote setting access is enabled
• ACCESS REM CMND OFF: Asserted when remote command access is disabled
• ACCESS REM CMND ON: Asserted when remote command access is enabled
A command or setting write operation is required to update the state of all the remote and local security operands 5
shown above.
NOTE
LOCAL PASSWORDS
PATH: SETTINGS PRODUCT SETUP SECURITY CHANGE LOCAL PASSWORDS
Proper password codes are required to enable each access level. When a CHANGE COMMAND PASSWORD or CHANGE SET-
TING PASSWORD setting is programmed to “Yes” via the front panel interface, the following message sequence is invoked:
NOTE
REMOTE PASSWORDS
The remote password settings are visible only from a remote connection via the EnerVista UR Setup software.
Proper passwords are required to enable each command or setting level access.
To set the command or setting password:
1. In the EnerVista software, navigate to Settings > Product Setup > Security menu item to open the remote password
settings window.
2. Click the command or setting password Change button.
3. Enter the new password in the New Password field. Requirements are outlined in the Password Requirements section
at the beginning of the chapter. When an original password has already been used, enter it in the Enter Password
field and click the Send Password to Device button.
4. Re-enter the password in the Confirm Password field.
5. Click the OK button. The password is checked to ensure that is meets requirements.
If you establish a local connection to the relay (serial), you cannot view remote passcodes.
NOTE
ACCESS SUPERVISION
PATH: SETTINGS PRODUCT SETUP SECURITY ACCESS SUPERVISION
The UNAUTHORIZED ACCESS operand is reset with the COMMANDS CLEAR RECORDS RESET UNAUTHORIZED
ALARMS command. Therefore, to apply this feature with security, the command level should be password-protected. The
operand does not generate events or targets.
If events or targets are required, the UNAUTHORIZED ACCESS operand can be assigned to a digital element programmed
with event logs or targets enabled.
The access level timeout settings are shown below.
PATH: SETTINGS PRODUCT SETUP SECURITY ACCESS SUPERVISION ACCESS LEVEL TIMEOUTS
These settings allow the user to specify the length of inactivity required before returning to the restricted access level. Note
that the access level will set as restricted if control power is cycled.
• COMMAND LEVEL ACCESS TIMEOUT: This setting specifies the length of inactivity (no local or remote access)
required to return to restricted access from the command password level.
• SETTING LEVEL ACCESS TIMEOUT: This setting specifies the length of inactivity (no local or remote access)
required to return to restricted access from the command password level.
DUAL PERMISSION SECURITY ACCESS
PATH: SETTINGS PRODUCT SETUP SECURITY DUAL PERMISSION SECURITY ACCESS
DUAL PERMISSION LOCAL SETTING AUTH: Range: selected FlexLogic operands (see below)
SECURITY ACCESS On 5
REMOTE SETTING AUTH: Range: FlexLogic operand
MESSAGE
On
ACCESS AUTH Range: 5 to 480 minutes in steps of 1
MESSAGE
TIMEOUT: 30 min.
The dual permission security access feature provides a mechanism for customers to prevent unauthorized or unintended
upload of settings to a relay through the local or remote interfaces interface.
The following settings are available through the local (front panel) interface only.
• LOCAL SETTING AUTH: This setting is used for local (front panel or RS232 interface) setting access supervision.
Valid values for the FlexLogic operands are either “On” (default) or any physical “Contact Input ~~ On” value.
If this setting is “On“, then local setting access functions as normal; that is, a local setting password is required. If this
setting is any contact input on FlexLogic operand, then the operand must be asserted (set as on) prior to providing the
local setting password to gain setting access.
If setting access is not authorized for local operation (front panel or RS232 interface) and the user attempts to obtain
setting access, then the UNAUTHORIZED ACCESS message is displayed on the front panel.
• REMOTE SETTING AUTH: This setting is used for remote (Ethernet or RS485 interfaces) setting access supervision.
If this setting is “On” (the default setting), then remote setting access functions as normal; that is, a remote password is
required). If this setting is “Off”, then remote setting access is blocked even if the correct remote setting password is
provided. If this setting is any other FlexLogic operand, then the operand must be asserted (set as on) prior to provid-
ing the remote setting password to gain setting access.
• ACCESS AUTH TIMEOUT: This setting represents the timeout delay for local setting access. This setting is applicable
when the LOCAL SETTING AUTH setting is programmed to any operand except “On”. The state of the FlexLogic operand
is continuously monitored for an off-to-on transition. When this occurs, local access is permitted and the timer pro-
grammed with the ACCESS AUTH TIMEOUT setting value is started. When this timer expires, local setting access is
immediately denied. If access is permitted and an off-to-on transition of the FlexLogic operand is detected, the timeout
is restarted. The status of this timer is updated every 5 seconds.
The following settings are available through the remote (EnerVista UR Setup) interface only. Select the Settings > Product
Setup > Security menu item to display the security settings window.
The Remote Settings Authorized setting is used for remote (Ethernet or RS485 interfaces) setting access supervision. If
this setting is “On” (the default setting), then remote setting access functions as normal; that is, a remote password is
required). If this setting is “Off”, then remote setting access is blocked even if the correct remote setting password is pro-
vided. If this setting is any other FlexLogic operand, then the operand must be asserted (set as on) prior to providing the
e) ENERVISTA SECURITY
ENABLING THE SECURITY MANAGEMENT SYSTEM
The EnerVista security system allows an administrator to manage access privileges of multiple users to the EnerVista appli-
cation.
It is disabled by default to allow the administrator direct access to the EnerVista software immediately after installation.
When security is disabled, all users have administrator access. GE recommends enabling the EnerVista security before
placing the device in service.
To enable the security system and require password use:
1. Select the Security > User Management menu item to open the user management window.
2. Check the Enable Security box in the lower-left corner to enable the security management system.
Security is now enabled for the EnerVista UR Setup software. Upon starting the software, users are now required to enter a
username and password.
ADDING A NEW USER
The following pre-requisites are required to add user accounts to the EnerVista security management system: 5
• The user adding the account must have administrator rights
• The EnerVista security management system must be enabled (previous section)
To add user accounts:
1. Select the Security > User Management menu item to open the user management window.
2. Enter a username in the User field. The username must be 4 to 20 characters in length.
3. Select the user access rights by enabling the check box of one or more of the fields.
f) CYBERSENTRY SECURITY
The EnerVista software provides the means to configure and authenticate UR using either device or server authentication.
The access to various pieces of functionality depends on user role.
The login screen of EnerVista has two options for access to the UR, server and device authentication.
When the "Device" button is selected, the UR uses its local authentication database and not the RADIUS server to authen-
ticate the user. In this case, it uses built-in roles (Administrator, Engineer, Supervisor, Observer, Operator) as login
accounts and the associated passwords are stored on the UR device. In this case, access is not user-attributable. In cases
where user-attributable access is required, especially for auditable processes for compliance reasons, use server authenti-
cation (RADIUS) only.
When the "Server" Authentication Type option is selected, the UR uses the RADIUS server and not its local authentication
database to authenticate the user.
5
No password or security information is displayed in plain text by the EnerVista software or UR device, nor are they ever
transmitted without cryptographic protection.
For the Device > Settings > Product Setup > Supervisory option, the panel looks like the following.
Confirm RADIUS Confirmation of the shared secret. The See the 245 characters N/A - Administrator
Authentication entry displays as asterisks. following
(Shared) Secret password
section for
requirements
CHANGE LOCAL
MESSAGE See page 5–20.
PASSWORDS
SESSION
MESSAGE See page 5–20.
SETTINGS
MESSAGE
RESTORE DEFAULTS
See page 5–20.
5
SUPERVISORY
MESSAGE See page 5–21.
SYSLOG IP ADDRESS: Range: 0.0.0.0, 255.255.255.255
MESSAGE
0.0.0.0
SYSLOG PORT NUMBER: Range: 1 to 65535
MESSAGE
514
Login: This setting is applicable for Device Authentication only. This setting allows a user to login with a specific role, see
descriptions below. For the Supervisor role, the “Supervisor Role” setting should be enabled.
Whenever a new role is logged in, the user is prompted with a display to enter a password. Passwords must obey the
requirements specified the Password Requirements section in chapter 8.The UR device supports five roles. All roles have
their corresponding passwords. The Observer role is the only role that does not require a password.
The roles are defined as follows:
• Administrator: Complete read and write access to all settings and commands. This role does not allow concurrent
access. This role has an operand to indicate when it is logged on.
• Engineer: Complete read and write access to all settings and commands with the exception of configuring Security set-
tings and Firmware upgrades. This role does not allow concurrent access.
• Operator: The Operator has read/write access to all settings under the command menu/section. This role does not
exist offline.
• Supervisor: This is only an approving role. This role’s authentication commits setting changes submitted by Administra-
tor or Engineer. The Supervisor role authenticates to unlock the UR relay for setting changes and not approve changes
after the fact. Only Supervisor can set the Settings and Firmware Lock in the Security Settings. This role also has the
ability to forcefully logoff any other role and clear the security event log. This role can also be disabled, but only
through a Supervisor authentication. When this role is disabled its permissions are assigned to the Administrator role.
• Observer: This role has read only access to all UR settings. This role allows unlimited concurrent access but it has no
download access to any files on the device. Observer is the default role if no authentication has been done to the
device. This role displays as "None" on the front panel.
The Factory service role is not available and is intended for factory use only.
NOTE
Local Passwords
PATH: SETTINGS PRODUCT SETUP SECURITY CHANGE LOCAL PASSWORDS
The Change Local Passwords menu is shown on the front panel and Enervista on a successful login of Administrator role.
The “login setting” in this menu is similar to the login setting described in PATH: SETTINGS > PRODUCT SETUP > SECU-
RITY except for the factory role.
Passwords are stored in text format. No encryption is applied.
Notes:
NOTE
5 • In Device Authentication mode, the Observer role does not have a password associated with it. In Server Authentica-
tion mode the Observer role requires a password.
• The default password is “ChangeMe1#”.
• Once the passwords are set, the Administrator with Supervisor approval can change the role associated password.
• In CyberSentry, password encryption is not supported.
Session Settings
PATH: SETTINGS PRODUCT SETUP SECURITY SESSION SETTINGS
• LOAD FACTORY DEFAULTS: This setting is used to reset all the settings, communication and security passwords. An
Administrator role is used to change this setting and a Supervisor role (if not disabled) approves it.
Supervisory
PATH: SETTINGS PRODUCT SETUP SECURITY SUPERVISORY
The Supervisory menu settings are available for Supervisor role only or if the Supervisor role is disabled then for the
Administrator role only.
Device Authentication: This setting is enabled by default, meaning "Yes" is selected. When enabled, Device Authentica-
tion with roles is enabled. When this setting is disabled, the UR only authenticates to the AAA server (Radius). However,
the Administrator and Supervisor (when enabled) remain active even after device authentication is disabled and their only 5
permission is to re-enable device authentication. To re-enable device authentication, the Supervisor unlocks the device for
setting changes, then the Administrator re-enables device authentication.
Bypass Access: The bypass security feature provides an easier access, with no authentication and encryption for those
special situations when this is considered safe. Only the Supervisor, or the Administrator when the Supervisor role is dis-
abled, can enable this feature.
MODE FRONT PANEL OR SERIAL (RS232, RS485) ETHERNET
Normal mode Authentication — Role Based Access Control (RBAC) Authentication — RBAC and passwords encrypted
and passwords in clear SSH tunneling
Bypass access mode No passwords for allowed RBAC levels No passwords for allowed RBAC levels
No SSH tunneling
Supervisor Role: When enabled (i.e., "Yes" is selected) the Supervisor role is active. When "No" is selected this role is dis-
abled. To disabled this setting a Supervisor authentication is necessary. If disabled, the Supervisor role is not allowed to log
on. In this case the Administrator can change the settings under the Supervisory menu.
If enabled, Supervisor authentication is required to change the settings in the Supervisory menu. If the Supervisor disables
his role after authentication, the Supervisor session remains valid until he switches to another role using MMI or until he
ends the current Supervisor session if using communications.
This role is disabled by default.
Serial Inactivity Timeout: The role logged via a serial port is auto logged off after the Serial Inactivity timer times out. A
separate timer is maintained for RS232 and RS485 connections. The default value is 1 minute.
a) SELF TESTS
PATH: SETTINGS PRODUCT SETUP SECURITY SUPERVISORY SELF TESTS
Failed Authentications: If this setting is Enabled then the number of failed authentications is compared with the Session
lockout threshold. When the Session lockout threshold is exceeded, this minor alarm indication comes up.
Firmware Lock: If this setting is Enabled then any firmware upgrade operation attempt when the “LOCK FIRMWARE
5 UPGRADE” setting is set to “Yes” brings up this self test alarm.
Settings Lock: If this setting is Enabled then an unauthorized write attempt to a setting for a given role activates this self
test.
PATH: SETTINGS PRODUCT SETUP SECURITY SUPERVISORY SELF TESTS FAILED AUTHENTICATE
CYBERSENTRY SETUP
When first using CyberSentry security, use the following procedure for set up.
1. Log in to the relay as Administrator by using the Value keys on the front panel to enter the default password
"ChangeMe1#". Note that the "Lock relay" setting needs to be disabled in the Security > Supervisory menu. When
this setting is disabled, configuration and firmware upgrade are possible. By default, this setting is disabled.
2. Enable the Supervisor role if you have a need for it.
3. Make any required changes in configuration, such as setting a valid IP address for communication over Ethernet.
4. Log out of the Administrator account by choosing None.
Next, device or server authentication can be chosen on the login screen, but the choice is available only in EnerVista. Use
device authentication to log in using the five pre-configured roles (Administrator, Supervisor, Engineer, Operator,
Observer). When using a serial connection, only device authentication is supported. When server authentication is
required, characteristics for communication with a RADIUS server must be configured. This is possible only in the EnerV-
ista software. The RADIUS server itself also must be configured. The appendix called RADIUS Server gives an example of
how to setup a simple RADIUS server. Once both the RADIUS server and the parameters for connecting UR to the server
have been configured, you can choose server authentication on the login screen of EnerVista.
The use of CyberSentry for devices communicating through an Ethernet-to-RS485 gateway is not
supported. Because these gateways do not support the secure protocols necessary to communicate
with such devices, the connection cannot be established. Use the device as a non-CyberSentry
device.
Users logged in through the front panel are not timed out and cannot be forcefully logged out by a
supervisor. Roles logged in through the front panel that do no allow multiple instances (Administrator,
Supervisor, Engineer, Operator) must switch to None (equivalent to a logout) when they are done in
order to log out.
For all user roles except Observer, only one instance can be logged in at one time, for both login by
front panel and software.
Some relay messaging characteristics can be modified to suit different situations using the display properties settings.
• LANGUAGE: This setting selects the language used to display settings, actual values, and targets. The range is
dependent on the order code of the relay.
• FLASH MESSAGE TIME: Flash messages are status, warning, error, or information messages displayed for several
seconds in response to certain key presses during setting programming. These messages override any normal mes-
sages. The duration of a flash message on the display can be changed to accommodate different reading rates.
• DEFAULT MESSAGE TIMEOUT: If the keypad is inactive for a period of time, the relay automatically reverts to a
default message. The inactivity time is modified via this setting to ensure messages remain on the screen long enough
during programming or reading of actual values.
• DEFAULT MESSAGE INTENSITY: To extend phosphor life in the vacuum fluorescent display, the brightness can be
attenuated during default message display. During keypad interrogation, the display always operates at full brightness.
• SCREEN SAVER FEATURE and SCREEN SAVER WAIT TIME: These settings are only visible if the D60 has a liquid
crystal display (LCD) and control its backlighting. When the SCREEN SAVER FEATURE is “Enabled”, the LCD backlighting
is turned off after the DEFAULT MESSAGE TIMEOUT followed by the SCREEN SAVER WAIT TIME, providing that no keys
have been pressed and no target messages are active. When a keypress occurs or a target becomes active, the LCD
backlighting is turned on.
• CURRENT CUT-OFF LEVEL: This setting modifies the current cut-off threshold. Very low currents (1 to 2% of the
rated value) are very susceptible to noise. Some customers prefer very low currents to display as zero, while others
prefer the current be displayed even when the value reflects noise rather than the actual signal. The D60 applies a cut-
off value to the magnitudes and angles of the measured currents. If the magnitude is below the cut-off level, it is substi-
tuted with zero. This applies to phase and ground current phasors as well as true RMS values and symmetrical compo-
nents. The cut-off operation applies to quantities used for metering, protection, and control, as well as those used by
communications protocols. Note that the cut-off level for the sensitive ground input is 10 times lower that the CURRENT
CUT-OFF LEVEL setting value. Raw current samples available via oscillography are not subject to cut-off.
5 • VOLTAGE CUT-OFF LEVEL: This setting modifies the voltage cut-off threshold. Very low secondary voltage measure-
ments (at the fractional volt level) can be affected by noise. Some customers prefer these low voltages to be displayed
as zero, while others prefer the voltage to be displayed even when the value reflects noise rather than the actual sig-
nal. The D60 applies a cut-off value to the magnitudes and angles of the measured voltages. If the magnitude is below
the cut-off level, it is substituted with zero. This operation applies to phase and auxiliary voltages, and symmetrical
components. The cut-off operation applies to quantities used for metering, protection, and control, as well as those
used by communications protocols. Raw samples of the voltages available via oscillography are not subject cut-off.
The CURRENT CUT-OFF LEVEL and the VOLTAGE CUT-OFF LEVEL are used to determine the metered power cut-off levels. The
power cut-off level is calculated as shown below. For Delta connections:
We have:
CT primary = “100 A”, and
VT primary = PHASE VT SECONDARY x PHASE VT RATIO = 66.4 V x 208 = 13811.2 V
MESSAGE
CLEAR ARC AMPS 1:
Off
Range: FlexLogic operand
5
CLEAR ARC AMPS 2: Range: FlexLogic operand
MESSAGE
Off
CLEAR ENERGY: Range: FlexLogic operand
MESSAGE
Off
RESET UNAUTH ACCESS: Range: FlexLogic operand
MESSAGE
Off
CLEAR DIR I/O STATS: Range: FlexLogic operand.
MESSAGE Valid only for units with Direct I/O module.
Off
Selected records can be cleared from user-programmable conditions with FlexLogic operands. Assigning user-programma-
ble pushbuttons to clear specific records are typical applications for these commands. Since the D60 responds to rising
edges of the configured FlexLogic operands, they must be asserted for at least 50 ms to take effect.
Clearing records with user-programmable operands is not protected by the command password. However, user-program-
mable pushbuttons are protected by the command password. Thus, if they are used to clear records, the user-programma-
ble pushbuttons can provide extra security if required.
For example, to assign user-programmable pushbutton 1 to clear demand records, the following settings should be applied.
1. Assign the clear demand function to pushbutton 1 by making the following change in the SETTINGS PRODUCT SETUP
CLEAR RELAY RECORDS menu:
CLEAR DEMAND: “PUSHBUTTON 1 ON”
2. Set the properties for user-programmable pushbutton 1 by making the following changes in the SETTINGS PRODUCT
SETUP USER-PROGRAMMABLE PUSHBUTTONS USER PUSHBUTTON 1 menu:
PUSHBUTTON 1 FUNCTION: “Self-reset”
PUSHBTN 1 DROP-OUT TIME: “0.20 s”
5.2.4 COMMUNICATIONS
a) MAIN MENU
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS
5 MESSAGE
TFTP PROTOCOL
See page 5–53.
IEC 60870-5-104
MESSAGE See page 5–54.
PROTOCOL
b) SERIAL PORTS
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS SERIAL PORTS
SERIAL PORTS RS485 COM2 BAUD Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,
RATE: 19200 28800, 33600, 38400, 57600, 115200
The D60 is equipped with up to two independent serial communication ports. The faceplate RS232 port is intended for local
use and is fixed at 19200 baud and no parity. The rear COM2 port is RS485. The RS485 port has settings for baud rate and
parity. It is important that these parameters agree with the settings used on the computer or other equipment that is con-
nected to these ports. Any of these ports can be connected to a computer running EnerVista UR Setup. This software can
download and upload setting files, view measured parameters, and upgrade the relay firmware. A maximum of 32 relays
can be daisy-chained and connected to a DCS, PLC, or computer using the RS485 ports.
For the RS485 port, the minimum time before the port transmits after receiving data from a host can be set. This
feature allows operation with hosts which hold the RS485 transmitter active for some time after each transmission.
NOTE
Example 1
IP1/Mask1: 10.1.1.2/255.255.255.0 (where LAN 1 is 10.1.1.x/255.255.255.0)
IP2/Mask2: 10.2.1.2/255.255.255.0 (where LAN2 is 10.2.1.x/255.255.255.0)
IP3/Mask3: 10.3.1.2/255.255.255.0 (where LAN3 is 10.3.1.x/255.255.255.0)
Example 2
IP1/Mask1: 10.1.1.2/255.0.0.0 (where LAN1 is 10.x.x.x/255.0.0.0)
IP2/Mask2: 11.1.1.2/255.0.0.0 (where LAN2 is 11.x.x.x/255.0.0.0)
IP3/Mask3: 12.1.1.2/255.0.0.0 (where LAN3 is 12.x.x.x/255.0.0.0)
Example 3 — Incorrect
IP1/Mask1: 10.1.1.2/255.0.0.0
IP2/Mask2: 10.2.1.2/255.0.0.0
IP3/Mask3: 10.3.1.2/255.0.0.0
This example is incorrect because the mask of 255.0.0.0 used for the three IP addresses makes them belong to the same
network of 10.x.x.x.
Single LAN, No Redundancy
The topology shown in the following figure allows communications to SCADA, local configuration/monitoring through
EnerVista, and access to the public network shared on the same LAN. No redundancy is provided.
Figure 5–4: NETWORK CONFIGURATION FOR SINGLE LAN
d) NETWORK
As outlined in the previous section, when using more than one Ethernet port, configure each to belong to a different net-
work or subnet using the IP addresses and mask. Configure the network IP and subnet settings before configuring the rout-
ing settings.
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS NETWORK 1(3)
5
MESSAGE
01-15-4E-00-01-00
PRT2 GOOSE ENABLED: Range: Enabled, Disabled
MESSAGE
Enabled
The IP addresses are used with the DNP, Modbus/TCP, IEC 61580, IEC 60870-5-104, TFTP, HTTP, and PRP protocols.
The next section explains PRP.
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
NOTE
PRT1 (2 OR 3) IP ADDRESS: This setting sets the ports IPv4 address in standard IPV4 format. This setting is valid on port 3 if
port 2 REDUNDANCY is set to None.
PRT1 (2 OR 3) SUBNET MASK: This setting sets the ports IPv4 subnet mask in standard IPV4 format. This setting is valid on
port 3 if port 2 REDUNDANCY is set to None.
PRT2 REDUNDANCY is available when the hardware has multiple ports (modules T, U, and V). It determines if ports 2 and 3
operate in redundant or independent mode. If a license for PRP was purchased, the options are None, Failover, and PRP.
If a license for PRP was not purchased, the available options are None and Failover. In non-redundant mode (REDUNDANCY
set to None), ports 2 and 3 operate independently with their own MAC, IP, and mask addresses. If REDUNDANCY is set to
Failover, the operation of ports 2 and 3 is as follows:
• Ports 2 and 3 use the port 2 MAC address, IP address, and mask
• The configuration fields for IP address and mask on port 3 are hidden
• Port 3 is in standby mode and does not actively communicate on the Ethernet network but monitors its link to the Mul-
tilink switch. If port 2 detects a problem with the link, communications is switched to Port 3. Port 3 is, in effect, acting as
a redundant or backup link to the network for port 2. Once Port 2 detects that the link between port 2 and the switch is
good, communications automatically switch back to port 2 and port 3 goes back into standby mode.
If REDUNDANCY is set to PRP, the operation of ports 2 and 3 is as follows:
• Ports 2 and 3 use the port 2 MAC address, IP address, and mask
• The configuration fields for IP address and mask on port 3 are overwritten with those from port 2. This is visible on the
front panel but not displayed in the EnerVista software.
• Port 2 MCST ADDRESS field is visible
• The port 2 PTP function still uses only port 2 and the port 3 PTP function still uses only port 3. The relay still synchro-
nizes to whichever port has the best master. When ports 2 and 3 see the same master, as is typically the case for PRP
networks, the port with the better connectivity is used.
The two ports must be connected to completely independent LANS with no single point of failure, such as common
power supplies that feed switches on both LANS.
NOTE
5 The Parallel Redundancy Protocol (PRP) defines a redundancy protocol for high availability in substation automation net-
works. It applies to networks based on Ethernet technology (ISO/IEC 8802-3) and is based on the second edition (July
2012) of the IEC 62439-3, clause 4.
PRP is designed to provide seamless recovery in case of a single failure in the network, by using a combination of LAN
duplication and frame duplication technique. Identical frames are sent on two completely independent networks that con-
nect source and destination. Under normal circumstances both frames reach the destination and one of them is sent up the
OSI stack to the destination application, while the second one is discarded. If an error occurs in one of the networks and
traffic is prevented from flowing on that path, connectivity is still provided through the other network to ensure continuous
communication. Take care when designing the two LANs, so that no single point of failure (such as a common power sup-
ply) is encountered, as such scenarios can bring down both LANs simultaneously.
Figure 5–7: EXAMPLE OF PARALLEL REDUNDANT NETWORK
PRP uses specialized nodes called doubly attached nodes (DANPs) for handling the duplicated frames. DANPs devices
have an additional module, called Link Redundancy Entity (LRE). LRE is responsible for duplicating frames and adding the
specific PRP trailer when sending the frames out on the LAN, as well as making decisions on received frames as to which
one is sent up the OSI stack to the application layer and which one is discarded. LRE is responsible for making PRP trans-
parent to the higher layers of the stack. There is a second type of specialized device used in PRP networks, called RedBox,
with the role of connecting Single Attached Nodes (SANs) to a redundant network.
UR relays implement only the DANP functionality. The RedBox functionality is not implemented.
The original standard IEC 62439-3 (2010) was amended to align PRP with the High-availability Seamless Redundancy
(HSR) protocol. To achieve this, the original PRP was modified at the cost of losing compatibility with the PRP 2010 ver-
sion. The revised standard IEC 62439-3 (2012) is commonly referred to as PRP-1, while the original standard is PRP-0.
The UR relays support only PRP-1.
The relay implements PRP on two of its Ethernet ports, specifically Port 2 and 3 of the CPU module. Use the previous sec-
tion (network port configuration) to configure PRP.
PRP is purchased as a separate option. If purchased (valid order code), PRP can be enabled in configuration through a
setting available on the network configuration menu, REDUNDANCY, which already has the capability of enabling failover
redundancy. The options on this setting must be changed to accommodate two types of redundancy: failover and PRP.
When REDUNDANCY is set to either failover or PRP, the ports dedicated for PRP (Port 2 and 3) operate in redundant
mode. In this mode, Port 3 uses the Mac, IP address, and mask of Port 2.
f) ROUTING
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS ROUTING 1(6)
IPV4 STATIC
MESSAGE
NETWORK ROUTE 6
A default route and a maximum number of six static routes can be configured. 5
The default route is used as the last choice when no other route towards a given destination is found.
IPV4 DEFAULT ROUTE GATEWAY ADDRESS Range: Standard IPV4 unicast address format
127.0.0.1
Configure the network IP and subnet settings before configuring the routing settings.
ADDING AND DELETING STATIC ROUTES
Host routes are not supported at present.
The routing table configuration is available on the serial port and front panel. This is a deliberate decision, to avoid loss of
connectivity when remotely configuring the UR.
By default the value of the destination field is 127.0.0.1 for all static routes (1 to 6). This is equivalent to saying that the
static routes are not configured. When the destination address is 127.0.0.1, the mask and gateway must be also kept on
default values.
By default, the value of the route gateway address is 127.0.0.1. This means the default route is not configured.
To add a route:
1. Use any of the static network route entries numbered 1 to 6 to configure a static network route. Once a route destina-
tion is configured for any of the entries 1 to 6, that entry becomes a static route and it must meet all the rules listed in
the next section, General Conditions to be Satisfied by Static Routes.
2. To configure the default route, enter a default gateway address. Once a default gateway address is configured, it must
be validated against condition 2 of the General Conditions to be Satisfied by Static Routes.
To delete a route:
1. Replace the route destination with the default loopback address (127.0.0.1). When deleting a route, the mask and
gateway must be also brought back to default values.
2. Delete the default route by replacing the default gateway with the default value 127.0.0.1.
GENERAL CONDITIONS TO BE SATISFIED BY STATIC ROUTES
The following rules are validated internally:
• The route mask has IP mask format. In binary this needs to be a set of contiguous bits of 1 from left to right, followed
by one or more contiguous bits of 0.
• The route destination and mask must match. This can be verified by checking that
RtDestination and RtMask = RtDestination
Example of good configuration: RtDestination = 10.1.1.0; Rt Mask = 255.255.255.0
Example of bad configuration: RtDestination = 10.1.1.1; Rt Mask = 255.255.255.0
The following rules must be observed when you configure static routes:
• The route destination must not be a connected network
• The route gateway must be on a connected network. This rule applies to the gateway address of the default route as
well. This can be verified by checking that:
RtGwy and Prt1Mask = Prt1IP and Prt1Mask || RtGwy and Prt2Mask = Prt2IP and Prt2Mask || RtGwy and Prt3Mask =
Prt3IP and Prt3Mask
ROUTING BEHAVIOR COMPARED TO PREVIOUS RELEASES
5 Prior to release 7.10, the UR did not have an explicit manner of configuring routes. The only available route was the default
route configured as part of the network settings (port gateway IP address). This limited the ability to route to specific desti-
nations, particularly if these destinations were reachable through a different interface than the one on which the default
gateway was.
Starting with UR 7.10, up to six static network routes can be configured in addition to a default route. The default route con-
figuration was also moved from the network settings into the routing section.
The figure shows an example of topology that benefits from the addition of static routes.
Figure 5–8: USING STATIC ROUTES
In the figure, the UR connects through the following two Ethernet ports:
• Port 1 (IP address 10.1.1.2) connects the UR to LAN 10.1.1.0/24 and to the Internet through Router1. Router 1 has an
interface on 10.1.1.0/24 and the IP address of this interface is 10.1.1.1.
• Port 2 (IP address 10.1.2.2) connects the UR to LAN 10.1.2.0/24 and to the EnerVista software through Router 2.
Router 2 has an interface on 10.1.2.0/24 and the IP address of this interface is 10.1.2.1.
The configuration before release 7.10 was as follows:
• PRT1 IP ADDRESS = 10.1.1.2
PRT1 SUBNET IP MASK = 255.255.255.0
PRT1 GWY IP ADDRESS = 10.1.1.1
PRT2 IP ADDRESS = 10.1.2.2
PRT2 SUBNET IP MASK = 255.255.255.0
The behavior before release 7.10 was as follows. When sending packets to EnerVista, the UR noticed that the destination
was not on a connected network and it tried to find a route to destination. Since the default route was the only route it knew,
it used it. Yet EnerVista was on a private network, which was not reachable through Router 1. Hence a destination unreach-
able message was received from the router.
The configuration starting release 7.10 is as follows:
• PRT1 IP ADDRESS = 10.1.1.2
PRT1 SUBNET IP MASK = 255.255.255.0
PRT2 IP ADDRESS = 10.1.2.2
PRT2 SUBNET IP MASK = 255.255.255.0
IPV4 DEFAULT ROUTE: GATEWAY ADDRESS = 10.1.1.1
STATIC NETWORK ROUTE 1: RT1 DESTINATION = 10.1.3.0/24; RT1 NET MASK = 255.255.255.0; and RT1 GATE-
WAY = 10.1.2.1
The behavior since release 7.10 is as follows. There is one added static network route to the destination 10.1.3.0/24, where
a laptop running EnerVista is located. This static route uses a different gateway (10.1.2.1) than the default route. This gate-
way is the address of Router 2, which has knowledge about 10.1.3.0 and is able to route packets coming from UR and des-
tined to EnerVista. 5
SHOW ROUTES AND ARP TABLES
This feature is available on the Web interface, where the main menu contains an additional Communications menu and two
submenus:
• Routing Table
• ARP Table
The tables outline the information displayed when the two submenus are selected.
Table 5–3: ROUTING TABLE INFORMATION
FIELD DESCRIPTION
Destination The IP address of the remote network to which this route points
Mask The network mask for the destination
Gateway The IP address of the next router to the remote network
Interface Interface through which the specified network can be reached
g) MODBUS PROTOCOL
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS MODBUS PROTOCOL
The serial communication ports utilize the Modbus protocol, unless configured for DNP operation (see descriptions below).
This allows the EnerVista UR Setup software to be used. The UR operates as a Modbus slave device only. When using
Modbus protocol on the RS232 port, the D60 responds regardless of the MODBUS SLAVE ADDRESS programmed. For the
RS485 port, each D60 must have a unique address from 1 to 254. Address 0 is the broadcast address which all Modbus
slave devices listen to. Addresses do not have to be sequential, but no two devices can have the same address or conflicts
resulting in errors will occur. Generally, each device added to the link should use the next higher address starting at 1. See
Appendix B for more information on the Modbus protocol.
A value of 0 closes the port. When the Modbus port is set to 0, communicate with the relay using the front panel or serial
port.
When a 0 value is involved in a change, the changes to the MODBUS TCP PORT NUMBER setting take effect
when the D60 is restarted.
NOTE
h) DNP PROTOCOL
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS DNP PROTOCOL
5 DNP PROTOCOL
DNP CHANNELS
Range: see sub-menu below
DNP OTHER SCALE Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
MESSAGE 100000
FACTOR: 1
DNP CURRENT DEFAULT Range: 0 to 100000000 in steps of 1
MESSAGE
DEADBAND: 30000
DNP VOLTAGE DEFAULT Range: 0 to 100000000 in steps of 1
MESSAGE
DEADBAND: 30000
DNP POWER DEFAULT Range: 0 to 100000000 in steps of 1
MESSAGE
DEADBAND: 30000
DNP ENERGY DEFAULT Range: 0 to 100000000 in steps of 1
MESSAGE
DEADBAND: 30000
DNP PF DEFAULT Range: 0 to 100000000 in steps of 1
MESSAGE
DEADBAND: 30000
DNP OTHER DEFAULT Range: 0 to 100000000 in steps of 1
MESSAGE
DEADBAND: 30000
DNP TIME SYNC IIN Range: 1 to 10080 min. in steps of 1
MESSAGE
PERIOD: 1440 min
DNP MESSAGE FRAGMENT Range: 30 to 2048 in steps of 1
MESSAGE
SIZE: 240
DNP OBJECT 1 Range: 1, 2
MESSAGE
DEFAULT VARIATION: 2
DNP OBJECT 2 Range: 1, 2, 3
5
MESSAGE
DEFAULT VARIATION: 2
DNP OBJECT 20 Range: 1, 2, 5, 6
MESSAGE
DEFAULT VARIATION: 1
DNP OBJECT 21 Range: 1, 2, 9, 10
MESSAGE
DEFAULT VARIATION: 1
DNP OBJECT 22 Range: 1, 2, 5, 6
MESSAGE
DEFAULT VARIATION: 1
DNP OBJECT 23 Range: 1, 2, 5, 6
MESSAGE
DEFAULT VARIATION: 2
DNP OBJECT 30 Range: 1, 2, 3, 4, 5
MESSAGE
DEFAULT VARIATION: 1
DNP OBJECT 32 Range: 1, 2, 3, 4, 5, 7
MESSAGE
DEFAULT VARIATION: 1
DNP NUMBER OF PAIRED Range: 0 to 32 in steps of 1
MESSAGE
CONTROL POINTS: 0
DNP TCP CONNECTION Range: 10 to 7200 s in steps of 1
MESSAGE
TIMEOUT: 120 s
The D60 supports the Distributed Network Protocol (DNP) version 3.0. The D60 can be used as a DNP slave device con-
nected to multiple DNP masters (usually an RTU or a SCADA master station). Since the D60 maintains two sets of DNP
data change buffers and connection information, two DNP masters can actively communicate with the D60 at one time.
The IEC 60870-5-104 and DNP protocols cannot be used simultaneously. When the IEC 60870-5-104 FUNCTION
setting is set to “Enabled”, the DNP protocol is not operational. When this setting is changed it does not become
NOTE
active until power to the relay has been cycled (off-to-on).
The DNP Channels sub-menu is shown below.
The DNP CHANNEL 1 PORT and DNP CHANNEL 2 PORT settings select the communications port assigned to the DNP protocol
for each channel. Once DNP is assigned to a serial port, the Modbus protocol is disabled on that port. When this setting is
set to “Network - TCP”, the DNP protocol can be used over TCP/IP on channels 1 or 2. When this value is set to “Network -
UDP”, the DNP protocol can be used over UDP/IP on channel 1 only. Refer to Appendix E for additional information on the
DNP protocol.
Changes to the DNP CHANNEL 1 PORT and DNP CHANNEL 2 PORT settings take effect only after power has
been cycled to the relay.
NOTE
The DNP NETWORK CLIENT ADDRESS settings can force the D60 to respond to a maximum of five specific DNP masters. The
settings in this sub-menu are shown below.
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS DNP PROTOCOL DNP NETWORK CLIENT ADDRESSES
5 MESSAGE
CLIENT ADDRESS 3:
0.0.0.0
Range: standard IP address
The DNP UNSOL RESPONSE FUNCTION should be “Disabled” for RS485 applications since there is no collision avoidance
mechanism. The DNP UNSOL RESPONSE TIMEOUT sets the time the D60 waits for a DNP master to confirm an unsolicited
response. The DNP UNSOL RESPONSE MAX RETRIES setting determines the number of times the D60 retransmits an unsolic-
ited response without receiving confirmation from the master; a value of “255” allows infinite re-tries. The DNP UNSOL
RESPONSE DEST ADDRESS is the DNP address to which all unsolicited responses are sent. The IP address to which unsolic-
ited responses are sent is determined by the D60 from the current TCP connection or the most recent UDP message.
The DNP scale factor settings are numbers used to scale analog input point values. These settings group the D60 analog
input data into the following types: current, voltage, power, energy, power factor, and other. Each setting represents the
scale factor for all analog input points of that type. For example, if the DNP VOLTAGE SCALE FACTOR setting is set to “1000”,
all DNP analog input points that are voltages will be returned with values 1000 times smaller (for example, a value of 72000
V on the D60 will be returned as 72). These settings are useful when analog input values must be adjusted to fit within cer-
tain ranges in DNP masters. Note that a scale factor of 0.1 is equivalent to a multiplier of 10 (that is, the value will be 10
times larger).
The DNP DEFAULT DEADBAND settings determine when to trigger unsolicited responses containing analog input data. These
settings group the D60 analog input data into the following types: current, voltage, power, energy, power factor, and other.
Each setting represents the default deadband value for all analog input points of that type. For example, to trigger unsolic-
ited responses from the D60 when any current values change by 15 A, the DNP CURRENT DEFAULT DEADBAND setting
should be set to “15”. Note that these settings are the deadband default values. DNP object 34 points can be used to
change deadband values, from the default, for each individual DNP analog input point. Whenever power is removed and
re-applied to the D60, the default deadbands will be in effect.
The DNP TIME SYNC IIN PERIOD setting determines how often the Need Time Internal Indication (IIN) bit is set by the D60.
Changing this time allows the DNP master to send time synchronization commands more or less often, as required.
The DNP MESSAGE FRAGMENT SIZE setting determines the size, in bytes, at which message fragmentation occurs. Large
fragment sizes allow for more efficient throughput; smaller fragment sizes cause more application layer confirmations to be
necessary which can provide for more robust data transfer over noisy communication channels.
When the DNP data points (analog inputs and/or binary inputs) are configured for Ethernet-enabled relays, check
the “DNP Points Lists” D60 web page to view the points lists. This page can be viewed with a web browser by enter-
NOTE
ing the D60 IP address to access the D60 “Main Menu”, then by selecting the “Device Information Menu” > “DNP
Points Lists” menu item.
The DNP OBJECT 1 DEFAULT VARIATION to DNP OBJECT 32 DEFAULT VARIATION settings allow the user to select the DNP
default variation number for object types 1, 2, 20, 21, 22, 23, 30, and 32. The default variation refers to the variation
response when variation 0 is requested and/or in class 0, 1, 2, or 3 scans. Refer to the DNP implementation section in
appendix E for additional details.
The DNP binary outputs typically map one-to-one to IED data points. That is, each DNP binary output controls a single
physical or virtual control point in an IED. In the D60 relay, DNP binary outputs are mapped to virtual inputs. However, some
legacy DNP implementations use a mapping of one DNP binary output to two physical or virtual control points to support
the concept of trip/close (for circuit breakers) or raise/lower (for tap changers) using a single control point. That is, the DNP
master can operate a single point for both trip and close, or raise and lower, operations. The D60 can be configured to sup-
port paired control points, with each paired control point operating two virtual inputs. The DNP NUMBER OF PAIRED CONTROL
POINTS setting allows configuration of from 0 to 32 binary output paired controls. Points not configured as paired operate on
a one-to-one basis.
The DNP ADDRESS setting is the DNP slave address. This number identifies the D60 on a DNP communications link. Each
DNP slave should be assigned a unique address.
The DNP TCP CONNECTION TIMEOUT setting specifies a time delay for the detection of dead network TCP connections. If
there is no data traffic on a DNP TCP connection for greater than the time specified by this setting, the connection will be
aborted by the D60. This frees up the connection to be re-used by a client.
5
Relay power must be re-cycled after changing the DNP TCP CONNECTION TIMEOUT setting for the changes to take
effect.
NOTE
The binary and analog inputs points for the DNP protocol, or the MSP and MME points for IEC 60870-5-104 protocol, can
configured to a maximum of 256 points. The value for each point is user-programmable and can be configured by assigning
FlexLogic operands for binary inputs / MSP points or FlexAnalog parameters for analog inputs / MME points.
The menu for the binary input points (DNP) or MSP points (IEC 60870-5-104) is shown below.
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS DNP / IEC104 POINT LISTS BINARY INPUT / MSP POINTS
Up to 256 binary input points can be configured for the DNP or IEC 60870-5-104 protocols. The points are configured by
assigning an appropriate FlexLogic operand. Refer to the Introduction to FlexLogic section in this chapter for the full range
of assignable operands.
The menu for the analog input points (DNP) or MME points (IEC 60870-5-104) is shown below.
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS DNP / IEC104 POINT LISTS ANALOG INPUT / MME POINTS
Up to 256 analog input points can be configured for the DNP or IEC 60870-5-104 protocols. The analog point list is config-
ured by assigning an appropriate FlexAnalog parameter to each point. Refer to Appendix A: FlexAnalog Parameters for the
full range of assignable parameters.
The DNP / IEC 60870-5-104 point lists always begin with point 0 and end at the first “Off” value. Since DNP / IEC
60870-5-104 point lists must be in one continuous block, any points assigned after the first “Off” point are ignored.
NOTE
Changes to the DNP / IEC 60870-5-104 point lists will not take effect until the D60 is restarted.
NOTE
5 CONFIGURATION
SERVER
MESSAGE
CONFIGURATION
IEC 61850 LOGICAL
MESSAGE
NODE NAME PREFIXES
MMXU DEADBANDS
MESSAGE
GGIO1 STATUS
MESSAGE
CONFIGURATION
GGIO2 CONTROL
MESSAGE
CONFIGURATION
GGIO4 ANALOG
MESSAGE
CONFIGURATION
GGIO5 UINTEGER
MESSAGE
CONFIGURATION
REPORT CONTROL
MESSAGE
CONFIGURATION
XCBR
MESSAGE
CONFIGURATION
XSWI
MESSAGE
CONFIGURATION
The D60 Line Distance Protection System is provided with optional IEC 61850 communications capability.
This feature is specified as a software option at the time of ordering. Refer to the Ordering section of chap-
ter 2 for additional details.
Use independent ports for IEC 61850 communication and take care when configuring the settings,
else loss of protection or misoperation of the relay can result.
The D60 supports the Manufacturing Message Specification (MMS) protocol as specified by IEC 61850. MMS is supported
over two protocol stacks: TCP/IP over Ethernet. The D60 operates as an IEC 61850 server. The Remote inputs and outputs
section in this chapter describe the peer-to-peer GSSE/GOOSE message scheme.
The GSSE/GOOSE configuration main menu is divided into two areas: transmission and reception.
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL GSSE/GOOSE CONFIGURATION
The DEFAULT GSSE/GOOSE UPDATE TIME sets the time between GSSE or GOOSE messages when there are no remote out-
put state changes to be sent. When remote output data changes, GSSE or GOOSE messages are sent immediately. This
setting controls the steady-state heartbeat time interval.
The DEFAULT GSSE/GOOSE UPDATE TIME setting is applicable to GSSE, fixed D60 GOOSE, and configurable GOOSE.
The GSSE settings are shown below:
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL GSSE/GOOSE CONFIGURATION
TRANSMISSION GSEE
GSSE GSSE FUNCTION: Range: Enabled, Disabled
Enabled
GSSE ID: Range: 65-character ASCII string
MESSAGE
GSSEOut
DESTINATION MAC: Range: standard MAC address
MESSAGE
000000000000
These settings are applicable to GSSE only. If the fixed GOOSE function is enabled, GSSE messages are not transmitted.
The GSSE ID setting represents the IEC 61850 GSSE application ID name string sent as part of each GSSE message. This
string identifies the GSSE message to the receiving device. In D60 releases previous to 5.0x, this name string was repre-
sented by the RELAY NAME setting.
The details about each scheme are shown in the following table.
The configurable GOOSE feature is recommended for applications that require GOOSE data transfer between UR-series
IEDs and devices from other manufacturers. Fixed GOOSE is recommended for applications that require GOOSE data
transfer between UR-series IEDs.
IEC 61850 GOOSE messaging contains a number of configurable parameters, all of which must be correct to achieve the
successful transfer of data. It is critical that the configured datasets at the transmission and reception devices are an exact
match in terms of data structure, and that the GOOSE addresses and name strings match exactly. Manual configuration is
possible, but third-party substation configuration software may be used to automate the process. The EnerVista UR Setup
software can produce IEC 61850 ICD files and import IEC 61850 SCD files produced by a substation configurator (refer to
the IEC 61850 IED configuration section later in this appendix).
The following example illustrates the configuration required to transfer IEC 61850 data items between two devices. The
general steps required for transmission configuration are:
1. Configure the transmission dataset.
2. Configure the GOOSE service settings.
3. Configure the data.
The general steps required for reception configuration are:
1. Configure the reception dataset.
2. Configure the GOOSE service settings.
3. Configure the data.
This example shows how to configure the transmission and reception of three IEC 61850 data items: a single point status
value, its associated quality flags, and a floating point analog value.
The following procedure illustrates the transmission configuration.
1. Configure the transmission dataset by making the following changes in the PRODUCT SETUP COMMUNICATION
IEC 61850 PROTOCOL GSSE/GOOSE CONFIGURATION TRANSMISSION CONFIGURABLE GOOSE CONFIGURABLE
GOOSE 1 CONFIG GSE 1 DATASET ITEMS settings menu:
– Set ITEM 1 to “GGIO1.ST.Ind1.q” to indicate quality flags for GGIO1 status indication 1.
– Set ITEM 2 to “GGIO1.ST.Ind1.stVal” to indicate the status value for GGIO1 status indication 1.
– Set ITEM 3 to “MMXU1.MX.Hz.mag.f” to indicate the analog frequency magnitude for MMXU1 (the metered fre-
quency for SRC1).
The transmission dataset now contains a quality flag, a single point status Boolean value, and a floating point analog
value. The reception dataset on the receiving device must exactly match this structure.
2. Configure the GOOSE service settings by making the following changes in the PRODUCT SETUP COMMUNICATION
IEC 61850 PROTOCOL GSSE/GOOSE CONFIGURATION TRANSMISSION CONFIGURABLE GOOSE CONFIGU-
RABLE GOOSE 1 settings menu:
– Set ITEM 1 to “GGIO3.ST.Ind1.q” to indicate quality flags for GGIO3 status indication 1.
– Set ITEM 2 to “GGIO3.ST.Ind1.stVal” to indicate the status value for GGIO3 status indication 1.
– Set ITEM 3 to “GGIO3.MX.AnIn1.mag.f” to indicate the analog magnitude for GGIO3 analog input 1.
The reception dataset now contains a quality flag, a single point status Boolean value, and a floating point analog
value. This matches the transmission dataset configuration above.
2. Configure the GOOSE service settings by making the following changes in the INPUTS/OUTPUTS REMOTE DEVICES
REMOTE DEVICE 1 settings menu:
– Set REMOTE DEVICE 1 ID to match the GOOSE ID string for the transmitting device. Enter “GOOSEOut_1”.
– Set REMOTE DEVICE 1 ETYPE APPID to match the ETHERTYPE application ID from the transmitting device. This is
“0” in the example above.
– Set the REMOTE DEVICE 1 DATASET value. This value represents the dataset number in use. Since we are using
configurable GOOSE 1 in this example, program this value as “GOOSEIn 1”.
3. Configure the Boolean data by making the following changes in the INPUTS/OUTPUTS REMOTE INPUTS REMOTE
INPUT 1settings menu:
– Set REMOTE IN 1 DEVICE to “GOOSEOut_1”.
– Set REMOTE IN 1 ITEM to “Dataset Item 2”. This assigns the value of the GGIO3.ST.Ind1.stVal single point status
item to remote input 1.
4. Configure the analog data by making the following changes in the INPUTS/OUTPUTS IEC 61850 GOOSE ANALOG
INPUTS settings menu:
– Set the IEC61850 GOOSE ANALOG INPUT 1 DEFAULT VALUE to “60.000”.
– Enter “Hz” for the IEC61850 GOOSE ANALOG INPUT 1 UNITS setting.
The GOOSE analog input 1 can now be used as a FlexAnalog value in a FlexElement or in other settings. The D60 must be
rebooted (control power removed and re-applied) before these settings take effect.
The value of GOOSE analog input 1 in the receiving device will be determined by the MMXU1.MX.Hz.mag.f value in the
sending device. This MMXU value is determined by the source 1 frequency value and the MMXU Hz deadband setting of
the sending device.
Remote input 1 can now be used in FlexLogic equations or other settings. The D60 must be rebooted (control power
removed and re-applied) before these settings take effect.
The value of remote input 1 (Boolean on or off) in the receiving device will be determined by the GGIO1.ST.Ind1.stVal value
5 in the sending device. The above settings will be automatically populated by the EnerVista UR Setup software when a com-
plete SCD file is created by third party substation configurator software.
For intercommunication between D60 IEDs, the fixed (DNA/UserSt) dataset can be used. The DNA/UserSt dataset con-
tains the same DNA and UserSt bit pairs that are included in GSSE messages. All GOOSE messages transmitted by the
D60 (DNA/UserSt dataset and configurable datasets) use the IEC 61850 GOOSE messaging services (for example, VLAN
support).
Set the CONFIG GSE 1 FUNCTION function to “Disabled” when configuration changes are required. Once changes are
entered, return the CONFIG GSE 1 FUNCTION to “Enabled” and restart the unit for changes to take effect.
NOTE
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL GSSE/GOOSE CONFIGURATION
TRANSMISSION CONFIGURABLE GOOSE CONFIGURABLE GOOSE 1(8) CONFIG GSE 1(64) DATA ITEMS
CONFIG GSE 1 ITEM 1: Range: all valid MMS data item references for
DATASET ITEMS GGIO1.ST.Ind1.stVal transmitted data
ITEM 64: Range: all valid MMS data item references for
MESSAGE transmitted data
None
To create a configurable GOOSE dataset that contains an IEC 61850 Single Point Status indication and its associated qual-
ity flags, the following dataset items can be selected: “GGIO1.ST.Ind1.stVal” and “GGIO1.ST.Ind1.q”. The D60 will then cre-
ate a dataset containing these two data items. The status value for GGIO1.ST.Ind1.stVal is determined by the FlexLogic
operand assigned to GGIO1 indication 1. Changes to this operand will result in the transmission of GOOSE messages con-
taining the defined dataset.
The main reception menu is applicable to configurable GOOSE only and contains the configurable GOOSE dataset items
for reception:
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL GSSE/GOOSE CONFIGURATION
RECEPTION CONFIGURABLE GOOSE CONFIGURABLE GOOSE 1(16) CONFIG GSE 1(32) DATA ITEMS
CONFIG GSE 1 ITEM 1: Range: all valid MMS data item references for
DATASET ITEMS GGIO3.ST.Ind1.stVal transmitted data
ITEM 32: Range: all valid MMS data item references for
MESSAGE transmitted data
None
The configurable GOOSE settings allow the D60 to be configured to receive a number of different datasets within IEC
61850 GOOSE messages. Up to sixteen different configurable datasets can be configured for reception. This is useful for
intercommunication between D60 IEDs and devices from other manufacturers that support IEC 61850.
For intercommunication between D60 IEDs, the fixed (DNA/UserSt) dataset can be used. The DNA/UserSt dataset con-
tains the same DNA and UserSt bit pairs that are included in GSSE messages.
To set up a D60 to receive a configurable GOOSE dataset that contains two IEC 61850 single point status indications, the
following dataset items can be selected (for example, for configurable GOOSE dataset 1): “GGIO3.ST.Ind1.stVal” and
“GGIO3.ST.Ind2.stVal”. The D60 will then create a dataset containing these two data items. The Boolean status values from
these data items can be utilized as remote input FlexLogic operands. First, the REMOTE DEVICE 1(16) DATASET setting must 5
be set to contain dataset “GOOSEIn 1” (that is, the first configurable dataset). Then REMOTE IN 1(16) ITEM settings must be
set to “Dataset Item 1” and “Dataset Item 2”. These remote input FlexLogic operands will then change state in accordance
with the status values of the data items in the configured dataset.
Double-point status values may be included in the GOOSE dataset. Received values are populated in the
GGIO3.ST.IndPos1.stVal and higher items.
Floating point analog values originating from MMXU logical nodes may be included in GOOSE datasets. Deadband (non-
instantaneous) values can be transmitted. Received values are used to populate the GGIO3.MX.AnIn1 and higher items.
Received values are also available as FlexAnalog parameters (GOOSE analog In1 and up).
GGIO3.MX.AnIn1 to GGIO3.MX.AnIn32 can only be used once for all sixteen reception datasets.
NOTE
The main menu for the IEC 61850 server configuration is shown below.
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL SERVER CONFIGURATION
5
MESSAGE
The IED NAME and LD INST settings represent the MMS domain name (IEC 61850 logical device) where all IEC/MMS logical
nodes are located. Valid characters for these values are upper and lowercase letters, numbers, and the underscore (_)
character, and the first character in the string must be a letter. This conforms to the IEC 61850 standard. The LOCATION is a
variable string and can be composed of ASCII characters. This string appears within the PhyName of the LPHD node.
The IEC/MMS TCP PORT NUMBER setting allows the user to change the TCP port number for MMS connections. The INCLUDE
NON-IEC DATA setting determines whether or not the “UR” MMS domain will be available. This domain contains a large num-
ber of UR-series specific data items that are not available in the IEC 61850 logical nodes. This data does not follow the IEC
61850 naming conventions. For communications schemes that strictly follow the IEC 61850 standard, this setting should be
“Disabled”.
When a 0 value is involved in a change, the changes to the IEC/MMS TCP PORT NUMBER setting take effect when the
D60 is restarted.
NOTE
The SERVER SCANNING feature should be set to “Disabled” when IEC 61850 client/server functionality is not required. IEC
61850 has two modes of functionality: GOOSE/GSSE inter-device communication and client/server communication. If the
GOOSE/GSSE functionality is required without the IEC 61850 client server feature, then server scanning can be disabled
to increase CPU resources. When server scanning is disabled, there is no updating of the IEC 61850 logical node status
values in the D60. Clients are still able to connect to the server (D60 relay), but most data values are not updated. This set-
ting does not affect GOOSE/GSSE operation.
Changes to the IED NAME setting, LD INST setting, and GOOSE dataset take effect when the D60 is restarted.
NOTE
The main menu for the IEC 61850 logical node name prefixes is shown below.
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL
IEC 61850 LOGICAL NODE NAME PREFIXES
IEC 61850 LOGICAL PIOC LOGICAL NODE
NODE NAME PREFIXES NAME PREFIXES
The IEC 61850 logical node name prefix settings are used to create name prefixes to uniquely identify each logical node.
For example, the logical node “PTOC1” may have the name prefix “abc”. The full logical node name will then be
“abcMMXU1”. Valid characters for the logical node name prefixes are upper and lowercase letters, numbers, and the
underscore (_) character, and the first character in the prefix must be a letter. This conforms to the IEC 61850 standard.
Changes to the logical node prefixes will not take effect until the D60 is restarted.
The main menu for the IEC 61850 MMXU deadbands is shown below.
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL MMXU DEADBANDS
MESSAGE
MMXU2 DEADBANDS
5
MMXU3 DEADBANDS
MESSAGE
MMXU4 DEADBANDS
MESSAGE
The MMXU deadband settings represent the deadband values used to determine when the update the MMXU “mag” and
“cVal” values from the associated “instmag” and “instcVal” values. The “mag” and “cVal” values are used for the IEC 61850
buffered and unbuffered reports. These settings correspond to the associated “db” data items in the CF functional con-
straint of the MMXU logical node, as per the IEC 61850 standard. According to IEC 61850-7-3, the db value “shall repre-
sent the percentage of difference between the maximum and minimum in units of 0.001%”. Thus, it is important to know the
maximum value for each MMXU measured quantity, since this represents the 100.00% value for the deadband.
The minimum value for all quantities is 0; the maximum values are as follows:
• phase current: 46 phase CT primary setting
• neutral current: 46 ground CT primary setting
• voltage: 275 VT ratio setting
• power (real, reactive, and apparent): 46 phase CT primary setting 275 VT ratio setting
• frequency: 90 Hz
• power factor: 2
The NUMBER OF STATUS POINTS IN GGIO1 setting specifies the number of “Ind” (single point status indications) that are
instantiated in the GGIO1 logical node. Changes to the NUMBER OF STATUS POINTS IN GGIO1 setting will not take effect until
the D60 is restarted.
The GGIO2 control configuration points are shown below:
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL GGIO2 CONTROL CONFIGURATION
GGIO2 CF SPSCO 1(64)
5 GGIO2 CF SPCSO 1
GGIO2 CF SPCSO 1
CTLMODEL: 1
Range: 0, 1, or 2
The GGIO2 control configuration settings are used to set the control model for each input. The available choices are “0”
(status only), “1” (direct control), and “2” (SBO with normal security). The GGIO2 control points are used to control the D60
virtual inputs.
The GGIO4 analog configuration points are shown below:
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL GGIO4 ANALOG CONFIGURATION
GGIO4 ANALOG 1
MESSAGE
MEASURED VALUE
GGIO4 ANALOG 2
MESSAGE
MEASURED VALUE
GGIO4 ANALOG 3
MESSAGE
MEASURED VALUE
GGIO4 ANALOG 32
MESSAGE
MEASURED VALUE
The NUMBER OF ANALOG POINTS setting determines how many analog data points will exist in GGIO4. When this value is
changed, the D60 must be rebooted in order to allow the GGIO4 logical node to be re-instantiated and contain the newly
configured number of analog points.
The measured value settings for each of the 32 analog values are shown below.
PATH: SETTINGS PRODUCT... COMMUNICATIONS IEC 61850 PROTOCOL GGIO4 ANALOG CONFIGURATION
GGIO4 ANALOG 1(32) MEASURED VALUE
GGIO4 ANALOG 1 ANALOG IN 1 VALUE: Range: any FlexAnalog value
MEASURED VALUE Off
The GGIO5 logical node allows IEC 61850 client access to integer data values. This allows access to as many as 16
unsigned integer value points, associated timestamps, and quality flags. The method of configuration is similar to that of
GGIO1 (binary status values). The settings allow the selection of FlexInteger values for each GGIO5 integer value point.
It is intended that clients use GGIO5 to access generic integer values from the D60. Additional settings are provided to
allow the selection of the number of integer values available in GGIO5 (1 to 16), and to assign FlexInteger values to the
GGIO5 integer inputs. The following setting is available for all GGIO5 configuration points.
• GGIO5 UINT IN 1 VALUE: This setting selects the FlexInteger value to drive each GGIO5 integer status value
(GGIO5.ST.UIntIn1). This setting is stored as an 32-bit unsigned integer value.
To create the dataset for logical node LN, program the ITEM 1 to ITEM 64 settings to a value from the list of IEC 61850 data
attributes supported by the D60. Changes to the dataset will only take effect when the D60 is restarted. It is recommended
to use reporting service from logical node LLN0 if a user needs some (but not all) data from already existing GGIO1,
GGIO4, and MMXU4 points and their quantity is not greater than 64 minus the number items in this dataset.
The breaker configuration settings are shown below. Changes to these values take effect when the UR is restarted:
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL XCBR CONFIGURATION
The XCBR1 SYNCCHECK CLS setting is used to supervise a close command with a synchrocheck condition within XCBR
logical node. If a Close with SynchroCheck is requested (through a SelectWithValue service) and the SynchroCheck condi-
tion is not satisfied, a Negative Response (-Rsp) is issued with the REASON CODE of Blocked-by-synchrocheck.
The XCBR1 INTERLOCK OPN/CLS settings are used to assign an operand, which is linked into the EnaOpn or EnaCls
INTERLOCKED inputs respectively of the XCBR. When this operand is asserted, XCBR logical node inhibits execution of
the open and close commands respectively. If select before operate (SBO) with Extended Security is requested and Inter-
lock condition exists, the UR responds with a Negative response (-Rsp) with the Reason Code Blocked-by-interlocking.
The XCBR1 Pos ctlModel setting is used to select control model per IEC 61850-7-3. The following control models are sup-
ported by URs:
0 — Status only
1 — Direct control with normal security (direct-operate)
2 — SBO control with normal security (operate-once)
3 — Direct control with enhanced security (direct-operate)
4 — SBO control with enhanced security (operate-once)
See IEC 61850-7-2 for complete details on these control models.
The XCBR1 Pos sboTimeout setting is used to select SBO timeout value. To be successful, the IEC 61850 "operate" com-
mand must be executed after the "select" command within the XCBR1 Pos sboTimeout setting value.
The disconnect switch configuration settings are shown below. Changes to these values will not take effect until the UR is
restarted:
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL XSWI CONFIGURATION
5 XSWI
CONFIGURATION
XSWI1 ST.LOC OPERAND
Off
Range: FlexLogic operand
The CLEAR XSWI1 OpCnt setting represents the disconnect switch operating counter. As disconnect switches operate by
opening and closing, the XSWI operating counter status attribute (OpCnt) increments with every operation. Frequent switch
operation may result in very large OpCnt values over time. This setting allows the OpCnt to be reset to “0” for XSWI1.
Since GSSE/GOOSE messages are multicast Ethernet by specification, they are not usually be forwarded by net-
work routers. However, GOOSE messages may be forwarded by routers if the router has been configured for VLAN
NOTE functionality.
The D60 contains an embedded web server and is capable of transferring web pages to a web browser such as Internet
Explorer or Firefox. The web pages are organized as a series of menus that can be accessed starting at the D60 “Main
Menu”. Web pages are available showing DNP and IEC 60870-5-104 points lists, Modbus registers, event records, fault
reports, and so on. First connect the UR and a computer to an Ethernet network, then enter the IP address of the D60 into
the “Address” box of the web browser.
When the port is set to 0, the change takes effect when the D60 is restarted.
NOTE
l) TFTP PROTOCOL
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS TFTP PROTOCOL
The Trivial File Transfer Protocol (TFTP) can be used to transfer files from the D60 over a network. The D60 operates as a
TFTP server. TFTP client software is available from various sources, including Microsoft Windows NT. The dir.txt file
5
obtained from the D60 contains a list and description of all available files (event records, oscillography, etc.).
When the TFTP MAIN UDP PORT NUMBER is set to 0, the change takes effect when the D60 is restarted.
NOTE
The D60 supports the IEC 60870-5-104 protocol. The D60 can be used as an IEC 60870-5-104 slave device connected to
a maximum of two masters (usually either an RTU or a SCADA master station). Since the D60 maintains two sets of IEC
60870-5-104 data change buffers, no more than two masters should actively communicate with the D60 at one time.
The IEC ------- DEFAULT THRESHOLD settings are used to determine when to trigger spontaneous responses containing
M_ME_NC_1 analog data. These settings group the D60 analog data into types: current, voltage, power, energy, and other.
Each setting represents the default threshold value for all M_ME_NC_1 analog points of that type. For example, to trigger
spontaneous responses from the D60 when any current values change by 15 A, the IEC CURRENT DEFAULT THRESHOLD set-
ting should be set to 15. Note that these settings are the default values of the deadbands. P_ME_NC_1 (parameter of mea-
sured value, short floating point value) points can be used to change threshold values, from the default, for each individual
M_ME_NC_1 analog point. Whenever power is removed and re-applied to the D60, the default thresholds are in effect.
The IEC REDUNDANCY setting decides whether multiple client connections are accepted or not. If redundancy is set to Yes,
two simultaneous connections can be active at any given time.
When the IEC port number is set to 0, the change takes effect when the D60 is restarted.
NOTE
The IEC 60870-5-104 and DNP protocols cannot be used simultaneously. When the IEC 60870-5-104 FUNCTION
setting is set to “Enabled”, the DNP protocol does not operate. When this setting is changed, it takes effect when
NOTE
power to the relay is cycled (off-to-on).
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 60870-5-104 PROTOCOL IEC NETWORK CLIENT
ADDRESSES
The UR can specify a maximum of five clients for its IEC 104 connections. These are IP addresses for the controllers to
which the UR can connect.
A maximum of two simultaneous connections are supported at any given time.
The Modbus user map provides read-only access for up to 256 registers. To obtain a memory map value, enter the desired
address in the ADDRESS line (converted from hex to decimal format). The corresponding value displays in the VALUE line. A
value of “0” in subsequent register ADDRESS lines automatically returns values for the previous ADDRESS lines incremented
by “1”. An address value of “0” in the initial register means “none” and values of “0” display for all registers. Different
ADDRESS values can be entered as required in any of the register positions.
a) MAIN MENU
PATH: SETTINGS PRODUCT SETUP REAL TIME CLOCK
The relay contains a real time clock (RTC) to create timestamps for communications protocols as well as for historical data,
such as event records and oscillography. When the relay restarts, the RTC initializes from an onboard battery-backed
clock, which has the same accuracy as an electronic watch, approximately ±1 minute per month (~23 ppm). Once the RTC
is synchronized with the Precision Time Protocol (PTP), IRIG-B, or SNTP, its accuracy approaches that of the synchroniz-
ing time delivered to the relay.
5 The SYNCHRONIZING SOURCE setting configures the priority sequence that the relay uses to determine which of the avail-
able external time sources synchronizes the RTC and the synchrophasor clock. A setting of None causes the RTC and the
synchrophasor clock to free-run. A setting of PP/IRIGB/PTP/SNTP, IRIGB/PP/PTP/SNTP, or PP/PTP/IRIGB/SNTP causes
the relay to track the first source named that is enabled and operational, or free-run if none of these are available. Here, PP
means a time source that is strictly compliant with PP, PTP means a time source that is not strictly compliant with PP. When
a time source fails or recovers, the relay automatically transfers synchronization as required by this setting.
See the COMMANDS SET DATE AND TIME menu section of this manual to manually set the RTC.
The REAL TIME CLOCK EVENTS setting allows changes to the date and/or time to be captured in the event record. The event
records the RTC time before the adjustment.
To enable IRIG-B synchronization, the input IRIG-B SIGNAL TYPE must be set to DC Shift or Amplitude Modulated. IRIG-B
synchronization can be disabled by making this setting None.
To configure and enable PTP and/or SNTP, or to set local time parameters (for example time zone, daylight savings), use
the following sections.
PATH: SETTINGS PRODUCT SETUP REAL TIME CLOCK PRECISION TIME PROTOCOL (1588) PTP PORT 1(3)
The UR supports the Precision Time Protocol (PTP) specified in IEEE Std 1588 2008 using the Power Profile (PP) specified
in IEEE Std C37.238 2011. This enables the relay to synchronize to the international time standard over an Ethernet net-
work that implements PP.
The relay can be configured to operate on some PTP networks that are not strictly PP. Time accuracy can be less than
specified for a PP network. Tolerated deviations from strict PP include 1) missing declaration of PP compliance in the mes-
sages, 2) connection to a network device that does not support the PTP peer delay mechanism, 3) jitter substantially
greater than 1 µs in received event messages, and 4) certain non-compliant announce and sync message update rates.
The relay implements PTP according to IEEE Std 1588 2008 and the equivalent IEC 61588:2009(E), sometimes
referred to as version 2 PTP. It does not support the previous version of the standard (version 1).
NOTE
PTP is a protocol that allows multiple clocks in a network to synchronize with one another. It permits synchronization accu-
racies better than 1 ns, but this requires each and every component in the network achieve very high levels of accuracy and
a very high baud rate, faster than normally used for relay communications. When operating over a generic Ethernet net-
work, time error may amount to 1 ms or more. PP is a profile of PTP which specifies a limited subset of PTP suitable for use
in power system protection, control, automation and data communication applications, and thereby facilitates interoperabil-
ity between different vendor’s clocks and switches. PP specifies a worst-case delivered time error of less than 1 µs over a
5
16-hop network.
In a PTP system and in a PP system, the clocks automatically organize themselves into a master-slave synchronization
hierarchy with the “best” clock available making itself the "grandmaster" at the top of the hierarchy; all others make them-
selves “slaves” and track the grandmaster. Typically the grandmaster clock receives its time from GPS satellites or some
other link to the international time standard. If the grandmaster fails, the next “best” clock available in the domain assumes
the grandmaster role. Should a clock on starting up discover it is “better” that the present grandmaster, it assumes the
grandmaster role and the previous grandmaster reverts to slave.
Time messages issued by the grandmaster are delayed as they pass through the network both due to the finite speed of
the signal in the interconnecting fiber or wire. Each clock and switch implementing PP measures the propagation delay to
each of its PP neighbors, and compensates for these delays in the time received. Each network device implementing PP
measures the processing delay it introduces in each time message and compensates for this delay in the time it transmits.
As a result, the time delivered to end-devices such as the UR are virtually identical to the grandmaster time. Should one of
the network devices in the hierarchy not fully implement PP, the associated propagation delay and/or latency may not be
compensated for, and the time received at the end-device could be in error by more than 100 µs.
See the Settings > Product Setup > Real Time Clock section of this manual for a description of when time values
received via PTP are used to update the relay’s real time clock.
The following settings are available for configuring the relay for PTP.
STRICT POWER PROFILE
• Power profile (IEEE Std C37.238 2011) requires that the relay only select as a grandmaster power profile compliant
clocks, that the delivered time have worst-case error of ±1 µs, and that the peer delay mechanism be implemented.
With the strict power profile setting enabled, the relay will only select as master clocks displaying the IEEE_C37_238
identification codes. It will use a port only when the peer delay mechanism is operational. With the strict power profile
setting disabled, the relay will use clocks without the power profile identification when no power profile clocks are pres-
ent, and will use ports even if the peer delay mechanism is non-operational.
• This setting applies to all of the relay’s PTP capable ports.
c) SNTP PROTOCOL
PATH: SETTINGS PRODUCT SETUP REAL TIME CLOCK SNTP PROTOCOL
The D60 supports the Simple Network Time Protocol specified in RFC-2030. With SNTP, the D60 can obtain clock time
over an Ethernet network. The D60 acts as an SNTP client to receive time values from an SNTP/NTP server, usually a ded-
icated product using a GPS receiver to provide an accurate time. Unicast SNTP is supported. The UR-series relays do not
support the broadcast, multicast or anycast SNTP functionality.
The SNTP FUNCTION setting enables or disabled the SNTP feature on the D60.
To use SNTP, SNTP SERVER IP ADDR must be set to the SNTP/NTP server IP address. Once this address is set and SNTP
FUNCTION is “Enabled”, the D60 attempts to obtain time values from the SNTP/NTP server. Since many time values are
obtained and averaged, it generally takes three to four minutes until the D60 clock is closely synchronized with the SNTP/
NTP server. It takes up to two minutes for the D60 to signal an SNTP self-test error if the server is offline.
The SNTP UDP PORT NUMBER is 123 for normal SNTP operation. If SNTP is not required, close the port by setting it to 0.
When the SNTP UDP PORT NUMBER is set to 0, the change takes effect when the D60 is restarted.
NOTE
d) LOCAL TIME 5
PATH: SETTINGS PRODUCT SETUP REAL TIME CLOCK LOCAL TIME
LOCAL TIME LOCAL TIME OFFSET Range: –24.0 to 24.0 hrs in steps of 0.5
FROM UTC: 0.0 hrs
DAYLIGHT SAVINGS Range: Disabled, Enabled
MESSAGE
TIME: Disabled
DST START MONTH: Range: January to December (all months)
MESSAGE
January
DST START DAY: Range: Sunday to Saturday (all days of the week)
MESSAGE
Sunday
DST START DAY Range: First, Second, Third, Fourth, Last
MESSAGE
INSTANCE: First
DST START HOUR: Range: 0 to 23
MESSAGE
2
DST STOP MONTH: Range: January to December (all months)
MESSAGE
January
DST STOP DAY: Range: Sunday to Saturday (all days of the week)
MESSAGE
Sunday
DST STOP DAY Range: First, Second, Third, Fourth, Last
MESSAGE
INSTANCE: First
DST STOP HOUR: Range: 0 to 23
MESSAGE
2
The UR device maintains two times: local time and Universal Coordinated Time (UTC). Local time can be provided by IRIG-
B signals. UTC time is provided by SNTP servers.
The real-time clock (RTC) and communication protocol times are not correct unless Local Time is configured for the current
location. When the RTC is synchronized with IRIG-B, Local Time must be configured for the current location or else the
timestamps may not be accurate. Furthermore, times reported in historical records and communication protocols may be
incorrect if the Local Time setting is not configured properly.
The LOCAL TIME OFFSET FROM UTC setting is used to specify the local time zone offset from UTC (Greenwich Mean Time) in
hours. Time zones in the eastern hemisphere have positive values; time zones in the western hemisphere have negative
values. A value of zero causes the relay to use UTC for local time. This setting has two uses. When the system RTC is syn-
chronized with a communications protocol providing only local time or it is free-running, the offset setting is used to calcu-
late UTC from the local time these provide. When the RTC is synchronized with a communications protocol providing only
UTC (such as PTP or SNTP), the time offset setting is used to determine local time from the UTC provided. PTP
ALTERNATE_TIME_OFFSET_INDICATOR TLVs are not used to calculate local time. When a communications protocol
other than PTP provides UTC to local time offset (meaning IRIG-B), that offset is used instead of the local time and daylight
time settings.
The DAYLIGHT SAVINGS TIME (DST) settings can be used to allow the relay to follow the DST rules of the local time zone.
Note that when IRIG-B time synchronization is active, the local time in the IRIG-B signal contains any daylight savings time
offset and so the DST settings are ignored.
5
MESSAGE
Off
FAULT REPORT 1 Z1 Range: 0.01 to 250.00 ohms in steps of 0.01
MESSAGE
MAG: 3.00
FAULT REPORT 1 Z1 Range: 25 to 90° in steps of 1
MESSAGE
ANGLE: 75°
FAULT REPORT 1 Z0 Range: 0.01 to 650.00 ohms in steps of 0.01
MESSAGE
MAG: 9.00
FAULT REPORT 1 Z0 Range: 25 to 90° in steps of 1
MESSAGE
ANGLE: 75°
FAULT REPORT 1 LINE Range: km, miles
MESSAGE
LENGTH UNITS: km
FAULT REP 1 LENGTH Range: 0.0 to 2000.0 in steps of 0.1
MESSAGE
(km ): 100.0
FAULT REPORT 1 VT Range: None, I0, V0
MESSAGE
SUBSTITUTION: None
FAULT REP 1 SYSTEM Range: 0.01 to 650.00 ohms in steps of 0.01
MESSAGE
Z0 MAG: 2.00
FAULT REP 1 SYSTEM Range: 25 to 90° in steps of 1
MESSAGE
Z0 ANGLE: 75°
The D60 relay supports one fault report and an associated fault locator. The signal source and trigger condition, as well as
the characteristics of the line or feeder, are entered in this menu.
The fault report stores data, in non-volatile memory, pertinent to an event when triggered. The captured data contained in
the FaultReport.txt file includes:
• Fault report number.
• Name of the relay, programmed by the user.
The FAULT REPORT 1 VT SUBSTITUTION setting shall be set to “None” if the relay is fed from wye-connected VTs. If delta-con-
nected VTs are used, and the relay is supplied with the neutral (3V0) voltage, this setting shall be set to “V0”. The method is
still exact, as the fault locator would combine the line-to-line voltage measurements with the neutral voltage measurement
to re-create the line-to-ground voltages. See the ACTUAL VALUES RECORDS FAULT REPORTS menu for additional
details. It required to configure the delta and neutral voltages under the source indicated as input for the fault report. Also,
the relay will check if the auxiliary signal configured is marked as “Vn” by the user (under VT setup), and inhibit the fault
location if the auxiliary signal is labeled differently.
If the broken-delta neutral voltage is not available to the relay, an approximation is possible by assuming the missing zero-
sequence voltage to be an inverted voltage drop produced by the zero-sequence current and the user-specified equivalent
zero-sequence system impedance behind the relay: V0 = –Z0 I0. In order to enable this mode of operation, the FAULT
REPORT 1 VT SUBSTITUTION setting shall be set to “I0”.
The FAULT REP 1 SYSTEM Z0 MAG and FAULT REP 1 SYSTEM Z0 ANGLE settings are used only when the VT SUBSTITUTION set-
ting value is “I0”. The magnitude is to be entered in secondary ohms. This impedance is an average system equivalent
behind the relay. It can be calculated as zero-sequence Thevenin impedance at the local bus with the protected line/feeder
disconnected. The method is accurate only if this setting matches perfectly the actual system impedance during the fault. If
the system exhibits too much variability, this approach is questionable and the fault location results for single-line-to-ground
faults shall be trusted with accordingly. It should be kept in mind that grounding points in vicinity of the installation impact
the system zero-sequence impedance (grounded loads, reactors, zig-zag transformers, shunt capacitor banks, etc.).
5.2.8 OSCILLOGRAPHY
a) MAIN MENU
PATH: SETTINGS PRODUCT SETUP OSCILLOGRAPHY
5 MESSAGE
ANALOG CHANNELS
Oscillography records contain waveforms captured at the sampling rate as well as other relay data at the point of trigger.
Oscillography records are triggered by a programmable FlexLogic operand. Multiple oscillography records may be captured
simultaneously.
The NUMBER OF RECORDS is selectable, but the number of cycles captured in a single record varies considerably based on
other factors such as sample rate and the number of operational modules. There is a fixed amount of data storage for oscil-
lography; the more data captured, the less the number of cycles captured per record. See the ACTUAL VALUES
RECORDS OSCILLOGRAPHY menu to view the number of cycles captured per record. The following table provides sam-
ple configurations with corresponding cycles/record. The minimum number of oscillographic records is three.
A new record may automatically overwrite an older record if TRIGGER MODE is set to “Automatic Overwrite”.
Set the TRIGGER POSITION to a percentage of the total buffer size (for example, 10%, 50%, 75%, etc.). A trigger position of
25% consists of 25% pre- and 75% post-trigger data. The TRIGGER SOURCE is always captured in oscillography and may be
any FlexLogic parameter (element state, contact input, virtual output, etc.). The relay sampling rate is 64 samples per cycle.
The AC INPUT WAVEFORMS setting determines the sampling rate at which AC input signals (that is, current and voltage) are
stored. Reducing the sampling rate allows longer records to be stored. This setting has no effect on the internal sampling
rate of the relay which is always 64 samples per cycle; that is, it has no effect on the fundamental calculations of the device.
When changes are made to the oscillography settings, all existing oscillography records will be CLEARED.
NOTE
b) DIGITAL CHANNELS
PATH: SETTINGS PRODUCT SETUP OSCILLOGRAPHY DIGITAL CHANNELS
A DIGITAL 1(63) CHANNEL setting selects the FlexLogic operand state recorded in an oscillography trace. The length of each
oscillography trace depends in part on the number of parameters selected here. Parameters set to “Off” are ignored. Upon
startup, the relay will automatically prepare the parameter list.
c) ANALOG CHANNELS 5
PATH: SETTINGS PRODUCT SETUP OSCILLOGRAPHY ANALOG CHANNELS
These settings select the metering actual value recorded in an oscillography trace. The length of each oscillography trace
depends in part on the number of parameters selected here. Parameters set to “Off” are ignored. The parameters available
in a given relay are dependent on:
• The type of relay,
• The type and number of CT/VT hardware modules installed, and
• The type and number of analog input hardware modules installed.
Upon startup, the relay will automatically prepare the parameter list. A list of all possible analog metering actual value
parameters is presented in Appendix A: FlexAnalog parameters. The parameter index number shown in any of the tables is
used to expedite the selection of the parameter on the relay display. It can be quite time-consuming to scan through the list
of parameters via the relay keypad and display - entering this number via the relay keypad will cause the corresponding
parameter to be displayed.
All eight CT/VT module channels are stored in the oscillography file. The CT/VT module channels are named as follows:
<slot_letter><terminal_number>—<I or V><phase A, B, or C, or 4th input>
The fourth current input in a bank is called IG, and the fourth voltage input in a bank is called VX. For example, F2-IB desig-
nates the IB signal on terminal 2 of the CT/VT module in slot F.
If there are no CT/VT modules and analog input modules, no analog traces will appear in the file; only the digital traces will
appear.
The data logger samples and records up to 16 analog parameters at a user-defined sampling rate. This recorded data may
be downloaded to EnerVista UR Setup and displayed with parameters on the vertical axis and time on the horizontal axis.
All data is stored in non-volatile memory, meaning that the information is retained when power to the relay is lost.
For a fixed sampling rate, the data logger can be configured with a few channels over a long period or a larger number of
channels for a shorter period. The relay automatically partitions the available memory between the channels in use. Exam-
ple storage capacities for a system frequency of 60 Hz are shown in the following table.
Changing any setting affecting data logger operation will clear any data that is currently in the log.
NOTE
• DATA LOGGER MODE: This setting configures the mode in which the data logger will operate. When set to “Continu-
ous”, the data logger will actively record any configured channels at the rate as defined by the DATA LOGGER RATE. The
5
data logger will be idle in this mode if no channels are configured. When set to “Trigger”, the data logger will begin to
record any configured channels at the instance of the rising edge of the DATA LOGGER TRIGGER source FlexLogic oper-
and. The data logger will ignore all subsequent triggers and will continue to record data until the active record is full.
Once the data logger is full a CLEAR DATA LOGGER command is required to clear the data logger record before a new
record can be started. Performing the CLEAR DATA LOGGER command will also stop the current record and reset the
data logger to be ready for the next trigger.
• DATA LOGGER TRIGGER: This setting selects the signal used to trigger the start of a new data logger record. Any
FlexLogic operand can be used as the trigger source. The DATA LOGGER TRIGGER setting only applies when the mode
is set to “Trigger”.
• DATA LOGGER RATE: This setting selects the time interval at which the actual value data will be recorded.
• DATA LOGGER CHNL 1(16): This setting selects the metering actual value that is to be recorded in Channel 1(16) of
the data log. The parameters available in a given relay are dependent on: the type of relay, the type and number of CT/
VT hardware modules installed, and the type and number of Analog Input hardware modules installed. Upon startup,
the relay will automatically prepare the parameter list. A list of all possible analog metering actual value parameters is
shown in Appendix A: FlexAnalog Parameters. The parameter index number shown in any of the tables is used to
expedite the selection of the parameter on the relay display. It can be quite time-consuming to scan through the list of
parameters via the relay keypad/display – entering this number via the relay keypad will cause the corresponding
parameter to be displayed.
• DATA LOGGER CONFIG: This display presents the total amount of time the Data Logger can record the channels not
selected to “Off” without over-writing old data.
a) MAIN MENU
PATH: SETTINGS PRODUCT SETUP USER-PROGRAMMABLE LEDS
USER-PROGRAMMABLE
MESSAGE
LED48
The 48 amber LEDs on relay panels 2 and 3 can be customized to illuminate when a selected FlexLogic operand is in the
logic 1 state. The trip and alarm LEDs on panel 1 can also be customized in a similar manner. To ensure correct functional-
ity of all LEDs, an LED test feature is also provided.
b) LED TEST
When enabled, the LED test can be initiated from any digital input or user-programmable condition such as user-program-
mable pushbutton. The control operand is configured under the LED TEST CONTROL setting. The test covers all LEDs,
including the LEDs of the optional user-programmable pushbuttons.
The test consists of three stages.
1. All 62 LEDs on the relay are illuminated. This is a quick test to verify if any of the LEDs is “burned”. This stage lasts as
long as the control input is on, up to a maximum of 1 minute. After 1 minute, the test will end.
2. All the LEDs are turned off, and then one LED at a time turns on for 1 second, then back off. The test routine starts at
the top left panel, moving from the top to bottom of each LED column. This test checks for hardware failures that lead
to more than one LED being turned on from a single logic point. This stage can be interrupted at any time.
3. All the LEDs are turned on. One LED at a time turns off for 1 second, then back on. The test routine starts at the top left
panel moving from top to bottom of each column of the LEDs. This test checks for hardware failures that lead to more
than one LED being turned off from a single logic point. This stage can be interrupted at any time.
When testing is in progress, the LEDs are controlled by the test sequence, rather than the protection, control, and monitor-
ing features. However, the LED control mechanism accepts all the changes to LED states generated by the relay and
stores the actual LED states (on or off) in memory. When the test completes, the LEDs reflect the actual state resulting from
relay response during testing. The reset pushbutton will not clear any targets when the LED Test is in progress.
A dedicated FlexLogic operand, LED TEST IN PROGRESS, is set for the duration of the test. When the test sequence is initi-
ated, the LED TEST INITIATED event is stored in the event recorder.
The entire test procedure is user-controlled. In particular, stage 1 can last as long as necessary, and stages 2 and 3 can be
interrupted. The test responds to the position and rising edges of the control input defined by the LED TEST CONTROL set-
ting. The control pulses must last at least 250 ms to take effect. The following diagram explains how the test is executed.
READY TO TEST
Reset the
LED TEST IN PROGRESS
rising edge of the
operand
control input
Set the
LED TEST IN PROGRESS
operand
control input is on
STAGE 1 time-out
(all LEDs on) (1 minute)
5
control input
rising edge
STAGE 3
of the control
(one LED off at a time) input
842011A1.CDR
Configure the LED test to recognize user-programmable pushbutton 1 by making the following entries in the SETTINGS
PRODUCT SETUP USER-PROGRAMMABLE LEDS LED TEST menu:
The test will be initiated when the user-programmable pushbutton 1 is pressed. The pushbutton should remain pressed for
as long as the LEDs are being visually inspected. When finished, the pushbutton should be released. The relay will then
automatically start stage 2. At this point forward, test may be aborted by pressing the pushbutton.
APPLICATION EXAMPLE 2:
Assume one needs to check if any LEDs are “burned” as well as exercise one LED at a time to check for other failures. This
is to be performed via user-programmable pushbutton 1.
After applying the settings in application example 1, hold down the pushbutton as long as necessary to test all LEDs. Next,
release the pushbutton to automatically start stage 2. Once stage 2 has started, the pushbutton can be released. When
stage 2 is completed, stage 3 will automatically start. The test may be aborted at any time by pressing the pushbutton.
TRIP & ALARM LEDS TRIP LED INPUT: Range: FlexLogic operand
Off
ALARM LED INPUT: Range: FlexLogic operand
MESSAGE
Off
The trip and alarm LEDs are in the first LED column (enhanced faceplate) and on LED panel 1 (standard faceplate). Each
indicator can be programmed to become illuminated when the selected FlexLogic operand is in the logic 1 state.
There are 48 amber LEDs across the relay faceplate LED panels. Each of these indicators can be programmed to illumi-
nate when the selected FlexLogic operand is in the logic 1 state.
For the standard faceplate, the LEDs are located as follows.
• LED Panel 2: user-programmable LEDs 1 through 24
Refer to the Control of setting groups example in the Control elements section of this chapter for group activation.
For user-programmable self-tests for CyberSentry, use the Setup > Security > Supervisory menu instead.
PATH: SETTINGS PRODUCT SETUP USER-PROGRAMMABLE SELF TESTS
USER-PROGRAMMABLE DIRECT RING BREAK Range: Disabled, Enabled. Valid for units equipped with
SELF TESTS FUNCTION: Enabled Direct Input/Output module.
DIRECT DEVICE OFF Range: Disabled, Enabled. Valid for units equipped with
MESSAGE Direct Input/Output module.
FUNCTION: Enabled
REMOTE DEVICE OFF Range: Disabled, Enabled.
MESSAGE
FUNCTION: Enabled
FIRST ETHERNET FAIL Range: Disabled, Enabled.
MESSAGE
FUNCTION: Disabled
SEC. ETHERNET FAIL Range: Disabled, Enabled.
MESSAGE
FUNCTION: Disabled
THIRD ETHERNET FAIL Range: Disabled, Enabled.
MESSAGE
FUNCTION: Disabled
BATTERY FAIL Range: Disabled, Enabled.
MESSAGE
FUNCTION: Enabled
MESSAGE
SNTP FAIL
FUNCTION: Enabled
Range: Disabled, Enabled.
5
IRIG-B FAIL Range: Disabled, Enabled.
MESSAGE
FUNCTION: Enabled
PTP FAIL Range: Disabled, Enabled.
MESSAGE
FUNCTION: Enabled
SFP MODULE FAIL Range: Disabled, Enabled.
MESSAGE
FUNCTION: Disabled
All major self-test alarms are reported automatically with their corresponding FlexLogic operands, events, and targets. Most
of the minor alarms can be disabled if desired.
When in the “Disabled” mode, minor alarms will not assert a FlexLogic operand, write to the event recorder, or display tar-
get messages. Moreover, they will not trigger the ANY MINOR ALARM or ANY SELF-TEST messages. When in the “Enabled”
mode, minor alarms continue to function along with other major and minor alarms. Refer to the Relay self-tests section in
chapter 7 for additional information on major and minor self-test alarms.
There are three standard control pushbuttons, labeled USER 1, USER 2, and USER 3, on the standard and enhanced front
panels. These are user-programmable and can be used for various applications such as performing an LED test, switching
setting groups, and invoking and scrolling though user-programmable displays.
Firmware revisions 3.2x and older use these three pushbuttons for manual breaker control. This functionality has been
retained – if the breaker control feature is configured to use the three pushbuttons, they cannot be used as user-program-
mable control pushbuttons.
The location of the control pushbuttons are shown in the following figures.
Control pushbuttons
842813A1.CDR
5
USER 4
842733A2.CDR
SETTING
CONTROL PUSHBUTTON
{
1 FUNCTION:
Enabled=1
SETTINGS
SYSTEM SETUP/
BREAKERS/BREAKER 1/
BREAKER 1 PUSHBUTTON
CONTROL:
When applicable
AND RUN
Enabled=1
OFF TIMER
SYSTEM SETUP/ FLEXLOGIC OPERAND
BREAKERS/BREAKER 2/ ON 0 CONTROL PUSHBTN 1 ON
BREAKER 2 PUSHBUTTON 100 msec
CONTROL:
842010A2.CDR
Enabled=1
The optional user-programmable pushbuttons (specified in the order code) provide an easy and error-free method of enter-
ing digital state (on, off) information. The number of available pushbuttons is dependent on the faceplate module ordered
with the relay.
• Type P faceplate: standard horizontal faceplate with 12 user-programmable pushbuttons.
• Type Q faceplate: enhanced horizontal faceplate with 16 user-programmable pushbuttons.
The digital state can be entered locally (by directly pressing the front panel pushbutton) or remotely (via FlexLogic oper-
ands) into FlexLogic equations, protection elements, and control elements. Typical applications include breaker control,
autorecloser blocking, and setting groups changes. The user-programmable pushbuttons are under the control level of
password protection.
The user-configurable pushbuttons for the enhanced faceplate are shown below.
USER USER USER USER USER USER USER USER USER USER USER USER USER USER USER USER
LABEL 1 LABEL 2 LABEL 3 LABEL 4 LABEL 5 LABEL 6 LABEL 7 LABEL 8 LABEL 9 LABEL 10 LABEL 11 LABEL 12 LABEL 13 LABEL 14 LABEL 15 LABEL 16
842814A1.CDR
5 1
USER LABEL
3
USER LABEL
5
USER LABEL
7
USER LABEL
9
USER LABEL
11
USER LABEL
2 4 6 8 10 12
USER LABEL USER LABEL USER LABEL USER LABEL USER LABEL USER LABEL
842779A1.CDR
The pushbuttons can be automatically controlled by activating the operands assigned to the PUSHBTN 1 SET (for latched and
self-reset mode) and PUSHBTN 1 RESET (for latched mode only) settings. The pushbutton reset status is declared when the
PUSHBUTTON 1 OFF operand is asserted. The activation and deactivation of user-programmable pushbuttons is dependent
on whether latched or self-reset mode is programmed.
• Latched mode: In latched mode, a pushbutton can be set (activated) by asserting the operand assigned to the PUSH-
BTN 1 SET setting or by directly pressing the associated front panel pushbutton. The pushbutton maintains the set state
until deactivated by the reset command or after a user-specified time delay. The state of each pushbutton is stored in
non-volatile memory and maintained through a loss of control power.
The pushbutton is reset (deactivated) in latched mode by asserting the operand assigned to the PUSHBTN 1 RESET set-
ting or by directly pressing the associated active front panel pushbutton.
It can also be programmed to reset automatically through the PUSHBTN 1 AUTORST and PUSHBTN 1 AUTORST DELAY set-
tings. These settings enable the autoreset timer and specify the associated time delay. The autoreset timer can be
used in select-before-operate (SBO) breaker control applications, where the command type (close/open) or breaker
location (feeder number) must be selected prior to command execution. The selection must reset automatically if con-
trol is not executed within a specified time period.
• Self-reset mode: In self-reset mode, a pushbutton will remain active for the time it is pressed (the pulse duration) plus
the dropout time specified in the PUSHBTN 1 DROP-OUT TIME setting. If the pushbutton is activated via FlexLogic, the
pulse duration is specified by the PUSHBTN 1 DROP-OUT TIME only. The time the operand remains assigned to the PUSH-
BTN 1 SET setting has no effect on the pulse duration.
The pushbutton is reset (deactivated) in self-reset mode when the dropout delay specified in the PUSHBTN 1 DROP-OUT
TIMEsetting expires.
The pulse duration of the remote set, remote reset, or local pushbutton must be at least 50 ms to operate the push-
button. This allows the user-programmable pushbuttons to properly operate during power cycling events and vari-
NOTE ous system disturbances that may cause transient assertion of the operating signals.
The local and remote operation of each user-programmable pushbutton can be inhibited through the PUSHBTN 1 LOCAL and
PUSHBTN 1 REMOTE settings, respectively. If local locking is applied, the pushbutton will ignore set and reset commands
executed through the front panel pushbuttons. If remote locking is applied, the pushbutton will ignore set and reset com-
mands executed through FlexLogic operands.
The locking functions are not applied to the autorestart feature. In this case, the inhibit function can be used in SBO control
operations to prevent the pushbutton function from being activated and ensuring “one-at-a-time” select operation.
The locking functions can also be used to prevent the accidental pressing of the front panel pushbuttons. The separate
inhibit of the local and remote operation simplifies the implementation of local/remote control supervision.
Pushbutton states can be logged by the event recorder and displayed as target messages. In latched mode, user-defined
messages can also be associated with each pushbutton and displayed when the pushbutton is on or changing to off. 5
• PUSHBUTTON 1 FUNCTION: This setting selects the characteristic of the pushbutton. If set to “Disabled”, the push-
button is not active and the corresponding FlexLogic operands (both “On” and “Off”) are de-asserted. If set to “Self-
Reset”, the control logic is activated by the pulse (longer than 100 ms) issued when the pushbutton is being physically
pressed or virtually pressed via a FlexLogic operand assigned to the PUSHBTN 1 SET setting.
When in “Self-Reset” mode and activated locally, the pushbutton control logic asserts the “On” corresponding Flex-
Logic operand as long as the pushbutton is being physically pressed, and after being released the deactivation of the
operand is delayed by the drop out timer. The “Off” operand is asserted when the pushbutton element is deactivated. If
the pushbutton is activated remotely, the control logic of the pushbutton asserts the corresponding “On” FlexLogic
operand only for the time period specified by the PUSHBTN 1 DROP-OUT TIME setting.
If set to “Latched”, the control logic alternates the state of the corresponding FlexLogic operand between “On” and “Off”
on each button press or by virtually activating the pushbutton (assigning set and reset operands). When in the
“Latched” mode, the states of the FlexLogic operands are stored in a non-volatile memory. Should the power supply be
lost, the correct state of the pushbutton is retained upon subsequent power up of the relay.
• PUSHBTN 1 ID TEXT: This setting specifies the top 20-character line of the user-programmable message and is
intended to provide ID information of the pushbutton. Refer to the User-definable displays section for instructions on
how to enter alphanumeric characters from the keypad.
• PUSHBTN 1 ON TEXT: This setting specifies the bottom 20-character line of the user-programmable message and is
displayed when the pushbutton is in the “on” position. Refer to the User-definable displays section for instructions on
entering alphanumeric characters from the keypad.
• PUSHBTN 1 OFF TEXT: This setting specifies the bottom 20-character line of the user-programmable message and is
displayed when the pushbutton is activated from the on to the off position and the PUSHBUTTON 1 FUNCTION is
“Latched”. This message is not displayed when the PUSHBUTTON 1 FUNCTION is “Self-reset” as the pushbutton operand
status is implied to be “Off” upon its release. The length of the “Off” message is configured with the PRODUCT SETUP
DISPLAY PROPERTIES FLASH MESSAGE TIME setting.
• PUSHBTN 1 HOLD: This setting specifies the time required for a pushbutton to be pressed before it is deemed active.
This timer is reset upon release of the pushbutton. Note that any pushbutton operation will require the pushbutton to be
pressed a minimum of 50 ms. This minimum time is required prior to activating the pushbutton hold timer.
• PUSHBTN 1 SET: This setting assigns the FlexLogic operand serving to operate the pushbutton element and to assert
PUSHBUTTON 1 ON operand. The duration of the incoming set signal must be at least 100 ms.
• PUSHBTN 1 RESET: This setting assigns the FlexLogic operand serving to reset pushbutton element and to assert
PUSHBUTTON 1 OFF operand. This setting is applicable only if pushbutton is in latched mode. The duration of the
incoming reset signal must be at least 50 ms.
• PUSHBTN 1 AUTORST: This setting enables the user-programmable pushbutton autoreset feature. This setting is
applicable only if the pushbutton is in the “Latched” mode.
• PUSHBTN 1 AUTORST DELAY: This setting specifies the time delay for automatic reset of the pushbutton when in
the latched mode.
• PUSHBTN 1 REMOTE: This setting assigns the FlexLogic operand serving to inhibit pushbutton operation from the
operand assigned to the PUSHBTN 1 SET or PUSHBTN 1 RESET settings.
• PUSHBTN 1 LOCAL: This setting assigns the FlexLogic operand serving to inhibit pushbutton operation from the front
panel pushbuttons. This locking functionality is not applicable to pushbutton autoreset.
• PUSHBTN 1 DROP-OUT TIME: This setting applies only to “Self-Reset” mode and specifies the duration of the push-
button active status after the pushbutton has been released. When activated remotely, this setting specifies the entire
activation time of the pushbutton status; the length of time the operand remains on has no effect on the pulse duration.
This setting is required to set the duration of the pushbutton operating pulse.
• PUSHBTN 1 LED CTL: This setting assigns the FlexLogic operand serving to drive pushbutton LED. If this setting is
“Off”, then LED operation is directly linked to PUSHBUTTON 1 ON operand.
• PUSHBTN 1 MESSAGE: If pushbutton message is set to “High Priority”, the message programmed in the PUSHBTN 1
IDand PUSHBTN 1 ON TEXT settings will be displayed undisturbed as long as PUSHBUTTON 1 ON operand is asserted.
The high priority option is not applicable to the PUSHBTN 1 OFF TEXT setting.
5 This message can be temporary removed if any front panel keypad button is pressed. However, ten seconds of keypad
inactivity will restore the message if the PUSHBUTTON 1 ON operand is still active.
If the PUSHBTN 1 MESSAGE is set to “Normal”, the message programmed in the PUSHBTN 1 ID and PUSHBTN 1 ON TEXT
settings will be displayed as long as PUSHBUTTON 1 ON operand is asserted, but not longer than time period specified
by FLASH MESSAGE TIME setting. After the flash time is expired, the default message or other active target message is
displayed. The instantaneous reset of the flash message will be executed if any relay front panel button is pressed or
any new target or message becomes active.
The PUSHBTN 1 OFF TEXT setting is linked to PUSHBUTTON 1 OFF operand and will be displayed in conjunction with
PUSHBTN 1 ID only if pushbutton element is in the “Latched” mode. The PUSHBTN 1 OFF TEXT message will be displayed
as “Normal” if the PUSHBTN 1 MESSAGE setting is “High Priority” or “Normal”.
• PUSHBUTTON 1 EVENTS: If this setting is enabled, each pushbutton state change will be logged as an event into
event recorder.
SETTING
Function
LATCHED To user-programmable
= Enabled
pushbuttons logic
= Latched sheet 2, 842024A2
OR LATCHED/SELF-RESET
= Self-Reset
SETTING
Local Lock
Off = 0
Non-volatile latch
AND
S
TIMER
SETTING Latch
50 ms
Remote Lock R
Off = 0 AND
0
SETTING OR
TIMER
Hold 50 ms
TPKP
0
0
OR
SETTING
Set AND
Off = 0
To user-programmable
OR PUSHBUTTON ON pushbuttons logic
OR
sheet 2, 842024A2
SETTING
Reset AND
5
Off = 0
AND
SETTING
SETTING
Autoreset Delay
Autoreset Function
TPKP
= Enabled
AND
= Disabled
0
AND
SETTING
Drop-Out Timer
TIMER 0
FLEXLOGIC OPERAND 200 ms OR
TRST
PUSHBUTTON 1 ON
0
842021A3.CDR
AND
LCD MESSAGE
ENGAGE MESSAGE
SETTING
LATCHED Flash Message Time
SETTINGS
0 Top Text
AND
OR TRST = XXXXXXXXXX
On Text
= XXXXXXXXXX
Instantaneous
From user-programmable reset *
pushbuttons logic
sheet 1, 842021A3
FLEXLOGIC OPERAND
LATCHED/SELF-RESET
AND PUSHBUTTON 1 OFF
FLEXLOGIC OPERAND
PUSHBUTTON ON PUSHBUTTON 1 ON
Instantaneous
Instantaneous reset will be executed if any reset *
front panel button is pressed or any new
5
target or message becomes active.
PUSHBUTTON 1 LED LOGIC
1. If pushbutton 1 LED control is set to off.
Pushbutton 1
FLEXLOGIC OPERAND LED
FLEXLOGIC OPERAND PUSHBUTTON 1 ON
PUSHBUTTON 1 ON
PUSHBUTTON 2 ON 2. If pushbutton 1 LED control is not set to off.
FLEXLOGIC OPERAND
PUSHBUTTON 3 ON SETTING Pushbutton 1
OR ANY PB ON
PUSHBTN 1 LED CTL LED
This feature provides a mechanism where any of 256 selected FlexLogic operand states can be used for efficient monitor-
ing. The feature allows user-customized access to the FlexLogic operand states in the relay. The state bits are packed so
that 16 states may be read out in a single Modbus register. The state bits can be configured so that all of the states which
are of interest to the user are available in a minimum number of Modbus registers.
The state bits may be read out in the “Flex States” register array beginning at Modbus address 0900h. Sixteen states are
packed into each register, with the lowest-numbered state in the lowest-order bit. There are sixteen registers to accommo-
date the 256 state bits.
a) MAIN MENU
PATH: SETTINGS PRODUCT SETUP USER-DEFINABLE DISPLAYS
MESSAGE
USER DISPLAY 16
Range: up to 20 alphanumeric characters
5
This menu provides a mechanism for manually creating up to 16 user-defined information displays in a convenient viewing
sequence in the USER DISPLAYS menu (between the TARGETS and ACTUAL VALUES top-level menus). The sub-menus facili-
tate text entry and Modbus register data pointer options for defining the user display content.
Once programmed, the user-definable displays can be viewed in two ways.
• KEYPAD: Use the MENU key to select the USER DISPLAYS menu item to access the first user-definable display (note
that only the programmed screens are displayed). The screens can be scrolled using the UP and DOWN keys. The
display disappears after the default message time-out period specified by the PRODUCT SETUP DISPLAY PROPER-
TIES DEFAULT MESSAGE TIMEOUT setting.
• USER-PROGRAMMABLE CONTROL INPUT: The user-definable displays also respond to the INVOKE AND SCROLL
setting. Any FlexLogic operand (in particular, the user-programmable pushbutton operands), can be used to navigate
the programmed displays.
On the rising edge of the configured operand (such as when the pushbutton is pressed), the displays are invoked by
showing the last user-definable display shown during the previous activity. From this moment onward, the operand
acts exactly as the down key and allows scrolling through the configured displays. The last display wraps up to the first
one. The INVOKE AND SCROLL input and the DOWN key operate concurrently.
When the default timer expires (set by the DEFAULT MESSAGE TIMEOUT setting), the relay will start to cycle through the
user displays. The next activity of the INVOKE AND SCROLL input stops the cycling at the currently displayed user dis-
play, not at the first user-defined display. The INVOKE AND SCROLL pulses must last for at least 250 ms to take effect.
Any existing system display can be automatically copied into an available user display by selecting the existing display and
pressing the ENTER key. The display will then prompt ADD TO USER DISPLAY LIST?. After selecting “Yes”, a message indi-
cates that the selected display has been added to the user display list. When this type of entry occurs, the sub-menus are
automatically configured with the proper content – this content may subsequently be edited.
5 This menu is used to enter user-defined text and user-selected Modbus-registered data fields into the particular user dis-
play. Each user display consists of two 20-character lines (top and bottom). The tilde (~) character is used to mark the start
of a data field – the length of the data field needs to be accounted for. Up to five separate data fields can be entered in a
user display – the nth tilde (~) refers to the nth item.
A user display may be entered from the faceplate keypad or the EnerVista UR Setup interface (preferred for convenience).
The following procedure shows how to enter text characters in the top and bottom lines from the faceplate keypad:
1. Select the line to be edited.
2. Press the decimal key to enter text edit mode.
3. Use either VALUE key to scroll through the characters. A space is selected like a character.
4. Press the decimal key to advance the cursor to the next position.
5. Repeat step 3 and continue entering characters until the desired text is displayed.
6. The HELP key may be pressed at any time for context sensitive help information.
7. Press the ENTER key to store the new settings.
To enter a numerical value for any of the five items (the decimal form of the selected Modbus address) from the faceplate
keypad, use the number keypad. Use the value of “0” for any items not being used. Use the HELP key at any selected sys-
tem display (setting, actual value, or command) which has a Modbus address, to view the hexadecimal form of the Modbus
address, then manually convert it to decimal form before entering it (EnerVista UR Setup usage conveniently facilitates this
conversion).
Use the MENU key to go to the user displays menu to view the user-defined content. The current user displays will show in
sequence, changing every four seconds. While viewing a user display, press the ENTER key and then select the ‘Yes”
option to remove the display from the user display list. Use the MENU key again to exit the user displays menu.
USER DISPLAY 1 DISP 1 TOP LINE: Shows user-defined text with first tilde marker.
Current X ~ A
DISP 1 BOTTOM LINE: Shows user-defined text with second tilde marker.
MESSAGE
Current Y ~ A
DISP 1 ITEM 1: Shows decimal form of user-selected Modbus register
MESSAGE address, corresponding to first tilde marker.
6016
DISP 1 ITEM 2: Shows decimal form of user-selected Modbus register
MESSAGE address, corresponding to second tilde marker.
6357
DISP 1 ITEM 3: This item is not being used. There is no corresponding
MESSAGE tilde marker in top or bottom lines.
0
DISP 1 ITEM 4: This item is not being used. There is no corresponding
MESSAGE tilde marker in top or bottom lines.
0
DISP 1 ITEM 5: This item is not being used. There is no corresponding
MESSAGE
0 tilde marker in top or bottom lines.
If the parameters for the top line and the bottom line items have the same units, then the unit is displayed on the
bottom line only. The units are only displayed on both lines if the units specified both the top and bottom line items 5
NOTE are different.
a) MAIN MENU
PATH: SETTINGS PRODUCT SETUP DIRECT I/O
Direct inputs and outputs are intended for exchange of status information (inputs and outputs) between UR-series relays
connected directly via type 7 digital communications cards. The mechanism is very similar to IEC 61850 GSSE, except that
communications takes place over a non-switchable isolated network and is optimized for speed. On type 7 cards that sup-
port two channels, direct output messages are sent from both channels simultaneously. This effectively sends direct output
messages both ways around a ring configuration. On type 7 cards that support one channel, direct output messages are
sent only in one direction. Messages will be resent (forwarded) when it is determined that the message did not originate at
the receiver.
Direct output message timing is similar to GSSE message timing. Integrity messages (with no state changes) are sent at
least every 1000 ms. Messages with state changes are sent within the main pass scanning the inputs and asserting the
outputs unless the communication channel bandwidth has been exceeded. Two self-tests are performed and signaled by
the following FlexLogic operands:
1. DIRECT RING BREAK (direct input/output ring break). This FlexLogic operand indicates that direct output messages
sent from a UR-series relay are not being received back by the relay.
2. DIRECT DEVICE 1 OFF to DIRECT DEVICE 16 OFF (direct device offline). These FlexLogic operands indicate that direct
output messages from at least one direct device are not being received.
Direct input and output settings are similar to remote input and output settings. The equivalent of the remote device name
strings for direct inputs and outputs is the DIRECT OUTPUT DEVICE ID. The DIRECT OUTPUT DEVICE ID setting identifies the
relay in all direct output messages. All UR-series IEDs in a ring should have unique numbers assigned. The IED ID is used
to identify the sender of the direct input and output message.
If the direct input and output scheme is configured to operate in a ring (DIRECT I/O CH1 RING CONFIGURATION or DIRECT I/O
CH2 RING CONFIGURATION is “Yes”), all direct output messages should be received back. If not, the direct input/output ring
break self-test is triggered. The self-test error is signaled by the DIRECT RING BREAK FlexLogic operand.
Select the DIRECT I/O DATA RATE to match the data capabilities of the communications channel. All IEDs communicating
5 over direct inputs and outputs must be set to the same data rate. UR-series IEDs equipped with dual-channel communica-
tions cards apply the same data rate to both channels. Delivery time for direct input and output messages is approximately
0.2 of a power system cycle at 128 kbps and 0.4 of a power system cycle at 64 kbps, per each ‘bridge’.
The G.703 modules are fixed at 64 kbps. The DIRECT I/O DATA RATE setting is not applicable to these modules.
NOTE
The DIRECT I/O CHANNEL CROSSOVER setting applies to D60s with dual-channel communication cards and allows crossing
over messages from channel 1 to channel 2. This places all UR-series IEDs into one direct input and output network
regardless of the physical media of the two communication channels.
The following application examples illustrate the basic concepts for direct input and output configuration. Please refer to the
Inputs and outputs section in this chapter for information on configuring FlexLogic operands (flags, bits) to be exchanged.
TX1
UR IED 1
RX1
TX1
UR IED 2
RX1
842711A1.CDR
Figure 5–17: INPUT AND OUTPUT EXTENSION VIA DIRECT INPUTS AND OUTPUTS
In the above application, the following settings should be applied. For UR-series IED 1:
DIRECT OUTPUT DEVICE ID: “1”
DIRECT I/O CH1 RING CONFIGURATION: “Yes”
DIRECT I/O DATA RATE: “128 kbps”
The message delivery time is about 0.2 of power cycle in both ways (at 128 kbps); that is, from device 1 to device 2, and
from device 2 to device 1. Different communications cards can be selected by the user for this back-to-back connection (for
example: fiber, G.703, or RS422).
EXAMPLE 2: INTERLOCKING BUSBAR PROTECTION
A simple interlocking busbar protection scheme could be accomplished by sending a blocking signal from downstream
devices, say 2, 3, and 4, to the upstream device that monitors a single incomer of the busbar, as shown below.
UR IED 1 BLOCK
842712A1.CDR
TX1 RX1
UR IED 1
RX2 TX2
TX2 RX2
UR IED 3
RX1 TX1
842716A1.CDR
UR IED 1 UR IED 2
UR IED 3
842713A1.CDR
5
RX1
UR IED 3
TX1
842714A1.CDR
TX1 RX1
UR IED 3
RX2 TX2
842715A1.CDR
b) CRC ALARMS
PATH: SETTINGS PRODUCT SETUP DIRECT I/O CRC ALARM CH1(2)
The D60 checks integrity of the incoming direct input and output messages using a 32-bit CRC. The CRC alarm function is
available for monitoring the communication medium noise by tracking the rate of messages failing the CRC check. The
monitoring function counts all incoming messages, including messages that failed the CRC check. A separate counter adds
up messages that failed the CRC check. When the failed CRC counter reaches the user-defined level specified by the CRC
ALARM CH1 THRESHOLD setting within the user-defined message count CRC ALARM 1 CH1 COUNT, the DIR IO CH1 CRC ALARM
FlexLogic operand is set.
When the total message counter reaches the user-defined maximum specified by the CRC ALARM CH1 MESSAGE COUNT set-
ting, both the counters reset and the monitoring process is restarted.
The operand shall be configured to drive an output contact, user-programmable LED, or selected communication-based
output. Latching and acknowledging conditions - if required - should be programmed accordingly.
The CRC alarm function is available on a per-channel basis. The total number of direct input and output messages that
failed the CRC check is available as the ACTUAL VALUES STATUS DIRECT INPUTS CRC FAIL COUNT CH1 actual
value.
• Message count and length of the monitoring window: To monitor communications integrity, the relay sends 1 message
per second (at 64 kbps) or 2 messages per second (128 kbps) even if there is no change in the direct outputs. For
example, setting the CRC ALARM CH1 MESSAGE COUNT to “10000”, corresponds a time window of about 160 minutes at
64 kbps and 80 minutes at 128 kbps. If the messages are sent faster as a result of direct outputs activity, the monitor-
ing time interval will shorten. This should be taken into account when determining the CRC ALARM CH1 MESSAGE COUNT
setting. For example, if the requirement is a maximum monitoring time interval of 10 minutes at 64 kbps, then the CRC
ALARM CH1 MESSAGE COUNT should be set to 10 60 1 = 600.
• Correlation of failed CRC and bit error rate (BER): The CRC check may fail if one or more bits in a packet are cor-
rupted. Therefore, an exact correlation between the CRC fail rate and the BER is not possible. Under certain assump-
tions an approximation can be made as follows. A direct input and output packet containing 20 bytes results in 160 bits
of data being sent and therefore, a transmission of 63 packets is equivalent to 10,000 bits. A BER of 10–4 implies 1 bit
error for every 10000 bits sent or received. Assuming the best case of only 1 bit error in a failed packet, having 1 failed
packet for every 63 received is about equal to a BER of 10–4.
The D60 checks integrity of the direct input and output communication ring by counting unreturned messages. In the ring
configuration, all messages originating at a given device should return within a pre-defined period of time. The unreturned
messages alarm function is available for monitoring the integrity of the communication ring by tracking the rate of unre-
turned messages. This function counts all the outgoing messages and a separate counter adds the messages have failed
to return. When the unreturned messages counter reaches the user-definable level specified by the UNRET MSGS ALARM
CH1 THRESHOLD setting and within the user-defined message count UNRET MSGS ALARM CH1 COUNT, the DIR IO CH1 UNRET
ALM FlexLogic operand is set.
When the total message counter reaches the user-defined maximum specified by the UNRET MSGS ALARM CH1 MESSAGE
COUNT setting, both the counters reset and the monitoring process is restarted.
The operand shall be configured to drive an output contact, user-programmable LED, or selected communication-based
output. Latching and acknowledging conditions, if required, should be programmed accordingly.
The unreturned messages alarm function is available on a per-channel basis and is active only in the ring configuration.
The total number of unreturned input and output messages is available as the ACTUAL VALUES STATUS DIRECT
INPUTS UNRETURNED MSG COUNT CH1 actual value.
5.2.17 TELEPROTECTION
Digital teleprotection functionality is designed to transfer protection commands between two or three relays in a secure,
fast, dependable, and deterministic fashion. Possible applications are permissive or blocking pilot schemes and direct
transfer trip (DTT). Teleprotection can be applied over any analog or digital channels and any communications media, such
as direct fiber, copper wires, optical networks, or microwave radio links. A mixture of communication media is possible.
Once teleprotection is enabled and the teleprotection input/outputs are configured, data packets are transmitted continu-
ously every 1/4 cycle (3/8 cycle if using C37.94 modules) from peer-to-peer. Security of communication channel data is
achieved by using CRC-32 on the data packet.
5
Teleprotection inputs/outputs and direct inputs/outputs are mutually exclusive – as such, they cannot be used
simultaneously. Once teleprotection inputs and outputs are enabled, direct inputs and outputs are blocked, and vice
NOTE versa.
• NUMBER OF TERMINALS: Specifies whether the teleprotection system operates between two peers or three peers.
• NUMBER OF CHANNELS: Specifies how many channels are used. If the NUMBER OF TERMINALS is “3” (three-terminal
system), set the NUMBER OF CHANNELS to “2”. For a two-terminal system, the NUMBER OF CHANNELS can set to “1” or
“2” (redundant channels).
• LOCAL RELAY ID NUMBER, TERMINAL 1 RELAY ID NUMBER, and TERMINAL 2 RELAY ID NUMBER: In installa-
tions that use multiplexers or modems, it is desirable to ensure that the data used by the relays protecting a given line
is from the correct relays. The teleprotection function performs this check by reading the message ID sent by transmit-
ting relays and comparing it to the programmed ID in the receiving relay. This check is also used to block inputs if inad-
vertently set to loopback mode or data is being received from a wrong relay by checking the ID on a received channel.
If an incorrect ID is found on a channel during normal operation, the TELEPROT CH1 ID FAIL or TELEPROT CH2 ID FAIL
FlexLogic operand is set, driving the event with the same name and blocking the teleprotection inputs. For commis-
sioning purposes, the result of channel identification is also shown in the STATUS CHANNEL TESTS VALIDITY OF
CHANNEL CONFIGURATION actual value. The default value of “0” for the LOCAL RELAY ID NUMBER indicates that relay ID
is not to be checked. On two- terminals two-channel systems, the same LOCAL RELAY ID NUMBER is transmitted over
both channels; as such, only the TERMINAL 1 ID NUMBER has to be programmed on the receiving end.
5.2.18 INSTALLATION
To safeguard against the installation of a relay without any entered settings, the unit will not allow signaling of any output
relay until RELAY SETTINGS is set to "Programmed". This setting is defaulted to "Not Programmed" when at the factory. The
UNIT NOT PROGRAMMED self-test error message is displayed until the relay is put into the "Programmed" state.
The RELAY NAME setting allows the user to uniquely identify a relay. This name will appear on generated reports.
When D60 is ordered with a process card module as a part of HardFiber system, then an additional Remote Resources
menu tree is available in EnerVista UR Setup software to allow configuration of the HardFiber system.
a) CURRENT BANKS
PATH: SETTINGS SYSTEM SETUP AC INPUTS CURRENT BANK F1(M5)
Because energy parameters are accumulated, these values should be recorded and then reset immediately
prior to changing CT characteristics.
NOTE
Four banks of phase and ground CTs can be set, where the current banks are denoted in the following format (X represents
the module slot position letter):
Xa, where X = {F, M} and a = {1, 5}.
See the Introduction to AC Sources section at the beginning of this chapter for additional details.
These settings are critical for all features that have settings dependent on current measurements. When the relay is
5 ordered, the CT module must be specified to include a standard or sensitive ground input. As the phase CTs are connected
in wye (star), the calculated phasor sum of the three phase currents (IA + IB + IC = neutral current = 3Io) is used as the
input for the neutral overcurrent elements. In addition, a zero-sequence (core balance) CT which senses current in all of the
circuit primary conductors, or a CT in a neutral grounding conductor may also be used. For this configuration, the ground
CT primary rating must be entered. To detect low level ground fault currents, the sensitive ground input may be used. In this
case, the sensitive ground CT primary rating must be entered. Refer to chapter 3 for more details on CT connections.
Enter the rated CT primary current values. For both 1000:5 and 1000:1 CTs, the entry would be 1000. For correct opera-
tion, the CT secondary rating must match the setting (which must also correspond to the specific CT connections used).
The following example illustrates how multiple CT inputs (current banks) are summed as one source current. Given the fol-
lowing current banks:
• F1: CT bank with 500:1 ratio.
• F5: CT bank with 1000:1 ratio.
• M1: CT bank with 800:1 ratio.
The following rule applies:
SRC 1 = F1 + F5 + M1 (EQ 5.6)
1 pu is the highest primary current. In this case, 1000 is entered and the secondary current from the 500:1 ratio CT will be
adjusted to that created by a 1000:1 CT before summation. If a protection element is set up to act on SRC 1 currents, then
a pickup level of 1 pu will operate on 1000 A primary.
The same rule applies for current sums from CTs with different secondary taps (5 A and 1 A).
b) VOLTAGE BANKS
PATH: SETTINGS SYSTEM SETUP AC INPUTS VOLTAGE BANK F5(M5)
Because energy parameters are accumulated, these values should be recorded and then reset
immediately prior to changing VT characteristics.
Two banks of phase/auxiliary VTs can be set, where voltage banks are denoted in the following format (X represents the
module slot position letter):
Xa, where X = {F, M} and a = {5}.
See the Introduction to AC sources section at the beginning of this chapter for additional details.
5
With VTs installed, the relay can perform voltage measurements as well as power calculations. Enter the PHASE VT F5 CON-
NECTION made to the system as “Wye” or “Delta”. An open-delta source VT connection would be entered as “Delta”.
The nominal PHASE VT F5 SECONDARY voltage setting is the voltage across the relay input terminals when nominal
voltage is applied to the VT primary.
NOTE
For example, on a system with a 13.8 kV nominal primary voltage and with a 14400:120 volt VT in a delta connec-
tion, the secondary voltage would be 115; that is, (13800 / 14400) × 120. For a wye connection, the voltage value
entered must be the phase to neutral voltage which would be 115 3 = 66.4.
On a 14.4 kV system with a delta connection and a VT primary to secondary turns ratio of 14400:120, the voltage
value entered would be 120; that is, 14400 / 120.
The power system NOMINAL FREQUENCY value is used as a default to set the digital sampling rate if the system frequency
cannot be measured from available signals. This may happen if the signals are not present or are heavily distorted. Before
reverting to the nominal frequency, the frequency tracking algorithm holds the last valid frequency measurement for a safe
period of time while waiting for the signals to reappear or for the distortions to decay.
The phase sequence of the power system is required to properly calculate sequence components and power parameters.
The PHASE ROTATION setting matches the power system phase sequence. Note that this setting informs the relay of the
actual system phase sequence, either ABC or ACB. CT and VT inputs on the relay, labeled as A, B, and C, must be con-
nected to system phases A, B, and C for correct operation.
The FREQUENCY AND PHASE REFERENCE setting determines which signal source is used (and hence which AC signal) for
phase angle reference. The AC signal used is prioritized based on the AC inputs that are configured for the signal source:
phase voltages takes precedence, followed by auxiliary voltage, then phase currents, and finally ground current.
For three phase selection, phase A is used for angle referencing ( V ANGLE REF = V A ), while Clarke transformation of the
phase signals is used for frequency metering and tracking ( V FREQUENCY = 2V A – V B – V C 3 ) for better performance dur-
ing fault, open pole, and VT and CT fail conditions.
The phase reference and frequency tracking AC signals are selected based upon the Source configuration, regardless of
whether or not a particular signal is actually applied to the relay.
Phase angle of the reference signal will always display zero degrees and all other phase angles will be relative to this sig-
nal. If the pre-selected reference signal is not measurable at a given time, the phase angles are not referenced.
The phase angle referencing is done via a phase locked loop, which can synchronize independent UR-series relays if they
have the same AC signal reference. This results in very precise correlation of phase angle indications between different
UR-series relays.
FREQUENCY TRACKING is set to “Disabled” only in unusual circumstances; consult the factory for special variable-
frequency applications.
NOTE
The frequency tracking feature functions only when the D60 is in the “Programmed” mode. If the D60 is “Not Pro-
grammed”, then metering values are available but can exhibit significant errors.
5
NOTE
Identical menus are available for each source. The "SRC 1" text can be replaced by with a user-defined name appropriate
for the associated source.
The first letter in the source identifier represents the module slot position. The number directly following this letter repre-
sents either the first bank of four channels (1, 2, 3, 4) called “1” or the second bank of four channels (5, 6, 7, 8) called “5” in
a particular CT/VT module. Refer to the Introduction to AC sources section at the beginning of this chapter for additional
details on this concept.
It is possible to select the sum of all CT combinations. The first channel displayed is the CT to which all others will be
referred. For example, the selection “F1+F5” indicates the sum of each phase from channels “F1” and “F5”, scaled to
whichever CT has the higher ratio. Selecting “None” hides the associated actual values.
The approach used to configure the AC sources consists of several steps; first step is to specify the information about each
CT and VT input. For CT inputs, this is the nominal primary and secondary current. For VTs, this is the connection type,
ratio and nominal secondary voltage. Once the inputs have been specified, the configuration for each source is entered,
including specifying which CTs will be summed together.
SETTING
ACTUAL
PRODUCT SETUP/DISPLAY
SOURCE 1 PROPERTIES/CURRENT
CURRENT PHASOR CUT-OFF LEVEL
I_1 I_1 - I_1’ >2*CUT-OFF FLEXLOGIC OPERAND
I_2 I_2 - I_2’ >2*CUT-OFF OR SRC 1 50DD OP
I_0 I_0 - I_0’ >2*CUT-OFF
Where I’ is 2 cycles old
SETTING
5
ACTUAL
PRODUCT SETUP/DISPLAY
SOURCE 2 PROPERTIES/CURRENT
CURRENT PHASOR CUT-OFF LEVEL
I_1 I_1 - I_1’ >2*CUT-OFF FLEXLOGIC OPERAND
I_2 I_2 - I_2’ >2*CUT-OFF OR SRC 2 50DD OP
I_0 I_0 - I_0’ >2*CUT-OFF
Where I’ is 2 cycles old
SETTING
ACTUAL
PRODUCT SETUP/DISPLAY
SOURCE 6 PROPERTIES/CURRENT
CURRENT PHASOR CUT-OFF LEVEL
I_1 I_1 - I_1’ >2*CUT-OFF FLEXLOGIC OPERAND
I_2 I_2 - I_2’ >2*CUT-OFF OR SRC 6 50DD OP
I_0 I_0 - I_0’ >2*CUT-OFF
Where I’ is 2 cycles old 827092A3.CDR
This configuration could be used on a two-winding transformer, with one winding connected into a breaker-and-a-half sys-
tem. The following figure shows the arrangement of sources used to provide the functions required in this application, and
the CT/VT inputs that are used to provide the data.
F1 DSP Bank
F5
Source 1 Source 2
Amps Amps
Source 3
51BF-1 51BF-2
U1 Volts Amps
A W Var 87T
A W Var 51P
Volts Amps
M1
M1 Source 4
UR Relay
M5
Y LV D HV AUX
SRC 1 SRC 2 SRC 3
5 Phase CT
Ground CT
M1
M1
F1+F5
None
None
None
Phase VT M5 None None
Aux VT None None U1
5.4.4 BREAKERS
A description of the operation of the breaker control and status monitoring features is provided in chapter 4. Only informa-
tion concerning programming of the associated settings is covered here. These features are provided for two or more
breakers; a user may use only those portions of the design relevant to a single breaker, which must be breaker 1.
The number of breaker control elements is dependent on the number of CT/VT modules specified with the D60. The follow-
ing settings are available for each breaker control element.
• BREAKER 1 FUNCTION: This setting enables and disables the operation of the breaker control feature.
• BREAKER1 PUSH BUTTON CONTROL: Set to “Enable” to allow faceplate push button operations.
• BREAKER 1 NAME: Assign a user-defined name (up to six characters) to the breaker. This name will be used in flash
messages related to breaker 1.
• BREAKER 1 MODE: This setting selects “3-Pole” mode, where all breaker poles are operated simultaneously, or “1-
Pole” mode where all breaker poles are operated either independently or simultaneously.
• BREAKER 1 OPEN: This setting selects an operand that creates a programmable signal to operate an output relay to
open breaker 1.
• BREAKER 1 BLK OPEN: This setting selects an operand that prevents opening of the breaker. This setting can be
used for select-before-operate functionality or to block operation from a panel switch or from SCADA.
• BREAKER 1 CLOSE: This setting selects an operand that creates a programmable signal to operate an output relay
to close breaker 1.
• BREAKER 1 BLK CLOSE: This setting selects an operand that prevents closing of the breaker. This setting can be
used for select-before-operate functionality or to block operation from a panel switch or from SCADA.
• BREAKER 1 A/3P CLOSED: This setting selects an operand, usually a contact input connected to a breaker auxil-
iary position tracking mechanism. This input should be a normally-open 52/a status input to create a logic 1 when the
5 breaker is closed. If the BREAKER 1 MODE setting is selected as “3-Pole”, this setting selects a single input as the oper-
and used to track the breaker open or closed position. If the mode is selected as “1-Pole”, the input mentioned above
is used to track phase A and the BREAKER 1 B and BREAKER 1 C settings select operands to track phases B and C,
respectively.
• BREAKER 1 A/3P OPND: This setting selects an operand, usually a contact input, that should be a normally-closed
52/b status input to create a logic 1 when the breaker is open. If a separate 52/b contact input is not available, then the
inverted BREAKER 1 CLOSED status signal can be used.
• BREAKER 1 B CLOSED: If the mode is selected as three-pole, this setting has no function. If the mode is selected
as single-pole, this input is used to track the breaker phase B closed position as above for phase A.
• BREAKER 1 B OPENED: If the mode is selected as three-pole, this setting has no function. If the mode is selected
as single-pole, this input is used to track the breaker phase B opened position as above for phase A.
• BREAKER 1 C CLOSED: If the mode is selected as three-pole, this setting has no function. If the mode is selected
as single-pole, this input is used to track the breaker phase C closed position as above for phase A.
• BREAKER 1 C OPENED: If the mode is selected as three-pole, this setting has no function. If the mode is selected
as single-pole, this input is used to track the breaker phase C opened position as above for phase A.
• BREAKER 1 Toperate: This setting specifies the required interval to overcome transient disagreement between the
52/a and 52/b auxiliary contacts during breaker operation. If transient disagreement still exists after this time has
expired, the BREAKER 1 BAD STATUS FlexLogic operand is asserted from alarm or blocking purposes.
• BREAKER 1 EXT ALARM: This setting selects an operand, usually an external contact input, connected to a breaker
alarm reporting contact.
• BREAKER 1 ALARM DELAY: This setting specifies the delay interval during which a disagreement of status among
the three-pole position tracking operands will not declare a pole disagreement. This allows for non-simultaneous oper-
ation of the poles.
If single-pole tripping and reclosing is used, the breaker may trip unsymmetrically for faults. In this case, the minimum
alarm delay setting must exceed the maximum time required for fault clearing and reclosing by a suitable margin.
• MANUAL CLOSE RECAL1 TIME: This setting specifies the interval required to maintain setting changes in effect after
an operator has initiated a manual close command to operate a circuit breaker.
• BREAKER 1 OUT OF SV: Selects an operand indicating that breaker 1 is out-of-service.
NOTE
The disconnect switch element contains the auxiliary logic for status and serves as the interface for opening and closing of
disconnect switches from SCADA or through the front panel interface. The disconnect switch element can be used to cre-
ate an interlocking functionality. For greater security in determination of the switch pole position, both the 89/a and 89/b
auxiliary contacts are used with reporting of the discrepancy between them. The number of available disconnect switches
depends on the number of the CT/VT modules ordered with the D60.
• SWITCH 1 FUNCTION: This setting enables and disables the operation of the disconnect switch element.
• SWITCH 1 NAME: Assign a user-defined name (up to six characters) to the disconnect switch. This name will be used
in flash messages related to disconnect switch 1.
• SWITCH 1 MODE: This setting selects “3-Pole” mode, where disconnect switch poles have a single common auxiliary
switch, or “1-Pole” mode where each disconnect switch pole has its own auxiliary switch.
• SWITCH 1 OPEN: This setting selects an operand that creates a programmable signal to operate a contact output to
open disconnect switch 1.
• SWITCH 1 BLK OPEN: This setting selects an operand that prevents opening of the disconnect switch. This setting
can be used for select-before-operate functionality or to block operation from a panel switch or from SCADA.
• SWITCH 1 CLOSE: This setting selects an operand that creates a programmable signal to operate a contact output to
close disconnect switch 1.
• SWITCH 1 BLK CLOSE: This setting selects an operand that prevents closing of the disconnect switch. This setting
can be used for select-before-operate functionality or to block operation from a panel switch or from SCADA.
• SWTCH 1 A/3P CLSD: This setting selects an operand, usually a contact input connected to a disconnect switch
auxiliary position tracking mechanism. This input should be a normally-open 89/a status input to create a logic 1 when
the disconnect switch is closed. If the SWITCH 1 MODE setting is selected as “3-Pole”, this setting selects a single input
as the operand used to track the disconnect switch open or closed position. If the mode is selected as “1-Pole”, the
input mentioned above is used to track phase A and the SWITCH 1 B and SWITCH 1 C settings select operands to
track phases B and C, respectively.
• SWTCH 1 A/3P OPND: This setting selects an operand, usually a contact input, that should be a normally-closed 89/
b status input to create a logic 1 when the disconnect switch is open. If a separate 89/b contact input is not available,
then an inverted 89/a status signal can be used.
• SWITCH 1 B CLOSED: If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase B closed position as above for phase A.
• SWITCH 1 B OPENED: If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase B opened position as above for phase A.
• SWITCH 1 C CLOSED: If the mode is selected as three-pole, this setting has no function. If the mode is selected as
5 single-pole, this input is used to track the disconnect switch phase C closed position as above for phase A.
• SWITCH 1 C OPENED: If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase C opened position as above for phase A.
• SWITCH 1 Toperate: This setting specifies the required interval to overcome transient disagreement between the 89/a
and 89/b auxiliary contacts during disconnect switch operation. If transient disagreement still exists after this time has
expired, the SWITCH 1 BAD STATUS FlexLogic operand is asserted from alarm or blocking purposes.
• SWITCH 1 ALARM DELAY: This setting specifies the delay interval during which a disagreement of status among the
three-pole position tracking operands will not declare a pole disagreement. This allows for non-simultaneous operation
of the poles.
IEC 61850 functionality is permitted when the D60 is in “Programmed” mode and not in the local control mode.
NOTE
The switch element has direct hard-coded connections to IEC 61850 model as shown in the logic diagram. This allows
remote open/close operation of each switch, using either CSWI or XSWI IEC 61850 logical nodes. IEC 61850 select-
before-operate functionality, local/remote switch functionality along with a blocking open/close commands are provided.
Note that IEC 61850 commands are event-driven and dwell time for these is one protection pass only. If you want to main-
tain close/open command for a certain time, do so either on the contact outputs using the "Seal-in" setting or in FlexLogic.
5.4.6 FLEXCURVES
a) SETTINGS
PATH: SETTINGS SYSTEM SETUP FLEXCURVES FLEXCURVE A(D)
FlexCurves A through D have settings for entering times to reset and operate at the following pickup levels: 0.00 to 0.98
and 1.03 to 20.00. This data is converted into two continuous curves by linear interpolation between data points. To enter a
custom FlexCurve, enter the reset and operate times (using the VALUE keys) for each selected pickup point (using the
MESSAGE UP/DOWN keys) for the desired protection curve (A, B, C, or D).
The relay using a given FlexCurve applies linear approximation for times between the user-entered points. Special
care must be applied when setting the two points that are close to the multiple of pickup of 1; that is, 0.98 pu and
NOTE
1.03 pu. It is recommended to set the two times to a similar value; otherwise, the linear approximation may result in
undesired behavior for the operating quantity that is close to 1.00 pu.
Addr: Adds the time specified in this field (in ms) to each
5
curve operating time value.
d) EXAMPLE
A composite curve can be created from the GE_111 standard with MRT = 200 ms and HCT initially disabled and then
enabled at eight (8) times pickup with an operating time of 30 ms. At approximately four (4) times pickup, the curve operat-
ing time is equal to the MRT and from then onwards the operating time remains at 200 ms (see below).
842719A1.CDR
842720A1.CDR
1 GE106
0.5
0.2
TIME (sec)
GE103
GE104 GE105
0.1
0.05
GE101 GE102
0.02
0.01
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842723A1.CDR
5
Figure 5–32: RECLOSER CURVES GE101 TO GE106
50
20 GE142
10
5
GE138
TIME (sec)
1 GE120
GE113
0.5
0.2
0.1
0.05
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842725A1.CDR
50
20
10
GE201
TIME (sec)
GE151
2
GE134 GE140
1
GE137
0.5
5
CURRENT (multiple of pickup) 842730A1.CDR
Figure 5–34: RECLOSER CURVES GE134, GE137, GE140, GE151 AND GE201
50
GE152
20
TIME (sec)
GE141
10
GE131
5
GE200
2
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842728A1.CDR
50
20
GE164
10
2
TIME (sec)
GE162
1
0.5
GE133
0.2
GE165
0.1
0.05
GE161
0.02 GE163
0.01
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842729A1.CDR
Figure 5–36: RECLOSER CURVES GE133, GE161, GE162, GE163, GE164 AND GE165 5
20
GE132
10
1
TIME (sec)
0.5 GE139
0.2
GE136
0.1
GE116
0.05
GE118 GE117
0.02
0.01
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842726A1.CDR
Figure 5–37: RECLOSER CURVES GE116, GE117, GE118, GE132, GE136, AND GE139
20
10
5
GE122
2
1
TIME (sec)
0.5
GE114
0.2
GE111
GE121
0.1
0.02
0.01
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup)
5
842724A1.CDR
Figure 5–38: RECLOSER CURVES GE107, GE111, GE112, GE114, GE115, GE121, AND GE122
50
20
GE202
10
TIME (sec)
GE135
2 GE119
0.5
0.2
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842727A1.CDR
a) MAIN MENU
PATH: SETTINGS SYSTEM SETUP PHASOR MEASUREMENT UNIT
The D60 Line Distance Protection System is provided with an optional phasor measurement unit feature.
This feature is specified as a software option at the time of ordering. The number of phasor measurement
units available is also dependent on this option. See the Ordering section of chapter 2 for details.
UR Synchrophasor Implementation
PHASORS are used within protection relays. If these phasors are referenced to a common time base they are referred to as
a SYNCHROPHASOR. A vastly improved method for tracking power system dynamic phenomena for improved power system
monitoring, protection, operation, and control can be realized if Synchrophasors from different locations within the power
system are networked to a central location.
The D60 offers PMU features over two communication standards, IEC61850-9-5 and IEEE C37.118. The figure shows
complete Synchrophasor implementation.
5
Firmware versions 7.0 and above have a 90-5 based R-SV implementation equivalent in structure and configuration to that
of the existing C37.118 implementation of firmware version 6.0, that is, synchrophasor data at rates up to 60 Hz for meter-
ing and 120 Hz for protection class synchrophasors. The two figures below depict the general data flow for the generation
of synchrophasor data for IEC61850-90-5. In the first figure, when IEC61850-90-5 is selected all real and virtual sources
are available for the IEC61850-90-5 PMUs.
Firmware version 7.0 allows the N60 to support a maximum of four Logical Device PMUs (Logical Device 2 through 5) and
four aggregators (located in Logical Device 1 (LD1)), while other UR family members support one PMU and only one
aggregator. The control blocks for the aggregators are located in LD1. A 64 char LDName setting is provided, see figure
below..
Precise time input to the relay from the international time standard, via either IRIG-B or PTP, is vital for correct syn-
chrophasor measurement and reporting. For IRIG-B, a DC level shift IRIG-B receiver must be used for the phasor
NOTE measurement unit to output proper synchrophasor values.
Depending on the applied filter, the Synchrophasors that are produced by PMUs are classified as either P (protection) or M
(Measurement) class Synchrophasors. Synchrophasors available within the UR that have no filtering applied are classified
as NONE which within the standard is classified as PRES OR UNKNOWN under the Calculation Method - ClcMth. Each
Logical Device PMU supports one MxxMMXU, MxxMSQI, PxxxMMXU , PxxxMSQI, NxxMMXU, and one NxxMSQI logical
node.
All bitstrings less than or equal to 32 bits in length map into a 32 bit bitstring in an IEC 61850-90-5 dataset.
NOTE
The Value of the Nominal Frequency of the chassis is instantiated as a DO in LPHD of LD1. The value is named
HzNom and is an Integer Status (INS).
The UR also supports the option to apply no filtering to the synchrophasors. If no filtering is applied (PMU Class = None),
according to the standard the ClcMth attribute will be PRES. The semantic of the ClcMth used is not carried in the individual
DO and so it is recommended that one of letters of the prefix on the instantiated LNs be set to “P” or “M” accordingly in
order to differentiate. For version 7.0 only FCDA data is supported. The Implementation by Model Number table, see
above, describes the maximum size of each PMU data set for version 7.0 using FCDA data (non-structured data).
EXAMPLE: PROTECTION SYNCHROPHASORS DATA SET WITH REPORTING RATE 60 FRAMES/SECOND
This example gives the protection synchrophasors data set with a reporting rate of 60 frames per second (P60MMXU1).
See figure above, Logical Nodes Supported in Each Logical Device. This data or list of items, see figure below, is not avail-
able to the UR setup program but is available to be mapped by the user into a selected aggregator or aggregators dataset.
The logical device name – LDName - of each PMU LD will be a 64 character user setting. The C37.118 STN and IDCode is
to be mapped as a concatenated value in the (d)escription field of LPL CDC of the NamPlt DO in LLN0. The mapping is
implemented as STN-IDCode(text string).
From each PMU the user selects the phasor information of interest that is mapped into the selected aggregator datset(s).
For version 7.0 only FCDA data is supported.
Figure 5–43: DATA SET CREATED FROM USER SELECTED INTERNAL ITEMS
VALUE
(DECIMAL) # OF ASDUS
11 1
12 2
13 3
14 4
b) BASIC CONFIGURATION
PATH: SETTINGS SYSTEM SETUP PHASOR MEASUREMENT BASIC CONFIGURATION PMU1
MESSAGE
PMU 1 PHS-14:
Off
Range: Available synchrophasor values
Default: Off 5
PMU 1 PHS-14: Range: 16 -character ASCII string
MESSAGE
NAME: GE-UR-PMU-PHS-14 Default: GE-UR-PMU-PHS-14
37.118 PMU 1
MESSAGE See below
CONFIGURATION
90-5 PMU 1
MESSAGE See below.
CONFIGURATION
This section contains basic phasor measurement unit (PMU) data, such as functions, source settings, and names.
• PMU 1 FUNCTION: This setting enables the LOGICAL Device PMU 1 functionality. Use this setting to permanently
enable or disable the feature.
• PMU 1 IDCODE: This setting assigns a numerical ID to the PMU. It corresponds to the IDCODE field of the data, con-
figuration, header, and command frames of the IEEE C37.118 protocol. The PMU uses this value when sending data,
configuration, and header frames; and it responds to this value when receiving the command frame. This is used when
only data from one PMU is present.
• PMU 1 STN: This setting assigns an alphanumeric ID to the PMU station. It corresponds to the STN field of the config-
uration frame of the IEEE C37.118 protocol. This value is a 16-character ASCII string as per the IEEE C37.118 stan-
dard.
• PMU 1 SIGNAL SOURCE: This setting specifies one of the available D60 signal sources for processing in the PMU.
Note that any combination of voltages and currents can be configured as a source. The current channels could be con-
figured as sums of physically connected currents. This facilitates PMU applications in breaker-and-a-half, ring-bus, and
similar arrangements. The PMU feature calculates voltage phasors for actual voltage (A, B, C, and auxiliary) and cur-
rent (A, B, C, and ground) channels of the source, as well as symmetrical components (0, 1, and 2) of both voltages
5 and currents. When configuring communication and recording features of the PMU, the user could select – from the
above superset – the content to be sent out or recorded. When one source is selected by one PMU, it cannot be
selected by another PMU.
• PMU 1 CLASS (Range P, M, None): This setting selects the synchrophasor class. Note that a reporting rate of 100 or
120 can only be selected for class P synchrophasors and if the system frequency is 50 Hz or 60 Hz, respectively.
• PMU 1 NETWORK REPORTING FORMAT: This setting selects whether synchrophasors are reported as 16-bit inte-
gers or 32-bit IEEE floating point numbers. This setting complies with bit-1 of the FORMAT field of the IEEE C37.118
configuration frame. This setting applies to synchrophasors only; the user-selectable FlexAnalog channels are always
transmitted as 16-bit integer values.
• PMU 1 NETWORK REPORTING STYLE: This setting selects whether synchrophasors are reported in rectangular
(real and imaginary) coordinates or in polar (magnitude and angle) coordinates. This setting complies with bit-0 of the
FORMAT field of the IEEE C37.118 configuration frame.
• PMU 1 RATE: This setting specifies the reporting rate for the network (Ethernet) port. This value applies to all PMU
streams of the device that are assigned to transmit over this aggregator. For a system frequency of 60 Hz (50 Hz), the
D60 generates a reporting mismatch message if the selected rate is not set as 10 Hz, 12 Hz, 15 Hz, 20 Hz, 30 Hz,
60 Hz, or 120 Hz (or 10 Hz, 25 Hz, 50 Hz or 100 Hz when the system frequency is 50 Hz) when entered via the keypad
or software; and the D60 stops the transmission of reports. Note that 4 Hz is not allowed for an M-class 50 Hz system).
• PMU1 PHS-1 to PMU1 PHS-14: These settings specify synchrophasors to be transmitted from the superset of all syn-
chronized measurements. The available synchrophasor values are tabulated below.
SELECTION MEANING
Va First voltage channel, either Va or Vab
Vb Second voltage channel, either Vb or Vbc
Vc Third voltage channel, either Vc or Vca
Vx Fourth voltage channel
Ia Phase A current, physical channel or summation as per the source settings
Ib Phase B current, physical channel or summation as per the source settings
Ic Phase C current, physical channel or summation as per the source settings
Ig Fourth current channel, physical or summation as per the source settings
V1 Positive-sequence voltage, referenced to Va
V2 Negative-sequence voltage, referenced to Va
V0 Zero-sequence voltage
I1 Positive-sequence current, referenced to Ia
I2 Negative-sequence current, referenced to Ia
I0 Zero-sequence current
These settings allow for optimizing the frame size and maximizing transmission channel usage, depending on a given
application. Select “Off” to suppress transmission of a given value.
• PMU1 PHS-1 NM to PMU1 PHS-14 NM: These settings allow for custom naming of the synchrophasor channels. Six-
teen-character ASCII strings are allowed as in the CHNAM field of the configuration frame. These names are typically
based on station, bus, or breaker names.
5
• PMU1 A-CH-1 to PMU1 A-CH-16: These settings specify any analog data measured by the relay to be included as a
user-selectable analog channel of the data frame. Up to 16 analog channels can be configured to send any FlexAnalog
value from the relay. Examples include frequency, rate of frequency change, active and reactive power, per phase or
three-phase power, power factor, temperature via RTD inputs, and THD. The configured analog values are sampled
concurrently with the synchrophasor instant and sent as 32-bit floating-point values scaled to Engineering units.
• PMU1 A-CH-1 NM to PMU1 A-CH-16 NM: These settings allow for custom naming of the analog channels. Sixteen-
character ASCII strings are allowed as in the CHNAM field of the configuration frame.
• PMU1 D-CH-1 to PMU1 D-CH-16: These settings specify any digital flag measured by the relay to be included as a
user-selectable digital channel of the data frame. Up to sixteen digital channels can be configured to send any Flex-
Logic operand from the relay. The configured digital flags are sampled concurrently with the synchrophasor instant.
These values are mapped into a two-byte integer number, with byte 1 LSB corresponding to the digital channel 1and
byte 2 MSB corresponding to digital channel 16.
• PMU1 D-CH-1 NM to PMU1 D-CH-16 NM: These settings allow for custom naming of the digital channels. Sixteen-
character ASCII strings are allowed as in the CHNAM field of the configuration frame.
• PMU1 D-CH-1 NORMAL STATE to PMU1 D-CH-16 NORMAL STATE: These settings allow for specifying a normal
state for each digital channel. These states are transmitted in configuration frames to the data concentrator.
C37.118 PMU 1 CONFIGURATION
PATH: SETTINGS SYSTEM SETUP PHASOR MEASUREMENT BASIC CONFIGURATION PMU 1 PMU 1 BASIC CONFIGU-
RATION 37.118 PMU 1 CONFIGURATION
PMU 1 FORMAT: This setting selects whether synchrophasors are reported as 16-bit integers or 32-bit IEEE floating point
numbers. This setting complies with bit-1 of the FORMAT field of the IEEE C37.118 configuration frame. This setting
applies to synchrophasors only; the user-selectable FlexAnalog channels are always transmitted as 16-bit integer values.
PMU 1 STYLE: This setting selects whether synchrophasors are reported in rectangular (real and imaginary) coordinates
or in polar (magnitude and angle) coordinates. This setting complies with bit-0 of the FORMAT field of the IEEE C37.118
configuration frame.
With 90-5 PMU, the FORMAT and STYLE are Floating-point and Polar respectively, as specified in the IEC 61850
standard.
NOTE
PMU1 LDINST: A user-defined visible string (maximum 64 char ASCII test) to assign Logical Device (LD) Inst for a PMU
LD.
As per IEC 61850-6 standard specification, the PMU LD Name is the concatenated combination (to total 64 charac-
ters) of IED Name (specified in IEC 61850 Server Settings) appended with PMU X LDINST string.
NOTE
c) CALIBRATION
PATH: SETTINGS SYSTEM SETUP PHASOR MEASUREMENT UNIT PHASOR MEASUREMENT UNIT 1 PMU 1 (to 4)
CALIBRATION
This menu contains user angle and magnitude calibration data for the phasor measurement unit (PMU). This data is com-
bined with the factory adjustments to shift the phasors for better accuracy.
• PMU 1 VA... IG CALIBRATION ANGLE: These settings recognize applications with protection class voltage and cur-
rent sources, and allow the user to calibrate each channel (four voltages and four currents) individually to offset errors
introduced by VTs, CTs, and cabling. The setting values are effectively added to the measured angles. Therefore, enter
a positive correction of the secondary signal lags the true signal; and negative value if the secondary signal leads the
true signal.
• PMU 1 VA... IG CALIBRATION MAGNITUDE: These settings recognize applications with protection class voltage and
current sources, and allow the user to calibrate each channel (four voltages and four currents) individually to offset
errors introduced by VTs, CTs. The setting values are effectively a multiplier of the measured magnitudes. Therefore,
enter a multiplier greater than 100% of the secondary signal increases the true signal; and a multiplier less than 100%
value of the secondary signal reduces the true signal.
• PMU 1 SEQ VOLT SHIFT ANGLE: This setting allows correcting positive- and negative-sequence voltages for vector
groups of power transformers located between the PMU voltage point, and the reference node. This angle is effectively
added to the positive-sequence voltage angle, and subtracted from the negative-sequence voltage angle. Note that:
1. When this setting is not “0°”, the phase and sequence voltages will not agree. Unlike sequence voltages, the
phase voltages cannot be corrected in a general case, and therefore are reported as measured.
2. When receiving synchrophasor data at multiple locations, with possibly different reference nodes, it can be more
beneficial to allow the central locations to perform the compensation of sequence voltages.
3. This setting applies to PMU data only. The D60 calculates symmetrical voltages independently for protection and
control purposes without applying this correction.
4. When connected to line-to-line voltages, the PMU calculates symmetrical voltages with the reference to the AG
voltage, and not to the physically connected AB voltage (see the Metering Conventions section in Chapter 6).
• PMU 1 SEQ CURR SHIFT ANGLE: This setting allows correcting positive and negative-sequence currents for vector
groups of power transformers located between the PMU current point and the reference node. The setting has the
same meaning for currents as the PMU 1 SEQ VOLT SHIFT ANGLE setting has for voltages. Normally, the two correcting
angles are set identically, except rare applications when the voltage and current measuring points are located at differ-
ent windings of a power transformer.
Each logical phasor measurement unit (PMU) contains five triggering mechanisms to facilitate triggering of the associated
PMU recorder, or cross-triggering of other PMUs of the system. They are:
• Overfrequency and underfrequency
• Overvoltage and undervoltage
• Overcurrent
• Overpower
• High rate of change of frequency
The pre-configured triggers could be augmented with a user-specified condition built freely using programmable logic of the
relay. The entire triggering logic is refreshed once every two power system cycles.
All five triggering functions and the user-definable condition are consolidated (ORed) and connected to the PMU recorder.
Each trigger can be programmed to log its operation into the event recorder, and to signal its operation via targets. The five
triggers drive the STAT bits of the data frame to inform the destination of the synchrophasor data regarding the cause of
trigger. The following convention is adopted to drive bits 11, 3, 2, 1, and 0 of the STAT word.
e) USER TRIGGERING
PATH: SETTINGS SYSTEM SETUP PHASOR MEASUREMENT... PMU 1 TRIGGERING PMU 1 USER TRIGGER
PMU 1 USER
TRIGGER
PMU1 USER TRIGGER:
Off
Range: FlexLogic operands
5
The user trigger allows customized triggering logic to be constructed from FlexLogic. The entire triggering logic is refreshed
once every two power system cycles.
f) FREQUENCY TRIGGERING
PATH: SETTINGS SYSTEM SETUP PHASOR MEASUREMENT... PMU 1 TRIGGERING PMU 1 FREQUENCY TRIGGER
The trigger responds to the frequency signal of the phasor measurement unit (PMU) source. The frequency is calculated
from either phase voltages, auxiliary voltage, phase currents and ground current, in this hierarchy, depending on the source
configuration as per D60 standards. This element requires the frequency is above the minimum measurable value. If the
frequency is below this value, such as when the circuit is de-energized, the trigger drops out.
• PMU 1 FREQ TRIGGER LOW-FREQ: This setting specifies the low threshold for the abnormal frequency trigger. The
comparator applies a 0.02 Hz hysteresis.
• PMU 1 FREQ TRIGGER HIGH-FREQ: This setting specifies the high threshold for the abnormal frequency trigger. The
comparator applies a 0.02 Hz hysteresis.
• PMU 1 FREQ TRIGGER PKP TIME: This setting could be used to filter out spurious conditions and avoid unnecessary
triggering of the recorder.
• PMU 1 FREQ TRIGGER DPO TIME: This setting could be used to extend the trigger after the situation returned to nor-
mal. This setting is of particular importance when using the recorder in the forced mode (recording as long as the trig-
gering condition is asserted).
5
Figure 5–47: FREQUENCY TRIGGER SCHEME LOGIC
g) VOLTAGE TRIGGERING
PATH: SETTINGS SYSTEM SETUP PHASOR MEASUREMENT... PMU 1 TRIGGERING PMU 1 VOLTAGE TRIGGER
This element responds to abnormal voltage. Separate thresholds are provided for low and high voltage. In terms of signal-
ing its operation, the element does not differentiate between the undervoltage and overvoltage events. The trigger
responds to the phase voltage signal of the phasor measurement unit (PMU) source. All voltage channels (A, B, and C or
AB, BC, and CA) are processed independently and could trigger the recorder. A minimum voltage supervision of 0.1 pu is
implemented to prevent pickup on a de-energized circuit, similarly to the undervoltage protection element.
• PMU 1 VOLT TRIGGER LOW-VOLT: This setting specifies the low threshold for the abnormal voltage trigger, in per-
unit of the PMU source. 1 pu is a nominal voltage value defined as the nominal secondary voltage times VT ratio. The
comparator applies a 1% hysteresis.
• PMU 1 VOLT TRIGGER HIGH-VOLT: This setting specifies the high threshold for the abnormal voltage trigger, in per-
unit of the PMU source. 1 pu is a nominal voltage value defined as the nominal secondary voltage times VT ratio. The
comparator applies a 1% hysteresis.
• PMU 1 VOLT TRIGGER PKP TIME: This setting could be used to filter out spurious conditions and avoid unnecessary
triggering of the recorder.
• PMU 1 VOLT TRIGGER DPO TIME: This setting could be used to extend the trigger after the situation returned to nor-
mal. This setting is of particular importance when using the recorder in the forced mode (recording as long as the trig-
gering condition is asserted).
h) CURRENT TRIGGERING
PATH: SETTINGS SYSTEM SETUP PHASOR MEASUREMENT... PMU 1 TRIGGERING PMU 1 CURRENT TRIGGER
This element responds to elevated current. The trigger responds to the phase current signal of the phasor measurement
unit (PMU) source. All current channel (A, B, and C) are processed independently and could trigger the recorder.
• PMU 1 CURR TRIGGER PICKUP: This setting specifies the pickup threshold for the overcurrent trigger, in per unit of
the PMU source. A value of 1 pu is a nominal primary current. The comparator applies a 3% hysteresis.
• PMU 1 CURR TRIGGER PKP TIME: This setting could be used to filter out spurious conditions and avoid unneces-
sary triggering of the recorder.
• PMU 1 CURR TRIGGER DPO TIME: This setting could be used to extend the trigger after the situation returned to nor-
mal. This setting is of particular importance when using the recorder in the forced mode (recording as long as the trig-
gering condition is asserted).
i) POWER TRIGGERING
PATH: SETTINGS SYSTEM SETUP PHASOR MEASUREMENT... PMU 1 TRIGGERING PMU 1 POWER TRIGGER
5 PMU 1 POWER PMU 1 POWER TRIGGER Range: Enabled, Disabled
TRIGGER FUNCTION: Disabled
PMU 1 POWER TRIGGER Range: 0.250 to 3.000 pu in steps of 0.001
MESSAGE
ACTIVE: 1.250 pu
PMU 1 POWER TRIGGER Range: 0.250 to 3.000 pu in steps of 0.001
MESSAGE
REACTIVE: 1.250 pu
PMU 1 POWER TRIGGER Range: 0.250 to 3.000 pu in steps of 0.001
MESSAGE
APPARENT: 1.250 pu
PMU 1 POWER TRIGGER Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
PKP TIME: 0.10 s
PMU 1 POWER TRIGGER Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
DPO TIME: 1.00 s
PMU 1 PWR TRIG BLK: Range: FlexLogic operand
MESSAGE
Off
PMU 1 POWER TRIGGER Range: Self-Reset, Latched, Disabled
MESSAGE
TARGET: Self-Reset
PMU 1 POWER TRIGGER Range: Enabled, Disabled
MESSAGE
EVENTS: Disabled
This element responds to abnormal power. Separate thresholds are provided for active, reactive, and apparent powers. In
terms of signaling its operation the element does not differentiate between the three types of power. The trigger responds to
the single-phase and three-phase power signals of the phasor measurement unit (PMU) source.
• PMU 1 POWER TRIGGER ACTIVE: This setting specifies the pickup threshold for the active power of the source. For
single-phase power, 1 pu is a product of 1 pu voltage and 1 pu current, or the product of nominal secondary voltage,
the VT ratio and the nominal primary current. For the three-phase power, 1 pu is three times that for a single-phase
power in case of wye-connected VTs and 3 times in case of delta-connected VTs. The comparator applies a 3% hys-
teresis.
• PMU 1 POWER TRIGGER REACTIVE: This setting specifies the pickup threshold for the reactive power of the
source. For single-phase power, 1 pu is a product of 1 pu voltage and 1 pu current, or the product of nominal second-
ary voltage, the VT ratio and the nominal primary current. For the three-phase power, 1 pu is three times that for a sin-
gle-phase power in case of wye-connected VTs and 3 times in case of delta-connected VTs. The comparator applies
a 3% hysteresis.
• PMU 1 POWER TRIGGER APPARENT: This setting specifies the pickup threshold for the apparent power of the
source. For single-phase power, 1 pu is a product of 1 pu voltage and 1 pu current, or the product of nominal second-
ary voltage, the VT ratio and the nominal primary current. For the three-phase power, 1 pu is three times that for a sin-
gle-phase power in case of wye-connected VTs and 3 times in case of delta-connected VTs. The comparator applies
a 3% hysteresis.
• PMU 1 POWER TRIGGER PKP TIME: This setting could be used to filter out spurious conditions and avoid unneces-
sary triggering of the recorder.
• PMU 1 POWER TRIGGER DPO TIME: This setting could be used to extend the trigger after the situation returned to
normal. This setting is of particular importance when using the recorder in the forced mode (recording as long as the
triggering condition is asserted).
j) DF/DT TRIGGERING
PATH: SETTINGS SYSTEM SETUP PHASOR MEASUREMENT... PMU 1 TRIGGERING PMU 1 df/dt TRIGGER
This element responds to frequency rate of change. Separate thresholds are provided for rising and dropping frequency.
5 The trigger responds to the rate of change of frequency (df/dt) of the phasor measurement unit (PMU) source.
• PMU 1 df/dt TRIGGER RAISE: This setting specifies the pickup threshold for the rate of change of frequency in the
raising direction (positive df/dt). The comparator applies a 4% hysteresis.
• PMU 1 df/dt TRIGGER FALL: This setting specifies the pickup threshold for the rate of change of frequency in the fall-
ing direction (negative df/dt). The comparator applies a 4% hysteresis.
• PMU 1 df/dt TRIGGER PKP TIME: This setting could be used to filter out spurious conditions and avoid unnecessary
triggering of the recorder.
• PMU 1 df/dt TRIGGER DPO TIME: This setting could be used to extend the trigger after the situation returned to nor-
mal. This setting is of particular importance when using the recorder in the forced mode (recording as long as the trig-
gering condition is asserted).
FLEXLOGIC OPERANDS
PMU 1 FREQ TRIGGER
PMU 1 VOLT TRIGGER
PMU 1 CURR TRIGGER
PMU 1 TRIGGERED
PMU 1 df/dt TRIGGER SETTING
FUNCTION:
PMU 1 USER TRIGGER:
Enabled = 1
Off = 0
AND
k) PMU RECORDING
PATH: SETTINGS SYSTEM SETUP PHASOR MEASUREMENT PHASOR MEASUREMENT UNIT1 RECORDING PMU1
• PMU 1 FUNCTION: This setting enables or disables the recorder for PMU 1. The rate is fixed at the reporting rate set
within the aggregator (i.e., Aggregator 1).
• PMU 1 NO OF TIMED RECORDS: This setting specifies the number of timed records that are available for a given log-
ical PMU 1(4). The length of each record is equal to the available memory divided by the content size and number of
records. As the number of records is increased the available storage for each record is reduced. The relay supports a
maximum of 128 records in either timed or forced mode.
• PMU 1 TRIGGER MODE: This setting specifies what happens when the recorder uses its entire available memory
storage. Under the “Automatic Overwrite”, the last record is erased to facilitate new recording, when triggered. Under
the “Protected” selection, the recorder stops creating new records when the entire memory is used up by the old un-
cleared records.
• PMU 1 TIMED TRIGGER POSITION: This setting specifies the amount of pre-trigger data as a percent of the entire
record. This setting applies only to the timed mode of recording. 5
l) AGGREGATORS
PATH: SETTINGS SYSTEM SETUP PHASOR MEASUREMENT UNIT PMU AGGREGATOR 1
37.118 AGGR 1
MESSAGE See below.
CONFIGURATION
90-5 AGGR 1
MESSAGE See below.
CONFIGURATION
When the protocol selection is set via the software or keypad, all aggregators whose protocol is not set to None will
be set to the last protocol saved (i.e., IEEE C37.118 or IEC 61850-90-5) to any aggregators, as both IEEE C37.118
NOTE and IEC 61850-90-5 simultaneous streaming of both R-SV values is not possible.
PATH: SETTINGS SYSTEM SETUP PHASOR MEASUREMENT UNIT PMU AGGREGATOR 1 37.118 AGGR 1 CONFIG-
URATION
PATH: SETTINGS SYSTEM SETUP PHASOR MEASUREMENT UNIT PMU AGGREGATOR 1 90-5 AGGR 1 CONFIGU-
RATION
• PMU AGGREGATOR1 PROTOCOL: This setting selects if the IEEE C37.118 or IEC 61850 standard is used.
• PMU AGGREGATOR1 IDCODE: Numeric identifier of the Aggregator / PDC function. In an IEEE C37.118 output
stream, this identifies the ID of the aggregator - which is only used if there is more than 1 PMU mapped into an aggre-
gator.
• PMU AGGREGATOR1 PMU1: If set to “Yes” aggregator 1 includes the PMU1 data set in the reporting data stream.
AGGREGATOR1 will not include PMU1 data set in the report if set to “No”.
C37.118 AGGREGATOR 1 CONFIGURATION
• PMU AGGREGATOR1: TCP PORT: This setting selects the TCP port number to be used by this aggregator for net-
work reporting. All ports, even those of unused aggregators, must be valid and unique to avoid port number collisions.
• PMU AGGREGATOR1 UDP PORT: This setting selects the UDP port number to be used by this aggregator for net-
5 work reporting. All ports, even those of unused aggregators, must be valid and unique to avoid port number collisions.
• PMU AGGREGATOR1 PDC CONTROL: The synchrophasor standard allows for user-defined controls originating at
the PDC, to be executed on the PMU. The control is accomplished via an extended command frame. The relay
decodes the first word of the extended field, EXTFRAME, to drive 16 dedicated FlexLogic operands. Each aggregator
supports 16 FlexLogic operands as shown in table 2. The operands are asserted for 5 seconds following reception of
the command frame. If the new command frame arrives within the 5 second period, the FlexLogic operands are
updated, and the 5 second timer is re-started. This setting enables or disables the control. When enabled, all 16 oper-
ands for each aggregator are active; when disabled all 16 operands for each aggregator remain reset.
Table 5–12: FLEXLOGIC OPERANDS SUPPORTED BY AGGREGATOR
OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION
ELEMENT: AGTR1 PDC CNTRL 1 Phasor data concentrator asserts control bit 1, as
Synchrophasor, phasor data, received via the network.
concentrator
as above AGTR1 PDC CNTRL 2 Phasor data concentrator asserts control bit 2 as
received via the network.
as above AGTR1 PDC CNTRL 3 Phasor data concentrator asserts control bit 3 as
received via the network.
as above AGTR1 PDC CNTRL 16 Phasor data concentrator asserts control bit 16, as
received via the network.
as above AGTR2 PDC CNTRL 1 Phasor data concentrator asserts control bit 1 as
received via the network
as above AGTR2 PDC CNTRL 2 Phasor data concentrator asserts control bit 2 as
received via the network
as above AGTR2 PDC CNTRL 3 Phasor data concentrator asserts control bit 3 as
received via the network.
as above AGTR1 PDC CNTRL 16 Phasor data concentrator asserts control bit 16, as
received via the network.
m) CONTROL BLOCKS
PATH: SETTINGS SYSTEM SETUP PHASOR MEASUREMENT UNIT IEC 90 – 5 MSVCB01 CONFIGURATION
• MSVCB 1 SVENA: The SV Stream Control is set by either toggling an assigned FlexLogic operand or a remote client
write, to start and stop the streaming of R-SV frames. If remote client control is disabled, a negative response is pro-
vided to the client in response to a write attempt. A FlexLogic operand (SvEna) is provided for each Aggregator that
reflects the state of the SvEna control where “1”= Enabled and “0”=Disabled. The logic for setting the SvEna control bit
is shown in the following figure.
5 • MSVCB 1 SVENA Default: This setting sets the default state of the stream (On or Off) on power-up or restart.
• MSVCB 1 CONFREV: The relay increments the Configuration revision every time the configuration is changed. This
setting allows the user to reset the configuration back to 1 or a value from 1 to 4294967295.
• MSVCB 1 PRIORITY: A value from 0 through 7: The default value is 4.
• MSVCB 1 IP Class: The value represents the IPv4 Differentiated Services (formerly called TypeOfService) value. The
default value is set for Expedited Forwarding (101110B (46 or 2EH). This value provides priority routing, when sup-
ported in the routers.
• MSVCB 1 VID: A range of values limited from 0 to 4095.
• MSVCB 1 APPID: This setting allows the selection of a specific application ID for each sending device.
• MSVCB 1 DEST IP Address: This is the destination multicast address IP address that is entered in Standard IPV4
address format. The valid range for IPv4 is from 224.0.0.0 to 239.255.255.255, but the UR does not test the address
entered.
• MSVCB 1 Security: This setting selects the level of security and authentication used, as outlined in the following table,
and is in the form of an enumeration as per standard. The range is 0 to 2.
Shaded settings in the table are not supported in firmware 7.0.
To provide maximum flexibility to the user, the arrangement of internal digital logic combines fixed and user-programmed
parameters. Logic upon which individual features are designed is fixed, and all other logic, from digital input signals through
elements or combinations of elements to digital outputs, is variable. The user has complete control of all variable logic
through FlexLogic. In general, the system receives analog and digital inputs which it uses to produce analog and digital out-
puts. The major sub-systems of a generic UR-series relay involved in this process are shown below.
The logic that determines the interaction of inputs, elements, schemes and outputs is field programmable through the use
of logic equations that are sequentially processed. The use of virtual inputs and outputs in addition to hardware is available
internally and on the communication ports for other relays to use (distributed FlexLogic).
FlexLogic allows users to customize the relay through a series of equations that consist of operators and operands. The
operands are the states of inputs, elements, schemes and outputs. The operators are logic gates, timers and latches (with
set and reset inputs). A system of sequential operations allows any combination of specified operands to be assigned as
inputs to specified operators to create an output. The final output of an equation is a numbered register called a virtual out-
put. Virtual outputs can be used as an input operand in any equation, including the equation that generates the output, as a
seal-in or other type of feedback.
A FlexLogic equation consists of parameters that are either operands or operators. Operands have a logic state of 1 or 0.
Operators provide a defined function, such as an AND gate or a Timer. Each equation defines the combinations of parame-
ters to be used to set a Virtual Output flag. Evaluation of an equation results in either a 1 (=ON, i.e. flag set) or 0 (=OFF, i.e.
flag not set). Each equation is evaluated at least 4 times every power system cycle.
Some types of operands are present in the relay in multiple instances; e.g. contact and remote inputs. These types of oper-
ands are grouped together (for presentation purposes only) on the faceplate display. The characteristics of the different
types of operands are listed in the table below.
The operands available for this relay are listed alphabetically by types in the following table.
Table 5–15: D60 FLEXLOGIC OPERANDS (Sheet 1 of 11)
OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION
CONTROL CONTROL PUSHBTN 1 ON Control pushbutton 1 is being pressed
PUSHBUTTONS CONTROL PUSHBTN 2 ON Control pushbutton 2 is being pressed
CONTROL PUSHBTN 3 ON Control pushbutton 3 is being pressed
CONTROL PUSHBTN 4 ON Control pushbutton 4 is being pressed
CONTROL PUSHBTN 5 ON Control pushbutton 5 is being pressed
CONTROL PUSHBTN 6 ON Control pushbutton 6 is being pressed
CONTROL PUSHBTN 7 ON Control pushbutton 7 is being pressed
DIRECT DEVICES DIRECT DEVICE 1On Flag is set, logic=1
DIRECT DEVICE 16On Flag is set, logic=1
DIRECT DEVICE 1Off Flag is set, logic=1
DIRECT DEVICE 16Off Flag is set, logic=1
DIRECT INPUT/ DIR IO CH1 CRC ALARM The rate of direct input messages received on channel 1 and failing the CRC
OUTPUT exceeded the user-specified level.
CHANNEL DIR IO CH2 CRC ALARM The rate of direct input messages received on channel 2 and failing the CRC
MONITORING exceeded the user-specified level.
DIR IO CH1 UNRET ALM The rate of returned direct input/output messages on channel 1 exceeded the
user-specified level (ring configurations only).
DIR IO CH2 UNRET ALM The rate of returned direct input/output messages on channel 2 exceeded the
user-specified level (ring configurations only).
ELEMENT: AR ENABLED Autoreclosure is enabled and ready to perform
Autoreclose AR DISABLED Autoreclosure is disabled
(1P/3P) AR RIP Autoreclosure is in “reclose-in-progress” state
AR 1-P RIP A single-pole reclosure is in progress
AR 3-P/1 RIP A three-pole reclosure is in progress, via dead time 1
AR 3-P/2 RIP A three-pole reclosure is in progress, via dead time 2
AR 3-P/3 RIP A three-pole reclosure is in progress, via dead time 3
AR 3-P/4 RIP
AR LO
A three-pole reclosure is in progress, via dead time 4
Autoreclosure is in lockout state
5
AR BKR1 BLK Reclosure of breaker 1 is blocked
AR BKR2 BLK Reclosure of breaker 2 is blocked
AR CLOSE BKR1 Reclose breaker 1 signal
AR CLOSE BKR2 Reclose breaker 2 signal
AR FORCE 3-P TRIP Force any trip to a three-phase trip
AR SHOT CNT > 0 The first ‘CLOSE BKR X’ signal has been issued
AR SHOT CNT = 1 Shot count is equal to 1
AR SHOT CNT = 2 Shot count is equal to 2
AR SHOT CNT = 3 Shot count is equal to 3
AR SHOT CNT = 4 Shot count is equal to 4
AR MODE = 1 Autoreclose mode equal to 1 (1 and 3 pole mode)
AR MODE = 2 Autoreclose mode equal to 2 (1 pole mode)
AR MODE = 3 Autoreclose mode equal to 3 (3 pole-A mode)
AR MODE = 4 Autoreclose mode equal to 4 (3 pole-B mode)
AR MODE SWITCH FAIL Autoreclose mode switching is attempted, but failed
AR ZONE 1 EXTENT The zone 1 distance function must be set to the extended overreach value
AR INCOMPLETE SEQ The incomplete sequence timer timed out
AR RESET Autoreclose has been reset either manually or by the reset timer
ELEMENT: AUX OV1 PKP Auxiliary overvoltage element has picked up
Auxiliary AUX OV1 DPO Auxiliary overvoltage element has dropped out
overvoltage AUX OV1 OP Auxiliary overvoltage element has operated
AUX OV2 to AUX OV3 Same set of operands as shown for AUX OV1
ELEMENT: AUX UV1 PKP Auxiliary undervoltage element has picked up
Auxiliary AUX UV1 DPO Auxiliary undervoltage element has dropped out
undervoltage AUX UV1 OP Auxiliary undervoltage element has operated
AUX UV2 to AUX UV3 Same set of operands as shown for AUX UV1
ELEMENT BKR 1 FLSHOVR PKP A Breaker 1 flashover element phase A has picked up
Breaker flashover BKR 1 FLSHOVR PKP B Breaker 1 flashover element phase B has picked up
BKR 1 FLSHOVR PKP C Breaker 1 flashover element phase C has picked up
BKR 1 FLSHOVR PKP Breaker 1 flashover element has picked up
BKR 1 FLSHOVR OP A Breaker 1 flashover element phase A has operated
BKR 1 FLSHOVR OP B Breaker 1 flashover element phase B has operated
BKR 1 FLSHOVR OP C Breaker 1 flashover element phase C has operated
BKR 1 FLSHOVR OP Breaker 1 flashover element has operated
BKR 1 FLSHOVR DPO A Breaker 1 flashover element phase A has dropped out
BKR 1 FLSHOVR DPO B Breaker 1 flashover element phase B has dropped out
BKR 1 FLSHOVR DPO C Breaker 1 flashover element phase C has dropped out
BKR 1 FLSHOVR DPO Breaker 1 flashover element has dropped out
BKR 2 FLSHOVR... Same set of operands as shown for BKR 1 FLSHOVR
FIXED OPERANDS Off Logic = 0. Does nothing and may be used as a delimiter in an equation list;
used as ‘Disable’ by other features.
On Logic = 1. Can be used as a test setting.
INPUTS/OUTPUTS: Cont Ip 1 On (will not appear unless ordered)
Contact inputs Cont Ip 2 On (will not appear unless ordered)
Cont Ip 1 Off (will not appear unless ordered)
Cont Ip 2 Off (will not appear unless ordered)
INPUTS/OUTPUTS: Cont Op 1 IOn (will not appear unless ordered)
Contact outputs, Cont Op 2 IOn (will not appear unless ordered)
current
(from detector on
form-A output only)
INPUTS/OUTPUTS: Cont Op 1 VOn (will not appear unless ordered)
Contact outputs, Cont Op 2 VOn (will not appear unless ordered)
voltage
(from detector on
form-A output only) Cont Op 1 VOff (will not appear unless ordered)
Cont Op 2 VOff (will not appear unless ordered)
INPUTS/OUTPUTS DIRECT INPUT 1 On Flag is set, logic=1
Direct inputs
DIRECT INPUT 32 On Flag is set, logic=1
PASSWORD ACCESS LOC SETG OFF Asserted when local setting access is disabled.
SECURITY ACCESS LOC SETG ON Asserted when local setting access is enabled.
ACCESS LOC CMND OFF Asserted when local command access is disabled.
ACCESS LOC CMND ON Asserted when local command access is enabled.
ACCESS REM SETG OFF Asserted when remote setting access is disabled.
ACCESS REM SETG ON Asserted when remote setting access is enabled.
ACCESS REM CMND OFF Asserted when remote command access is disabled.
ACCESS REM CMND ON Asserted when remote command access is enabled.
UNAUTHORIZED ACCESS Asserted when a password entry fails while accessing a password protected
level of the D60.
REMOTE DEVICES REMOTE DEVICE 1 On Flag is set, logic=1
REMOTE DEVICE 2 On Flag is set, logic=1
REMOTE DEVICE 2 On Flag is set, logic=1
REMOTE DEVICE 16 On Flag is set, logic=1
RESETTING RESET OP Reset command is operated (set by all three operands below).
RESET OP (COMMS) Communications source of the reset command.
RESET OP (OPERAND) Operand (assigned in the INPUTS/OUTPUTS RESETTING menu) source
of the reset command.
RESET OP (PUSHBUTTON) Reset key (pushbutton) source of the reset command.
Some operands can be re-named by the user. These are the names of the breakers in the breaker control feature, the ID
(identification) of contact inputs, the ID of virtual inputs, and the ID of virtual outputs. If the user changes the default name
5
or ID of any of these operands, the assigned name will appear in the relay list of operands. The default names are shown in
the FlexLogic operands table above.
The characteristics of the logic gates are tabulated below, and the operators available in FlexLogic are listed in the Flex-
Logic operators table.
5 LATCH (S,R) Latch (set, reset): reset-dominant The parameter preceding LATCH(S,R) is
the reset input. The parameter preceding
the reset input is the set input.
Timer TIMER 1 Timer set with FlexLogic timer 1 settings. The timer is started by the preceding
parameter. The output of the timer is
TIMER 32 Timer set with FlexLogic timer 32 settings. TIMER #.
Assign = Virt Op 1 Assigns previous FlexLogic operand to virtual The virtual output is set by the preceding
virtual output 1. parameter
output = Virt Op 96
Assigns previous FlexLogic operand to virtual
output 96.
When forming a FlexLogic equation, the sequence in the linear array of parameters must follow these general rules:
1. Operands must precede the operator which uses the operands as inputs.
2. Operators have only one output. The output of an operator must be used to create a virtual output if it is to be used as
an input to two or more operators.
3. Assigning the output of an operator to a virtual output terminates the equation.
4. A timer operator (for example, "TIMER 1") or virtual output assignment (for example, " = Virt Op 1") may only be used
once. If this rule is broken, a syntax error will be declared.
Each equation is evaluated in the order in which the parameters have been entered.
FlexLogic provides latches which by definition have a memory action, remaining in the set state after the set input
has been asserted. However, they are volatile; that is, they reset on the re-application of control power.
NOTE
When making changes to settings, all FlexLogic equations are re-compiled whenever any new setting value is
entered, so all latches are automatically reset. If it is necessary to re-initialize FlexLogic during testing, for example,
it is suggested to power the unit down and then back up.
This section provides an example of implementing logic for a typical application. The sequence of the steps is quite impor-
tant as it should minimize the work necessary to develop the relay settings. Note that the example presented in the figure
below is intended to demonstrate the procedure, not to solve a specific application situation.
In the example below, it is assumed that logic has already been programmed to produce virtual outputs 1 and 2, and is only
a part of the full set of equations used. When using FlexLogic, it is important to make a note of each virtual output used – a
virtual output designation (1 to 96) can only be properly assigned once.
VIRTUAL OUTPUT 1
State=ON
VIRTUAL OUTPUT 2
Set
State=ON
LATCH
VIRTUAL INPUT 1 OR #1 Reset
State=ON Timer 2
XOR Time Delay Operate Output
DIGITAL ELEMENT 1 OR #2
on Dropout Relay H1
State=Pickup
(200 ms)
VIRTUAL OUTPUT 1
State=ON
VIRTUAL OUTPUT 2
Set
State=ON
LATCH
VIRTUAL INPUT 1 OR #1 Reset
State=ON Timer 2
XOR Time Delay
DIGITAL ELEMENT 1 OR #2 VIRTUAL OUTPUT 4
on Dropout
State=Pickup (200 ms)
827026A2.VSD
2. Prepare a logic diagram for the equation to produce virtual output 3, as this output will be used as an operand in the
virtual output 4 equation (create the equation for every output that will be used as an operand first, so that when these
operands are required they will already have been evaluated and assigned to a specific virtual output). The logic for
virtual output 3 is shown below with the final output assigned.
DIGITAL ELEMENT 2
State=Operated
827027A2.VSD
VIRTUAL OUTPUT 1
State=ON
VIRTUAL OUTPUT 2
Set
State=ON
LATCH
VIRTUAL INPUT 1 OR #1 Reset
State=ON Timer 2
XOR Time Delay VIRTUAL
DIGITAL ELEMENT 1 OR #2
on Dropout OUTPUT 4
State=Pickup
(200 ms)
Timer 1
5 VIRTUAL OUTPUT 3
State=ON
Time Delay
on Pickup
(800 ms)
CONTACT INPUT H1c
State=Closed 827028A2.VSD
01
02
03
04
05
.....
97
98
99
827029A1.VSD
98: The gate preceding the output is an AND, which in this case requires two inputs. The operator for this gate is a 2-
input AND so the parameter is “AND(2)”. Note that FlexLogic rules require that the number of inputs to most types
of operators must be specified to identify the operands for the gate. As the 2-input AND will operate on the two
operands preceding it, these inputs must be specified, starting with the lower.
97: This lower input to the AND gate must be passed through an inverter (the NOT operator) so the next parameter is
“NOT”. The NOT operator acts upon the operand immediately preceding it, so specify the inverter input next.
96: The input to the NOT gate is to be contact input H1c. The ON state of a contact input can be programmed to be
set when the contact is either open or closed. Assume for this example the state is to be ON for a closed contact.
The operand is therefore “Cont Ip H1c On”.
95: The last step in the procedure is to specify the upper input to the AND gate, the operated state of digital element 2.
This operand is "DIG ELEM 2 OP".
Writing the parameters in numerical order can now form the equation for virtual output 3:
[95] DIG ELEM 2 OP
[96] Cont Ip H1c On
[97] NOT
[98] AND(2)
[99] = Virt Op 3
It is now possible to check that this selection of parameters will produce the required logic by converting the set of parame-
ters into a logic diagram. The result of this process is shown below, which is compared to the logic for virtual output 3 dia-
gram as a check.
FLEXLOGIC ENTRY n:
95 DIG ELEM 2 OP VIRTUAL
AND
FLEXLOGIC ENTRY n: OUTPUT 3
96 Cont Ip H1c On
FLEXLOGIC ENTRY n:
5
97 NOT
FLEXLOGIC ENTRY n:
98 AND (2)
FLEXLOGIC ENTRY n:
99 =Virt Op 3
827030A2.VSD
FLEXLOGIC ENTRY n:
85 Virt Op 4 On
FLEXLOGIC ENTRY n:
86 Virt Op 1 On
FLEXLOGIC ENTRY n:
5 87
88
Virt Op 2 On
FLEXLOGIC ENTRY n:
Set
LATCH
Virt Ip 1 On
XOR OR Reset
FLEXLOGIC ENTRY n:
89 DIG ELEM 1 PKP
FLEXLOGIC ENTRY n:
90 XOR
FLEXLOGIC ENTRY n:
91 Virt Op 3 On VIRTUAL
OR T2 OUTPUT 4
FLEXLOGIC ENTRY n:
92 OR (4)
FLEXLOGIC ENTRY n:
93 LATCH (S,R)
FLEXLOGIC ENTRY n:
94 Virt Op 3 On T1
FLEXLOGIC ENTRY n:
95 TIMER 1
FLEXLOGIC ENTRY n:
96 Cont Ip H1c On
FLEXLOGIC ENTRY n:
97 OR (3)
FLEXLOGIC ENTRY n:
98 TIMER 2
FLEXLOGIC ENTRY n:
99 =Virt Op 4 827031A2.VSD
= Virt Op 3
Virt Op 4 On
Virt Op 1 On
Virt Op 2 On
Virt Ip 1 On
DIG ELEM 1 PKP
XOR(2)
Virt Op 3 On
OR(4)
LATCH (S,R)
Virt Op 3 On
TIMER 1
Cont Ip H1c On
OR(3)
TIMER 2
= Virt Op 4
END
In the expression above, the virtual output 4 input to the four-input OR is listed before it is created. This is typical of a
form of feedback, in this case, used to create a seal-in effect with the latch, and is correct.
8. The logic should always be tested after it is loaded into the relay, in the same fashion as has been used in the past.
Testing can be simplified by placing an "END" operator within the overall set of FlexLogic equations. The equations will
then only be evaluated up to the first "END" operator.
The "On" and "Off" operands can be placed in an equation to establish a known set of conditions for test purposes, and
the "INSERT" and "DELETE" commands can be used to modify equations.
There are 512 FlexLogic entries available, numbered from 1 to 512, with default END entry settings. If a "Disabled" Element
is selected as a FlexLogic entry, the associated state flag will never be set to ‘1’. The ‘+/–‘ key may be used when editing
FlexLogic equations from the keypad to quickly scan through the major parameter types.
There are 32 identical FlexLogic timers available. These timers can be used as operators for FlexLogic equations.
• TIMER 1 TYPE: This setting is used to select the time measuring unit.
• TIMER 1 PICKUP DELAY: Sets the time delay to pickup. If a pickup delay is not required, set this function to "0".
• TIMER 1 DROPOUT DELAY: Sets the time delay to dropout. If a dropout delay is not required, set this function to "0".
5.5.7 FLEXELEMENTS
5 PICKUP: 1.000 pu
FLEXELEMENT 1 Range: 0.1 to 50.0% in steps of 0.1
MESSAGE
HYSTERESIS: 3.0%
FLEXELEMENT 1 dt Range: milliseconds, seconds, minutes
MESSAGE
UNIT: milliseconds
FLEXELEMENT 1 dt: Range: 20 to 86400 in steps of 1
MESSAGE
20
FLEXELEMENT 1 PKP Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
DELAY: 0.000 s
FLEXELEMENT 1 RST Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
DELAY: 0.000 s
FLEXELEMENT 1 BLK: Range: FlexLogic operand
MESSAGE
Off
FLEXELEMENT 1 Range: Self-reset, Latched, Disabled
MESSAGE
TARGET: Self-reset
FLEXELEMENT 1 Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled
A FlexElement is a universal comparator that can be used to monitor any analog actual value calculated by the relay or a
net difference of any two analog actual values of the same type. The effective operating signal could be treated as a signed
number or its absolute value could be used as per user's choice.
The element can be programmed to respond either to a signal level or to a rate-of-change (delta) over a pre-defined period
of time. The output operand is asserted when the operating signal is higher than a threshold or lower than a threshold as
per user's choice.
SETTING
SETTINGS
FLEXELEMENT 1
FUNCTION: FLEXELEMENT 1 INPUT MODE:
Enabled = 1
FLEXELEMENT 1 COMP MODE:
FLEXELEMENT 1 DIRECTION:
SETTING
FLEXELEMENT 1 PICKUP:
FLEXELEMENT 1 BLK:
FLEXELEMENT 1 INPUT
AND HYSTERESIS:
Off = 0
FLEXELEMENT 1 dt UNIT: SETTINGS
FxE 1 PKP
ACTUAL VALUE
FlexElement 1 OpSig
842004A4.CDR
The FLEXELEMENT 1 DIRECTION setting enables the relay to respond to either high or low values of the operating signal. The
following figure explains the application of the FLEXELEMENT 1 DIRECTION, FLEXELEMENT 1 PICKUP and FLEXELEMENT 1 HYS-
TERESIS settings.
FLEXELEMENT 1 PKP
FLEXELEMENT
DIRECTION = Over
HYSTERESIS = % of PICKUP
FlexElement 1 OpSig
PICKUP
FLEXELEMENT 1 PKP
FLEXELEMENT
DIRECTION = Under
HYSTERESIS = % of PICKUP
FlexElement 1 OpSig
PICKUP
842705A1.CDR
FLEXELEMENT 1 PKP
5 FLEXELEMENT
DIRECTION = Over;
FLEXELEMENT INPUT
MODE = Signed;
FlexElement 1 OpSig
FLEXELEMENT 1 PKP
FLEXELEMENT
DIRECTION = Over;
FLEXELEMENT INPUT
MODE = Absolute;
FlexElement 1 OpSig
FLEXELEMENT 1 PKP
FLEXELEMENT
DIRECTION = Under;
FLEXELEMENT INPUT
MODE = Signed;
FlexElement 1 OpSig
FLEXELEMENT 1 PKP
FLEXELEMENT
DIRECTION = Under;
FLEXELEMENT INPUT
MODE = Absolute;
FlexElement 1 OpSig
842706A2.CDR
The FLEXELEMENT 1 PICKUP setting specifies the operating threshold for the effective operating signal of the element. If set
to “Over”, the element picks up when the operating signal exceeds the FLEXELEMENT 1 PICKUP value. If set to “Under”, the
element picks up when the operating signal falls below the FLEXELEMENT 1 PICKUP value.
The FLEXELEMENT 1 HYSTERESIS setting controls the element dropout. It should be noticed that both the operating signal
and the pickup threshold can be negative facilitating applications such as reverse power alarm protection. The FlexElement
can be programmed to work with all analog actual values measured by the relay. The FLEXELEMENT 1 PICKUP setting is
entered in per-unit values using the following definitions of the base units:
The FLEXELEMENT 1 HYSTERESIS setting defines the pickup–dropout relation of the element by specifying the width of the
hysteresis loop as a percentage of the pickup value as shown in the FlexElement direction, pickup, and hysteresis diagram.
The FLEXELEMENT 1 DT UNIT setting specifies the time unit for the setting FLEXELEMENT 1 dt. This setting is applicable only if
FLEXELEMENT 1 COMP MODE is set to “Delta”. The FLEXELEMENT 1 DT setting specifies duration of the time interval for the
rate of change mode of operation. This setting is applicable only if FLEXELEMENT 1 COMP MODE is set to “Delta”.
This FLEXELEMENT 1 PKP DELAY setting specifies the pickup delay of the element. The FLEXELEMENT 1 RST DELAY setting
specifies the reset delay of the element.
The non-volatile latches provide a permanent logical flag that is stored safely and will not reset upon reboot after the relay
is powered down. Typical applications include sustaining operator commands or permanently block relay functions, such as
Autorecloser, until a deliberate interface action resets the latch. The settings element operation is described below:
• LATCH 1 TYPE: This setting characterizes Latch 1 to be Set- or Reset-dominant.
• LATCH 1 SET: If asserted, the specified FlexLogic operands 'sets' Latch 1.
5 • LATCH 1 RESET: If asserted, the specified FlexLogic operand 'resets' Latch 1.
SETTING
SETTING
LATCH N LATCH N LATCH N LATCH N LATCH N LATCH 1 FUNCTION:
TYPE SET RESET ON OFF
LATCH 1 TYPE:
Reset ON OFF ON OFF Disabled=0
Dominant Enabled=1 RUN
OFF OFF Previous Previous
State State
ON ON OFF ON SETTING
Each protection element can be assigned up to six different sets of settings according to setting group designations 1 to 6.
The performance of these elements is defined by the active setting group at a given time. Multiple setting groups allow the
user to conveniently change protection settings for different operating situations (for example, altered power system config-
uration, season of the year, etc.). The active setting group can be preset or selected via the SETTING GROUPS menu (see the
Control elements section later in this chapter). See also the Introduction to elements section at the beginning of this chap-
ter.
Each of the six setting group menus is identical. Setting group 1 (the default active group) automatically becomes active if
no other group is active (see the Control elements section for additional details).
5 MESSAGE
DELAY: 0.045 s
AR CO-ORD RESET Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
DELAY: 0.005 s
TERMINAL OPEN: Range: FlexLogic operand
MESSAGE
Off
AR ACCELERATE: Range: FlexLogic operand
MESSAGE
Off
LINE PICKUP DISTANCE Range: Disabled, Enabled
MESSAGE
TRIP: Enabled
LINE PICKUP BLOCK: Range: FlexLogic operand
MESSAGE
Off
LINE PICKUP Range: Self-reset, Latched, Disabled
MESSAGE
TARGET: Self-reset
LINE PICKUP Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled
The line pickup feature uses a combination of undercurrent and undervoltage to identify a line that has been de-energized
(line end open). Alternately, the user may assign a FlexLogic operand to the TERMINAL OPEN setting that specifies the termi-
nal status. Three instantaneous overcurrent elements are used to identify a previously de-energized line that has been
closed onto a fault. Faults other than close-in faults can be identified satisfactorily with the distance elements.
Co-ordination features are included to ensure satisfactory operation when high speed automatic reclosure (AR) is
employed. The AR CO-ORD DELAY setting allows the overcurrent setting to be below the expected load current seen after
reclose. Co-ordination is achieved by all of the LINE PICKP UV elements resetting and blocking the trip path before the AR
CO-ORD DELAY times out. The AR CO-ORD BYPASS setting is normally enabled. It is disabled if high speed autoreclosure is
implemented.
The line pickup protection incorporates zone 1 extension capability. When the line is being re-energized from the local ter-
minal, pickup of an overreaching zone 2 or excessive phase current within eight power cycles after the autorecloser issues
a close command results in the LINE PICKUP RCL TRIP FlexLogic operand. For security, the overcurrent trip is supervised by
an undervoltage condition, which in turn is controlled by the VT FUSE FAIL OP operand with a 10 ms coordination timer. If a
trip from distance in not required, then it can be disabled with the LINE PICKUP DISTANCE TRIP setting. Configure the LINE
PICKUP RCL TRIP operand to perform a trip action if the intent is apply zone 1 extension.
The zone 1 extension philosophy used here normally operates from an under-reaching zone, and uses an overreaching
distance zone when reclosing the line with the other line end open. The AR ACCELERATE setting is provided to achieve
zone 1 extension functionality if external autoreclosure is employed. Another zone 1 extension approach is to permanently
apply an overreaching zone, and reduce the reach when reclosing. This philosophy can be programmed via the autore-
close scheme.
6(77,1*
7HUPLQDO2SHQ )/(;/2*,&23(5$1'
2II /,1(3,&.83893.3
$1'
6(77,1* 6(77,1*
)XQFWLRQ 2YHUYROWDJH3LFNXS'HOD\
(QDEOHG 73.3
'LVDEOHG 25
7567
$1'
6(77,1*
%ORFN
2II 6(77,1* 6(77,1*6
8QGHUYROWDJH3LFNXS /LQH(QG2SHQ3LFNXS'HOD\
)/(;/2*,&23(5$1'
581 /LQH(QG2SHQ5HVHW'HOD\
/,1(3,&.83/(23.3
6(77,1* 9$*RU9$%VHWWLQJ 73.3
/(2 OLQHHQGRSHQ
6LJQDO6RXUFH 9%*RU9%&VHWWLQJ $1' 25
7567
9$* 9$% 9&*RU9&$VHWWLQJ 6(77,1*6
9%* 9%& $1' $XWRUHFORVH&RRUGLQDWLRQ
9&* 9&$ 3LFNXS'HOD\
581
,$ ,$SX $XWRUHFORVH&RRUGLQDWLRQ
5HVHW'HOD\
,% ,%SX $1'
73.3
,& ,&SX
5
$1'
7567
$1'
PV
6(77,1* $1' 25
3KDVH,2&/LQH3LFNXS $1'
$1'
581
,$!VHWWLQJ
6(77,1* ,%!VHWWLQJ 25
$XWRUHFORVH&RRUGLQDWLRQ ,&!VHWWLQJ $1'
%\SDVV )/(;/2*,&23(5$1'6
(QDEOHG 25 /,1(3,&.8323
'LVDEOHG /,1(3,&.833.3
/,1(3,&.83'32
)/(;/2*,&23(5$1'6
$1'
*1'',67=3.3
25
3+',67=3.3
$1'
25
)/(;/2*,&23(5$1'
6(77,1* $1' /,1(3,&.835&/75,3
'LVWDQFH7ULS
7,0(5
(QDEOHG
'LVDEOHG
F\FOHV )/(;/2*,&23(5$1'6
/,1(3,&.83,$
6(77,1*
/,1(3,&.83,%
$XWRUHFORVH$FFHOHUDWH
/,1(3,&.83,&
2II
)/(;/2*,&23(5$1'6 25
$5&/26(%.5
$5&/26(%.5
'/DQG/RQO\
)/(;/2*,&23(5$1'
65&;97)86()$,/23
6RXUFHVHOHFWHGLQWKHOLQHSLFNXSHOHPHQW $.&'5
5.6.4 DISTANCE
a) MAIN MENU
PATH: SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) DISTANCE
5 MESSAGE
PHASE DISTANCE Z5
See page 5–159.
GROUND DISTANCE Z1
MESSAGE See page 5–168.
GROUND DISTANCE Z2
MESSAGE See page 5–168.
GROUND DISTANCE Z3
MESSAGE See page 5–168.
GROUND DISTANCE Z4
MESSAGE See page 5–168.
GROUND DISTANCE Z5
MESSAGE See page 5–168.
Four common settings are available for distance protection. The DISTANCE SOURCE identifies the signal source for all dis-
tance functions. The mho distance functions use a dynamic characteristic: the positive-sequence voltage – either memo-
rized or actual – is used as a polarizing signal. The memory voltage is also used by the built-in directional supervising
functions applied for both the mho and quad characteristics.
The MEMORY DURATION setting specifies the length of time a memorized positive-sequence voltage should be used in the
distance calculations. After this interval expires, the relay checks the magnitude of the actual positive-sequence voltage. If
it is higher than 10% of the nominal, the actual voltage is used, if lower – the memory voltage continues to be used.
The memory is established when the positive-sequence voltage stays above 80% of its nominal value for five power system
cycles. For this reason it is important to ensure that the nominal secondary voltage of the VT is entered correctly under the
SETTINGS SYSTEM SETUP AC INPUTS VOLTAGE BANK menu.
Set MEMORY DURATION long enough to ensure stability on close-in reverse three-phase faults. For this purpose, the maxi-
mum fault clearing time (breaker fail time) in the substation should be considered. On the other hand, the MEMORY DURA-
TION cannot be too long as the power system may experience power swing conditions rotating the voltage and current
phasors slowly while the memory voltage is static, as frozen at the beginning of the fault. Keeping the memory in effect for
too long may eventually lead to incorrect operation of the distance functions.
The distance zones can be forced to become self-polarized through the FORCE SELF-POLAR setting. Any user-selected con-
dition (FlexLogic operand) can be configured to force self-polarization. When the selected operand is asserted (logic 1), the
distance functions become self-polarized regardless of other memory voltage logic conditions. When the selected operand
is de-asserted (logic 0), the distance functions follow other conditions of the memory voltage logic as shown below.
The distance zones can be forced to become memory-polarized through the FORCE MEM-POLAR setting. Any user-selected
condition (any FlexLogic operand) can be configured to force memory polarization. When the selected operand is asserted
(logic 1), the distance functions become memory-polarized regardless of the positive-sequence voltage magnitude at this
time. When the selected operand is de-asserted (logic 0), the distance functions follow other conditions of the memory volt-
age logic.
The FORCE SELF-POLAR and FORCE MEM-POLAR settings should never be asserted simultaneously. If this happens, the logic
will give higher priority to forcing self-polarization as indicated in the logic below. This is consistent with the overall philoso-
phy of distance memory polarization.
The memory polarization cannot be applied permanently but for a limited time only; the self-polarization may be
applied permanently and therefore should take higher priority.
NOTE
SETTING
Force Memory Polarization
Update memory
Off = 0
AND RUN
SETTING
Memory duration
SETTING TIMER 0
Distance Source | V_1 | < 1.15 pu 5 cycles AND
= VA, Vrms_A | Vrms – | V | | < Vrms / 8 AND Treset
S Q
= VB, Vrms_B | Vrms – | V | | < Vrms / 8 0 AND
= VC, Vrms_C | Vrms – | V | | < Vrms / 8
Use V_1 memory
5
= V_1 | V_1 | > 0.80 pu TIMER
6 cycles OR
= IA | IA | < 0.05 pu
| IB | < 0.05 pu
AND
R Use V_1
= IB OR
0
= IC | IC | < 0.05 pu AND
Tracking Freq, *SRCx Freq | V_1 | < 0.10 pu
*SRCx is the source used in distance | fTRACK - fSRC | > 1 Hz
L90 Only
SETTING
Force Self Polarization
Off = 0 827842A9.CDR
b) PHASE DISTANCE
PATH: SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) DISTANCE PHASE DISTANCE Z1(Z5)
5
LEVEL: 0.000 pu
PHS DIST Z1 Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
DELAY: 0.000 s
PHS DIST Z1 BLK: Range: FlexLogic operand
MESSAGE
Off
PHS DIST Z1 Range: Self-reset, Latched, Disabled
MESSAGE
TARGET: Self-reset
PHS DIST Z1 Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled
The phase mho distance function uses a dynamic 100% memory-polarized mho characteristic with additional reactance,
directional, and overcurrent supervising characteristics. When set to “Non-directional”, the mho function becomes an offset
mho with the reverse reach controlled independently from the forward reach, and all the directional characteristics
removed.
The phase quadrilateral distance function is comprised of a reactance characteristic, right and left blinders, and 100%
memory-polarized directional and current supervising characteristics. When set to “Non-directional”, the quadrilateral func-
tion applies a reactance line in the reverse direction instead of the directional comparators. Refer to Chapter 8 for additional
information.
Each phase distance zone is configured individually through its own setting menu. All of the settings can be independently
modified for each of the zones except:
1. The SIGNAL SOURCE setting (common for the distance elements of all zones as entered under SETTINGS GROUPED
ELEMENTS SETTING GROUP 1(6) DISTANCE).
2. The MEMORY DURATION setting (common for the distance elements of all zones as entered under SETTINGS
GROUPED ELEMENTS SETTING GROUP 1(6) DISTANCE).
The common distance settings described earlier must be properly chosen for correct operation of the phase distance ele-
ments. Additional details may be found in chapter 8: Theory of operation.
Although all zones can be used as either instantaneous elements (pickup [PKP] and dropout [DPO] FlexLogic operands) or
time-delayed elements (operate [OP] FlexLogic operands), only zone 1 is intended for the instantaneous under-reaching
tripping mode.
Ensure that the Phase VT Secondary Voltage setting (see the SETTINGS ðò SYSTEM SETUP ð AC
INPUTS ðò VOLTAGE BANK menu) is set correctly to prevent improper operation of associated
memory action.
• PHS DIST Z1 DIR: All phase distance zones are reversible. The forward direction is defined by the PHS DIST Z1 RCA
setting, whereas the reverse direction is shifted 180° from that angle. The non-directional zone spans between the for-
ward reach impedance defined by the PHS DIST Z1 REACH and PHS DIST Z1 RCA settings, and the reverse reach imped-
ance defined by PHS DIST Z1 REV REACH and PHS DIST Z1 REV REACH RCA as illustrated below.
• PHS DIST Z1 SHAPE: This setting selects the shape of the phase distance function between the mho and quadrilat-
eral characteristics. The selection is available on a per-zone basis. The two characteristics and their possible varia-
tions are shown in the following figures.
COMP LIMIT
H
REAC
DIR RCA
RCA
R
5
837720A1.CDR
COMP LIMIT
R E AC H
RCA
REV REACH
RCA
E AC H
REV R
837802A1.CDR
COMP LIMIT
COMP LIMIT
REACH
DIR COMP LIMIT
DIR RCA
LFT BLD RCA RCA RGT BLD RCA
R
-LFT BLD RGT BLD
837721A1.CDR
COMP LIMIT
COMP LIMIT
5
R E AC H
R
-LFT BLD RGT BLD
REV REACH
R E V R E AC H
RCA
COMP LIMIT
COMP LIMIT
837803A1.CDR
H
REAC
REAC
R R
H
REAC
R R
837722A1.CDR
H
REAC
REAC
R R
REAC
R R
837723A1.CDR
• PHS DIST Z1 XFMR VOL CONNECTION: The phase distance elements can be applied to look through a three-phase
delta-wye or wye-delta power transformer. In addition, VTs and CTs could be located independently from one another
at different windings of the transformer. If the potential source is located at the correct side of the transformer, this set-
ting shall be set to “None”.
This setting specifies the location of the voltage source with respect to the involved power transformer in the direction
of the zone. The following figure illustrates the usage of this setting. In section (a), zone 1 is looking through a trans-
former from the delta into the wye winding. Therefore, the Z1 setting shall be set to “Dy11”. In section (b), Zone 4 is
looking through a transformer from the wye into the delta winding. Therefore, the Z4 setting shall be set to “Yd1”. The
zone is restricted by the potential point (location of the VTs) as illustrated in Figure (e).
• PHS DIST Z1 XFMR CUR CONNECTION: This setting specifies the location of the current source with respect to the
involved power transformer in the direction of the zone. In section (a) of the following figure, zone 1 is looking through
a transformer from the delta into the wye winding. Therefore, the Z1 setting shall be set to “Dy11”. In section (b), the
CTs are located at the same side as the read point. Therefore, the Z4 setting shall be set to “None”.
See the Theory of operation chapter for more details, and the Application of settings chapter for information on calcu-
lating distance reach settings in applications involving power transformers.
(a) (b)
delta wye, 330o lag delta wye, 330o lag
Z4 Z4
5
Z4 XFRM CUR CONNECTION = None Z4 XFRM CUR CONNECTION = None
Z1 Z1
(c) (e)
delta wye, 330o lag
L1 L2
Z4 Zone 4
Zone 1
Z4 XFRM VOL CONNECTION = None
Z4 XFRM CUR CONNECTION = Yd1 ZL1 ZT ZL2
Z1
To achieve specified operating speed of distance elements, the relay internally calculates source to line impedance
ratio (SIR) from fault phasors. In these calculations, line impedance is estimated based on the zone 1 reach setting.
Therefore, in order to calculate the SIR value properly and to maintain the optimal operating speed of the distance ele-
ments, you need to set zone 1 reach with a regular 80 to 85% of the line impedance reach setting, even when zone 1
is disabled.
• PHS DIST Z1 RCA: This setting specifies the characteristic angle (similar to the ‘maximum torque angle’ in previous
technologies) of the phase distance characteristic for the forward and reverse applications. In the non-directional appli-
cations, this setting defines the angle of the forward reach impedance. The reverse reach impedance in the non-direc-
tional applications is set independently. The setting is an angle of reach impedance as shown in the distance
characteristic figures shown earlier. This setting is independent from PHS DIST Z1 DIR RCA, the characteristic angle of an
extra directional supervising function.
• PHS DIST Z1 REV REACH: This setting defines the reverse reach of the zone set to non-directional (PHS DIST Z1 DIR
setting). The value must be entered in secondary ohms. This setting does not apply when the zone direction is set to
“Forward” or “Reverse”.
• PHS DIST Z1 REV REACH RCA: This setting defines the angle of the reverse reach impedance if the zone is set to
non-directional (PHS DIST Z1 DIR setting). This setting does not apply when the zone direction is set to “Forward” or
“Reverse”.
• PHS DIST Z1 COMP LIMIT: This setting shapes the operating characteristic. In particular, it produces the lens-type
characteristic of the mho function and a tent-shaped characteristic of the reactance boundary of the quadrilateral func-
tion. If the mho shape is selected, the same limit angle applies to both the mho and supervising reactance compara-
tors. In conjunction with the mho shape selection, the setting improves loadability of the protected line. In conjunction
with the quadrilateral characteristic, this setting improves security for faults close to the reach point by adjusting the
reactance boundary into a tent-shape.
• PHS DIST Z1 DIR RCA: This setting selects the characteristic angle (or maximum torque angle) of the directional
supervising function. If the mho shape is applied, the directional function is an extra supervising function as the 5
dynamic mho characteristic is itself directional. In conjunction with the quadrilateral shape, this setting defines the only
directional function built into the phase distance element. The directional function uses the memory voltage for polar-
ization. This setting typically equals the distance characteristic angle PHS DIST Z1 RCA.
• PHS DIST Z1 DIR COMP LIMIT: Selects the comparator limit angle for the directional supervising function.
• PHS DIST Z1 QUAD RGT BLD: This setting defines the right blinder position of the quadrilateral characteristic along
the resistive axis of the impedance plane (see the Quadrilateral distance characteristic figures). The angular position of
the blinder is adjustable with the use of the PHS DIST Z1 QUAD RGT BLD RCA setting. This setting applies only to the
quadrilateral characteristic and should be set giving consideration to the maximum load current and required resistive
coverage.
• PHS DIST Z1 QUAD RGT BLD RCA: This setting defines the angular position of the right blinder of the quadrilateral
characteristic (see the Quadrilateral distance characteristic figures).
• PHS DIST Z1 QUAD LFT BLD: This setting defines the left blinder position of the quadrilateral characteristic along the
resistive axis of the impedance plane (see the Quadrilateral distance characteristic figures). The angular position of the
blinder is adjustable with the use of the PHS DIST Z1 QUAD LFT BLD RCA setting. This setting applies only to the quadri-
lateral characteristic and should be set with consideration to the maximum load current.
• PHS DIST Z1 QUAD LFT BLD RCA: This setting defines the angular position of the left blinder of the quadrilateral
characteristic (see the Quadrilateral distance characteristic figures).
• PHS DIST Z1 SUPV: The phase distance elements are supervised by the magnitude of the line-to-line current (fault
loop current used for the distance calculations). For convenience, 3 is accommodated by the pickup (that is, before
being used, the entered value of the threshold setting is multiplied by 3 ).
If the minimum fault current level is sufficient, the current supervision pickup should be set above maximum full load
current preventing maloperation under VT fuse fail conditions. This requirement may be difficult to meet for remote
faults at the end of zones 2 and above. If this is the case, the current supervision pickup would be set below the full
load current, but this may result in maloperation during fuse fail conditions.
Zone 1 is sealed-in with the current supervision.
• PHS DIST Z1 VOLT LEVEL: This setting is relevant for applications on series-compensated lines, or in general, if
series capacitors are located between the relaying point and a point where the zone shall not overreach. For plain
(non-compensated) lines, set to zero. Otherwise, the setting is entered in per unit of the phase VT bank configured
under the DISTANCE SOURCE. Effectively, this setting facilitates dynamic current-based reach reduction. In non-direc-
tional applications (PHS DIST Z1 DIR set to “Non-directional”), this setting applies only to the forward reach of the non-
directional zone. See chapters 8 and 9 for information on calculating this setting for series compensated lines.
• PHS DIST Z1 DELAY: This setting allows the user to delay operation of the distance elements and implement stepped
distance protection. The distance element timers for zones 2 and higher apply a short dropout delay to cope with faults
located close to the zone boundary when small oscillations in the voltages or currents could inadvertently reset the
timer. Zone 1 does not need any drop out delay since it is sealed-in by the presence of current.
• PHS DIST Z1 BLK: This setting enables the user to select a FlexLogic operand to block a given distance element. VT
fuse fail detection is one of the applications for this setting.
AND
OR
SETTING
PH DIST Z1 DELAY AND FLEXLOGIC OPERANDS
FLEXLOGIC OPERAND TPKP OR OR PH DIST Z1 OP
PH DIST Z1 PKP AB
0
FLEXLOGIC OPERAND TPKP
PH DIST Z1 PKP BC
0 AND
FLEXLOGIC OPERAND TPKP OR
PH DIST Z1 PKP CA
0 FLEXLOGIC OPERANDS
PH DIST Z1 OP AB
PH DIST Z1 OP BC
AND
FLEXLOGIC OPERANDS PH DIST Z1 OP CA
AND
OPEN POLE OP **
** D60, L60, and L90 only. Other UR-series models apply regular current seal-in for zone 1. 837017A8.CDR
IURPWKHRSHQSROHHOHPHQW '/DQG/RQO\
)/(;/2*,&23(5$1'
23(132/(23
)/(;/2*,&23(5$1'
7,0(5 )/(;/2*,&23(5$1'
3+',67=3.3&$ 6(77,1*
PV $1' $1' 3+',67=23&$
3+',67='(/$<
25
IURPWKHWULSRXWSXWHOHPHQW 25
73.3
PV
)/(;/2*,&23(5$1'
)/(;/2*,&23(5$1'
75,3=3+705,1,7
25 3+',67=23
$&'5
)/(;/2*,&23(5$1'
23(132/(23
7,0(5 6(77,1*
)/(;/2*,&23(5$1' PV 3+',67='(/$<
$1' )/(;/2*,&23(5$1'
3+',67=3.3$% 73.3
PV 25 3+',67=23$%
7,0(5 6(77,1*
)/(;/2*,&23(5$1' PV 3+',67='(/$<
$1' )/(;/2*,&23(5$1'
3+',67=3.3%& 73.3
PV 25 3+',67=23%&
7,0(5 6(77,1*
)/(;/2*,&23(5$1' PV 3+',67='(/$<
$1' )/(;/2*,&23(5$1'
3+',67=3.3&$ 73.3
PV 25 3+',67=23&$
)/(;/2*,&23(5$1'
25 3+',67=23
'/DQG/RQO\ $$&'5
SETTINGS
PH DIST Z1 DIR
PH DIST Z1 SHAPE
PH DIST Z1 XFMR
VOL CONNECTION
5
SETTING PH DIST Z1 XFMR
PH DIST Z1 FUNCTION CUR CONNECTION
Enabled = 1 PH DIST Z1 REACH
PH DIST Z1 RCA
PH DIST Z1 REV REACH
AND PH DIST Z1 REV REACH RCA
SETTING
PH DIST Z1 COMP LIMIT
PH DIST Z1 BLK
PH DIST Z1 QUAD RGT BLD
Off = 0
PH DIST Z1 QUAD RGT BLD RCA Quadrilateral
PH DIST Z1 QUAD LFT BLD characteristic only
PH DIST Z1 QUAD LFT BLD RCA
SETTING PH DIST Z1 VOLT LEVEL FLEXLOGIC OPERANDS
DISTANCE SOURCE RUN AND PH DIST Z1 PKP AB
IA-IB PH DIST Z1 DPO AB
A-B ELEMENT
IB-IC
IC-IA RUN FLEXLOGIC OPERANDS
VAG-VBG B-C ELEMENT AND PH DIST Z1 PKP BC
Wye
VTs
SETTING
PHS DIST Z1 SUPV
RUN FLEXLOGIC OPERAND
| IA – IB | > 3 × Pickup PH DIST Z1 SUPN IAB
c) GROUND DISTANCE
PATH: SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) DISTANCE GROUND DISTANCE Z1(Z5)
The ground mho distance function uses a dynamic 100% memory-polarized mho characteristic with additional reactance,
directional, current, and phase selection supervising characteristics. The ground quadrilateral distance function is com-
posed of a reactance characteristic, right and left blinders, and 100% memory-polarized directional, overcurrent, and phase
selection supervising characteristics.
When set to non-directional, the mho function becomes an offset mho with the reverse reach controlled independently from
the forward reach, and all the directional characteristics removed. When set to non-directional, the quadrilateral function
applies a reactance line in the reverse direction instead of the directional comparators.
The reactance supervision for the mho function uses the zero-sequence current for polarization. The reactance line of the
quadrilateral function uses either zero-sequence or negative-sequence current as a polarizing quantity. The selection is
controlled by a user setting and depends on the degree of non-homogeneity of the zero-sequence and negative-sequence
equivalent networks.
The directional supervision uses memory voltage as polarizing quantity and both zero- and negative-sequence currents as 5
operating quantities.
The phase selection supervision restrains the ground elements during double-line-to-ground faults as they – by principles
of distance relaying – may be inaccurate in such conditions. Ground distance zones 2 and higher apply additional zero-
sequence directional supervision. See chapter 8 for additional details.
Each ground distance zone is configured individually through its own setting menu. All of the settings can be independently
modified for each of the zones except:
1. The SIGNAL SOURCE setting (common for both phase and ground elements for all zones as entered under the SETTINGS
GROUPED ELEMENTS SETTING GROUP 1(6) DISTANCE menu).
2. The MEMORY DURATION setting (common for both phase and ground elements for all zones as entered under the SET-
TINGS GROUPED ELEMENTS SETTING GROUP 1(6) DISTANCE menu).
The common distance settings noted at the start of this section must be properly chosen for correct operation of the ground
distance elements.
Although all ground distance zones can be used as either instantaneous elements (pickup [PKP] and dropout [DPO] Flex-
Logic signals) or time-delayed elements (operate [OP] FlexLogic signals), only zone 1 is intended for the instantaneous
under-reaching tripping mode.
Ensure that the PHASE VT SECONDARY VOLTAGE (see the SETTINGS SYSTEM SETUP AC INPUTS VOLTAGE
BANK menu) is set correctly to prevent improper operation of associated memory action.
NOTE
• GND DIST Z1 DIR: All ground distance zones are reversible. The forward direction is defined by the GND DIST Z1 RCA
setting and the reverse direction is shifted by 180° from that angle. The non-directional zone spans between the for-
ward reach impedance defined by the GND DIST Z1 REACH and GND DIST Z1 RCA settings, and the reverse reach imped-
ance defined by the GND DIST Z1 REV REACH and GND DIST Z1 REV REACH RCA settings.
• GND DIST Z1 SHAPE: This setting selects the shape of the ground distance characteristic between the mho and
quadrilateral characteristics. The selection is available on a per-zone basis.
The directional and non-directional quadrilateral ground distance characteristics are shown below. The directional and
non-directional mho ground distance characteristics are the same as those shown for the phase distance element in
the previous sub-section.
X
"+" NON-HOMOGEN. ANG
REACH
DIR COMP LIMIT
DIR RCA
LFT BLD RCA RCA RGT BLD RCA
R
-LFT BLD RGT BLD
837769A1.CDR
X
"+" NON-HOMOGEN. ANG
5
REACH
R
-LFT BLD RGT BLD
RE V REACH
REV REACH
RCA
837770A1.CDR
• GND DIST Z1 ZOM/Z1 ANG: This setting specifies the angle difference between the mutual zero-sequence imped-
ance between the lines and the positive-sequence impedance of the protected line.
• GND DIST Z1 REACH: This setting defines the reach of the zone for the forward and reverse applications. In non-
directional applications, this setting defines the forward reach of the zone. The reverse reach impedance in non-direc-
tional applications is set independently. The angle of the reach impedance is entered as the GND DIST Z1 RCA setting.
The reach impedance is entered in secondary ohms.
To achieve specified operating speed of distance elements, the relay internally calculates source to line impedance
ratio (SIR) from fault phasors. In these calculations, line impedance is estimated based on the zone 1 reach setting.
Therefore, in order to calculate the SIR value properly and to maintain the optimal operating speed of the distance ele-
ments, you need to set zone 1 reach with a regular 80 to 85% of the line impedance reach setting, even when zone 1
is disabled.
• GND DIST Z1 RCA: This setting specifies the characteristic angle (similar to the maximum torque angle in previous
technologies) of the ground distance characteristic for the forward and reverse applications. In the non-directional
applications this setting defines the forward reach of the zone. The reverse reach impedance in the non-directional
applications is set independently. This setting is independent from the GND DIST Z1 DIR RCA setting (the characteristic
angle of an extra directional supervising function).
The relay internally performs zero-sequence compensation for the protected circuit based on the values
entered for GND DIST Z1 Z0/Z1 MAG and GND DIST Z1 Z0/Z1 ANG, and if configured to do so, zero-sequence com-
NOTE
pensation for mutual coupling based on the values entered for GND DIST Z1 Z0M/Z1 MAG and GND DIST Z1 Z0M/Z1
ANG. The GND DIST Z1 REACH and GND DIST Z1 RCA should, therefore, be entered in terms of positive sequence
quantities. Refer to chapters 8 for additional information
• GND DIST Z1 REV REACH: This setting defines the reverse reach of the zone set to non-directional (GND DIST Z1 DIR
setting). The value must be entered in secondary ohms. This setting does not apply when the zone direction is set to
“Forward” or “Reverse”.
5
• GND DIST Z1 REV REACH RCA: This setting defines the angle of the reverse reach impedance if the zone is set to
non-directional (GND DIST Z1 DIR setting). This setting does not apply when the zone direction is set to “Forward” or
“Reverse”.
• GND DIST Z1 POL CURRENT: This setting applies only if the GND DIST Z1 SHAPE is set to “Quad” and controls the
polarizing current used by the reactance comparator of the quadrilateral characteristic. Either the zero-sequence or
negative-sequence current could be used. In general, a variety of system conditions must be examined to select an
optimum polarizing current. This setting becomes less relevant when the resistive coverage and zone reach are set
conservatively. Also, this setting is more relevant in lower voltage applications such as on distribution lines or cables,
as compared with high-voltage transmission lines. This setting applies to both the zone 1 and reverse reactance lines
if the zone is set to non-directional. Refer to chapters 8 and 9 for additional information.
• GND DIST Z1 NON-HOMOGEN ANG: This setting applies only if the GND DIST Z1 SHAPE is set to “Quad” and provides
a method to correct the angle of the polarizing current of the reactance comparator for non-homogeneity of the zero-
sequence or negative-sequence networks. In general, a variety of system conditions must be examined to select this
setting. In many applications this angle is used to reduce the reach at high resistances in order to avoid overreaching
under far-out reach settings and/or when the sequence networks are greatly non-homogeneous. This setting applies to
both the forward and reverse reactance lines if the zone is set to non-directional. Refer to chapters 8 and 9 for addi-
tional information.
• GND DIST Z1 COMP LIMIT: This setting shapes the operating characteristic. In particular, it enables a lens-shaped
characteristic of the mho function and a tent-shaped characteristic of the quadrilateral function reactance boundary. If
the mho shape is selected, the same limit angle applies to mho and supervising reactance comparators. In conjunction
with the mho shape selection, this setting improves loadability of the protected line. In conjunction with the quadrilat-
eral characteristic, this setting improves security for faults close to the reach point by adjusting the reactance boundary
into a tent-shape.
• GND DIST Z1 DIR RCA: Selects the characteristic angle (or ‘maximum torque angle’) of the directional supervising
function. If the mho shape is applied, the directional function is an extra supervising function, as the dynamic mho
characteristic itself is a directional one. In conjunction with the quadrilateral shape selection, this setting defines the
only directional function built into the ground distance element. The directional function uses memory voltage for polar-
ization.
• GND DIST Z1 DIR COMP LIMIT: This setting selects the comparator limit angle for the directional supervising function.
• GND DIST Z1 QUAD RGT BLD: This setting defines the right blinder position of the quadrilateral characteristic along
the resistive axis of the impedance plane (see the Quadrilateral distance characteristic figure). The angular position of
the blinder is adjustable with the use of the GND DIST Z1 QUAD RGT BLD RCA setting. This setting applies only to the
quadrilateral characteristic and should be set with consideration to the maximum load current and required resistive
coverage.
• GND DIST Z1 QUAD RGT BLD RCA: This setting defines the angular position of the right blinder of the quadrilateral
characteristic (see the Quadrilateral distance characteristic figure).
• GND DIST Z1 QUAD LFT BLD: This setting defines the left blinder position of the quadrilateral characteristic along the
resistive axis of the impedance plane (see the Quadrilateral distance characteristic figure). The angular position of the
blinder is adjustable with the use of the GND DIST Z1 QUAD LFT BLD RCA setting. This setting applies only to the quadri-
lateral characteristic and should be set with consideration to the maximum load current.
• GND DIST Z1 QUAD LFT BLD RCA: This setting defines the angular position of the left blinder of the quadrilateral
characteristic (see the Quadrilateral distance characteristic figure).
• GND DIST Z1 SUPV: The ground distance elements are supervised by the magnitude of the neutral (3I_0) current.
The current supervision pickup should be set less than the minimum 3I_0 current for the end of the zone fault, taking
into account the desired fault resistance coverage to prevent maloperation due to VT fuse failure. Settings less than
0.2 pu are not recommended and should be applied with caution. To enhance ground distance security against spuri-
ous neutral current during switch-off transients, three-phase faults, and phase-to-phase faults, a positive-sequence
current restraint of 5% is applied to the neutral current supervision magnitude. This setting should be at least three
times the CURRENT CUTOFF LEVEL setting specified in the PRODUCT SETUP DISPLAY PROPERTIES menu
Zone 1 is sealed in with the current supervision.
• GND DIST Z1 VOLT LEVEL: This setting is relevant for applications on series-compensated lines, or in general, if
series capacitors are located between the relaying point and a point for which the zone shall not overreach. For plain
5 (non-compensated) lines, this setting shall be set to zero. Otherwise, the setting is entered in per unit of the VT bank
configured under the DISTANCE SOURCE. Effectively, this setting facilitates dynamic current-based reach reduction. In
non-directional applications (GND DIST Z1 DIR set to “Non-directional”), this setting applies only to the forward reach of
the non-directional zone. See chapters 8 and 9 for additional details and information on calculating this setting value
for applications on series compensated lines.
• GND DIST Z1 DELAY: This setting enables the user to delay operation of the distance elements and implement a
stepped distance backup protection. The distance element timer applies a short drop out delay to cope with faults
located close to the boundary of the zone when small oscillations in the voltages or currents could inadvertently reset
the timer.
• GND DIST Z1 BLK: This setting enables the user to select a FlexLogic operand to block the given distance element.
VT fuse fail detection is one of the applications for this setting.
FLEXLOGIC OPERANDS
GND DIST Z1 OP A
SETTING GND DIST Z1 OP B
GND DIST Z1 DELAY AND GND DIST Z1 OP C
FLEXLOGIC OPERAND TPKP OR
GND DIST Z1 PKP A
0
FLEXLOGIC OPERAND TPKP
GND DIST Z1 PKP B
0 FLEXLOGIC OPERAND
AND
FLEXLOGIC OPERAND TPKP
OR OR GND DIST Z1 OP
GND DIST Z1 PKP C
0
FLEXLOGIC OPERANDS
GND DIST Z1 SUPN IN AND
AND
OPEN POLE OP ** OR
** D60, L60, and L90 only. Other UR-series models apply regular current seal-in for zone 1. 837018A7.CDR
IURPWKHRSHQSROHGHWHFWRUHOHPHQW'/DQG/RQO\
)/(;/2*,&23(5$1'
23(132/(23
)/(;/2*,&23(5$1'
7,0(5 )/(;/2*,&23(5$1'
*1'',67=3.3& 6(77,1*
PV $1' $1' *1'',67=23&
*1'',67='(/$<
25
25
73.3
IURPWKHWULSRXWSXWHOHPHQW PV
)/(;/2*,&23(5$1'
)/(;/2*,&23(5$1'
75,3=*5705,1,7
25 *1'',67=23
$&'5
)/(;/2*,&23(5$1'
23(132/(23
5
7,0(5 6(77,1*
)/(;/2*,&23(5$1' PV *1'',67='(/$<
$1' )/(;/2*,&23(5$1'
*1'',67=3.3$ 73.3
PV 25 *1'',67=23$
7,0(5 6(77,1*
)/(;/2*,&23(5$1' PV *1'',67='(/$<
$1' )/(;/2*,&23(5$1'
*1'',67=3.3% 73.3
PV 25 *1'',67=23%
7,0(5 6(77,1*
)/(;/2*,&23(5$1' PV *1'',67='(/$<
$1' )/(;/2*,&23(5$1'
*1'',67=3.3& 73.3
PV 25 *1'',67=23&
)/(;/2*,&23(5$1'
25 *1'',67=23
'/DQG/RQO\ $$&'5
SETTINGS
GND DIST Z1 DIR
GND DIST Z1 SHAPE
GND DIST Z1 Z0/Z1 MAG
GND DIST Z1 Z0/Z1 ANG
GND DIST Z1 ZOM/Z1 MAG
GND DIST Z1 ZOM/Z1 ANG
GND DIST Z1 REACH
GND DIST Z1 RCA
GND DIST Z1 REV REACH
SETTING
GND DIST Z1 FUNCTION GND DIST Z1 REV REACH RCA
Enabled = 1 GND DIST Z1 POL CURRENT
GND DIST Z1 NON-HOMGEN ANG
GND DIST Z1 COMP LIMIT
AND GND DIST Z1 DIR RCA
SETTING
GND DIST Z1 DIR COMP LIMIT
GND DIST Z1 BLK
GND DIST Z1 VOLT LEVEL
Off = 0
GND DIST Z1 QUAD RGT BLD
Quadrilateral
GND DIST Z1 QUAD RGT BLD RCA characteristic
GND DIST Z1 QUAD LFT BLD only
SETTING GND DIST Z1 QUAD LFT BLD RCA
DISTANCE SOURCE RUN
IA
IB FLEXLOGIC OPERANDS
A ELEMENT
IC AND GND DIST Z1 PKP A
VAG GND DIST Z1 DPO A
RUN
Wye
VTs
VBG
VCG FLEXLOGIC OPERANDS
B ELEMENT
I_2 AND GND DIST Z1 PKP B
I_0 GND DIST Z1 DPO B
V_1 RUN
5 I_1
IN
MEMORY
C ELEMENT
AND
FLEXLOGIC OPERANDS
GND DIST Z1 PKP C
GND DIST Z1 DPO C
SETTING
GND DIST Z1 SUPV
RUN FLEXLOGIC OPERAND
| IN – 0.05 × I_1 | > Pickup GND DIST Z1 SUPN IN
837007AH.CDR
SETTINGS
GND DIST Z2 DIR
GND DIST Z2 SHAPE
GND DIST Z2 Z0/Z2 MAG
GND DIST Z2 Z0/Z2 ANG
GND DIST Z2 ZOM/Z1 MAG
GND DIST Z2 ZOM/Z1 ANG
GND DIST Z2 REACH
GND DIST Z2 RCA
GND DIST Z2 REV REACH
SETTING
GND DIST Z2 FUNCTION GND DIST Z2 REV REACH RCA
Enabled = 1 GND DIST Z2 POL CURRENT
GND DIST Z2 NON-HOMGEN ANG
GND DIST Z2 COMP LIMIT
AND GND DIST Z2 DIR RCA
SETTING
GND DIST Z2 DIR COMP LIMIT
GND DIST Z2 BLK
GND DIST Z2 VOLT LEVEL
Off = 0
GND DIST Z2 QUAD RGT BLD
Quadrilateral
GND DIST Z2 QUAD RGT BLD RCA characteristic
GND DIST Z2 QUAD LFT BLD only
SETTING GND DIST Z2 QUAD LFT BLD RCA
DISTANCE SOURCE RUN
IA
IB A ELEMENT FLEXLOGIC OPERANDS
IC AND GND DIST Z2 PKP A
VAG GND DIST Z2 DPO A
RUN
Wye
VTs
VBG
VCG
B ELEMENT FLEXLOGIC OPERANDS
I_2
AND GND DIST Z2 PKP B
I_0
GND DIST Z2 DPO B
V_1 RUN
I_1
IN C ELEMENT
AND
FLEXLOGIC OPERANDS
GND DIST Z2 PKP C
5
MEMORY
GND DIST Z2 DPO C
TIMER
V_1 > 0.80 pu 1 cycle FLEXLOGIC OPERAND
OR GND DIST Z2 PKP
OR
1 cycle
I_1 > 0.025 pu
SETTING
GND DIST Z2 SUPV
RUN FLEXLOGIC OPERAND
| IN – 0.05 × I_1 | > Pickup GND DIST Z2 SUPN IN
GND DIST Z2 DIR SUPN
OR
OPEN POLE OP **
** D60, L60, and L90 only 837011AL.CDR
SETTING
Distance Source RUN
= V_0 OR
Zero-sequence
FLEXLOGIC OPERAND
= I_0 directional characteristic
TIMER AND GND DIST Z2 DIR SUPN
tpickup
FLEXLOGIC OPERAND
OPEN POLE OP treset
Co-ordinating time:
pickup = 1.0 cycle, reset = 1.0 cycle 837009A7.CDR
PATH: SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) POWER SWING DETECT
The power swing detect element provides both power swing blocking and out-of-step tripping functions. The element mea-
sures the positive-sequence apparent impedance and traces its locus with respect to either two or three user-selectable
operating characteristic boundaries. Upon detecting appropriate timing relations, the blocking and tripping indications are
given through FlexLogic operands. The element incorporates an adaptive disturbance detector. This function does not trig-
ger on power swings, but is capable of detecting faster disturbances – faults in particular – that may occur during power
swings. Operation of this dedicated disturbance detector is signaled via the POWER SWING 50DD operand.
The power swing detect element asserts two outputs intended for blocking selected protection elements on power swings:
POWER SWING BLOCK is a traditional signal that is safely asserted for the entire duration of the power swing, and POWER
SWING UN/BLOCK is established in the same way, but resets when an extra disturbance is detected during the power swing.
The POWER SWING UN/BLOCK operand may be used for blocking selected protection elements if the intent is to respond to
faults during power swing conditions.
Different protection elements respond differently to power swings. If tripping is required for faults during power swing condi-
tions, some elements may be blocked permanently (using the POWER SWING BLOCK operand), and others may be blocked
and dynamically unblocked upon fault detection (using the POWER SWING UN/BLOCK operand).
The operating characteristic and logic figures should be viewed along with the following discussion to develop an under-
standing of the operation of the element.
The power swing detect element operates in three-step or two-step mode:
• Three-step operation: The power swing blocking sequence essentially times the passage of the locus of the positive-
sequence impedance between the outer and the middle characteristic boundaries. If the locus enters the outer charac-
teristic (indicated by the POWER SWING OUTER FlexLogic operand) but stays outside the middle characteristic (indi-
cated by the POWER SWING MIDDLE FlexLogic operand) for an interval longer than POWER SWING PICKUP DELAY 1, the
power swing blocking signal (POWER SWING BLOCK FlexLogic operand) is established and sealed-in. The blocking sig-
nal resets when the locus leaves the outer characteristic, but not sooner than the POWER SWING RESET DELAY 1 time.
• Two-step operation: If the two-step mode is selected, the sequence is identical, but it is the outer and inner character-
istics that are used to time the power swing locus.
The out-of-step tripping feature operates as follows for three-step and two-step power swing detection modes:
• Three-step operation: The out-of-step trip sequence identifies unstable power swings by determining if the imped-
ance locus spends a finite time between the outer and middle characteristics and then a finite time between the middle
and inner characteristics. The first step is similar to the power swing blocking sequence. After timer POWER SWING
PICKUP DELAY 1 times out, latch 1 is set as long as the impedance stays within the outer characteristic.
If afterwards, at any time (given the impedance stays within the outer characteristic), the locus enters the middle char-
acteristic but stays outside the inner characteristic for a period of time defined as POWER SWING PICKUP DELAY 2, latch
2 is set as long as the impedance stays inside the outer characteristic. If afterwards, at any time (given the impedance
stays within the outer characteristic), the locus enters the inner characteristic and stays there for a period of time
defined as POWER SWING PICKUP DELAY 3, latch 2 is set as long as the impedance stays inside the outer characteristic;
the element is now ready to trip.
5 If the "Early" trip mode is selected, the POWER SWING TRIP operand is set immediately and sealed-in for the interval
set by the POWER SWING SEAL-IN DELAY. If the "Delayed" trip mode is selected, the element waits until the impedance
locus leaves the inner characteristic, then times out the POWER SWING PICKUP DELAY 2 and sets Latch 4; the element is
now ready to trip. The trip operand is set later, when the impedance locus leaves the outer characteristic.
• Two-step operation: The two-step mode of operation is similar to the three-step mode with two exceptions. First, the
initial stage monitors the time spent by the impedance locus between the outer and inner characteristics. Second, the
stage involving the POWER SWING PICKUP DELAY 2 timer is bypassed. It is up to the user to integrate the blocking
(POWER SWING BLOCK) and tripping (POWER SWING TRIP) FlexLogic operands with other protection functions and out-
put contacts in order to make this element fully operational.
The element can be set to use either lens (mho) or rectangular (quadrilateral) characteristics as illustrated below. When set
to “Mho”, the element applies the right and left blinders as well. If the blinders are not required, their settings should be set
high enough to effectively disable the blinders.
R
TE
OU
ACH
E
DL
FWD RE
ID
M
R
NE
IN
FW
E
GL
DR
AN
CA
LE IT
IM
ANG L EL
R
RE
IT DD
LIM MI
V RC
R
NE
A
IN
H
REV REAC
OUTER LIMIT ANGLE
827843A2.CDR
842734A1.CDR
INNER LFT BL
D INNER RGT BL
D
MIDDLE LFT BL
ACH OUT
ACH MID
D MIDDLE RGT
BLD
OUTER LFT BL
D OUTER RGT BL
D
QUAD FWD RE
QUAD FWD RE
FWD REACH
FWD RCA
CH MID
REV REACH
ACH OUT
QUAD REV REA
QUAD REV RE
5 842735A1.CDR
• POWER SWING MODE: This setting selects between the two-step and three-step operating modes and applies to
both power swing blocking and out-of-step tripping functions. The three-step mode applies if there is enough space
between the maximum load impedances and distance characteristics of the relay that all three (outer, middle, and
inner) characteristics can be placed between the load and the distance characteristics. Whether the spans between
the outer and middle as well as the middle and inner characteristics are sufficient should be determined by analysis of
the fastest power swings expected in correlation with settings of the power swing timers.
The two-step mode uses only the outer and inner characteristics for both blocking and tripping functions. This leaves
more space in heavily loaded systems to place two power swing characteristics between the distance characteristics
and the maximum load, but allows for only one determination of the impedance trajectory.
• POWER SWING SUPV: A common overcurrent pickup level supervises all three power swing characteristics. The
supervision responds to the positive sequence current.
• POWER SWING FWD REACH: This setting specifies the forward reach of all three mho characteristics and the inner
quadrilateral characteristic. For a simple system consisting of a line and two equivalent sources, this reach should be
higher than the sum of the line and remote source positive-sequence impedances. Detailed transient stability studies
may be needed for complex systems in order to determine this setting. The angle of this reach impedance is specified
by the POWER SWING FWD RCA setting.
• POWER SWING QUAD FWD REACH MID: This setting specifies the forward reach of the middle quadrilateral charac-
teristic. The angle of this reach impedance is specified by the POWER SWING FWD RCA setting. The setting is not used if
the shape setting is “Mho”.
• POWER SWING QUAD FWD REACH OUT: This setting specifies the forward reach of the outer quadrilateral charac-
teristic. The angle of this reach impedance is specified by the POWER SWING FWD RCA setting. The setting is not used if
the shape setting is “Mho”.
• POWER SWING FWD RCA: This setting specifies the angle of the forward reach impedance for the mho characteris-
tics, angles of all the blinders, and both forward and reverse reach impedances of the quadrilateral characteristics. 5
• POWER SWING REV REACH: This setting specifies the reverse reach of all three mho characteristics and the inner
quadrilateral characteristic. For a simple system of a line and two equivalent sources, this reach should be higher than
the positive-sequence impedance of the local source. Detailed transient stability studies may be needed for complex
systems to determine this setting. The angle of this reach impedance is specified by the POWER SWING REV RCA setting
for “Mho”, and the POWER SWING FWD RCA setting for “Quad”.
• POWER SWING QUAD REV REACH MID: This setting specifies the reverse reach of the middle quadrilateral charac-
teristic. The angle of this reach impedance is specified by the POWER SWING FWD RCA setting. The setting is not used if
the shape setting is “Mho”.
• POWER SWING QUAD REV REACH OUT: This setting specifies the reverse reach of the outer quadrilateral charac-
teristic. The angle of this reach impedance is specified by the POWER SWING FWD RCA setting. The setting is not used if
the shape setting is “Mho”.
• POWER SWING REV RCA: This setting specifies the angle of the reverse reach impedance for the mho characteris-
tics. This setting applies to mho shapes only.
• POWER SWING OUTER LIMIT ANGLE: This setting defines the outer power swing characteristic. The convention
depicted in the Power swing detect characteristic diagram should be observed: values greater than 90° result in an
apple-shaped characteristic; values less than 90° result in a lens shaped characteristic. This angle must be selected in
consideration of the maximum expected load. If the maximum load angle is known, the outer limit angle should be
coordinated with a 20° security margin. Detailed studies may be needed for complex systems to determine this setting.
This setting applies to mho shapes only.
• POWER SWING MIDDLE LIMIT ANGLE: This setting defines the middle power swing detect characteristic. It is rele-
vant only for the 3-step mode. A typical value would be close to the average of the outer and inner limit angles. This
setting applies to mho shapes only.
• POWER SWING INNER LIMIT ANGLE: This setting defines the inner power swing detect characteristic. The inner
characteristic is used by the out-of-step tripping function: beyond the inner characteristic out-of-step trip action is defi-
nite (the actual trip may be delayed as per the TRIP MODE setting). Therefore, this angle must be selected in consider-
ation to the power swing angle beyond which the system becomes unstable and cannot recover.
The inner characteristic is also used by the power swing blocking function in the two-step mode. In this case, set this
angle large enough so that the characteristics of the distance elements are safely enclosed by the inner characteristic.
This setting applies to mho shapes only.
• POWER SWING OUTER, MIDDLE, and INNER RGT BLD: These settings specify the resistive reach of the right
blinder. The blinder applies to both “Mho” and “Quad” characteristics. Set these value high if no blinder is required for
the “Mho” characteristic.
• POWER SWING OUTER, MIDDLE, and INNER LFT BLD: These settings specify the resistive reach of the left blinder.
Enter a positive value; the relay automatically uses a negative value. The blinder applies to both “Mho” and “Quad”
characteristics. Set this value high if no blinder is required for the “Mho” characteristic.
• POWER SWING PICKUP DELAY 1: All the coordinating timers are related to each other and should be set to detect
the fastest expected power swing and produce out-of-step tripping in a secure manner. The timers should be set in
consideration to the power swing detect characteristics, mode of power swing detect operation and mode of out-of-
step tripping. This timer defines the interval that the impedance locus must spend between the outer and inner charac-
teristics (two-step operating mode), or between the outer and middle characteristics (three-step operating mode)
before the power swing blocking signal is established. This time delay must be set shorter than the time required for
the impedance locus to travel between the two selected characteristics during the fastest expected power swing. This
setting is relevant for both power swing blocking and out-of-step tripping.
• POWER SWING RESET DELAY 1: This setting defines the dropout delay for the power swing blocking signal. Detec-
tion of a condition requiring a block output sets latch 1 after PICKUP DELAY 1 time. When the impedance locus leaves
the outer characteristic, timer POWER SWING RESET DELAY 1 is started. When the timer times-out the latch is reset. This
setting should be selected to give extra security for the power swing blocking action.
• POWER SWING PICKUP DELAY 2: Controls the out-of-step tripping function in the three-step mode only. This timer
defines the interval the impedance locus must spend between the middle and inner characteristics before the second
5 step of the out-of-step tripping sequence is completed. This time delay must be set shorter than the time required for
the impedance locus to travel between the two characteristics during the fastest expected power swing.
• POWER SWING PICKUP DELAY 3: Controls the out-of-step tripping function only. It defines the interval the imped-
ance locus must spend within the inner characteristic before the last step of the out-of-step tripping sequence is com-
pleted and the element is armed to trip. The actual moment of tripping is controlled by the TRIP MODE setting. This time
delay is provided for extra security before the out-of-step trip action is executed.
• POWER SWING PICKUP DELAY 4: Controls the out-of-step tripping function in “Delayed” trip mode only. This timer
defines the interval the impedance locus must spend outside the inner characteristic but within the outer characteristic
before the element is armed for the delayed trip. The delayed trip occurs when the impedance leaves the outer charac-
teristic. This time delay is provided for extra security and should be set considering the fastest expected power swing.
• POWER SWING SEAL-IN DELAY: The out-of-step trip FlexLogic operand (POWER SWING TRIP) is sealed-in for the
specified period of time. The sealing-in is crucial in the delayed trip mode, as the original trip signal is a very short
pulse occurring when the impedance locus leaves the outer characteristic after the out-of-step sequence is completed.
• POWER SWING TRIP MODE: Selection of the “Early” trip mode results in an instantaneous trip after the last step in
the out-of-step tripping sequence is completed. The early trip mode will stress the circuit breakers as the currents at
that moment are high (the electromotive forces of the two equivalent systems are approximately 180° apart). Selection
of the “Delayed” trip mode results in a trip at the moment when the impedance locus leaves the outer characteristic.
delayed trip mode will relax the operating conditions for the breakers as the currents at that moment are low. The
selection should be made considering the capability of the breakers in the system.
• POWER SWING BLK: This setting specifies the FlexLogic operand used for blocking the out-of-step function only. The
power swing blocking function is operational all the time as long as the element is enabled. The blocking signal resets
the output POWER SWING TRIP operand but does not stop the out-of-step tripping sequence.
SETTINGS
POWER SWING POWER SWING OUTER
SHAPE: LIMIT ANGLE:
POWER SWING FWD POWER SWING MIDDLE
REACH: LIMIT ANGLE:
POWER SWING QUAD POWER SWING INNER
FWD REACH MID: LIMIT ANGLE:
POWER SWING QUAD POWER SWING OUTER
FWD REACH OUT: RGT BLD:
POWER SWING FWD POWER SWING OUTER
RCA: LFT BLD:
POWER SWING REV POWER SWING MIDDLE
SETTING REACH: RGT BLD:
POWER SWING POWER SWING QUAD REV POWER SWING MIDDLE
FUNCTION: REACH MID: LFT BLD:
Enabled = 1 POWER SWING QUAD REV POWER SWING INNER
REACH OUT: RGT BLD:
SETTING POWER SWING REV POWER SWING INNER
RCA: LFT BLD:
POWER SWING SOURCE:
RUN
FLEXLOGIC OPERAND
V_1 OUTER IMPEDANCE
AND POWER SWING OUTER
I_1 REGION
RUN
FLEXLOGIC OPERAND
MIDDLE IMPEDANCE
AND POWER SWING MIDDLE
REGION
RUN
FLEXLOGIC OPERAND
INNER IMPEDANCE
AND POWER SWING INNER
REGION
SETTING
POWER SWING
SUPV:
5
RUN
SETTING
POWER SWING FUNCTION:
TIMER
Enabled = 1
0
SETTING 10 cycles
SETTING SETTINGS
POWER SWING
POWER SWING MODE:
DELAY 1 PICKUP:
POWER SWING
3-step
AND DELAY 1 RESET:
FLEXLOGIC OPERANDS
tPKP
S Q1 POWER SWING BLOCK
tRST
POWER SWING UN/BLOCK
AND L1 S Q5
2-step FLEXLOGIC OPERAND
L5
R POWER SWING 50DD
R
OR
OR
SETTING
POWER SWING FLEXLOGIC OPERAND
DELAY 2 PICKUP:
POWER SWING TMR2 PKP
tPKP
AND S Q2
0
L2
R
3-step
2-step
FLEXLOGIC OPERAND
SETTING POWER SWING TMR3 PKP
POWER SWING
DELAY 3 PICKUP: FLEXLOGIC OPERAND
5
tPKP POWER SWING INCOMING
AND S Q3
0
L3 SETTING
R
POWER SWING TRIP
MODE:
SETTING SETTING
POWER SWING POWER SWING
DELAY 4 PICKUP: Early
SEAL-IN DELAY:
tPKP 0
AND S Q4 FLEXLOGIC OPERAND
0 tRST
L4 AND POWER SWING TRIP
R AND
Delayed
FLEXLOGIC OPERAND
POWER SWING OUTGOING
827841A4.CDR
The load encroachment element responds to the positive-sequence voltage and current and applies a characteristic shown
in the figure below.
X
ANGLE
–REACH REACH
R
ANGLE
LOAD ENCROACHMENT
LOAD ENCROACHMENT
OPERATE
OPERATE
827846A1.CDR
837731A1.CDR
5 • LOAD ENCROACHMENT REACH: This setting specifies the resistive reach of the element as shown in the Load
encroachment characteristic diagram. This setting should be entered in secondary ohms and be calculated as the pos-
itive-sequence resistance seen by the relay under maximum load conditions and unity power factor.
• LOAD ENCROACHMENT ANGLE: This setting specifies the size of the blocking region as shown on the Load
encroachment characteristic diagram and applies to the positive-sequence impedance.
SETTING
LOAD ENCROACHMENT
FUNCTION:
Enabled=1 SETTINGS
LOAD ENCROACHMENT
SETTING REACH:
SETTINGS
LOAD ENCROACHMENT
LOAD ENCRMNT BLK:
ANGLE: LOAD ENCROACHMENT
Off=0 RUN PKP DELAY:
AND FLEXLOGIC OPERANDS
LOAD ENCROACHMENT
LOAD ENCHR PKP
RST DELAY:
SETTING SETTING LOAD ENCHR DPO
Load Encroachment t PKP
LOAD ENCROACHMENT LOAD ENCROACHMENT t RST LOAD ENCHR OP
SOURCE: MIN VOLT: Characteristic
Pos Seq Voltage (V_1) V_1 > Pickup
Pos Seq Current (I_1)
827847A3.CDR
a) MAIN MENU
PATH: SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) PHASE CURRENT
A time dial multiplier setting allows selection of a multiple of the base curve shape (where the time dial multiplier = 1) with
the curve shape (CURVE) setting. Unlike the electromechanical time dial equivalent, operate times are directly proportional
to the time multiplier (TD MULTIPLIER) setting value. For example, all times for a multiplier of 10 are 10 times the multiplier 1
or base curve values. Setting the multiplier to zero results in an instantaneous response to all current levels above pickup.
Time overcurrent time calculations are made with an internal energy capacity memory variable. When this variable indi-
cates that the energy capacity has reached 100%, a time overcurrent element will operate. If less than 100% energy capac-
ity is accumulated in this variable and the current falls below the dropout threshold of 97 to 98% of the pickup value, the
variable must be reduced. Two methods of this resetting operation are available: “Instantaneous” and “Timed”. The “Instan-
taneous” selection is intended for applications with other relays, such as most static relays, which set the energy capacity
directly to zero when the current falls below the reset threshold. The “Timed” selection can be used where the relay must
coordinate with electromechanical relays.
IEEE CURVES:
The IEEE time overcurrent curve shapes conform to industry standards and the IEEE C37.112-1996 curve classifications
for extremely, very, and moderately inverse. The IEEE curves are derived from the formulae:
A tr
---------------------------------- + B -----------------------------------
-
I p
T = TDM ---------------- – 1 , T RESET = TDM I 2
--------------- (EQ 5.7)
I pickup 1 – -
I pickup
where: T = operate time (in seconds), TDM = Multiplier setting, I = input current, Ipickup = Pickup Current setting
A, B, p = constants, TRESET = reset time in seconds (assuming energy capacity is 100% and RESET is “Timed”),
tr = characteristic constant
5 0.5
1.0
8.090
16.179
3.514
7.028
1.471
2.942
0.899
1.798
0.654
1.308
0.526
1.051
0.450
0.900
0.401
0.802
0.368
0.736
0.345
0.689
2.0 32.358 14.055 5.885 3.597 2.616 2.103 1.799 1.605 1.472 1.378
4.0 64.716 28.111 11.769 7.193 5.232 4.205 3.598 3.209 2.945 2.756
6.0 97.074 42.166 17.654 10.790 7.849 6.308 5.397 4.814 4.417 4.134
8.0 129.432 56.221 23.538 14.387 10.465 8.410 7.196 6.418 5.889 5.513
10.0 161.790 70.277 29.423 17.983 13.081 10.513 8.995 8.023 7.361 6.891
IEEE MODERATELY INVERSE
0.5 3.220 1.902 1.216 0.973 0.844 0.763 0.706 0.663 0.630 0.603
1.0 6.439 3.803 2.432 1.946 1.688 1.526 1.412 1.327 1.260 1.207
2.0 12.878 7.606 4.864 3.892 3.377 3.051 2.823 2.653 2.521 2.414
4.0 25.756 15.213 9.729 7.783 6.753 6.102 5.647 5.307 5.041 4.827
6.0 38.634 22.819 14.593 11.675 10.130 9.153 8.470 7.960 7.562 7.241
8.0 51.512 30.426 19.458 15.567 13.507 12.204 11.294 10.614 10.083 9.654
10.0 64.390 38.032 24.322 19.458 16.883 15.255 14.117 13.267 12.604 12.068
IEC CURVES
For European applications, the relay offers three standard curves defined in IEC 255-4 and British standard BS142. These
are defined as IEC Curve A, IEC Curve B, and IEC Curve C. The formulae for these curves are:
K tr
--------------------------------------- --------------------------------------
-
T = TDM I I pickup E – 1 , T RESET = TDM 1 – I I 2 (EQ 5.8)
pickup
where: T = operate time (in seconds), TDM = Multiplier setting, I = input current, Ipickup = Pickup Current setting, K, E =
constants, tr = characteristic constant, and TRESET = reset time in seconds (assuming energy capacity is 100%
and RESET is “Timed”)
IAC CURVES:
The curves for the General Electric type IAC relay family are derived from the formulae:
B D E tr
T = TDM A + ------------------------------ + -------------------------------------2- + -------------------------------------3- , T RESET = TDM -------------------------------
- (EQ 5.9)
I I pkp – C I I – C I I – C 2
pkp pkp 1 – I I pkp
where: T = operate time (in seconds), TDM = Multiplier setting, I = Input current, Ipkp = Pickup Current setting, A to E =
constants, tr = characteristic constant, and TRESET = reset time in seconds (assuming energy capacity is 100%
and RESET is “Timed”)
5 1.0
2.0
3.398
6.796
1.498
2.997
0.606
1.212
0.356
0.711
0.246
0.491
0.186
0.372
0.149
0.298
0.124
0.248
0.106
0.212
0.093
0.185
4.0 13.591 5.993 2.423 1.422 0.983 0.744 0.595 0.495 0.424 0.370
6.0 20.387 8.990 3.635 2.133 1.474 1.115 0.893 0.743 0.636 0.556
8.0 27.183 11.987 4.846 2.844 1.966 1.487 1.191 0.991 0.848 0.741
10.0 33.979 14.983 6.058 3.555 2.457 1.859 1.488 1.239 1.060 0.926
IAC VERY INVERSE
0.5 1.451 0.656 0.269 0.172 0.133 0.113 0.101 0.093 0.087 0.083
1.0 2.901 1.312 0.537 0.343 0.266 0.227 0.202 0.186 0.174 0.165
2.0 5.802 2.624 1.075 0.687 0.533 0.453 0.405 0.372 0.349 0.331
4.0 11.605 5.248 2.150 1.374 1.065 0.906 0.810 0.745 0.698 0.662
6.0 17.407 7.872 3.225 2.061 1.598 1.359 1.215 1.117 1.046 0.992
8.0 23.209 10.497 4.299 2.747 2.131 1.813 1.620 1.490 1.395 1.323
10.0 29.012 13.121 5.374 3.434 2.663 2.266 2.025 1.862 1.744 1.654
IAC INVERSE
0.5 0.578 0.375 0.266 0.221 0.196 0.180 0.168 0.160 0.154 0.148
1.0 1.155 0.749 0.532 0.443 0.392 0.360 0.337 0.320 0.307 0.297
2.0 2.310 1.499 1.064 0.885 0.784 0.719 0.674 0.640 0.614 0.594
4.0 4.621 2.997 2.128 1.770 1.569 1.439 1.348 1.280 1.229 1.188
6.0 6.931 4.496 3.192 2.656 2.353 2.158 2.022 1.921 1.843 1.781
8.0 9.242 5.995 4.256 3.541 3.138 2.878 2.695 2.561 2.457 2.375
10.0 11.552 7.494 5.320 4.426 3.922 3.597 3.369 3.201 3.072 2.969
IAC SHORT INVERSE
0.5 0.072 0.047 0.035 0.031 0.028 0.027 0.026 0.026 0.025 0.025
1.0 0.143 0.095 0.070 0.061 0.057 0.054 0.052 0.051 0.050 0.049
2.0 0.286 0.190 0.140 0.123 0.114 0.108 0.105 0.102 0.100 0.099
4.0 0.573 0.379 0.279 0.245 0.228 0.217 0.210 0.204 0.200 0.197
6.0 0.859 0.569 0.419 0.368 0.341 0.325 0.314 0.307 0.301 0.296
8.0 1.145 0.759 0.559 0.490 0.455 0.434 0.419 0.409 0.401 0.394
10.0 1.431 0.948 0.699 0.613 0.569 0.542 0.524 0.511 0.501 0.493
I2t CURVES:
The curves for the I2t are derived from the formulae:
100 100
-------------------------- ----------------------------
T = TDM ---------------
I 2 , T RESET = TDM I – 2
- ---------------- (EQ 5.10)
I pickup I pickup
where: T = Operate Time (sec.); TDM = Multiplier Setting; I = Input Current; Ipickup = Pickup Current Setting;
TRESET = Reset Time in sec. (assuming energy capacity is 100% and RESET: Timed)
FLEXCURVES:
The custom FlexCurves are described in detail in the FlexCurves section of this chapter. The curve shapes for the Flex-
Curves are derived from the formulae:
I
T = TDM FlexCurve Time at ----------------
I
when ---------------- 1.00 (EQ 5.11)
5
I pickup I pickup
I I
T RESET = TDM FlexCurve Time at ---------------- when ---------------- 0.98 (EQ 5.12)
I pickup I pickup
The phase time overcurrent element can provide a desired time-delay operating characteristic versus the applied current or
be used as a simple definite time element. The phase current input quantities may be programmed as fundamental phasor
magnitude or total waveform RMS magnitude as required by the application.
Two methods of resetting operation are available: “Timed” and “Instantaneous” (refer to the Inverse Time overcurrent
curves characteristic sub-section earlier for details on curve setup, trip times, and reset operation). When the element is
blocked, the time accumulator will reset according to the reset characteristic. For example, if the element reset characteris-
tic is set to “Instantaneous” and the element is blocked, the time accumulator will be cleared immediately.
The PHASE TOC1 PICKUP setting can be dynamically reduced by a voltage restraint feature (when enabled). This is accom-
plished via the multipliers (Mvr) corresponding to the phase-phase voltages of the voltage restraint characteristic curve (see
the figure below); the pickup level is calculated as ‘Mvr’ times the PHASE TOC1 PICKUP setting. If the voltage restraint feature
is disabled, the pickup level always remains at the setting value.
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Phase-Phase Voltage ÷ VT Nominal Phase-phase Voltage
818784A4.CDR
SETTING
PHASE TOC1
FUNCTION:
Enabled=1
SETTING
PHASE TOC1
BLOCK-A :
Off=0
SETTING
PHASE TOC1
BLOCK-B: 5
Off=0
SETTING
SETTING
PHASE TOC1
PHASE TOC1 INPUT:
BLOCK-C:
PHASE TOC1
Off=0 PICKUP:
PHASE TOC1
SETTING CURVE:
PHASE TOC1 PHASE TOC1
SOURCE: TD MULTIPLIER:
IA
PHASE TOC1
IB RESET: FLEXLOGIC OPERAND
IC AND RUN PHASE TOC1 A PKP
IA PICKUP
Seq=ABC Seq=ACB PHASE TOC1 A DPO
MULTIPLY INPUTS
RUN
t PHASE TOC1 A OP
VAB VAC Set
Calculate Multiplier Set Pickup AND RUN PHASE TOC1 B PKP
RUN
Multiplier-Phase A IB PICKUP
Set PHASE TOC1 B DPO
VBC VBA Set Pickup
Calculate Multiplier t PHASE TOC1 B OP
RUN
Multiplier-Phase B
Set AND RUN PHASE TOC1 C PKP
VCA VCB IC PICKUP
Calculate Multiplier Set Pickup PHASE TOC1 C DPO
Multiplier-Phase C
t PHASE TOC1 C OP
SETTING OR PHASE TOC1 PKP
PHASE TOC1 VOLT
RESTRAINT: OR PHASE TOC1 OP
Enabled
827072A5.CDR
The phase instantaneous overcurrent element may be used as an instantaneous element with no intentional delay or as a
definite time element. The input current is the fundamental phasor magnitude. For timing curves, see the publication Instan-
taneous Overcurrent Element Response to Saturated Waveforms in UR-Series Relays (GET-8400A).
The phase directional elements (one for each of phases A, B, and C) determine the phase current flow direction for steady
state and fault conditions and can be used to control the operation of the phase overcurrent elements via the BLOCK inputs
of these elements. 5
S
UT 0
TP
OU
–90°
VPol
VAG(Faulted) IA
ECA
set at 30°
VBC
VBC
VCG VBG +90°
To increase security for three phase faults very close to the VTs used to measure the polarizing voltage, a voltage memory
feature is incorporated. This feature stores the polarizing voltage the moment before the voltage collapses, and uses it to
determine direction. The voltage memory remains valid for one second after the voltage has collapsed.
The main component of the phase directional element is the phase angle comparator with two inputs: the operating signal
(phase current) and the polarizing signal (the line voltage, shifted in the leading direction by the characteristic angle, ECA).
The following table shows the operating and polarizing signals used for phase directional control:
PHASE OPERATING POLARIZING SIGNAL Vpol
SIGNAL
ABC PHASE SEQUENCE ACB PHASE SEQUENCE
A angle of IA angle of VBC (1ECA) angle of VCB (1ECA)
B angle of IB angle of VCA (1ECA) angle of VAC 1ECA)
C angle of IC angle of VAB (1ECA) angle of VBA (1ECA)
MODE OF OPERATION:
• When the function is “Disabled”, or the operating current is below 5% CT nominal, the element output is “0”.
• When the function is “Enabled”, the operating current is above 5% CT nominal, and the polarizing voltage is above
the PRODUCT SETUP DISPLAY PROPERTIES VOLTAGE CUT-OFF LEVEL value, the element output is dependent on
the phase angle between the operating and polarizing signals:
– The element output is logic “0” when the operating current is within polarizing voltage ±90°.
– For all other angles, the element output is logic “1”.
• Once the voltage memory has expired, the phase overcurrent elements under directional control can be set to block or
trip on overcurrent as follows:
5 – When BLOCK WHEN V MEM EXP is set to “Yes”, the directional element will block the operation of any phase
overcurrent element under directional control when voltage memory expires.
– When BLOCK WHEN V MEM EXP is set to “No”, the directional element allows tripping of phase overcurrent elements
under directional control when voltage memory expires.
In all cases, directional blocking will be permitted to resume when the polarizing voltage becomes greater than the ‘polariz-
ing voltage threshold’.
SETTINGS:
• PHASE DIR 1 SIGNAL SOURCE: This setting is used to select the source for the operating and polarizing signals.
The operating current for the phase directional element is the phase current for the selected current source. The polar-
izing voltage is the line voltage from the phase VTs, based on the 90° or ‘quadrature’ connection and shifted in the
leading direction by the element characteristic angle (ECA).
• PHASE DIR 1 ECA: This setting is used to select the element characteristic angle, i.e. the angle by which the polariz-
ing voltage is shifted in the leading direction to achieve dependable operation. In the design of the UR-series elements,
a block is applied to an element by asserting logic 1 at the blocking input. This element should be programmed via the
ECA setting so that the output is logic 1 for current in the non-tripping direction.
• PHASE DIR 1 POL V THRESHOLD: This setting is used to establish the minimum level of voltage for which the phase
angle measurement is reliable. The setting is based on VT accuracy. The default value is “0.700 pu”.
• PHASE DIR 1 BLOCK WHEN V MEM EXP: This setting is used to select the required operation upon expiration of
voltage memory. When set to "Yes", the directional element blocks the operation of any phase overcurrent element
under directional control, when voltage memory expires; when set to "No", the directional element allows tripping of
phase overcurrent elements under directional control.
The phase directional element responds to the forward load current. In the case of a following reverse fault, the ele-
ment needs some time – in the order of 8 ms – to establish a blocking signal. Some protection elements such as
NOTE
instantaneous overcurrent may respond to reverse faults before the blocking signal is established. Therefore, a
coordination time of at least 10 ms must be added to all the instantaneous protection elements under the supervi-
sion of the phase directional element. If current reversal is of a concern, a longer delay – in the order of 20 ms –
may be needed.
SETTING
PHASE DIR 1
FUNCTION:
Enabled=1
SETTING
AND
PHASE DIR 1
BLOCK:
Off=0
SETTING
FLEXLOGIC OPERAND
PHASE B LOGIC SIMILAR TO PHASE A
5
PH DIR1 BLK B
FLEXLOGIC OPERAND
PHASE C LOGIC SIMILAR TO PHASE A PH DIR1 BLK C
827078A7.CDR
a) MAIN MENU
PATH: SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) NEUTRAL CURRENT
The neutral time overcurrent element can provide a desired time-delay operating characteristic versus the applied current
or be used as a simple definite time element. The neutral current input value is a quantity calculated as 3Io from the phase
currents and may be programmed as fundamental phasor magnitude or total waveform RMS magnitude as required by the
application.
Two methods of resetting operation are available: “Timed” and “Instantaneous” (refer to the Inverse time overcurrent curve
characteristics section for details on curve setup, trip times and reset operation). When the element is blocked, the time
accumulator will reset according to the reset characteristic. For example, if the element reset characteristic is set to “Instan-
taneous” and the element is blocked, the time accumulator will be cleared immediately.
The neutral instantaneous overcurrent element may be used as an instantaneous function with no intentional delay or as a
definite time function. The element essentially responds to the magnitude of a neutral current fundamental frequency pha-
sor calculated from the phase currents. A positive-sequence restraint is applied for better performance. A small portion 5
(6.25%) of the positive-sequence current magnitude is subtracted from the zero-sequence current magnitude when forming
the operating quantity of the element as follows:
I op = 3 I_0 – K I_1 where K = 1 16 (EQ 5.15)
The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious zero-sequence currents
resulting from:
• System unbalances under heavy load conditions
• Transformation errors of current transformers (CTs) during double-line and three-phase faults.
• Switch-off transients during double-line and three-phase faults.
The positive-sequence restraint must be considered when testing for pickup accuracy and response time (multiple of
pickup). The operating quantity depends on how test currents are injected into the relay (single-phase injection:
I op = 0.9375 I injected ; three-phase pure zero-sequence injection: I op = 3 I injected ).
The neutral directional overcurrent element provides both forward and reverse fault direction indications the NEUTRAL DIR
OC1 FWD and NEUTRAL DIR OC1 REV operands, respectively. The output operand is asserted if the magnitude of the oper-
ating current is above a pickup level (overcurrent unit) and the fault direction is seen as forward or reverse, respectively
(directional unit).
The overcurrent unit responds to the magnitude of a fundamental frequency phasor of the either the neutral current calcu-
lated from the phase currents or the ground current. There are separate pickup settings for the forward-looking and
reverse-looking functions. If set to use the calculated 3I_0, the element applies a positive-sequence restraint for better per-
formance: a small user-programmable portion of the positive-sequence current magnitude is subtracted from the zero-
sequence current magnitude when forming the operating quantity.
I op = 3 I_0 – K I_1 (EQ 5.16)
The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious zero-sequence currents
resulting from:
• System unbalances under heavy load conditions.
• Transformation errors of current transformers (CTs) during double-line and three-phase faults.
• Switch-off transients during double-line and three-phase faults.
The positive-sequence restraint must be considered when testing for pickup accuracy and response time (multiple of
pickup). The operating quantity depends on the way the test currents are injected into the relay (single-phase injection:
Iop = (1 – K) Iinjected ; three-phase pure zero-sequence injection: Iop = 3 Iinjected).
The positive-sequence restraint is removed for low currents. If the positive-sequence current is below 0.8 pu, the restraint is
removed by changing the constant K to zero. This facilitates better response to high-resistance faults when the unbalance
is very small and there is no danger of excessive CT errors as the current is low.
The directional unit uses the zero-sequence current (I_0) or ground current (IG) for fault direction discrimination and may
be programmed to use either zero-sequence voltage (“Calculated V0” or “Measured VX”), ground current (IG), or both for
polarizing. The zero-sequence current (I_0) must be greater than the PRODUCT SETUP DISPLAY PROPERTIES CUR-
RENT CUT-OFF LEVEL setting value and IG must be greater than 0.05 pu to be validated as the operating quantity for direc-
tional current. The following tables define the neutral directional overcurrent element.
1
where: V_0 = --- VAG + VBG + VCG = zero sequence voltage ,
3
1 1
I_0 = --- IN = --- IA + IB + IC = zero sequence current ,
3 3
ECA = element characteristic angle and IG = ground current
When NEUTRAL DIR OC1 POL VOLT is set to “Measured VX”, one-third of this voltage is used in place of V_0. The following
figure explains the usage of the voltage polarized directional unit of the element.
The figure below shows the voltage-polarized phase angle comparator characteristics for a phase A to ground fault, with:
• ECA = 90° (element characteristic angle = centerline of operating characteristic)
• FWD LA = 80° (forward limit angle = the ± angular limit with the ECA for operation)
• REV LA = 80° (reverse limit angle = the ± angular limit with the ECA for operation)
The element incorporates a current reversal logic: if the reverse direction is indicated for at least 1.25 of a power system
cycle, the prospective forward indication is delayed by 1.5 of a power system cycle. The element is designed to emulate an
electromechanical directional device. Larger operating and polarizing signals results in faster directional discrimination
bringing more security to the element operation.
The forward-looking function is designed to be more secure as compared to the reverse-looking function, and therefore,
should be used for the tripping direction. The reverse-looking function is designed to be faster as compared to the forward-
looking function and should be used for the blocking direction. This allows for better protection coordination.
The above bias should be taken into account when using the neutral directional overcurrent element to directionalize other
protection elements.
REV LA FWD LA
line –3V_0 line line
VAG
(reference)
LA
LA
3I_0 line
ECA
ECA line
–ECA line
–3I_0 line LA
VCG LA
5 VBG
FWD LA
REV LA line
3V_0 line
line 827805A1.CDR
For a choice of current polarizing, it is recommended that the polarizing signal be analyzed to ensure that a known
direction is maintained irrespective of the fault location. For example, if using an autotransformer neutral current
as a polarizing source, it should be ensured that a reversal of the ground current does not occur for a high-side
fault. The low-side system impedance should be assumed minimal when checking for this condition. A similar sit-
uation arises for a wye/delta/wye transformer, where current in one transformer winding neutral may reverse when
faults on both sides of the transformer are considered.
– If “Dual” polarizing is selected, the element performs both directional comparisons as described above. A given
direction is confirmed if either voltage or current comparators indicate so. If a conflicting (simultaneous forward
and reverse) indication occurs, the forward direction overrides the reverse direction.
• NEUTRAL DIR OC1 POL VOLT: Selects the polarizing voltage used by the directional unit when "Voltage," "Dual,"
"Dual-V," or "Dual-I" polarizing mode is set. The polarizing voltage can be programmed to be either the zero-sequence
voltage calculated from the phase voltages ("Calculated V0") or supplied externally as an auxiliary voltage ("Measured
VX").
• NEUTRAL DIR OC1 OP CURR: This setting indicates whether the 3I_0 current calculated from the phase currents, or
the ground current shall be used by this protection. This setting acts as a switch between the neutral and ground
modes of operation (67N and 67G). If set to “Calculated 3I0” the element uses the phase currents and applies the pos-
itive-sequence restraint; if set to “Measured IG” the element uses ground current supplied to the ground CT of the CT
bank configured as NEUTRAL DIR OC1 SOURCE. If this setting is “Measured IG”, then the NEUTRAL DIR OC1 POLARIZING
setting must be “Voltage”, as it is not possible to use the ground current as an operating and polarizing signal simulta-
neously. IG current has to be above 0.05 ps to be used as operate quantity.
• NEUTRAL DIR OC1 POS-SEQ RESTRAINT: This setting controls the amount of the positive-sequence restraint. Set
to 0.063 for backward compatibility with firmware revision 3.40 and older. Set to zero to remove the restraint. Set
higher if large system unbalances or poor CT performance are expected.
• NEUTRAL DIR OC1 OFFSET: This setting specifies the offset impedance used by this protection. The primary appli-
cation for the offset impedance is to guarantee correct identification of fault direction on series compensated lines. In
regular applications, the offset impedance ensures proper operation even if the zero-sequence voltage at the relaying
point is very small. If this is the intent, the offset impedance shall not be larger than the zero-sequence impedance of
the protected circuit. Practically, it shall be several times smaller. The offset impedance shall be entered in secondary
ohms.
See chapter 8 for additional details and chapter 9 for information on how to calculate this setting
5
• NEUTRAL DIR OC1 FWD ECA: This setting defines the characteristic angle (ECA) for the forward direction in the
"Voltage" polarizing mode. The "Current" polarizing mode uses a fixed ECA of 0°. The ECA in the reverse direction is
the angle set for the forward direction shifted by 180°.
• NEUTRAL DIR OC1 FWD LIMIT ANGLE: This setting defines a symmetrical (in both directions from the ECA) limit
angle for the forward direction.
• NEUTRAL DIR OC1 FWD PICKUP: This setting defines the pickup level for the overcurrent unit of the element in the
forward direction. When selecting this setting it must be kept in mind that the design uses a ‘positive-sequence
restraint’ technique for the “Calculated 3I0” mode of operation.
• NEUTRAL DIR OC1 REV LIMIT ANGLE: This setting defines a symmetrical (in both directions from the ECA) limit
angle for the reverse direction.
• NEUTRAL DIR OC1 REV PICKUP: This setting defines the pickup level for the overcurrent unit of the element in the
reverse direction. When selecting this setting it must be kept in mind that the design uses a positive-sequence restraint
technique for the “Calculated 3I0” mode of operation.
MESSAGE
WATTMETRIC GND FLT 1 Range: 0.001 to 1.200 pu in steps of 0.001
5
REF PWR: 0.500 pu
WATTMETRIC GND FLT 1 Range: 0 to 360° Lag in steps of 1
MESSAGE
ECA: 0° Lag
WATTMETRIC GND FLT 1 Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
PWR PKP DEL: 0.20 s
WATTMETRIC GND FLT 1 Range: Definite Time, Inverse, FlexCurves A through D
MESSAGE
CURVE: Definite Time
WATTMETRIC GND FLT 1 Range: 0.01 to 2.00 s in steps of 0.01
MESSAGE
MULTIPLIER: 1.00 s
WATT GND FLT 1 BLK: Range: FlexLogic operand
MESSAGE
Off
WATTMETRIC GND FLT 1 Range: Self-reset, Latched, Disabled
MESSAGE
TARGET: Self-reset
WATTMETRIC GND FLT 1 Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled
The wattmetric zero-sequence directional element responds to power derived from zero-sequence voltage and current in a
direction specified by the element characteristic angle. The angle can be set within all four quadrants and the power can be
active or reactive. Therefore, the element may be used to sense either forward or reverse ground faults in either inductive,
capacitive or resistive networks. The inverse time characteristic allows time coordination of elements across the network.
Typical applications include ground fault protection in solidly grounded transmission networks, grounded/ungrounded/resis-
tor-grounded/resonant-grounded distribution networks, or for directionalizing other non-directional ground elements.
• WATTMETRIC GND FLT 1 VOLT: The element uses neutral voltage (that is, three times the zero-sequence voltage).
This setting allows selecting between the internally calculated neutral voltage, or externally supplied voltage (broken
delta VT connected to the auxiliary channel bank of the relay). When the latter selection is made, the auxiliary channel
must be identified by the user as a neutral voltage under the VT bank settings. This element operates when the auxil-
iary voltage is configured as neutral.
• WATTMETRIC GND FLT 1 OV PKP: This setting specifies the minimum zero sequence voltage supervising the direc-
tional power measurement. This threshold should be higher than possible unbalance during normal operation of the
system. Typically, this setting would be selected at 0.1 to 0.2 pu for the ungrounded or resonant grounded systems,
and at 0.05 to 0.1 pu for solidly or resistor-grounded systems. When using externally supplied voltage via the auxiliary
voltage channel, 1 pu is the nominal voltage of this channel as per VT bank settings. When using internally calculated
neutral voltage, 1 pu is the nominal phase to ground voltage as per the VT bank settings.
• WATTMETRIC GND FLT 1 CURR: The element responds to the neutral current (that is, three times zero-sequence
current), either calculated internally from the phase currents or supplied externally via the ground CT input from more
accurate sources such as the core balanced CT. This setting allows selecting the source of the operating current.
• WATTMETRIC GND FLT 1 OC PKP: This setting specifies the current supervision level for the measurement of the
zero-sequence power.
• WATTMETRIC GND FLT 1 OC PKP DEL: This setting specifies delay for the overcurrent portion of this element. The
delay applies to the WATTMETRIC 1 PKP operand driven from the overcurrent condition.
• WATTMETRIC GND FLT 1 PWR PKP: This setting specifies the operating point of the element. A value of 1 pu is a
product of the 1 pu voltage as specified for the overvoltage condition of this element, and 1 pu current as specified for
the overcurrent condition of this element.
• WATTMETRIC GND FLT 1 REF PWR: This setting is used to calculate the inverse time characteristic delay (defined
by Sref in the following equations). A value of 1 pu represents the product of a 1 pu voltage (as specified in the overvolt-
age condition for this element) and a 1 pu current (as specified in the overcurrent condition for this element.
• WATTMETRIC GND FLT 1 ECA: This setting adjusts the maximum torque angle of the element. The operating power
is calculated as:
5 where * indicates complex conjugate. By varying the element characteristic angle (ECA), the element can be made to
respond to forward or reverse direction in inductive, resistive, or capacitive networks as shown in the Wattmetric char-
acteristic angle response diagram.
• WATTMETRIC GND FLT 1 PWR PKP DEL: This setting defines a definite time delay before the inverse time charac-
teristic is activated. If the curve selection is set as “Definite Time”, the element would operate after this security time
delay. If the curve selection is “Inverse” or one of the FlexCurves, the element uses both the definite and inverse time
timers simultaneously. The definite time timer, specified by this setting, is used and when expires it releases the
inverse time timer for operation (torque control).
• WATTMETRIC GND FLT 1 CURVE: This setting allows choosing one of three methods to delay operate signal once all
conditions are met to discriminate fault direction.
The “Definite Time” selection allows for a fixed time delay defined by the WATTMETRIC GND FLT 1 PWR PKP DEL setting.
The “Inverse” selection allows for inverse time characteristics delay defined by the following formula:
S ref
t = m ---------- (EQ 5.18)
S op
where m is a multiplier defined by the multiplier setting, Sref is the multiplier setting, and Sop is the operating power at
the time. This timer starts after the definite time timer expires.
The four FlexCurves allow for custom user-programmable time characteristics. When working with FlexCurves, the
element uses the operate to pickup ratio, and the multiplier setting is not applied:
S op
t = FlexCurve ---------- (EQ 5.19)
S ref
Again, the FlexCurve timer starts after the definite time timer expires.
INDUCTIVE NETWORK
Vn Vn
In In
RESISTIVE NETWORK
Vn Vn
In In
In In
CAPACITIIVE NETWORK
5
Vn Vn
837804A1.CDR
SETTINGS SETTINGS
WATTMETRIC GND FLT 1 WATTMETRIC GND FLT 1
SOURCE: PWR PICKUP:
WATTMETRIC GND FLT 1 WATTMETRIC GND FLT 1
CURRENT: SETTING SETTINGS
OC PICKUP:
Calculated: Measured: WATTMETRIC GND FLT 1 WATTMETRIC GND FLT 1
WATTMETRIC GND FLT 1
Neutral, In Ground, Ig ECA: OV PICKUP: CURVE:
SETTING
WATTMETRIC GND FLT 1 WATTMETRIC GND FLT 1
VOLTAGE: S = V*conj (I*exp(-j*ECA)) SOP > PWR PICKUP WATTMETRIC GND FLT 1 REF PWR:
Calculated: Measured: 1 PWR PKP DEL:
WATTMETRIC GND FLT 1
Neutral, Vn Auxiliary, Vx MULTIPLIER:
VMAG > OV PICKUP
AND
tPKP RUN
0 FLEXLOGIC OPERAND
IMAG > OC PICKUP SREF
SETTINGS t = m× WATTMETRIC 1 OP
SOP
WATTMETRIC GND FLT
AND
SETTING
1 FUNCTION:
WATTMETRIC GND FLT 1
Enabled = 1
OC PKP DEL:
AND
5 MESSAGE
GROUND TOC1
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
This element can provide a desired time-delay operating characteristic versus the applied current or be used as a simple
definite time element. The ground current input value is the quantity measured by the ground input CT and is the funda-
mental phasor or RMS magnitude. Two methods of resetting operation are available: “Timed” and “Instantaneous” (refer to
the Inverse time overcurrent curve characteristics section for details). When the element is blocked, the time accumulator
will reset according to the reset characteristic. For example, if the element reset characteristic is set to “Instantaneous” and
the element is blocked, the time accumulator will be cleared immediately.
These elements measure the current that is connected to the ground channel of a CT/VT module. The conversion
range of a standard channel is from 0.02 to 46 times the CT rating.
NOTE
This channel may be also equipped with a sensitive input. The conversion range of a sensitive channel is from
0.002 to 4.6 times the CT rating.
NOTE
The ground instantaneous overcurrent element may be used as an instantaneous element with no intentional delay or as a
definite time element. The ground current input is the quantity measured by the ground input CT and is the fundamental
phasor magnitude. 5
These elements measure the current that is connected to the ground channel of a CT/VT module. The conversion
range of a standard channel is from 0.02 to 46 times the CT rating.
NOTE
This channel may be equipped with a standard or sensitive input. The conversion range of a sensitive channel is
from 0.002 to 4.6 times the CT rating.
NOTE
a) MAIN MENU
PATH: SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) NEGATIVE SEQUENCE CURRENT
The D60 relay provides two (2) negative-sequence time overcurrent elements, two (2) negative-sequence instantaneous
overcurrent elements, and two (2) negative-sequence directional overcurrent elements. For additional information on the
negative sequence time overcurrent curves, refer to the Inverse Time Overcurrent Curves section earlier.
SETTING
Off=0
t
SETTING
The negative-sequence instantaneous overcurrent element may be used as an instantaneous function with no intentional
5 delay or as a definite time function. The element responds to the negative-sequence current fundamental frequency phasor
magnitude (calculated from the phase currents) and applies a positive-sequence restraint for better performance: a small
portion (12.5%) of the positive-sequence current magnitude is subtracted from the negative-sequence current magnitude
when forming the operating quantity:
I op = I_2 – K I_1 where K = 1 8 (EQ 5.20)
The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious negative-sequence cur-
rents resulting from:
• system unbalances under heavy load conditions
• transformation errors of current transformers (CTs) during three-phase faults
• fault inception and switch-off transients during three-phase faults
The positive-sequence restraint must be considered when testing for pickup accuracy and response time (multiple of
pickup). The operating quantity depends on the way the test currents are injected into the relay (single-phase injection:
I op = 0.2917 I injected ; three-phase injection, opposite rotation: I op = I injected ).
SETTING
SETTING
NEG SEQ IOC1 FUNCTION: NEG SEQ IOC1
SETTING PICKUP DELAY:
Enabled=1 FLEXLOGIC OPERANDS
NEG SEQ IOC1
NEG SEQ IOC1 PICKUP: NEG SEQ IOC1 PKP
RESET DELAY:
SETTING NEG SEQ IOC1 DPO
AND RUN tPKP
tRST NEG SEQ IOC1 OP
NEG SEQ IOC1 BLOCK: I_2 - K I_1 PICKUP
Off=0
SETTING
I_2 827058A6.CDR
NEG SEQ DIR OC1 NEG SEQ DIR OC1 Range: Disabled, Enabled
FUNCTION: Disabled
NEG SEQ DIR OC1 Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
SOURCE: SRC 1
NEG SEQ DIR OC1 Range: 0.00 to 250.00 ohms in steps of 0.01
MESSAGE
OFFSET: 0.00
NEG SEQ DIR OC1 Range: Neg Sequence, Zero Sequence
MESSAGE
TYPE: Neg Sequence
NEG SEQ DIR OC1 POS- Range: 0.000 to 0.500 in steps of 0.001
MESSAGE
SEQ RESTRAINT: 0.063
NEG SEQ DIR OC1 FWD Range: 0 to 90° Lag in steps of 1
MESSAGE
ECA: 75° Lag
NEG SEQ DIR OC1 FWD Range: 40 to 90° in steps of 1
MESSAGE
LIMIT ANGLE: 90°
NEG SEQ DIR OC1 FWD Range: 0.015 to 30.000 pu in steps of 0.001
MESSAGE
PICKUP: 0.050 pu
NEG SEQ DIR OC1 REV Range: 40 to 90° in steps of 1
MESSAGE
LIMIT ANGLE: 90°
NEG SEQ DIR OC1 REV Range: 0.015 to 30.000 pu in steps of 0.001 5
MESSAGE
PICKUP: 0.050 pu
NEG SEQ DIR OC1 BLK: Range: FlexLogic operand
MESSAGE
Off
NEG SEQ DIR OC1 Range: Self-reset, Latched, Disabled
MESSAGE
TARGET: Self-reset
NEG SEQ DIR OC1 Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled
There are two negative-sequence directional overcurrent protection elements available. The element provides both forward
and reverse fault direction indications through its output operands NEG SEQ DIR OC1 FWD and NEG SEQ DIR OC1 REV,
respectively. The output operand is asserted if the magnitude of the operating current is above a pickup level (overcurrent
unit) and the fault direction is seen as forward or reverse, respectively (directional unit).
The overcurrent unit of the element essentially responds to the magnitude of a fundamental frequency phasor of either the
negative-sequence or neutral current as per user selection.
A positive-sequence restraint is applied for better performance: a small user-programmable portion of the positive-
sequence current magnitude is subtracted from the negative or zero-sequence current magnitude, respectively, when form-
ing the element operating quantity.
I op = I_2 – K I_1 or I op = 3 I_0 – K I_1 (EQ 5.21)
The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious negative-sequence and
zero-sequence currents resulting from:
• System unbalances under heavy load conditions.
• Transformation errors of current transformers (CTs).
• Fault inception and switch-off transients.
The positive-sequence restraint must be considered when testing for pick-up accuracy and response time (multiple of
pickup). The positive-sequence restraint is removed for low currents. If the positive-sequence current is less than 0.8 pu,
then the restraint is removed by changing the constant K to zero. This results in better response to high-resistance faults
when the unbalance is very small and there is no danger of excessive CT errors, since the current is low.
The operating quantity depends on the way the test currents are injected into the D60. For single phase injection:
• Iop = ⅓ (1 – K Iinjected for I_2 mode.
• Iop = (1 – K Iinjected for I_0 mode if I_1 > 0.8 pu.
The directional unit uses the negative-sequence current (I_2) and negative-sequence voltage (V_2).
The following tables define the negative-sequence directional overcurrent element.
Table 5–29: NEGATIVE-SEQUENCE DIRECTIONAL OVERCURRENT UNIT
MODE OPERATING CURRENT
Negative-sequence Iop = |I_2| – K I_1|
Zero-sequence Iop = 3 × (|I_0| – K × |I_1|) if |I_1| > 0.8 pu
Iop = 3 × |I_0| if |I_1| ≤ 0.8 pu
The element incorporates a current reversal logic: if the reverse direction is indicated for at least 1.25 of a power system
cycle, the prospective forward indication will be delayed by 1.5 of a power system cycle. The element is designed to emu-
late an electromechanical directional device. Larger operating and polarizing signals will result in faster directional discrimi-
nation bringing more security to the element operation.
–V_2 line
REV FWD
LA LA VAG (reference)
REV Operating
Region
LA
ECA line
LA ECA
I_2 line
–I_2 line LA
FWD Operating
Region
–ECA line
LA
VCG VBG
V_2 line
REV
LA
FWD
LA
5
827806A2.CDR
• NEG SEQ DIR OC1 OFFSET: This setting specifies the offset impedance used by this protection. The primary applica-
tion for the offset impedance is to guarantee correct identification of fault direction on series compensated lines (see
the Application of settings chapter for information on how to calculate this setting). In regular applications, the offset
impedance ensures proper operation even if the negative-sequence voltage at the relaying point is very small. If this is
the intent, the offset impedance shall not be larger than the negative-sequence impedance of the protected circuit.
Practically, it is several times smaller. The offset impedance is entered in secondary ohms. See the Theory of opera-
tion chapter for additional details.
• NEG SEQ DIR OC1 TYPE: This setting selects the operating mode for the overcurrent unit of the element. The
choices are “Neg Sequence” and “Zero Sequence”. In some applications it is advantageous to use a directional nega-
tive-sequence overcurrent function instead of a directional zero-sequence overcurrent function as inter-circuit mutual
effects are minimized.
• NEG SEQ DIR OC1 POS-SEQ RESTRAINT: This setting controls the positive-sequence restraint. Set to 0.063 (in
“Zero Sequence” mode) or 0.125 (in “Neg Sequence” mode) for backward compatibility with revisions 3.40 and earlier.
Set to zero to remove the restraint. Set higher if large system unbalances or poor CT performance are expected.
• NEG SEQ DIR OC1 FWD ECA: This setting select the element characteristic angle (ECA) for the forward direction.
The element characteristic angle in the reverse direction is the angle set for the forward direction shifted by 180°.
• NEG SEQ DIR OC1 FWD LIMIT ANGLE: This setting defines a symmetrical (in both directions from the ECA) limit
angle for the forward direction.
• NEG SEQ DIR OC1 FWD PICKUP: This setting defines the pickup level for the overcurrent unit in the forward direc-
tion. Upon NEG SEQ DIR OC1 TYPE selection, this pickup threshold applies to zero- or negative-sequence current. When
selecting this setting it must be kept in mind that the design uses a positive-sequence restraint technique.
• NEG SEQ DIR OC1 REV LIMIT ANGLE: This setting defines a symmetrical (in both directions from the ECA) limit
angle for the reverse direction.
• NEG SEQ DIR OC1 REV PICKUP: This setting defines the pickup level for the overcurrent unit in the reverse direc-
tion. Upon NEG SEQ DIR OC1 TYPE selection, this pickup threshold applies to zero- or negative-sequence current. When
selecting this setting it must be kept in mind that the design uses a positive-sequence restraint technique.
SETTINGS
Forward Pickup
Positive-Sequence Restraint
AND RUN
SETTING
Function
FLEXLOGIC OPERAND
Enabled = 1 SETTINGS AND NEG SEQ DIR OC1 FWD
Forward ECA
SETTING AND Forward Limit Angle
Block Reverse Limit Angle
Off = 0 Offset
TIMER
RUN
1.25 cycles
Forward AND
ACTUAL VALUES 1.5 cycles
V_2
I_2
I_0 Reverse
5 NOTE:
V_2 is negative-sequence voltage
I_2 is negative-sequence current
Voltage Polarization
PATH: SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) BREAKER FAILURE BREAKER FAILURE 1(2)
In general, a breaker failure scheme determines that a breaker signaled to trip has not cleared a fault within a definite time,
so further tripping action must be performed. Tripping from the breaker failure scheme should trip all breakers, both local
and remote, that can supply current to the faulted zone. Usually operation of a breaker failure element will cause clearing of
a larger section of the power system than the initial trip. Because breaker failure can result in tripping a large number of
breakers and this affects system safety and stability, a very high level of security is required.
Two schemes are provided: one for three-pole tripping only (identified by the name “3BF”) and one for three pole plus sin-
gle-pole operation (identified by the name “1BF”). The philosophy used in these schemes is identical. The operation of a
breaker failure element includes three stages: initiation, determination of a breaker failure condition, and output.
INITIATION STAGE:
A FlexLogic operand representing the protection trip signal initially sent to the breaker must be selected to initiate the
scheme. The initiating signal should be sealed-in if primary fault detection can reset before the breaker failure timers have
finished timing. The seal-in is supervised by current level, so it is reset when the fault is cleared. If desired, an incomplete
sequence seal-in reset can be implemented by using the initiating operand to also initiate a FlexLogic timer, set longer than
any breaker failure timer, whose output operand is selected to block the breaker failure scheme.
For the D60 relay, the protection trip signal initially sent to the breaker is already programmed as a trip output. The
protection trip signal does not include other breaker commands that are not indicative of a fault in the protected
NOTE
zone.
Schemes can be initiated either directly or with current level supervision. It is particularly important in any application to
decide if a current-supervised initiate is to be used. The use of a current-supervised initiate results in the breaker failure ele-
ment not being initiated for a breaker that has very little or no current flowing through it, which may be the case for trans-
former faults. For those situations where it is required to maintain breaker fail coverage for fault levels below the BF1 PH
AMP SUPV PICKUP or the BF1 N AMP SUPV PICKUP setting, a current supervised initiate should not be used. This feature
should be utilized for those situations where coordinating margins may be reduced when high speed reclosing is used.
Thus, if this choice is made, fault levels must always be above the supervision pickup levels for dependable operation of
the breaker fail scheme. This can also occur in breaker-and-a-half or ring bus configurations where the first breaker closes
into a fault; the protection trips and attempts to initiate breaker failure for the second breaker, which is in the process of
closing, but does not yet have current flowing through it.
When the scheme is initiated, it immediately sends a trip signal to the breaker initially signaled to trip (this feature is usually
described as re-trip). This reduces the possibility of widespread tripping that results from a declaration of a failed breaker.
DETERMINATION OF A BREAKER FAILURE CONDITION:
The schemes determine a breaker failure condition via three paths. Each of these paths is equipped with a time delay, after
which a failed breaker is declared and trip signals are sent to all breakers required to clear the zone. The delayed paths are
associated with breaker failure timers 1, 2, and 3, which are intended to have delays increasing with increasing timer num-
bers. These delayed paths are individually enabled to allow for maximum flexibility.
Timer 1 logic (early path) is supervised by a fast-operating breaker auxiliary contact. If the breaker is still closed (as indi-
cated by the auxiliary contact) and fault current is detected after the delay interval, an output is issued. Operation of the
breaker auxiliary switch indicates that the breaker has mechanically operated. The continued presence of current indicates
that the breaker has failed to interrupt the circuit.
Timer 2 logic (main path) is not supervised by a breaker auxiliary contact. If fault current is detected after the delay interval,
an output is issued. This path is intended to detect a breaker that opens mechanically but fails to interrupt fault current; the
logic therefore does not use a breaker auxiliary contact.
The timer 1 and 2 paths provide two levels of current supervision, high-set and low-set, that allow the supervision level to
change from a current which flows before a breaker inserts an opening resistor into the faulted circuit to a lower level after
resistor insertion. The high-set detector is enabled after timeout of timer 1 or 2, along with a timer that will enable the low-
set detector after its delay interval. The delay interval between high-set and low-set is the expected breaker opening time.
Both current detectors provide a fast operating time for currents at small multiples of the pickup value. The overcurrent
detectors are required to operate after the breaker failure delay interval to eliminate the need for very fast resetting overcur-
rent detectors. 5
Timer 3 logic (slow path) is supervised by a breaker auxiliary contact and a control switch contact used to indicate that the
breaker is in or out-of-service, disabling this path when the breaker is out-of-service for maintenance. There is no current
level check in this logic as it is intended to detect low magnitude faults and it is therefore the slowest to operate.
OUTPUT:
The outputs from the schemes are:
• FlexLogic operands that report on the operation of portions of the scheme
• FlexLogic operand used to re-trip the protected breaker
• FlexLogic operands that initiate tripping required to clear the faulted zone. The trip output can be sealed-in for an
adjustable period.
• Target message indicating a failed breaker has been declared
• Illumination of the faceplate Trip LED (and the Phase A, B or C LED, if applicable)
MAIN PATH SEQUENCE:
FAULT cycles
OCCURS
0 1 2 3 4 5 6 7 8 9 10 11
827083A6.CDR
The current supervision elements reset in less than 0.7 of a power cycle for any multiple of pickup current as shown below.
0.8
Margin
Maximum
0.4
0.2
0
0 20 40 60 80 100 120 140
MulWLple of pickup fault current
threshold setting 836769A4.CDR
5 •
the supervision pickup level.
BF1 USE SEAL-IN: If set to "Yes", the element will only be sealed-in if current flowing through the breaker is above the
supervision pickup level.
• BF1 3-POLE INITIATE: This setting selects the FlexLogic operand that will initiate three-pole tripping of the breaker.
• BF1 PH AMP SUPV PICKUP: This setting is used to set the phase current initiation and seal-in supervision level.
Generally this setting should detect the lowest expected fault current on the protected breaker. It can be set as low as
necessary (lower than breaker resistor current or lower than load current) – high-set and low-set current supervision
will guarantee correct operation.
• BF1 N AMP SUPV PICKUP: This setting is used to set the neutral current initiate and seal-in supervision level. Gener-
ally this setting should detect the lowest expected fault current on the protected breaker. Neutral current supervision is
used only in the three phase scheme to provide increased sensitivity. This setting is valid only for three-pole tripping
schemes.
• BF1 USE TIMER 1: If set to "Yes", the early path is operational.
• BF1 TIMER 1 PICKUP DELAY: Timer 1 is set to the shortest time required for breaker auxiliary contact Status-1 to
open, from the time the initial trip signal is applied to the breaker trip circuit, plus a safety margin.
• BF1 USE TIMER 2: If set to "Yes", the main path is operational.
• BF1 TIMER 2 PICKUP DELAY: Timer 2 is set to the expected opening time of the breaker, plus a safety margin. This
safety margin was historically intended to allow for measuring and timing errors in the breaker failure scheme equip-
ment. In microprocessor relays this time is not significant. In D60 relays, which use a Fourier transform, the calculated
current magnitude will ramp-down to zero one power frequency cycle after the current is interrupted, and this lag
should be included in the overall margin duration, as it occurs after current interruption. The Breaker failure main path
sequence diagram below shows a margin of two cycles; this interval is considered the minimum appropriate for most
applications.
Note that in bulk oil circuit breakers, the interrupting time for currents less than 25% of the interrupting rating can be
significantly longer than the normal interrupting time.
• BF1 USE TIMER 3: If set to "Yes", the Slow Path is operational.
• BF1 TIMER 3 PICKUP DELAY: Timer 3 is set to the same interval as timer 2, plus an increased safety margin.
Because this path is intended to operate only for low level faults, the delay can be in the order of 300 to 500 ms.
• BF1 BKR POS1 A/3P: This setting selects the FlexLogic operand that represents the protected breaker early-type
auxiliary switch contact (52/a). When using the single-pole breaker failure scheme, this operand represents the pro-
tected breaker early-type auxiliary switch contact on pole A. This is normally a non-multiplied form-A contact. The con-
tact may even be adjusted to have the shortest possible operating time.
• BF1 BKR POS2 A/3P: This setting selects the FlexLogic operand that represents the breaker normal-type auxiliary
switch contact (52/a). When using the single-pole breaker failure scheme, this operand represents the protected
breaker auxiliary switch contact on pole A. This may be a multiplied contact.
• BF1 BREAKER TEST ON: This setting is used to select the FlexLogic operand that represents the breaker in-service/
out-of-service switch set to the out-of-service position.
• BF1 PH AMP HISET PICKUP: This setting sets the phase current output supervision level. Generally this setting
should detect the lowest expected fault current on the protected breaker, before a breaker opening resistor is inserted.
• BF1 N AMP HISET PICKUP: This setting sets the neutral current output supervision level. Generally this setting
should detect the lowest expected fault current on the protected breaker, before a breaker opening resistor is inserted.
Neutral current supervision is used only in the three pole scheme to provide increased sensitivity. This setting is valid
only for three-pole breaker failure schemes.
• BF1 PH AMP LOSET PICKUP: This setting sets the phase current output supervision level. Generally this setting
should detect the lowest expected fault current on the protected breaker, after a breaker opening resistor is inserted
(approximately 90% of the resistor current).
• BF1 N AMP LOSET PICKUP: This setting sets the neutral current output supervision level. Generally this setting
should detect the lowest expected fault current on the protected breaker, after a breaker opening resistor is inserted
(approximately 90% of the resistor current). This setting is valid only for three-pole breaker failure schemes.
• BF1 LOSET TIME DELAY: Sets the pickup delay for current detection after opening resistor insertion.
• BF1 TRIP DROPOUT DELAY: This setting is used to set the period of time for which the trip output is sealed-in. This
timer must be coordinated with the automatic reclosing scheme of the failed breaker, to which the breaker failure ele-
5
ment sends a cancel reclosure signal. Reclosure of a remote breaker can also be prevented by holding a transfer trip
signal on longer than the reclaim time.
• BF1 PH A INITIATE / BF1 PH B INITIATE / BF 1 PH C INITIATE: These settings select the FlexLogic operand to initi-
ate phase A, B, or C single-pole tripping of the breaker and the phase A, B, or C portion of the scheme, accordingly.
This setting is only valid for single-pole breaker failure schemes.
• BF1 BKR POS1 B / BF1 BKR POS 1 C: These settings select the FlexLogic operand to represents the protected
breaker early-type auxiliary switch contact on poles B or C, accordingly. This contact is normally a non-multiplied Form-
A contact. The contact may even be adjusted to have the shortest possible operating time. This setting is valid only for
single-pole breaker failure schemes.
• BF1 BKR POS2 B: Selects the FlexLogic operand that represents the protected breaker normal-type auxiliary switch
contact on pole B (52/a). This may be a multiplied contact. This setting is valid only for single-pole breaker failure
schemes.
• BF1 BKR POS2 C: This setting selects the FlexLogic operand that represents the protected breaker normal-type
auxiliary switch contact on pole C (52/a). This may be a multiplied contact. For single-pole operation, the scheme has
the same overall general concept except that it provides re-tripping of each single pole of the protected breaker. The
approach shown in the following single pole tripping diagram uses the initiating information to determine which pole is
supposed to trip. The logic is segregated on a per-pole basis. The overcurrent detectors have ganged settings. This
setting is valid only for single-pole breaker failure schemes.
Upon operation of the breaker failure element for a single pole trip command, a three-pole trip command should be
given via output operand BKR FAIL 1 TRIP OP.
SETTINGS
Function
Enabled = 1
AND
Block
Off = 0
FLEXLOGIC OPERAND
TRIP PHASE A
from the trip output element
SETTING OR Initiated
Phase A Initiate to breaker failure
single-pole logic sheet 2
Off = 0 OR
OR Initiated phase A
SETTING
Three-Pole Initiate to breaker failure
single-pole logic sheet 2
Off = 0
SETTING
AND
Use Seal-In
Yes = 1
Seal-in path
No = 0
AND OR
SETTING OR
Use Current Supervision
Yes = 1
No = 0 OR
AND FLEXLOGIC OPERAND
FLEXLOGIC OPERAND AND BKR FAIL 1 RETRIP B
Seal-in path
5
TRIP PHASE B
from the trip output element
Initiated phase B
OR OR
SETTING to breaker failure
single-pole logic sheet 2
Phase B Initiate
Off = 0
OR
FLEXLOGIC OPERAND
AND
TRIP PHASE C
from the trip output element
OR FLEXLOGIC OPERAND
Seal-in path AND BKR FAIL 1 RETRIP C
SETTING
Phase C Initiate SETTING
Off = 0 Phase Current Initiated phase C
Supervision Pickup
to breaker failure
RUN single-pole logic sheet 2
IA ≥ Pickup
SETTING
SETTING
Source RUN OR
IA IB ≥ Pickup
IB RUN
IC IC ≥ Pickup
IC
to breaker failure
IB
single-pole logic sheet 3
IA 827069A9.CDR
GE Multilin
%UHDNHU3RV3KDVH$3 )/(;/2*,&23(5$1'
2II 25 %.5)$,/723
8VH7LPHU
5 SETTINGS
6(77,1* 6(77,1*
1R 7LPHU3LFNXS'HOD\ $1' 3KDVH&XUUHQW+L6HW3LFNXS
<HV 581
25
$1' ,$ 3LFNXS
,QLWLDWHGSKDVH$
IURPVLQJOHSROHEUHDNHU 6(77,1*
IDLOXUHORJLFVKHHW 6(77,1*
7LPHU3LFNXS'HOD\ /R6HW7LPH'HOD\ 6(77,1*
3KDVH&XUUHQW/R6HW3LFNXS
6(77,1*
$1' 581
8VH7LPHU
<HV ,$ 3LFNXS
1R
6(77,1*
6(77,1*6
7LPHU3LFNXS'HOD\ $1' 6(77,1*
%UHDNHU3RV3KDVH%
3KDVH&XUUHQW+L6HW3LFNXS
2II
$1' 25 581
,QLWLDWHGSKDVH% ,% 3LFNXS
IURPVLQJOHSROHEUHDNHU 6(77,1*
IDLOXUHORJLFVKHHW 6(77,1*
6(77,1* 7ULS'URSRXW'HOD\
7LPHU3LFNXS'HOD\
/R6HW7LPH'HOD\ 6(77,1* )/(;/2*,&23(5$1'
3KDVH&XUUHQW/R6HW3LFNXS 25 %.5)$,/75,323
$1'
6(77,1*6 581
%UHDNHU3RV3KDVH%
,% 3LFNXS
2II
6(77,1*
6(77,1*
$1' 3KDVH&XUUHQW+L6HW3LFNXS
7LPHU3LFNXS'HOD\
581
,$
,%
,&
,QLWLDWHG
IURPVLQJOHSROHEUHDNHUIDLOXUHORJLFVKHHW $&'5
5.6 GROUPED ELEMENTS
5-223
5
5.6 GROUPED ELEMENTS 5 SETTINGS
a) MAIN MENU
PATH: SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) VOLTAGE ELEMENTS
5 MESSAGE
NEG SEQ OV3
See page 5–231.
AUXILIARY UV1
MESSAGE See page 5–232.
AUXILIARY UV2
MESSAGE See page 5–232.
AUXILIARY OV1
MESSAGE See page 5–233.
AUXILIARY OV2
MESSAGE See page 5–233.
COMPENSATED
MESSAGE See page 5–233.
OVERVOLTAGE
These protection elements can be used for a variety of applications such as:
• Undervoltage Protection: For voltage sensitive loads, such as induction motors, a drop in voltage increases the
drawn current which may cause dangerous overheating in the motor. The undervoltage protection feature can be used
to either cause a trip or generate an alarm when the voltage drops below a specified voltage setting for a specified time
delay.
• Permissive Functions: The undervoltage feature may be used to block the functioning of external devices by operat-
ing an output relay when the voltage falls below the specified voltage setting. The undervoltage feature may also be
used to block the functioning of other elements through the block feature of those elements.
• Source Transfer Schemes: In the event of an undervoltage, a transfer signal may be generated to transfer a load
from its normal source to a standby or emergency power source.
The undervoltage elements can be programmed to have a definite time delay characteristic. The definite time curve oper-
ates when the voltage drops below the pickup level for a specified period of time. The time delay is adjustable from 0 to
600.00 seconds in steps of 0.01. The undervoltage elements can also be programmed to have an inverse time delay char-
acteristic.
The undervoltage delay setting defines the family of curves shown below.
D
T = ---------------------------------- (EQ 5.22)
V
1 – ------------------
V pickup
Time (seconds)
5
% of voltage pickup
842788A1.CDR
NOTE
This element may be used to give a desired time-delay operating characteristic versus the applied fundamental voltage
(phase-to-ground or phase-to-phase for wye VT connection, or phase-to-phase for delta VT connection) or as a definite
time element. The element resets instantaneously if the applied voltage exceeds the dropout voltage. The delay setting
selects the minimum operating time of the phase undervoltage. The minimum voltage setting selects the operating voltage
below which the element is blocked (a setting of “0” will allow a dead source to be considered a fault condition).
The phase overvoltage element may be used as an instantaneous element with no intentional time delay or as a definite
time element. The input voltage is the phase-to-phase voltage, either measured directly from delta-connected VTs or as cal-
culated from phase-to-ground (wye) connected VTs. The specific voltages to be used for each phase are shown below. 5
SETTINGS
SETTING
PHASE OV1 PICKUP
PHASE OV1 SETTING DELAY:
FUNCTION: FLEXLOGIC OPERANDS
PHASE OV1 PHASE OV1 RESET
Disabled = 0 PICKUP: DELAY: PHASE OV1 A PKP
Enabled = 1 PHASE OV1 A DPO
RUN tPKP
VAB ≥ PICKUP PHASE OV1 A OP
tRST
PHASE OV1 B PKP
SETTING AND RUN tPKP PHASE OV1 B DPO
PHASE OV1 VBC ≥ PICKUP
BLOCK: PHASE OV1 B OP
tRST
RUN PHASE OV1 C PKP
Off = 0
VCA ≥ PICKUP tPKP PHASE OV1 C DPO
PHASE OV1 C OP
tRST
SETTING
PHASE OV1
SOURCE: FLEXLOGIC OPERAND
Source VT = Delta OR PHASE OV1 OP
VAB
VBC
FLEXLOGIC OPERAND
VCA
AND PHASE OV1 DPO
Source VT = Wye
FLEXLOGIC OPERAND
OR PHASE OV1 PKP
827066A7.CDR
SETTING
NEUTRAL OV1
FUNCTION:
SETTING SETTING
Enabled=1
NEUTRAL OV1 PICKUP
NEUTRAL OV1 PICKUP: DELAY :
SETTING
AND RUN NEUTRAL OV1 RESET
DELAY :
NEUTRAL OV1 BLOCK:
NEUTRAL OV1 CURVE :
Off=0
FLEXLOGIC OPERANDS
3V_0< Pickup tPKP
t NEUTRAL OV1 OP
SETTING tRST
NEUTRAL OV1 DPO
NEUTRAL OV1 SIGNAL
SOURCE: NEUTRAL OV1 PKP
ZERO SEQ VOLT (V_0)
827848A3.CDR
SETTING
NEG SEQ OV1
FUNCTION:
SETTING
Enabled = 1
NEG SEQ OV1 PICKUP: SETTINGS
SETTING NEG SEQ OV1 PICKUP
AND RUN DELAY:
NEG SEQ OV1 BLOCK: FLEXLOGIC OPERANDS
NEG SEQ OV1 RESET
NEG SEQ OV1 PKP
DELAY:
Off = 0 NEG SEQ OV1 DPO
t PKP
t RST NEG SEQ OV1 OP
SETTING V_2 > PICKUP
NEG SEQ OV1 SIGNAL
SOURCE:
NEG SEQ VOLTAGE V_2
827839A4.CDR
827849A3.CDR
The D60 contains one auxiliary overvoltage element for each VT bank. This element is intended for monitoring overvoltage
conditions of the auxiliary voltage. The nominal secondary voltage of the auxiliary voltage channel entered under SYSTEM
SETUP AC INPUTS VOLTAGE BANK X5 AUXILIARY VT X5 SECONDARY is the per-unit (pu) base used when setting the 5
pickup level.
A typical application for this element is monitoring the zero-sequence voltage (3V_0) supplied from an open-corner-delta
VT connection.
SETTING
AUX OV1
FUNCTION:
SETTING
Enabled=1
AUX OV1 PICKUP: SETTING
SETTING
AND RUN AUX OV1 PICKUP
DELAY :
AUX OV1 BLOCK:
AUX OV1 RESET
Off=0 DELAY :
FLEXLOGIC OPERANDS
Vx < Pickup tPKP
SETTING tRST AUX OV1 OP
AUX OV1 DPO
AUX OV1 SIGNAL
SOURCE: AUX OV1 PKP
AUXILIARY VOLT (Vx)
827836A3.CDR
The compensated overvoltage function is intended to provide protection against an overvoltage due to the opening of the
remote terminal of a transmission line – the so called the Ferranti effect. This could be achieved using a transfer-tripping
scheme. However, with high voltage, more corona may exist on the line and inhibit the proper reception of a carrier-trans-
fer-trip signal. Also, the presence of a line with an open terminal in weak systems can raise the voltage level of the local
bus. Detecting and tripping a line with an open terminal can prevent tripping at the local bus in this case.
/RFDO 5HPRWH
WHUPLQDO WHUPLQDO
=F
,B
9B 9B&
$&'5
,B
9B 9BF
,Bî=F
$&'5
PATH: SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) POWER SENSITIVE DIRECTIONAL POWER
DIRECTIONAL POWER 1(2)
DIRECTIONAL DIR POWER 1 Range: Disabled, Enabled
POWER 1 FUNCTION: Disabled
DIR POWER 1 Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
SOURCE: SRC 1
DIR POWER 1 Range: 0 to 359° in steps of 1
MESSAGE
RCA: 0°
DIR POWER 1 Range: 0 to 0.95° in steps of 0.05
MESSAGE
CALIBRATION: 0.00°
DIR POWER 1 STG1 Range: –1.200 to 1.200 pu in steps of 0.001
MESSAGE
SMIN: 0.100 pu
DIR POWER 1 STG1 Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
DELAY: 0.50 s
DIR POWER 1 STG2 Range: –1.200 to 1.200 pu in steps of 0.001
MESSAGE
SMIN: 0.100 pu
DIR POWER 1 STG2 Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
DELAY: 20.00 s
MESSAGE
DIR POWER 1 BLK: Range: FlexLogic operand
5
Off
DIR POWER 1 Range: Self-Reset, Latched, Disabled
MESSAGE
TARGET: Self-Reset
DIR POWER 1 Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled
The sensitive directional power element responds to three-phase directional power and is designed for reverse power and
low forward power applications for synchronous machines or interconnections involving co-generation. The relay measures
the three-phase power from either full set of wye-connected VTs or full-set of delta-connected VTs. In the latter case, the
two-wattmeter method is used. Refer to the UR-series metering conventions section in chapter 6 for details regarding the
active and reactive powers used by the sensitive directional power element.
The element has an adjustable characteristic angle and minimum operating power as shown in the Directional power char-
acteristic diagram. The element responds to the following condition:
P cos + Q sin SMIN (EQ 5.25)
where: P and Q are active and reactive powers as measured per the UR-series metering convention,
is a sum of the element characteristic (DIR POWER 1 RCA) and calibration (DIR POWER 1 CALIBRATION) angles, and
SMIN is the minimum operating power
The operating quantity is displayed in the ACTUAL VALUES METERING SENSITIVE DIRECTIONAL POWER 1(2) actual
value. The element has two independent (as to the pickup and delay settings) stages for alarm and trip, respectively.
n
io
ct
re
Di
OPERATE
RCA+
CALIBRATION
SMIN
P
+
RESTRAIN
-
(a) Q (b) Q
RESTRAIN
OPERATE RESTRAIN OPERATE
P P
5 RCA = 180o
SMIN > 0
RCA = 180o
SMIN < 0
(c) Q (d) Q
OPERATE OPERATE
P P
RESTRAIN RESTRAIN
RCA = 0o RCA = 0o
SMIN < 0 SMIN > 0
(e) Q
OPERATE
(f) Q
RESTRAIN
RESTRAIN OPERATE
P P
842702A1.CDR
• DIR POWER 1 RCA: Specifies the relay characteristic angle (RCA) for the sensitive directional power function. Appli-
cation of this setting is threefold:
1. It allows the element to respond to active or reactive power in any direction (active overpower/underpower, etc.).
2. Together with a precise calibration angle, it allows compensation for any CT and VT angular errors to permit more
sensitive settings.
3. It allows for required direction in situations when the voltage signal is taken from behind a delta-wye connected
power transformer and the phase angle compensation is required.
For example, the active overpower characteristic is achieved by setting DIR POWER 1 RCA to “0°”, reactive overpower by
setting DIR POWER 1 RCA to “90°”, active underpower by setting DIR POWER 1 RCA to “180°”, and reactive underpower by
setting DIR POWER 1 RCA to “270°”.
• DIR POWER 1 CALIBRATION: This setting allows the relay characteristic angle to change in steps of 0.05°. This may
be useful when a small difference in VT and CT angular errors is to be compensated to permit more sensitive settings.
This setting virtually enables calibration of the directional power function in terms of the angular error of applied VTs
and CTs. The element responds to the sum of the DIR POWER 1 RCA and DIR POWER 1 CALIBRATION settings.
• DIR POWER 1 STG1 SMIN: This setting specifies the minimum power as defined along the relay characteristic angle
(RCA) for the stage 1 of the element. The positive values imply a shift towards the operate region along the RCA line;
the negative values imply a shift towards the restrain region along the RCA line. Refer to the Directional power sample
applications figure for details. Together with the RCA, this setting enables a wide range of operating characteristics.
This setting applies to three-phase power and is entered in per-unit (pu) values. The base quantity is 3-phase power
on primary side, which is calculated as 3 x Phase CT Primary x Phase VT Ratio x Phase VT Secondary in case of
delta connected VTs; and 3 x Phase CT Primary x Phase VT Ratio x Phase VT Secondary in case of wye connected
VTs.
For example, a setting of 2% for a 200 MW machine is 0.02 200 MW = 4 MW. If 7.967 kV is a primary VT voltage and
10 kA is a primary CT current, the source pu quantity is 239 MVA, and thus, SMIN should be set at 4 MW / 239 MVA = 5
0.0167 pu 0.017 pu. If the reverse power application is considered, RCA = 180° and SMIN = 0.017 pu.
The element drops out if the magnitude of the positive-sequence current becomes virtually zero, that is, it drops below
the cutoff level.
• DIR POWER 1 STG1 DELAY: This setting specifies a time delay for stage 1. For reverse power or low forward power
applications for a synchronous machine, stage 1 is typically applied for alarming and stage 2 for tripping.
SETTING
DIR POWER 1
FUNCTION:
Enabled = 1
SETTINGS SETTING
SETTING DIR POWER 1 RCA: DIR POWER 1 STG1
DIR POWER 1 BLK: DELAY:
AND
DIR POWER 1 OP
Three-phase reactive power (Q)
DIR POWER 1 STG2 DPO
DIR POWER 1 STG2 OP
SETTING
DIR POWER 1 STG2
DELAY:
tPKP
100 ms
842003A3.CDR
Control elements are generally used for control rather than protection. See the Introduction to Elements section at the
beginning of this chapter for further information.
The trip bus element allows aggregating outputs of protection and control elements without using FlexLogic and assigning
them a simple and effective manner. Each trip bus can be assigned for either trip or alarm actions. Simple trip conditioning
such as latch, delay, and seal-in delay are available.
The easiest way to assign element outputs to a trip bus is through the EnerVista UR Setup software A protection summary
is displayed by navigating to a specific protection or control protection element and checking the desired bus box. Once the
desired element is selected for a specific bus, a list of element operate-type operands are displayed and can be assigned
to a trip bus. If more than one operate-type operand is required, it may be assigned directly from the trip bus menu.
SETTINGS
TRIP BUS 1 INPUT 1
SETTINGS
= Off
TRIP BUS 1 PICKUP
TRIP BUS 1 INPUT 2
DELAY
= Off Non-volatile,
TRIP BUS 1 RESET
OR set-dominant
***
DELAY
AND S TPKP FLEXLOGIC OPERAND
TRIP BUS 1 INPUT 16 TRIP BUS 1 OP
Latch
= Off TRST
R
SETTINGS
TRIP BUS 1 FLEXLOGIC OPERAND
FUNCTION
TRIP BUS 1 PKP
= Enabled
TRIP BUS 1 BLOCK AND
= Off
SETTINGS
TRIP BUS 1
LATCHING
= Enabled
TRIP BUS 1 RESET
= Off
OR
FLEXLOGIC OPERAND
RESET OP 842023A1.CDR
5 MESSAGE
GROUP 6 NAME: Range: up to 16 alphanumeric characters
The 61850 standard provides for the ability to monitor, edit, and change setting groups in a relay through a series of ser-
vices operating on Setting Group Control Block values. There is one SGCB in LLN0 in LD1 in the UR as, at present, the
other LDs do not support multiple setting groups The default value of SETTING GROUPS is Disabled. In order for 61850 and/
or UR setting group control to function, the SETTING GROUPS FUNCTION must be set to Enabled.
The active setting group in the UR is settable from either the value set via a FlexLogic operand in the UR (present practice)
or a SelectActiveSG command from a 61850 Client. For both the UR and IEC 61850, the default active setting group is "1".
A 61850 SelectActiveSG command sets one of the internal Non-Volatile flags (61850 SG Level x) that represents the
requested Active Setting Group shown as follows:
Table 5–31: ACTIVE SETTING GROUP
SELECTACTIVESG VALUE FLAG SET
1 (default) SG Level 1
2 SG Level 2
3 SG Level 3
4 SG Level 4
5 SG Level 4
6 SG Level 6
On power-up or restart, the previously selected 61850 SG Level x is re-instated. Similarly, the input to the setting group
control in the UR can be designed with Non-Volatile latches to achieve the same effect.
The setting groups menu controls the activation and deactivation of up to six possible groups of settings in the GROUPED
ELEMENTS settings menu. The faceplate Settings In Use LEDs indicate which active group (with a non-flashing energized
LED) is in service.
The SETTING GROUPS BLK setting prevents the active setting group from changing when the FlexLogic parameter is set to
"On". This can be useful in applications where it is undesirable to change the settings under certain conditions, such as the
breaker being open.
The GROUP 2 ACTIVATE ON to GROUP 6 ACTIVATE ON settings select a FlexLogic operand which, when set, makes the partic-
ular setting group active for use by any grouped element. A priority scheme ensures that only one group is active at a given
time – the highest-numbered group that is activated by its ACTIVATE ON parameter takes priority over the lower-numbered
groups. There is no activate on setting for group 1 (the default active group), because group 1 automatically becomes
active if no other group is active.
The SETTING GROUP 1 NAME to SETTING GROUP 6 NAME settings allows the user to assign a name to each of the six settings
groups. Once programmed, this name appears on the second line of the GROUPED ELEMENTS SETTING GROUP 1(6) menu
display.
The relay can be set up via a FlexLogic equation to receive requests to activate or de-activate a particular non-default set-
tings group. The following FlexLogic equation (see the following figure) illustrates requests via remote communications (for
example, VIRTUAL INPUT 1 ON) or from a local contact input (for example, CONTACT IP 1 ON) to initiate the use of a particu-
lar settings group, and requests from several overcurrent pickup measuring elements to inhibit the use of the particular set-
tings group. The assigned VIRTUAL OUTPUT 1 operand is used to control the “On” state of a particular settings group.
1 VIRT IP 1 ON (VI1)
OR (2)
2 CONT IP 1 ON (H5A)
3 OR (2)
AND (3) = VIRT OP 1 (VO1)
4 PHASE TOC1 PKP
5 NOT
8 AND (3)
9 = VIRT OP 1 (VO1)
10 END
842789A1.CDR
5 MESSAGE
Off
SELECTOR 1 3BIT Range: Time-out, Acknowledge
MESSAGE
MODE: Time-out
SELECTOR 1 3BIT ACK: Range: FlexLogic operand
MESSAGE
Off
SELECTOR 1 POWER-UP Range: Restore, Synchronize, Sync/Restore
MESSAGE
MODE: Restore
SELECTOR 1 TARGETS: Range: Self-reset, Latched, Disabled
MESSAGE
Self-reset
SELECTOR 1 EVENTS: Range: Disabled, Enabled
MESSAGE
Disabled
The selector switch element is intended to replace a mechanical selector switch. Typical applications include setting group
control or control of multiple logic sub-circuits in user-programmable logic.
The element provides for two control inputs. The step-up control allows stepping through selector position one step at a
time with each pulse of the control input, such as a user-programmable pushbutton. The three-bit control input allows set-
ting the selector to the position defined by a three-bit word.
The element allows pre-selecting a new position without applying it. The pre-selected position gets applied either after time-
out or upon acknowledgement via separate inputs (user setting). The selector position is stored in non-volatile memory.
Upon power-up, either the previous position is restored or the relay synchronizes to the current three-bit word (user set-
ting). Basic alarm functionality alerts the user under abnormal conditions; for example, the three-bit control input being out
of range.
• SELECTOR 1 FULL RANGE: This setting defines the upper position of the selector. When stepping up through avail-
able positions of the selector, the upper position wraps up to the lower position (position 1). When using a direct three-
bit control word for programming the selector to a desired position, the change would take place only if the control word
is within the range of 1 to the SELECTOR FULL RANGE. If the control word is outside the range, an alarm is established
by setting the SELECTOR ALARM FlexLogic operand for 3 seconds.
• SELECTOR 1 TIME-OUT: This setting defines the time-out period for the selector. This value is used by the relay in
the following two ways. When the SELECTOR STEP-UP MODE is “Time-out”, the setting specifies the required period of
inactivity of the control input after which the pre-selected position is automatically applied. When the SELECTOR STEP-
UP MODE is “Acknowledge”, the setting specifies the period of time for the acknowledging input to appear. The timer is
re-started by any activity of the control input. The acknowledging input must come before the SELECTOR 1 TIME-OUT
timer expires; otherwise, the change will not take place and an alarm will be set.
• SELECTOR 1 STEP-UP: This setting specifies a control input for the selector switch. The switch is shifted to a new
position at each rising edge of this signal. The position changes incrementally, wrapping up from the last (SELECTOR 1
FULL RANGE) to the first (position 1). Consecutive pulses of this control operand must not occur faster than every
50 ms. After each rising edge of the assigned operand, the time-out timer is restarted and the SELECTOR SWITCH 1:
POS Z CHNG INITIATED target message is displayed, where Z the pre-selected position. The message is displayed for
the time specified by the FLASH MESSAGE TIME setting. The pre-selected position is applied after the selector times out
(“Time-out” mode), or when the acknowledging signal appears before the element times out (“Acknowledge” mode).
When the new position is applied, the relay displays the SELECTOR SWITCH 1: POSITION Z IN USE message. Typically,
a user-programmable pushbutton is configured as the stepping up control input.
• SELECTOR 1 STEP-UP MODE: This setting defines the selector mode of operation. When set to “Time-out”, the
selector will change its position after a pre-defined period of inactivity at the control input. The change is automatic and
does not require any explicit confirmation of the intent to change the selector's position. When set to “Acknowledge”,
the selector will change its position only after the intent is confirmed through a separate acknowledging signal. If the
acknowledging signal does not appear within a pre-defined period of time, the selector does not accept the change
and an alarm is established by setting the SELECTOR STP ALARM output FlexLogic operand for 3 seconds.
• SELECTOR 1 ACK: This setting specifies an acknowledging input for the stepping up control input. The pre-selected
position is applied on the rising edge of the assigned operand. This setting is active only under “Acknowledge” mode of
operation. The acknowledging signal must appear within the time defined by the SELECTOR 1 TIME-OUT setting after the
last activity of the control input. A user-programmable pushbutton is typically configured as the acknowledging input.
5
• SELECTOR 1 3BIT A0, A1, and A2: These settings specify a three-bit control input of the selector. The three-bit con-
trol word pre-selects the position using the following encoding convention:
A2 A1 A0 POSITION
0 0 0 rest
0 0 1 1
0 1 0 2
0 1 1 3
1 0 0 4
1 0 1 5
1 1 0 6
1 1 1 7
The “rest” position (0, 0, 0) does not generate an action and is intended for situations when the device generating the
three-bit control word is having a problem. When SELECTOR 1 3BIT MODE is “Time-out”, the pre-selected position is
applied in SELECTOR 1 TIME-OUT seconds after the last activity of the three-bit input. When SELECTOR 1 3BIT MODE is
“Acknowledge”, the pre-selected position is applied on the rising edge of the SELECTOR 1 3BIT ACK acknowledging
input.
The stepping up control input (SELECTOR 1 STEP-UP) and the three-bit control inputs (SELECTOR 1 3BIT A0 through A2)
lock-out mutually: once the stepping up sequence is initiated, the three-bit control input is inactive; once the three-bit
control sequence is initiated, the stepping up input is inactive.
• SELECTOR 1 3BIT MODE: This setting defines the selector mode of operation. When set to “Time-out”, the selector
changes its position after a pre-defined period of inactivity at the control input. The change is automatic and does not
require explicit confirmation to change the selector position. When set to “Acknowledge”, the selector changes its posi-
tion only after confirmation via a separate acknowledging signal. If the acknowledging signal does not appear within a
pre-defined period of time, the selector rejects the change and an alarm established by invoking the SELECTOR BIT
ALARM FlexLogic operand for 3 seconds.
• SELECTOR 1 3BIT ACK: This setting specifies an acknowledging input for the three-bit control input. The pre-
selected position is applied on the rising edge of the assigned FlexLogic operand. This setting is active only under the
“Acknowledge” mode of operation. The acknowledging signal must appear within the time defined by the SELECTOR
TIME-OUT setting after the last activity of the three-bit control inputs. Note that the stepping up control input and three-
bit control input have independent acknowledging signals (SELECTOR 1 ACK and SELECTOR 1 3BIT ACK, accordingly).
• SELECTOR 1 POWER-UP MODE: This setting specifies the element behavior on power up of the relay.
When set to “Restore”, the last position of the selector (stored in the non-volatile memory) is restored after powering up
the relay. If the position restored from memory is out of range, position 0 (no output operand selected) is applied and
an alarm is set (SELECTOR 1 PWR ALARM).
When set to “Synchronize” selector switch acts as follows. For two power cycles, the selector applies position 0 to the
switch and activates SELECTOR 1 PWR ALARM. After two power cycles expire, the selector synchronizes to the position
dictated by the three-bit control input. This operation does not wait for time-out or the acknowledging input. When the
synchronization attempt is unsuccessful (that is, the three-bit input is not available (0,0,0) or out of range) then the
selector switch output is set to position 0 (no output operand selected) and an alarm is established (SELECTOR 1 PWR
ALARM).
The operation of “Synch/Restore” mode is similar to the “Synchronize” mode. The only difference is that after an
unsuccessful synchronization attempt, the switch will attempt to restore the position stored in the relay memory. The
“Synch/Restore” mode is useful for applications where the selector switch is employed to change the setting group in
redundant (two relay) protection schemes.
• SELECTOR 1 EVENTS: If enabled, the following events are logged:
5 SELECTOR 1 BIT ALARM The selector position pre-selected via the three-bit control input has not been confirmed
before the time out.
The following figures illustrate the operation of the selector switch. In these diagrams, “T” represents a time-out setting.
STEP-UP
T T
3BIT A0
3BIT A1
3BIT A2
T T
POS 1
POS 2
POS 3
POS 4
POS 5
POS 6 5
POS 7
BIT 0
BIT 1
BIT 2
STP ALARM
BIT ALARM
ALARM
842737A1.CDR
STEP-UP
ACK
3BIT A0
3BIT A1
3BIT A2
3BIT ACK
POS 1
POS 2
POS 3
POS 4
POS 5
POS 6
5 POS 7
BIT 0
BIT 1
BIT 2
STP ALARM
BIT ALARM
ALARM
842736A1.CDR
Now, assign the contact output operation (assume the H6E module) to the selector switch element by making the following
changes in the SETTINGS INPUTS/OUTPUTS CONTACT OUTPUTS menu:
OUTPUT H1 OPERATE: “SELECTOR 1 BIT 0"
OUTPUT H2 OPERATE: “SELECTOR 1 BIT 1"
OUTPUT H3 OPERATE: “SELECTOR 1 BIT 2"
Finally, assign configure user-programmable pushbutton 1 by making the following changes in the SETTINGS PRODUCT
SETUP USER-PROGRAMMABLE PUSHBUTTONS USER PUSHBUTTON 1 menu:
SETTINGS
SELECTOR 1 FULL RANGE:
5
SELECTOR 1 FUNCTION: SELECTOR 1 POWER-UP MODE:
Enabled = 1 RUN
SELECTOR 1 STEP-UP: FLEXLOGIC™ OPERANDS
Off = 0 step up SELECTOR 1 POS 1
2
SELECTOR 1 ACK: 1 SELECTOR 1 POS 2
3
Off = 0 acknowledge SELECTOR 1 POS 3
SELECTOR 1 3BIT A0: 4
SELECTOR 1 POS 4
three-bit control input
SELECTOR 1 ALARM
SELECTOR 1 PWR ALARM
SELECTOR 1 BIT 0
SELECTOR 1 BIT 1
SELECTOR 1 BIT 2
842012A2.CDR
TRIP OUTPUT TRIP MODE: Range: Disabled, 3 Pole Only, 3 Pole & 1 Pole
Disabled
TRIP 3-POLE INPUT-1: Range: FlexLogic operand
MESSAGE
Off
TRIP 3-POLE INPUT-2: Range: FlexLogic operand
MESSAGE
Off
TRIP 3-POLE INPUT-6: Range: FlexLogic operand
MESSAGE
Off
TRIP 1-POLE INPUT-1: Range: FlexLogic operand
MESSAGE
Off
TRIP 1-POLE INPUT-2: Range: FlexLogic operand
MESSAGE
Off
TRIP 1-POLE INPUT-6: Range: FlexLogic operand
MESSAGE
Off
5 MESSAGE
TRIP RECLOSE INPUT-1:
Off
Range: FlexLogic operand
The trip output element is primarily used to collect trip requests from protection elements and other inputs to generate out-
put operands to initiate trip operations. Three pole trips will only initiate reclosure if programmed to do so, whereas single
pole trips will always automatically initiate reclosure. The TRIP 3-POLE and TRIP 1-POLE output operands can also be used
as inputs to a FlexLogic OR gate to operate the faceplate Trip indicator LED.
THREE POLE OPERATION:
In applications where single-pole tripping is not required this element provides a convenient method of collecting inputs to
initiate tripping of circuit breakers, the reclose element and breaker failure elements.
SINGLE POLE OPERATION:
This element must be used in single pole operation applications.
5
NOTE
• TRIP 1-POLE INPUT-1 to TRIP 1-POLE INPUT-6: These settings are used to select an operand representing a fault
condition that is desired to initiate a single pole trip-and-reclose if the fault is single phase to ground (for example, dis-
tance zone 1). Use a FlexLogic OR-gate if more than six inputs are required. The inputs do not have to be phase-spe-
cific as the phase selector determines the fault type.
The AR FORCE 3-P TRIP operand is asserted by the autorecloser 1.5 cycles after single-pole reclosing is initiated. This
operand calls for a three-pole trip if any protection element configured under TRIP 1-POLE INPUT remains picked-up. The
open pole detector provides blocking inputs to distance elements, and therefore the latter will reset immediately after
the TRIP 1-POLE operand is asserted. For other protection elements used in single-pole tripping, the user must ensure
they will reset immediately after tripping, otherwise the fact that they are still picked up will be detected as an evolving
fault and the relay will trip three-poles. For example, if high-set phase instantaneous overcurrent is used (TRIP 1-POLE
INPUT X: “PHASE IOC1 OP”), then OPEN POLE OP A shall be used for blocking phase A of the instantaneous overcur-
rent element. In this way, after tripping phase A, the phase a instantaneous overcurrent element is forced to reset.
Phases B and C are still operational and can detect an evolving fault as soon as 8 ms after tripping phase A. Neutral
and negative-sequence instantaneous overcurrent elements shall be blocked from the OPEN POLE BLK N operand
unless the pickup setting is high enough to prevent pickup during single-pole reclosing.
• TRIP RECLOSE INPUT-1 to TRIP RECLOSE INPUT-6: These settings select an operand representing a fault condi-
tion that is desired to initiate three pole reclosing (for example, phase distance zone 1). Use a FlexLogic OR-gate if
more than six inputs are required. These inputs also include the TRIP 1-POLE INPUT-1 to TRIP 1-POLE INPUT-6 values,
which are intended to initiate three-pole reclosing in situations where single-pole tripping commands are changed to
three-pole tripping commands. This can happen in cases where the phase selector identifies a multi-phase fault or the
AR FORCE 3P TRIP command is present.
• TRIP SEAL-IN DELAY: This setting specifies the minimum time that trip command signals are maintained to provide
sufficient time to open the breaker poles. If a value of “0” is specified, then the output signal is reset once the protection
elements initiating the trip are reset. If a value other than “0” is specified, then the protection elements must reset and
5 •
the timer initiated at the first trip command must expire.
TRIP RESET: This setting selects the option to reset the trip latches. If “Pole Curr OR Custom” is chosen, then the
OPEN POLE CURRENT PKP setting should be programmed accordingly. If “CBaux OR Custom” is chosen, then the break-
ers should be set appropriately. Both the “Current” and “CBaux” options can be complimented by custom conditions
using the BKR ΦA OPEN, BKR ΦB OPEN, and BKR ΦC OPEN settings indicated below. Alternately, a purely custom condi-
tion can be applied to reset trip output latches.
• START TMR Z2PH Inp1 and START TMR Z2PH Inp2: These settings select an operand that will start the phase dis-
tance zone 2 timer to avoid a trip delay if the fault evolves from one type to another type (for example, from a single-
line–to-ground fault to a multi-phase fault) or from one zone of protection to another zone of protection (for example,
from zone 3 to zone 2). For instance, the GND DIST Z2 PKP FlexLogic operand or the PH DIST Z3 PKP FlexLogic oper-
and could be assigned to either of these settings. Use a FlexLogic OR-gate if more than two inputs are required. Refer
to phase distance logic diagrams for additional information.
• START TMR Z2GR Inp1 and START TMR Z2GR Inp2: These settings select an operand that will start the ground dis-
tance zone 2 timer to avoid a trip delay if the fault evolves from one zone of protection to another zone of protection (for
example, from zone 3 to zone 2). For instance, the GND DIST Z3 PKP FlexLogic operand could be assigned to these
settings. Use a FlexLogic OR-gate if more than two inputs are required. Refer to ground distance logic diagrams for
additional information.
• BKR ΦA OPEN, BKR ΦB OPEN, and BKR ΦC OPEN: This settings are used to select an operand to indicates that
phase A, B, or C of the breaker is open, respectively.
• TRIP FORCE 3-POLE: Selects an operand that will force an input selected for single pole operation to produce a three
pole operation. The AR DISABLED FlexLogic operand is the recommended value for this setting. Power system config-
urations or conditions which require such operations may be considered as well.
• TRIP PILOT PRIORITY: This setting is used to set an interval equal to the inter-relay channel communications time,
plus an appropriate margin, during which outputs are not asserted. This delay permits fault identification information
from a remote terminal to be used instead of local data only.
• REVERSE FAULT: This setting should be used to guarantee accuracy of single-pole tripping under evolving external to
internal faults. When a close-in external fault occurs, the relay is biased toward very fast operation on a following inter-
nal fault. This is primarily due to depressed voltages and elevated currents in response to the first, external fault. The
phase selector can exhibit some time lag compared to the main protection elements. This can potentially result in a
spurious three-pole operation on a single-line-to-ground internal fault. Delaying tripping on internal faults that follow
detection of reverse faults solves the problem.
As long as the operand indicated under this setting is asserted the trip action is delayed by TRIP DELAY ON EVOLV
FAULTS time. Typically this operand should combine reverse zone indications (such as zone 4 pickup) with a half-cycle
pickup delay, and two-cycle dropout delay. This setting should be used only in single-pole tripping applications, when
evolving faults are of importance, and slightly delayed operation on evolving faults could be traded for enhanced accu-
racy of single-pole tripping.
• TRIP DELAY ON EVOLV FAULTS: Use this setting in conjunction with the REVERSE FAULT setting (see above). Typi-
cally this value is set around half a power system cycle. Use it only in single-pole tripping applications, when evolving
faults are of importance, and slightly delayed operation on evolving faults could be traded for enhanced accuracy of
single-pole tripping.
6(77,1*
7ULS'HOD\RQ(YROYLQJ)DXOWV
)URPWULSRXWSXWORJLFVKHHW$*
3+$6($ 6
25 )/(;/2*,&23(5$1'
3+$6(%
/DWFK 75,33+$6($
3+$6(&
$1' 5
6(77,1*
7ULS'HOD\RQ(YROYLQJ)DXOWV
6(77,1* 25 6 )/(;/2*,&23(5$1'
5HYHUVH)DXOW
$1' /DWFK 75,33+$6(%
2II
5
6(77,1*
7ULS'HOD\RQ(YROYLQJ)DXOWV
25 6 )/(;/2*,&23(5$1'
/DWFK 75,33+$6(&
)URPWULSRXWSXWORJLF $1'
5
VKHHW$*
3 6 )/(;/2*,&23(5$1'
/DWFK 75,332/(
25 5 25 75,328738723
$1'
6(77,1*
)/(;/2*,&23(5$1'
7ULS6HDO,Q'HOD\ $1'
$1' 75,332/(
;25
25
$1'
7,0(5
)/(;/2*,&23(5$1'
5
$1' 75,3$5,1,732/(
6(77,1* PV
)/(;/2*,&23(5$1'6 7ULS5HVHW
23(132/(,Ů$
25
23(132/(%.5Ů$23
3ROH&XUU25&XVWRP
6(77,1*
&%DX[25&XVWRP $1'
%NU3KDVH$2SHQ 25
2II
&XVWRP
)/(;/2*,&23(5$1'6
23(132/(,Ů%
25
23(132/(%.5Ů%23
3ROH&XUU25&XVWRP
6(77,1*
$1'
%NU3KDVH%2SHQ &%DX[25&XVWRP
25
2II
&XVWRP
)/(;/2*,&23(5$1'6
23(132/(,Ů%
25
23(132/(%.5Ů%23
3ROH&XUU25&XVWRP
6(77,1*
$1'
%NU3KDVH%2SHQ &%DX[25&XVWRP
25
2II
&XVWRP
6(77,1*
7ULS5HFORVH,QSXW
2II
6(77,1* 25
7ULS5HFORVH,QSXW
2II
6(77,1*6
6WDUW7LPHU=3K,Q
2II WRSKDVHGLVWDQFH]RQHORJLF
6WDUW7LPHU=3K,Q 25 )/(;/2*,&23(5$1'
2II $1' 75,3=3+705,1,7
6WDUW7LPHU=*U,Q
WRJURXQGGLVWDQFH]RQHORJLF
2II
)/(;/2*,&23(5$1'
6WDUW7LPHU=*U,Q 25
$1' 75,3=*5705,1,7
2II
)URPWULSRXWSXW
ORJLFVKHHW (1$%/('
$* $&'5
5.7.6 UNDERFREQUENCY
5 MESSAGE
Disabled
SETTING
UNDERFREQ 1 FUNCTION:
Enabled=1
5.7.7 OVERFREQUENCY
SETTING
OVERFREQ 1 FUNCTION:
SETTING
Enabled = 1
OVERFREQ 1 PICKUP : SETTING
SETTING OVERFREQ 1 PICKUP
AND RUN DELAY :
OVERFREQ 1 BLOCK: FLEXLOGIC OPERANDS
OVERFREQ 1 RESET
OVERFREQ 1 PKP
DELAY :
Off = 0 OVERFREQ 1 DPO
tPKP
tRST OVERFREQ 1 OP
SETTING f ≡ PICKUP
OVERFREQ 1 SOURCE:
Frequency 827832A6.CDR
PATH: SETTINGS CONTROL ELEMENTS FREQUENCY RATE OF CHANGE FREQUENCY RATE OF CHANGE 1(4)
5 MESSAGE
DELAY: 0.000 s
FREQ RATE 1 RESET Range: 0 to 65.535 s in steps of 0.001
MESSAGE
DELAY: 0.000 s
FREQ RATE 1 BLOCK: Range: FlexLogic operand
MESSAGE
Off
FREQ RATE 1 TARGET: Range: Self-Reset, Latched, Disabled
MESSAGE
Self-Reset
FREQ RATE 1 EVENTS: Range: Disabled, Enabled
MESSAGE
Disabled
Four independent rate of change of frequency elements are available. The element responds to rate of change of fre-
quency with voltage, current and frequency supervision.
• FREQ RATE 1 TREND: This setting allows configuring the element to respond to increasing or decreasing frequency,
or to frequency change in either direction.
• FREQ RATE 1 PICKUP: This setting specifies an intended df dt pickup threshold. For applications monitoring a
decreasing trend, set FREQ RATE 1 TREND to “Decreasing” and specify the pickup threshold accordingly. The operating
condition is: – df dt Pickup .
For applications monitoring an increasing trend, set FREQ RATE 1 TREND to “Increasing” and specify the pickup thresh-
old accordingly. The operating condition is: df dt Pickup .
For applications monitoring rate of change of frequency in any direction set FREQ RATE 1 TREND to “Bi-Directional” and
specify the pickup threshold accordingly. The operating condition is: abs df dt Pickup
• FREQ RATE 1 OV SUPV PICKUP: This setting defines minimum voltage level required for operation of the element.
The supervising function responds to the positive-sequence voltage. Overvoltage supervision should be used to pre-
vent operation under specific system conditions such as faults.
• FREQ RATE 1 OC SUPV PICKUP: This setting defines minimum current level required for operation of the element.
The supervising function responds to the positive-sequence current. Typical application includes load shedding. Set
the pickup threshold to zero if no overcurrent supervision is required.
• FREQ RATE 1 MIN FREQUENCY: This setting defines minimum frequency level required for operation of the element.
The setting may be used to effectively block the feature based on frequency. For example, if the intent is to monitor an
increasing trend but only if the frequency is already above certain level, this setting should be set to the required fre-
quency level.
• FREQ RATE 1 MAX FREQUENCY: This setting defines maximum frequency level required for operation of the ele-
ment. The setting may be used to effectively block the feature based on frequency. For example, if the intent is to mon-
itor a decreasing trend but only if the frequency is already below certain level (such as for load shedding), this setting
should be set to the required frequency level.
If the signal source assigned to the frequency rate of change element is only set to auxiliary VT, then the minimum
voltage supervision is 3 V.
NOTE
SETTINGS
SETTING
FREQ RATE 1 FUNCTION:
FREQ RATE 1 OV SUPV
Enabled = 1 PICKUP:
AND
RUN
Calculate df/dt
832023A2.CDR
5.7.9 SYNCHROCHECK
5 MESSAGE
SELECT: LV1 and DV2 DV1 Xor DV2, DV1 and DV2
If one or both sources are de-energized, the synchrocheck programming can allow for closing of the circuit breaker using
undervoltage control to by-pass the synchrocheck measurements (dead source function).
• SYNCHK1 V1 SOURCE: This setting selects the source for voltage V1 (see NOTES below).
• SYNCHK1 V2 SOURCE: This setting selects the source for voltage V2, which must not be the same as used for the
V1 (see NOTES below).
• SYNCHK1 MAX VOLT DIFF: This setting selects the maximum primary voltage difference in volts between the two
sources. A primary voltage magnitude difference between the two input voltages below this value is within the permis-
sible limit for synchronism.
• SYNCHK1 MAX ANGLE DIFF: This setting selects the maximum angular difference in degrees between the two
sources. An angular difference between the two input voltage phasors below this value is within the permissible limit
for synchronism.
• SYNCHK1 MAX FREQ DIFF: This setting selects the maximum frequency difference in ‘Hz’ between the two sources.
A frequency difference between the two input voltage systems below this value is within the permissible limit for syn-
chronism.
• SYNCHK1 MAX FREQ HYSTERESIS: This setting specifies the required hysteresis for the maximum frequency differ-
ence condition. The condition becomes satisfied when the frequency difference becomes lower than SYNCHK1 MAX
FREQ DIFF. Once the Synchrocheck element has operated, the frequency difference must increase above the SYNCHK1
MAX FREQ DIFF + SYNCHK1 MAX FREQ HYSTERESIS sum to drop out (assuming the other two conditions, voltage and
angle, remain satisfied).
• SYNCHK1 DEAD SOURCE SELECT: This setting selects the combination of dead and live sources that will by-pass
synchronism check function and permit the breaker to be closed when one or both of the two voltages (V1 or/and V2)
are below the maximum voltage threshold. A dead or live source is declared by monitoring the voltage level. Six
options are available:
None: Dead Source function is disabled
5
LV1 and DV2: Live V1 and Dead V2
DV1 and LV2: Dead V1 and Live V2
DV1 or DV2: Dead V1 or Dead V2
DV1 Xor DV2: Dead V1 exclusive-or Dead V2 (one source is Dead and the other is Live)
DV1 and DV2: Dead V1 and Dead V2
• SYNCHK1 DEAD V1 MAX VOLT: This setting establishes a maximum voltage magnitude for V1 in 1 ‘pu’. Below this
magnitude, the V1 voltage input used for synchrocheck will be considered “Dead” or de-energized.
• SYNCHK1 DEAD V2 MAX VOLT: This setting establishes a maximum voltage magnitude for V2 in ‘pu’. Below this
magnitude, the V2 voltage input used for synchrocheck will be considered “Dead” or de-energized.
• SYNCHK1 LIVE V1 MIN VOLT: This setting establishes a minimum voltage magnitude for V1 in ‘pu’. Above this mag-
nitude, the V1 voltage input used for synchrocheck will be considered “Live” or energized.
• SYNCHK1 LIVE V2 MIN VOLT: This setting establishes a minimum voltage magnitude for V2 in ‘pu’. Above this mag-
nitude, the V2 voltage input used for synchrocheck will be considered “Live” or energized.
NOTES ON THE SYNCHROCHECK FUNCTION:
1. The selected sources for synchrocheck inputs V1 and V2 (which must not be the same source) may include both a
three-phase and an auxiliary voltage. The relay will automatically select the specific voltages to be used by the syn-
chrocheck element in accordance with the following table.
The voltages V1 and V2 will be matched automatically so that the corresponding voltages from the two sources will be
used to measure conditions. A phase to phase voltage will be used if available in both sources; if one or both of the
Sources have only an auxiliary voltage, this voltage will be used. For example, if an auxiliary voltage is programmed to
VAG, the synchrocheck element will automatically select VAG from the other source. If the comparison is required on a
specific voltage, the user can externally connect that specific voltage to auxiliary voltage terminals and then use this
"Auxiliary Voltage" to check the synchronism conditions.
If using a single CT/VT module with both phase voltages and an auxiliary voltage, ensure that only the auxiliary voltage
is programmed in one of the sources to be used for synchrocheck.
Exception: Synchronism cannot be checked between Delta connected phase VTs and a Wye connected auxil-
iary voltage.
NOTE
2. The relay measures frequency and Volts/Hz from an input on a given source with priorities as established by the con-
figuration of input channels to the source. The relay will use the phase channel of a three-phase set of voltages if pro-
grammed as part of that source. The relay will use the auxiliary voltage channel only if that channel is programmed as
part of the Source and a three-phase set is not.
FLEXLOGIC OPERAND
AND SYNC1 V2 ABOVE MIN
FLEXLOGIC OPERAND
AND SYNC1 V1 ABOVE MIN
FLEXLOGIC OPERAND
AND SYNC1 V1 BELOW MAX
Enabled = 1
AND
Block
Off = 0
AND
FLEXLOGIC OPERANDS
AND SYNC1 DEAD S OP
AND SYNC1 DEAD S DPO
SETTING
Dead Source Select FLEXLOGIC OPERANDS
AND OR OR SYNC1 CLS OP
None
LV1 and DV2 SYNC1 CLS DPO
DV1 and LV2
AND
DV1 or DV2
DV1 xor DV2
DV1 and DV2
AND
SETTING
Dead V1 Max Volt
V1 ≤ Maximum
XOR
SETTING
Dead V2 Max Volt
OR
V2 ≤ Maximum
SETTING
5
Live V1 Min Volt
AND
V1 ≥ Minimum
SETTING
Live V2 Min Volt
AND
V2 ≥ Minimum
SETTING
CALCULATE Max Volt Diff
SETTING Magnitude V1 Calculate
ΔV ≤ Maximum
V1 Source Angle Φ1 I V1 – V2 I = ΔV
= SRC 1 Frequency F1 FLEXLOGIC OPERANDS
AND SYNC1 SYNC OP
SETTING
SYNC1 SYNC DPO
Max Angle Diff
Calculate
ΔΦ ≤ Maximum
I Φ1 – Φ2 I = ΔΦ
SETTINGS SYNCHROCHECK 1
CALCULATE Max Freq Diff
SETTING Magnitude V2 Freq Hysteresis
V2 Source Angle Φ2 Calculate
ΔF ≤ Maximum
= SRC 2 Frequency F2 I F1 – F2 I = ΔF
ACTUAL VALUES
Synchrocheck 1 ΔV
Synchrocheck 1 ΔΦ
Synchrocheck 1 ΔF
827076AD.CDR
5.7.10 AUTORECLOSE
5 MESSAGE
Off
AR CLOSE TIME BKR 1: Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
0.10 s
AR BKR MAN CLOSE: Range: FlexLogic operand
MESSAGE
Off
AR BLK TIME UPON MAN Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
CLS: 10.00 s
AR 1P INIT: Range: FlexLogic operand
MESSAGE
Off
AR 3P INIT: Range: FlexLogic operand
MESSAGE
Off
AR 3P TD INIT: Range: FlexLogic operand
MESSAGE
Off
AR MULTI-P FAULT: Range: FlexLogic operand
MESSAGE
Off
BKR ONE POLE OPEN: Range: FlexLogic operand
MESSAGE
Off
BKR 3 POLE OPEN: Range: FlexLogic operand
MESSAGE
Off
AR 3-P DEAD TIME 1: Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
0.50 s
AR 3-P DEAD TIME 2: Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
1.20 s
AR 3-P DEAD TIME 3: Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
2.00 s
The autoreclose scheme is intended for use on transmission lines with circuit breakers operated in both the single pole and
three pole modes, in one or two breaker arrangements. The autoreclose scheme provides four programs with different
operating cycles, depending on the fault type. Each of the four programs can be set to trigger up to four reclosing attempts.
The second, third, and fourth attempts always perform three-pole reclosing and have independent dead time delays.
When used in two breaker applications, the reclosing sequence is selectable. The reclose signal can be sent to one
selected breaker only, to both breakers simultaneously or to both breakers in sequence (one breaker first and then, after a
delay to check that the reclose was successful, to the second breaker). When reclosing in sequence, the first breaker
should reclose with either the single-pole or three-pole dead time according to the fault type and reclose mode; the second
breaker should follow the successful reclosure of the first breaker. When reclosing simultaneously, for the first shot both
breakers should reclose with either the single-pole or three-pole dead time, according to the fault type and the reclose
mode.
The signal used to initiate the autoreclose scheme is the trip output from protection. This signal can be single pole tripping
for single phase faults and three phase tripping for multi-phase faults. The autoreclose scheme has five operating states.
STATE CHARACTERISTICS
Enabled Scheme is permitted to operate
Disabled Scheme is not permitted to operate
Reset Scheme is permitted to operate and shot count is reset to 0
Reclose in progress Scheme has been initiated but the reclose cycle is not finished (successful or not)
Lockout Scheme is not permitted to operate until reset received
AR PROGRAMS:
The autorecloser provides four programs that can cause from one to four reclose attempts (shots). After the first shot, all
subsequent recloses are always be three-pole. If the maximum number of shots selected is “1” (only one reclose attempt)
and the fault is persistent, after the first reclose the scheme goes to lockout upon another Initiate signal.
For the 3-pole reclose programs (modes 3 and 4), an AR FORCE 3-P FlexLogic operand is set. This operand can be used in
connection with the tripping logic to cause a three-pole trip for single-phase faults.
5
Table 5–32: AUTORECLOSE PROGRAMS
MODE AR MODE FIRST SHOT SECOND SHOT THIRD SHOT FOURTH SHOT
SINGLE- MULTI- SINGLE- MULTI- SINGLE- MULTI- SINGLE- MULTI-
PHASE PHASE PHASE PHASE PHASE PHASE PHASE PHASE
FAULT FAULT FAULT FAULT FAULT FAULT FAULT FAULT
1 1 & 3 POLE 1 POLE 3 POLE 3 POLE or 3 POLE or 3 POLE or 3 POLE or 3 POLE or 3 POLE or
LO LO LO LO LO LO
2 1 POLE 1 POLE LO 3 POLE or 3 POLE or 3 POLE or 3 POLE or 3 POLE or 3 POLE or
LO LO LO LO LO LO
3 3 POLE-A 3 POLE LO 3 POLE or LO 3 POLE or LO 3 POLE or LO
LO LO LO
4 3 POLE-B 3 POLE 3 POLE 3 POLE or 3 POLE or 3 POLE or 3 POLE or 3 POLE or 3 POLE or
LO LO LO LO LO LO
EVOLVING FAULTS: 5
1.25 cycles after the single pole dead time has been initiated, the AR FORCE 3P TRIP operand is set and it will be reset only
when the scheme is reset or goes to Lockout. This will ensure that when a fault on one phase evolves to include another
phase during the single pole dead time of the auto-recloser the scheme will force a 3 pole trip and reclose.
RECLOSING SCHEME OPERATION FOR ONE BREAKER:
• Permanent Fault: Consider Mode 1, which calls for 1-Pole or 3-Pole Time Delay 1 for the first reclosure and 3-Pole
Time Delay 2 for the second reclosure, and assume a permanent fault on the line. Also assume the scheme is in the
Reset state. For the first single-phase fault the AR 1-P DEAD TIME timer will be started, while for the first multi-phase fault
the AR 3-P DEAD TIME 1 timer will be started. If the AR 3P TD INIT signal is high, the AR 3-P DEAD TIME 2 will be started for
the first shot.
If AR MAX NO OF SHOTS is set to “1”, upon the first reclose the shot counter is set to 1. Upon reclosing, the fault is again
detected by protection and reclose is initiated. The breaker is tripped three-pole through the AR SHOT COUNT >0 oper-
and that will set the AR FORCE 3P operand. Because the shot counter has reached the maximum number of shots per-
mitted the scheme is sent to the Lockout state.
If AR MAX NO OF SHOTS is set to “2”, upon the first reclose the shot counter is set to 1. Upon reclosing, the fault is again
detected by protection and reclose is initiated. The breaker is tripped three-pole through the AR SHOT COUNT >0 oper-
and that will set the AR FORCE 3P operand. After the second reclose the shot counter is set to 2. Upon reclosing, the
fault is again detected by protection, the breaker is tripped three-pole, and reclose is initiated again. Because the shot
counter has reached the maximum number of shots permitted the scheme is sent to the lockout state.
• Transient Fault: When a reclose output signal is sent to close the breaker the reset timer is started. If the reclosure
sequence is successful (there is no initiating signal and the breaker is closed) the reset timer will time out returning the
scheme to the reset state with the shot counter set to "0" making it ready for a new reclose cycle.
RECLOSING SCHEME OPERATION FOR TWO BREAKERS:
• Permanent Fault: The general method of operation is the same as that outlined for the one breaker applications
except for the following description, which assumes AR BKR SEQUENCE is “1-2” (reclose Breaker 1 before Breaker 2)
The signal output from the dead time timers passes through the breaker selection logic to initiate reclosing of Breaker
1. The Close Breaker 1 signal will initiate the Transfer Timer. After the reclose of the first breaker the fault is again
detected by the protection, the breaker is tripped three pole and the autoreclose scheme is initiated. The Initiate signal
will stop the transfer timer. After the 3-P dead time times out the Close Breaker 1 signal will close first breaker again
and will start the transfer timer. Since the fault is permanent the protection will trip again initiating the autoreclose
scheme that will be sent to Lockout by the SHOT COUNT = MAX signal.
• Transient Fault: When the first reclose output signal is sent to close Breaker 1, the reset timer is started. The close
Breaker 1 signal initiates the transfer timer that times out and sends the close signal to the second breaker. If the reclo-
sure sequence is successful (both breakers closed and there is no initiating signal) the reset timer will time out, return-
ing the scheme to the reset state with the shot counter set to 0. The scheme will be ready for a new reclose cycle.
AR BKR1(2) RECLS FAIL:
If the selected sequence is “1–2” or “2–1” and after the first or second reclose attempt the breaker fails to close, there are
two options. If the AR BKR 1(2) FAIL OPTION is set to “Lockout”, the scheme will go to lockout state. If the AR BKR 1(2) FAIL
OPTION is set to “Continue”, the reclose process will continue with Breaker 2. At the same time the shot counter will be
decreased (since the closing process was not completed).
SCHEME RESET AFTER RECLOSURE:
When a reclose output signal is sent to close either breaker 1 or 2 the reset timer is started. If the reclosure sequence is
successful (there is no initiating signal and the breakers are closed) the reset timer will time out, returning the scheme to
the reset state, with the shot counter set to 0, making it ready for a new reclose cycle.
In two breaker schemes, if one breaker is in the out-of-service state and the other is closed at the end of the reset time, the
scheme will also reset. If at the end of the reset time at least one breaker, which is not in the out-of-service state, is open
the scheme will be sent to Lockout.
The reset timer is stopped if the reclosure sequence is not successful: an initiating signal present or the scheme is in Lock-
out state. The reset timer is also stopped if the breaker is manually closed or the scheme is otherwise reset from lockout.
LOCKOUT:
5 When a reclose sequence is started by an initiate signal the scheme moves into the reclose-in-progress state and starts the
incomplete sequence timer. The setting of this timer determines the maximum time interval allowed for a single reclose
shot. If a close breaker 1 or 2 signal is not present before this time expires, the scheme goes to “Lockout”.
There are four other conditions that can take the scheme to the Lockout state, as shown below:
• Receipt of ‘Block’ input while in the reclose-in-progress state
• The reclosing program logic: when a 3P Initiate is present and the autoreclose mode is either 1 Pole or 3Pole-A (3 pole
autoreclose for single pole faults only)
• Initiation of the scheme when the count is at the maximum allowed
• If at the end of the reset time at least one breaker, which is not in the out-of-service state, is open the scheme will be
sent to Lockout. The scheme will be also sent to Lockout if one breaker fails to reclose and the setting AR BKR FAIL
OPTION is set to “Lockout”.
Once the Lockout state is set it will be latched until one or more of the following occurs:
• The scheme is intentionally reset from Lockout, employing the Reset setting of the Autorecloser;
• The Breaker(s) is(are) manually closed from panel switch, SCADA or other remote control through the AR BRK MAN
CLOSE setting;
USE OF SETTINGS: 5
The single-phase autoreclose settings are described here.
• AR MODE: This setting selects the Autoreclose operating mode from the four available reclose modes (Mode 1: 1 & 3
Pole, Mode 2: 1 Pole, Mode 3: 3 Pole-A and Mode 4: 3 Pole-B), which functions in conjunction with signals received at
the initiation inputs as described previously. The autorecloser runs in this mode until a different mode is activated
through the AR Mode Activation inputs explained as follows.
• MODE 1 to MODE 4 ACTIVATION: This setting selects an operand for activating the corresponding AR mode in run-
time. Mode change via activation input takes place when only one of the four activation inputs is high and the AR RIP
operand is low (that is, reclose is not in progress) and also the mode to be activated is different from the existing mode,
otherwise the activation input is ignored and the existing mode continues to be used. See details in the Mode Control
Logic diagram.
• AR MAX NUMBER OF SHOTS: This setting specifies the number of reclosures that can be attempted before reclo-
sure goes to lockout when the fault is permanent.
• AR INITIATE MODE: This setting selects the autoreclose initiation mode. When selected as “Protection AND CB”, the
autoreclose element is initiated by protection operation and begins incrementing the autoreclose dead time timer when
a circuit breaker is open. Breaker status is determined from breaker auxiliary contacts which should be correctly config-
ured in breaker settings. In “Protection only” initiation mode, the autoreclose element is initiated by protection opera-
tion and begins incrementing the dead time when protection resets, without the need of breaker auxiliary contacts.
• AR BLOCK BKR1: This input selects an operand that will block the reclose command for breaker 1. This condition can
be for example: breaker low air pressure, reclose in progress on another line (for the central breaker in a breaker and
a half arrangement), or a sum of conditions combined in FlexLogic.
• AR CLOSE TIME BKR1:This setting represents the closing time for the breaker 1 from the moment the “Close” com-
mand is sent to the moment the contacts are closed.
• AR BKR MAN CLOSE: This setting selects a FlexLogic operand that represents manual close command to a breaker
associated with the autoreclose scheme.
• AR BLK TIME UPON MAN CLS: The autoreclose scheme can be disabled for a programmable time delay after an
associated circuit breaker is manually commanded to close, preventing reclosing onto an existing fault such as
grounds on the line. This delay must be longer than the slowest expected trip from any protection not blocked after
manual closing. If the autoreclose scheme is not initiated after a manual close and this time expires the autoreclose
scheme is set to the reset state.
• AR 1P INIT: This setting selects a FlexLogic operand that is intended to initiate single-pole autoreclosure.
• AR 3P INIT: This setting selects a FlexLogic operand that is intended to initiate three-pole autoreclosure, first timer (AR
3P DEAD TIME 1) that can be used for a high-speed autoreclosure.
• AR 3P TD INIT: This setting selects a FlexLogic operand intended to initiate three-pole autoreclosure. second timer
(AR 3P DEAD TIME 2) can be used for a time-delay autoreclosure. If the operand assigned to this setting and the AR 3P
INIT setting are asserted simultaneously, then autoreclose will not activate the first and second shot timers at the same
time. Instead, the priority is given to the AR 3P INIT operand.
• AR MULTI-P FAULT: This setting selects a FlexLogic operand that indicates a multi-phase fault. The operand value
should be zero for single-phase to ground faults.
• BKR ONE POLE OPEN: This setting selects a FlexLogic operand which indicates that the breaker has opened cor-
rectly following a single phase to ground fault and the autoreclose scheme can start timing the single pole dead time
(for 1-2 reclose sequence for example, breaker 1 should trip single pole and breaker 2 should trip 3 pole).
The scheme has a pre-wired input that indicates breaker status.
• BKR 3 POLE OPEN: This setting selects a FlexLogic operand which indicates that the breaker has opened three pole
and the autoreclose scheme can start timing the three pole dead time. The scheme has a pre-wired input that indicates
breaker status.
• AR 3-P DEAD TIME 1: This is the dead time following the first three pole trip. This intentional delay can be used for a
high-speed three-pole autoreclose. However, it should be set longer than the estimated de-ionizing time following the
three-pole trip.
5 • AR 3-P DEAD TIME 2: This is the dead time following the second three-pole trip or initiated by the AR 3P TD INIT input.
This intentional delay is typically used for a time delayed three-pole autoreclose (as opposed to high speed three-pole
autoreclose).
• AR 3-P DEAD TIME 3: This setting represents the dead time following the third three-pole trip.
• AR 3-P DEAD TIME 4: This setting represents the dead time following the third three-pole trip.
• AR EXTEND DEAD T 1: This setting selects an operand that will adapt the duration of the dead time for the first shot
to the possibility of non-simultaneous tripping at the two line ends. Typically this is the operand set when the communi-
cation channel is out of service
• AR DEAD TIME 1 EXTENSION: This timer is used to set the length of the dead time 1 extension for possible non-
simultaneous tripping of the two ends of the line.
• AR RESET: This setting selects the operand that forces the autoreclose scheme from any state to reset. Typically this
is a manual reset from lockout, local or remote.
• AR RESET TIME: A reset timer output resets the recloser following a successful reclosure sequence. The setting is
based on the breaker time which is the minimum time required between successive reclose sequences.
• AR BKR CLOSED: This setting selects an operand that indicates that the breakers are closed at the end of the reset
time and the scheme can reset.
• AR BLOCK: This setting selects the operand that blocks the autoreclose scheme (it can be a sum of conditions such
as: time delayed tripping, breaker failure, bus differential protection, etc.). If the block signal is present before autore-
close scheme initiation the AR DISABLED FlexLogic operand will be set. If the block signal occurs when the scheme is
in the RIP state the scheme will be sent to lockout.
• AR PAUSE: The pause input offers the ability to freeze the autoreclose cycle until the pause signal disappears. This
may be done when a trip occurs and simultaneously or previously, some conditions are detected such as out-of step or
loss of guard frequency, or a remote transfer trip signal is received. When the pause signal disappears the autoreclose
cycle is resumed. This feature can also be used when a transformer is tapped from the protected line and a reclose is
not desirable until it is disconnected from the line. In this situation, the reclose scheme is paused until the transformer
is disconnected.
• AR INCOMPLETE SEQ TIME: This timer is used to set the maximum time interval allowed for a single reclose shot. It
is started whenever a reclosure is initiated and is active until the CLOSE BKR1 or CLOSE BKR2 signal is sent. If all con-
ditions allowing a breaker closure are not satisfied when this time expires, the scheme goes to “Lockout”. The mini-
mum permissible setting is established by the AR 3-P DEAD TIME 2 timer setting. Settings beyond this will determine the
wait time for the breaker to open so that the reclose cycle can continue and/or for the AR PAUSE signal to reset and
allow the reclose cycle to continue and/or for the AR BKR1 BLK signal to disappear and allow the AR CLOSE BKR1 signal
to be sent.
• AR BLOCK BKR2: This input selects an operand that will block the reclose command for breaker 2. This condition can
be for example: breaker low air pressure, reclose in progress on another line (for the central breaker in a breaker and
a half arrangement), or a sum of conditions combined in FlexLogic.
• AR CLOSE TIME BKR2: This setting represents the closing time for the breaker 2 from the moment the ‘Close’ com-
mand is sent to the moment the contacts are closed.
• AR TRANSFER 1 TO 2: This setting establishes how the scheme performs when the breaker closing sequence is 1-2
and breaker 1 is blocked. When set to “Yes” the closing command will be transferred direct to breaker 2 without waiting
the transfer time. When set to “No” the closing command will be blocked by the AR BKR1 BLK signal and the scheme
will be sent to lockout by the incomplete sequence timer.
• AR TRANSFER 2 TO 1: This setting establishes how the scheme performs when the breaker closing sequence is 2-1
and breaker 2 is blocked. When set to “Yes” the closing command will be transferred direct to breaker 1 without waiting
the transfer time. When set to “No”, the closing command will be blocked by the AR BKR2 BLK signal and the scheme
will be sent to lockout by the incomplete sequence timer.
• AR BKR1 FAIL OPTION: This setting establishes how the scheme performs when the breaker closing sequence is 1-
2 and Breaker 1 has failed to close. When set to “Continue” the closing command will be transferred to breaker 2 which
will continue the reclosing cycle until successful (the scheme will reset) or unsuccessful (the scheme will go to Lock-
out). When set to “Lockout” the scheme will go to lockout without attempting to reclose breaker 2.
• AR BKR2 FAIL OPTION: This setting establishes how the scheme performs when the breaker closing sequence is 2-
1 and Breaker 2 has failed to close. When set to “Continue” the closing command will be transferred to breaker 1 which
will continue the reclosing cycle until successful (the scheme will reset) or unsuccessful (the scheme will go to Lock- 5
out). When set to “Lockout” the scheme will go to lockout without attempting to reclose breaker 1.
• AR 1-P DEAD TIME: Set this intentional delay longer than the estimated de-ionizing time after the first single-pole trip.
• AR BREAKER SEQUENCE: This setting selects the breakers reclose sequence: Select “1” for reclose breaker 1 only,
“2” for reclose breaker 2 only, “1&2” for reclose both breakers simultaneously, “1-2” for reclose breakers sequentially;
Breaker 1 first, and “2-1” for reclose breakers sequentially; Breaker 2 first.
• AR TRANSFER TIME: The transfer time is used only for breaker closing sequence 1-2 or 2-1, when the two breakers
are reclosed sequentially. The transfer timer is initiated by a close signal to the first breaker. The transfer timer trans-
fers the reclose signal from the breaker selected to close first to the second breaker. The time delay setting is based on
the maximum time interval between the autoreclose signal and the protection trip contact closure assuming a perma-
nent fault (unsuccessful reclose). Therefore, the minimum setting is equal to the maximum breaker closing time plus
the maximum line protection operating time plus a suitable margin. This setting will prevent the autoreclose scheme
from transferring the close signal to the second breaker unless a successful reclose of the first breaker occurs.
• AR BUS FLT INIT: This setting is used in breaker-and-a-half applications to allow the autoreclose control function to
perform reclosing with only one breaker previously opened by bus protection. For line faults, both breakers must open
for the autoreclose reclosing cycles to take effect.
The active AR mode is memorized (latched) on power cycling. This means that the relay uses the last-used mode on
power-up. The AR mode resets to the default mode (specified by the AR MODE setting) when any settings in the autore-
close function are changed.
Figure 5–144: MODE CONTROL LOGIC
Multiple (>1)
inputs are
high
FLEXLOGIC OPERAND
OR
AR MODE SWITCH FAIL
AND
FLEXLOGIC OPERAND
AR MODE =1
FLEXLOGIC OPERAND AR MODE =2
AR RIP AR MODE =3
AR MODE =4
SETTING
Only 1
out of 4 AR M0DE:
SETTING
is high Mode 1: 1 & 3 Pole Current AR Mode
AR Mode Activation AND Mode 2: 1 Pole
b=1….4
Mode 1: Off = 0 Mode 3: 3 Pole - A
Mode 2: Off = 0 Mode to be activated Mode 4: 3 Pole -B
Switch to
Mode 3: Off = 0 a=1….4 a new mode
1 if a ≠ b
Mode 4: Off = 0 Note: only one mode can =
0 otherwise
be activated at a time. b
Simultaneous multiple
modes activation will be
ignored. 427248A1.vsd
In addition, the current AR mode is available as FlexLogic Operands because AR Mode equals to 1, 2, 3, and 4 respec-
tively so that it can be monitored and logged.
}
FLEXLOGIC OPERAND OR
}
BKR 2 MNL OPEN
1
2
From sheet 2 1&2
1-2
2-1
OR
}
AND
FLEXLOGIC OPERAND
BREAKER 1 MNL CLS
OR
AND
FLEXLOGIC OPERAND
BREAKER 2 MNL CLS
FLEXLOGIC OPERAND
AND
BREAKER 1 CLOSED
FLEXLOGIC OPERAND
AND
BREAKER 2 CLOSED
AND
BKR CLOSED
5
OR (To sheet 1 and 2)
OR
From
Breaker Control
scheme
AND
AND
FLEXLOGIC OPERAND
AND
BREAKER 1 OPEN
OR
FLEXLOGIC OPERAND
AND
BREAKER 2 OPEN
OR BKR 3 POLE OPEN
(To sheet 1)
OR
FLEXLOGIC OPERAND AND
BUS-FLT INIT
OR AND
OFF = 0
AND
AND
FLEXLOGIC OPERAND
AND
BREAKER 1 ONE P OPEN
OR
FLEXLOGIC OPERAND
AND
BREAKER 2 ONE P OPEN
OR
OR
AND
OR
AND
827833AA.CDR
5-276
1ST SHOT 2ND SHOT
F R
A T PROT E
T
U R T TRIP BKR S
L I T PROT RESET E
T P T
5.7 CONTROL ELEMENTS
PREFAULT
AR 1P INIT
AR RIP
1-P DEAD TIME
AR 1-P RIP
1.25 cycle
AR FORCE 3P TRIP
CLOSE
AR CLOSE BKR1
T CLOSE BKR1 T CLOSE BKR1
AR RESET TIME
RESET TIME
BREAKER 1 CLOSED
T TRIP BKR T PROT RESET
T PROT
AR 3P INIT
3-P/2 DEAD TIME
BREAKER 2 CLOSED
AR TRANSFER TIME
GE Multilin
5 SETTINGS 5.7 CONTROL ELEMENTS
As long as the current through the voltage monitor is above a threshold (see technical specifications for form-A), the “Cont
Op 1 VOn” FlexLogic operand will be set (for contact input 1 – corresponding operands exist for each contact output). If the
output circuit has a high resistance or the DC current is interrupted, the trickle current will drop below the threshold and the
“Cont Op 1 VOff” FlexLogic operand will be set. Consequently, the state of these operands can be used as indicators of the
integrity of the circuits in which form-A contacts are inserted.
EXAMPLE 1: BREAKER TRIP CIRCUIT INTEGRITY MONITORING
In many applications it is desired to monitor the breaker trip circuit integrity so problems can be detected before a trip oper-
ation is required. The circuit is considered to be healthy when the voltage monitor connected across the trip output contact
detects a low level of current, well below the operating current of the breaker trip coil. If the circuit presents a high resis-
tance, the trickle current will fall below the monitor threshold and an alarm would be declared.
In most breaker control circuits, the trip coil is connected in series with a breaker auxiliary contact which is open when the
breaker is open (see diagram below). To prevent unwanted alarms in this situation, the trip circuit monitoring logic must
include the breaker position.
85VHULHVGHYLFH
ZLWKIRUP$FRQWDFWV
+D
,
+E '&²
9 '&
+F D 7ULSFRLO
5
, FXUUHQWPRQLWRU
9 YROWDJHPRQLWRU $&'5
The PICKUP DELAY setting should be greater than the operating time of the breaker to avoid nuisance alarms.
NOTE
85VHULHVGHYLFH
ZLWKIRUP$FRQWDFWV
+D
9DOXHVIRUUHVLVWRU´5µ 5
3RZHUVXSSO\ 5HVLVWDQFH 3RZHU
,
9'& ű :
+E '&² 9'& ű :
9'& ű :
9 '&
9'& ű :
+F D 7ULSFRLO
9'& ű :
5
9'& ű :
%\SDVV
, FXUUHQWPRQLWRU UHVLVWRU
9 YROWDJHPRQLWRU $&'5
5 MESSAGE
Off
COUNTER 1 RESET: Range: FlexLogic operand
MESSAGE
Off
COUNT1 FREEZE/RESET: Range: FlexLogic operand
MESSAGE
Off
COUNT1 FREEZE/COUNT: Range: FlexLogic operand
MESSAGE
Off
There are 8 identical digital counters, numbered from 1 to 8. A digital counter counts the number of state transitions from
Logic 0 to Logic 1. The counter is used to count operations such as the pickups of an element, the changes of state of an
external contact (e.g. breaker auxiliary switch), or pulses from a watt-hour meter.
• COUNTER 1 UNITS: Assigns a label to identify the unit of measure pertaining to the digital transitions to be counted.
The units label will appear in the corresponding actual values status.
• COUNTER 1 PRESET: Sets the count to a required preset value before counting operations begin, as in the case
where a substitute relay is to be installed in place of an in-service relay, or while the counter is running.
• COUNTER 1 COMPARE: Sets the value to which the accumulated count value is compared. Three FlexLogic output
operands are provided to indicate if the present value is ‘more than (HI)’, ‘equal to (EQL)’, or ‘less than (LO)’ the set
value.
• COUNTER 1 UP: Selects the FlexLogic operand for incrementing the counter. If an enabled UP input is received when
the accumulated value is at the limit of +2,147,483,647 counts, the counter will rollover to –2,147,483,648.
• COUNTER 1 DOWN: Selects the FlexLogic operand for decrementing the counter. If an enabled DOWN input is
received when the accumulated value is at the limit of –2,147,483,648 counts, the counter will rollover to
+2,147,483,647.
• COUNTER 1 BLOCK: Selects the FlexLogic operand for blocking the counting operation. All counter operands are
blocked.
• CNT1 SET TO PRESET: Selects the FlexLogic operand used to set the count to the preset value. The counter will be
set to the preset value in the following situations:
1. When the counter is enabled and the CNT1 SET TO PRESET operand has the value 1 (when the counter is enabled
and CNT1 SET TO PRESET operand is 0, the counter will be set to 0).
2. When the counter is running and the CNT1 SET TO PRESET operand changes the state from 0 to 1 (CNT1 SET TO
PRESET changing from 1 to 0 while the counter is running has no effect on the count).
3. When a reset or reset/freeze command is sent to the counter and the CNT1 SET TO PRESET operand has the value
1 (when a reset or reset/freeze command is sent to the counter and the CNT1 SET TO PRESET operand has the
value 0, the counter will be set to 0).
• COUNTER 1 RESET: Selects the FlexLogic operand for setting the count to either “0” or the preset value depending
on the state of the CNT1 SET TO PRESET operand.
• COUNTER 1 FREEZE/RESET: Selects the FlexLogic operand for capturing (freezing) the accumulated count value
into a separate register with the date and time of the operation, and resetting the count to “0”.
• COUNTER 1 FREEZE/COUNT: Selects the FlexLogic operand for capturing (freezing) the accumulated count value
into a separate register with the date and time of the operation, and continuing counting. The present accumulated
value and captured frozen value with the associated date/time stamp are available as actual values. If control power is
interrupted, the accumulated and frozen values are saved into non-volatile memory during the power down operation.
SETTING
COUNTER 1 FUNCTION:
Disabled = 0
SETTINGS
Enabled = 1
COUNTER 1 NAME:
SETTING
COUNTER 1 UP:
AND COUNTER 1 UNITS:
COUNTER 1 PRESET:
RUN
5
Off = 0 SETTING
FLEXLOGIC
COUNTER 1 COMPARE: OPERANDS
SETTING
CALCULATE Count more than Comp. COUNTER 1 HI
COUNTER 1 DOWN: VALUE Count equal to Comp. COUNTER 1 EQL
Off = 0 Count less than Comp. COUNTER 1 LO
SETTING
COUNTER 1 BLOCK:
Off = 0 SET TO PRESET VALUE
a) MAIN MENU
PATH: SETTINGS CONTROL ELEMENTS MONITORING ELEMENTS
MONITORING BREAKER 1
See below.
ELEMENTS ARCING CURRENT
BREAKER 2
MESSAGE See below.
ARCING CURRENT
BREAKER
MESSAGE See page 5–285.
FLASHOVER 1
BREAKER
MESSAGE See page 5–285.
FLASHOVER 2
BREAKER RESTRIKE 1
MESSAGE See page 5–289.
BREAKER RESTRIKE 2
MESSAGE See page 5–289.
VT FUSE FAILURE 1
MESSAGE See page 5–292.
VT FUSE FAILURE 2
MESSAGE See page 5–292.
5 MESSAGE
VT FUSE FAILURE 3
See page 5–292.
VT FUSE FAILURE 4
MESSAGE See page 5–292.
OPEN POLE
MESSAGE See page 5–294.
BROKEN CONDUCTOR 1
MESSAGE See page 5–297.
BROKEN CONDUCTOR 2
MESSAGE See page 5–297.
THERMAL OVERLOAD
MESSAGE See page 5–299.
PROTECTION
There is one breaker arcing current element available per CT bank, with a minimum of two elements. This element calcu-
lates an estimate of the per-phase wear on the breaker contacts by measuring and integrating the current squared passing
through the breaker contacts as an arc. These per-phase values are added to accumulated totals for each phase and com-
pared to a programmed threshold value. When the threshold is exceeded in any phase, the relay can set an output operand
to “1”. The accumulated value for each phase can be displayed as an actual value.
The operation of the scheme is shown in the following logic diagram. The same output operand that is selected to operate
the output relay used to trip the breaker, indicating a tripping sequence has begun, is used to initiate this feature. A time
delay is introduced between initiation and the starting of integration to prevent integration of current flow through the
breaker before the contacts have parted. This interval includes the operating time of the output relay, any other auxiliary
relays and the breaker mechanism. For maximum measurement accuracy, the interval between change-of-state of the
operand (from 0 to 1) and contact separation should be measured for the specific installation. Integration of the measured
current continues for 100 ms, which is expected to include the total arcing period.
The feature is programmed to perform fault duration calculations. Fault duration is defined as a time between operation of
the disturbance detector occurring before initiation of this feature, and reset of an internal low-set overcurrent function. Cor-
rection is implemented to account for a non-zero reset time of the overcurrent function.
Breaker arcing currents and fault duration values are available under the ACTUAL VALUES RECORDS MAINTENANCE
BREAKER 1(4) menus.
• BKR 1 ARC AMP INT-A(C): Select the same output operands that are configured to operate the output relays used to
trip the breaker. In three-pole tripping applications, the same operand should be configured to initiate arcing current
calculations for poles A, B and C of the breaker. In single-pole tripping applications, per-pole tripping operands should
be configured to initiate the calculations for the poles that are actually tripped.
• BKR 1 ARC AMP DELAY: This setting is used to program the delay interval between the time the tripping sequence is
initiated and the time the breaker contacts are expected to part, starting the integration of the measured current.
• BKR 1 ARC AMP LIMIT: Selects the threshold value above which the output operand is set.
Breaker
Contacts Arc
Initiate Part Extinguished
Total Area =
Breaker
Arcing
Current
(kA·cycle)
Programmable
Start Delay 100 ms
Start Stop
Integration Integration
SETTING
AND
BREAKER 1 ARCING
SETTING
AMP FUNCTION:
Enabled=1 BREAKER 1 ARCING
AMP DELAY: 100 ms
SETTING OR 0 0
BREAKER 1 ARCING
AMP BLOCK:
Off=0
5 SETTINGS
BREAKER 1 ARCING
AMP INIT-A:
AND
Off=0
BREAKER 1 ARCING
AMP INIT-B:
Off=0 OR
BREAKER 1 ARCING
AMP INIT-C:
Off=0
AND RUN
SETTING Integrate
BREAKER 1 ARCING Add to SETTING
AMP SOURCE: AND RUN Accumulator BREAKER 1 ARCING
IA IA 2-Cycle Select
AMP LIMIT: FLEXLOGIC OPERANDS
2
IB Integrate IB 2-Cycle Highest KA * Cycle Limit BKR1 ARC OP
IC IC 2-Cycle Value BKR1 ARC DPO
AND RUN
COMMAND
c) BREAKER FLASHOVER
PATH: SETTINGS CONTROL ELEMENTS MONITORING ELEMENTS BREAKER FLASHOVER 1(4)
Bus
CTs Breaker
Line/Feeder
5 Bus VTs
842746A1.CDR
The source 1 (SRC1) phase currents are feeder CTs and phase voltages are bus VTs, and Contact Input 1 is set as Breaker
52a contact. The conditions prior to flashover detection are:
1. 52a status = 0.
2. VAg, VBg, or VCg is greater than the pickup setting.
3. IA, IB, IC = 0; no current flows through the breaker.
4. VA is greater than pickup (not applicable in this scheme).
The conditions at flashover detection are:
1. 52a status = 0.
2. IA, IB, or IC is greater than the pickup current flowing through the breaker.
3. VA is greater than pickup (not applicable in this scheme).
SIX VT BREAKER FLASHOVER APPLICATION
The per-phase voltage difference approaches zero when the breaker is closed. The is well below any typical minimum
pickup voltage. Select the level of the BRK 1 FLSHOVR DIFF V PKP setting to be less than the voltage difference measured
across the breaker when the close or open breaker resistors are left in service. Prior to flashover, the voltage difference is
larger than BRK 1 FLSHOVR DIFF V PKP. This applies to either the difference between two live voltages per phase or when the
voltage from one side of the breaker has dropped to zero (line de-energized), at least one per-phase voltage is larger than
the BRK 1 FLSHOVR V PKP setting, and no current flows through the breaker poles. During breaker flashover, the per-phase
voltages from both sides of the breaker drops below the pickup value defined by the BRK 1 FLSHOVR V PKP setting, the volt-
age difference drops below the pickup setting, and flashover current is detected. These flashover conditions initiate Flex-
Logic pickup operands and start the BRK 1 FLSHOVR PKP DELAY timer.
This application does not require detection of breaker status via a 52a contact, as it uses a voltage difference larger than
the BRK 1 FLSHOVR DIFF V PKP setting. However, monitoring the breaker contact will ensure scheme stability.
Bus
CTs Breaker
Line/Feeder
VTs
VTs
842745A1.CDR
The source 1 (SRC1) phase currents are CTs and phase voltages are bus VTs. The source 2 (SRC2) phase voltages are
line VTs. Contact input 1 is set as the breaker 52a contact (optional).
The conditions prior to flashover detection are:
1. VA is greater than pickup
2. IA, IB, IC = 0; no current flows through the breaker
3. 52a status = 0 (optional)
The conditions at flashover detection are:
1. VA is less than pickup
2. VAg, VBg, or VCg is lower than the pickup setting
3. IA, IB, or IC is greater than the pickup current flowing through the breaker
4. 52a status = 0 (optional)
5
The element is operational only when phase-to-ground voltages are connected to relay terminals. The flashover
element will not operate if delta voltages are applied.
NOTE
elements, breaker failure, and close and trip commands. A six-cycle time delay applies after the selected FlexLogic
operand resets.
• BRK FLSHOVR PKP DELAY: This setting specifies the time delay to operate after a pickup condition is detected.
SETTINGS
Phase B logic
RESET
SETTINGS
5 cycle
BRK 1 STATUS CLSD A:
0 OR
SET SETTING
RUN dominant
BRK 1 FLSHOVR PKP
FlexLogic operand: On=1
DELAY:
FLEXLOGIC OPERANDS
BRK 1 STATUS CLSD B: Phase B tPKP
logic 0 BRK 1 FLSHOVR OP A
RUN
FLEXLOGIC OPERAND
FlexLogic operand: On=1
Phase B logic BRK 1 FLSHOVR OP B OR BRK 1 FLSHOVR OP
BRK 1 STATUS CLSD C: Phase C RESET
logic OR Phase C logic BRK 1 FLSHOVR OP C
SETTINGS RUN
BRK 1 FLSHOVR SIDE 1 FlexLogic operand: On=1
SRC:
SRC 1, SRC 2, … , SRC 6 SETTING
VA
BRK 1 FLSHOVR AMP PKP:
VB
VC RUN
IA IA > PKP
IB
AND
IC
5
SETTINGS
SETTING
BRK 1 FLSHOVR SIDE 2
SRC: BRK 1 FLSHOVR DIFF V
PKP:
SRC 1, SRC 2, … , SRC 6, none
RUN
Va ΔVA > PKP
ΔVA = | VA - Va |
Vb
Vc 842018A2.CDR
d) BREAKER RESTRIKE
PATH: SETTINGS CONTROL ELEMENTS MONITORING ELEMENTS BREAKER RESTRIKE 1(2)
According to IEEE standard C37.100: IEEE Standard Definitions for Power Switchgear, restrike is defined as “a resumption
of current between the contacts of a switching device during an opening operation after an interval of zero current of
¼ cycle at normal frequency or longer”.
10
8
6
4
current (amps)
2
0.01 0.03
0 time (ms)
0.02 0.05
–2
–4
–6
–8
OPERATE
–10
834764A1.CDR
Breaker open
command or breaker
open state
Capacitor bank
offline
Breaker
close
Current
Capacitor bank
interruption
Breaker online
(overcurrent)
close
High-frequency
elevated current Breaker close
Current
interruption
5 (overcurrent)
Restrike detected:
OP state asserted
834768A1.CDR
SETTING
BREAKER RESTRIKE 1
FUNCTION
= Enabled
SETTING AND
BKR RSTR 1 BLK
= Off SETTING SETTING
BREAKER RESTRIKE 1 PICKUP BREAKER RESTRIKE 1
RUN RESET DELAY
SETTING 0
BREAKER RESTRIKE 1 RUN Restrike detection logic
SOURCE ARMED TRST
Current interruption
= IA detection logic 0
FLEXLOGIC OPERANDS
= IB
Imag < 0.05 pu TRST BKR RESTRIKE 1 OP A
= IC
for t > ¼ cycle 0 BKR RESTRIKE 1 OP B
BKR RESTRIKE 1 OP C
SETTING RESET TRST
BKR RSTR 1 BKR OPEN
= Off
FLEXLOGIC OPERAND
OR BKR RESTRIKE 1 OP
SETTING OR
BKR RSTR 1 OPEN CMD
= Off
AND
SETTING
BKR RSTR 1 CLS CMD
= Off 834012A1.CDR
e) VT FUSE FAILURE
PATH: SETTINGS CONTROL ELEMENTS MONITORING ELEMENTS VT FUSE FAILURE 1(4)
OR 30 cycles
RESET
0
AND Reset-dominant
FLEXLOGIC OPERAND
AND SRC1 VT FUSE FAIL VOL LOSS
SETTING
AND
TIMER
5 cycles
5
3 HARM PKP
0
AND Run FLEXLOGIC OPERAND
SETTING 3V_0 3rd Harm >setting OR SRC1 VT NEU WIRE OPEN
TIMER
Neutral Wire Open Detect
0
Enabled = 1
AND 20 cycles
SOURCE 1 FLEX-ANALOG
3V_0 (3rd Harmonic) SRC1 3V0 3nd Harmonic
827093AQ.CDR
The open pole detector is intended to identify an open pole of the line circuit breaker. The scheme monitors the breakers
auxiliary contacts, current in the circuit and optionally voltage on the line. The scheme generates output operands used to
block the phase selector and some specific protection elements, thus preventing maloperation during the dead time of a
single-pole autoreclose cycle or any other open pole conditions.
The scheme declares an open pole at the moment a single-pole trip is issued.
In two-breaker and breaker-and-a-half applications, an open pole condition is declared when one or more of the following
hold:
• Both breakers have an open pole on the same phase.
• The current on the line drops below a threshold.
• The current and voltage on the line drop below a threshold.
The open pole feature uses signals defined by the GROUPED ELEMENTS SETTING GROUP 1(6) DISTANCE DISTANCE
SOURCE setting. Voltage supervision can be used only with wye VTs on the line side of the breaker.
The OPEN POLE CURRENT PICKUP setting establishes the current threshold below which an open pole is declared.
The OPEN POLE LINE XC1 setting specifies positive-sequence reactance of the entire line. If shunt reactors are applied, this
value should be a net capacitive reactance of the line and the reactors installed between the line breakers. The value is
entered in secondary ohms. This setting is relevant if open pole condition at the remote end of the line is to be sensed and
utilized by the relay.
The OPEN POLE LINE XC0 setting specifies zero-sequence reactance of the entire line. If shunt reactors are applied, this
value should be a net capacitive reactance of the line and the reactors installed between the line breakers. The value shall
be entered in secondary ohms. This setting is relevant if open pole condition at the remote end of the line is to be sensed
and utilized by the relay (OPEN POLE REM OP FlexLogic operand).
The OPEN POLE REM CURR PKP setting specifies pickup level for the remote-end current estimated by the relay as the local
current compensated by the calculated charging current. The latter is calculated based on the local voltages and the capac-
itive reactances of the line. This setting is relevant if open pole condition at the remote end of the line is to be sensed and
utilized by the relay (OPEN POLE REM OP FlexLogic operand).
The OPEN POLE MODE setting selects the mode of operation of the open pole function. When the “Accelerated” mode is cho-
sen, an open pole will be declared ½ cycle after trip output operation and before the breaker pole opens. This blocks dis-
tance loops involved in the faulted phase and phase selector, and arms the trip output to produce three-pole trip for the next
fault. If the fault evolves into multi-phase fault before breaker pole opens for the first fault, the remaining in-service distance
loops would initiate a three-pole trip. When the “Traditional” mode is selected, then an open pole is declared only after the
breaker opens and current disappears. If the fault evolves into a multi-phase fault before the circuit breaker pole opens for
the first fault, the phase selector will change the fault type from a single-line-to-ground fault to a multi-phase fault, thereby
initiating a three-pole trip.
The OPEN POLE DETECTION setting selects the signals used to detect an open pole condition. When “I AND V AND CBaux”
value is selected, the breaker 52 contacts and the current with optional voltage signals are used to determine open pole
conditions. For the “I AND V only” selection, only the current with optional voltage signals are used.
For convenience, the position of the breaker poles defined in the breaker control feature and available as FlexLogic oper-
and BREAKER 1 ΦA CLSD through BREAKER 1 ΦC CLSD and BREAKER 1 OOS are used by the open pole feature if the “I AND
V AND CBaux” detection value is selected.
For correct operation of the open pole detector, the breaker control, trip output, and single-pole autoreclose features must
be enabled and configured properly. When used in configuration with only one breaker, the BREAKER 2 FUNCTION should be
“Enabled” and the BREAKER 2 OUT OF SV setting should be “On” (refer to the Breaker Control section earlier in this chapter
for additional details).
To distinguish between single-phase disappearance and system disturbance in all three phases (such as load change,
switching, etc.), the broken conductor element monitors the change in all three phase currents at the present instance and
at four cycles previous. It also monitors changes in the I_2 / I_1 ratio, I_1 minimum, and I_1 maximum.
The broken conductor function should not be used to respond to fault transients and single-pole tripping/reclosing condi-
tions. Therefore, the time delay should be programmed to a sufficient length to ensure coordination with the breaker dead
time of the recloser function.
• BROKEN CONDUCTOR 1 FUNCTION: This setting enables and disables the broken conductor function.
• BROKEN CONDUCTOR 1 SOURCE: This setting selects a signal source used to provide three-phase current inputs
to this function.
• BROKEN CONDUCTOR 1 I2/I1 RATIO: This setting specifies the ratio of negative-sequence current to positive-
sequence current. When one phase conductor is broken, the I_2 / I_1 ratio with a balanced remaining two phases is
50%. So normally this setting should be set below 50% (for example, to 30%).
• BROKEN CONDUCTOR 1 I1 MIN: This setting specifies the minimum positive-sequence current supervision level.
Ensure this setting is programmed to a sufficient level to prevent I_2 / I_1 from erratic pickup due to a low I_1 signal.
However, this setting should not be set too high, since the broken conductor condition cannot be detected under light
load conditions when I_1 is less than the value specified by this setting.
• BROKEN CONDUCTOR 1 I1 MAX: This setting specifies the maximum I_1 level allowed for the broken conductor
function to operate. When I_1 exceeds this setting, this it is considered a fault. This broken conductor function should
not respond to any fault conditions, so normally this setting is programmed to less than the maximum load current.
• BROKEN CONDUCTOR 1 PKP DELAY: This setting specifies the pickup time delay for this function to operate after
assertion of the broken conductor pickup FlexLogic operand.
5 SETTINGS
BROKEN CONDUCTOR 1
FUNCTION:
Enabled = 1
AND
AND
Ib | Ib | < I1 MIN
0
Ic | Ic | < I1 MIN
| Ia’ | - | Ia | > 0.05pu
| Ib’ | - | Ib | > 0.05pu
2 cyc
AND
OR
FLEXLOGIC OPERAND
BROKEN CONDUCT 1 PKP
AND
The thermal overload protection element corresponds to the IEC 255-8 standard and is used to detect thermal overload
conditions in protected power system elements. Choosing an appropriate time constant element can be used to protect dif-
ferent elements of the power system. The cold curve characteristic is applied when the previous averaged load current over
the last 5 cycles is less than 10% of the base current. If this current is greater or equal than 10% than the base current, then
the hot curve characteristic is applied.
The IEC255-8 cold curve is defined as follows:
2
I
t op = op ln -------------------------
2
-
2
(EQ 5.27)
I – kI B
The reset time of the thermal overload protection element is also time delayed using following formula:
2
kI B
t rst = rst ln ----------------------------
2 2
- + T min (EQ 5.29)
I – kI B
7PLQ
ƌUVW
ƌRS
5
W PLQ
,,SNS
$&'5
When current is less than the dropout level, In > 0.97 × k × IB, the element starts decreasing the thermal energy:
t
E n = E n – 1 – --------------- (EQ 5.31)
t rst In
The logic for the thermal overload protection element is shown below.
6(77,1*6
)XQFWLRQ
(QDEOHG
%ORFN $1'
2II
6(77,1*6 )/(;/2*,&23(5$1'
6(77,1* %DVH&XUUHQW $1' 7+(50$/35273.3
6RXUFH .)DFWRU
,$506 ,$!Nî,E 6(77,1*
,%506 ,%!Nî,E 25 7ULS7LPH&RQVWDQW
,&506 ,&!Nî,F 581
(! 6 )/(;/2*,&23(5$1'
/DWFK 7+(50$/352723
5
5HVHWGRPLQDQW
6(77,1*6
5HVHW7LPH&RQVWDQW
0LQLPXP5HVHW7LPH
581
(
6(77,1*
5HVHW
2II 5HVHW(WR $&'5
a) MAIN MENU
PATH: SETTINGS CONTROL ELEMENTS PILOT SCHEMES
This menu contains settings for selecting and configuring protection signaling schemes. All schemes are available for sin-
gle-pole tripping applications and can be used with one, two, or four-bit communications channels. Choices of communica-
5 tions channels include remote inputs/outputs and telecommunications interfaces.
This scheme uses an under-reaching Zone 1 distance element to key a transfer trip signal(s) to the remote end(s), where
on receipt, the DUTT pilot scheme operates without additional protection supervision. For proper operation of the scheme
the Zone 1 phase and ground distance elements must be enabled, configured, and set per rules of distance relaying.
In single-pole tripping applications, the scheme uses local fault type identification provided by the Phase Selector together
with information received from the remote terminal(s). The latter may be coded into one, two or four bits over the communi-
cations channel.
The scheme generates output operands (DUTT TX1 through DUTT TX4) that are used to transmit the direct under-reaching
signals to the remote end(s). Choices of communications channel include remote inputs/outputs and telecommunications
interfaces. When used with telecommunications facilities the output operands should be assigned to operate output con-
tacts connected to assert the individual bits at the interface.
To make the scheme a fully operational stand-alone feature, the scheme output operands must be configured to interface
with other relay functions, output contacts in particular. Typically, the output operands should be programmed to initiate a
trip, breaker fail, and autoreclose, and drive a user-programmable LED as per user application. When used in conjunction
with the trip output element, the scheme is pre-configured to initiate trip, breaker fail, and single-pole autoreclose actions.
• DUTT SCHEME BLOCK: This setting allows the user to assign any FlexLogic operand to block the scheme. Contact
inputs from a pilot cut-out switch are typically used for this purpose.
• DUTT SEAL-IN DELAY: The output FlexLogic operand (DUTT OP) is produced according to the DUTT scheme logic. A
seal-in time delay is applied to this operand for coping with noisy communication channels such as a power line carrier.
The DUTT SEAL-IN DELAY is a minimum guaranteed duration of the DUTT OP pulse. As this operand activates the Trip
Table of the DUTT scheme, the trip operands DUTT TRIP A, B, C and 3P are sealed-in for the same period of time.
• DUTT NO OF COMM BITS: This setting specifies the number of bits available on the communications channel. With
only one bit available, the scheme sends the direct under-reaching transfer trip command on bit no.1 (DUTT TX1 oper-
and) and responds to the direct trip command received on bit no. 1 (DUTT RX1 setting). The scheme uses only local
fault type identification provided by the Phase Selector to assert the output operands DUTT TRIP A, B, C and 3P (see 5
Chapter 8: Theory of Operation for details on the use of communication channels).
• DUTT RX1 through DUTT RX4: These settings allow the user to select the FlexLogic operands that represent the
receive signals for the scheme. Typically input contacts interfacing with a signaling system are used.
The DUTT scheme requires a secure and dependable signaling system. For this reason, a series/parallel combination
of receive signal “contacts” is often used. This is accomplished by using a multi-bit communications system to transmit
redundant copies of the TX signal (often via different paths) and building appropriate security logic (such as series
(AND gate) or 2-out-of-3 voting logic) with FlexLogic. The DUTT RX1(4) settings should be associated with the final
(secure) TX signals.
In single-bit applications, DUTT RX1 must be used. In two-bit applications, DUTT RX1 and DUTT RX2 must be used. In
four-bit applications, DUTT RX1, DUTT RX2, DUTT RX3, and DUTT RX4 must be used. In multi-terminal applications, the RX
signals from two or more remote terminals should be connected through OR gates in the FlexLogic and the resulting
signals should be configured as the DUTT RX inputs.
SETTING
DUTT SCHEME
FUNCTION:
Disabled = 0
Enabled = 1
SETTINGS
DUTT NO OF COMM
BITS: SETTINGS
DUTT SEAL-IN
DUTT RX1: DELAY:
FLEXLOGIC OPERAND
Off = 0 0
AND t RST DUTT OP
5 DUTT RX2:
Off = 0
DUTT RX3: OR
DUTT NO OF COMM
BITS:
Off = 0
RUN
DUTT RX4:
RX FLEXLOGIC OPERANDS
Off = 0 DUTT TRIP A
Phase DUTT TRIP B
Selector TRIP TABLE
DUTT TRIP C
DUTT TRIP 3P
FLEXLOGIC OPERANDS
AR FORCE 3P TRIP
OPEN POLE OP
837012AD.CDR
This scheme uses an under-reaching zone 1 distance element to key a transfer trip signal(s) to the remote terminal(s)
where it is supervised by an over-reaching zone 2 distance element. For proper operation, the zone 1 and 2 phase and
ground distance elements must be enabled, configured, and set per rules of distance relaying.
In single-pole tripping applications, the scheme uses local fault type identification provided by the phase selector together
with information received from the remote terminal(s). The scheme generates output operands (PUTT TX1 through PUTT
TX4) that are used to transmit the signal to the remote end(s). Choices of communications channel include remote inputs/
outputs and telecommunications interfaces. When used with telecommunications facilities the output operands should be
assigned to operate output contacts connected to assert the individual bits at the interface.
To make the scheme a fully operational stand-alone feature, the scheme output operands must be configured to interface
with other relay functions, output contacts in particular. Typically, the output operands should be programmed to initiate a
trip, breaker fail, and autoreclose, and drive a user-programmable LED as per user application. When used in conjunction
with the Trip Output element, the scheme is pre-configured to initiate trip, breaker fail and single-pole autoreclose actions.
• PUTT SCHEME BLOCK: This setting allows the user to assign any FlexLogic operand to block the scheme. Contact
inputs from a pilot cut-out switch are typically used for this purpose.
• PUTT RX PICKUP DELAY: This setting enables the relay to cope with spurious receive signals. This delay should be
set longer than the longest spurious TX signal that can be received simultaneously with the zone 1 pickup. The
selected delay will increase the response time of the scheme.
• PUTT SEAL-IN DELAY: The output FlexLogic operand (PUTT OP) is produced according to the PUTT scheme logic. A
seal-in time delay is applied to this operand for coping with noisy communication channels such as a power line carrier.
The PUTT SEAL-IN DELAY is a minimum guaranteed duration of the PUTT OP pulse. As this operand activates the trip
table of the PUTT scheme, the trip operands PUTT TRIP A, B, C and 3P are sealed-in for the same period of time.
• PUTT NO OF COMM BITS: This setting specifies the number of bits of the communications channel available for the
scheme. The transmit codes and trip table of the PUTT scheme are identical as those for the direct under-reaching
transfer trip scheme. Please refer to Chapter 8: Theory of Operation for more information.
• PUTT RX1 through PUTT RX4: These settings allow the user to select the FlexLogic operands that represent the
receive signals for the scheme. Typically input contacts interfacing with a signaling system are used. In single-bit appli-
cations, PUTT RX1 must be used. In two-bit applications, PUTT RX1 and PUTT RX2 must be used. In four-bit applica-
tions, PUTT RX1, PUTT RX2, PUTT RX3, and PUTT RX4 must be used. In multi-terminal applications, the RX signals from
two or more remote terminals should be connected through OR gates in the FlexLogic and the resulting signals should
be configured as the PUTT RX inputs.
SETTING
PUTT SCHEME
FUNCTION:
Disabled = 0
Enabled = 1
AND
SETTING
PUTT SCHEME BLOCK:
OFF = 0 SETTINGS
PUTT RX PICKUP
SETTINGS DELAY: SETTINGS
PUTT NO OF COMM tPKP
AND PUTT SEAL-IN
BITS: 0 DELAY:
0 FLEXLOGIC OPERAND
PUTT RX1:
AND t RST PUTT OP
Off = 0
PUTT RX2:
PUTT NO OF COMM
Off = 0
BITS:
PUTT RX3: OR RUN
FLEXLOGIC OPERANDS
Off = 0 RX
PUTT TRIP A
5
PUTT RX4: Phase PUTT TRIP B
Selector TRIP TABLE
PUTT TRIP C
Off = 0
PUTT TRIP 3P
FLEXLOGIC OPERANDS
FLEXLOGIC OPERANDS
AR FORCE 3P TRIP
PH DIST Z2 PKP OPEN POLE OP
OR
GND DIST Z2 PKP
PUTT NO OF COMM
FLEXLOGIC OPERANDS BITS:
PH DIST Z1 PKP AND RUN
OR
FLEXLOGIC OPERANDS
GND DIST Z1 PKP
PUTT TX1
Phase PUTT TX2
TRANSMIT TABLE
Selector PUTT TX3
FLEXLOGIC OPERANDS PUTT TX4
AR FORCE 3P TRIP
OPEN POLE OP 837013AD.CDR
This scheme is primarily intended for two-terminal line applications. The scheme uses an over-reaching Zone 2 distance
element to essentially compare the direction to a fault at both terminals of the line. Ground directional overcurrent functions
available in the relay can be used in conjunction with the Zone 2 distance element to key the scheme and initiate its opera-
tion. This provides increased coverage for high-resistance faults.
For proper operation, the Zone 2 phase and ground distance elements must be enabled, configured and set per rules of
distance relaying. The Line Pickup element should be enabled, configured and set properly to detect line-end-open/weak-
infeed conditions. If used by this scheme, the selected ground directional overcurrent function(s) must be enabled, config-
ured and set accordingly.
In single-pole tripping applications, the scheme uses local fault type identification provided by the Phase Selector together
with information received from the remote terminal. The scheme generates output operands (POTT TX1 through POTT TX4)
that are used to transmit the signal to the remote end. Choices of communications channel include remote inputs/outputs
and telecommunications interfaces. When used with telecommunications facilities the output operands should be assigned
to operate output contacts connected to assert the individual bits at the interface.
To make the scheme fully operational as a stand-alone feature, the scheme output operands must be configured to inter-
face with other relay functions, output contacts in particular. Typically, the output operands should be programmed to initiate
a trip, breaker fail, and autoreclose, and drive a user-programmable LED as per user application.
When used in conjunction with the Trip Output element, the scheme is pre-configured to initiate trip, breaker fail, and single-
pole autoreclose actions.
• POTT SCHEME BLOCK: This setting allows the user to assign any FlexLogic operand to block the scheme. Contact
inputs from a pilot cut-out switch are typically used for this purpose.
• POTT PERMISSIVE ECHO: If this setting is set to “Enabled”, the scheme sends a permissive echo signal to the
remote end(s) using a pre-programmed logic (see the following logic diagram). If set to “Custom”, the echo signal is
sent if a condition selected via the POTT ECHO COND setting is satisfied. The echo is sent only once and then the logic
locks out for the time specified by the ECHO LOCKOUT. The duration of the echo pulse is settable as ECHO DURATION.
Operation of the overreaching protection elements (Distance Zone 2 or GND DIR O/C FWD setting) inhibits the echo.
• POTT ECHO COND: This setting specifies a user-selected echo condition and applies only if the HYB POTT PERMIS-
is set to “Custom”.
SIVE ECHO
5 • POTT RX PICKUP DELAY: This setting enables the relay to cope with spurious receive signals. The delay should be
set longer than the longest spurious TX signal that can be received simultaneously with the Zone 2 pickup. The
selected delay will increase the response time of the scheme.
• TRANS BLOCK PICKUP DELAY: This setting defines a transient blocking mechanism embedded in the POTT
scheme for coping with the exposure of a ground directional overcurrent function (if used) to current reversal condi-
tions. The transient blocking mechanism applies to the ground overcurrent path only as the reach settings for the Zone
2 distance functions is not expected to be long for two-terminal applications, and the security of the distance functions
is not endangered by the current reversal conditions.
Upon receiving the POTT RX signal, the transient blocking mechanism allows the RX signal to be passed and aligned
with the GND DIR O/C FWD indication only for a period of time set by TRANS BLOCK PICKUP DELAY. After that the ground
directional overcurrent path will be virtually disabled for a period of time specified as TRANS BLOCK RESET DELAY.
The TRANS BLOCK PICKUP DELAY should be long enough to give the selected ground directional overcurrent function
time to operate, but not longer than the fastest possible operation time of the protection system that can create current
reversal conditions within the reach of the selected ground directional overcurrent function.
This setting should take into account the POTT RX PICKUP DELAY. The POTT RX signal is shaped for aligning with the
ground directional indication as follows: the original RX signal is delayed by the POTT RX PICKUP DELAY, then terminated
at TRANS BLOCK PICKUP DELAY after the pickup of the original POTT TX signal, and eventually locked-out for TRANS
BLOCK RESET DELAY.
• TRANS BLOCK RESET DELAY: This setting defines a transient blocking mechanism embedded in the POTT scheme
for coping with the exposure of a ground directional overcurrent function (if used) to current reversal conditions (see
the TRANS BLOCK PICKUP DELAY). This delay should be selected long enough to cope with transient conditions includ-
ing not only current reversals but also spurious negative- and zero-sequence currents occurring during breaker opera-
tions. The breaker failure time of the surrounding protection systems within the reach of the ground directional function
used by the POTT scheme may be considered to make sure that the ground directional function is not jeopardized dur-
ing delayed breaker operations.
• ECHO DURATION: This setting defines the guaranteed and exact duration of the echo pulse. The duration does not
depend on the duration and shape of the received RX signal. This setting enables the relay to avoid a permanent lock-
up of the transmit/receive loop.
• ECHO LOCKOUT: This setting defines the lockout period for the echo logic after sending the echo pulse.
• LINE END OPEN PICKUP DELAY: This setting defines the pickup value for validation of the line end open conditions
as detected by the Line Pickup logic through the LINE PICKUP LEO PKP FlexLogic operand. The validated line end open
condition is a requirement for the POTT scheme to return a received echo signal (if the echo feature is enabled). This
value should take into account the principle of operation and settings of the Line Pickup element.
• POTT SEAL-IN DELAY: The output FlexLogic operand (POTT OP) is produced according to the POTT scheme logic. A
seal-in time delay is applied to this operand for coping with noisy communication channels. The POTT SEAL-IN DELAY
defines a minimum guaranteed duration of the POTT OP pulse. As this operand activates the trip table of the POTT
scheme, the trip operands POTT TRIP A, B, C and 3P are sealed-in for the same period of time.
• GND DIR O/C FWD: This setting defines the FlexLogic operand (if any) of a protection element that is used in addition
to the Zone 2 for identifying faults on the protected line, and thus, for keying the communication channel and initiating
operation of the scheme. Good directional integrity is the key requirement for an over-reaching forward-looking protec-
tion element used as GND DIR O/C FWD. Even though any FlexLogic operand could be used as GND DIR O/C FWD allow-
ing the user to combine responses of various protection elements, or to apply extra conditions through FlexLogic
equations, this extra signal is primarily meant to be the output operand from either the negative-sequence directional
overcurrent or neutral directional overcurrent. Both of these elements have separate forward (FWD) and reverse (REV)
output operands. The forward indication should be used (NEG SEQ DIR OC1 FWD or NEUTRAL DIR OC1 FWD). For greater
security and to overcome spurious directional element operation during transients, adding at least 0.5 cycles of pickup
delay to the forward directional element is recommended.
• POTT NO OF COMM BITS: This setting specifies the number of bits of the communications channel available for the
scheme. The transmit codes and trip tables of the POTT scheme are the same as those for the permissive under-
reaching transfer trip scheme. Please refer to the description of the PUTT scheme for more information.
• POTT RX1 through POTT RX4: These settings allow the user to select the FlexLogic operands that represent the
receive signals for the scheme. Typically input contacts interfacing with a signaling system are used. In single-bit appli-
cations, POTT RX1 must be used. In two-bit applications, POTT RX1 and POTT RX2 must be used. In four-bit applications,
POTT RX1, POTT RX2, POTT RX3, and POTT RX4 must be used. 5
SETTING
POTT SCHEME
FUNCTION:
Disabled = 0
Enabled = 1
AND
SETTING
POTT SCHEME BLOCK:
OFF = 0
5
FLEXLOGIC OPERANDS
Disabled SETTINGS SETTINGS POTT TX1
Off AND RUN POTT TX2
LINE END OPEN PICKUP ECHO DURATION:
DELAY: POTT TX3
FLEXLOGIC OPERAND AND
Enabled POTT TX4
LINE PICKUP LEO PKP
t PKP ECHO LOCKOUT:
0
Echo duration and lockout logic
SETTING
RX ECHO TABLE
POTT ECHO COND:
Phase
Custom Selector
Off = 0
FLEXLOGIC OPERANDS
AR FORCE 3P TRIP
OPEN POLE OP 837014AH.CDR
The POTT1 pilot scheme operates the same way as the regular POTT scheme, except hard-coded connections to phase
and ground distance elements are removed to allow the user to choose directional elements, for example ground OC direc-
tional elements. This allows a user to apply the POTT1 scheme using solely directional elements to achieve better coordi-
nation, rather than mixing up distance and ground OC directional elements together.
The settings and application guidance for the POTT scheme applies to the POTT1 scheme. See the POTT section.
• DIR FWD1..3: This setting defines the FlexLogic operand of a protection element used for keying the communication
channel and initiating operation of the scheme. Good directional integrity is the key requirement for an over-reaching
forward-looking protection element used as DIR FWD.
Even though any FlexLogic operand can be used as DIR FWD allowing the user to combine responses of various pro-
tection elements, or to apply extra security conditions through FlexLogic equations, this signal is primarily meant to be
the output operand from either the Negative-Sequence Directional IOC or Neutral Directional IOC. Both of these ele-
ments have separate forward (FWD) and reverse (REV) output operands. The forward indication is used (NEG SEQ
DIR OC1 FWD or NEUTRAL DIR OC1 FWD).
SETTING
POTT1 SCHEME
FUNCTION:
Disabled = 0
AND
SETTING
POTT1 SCHEME BLOCK:
OFF = 0
SETTING
DIR FWD1: AND
Off = 0
DIR FWD2:
SETTINGS
Off = 0 OR
POTT1 SEAL-IN
DIR FWD3: DELAY:
5
FLEXLOGIC OPERAND
Off = 0
0 POTT1 OP
t RST
FLEXLOGIC OPERANDS
AR FORCE 3P TRIP
OPEN POLE OP 837039A2.CDR
Generally, this scheme uses an overreaching zone 2 distance element to essentially compare the direction to a fault at all
terminals of the line. Ground directional overcurrent functions available in the D60 can be used in conjunction with the zone
2 distance element to key the scheme and initiate operation. This increases the coverage for high-resistance faults.
The scheme is intended for three-terminal and two-terminal applications with weak-infeed conditions. As a long reach of the
overreaching distance element may be required for three-terminal applications, transient blocking logic is provided for both
distance and ground directional overcurrent elements. In order to cope with weak-infeed conditions an echo feature is
made available.
By default the scheme uses the reverse-looking zone 4 distance element to identify reverse faults. Additionally, reverse-
looking ground directional overcurrent functions can be used in conjunction with the zone 4.
For proper operation, the zone 2 and 4 phase and ground distance elements must be enabled, configured and set per rules
of distance relaying. The line pickup element should be enabled, configured and set properly to detect line-end-open/weak-
infeed and undervoltage conditions. If used by the scheme, the selected ground directional overcurrent function(s) must be
enabled, configured, and set accordingly.
In single-pole tripping applications, the scheme uses local fault type identification provided by the phase selector together
with information received from the remote terminal. The scheme generates output operands (HYBRID POTT TX1 through
HYBRID POTT TX4) that are used to transmit the signal to the remote terminal(s). Choices of communications channel
include remote inputs/outputs and telecommunications interfaces. When used with telecommunications facilities the output
operand should be assigned to operate an output contact connected to key the transmitter at the interface. When used with
telecommunications facilities the output operands should be assigned to operate output contacts connected to assert the
individual bits at the interface.
To make the scheme fully operational as a stand-alone feature, the scheme output operands must be configured to inter-
face with other relay functions, output contacts in particular. Typically, the output operands should be programmed to initiate
a trip, breaker fail, and autoreclose, and drive a user-programmable LED as per user application.
5 When used in conjunction with the trip output element, the scheme is pre-configured to initiate trip, breaker fail and single-
pole autoreclose actions.
• HYB POTT BLOCK: This setting allows the user to assign any FlexLogic operand to block the scheme. Contact inputs
from a pilot cut-out switch are typically used for this purpose.
• HYB POTT PERMISSIVE ECHO: If set to “Enabled”, the scheme sends a permissive echo signal to the remote end(s)
using a pre-programmed logic (refer to the logic diagram below). If set to “Custom”, the echo signal is sent if a condi-
tion selected via the HYB POTT ECHO COND setting is satisfied. The echo is sent only once and then the logic locks out
for the time specified by the ECHO LOCKOUT setting. The duration of the echo pulse is settable as ECHO DURATION.
Operation of the overreaching protection elements (distance zone 2 or GND DIR O/C FWD setting) inhibits the echo.
• HYB POTT ECHO COND: This setting specifies a user-selected echo condition and applies only if the HYB POTT PER-
is set to “Custom”.
MISSIVE ECHO
• HYB POTT WEAK INFEED: If this setting is set to “Enabled”, the scheme activates both the keying and operating
paths using a pre-programmed weak infeed logic (refer to the logic diagram below). If this setting is set to “Custom”,
the weak infeed condition is to be specified by the user via the HYB POTT W/I COND setting.
• HYB POTT W/I COND: This setting specifies user-selected weak infeed condition and applies only if the HYB POTT
WEAK INFEED is set to “Custom”.
• HYB POTT RX PICKUP DELAY: This setting enables the relay to cope with spurious received signals. The delay
should be set longer than the longest spurious TX signal that can be received simultaneously with the zone 2 pickup.
The selected delay will increase the response time of the scheme.
• TRANS BLOCK PICKUP DELAY: This setting defines a transient blocking mechanism embedded in the hybrid POTT
scheme for coping with the exposure of both the over-reaching zone 2 and ground directional overcurrent function to
current reversal conditions.
The transient blocking logic applies to both operate (trip) and send (transmit) paths. Identifying the fault as a reverse
fault prevents the scheme from both operating and keying the channel. If the reverse fault condition prevails for TRANS
BLOCK PICKUP DELAY, the blocking operation will be extended by the transient blocking timer for TRANS BLOCK RESET
DELAY. This allows riding through current reversal conditions.
However, if distance zone 1 picks up during the transient blocking condition, the blocking action is removed. This is to
cope with evolving faults when an external fault is followed by an internal fault. Without the zone 1 feedback, the trip
would be delayed unnecessarily.
The TRANS BLOCK PICKUP DELAY should not be longer than the fastest possible trip time for faults on an adjacent line
so that extended blocking action could be established. This should take into account the pickup time of the reverse-
looking elements of the scheme.
The delay defined by this setting should not be too short in order to avoid locking up a spurious reverse fault indication
that can occur during internal fault conditions.
• TRANS BLOCK RESET DELAY: This setting defines a transient blocking mechanism embedded in the hybrid POTT
scheme for coping with the exposure of the overreaching protection functions to current reversal conditions (see also
the TRANS BLOCK PICKUP DELAY).
This delay should be selected long enough to cope with transient conditions including not only current reversals but
also spurious negative and zero-sequence currents occurring during breaker operations (in the case when neutral
directional overcurrent or negative-sequence directional overcurrent functions are used). The breaker failure time of
the surrounding protection systems within the reach of the ground directional function used by the hybrid POTT
scheme should be considered to make sure that the ground directional function is not jeopardized during delayed
breaker operations.
• ECHO DURATION: This setting defines the guaranteed and exact duration of the echo pulse. The duration is not
dependent on the duration and shape of received RX signals. This setting enables the relay to avoid a permanent lock-
up of the transmit/receive loop.
• ECHO LOCKOUT: This setting defines the lockout period for the echo logic after sending the echo pulse. This enables
the relay to avoid oscillations of the echo pulses during an autoreclosure dead-time after clearing an internal fault.
• HYB POTT SEAL-IN DELAY: The output FlexLogic operand (HYB POTT OP) is produced according to the hybrid POTT
scheme logic. The HYB POTT SEAL-IN DELAY defines a minimum guaranteed duration of the HYB POTT OP pulse. As this
operand runs the trip table of the hybrid POTT scheme, the trip operands HYB POTT TRIP A, B, C and 3P are sealed-in
for the same period of time.
• GND DIR O/C FWD: This setting defines the FlexLogic operand (if any) of a protection element that is used in addition 5
to zone 2 for identifying faults on the protected line, and thus, for keying the communication channel and initiating oper-
ation of the scheme (both through the transient blocking logic). Good directional integrity is the key requirement for an
over-reaching forward-looking protection element used as GND DIR O/C FWD.
Even though any FlexLogic operand could be used as GND DIR O/C FWD enabling the user to combine responses of var-
ious protection elements or to apply extra conditions through FlexLogic equations, this extra signal is primarily meant
to be the output operand from either the negative-sequence directional or neutral directional overcurrent elements.
Both these elements have separate forward (FWD) and reverse (REV) output operands. The forward indication should
be used (NEG SEQ DIR OC1 FWD or NEUTRAL DIR OC1 FWD).
The selected protection element (or elements in combination) should be coordinated with the selection of GND DIR O/C
REV. For all the forward external faults seen by an element used as GND DIR O/C FWD at one end of the line, the reverse-
looking element used as GND DIR O/C REV at the other end should pickup and provide a blocking signal. For greater
security and to overcome spurious directional element operation during transients, adding at least 0.5 cycles of pickup
delay to the forward directional element is recommended.
• GND DIR O/C REV: This setting defines the FlexLogic operand (if any) of a protection element used in addition to zone
4 for identifying reverse faults, and thus, for stopping the transmit signal and initiating the transient blocking timer.
Good directional integrity is the key requirement for a reverse-looking protection element used as GND DIR O/C REV.
Even though any FlexLogic operand could be used as GND DIR O/C REV enabling the user to combine responses of var-
ious protection elements or to apply extra conditions through FlexLogic equations, this extra signal is primarily meant
to be the output operand from either the negative sequence directional or neutral directional overcurrent element. Both
these elements have separate forward (FWD) and reverse (REV) output operands. The reverse indication should be
used (NEG SEQ DIR OC1 REV or NEUTRAL DIR OC1 REV).
The selected protection element (or elements in combination) should be coordinated with the selection of GND DIR O/C
FWD. For all the forward external faults seen by an element used as GND DIR O/C FWD at one end of the line, the
reverse-looking element used as GND DIR O/C REV at the other end should pickup and provide a blocking signal. For
greater security and to overcome spurious directional element operation during transients, adding a pickup delay
greater than the pilot channel delay to the reverse directional element is recommended.
• HYB POTT NO OF COMM BITS: This setting specifies the number of bits of the communications channel available for
the scheme. The transmit codes and trip table of the hybrid POTT scheme are the same as those for the permissive
under-reaching transfer trip scheme. Please refer to the description of the PUTT scheme for more information.
• HYB POTT RX1 through HYB POTT RX4: These settings allow the user to select the FlexLogic operands that repre-
sent the receive signals for the scheme. Typically input contacts interfacing with a signaling system are used. In single-
bit applications, HYB POTT RX1 must be used. In two-bit applications, HYB POTT RX1 and HYB POTT RX2 must be used. In
four-bit applications, HYB POTT RX1, HYB POTT RX2, HYB POTT RX3, and HYB POTT RX4 must be used.
SETTING SETTING
HYB POTT WEAK
GND DIR O/C FWD:
INFEED:
Off = 0
FLEXLOGIC OPERANDS OR
PH DIST Z2 PKP
GND DIST Z2 PKP
Disabled
Off OR
FLEXLOGIC OPERAND
LINE PICKUP LEO PKP
OPEN POLE OP Enabled
AND
LINE PICKUP UV PKP
SETTING
SETTING
HYB POTT SCHEME
FUNCTION: SETTING
Disabled=0 HYB POTT SEAL-IN
Enabled=1 DELAY:
FLEXLOGIC OPERAND
AND 0
AND HYB POTT OP
t RST
SETTING
5
Off = 0
HYB POTT NO OF
COMM BITS:
RUN
SETTINGS SETTING FLEXLOGIC OPERANDS
AND Phase
HYB POTT NO OF HYB POTT RX PICKUP Selector HYB POTT TRIP A
COMM BITS: DELAY:
RX HYB POTT TRIP B
TRIP TABLE
HYB POTT RX1: t PKP HYB POTT TRIP C
0 FLEXLOGIC OPERANDS HYB POTT TRIP 3P
Off = 0 AR FORCE 3P TRIP
HYB POTT RX2: OPEN POLE OP
Off = 0 0
100 msec
HYB POTT RX3: OR
Off = 0
SETTING
HYB POTT RX4:
HYB POTT SETTINGS
Off = 0 PERMISSIVE ECHO:
ECHO DURATION: SETTING
Disabled HYB POTT NO OF
Off
ECHO LOCKOUT: COMM BITS:
AND RUN
Echo duration and
Enabled AND lockout logic RX
SETTING AND
Phase
HYB POTT ECHO COND: Selector ECHO TABLE
Custom FLEXLOGIC OPERANDS
Off=0 FLEXLOGIC OPERANDS
AR FORCE 3P TRIP
HYB POTT TX1
OPEN POLE OP
HYB POTT TX2
SETTINGS
SETTING RUN HYB POTT TX3
TRANS BLOCK PICKUP AND
HYB POTT TX4
GND DIR O/C REV: DELAY: OR
TRANS BLOCK RESET Phase
Off = 0
DELAY: Selector
t PKP TRANSMIT TABLE
FLEXLOGIC OPERANDS OR OR FLEXLOGIC OPERANDS
t RST
PH DIST Z4 PKP AR FORCE 3P TRIP
GND DIST Z4 PKP OPEN POLE OP 837015AL.CDR
PH DIST Z1 PKP
GND DIST Z1 PKP
Generally, the scheme compares the direction to a fault at all terminals of the line. Unlike the permissive schemes, the
absence of a blocking signal permits operation of the scheme. Consequently, the scheme is biased toward dependability
and requires an "on/off" type of signaling.
By default this scheme uses only a forward-looking over-reaching zone 2 distance element to identify forward faults.
Ground directional overcurrent functions available in the relay can be used in conjunction with the zone 2 distance element
to increase the coverage for high-resistance faults. Also by default, only a reverse-looking zone 4 distance element to iden-
tify reverse faults. Ground directional overcurrent functions available in the relay can be used in conjunction with the zone 4
distance element for better time and sensitivity coordination.
For proper operation, the zone 2 and 4 phase and ground distance elements must be enabled, configured and set per rules
of distance relaying. If used by this scheme, the selected ground directional overcurrent functions must be enabled, config-
ured, and programmed accordingly.
In single-pole tripping applications, the scheme uses local fault type identification provided by the phase selector together
with information received from the remote terminal.
The scheme generates output operands (DIR BLOCK TX INIT and DIR BLOCK TX1 STOP through DIR BLOCK TX4 STOP) that
control the transmission of signals to the remote end(s). When used with telecommunications facilities the output operands
should be assigned to operate output contacts connected to key the transmitter at the interface.
The output operands from the scheme (DIR BLOCK A, B, C and 3P) must be configured to interface with other relay func-
tions, output contacts in particular, in order to make the scheme fully operational. Typically, the output operand should be
programmed to initiate a trip, breaker fail, and autoreclose, and drive a user-programmable LED as per user application.
When used in conjunction with the trip output element, the scheme is pre-configured to initiate trip, breaker fail, and single-
pole autoreclose actions.
• BLOCK SCHEME BLOCK: This setting allows the user to assign any FlexLogic operand to block the scheme. Contact
inputs from a pilot cut-out switch are typically used for this purpose.
• BLOCK RX CO-ORD PKP DELAY: This setting defines a delay for the forward-looking protection elements used by
the scheme for coordination with the blocking response from the remote end(s). This setting should include both the
response time of the protection elements used to establish a blocking signal and the total transmission time of that sig-
nal including the relay communications equipment interfacing and the communications channel itself.
• TRANS BLOCK PICKUP DELAY: This setting defines a transient blocking mechanism embedded in the blocking
scheme for coping with the exposure of both the over-reaching zone 2 and ground directional overcurrent function to
current reversal conditions.
The transient blocking logic applies to the send path only. Identifying the fault as a reverse fault establishes the block-
ing signal. If the reverse fault condition prevails for TRANS BLOCK PICKUP DELAY, the blocking operation will be
extended by the transient blocking timer for TRANS BLOCK RESET DELAY. This allows riding through current reversal
conditions. However, if zone 1 picks up during the transient blocking condition, the blocking action is removed. This is
done to cope with evolving faults when an external fault is followed by an internal fault. Without the zone 1 feedback,
the trip would be unnecessarily delayed.
5 The TRANS BLOCK PICKUP DELAY should not be longer than the fastest possible trip time for faults on an adjacent line
so that the extended blocking action could be established. This should take into account the pickup time of the reverse-
looking elements of the scheme. The delay defined by this setting should not be too short in order to avoid locking up a
spurious reverse fault indication that can occur during internal fault conditions.
• TRANS BLOCK RESET DELAY: This setting defines a transient blocking mechanism embedded in the blocking
scheme for coping with the exposure of the overreaching protection functions to current reversal conditions (see also
the TRANS BLOCK PICKUP DELAY).
This delay should be selected long enough to cope with transient conditions including not only current reversals but
also spurious negative and zero-sequence currents occurring during breaker operations (in the case when neutral
directional or negative-sequence directional overcurrent functions are used). Breaker failure time of the surrounding
protection systems within the reach of the ground directional function used by the blocking scheme should be consid-
ered to make sure that the ground directional function is not jeopardized during delayed breaker operations.
• BLOCK SCHEME SEAL-IN DELAY: The output FlexLogic operand (DIR BLOCK OP) is produced according to the
Blocking scheme logic. The BLOCK SCHEME SEAL-IN DELAY defines a minimum guaranteed duration of the DIR BLOCK
OP pulse. As this operand runs the Trip Table of the Blocking scheme, the trip operands DIR BLOCK TRIP A, B, C and 3P
are sealed-in for the same period of time.
• GND DIR O/C FWD: This setting defines the FlexLogic operand (if any) of a protection element used in addition to
zone 2 for identifying faults on the protected line, and thus, for initiating operation of the scheme. Good directional
integrity is the key requirement for an over-reaching forward-looking protection element used as GND DIR O/C FWD.
Even though any FlexLogic operand could be used as GND DIR O/C FWD enabling the user to combine responses of var-
ious protection elements or to apply extra conditions through FlexLogic equations, this extra signal is primarily meant
to be the output operand from either the negative-sequence directional or neutral directional overcurrent elements.
Both these elements have separate forward (FWD) and reverse (REV) output operands.
The forward indication should be used (NEG SEQ DIR OC1 FWD or NEUTRAL DIR OC1 FWD). The selected protection ele-
ment (or elements in combination) should be coordinated with the selection of GND DIR O/C REV. For all the forward
external faults seen by an element used as GND DIR O/C FWD at one end of the line, the reverse-looking element used
as GND DIR O/C REV at the other end should pickup and provide a blocking signal. For greater security and to overcome
spurious directional element operation during transients, adding at least 0.5 cycles of pickup delay to the forward direc-
tional element is recommended.
• GND DIR O/C REV: This setting defines the FlexLogic operand (if any) of a protection element that is used in addition
to zone 4 for identifying reverse faults, and thus, for initiating the blocking signal. Either reverse-looking directional or
non-directional overcurrent protection element may be used as GND DIR O/C REV.
Even though any FlexLogic operand could be used as GND DIR O/C REV, enabling the user to combine responses of var-
ious protection elements or to apply extra conditions through FlexLogic equations, this extra signal is primarily meant
to be the output operand from either the negative-sequence directional, neutral directional, or a non-directional instan-
taneous overcurrent element.
The selected protection element (or elements in combination) should be coordinated with the selection of GND DIR O/C
FWD. For all the forward external faults seen by an element used as GND DIR O/C FWD at one end of the line, the
reverse-looking element used as GND DIR O/C REV at the other end should pickup and provide a blocking signal. For
greater security and to overcome spurious directional element operation during transients, adding a pickup delay
greater than the pilot channel delay to the reverse directional element is recommended.
• BLOCK SCHEME NO OF COMM BITS: This setting specifies the number of bits of the communications channel avail-
able for the scheme. With only one bit available, the scheme sends the blocking signal by asserting the DIR BLOCK TX
INIT FlexLogic operand. This operand should be used to start the channel (set the blocking signal). On internal faults,
the scheme removes the blocking signal by asserting the DIR BLOCK TX1 FlexLogic operand.
For tripping the scheme responds to lack of the blocking signal on bit 1 (BLOCK SCHEME RX1 setting). The scheme uses
only local fault type identification provided by the phase selector to assert the output operands DIR BLOCK TRIP A, B, C
and 3P. Please refer to the Theory of operation chapter for more information on communications.
To take advantage of the four-bit blocking scheme, the blocking signals should be initiated from a disturbance detector.
This can be accomplished by using both 50DD and DIR BLOCK TX INIT to assert the blocking signal. Subsequently, spe-
cific bits will be de-asserted by the scheme based on the phase selection providing the peer relay with more informa-
tion on the fault type. Otherwise, the peer relay issues a three-pole trip upon receiving the bit pattern (0, 0, 0, 0).
• BLOCK SCHEME RX1 through BLOCK SCHEME RX4: These settings allow the user to select the FlexLogic oper- 5
ands that represent the receive signals for the scheme. Typically input contacts interfacing with a signaling system are
used. In single-bit applications, BLOCK SCHEME RX1 must be used. In two-bit applications, BLOCK SCHEME RX1 and
BLOCK SCHEME RX2 must be used. In four-bit applications, BLOCK SCHEME RX1, BLOCK SCHEME RX2, BLOCK SCHEME
RX3, and BLOCK SCHEME RX4 must be used.
SETTING
BLOCKING SCHEME
FUNCTION:
Disabled=0
AND
SETTING
BLOCK SCHEME BLOCK:
OFF = 0
SETTING
BLOCKING RX CO-ORD PKP
DELAY:
FLEXLOGIC OPERANDS
PH DIST Z2 PKP AND t PKP
0
GND DIST Z2 PKP
SETTING OR
5
AND OPEN POLE OP
OR
FLEXLOGIC OPERANDS SETTINGS
PH DIST Z4 PKP
TRANS BLOCK PICKUP FLEXLOGIC OPERAND
GND DIST Z4 PKP DELAY:
OR DIR BLOCK TX INIT
TRANS BLOCK RESET
DELAY:
t PKP
FLEXLOGIC OPERANDS t RST
OR
PH DIST Z1 PKP
OR
GND DIST Z1 PKP 837016AG.CDR
This menu allows selecting and setting up protection signaling of the directional comparison unblocking scheme. This
scheme is available for single-pole tripping applications and can be used with one, two, or four bit communications chan-
nels. Choices of communications channel include remote inputs/outputs and telecommunications interfaces.
Generally, this scheme uses an over-reaching zone 2 distance element to compare the direction to a fault at all terminals of
the line. Ground directional overcurrent functions available in the relay can be used in conjunction with the zone 2 distance
element to key the scheme and initiate its operation. This increases the coverage for high-resistance faults.
The scheme is intended for two or three-terminal applications. As a long reach of the overreaching distance element may
be required for three-terminal applications, transient blocking logic is provided for both distance and ground directional
overcurrent elements. An echo feature is made available to cope with line open conditions.
By default the scheme uses the reverse-looking zone 4 distance element to identify reverse faults. Additionally, reverse-
looking ground directional overcurrent functions can be used in conjunction with the zone 4.
5 For proper operation of the scheme the zone 2 and 4 phase and ground distance elements must be enabled, configured
and set per rules of distance relaying. The line pickup element should be enabled, configured and set properly to detect
line-end-open conditions. If used by this scheme, the selected ground directional overcurrent function(s) must be enabled,
configured and set accordingly.
In single-pole tripping applications, the scheme uses local fault type identification provided by the phase selector together
with information received from the remote terminal. The scheme generates output operands ( DCUB TX1 through DCUB TX4)
that are used to transmit the signal to the remote terminal(s). The directional comparison unblocking scheme was devel-
oped for use with frequency shift keying communications channels, though different telecommunications interfaces can be
used (for example, digital communication channels utilizing the D60 teleprotection input/outputs).
To make the scheme fully operational as a stand-alone feature, the scheme output operands must be configured to inter-
face with other relay functions, output contacts in particular. Typically, the output operands should be programmed to initiate
a trip, breaker fail, and autoreclose, and drive a user-programmable LED as per the intended application.
When used in conjunction with the trip output element, the scheme is pre-configured to initiate trip, breaker fail and autore-
close actions.
• DCUB BLOCK: This setting allows the user to assign any FlexLogic operand to block the scheme. Contact inputs from
a pilot cut-out switch are typically used for this purpose.
• DCUB PERMISSIVE ECHO: Enabling this setting will send a permissive echo signal to the remote end(s) under cer-
tain conditions (see the logic diagram for details). If set to “Custom”, the echo signal is sent if a condition selected with
the DCUB ECHO COND setting is satisfied. The echo is sent only once and then the echo logic locks out for the time
specified by the ECHO LOCKOUT setting. The duration of the echo pulse is programmable by the ECHO DURATION set-
ting. The echo is returned only if no overreaching and reverse protection elements operate.
• DCUB ECHO COND: This setting specifies a user-selected echo condition and applies only if the DCUB PERMISSIVE
ECHO setting is “Custom”.
• GND DIR O/C FWD: This setting defines the FlexLogic operand (if any) of a protection element used in addition to
zone 2 for identifying faults on the protected line, and thus, for keying the communication channel(s) and initiating
operation of the scheme (both through the transient blocking logic).
Good directional integrity is the key requirement for an over-reaching forward-looking protection element set as GND
DIR O/C FWD. Even though any FlexLogic operand could be set as GND DIR O/C FWD, thereby enabling the user to com-
bine responses of various protection elements or to apply extra conditions through FlexLogic equations, this extra sig-
nal is primarily meant to be the output operand from either the negative-sequence directional or neutral directional
overcurrent elements. As both these elements have separate forward and reverse output operands, the forward indica-
tion should be used (that is, NEG SEQ DIR OC1 FWD or NEUTRAL DIR OC1 FWD).
The selected protection element (or elements in combination) should be coordinated with the selection of GND DIR O/C
REV. For all forward external faults seen by an element set as GND DIR O/C FWD at one end of the line, the reverse-look-
ing element set as GND DIR O/C REV at the other end should pickup and provide a blocking signal. For greater security
and to overcome spurious directional element operation during transients, adding at least 0.5 cycles of pickup delay to
the forward directional element is recommended.
• GND DIR O/C REV: This setting defines the FlexLogic operand (if any) of a protection element used in addition to zone
4 for identifying reverse faults, and thus, for stopping the transmit signal and initiating the transient blocking timer.
Good directional integrity is the key requirement for a reverse-looking protection element set as GND DIR O/C REV. Even
though any FlexLogic operand could be set as GND DIR O/C REV, thereby enabling the user to combine responses of
various protection elements or to apply extra conditions through FlexLogic equations, this extra signal is primarily
meant to be the output operand from either the negative-sequence directional or neutral directional overcurrent ele-
ment. As both these elements have separate forward and reverse output operands, the reverse indication should be
used (that is, NEG SEQ DIR OC1 REV or NEUTRAL DIR OC1 REV).
The selected protection element (or elements in combination) should be coordinated with the selection of GND DIR O/C
FWD. For all the forward external faults seen by an element set as GND DIR O/C FWD at one end of the line, the reverse-
looking element set as GND DIR O/C REV at the other end should pickup and provide a blocking signal. For greater secu-
rity and to overcome spurious directional element operation during transients, adding a pickup delay greater than the
pilot channel delay to the reverse directional element is recommended.
• TRANS BLOCK PICKUP DELAY: This setting defines a transient blocking mechanism embedded in the directional
comparison unblocking scheme for coping with the exposure of both the over-reaching zone 2 and ground directional
overcurrent function to current reversal conditions.
5
The transient blocking logic applies to both operate (trip) and send (transmit) paths. Identifying the fault as a reverse
fault prevents the scheme from both operating and keying the channel. If the reverse fault condition prevails for TRANS
BLOCK PICKUP DELAY value, the blocking operation will be extended by the transient blocking timer for the TRANS
BLOCK RESET DELAY value. This allows riding through current reversal conditions.
However, if distance zone 1 picks up during the transient blocking condition, the blocking action is removed. This is to
cope with evolving faults when an external fault is followed by an internal fault. Without the zone 1 feedback, the trip
would be delayed unnecessarily.
The TRANS BLOCK PICKUP DELAY should not be longer than the fastest possible trip time for faults on an adjacent line
so that extended blocking action could be established. This should take into account the pickup time of the reverse-
looking elements of the scheme. To avoid locking up a spurious reverse fault indication that can occur during internal
fault conditions, the delay defined by this setting should not be too short.
• TRANS BLOCK RESET DELAY: This setting defines a transient blocking mechanism embedded in the directional
comparison unblocking scheme for coping with the exposure of the overreaching protection functions to current rever-
sal conditions (see also the TRANS BLOCK PICKUP DELAY setting above).
This delay should be selected long enough to cope with transient conditions including not only current reversals but
also spurious negative and zero-sequence currents occurring during breaker operations (in the case when neutral
directional or negative-sequence directional overcurrent functions are used). The breaker failure time of the surround-
ing protection systems within the reach of the ground directional function used by the directional comparison unblock-
ing scheme should be considered to make sure that the ground directional function is not jeopardized during delayed
breaker operations.
• ECHO DURATION: This setting defines the guaranteed and exact duration of the echo pulse. The duration does not
depend on the duration and shape of the received RX signals. This setting enables the relay to avoid a permanent lock-
up of the transmit/receive loop.
• ECHO LOCKOUT: This setting defines the lockout period for the echo logic after sending the echo pulse. This setting
enables the relay to avoid oscillations of the echo pulses during an autoreclosure dead-time after clearing an internal
fault.
• LINE END OPEN PICKUP DELAY: This setting defines the pickup value for validation of the line end open conditions
as detected by the line pickup logic via the LINE PICKUP LEO PKP FlexLogic operand. The validated line end open con-
dition is a requirement for the directional comparison unblocking scheme to return a received echo signal (if the echo
feature is enabled).
The value of this setting should take into account the principle of operation and settings of the line pickup element,
which should thus be enabled.
• DCUB LOG PICKUP DELAY: This setting represents the directional comparison unblocking duration time delay, and is
the amount of time that the loss-of-guard without receipt of permissive trip must be present before the logic provides
permission to operate if a forward fault is detected. It is set relatively short, but long enough to ride through the transi-
tion period of loss-of-guard with the receipt of a permissive signal that occurs with a normal trip. Typical setting values
are from 4 to 32 ms. For most cases, a value of 8 ms may be used.
The tripping or unblocking window for loss-of-guard without permission is the difference between the DCUB LOG TRIP
WINDOW and DCUB LOG PICKUP DELAY timers. For the default settings, this difference is 150 – 8 = 142 ms and occurs
8 ms after loss-of-guard was received, when the DCUB LOG PICKUP DELAY timer has timed out. During this interval, the
scheme has permission to operate if a forward fault is sensed, and no reverse faults or transient blocking.
• GUARD HEALTHY RESET DELAY: This setting represents the guard healthy security time delay, and is the time after
the channel is restored that the guard signal must be present before the directional comparison unblocking scheme is
put back in service. This reset timer allows the scheme to ride through any chattering in the channel. Typical values are
from 100 to 500 ms, with a value of 150 ms commonly used.
• DCUB LOG TRIP WINDOW: This setting represents the directional comparison unblocking lockout time delay, and is
the amount of time from when any loss-of-guard signal is received until the directional comparison unblocking scheme
is locked out without the presence of any RX1 to RX4 receive signal or any forward element. This timer seals-in when it
expires, creating a blocking signal for all scheme functions and disabling the scheme until the guard signal is restored
and the GUARD HEALTHY RESET DELAY timer expires. Typical values for this setting are from 160 to 180 ms; for most
cases, a setting of about 150 ms may be used.
5 • DCUB SEAL-IN DELAY: The output FlexLogic operand (DCUB OP) is produced according to the directional compari-
son unblocking scheme logic. The DCUB SEAL-IN DELAY defines a minimum guaranteed duration of the DCUB OP pulse.
As this operand runs the trip table of the directional comparison unblocking scheme, the DCUB TRIP A, DCUB TRIP B,
DCUB TRIP C, and DCUB TRIP 3P trip operands are sealed-in for the same period of time.
• DCUB NO OF COMM BITS: This setting specifies the number of bits available on the communications channel for the
scheme. With only one bit available, the scheme sends the direct under-reaching transfer trip command on bit 1 (DCUB
TX1 operand) and responds to the direct trip command received on bit 1 (DCUB RX1 setting). The scheme uses only
local fault type identification provided by the phase selector to assert the DCUB TRIP A, DCUB TRIP B, DCUB TRIP C and
DCUB TRIP 3P output operands (see Chapter 8: Theory of Operation for details on the use of communication channels).
• DCUB RX1 through DCUB RX4: These settings allow the user to select the FlexLogic operands to represent the per-
mission receive signals for the scheme. Contact inputs interfacing with a signaling system(s) are typically used. These
settings must be used in conjunction with the loss-of-guard signals, otherwise the scheme will not unblock and thus fail
to operate.
In single-bit applications, DCUB RX1 must be used. In two-bit applications, DCUB RX1 and DCUB RX2 must be used. In
four-bit applications, DCUB RX1, DCUB RX2, DCUB RX3, and DCUB RX4 must be used.
• DCUB LOG1 through DCUB LOG4: These settings allow the user to select the FlexLogic operands to represent the
loss-of-guard receive signals for the scheme. Contact inputs interfacing with a signaling system(s) are typically used.
Each loss-of-guard signal must correspond to the same receive signal from the same communications channel (that is,
RX1 and LOG1 must be from the same communications channel, and the same for channels 2, 3 and 4, if used).
In single-bit applications, DCUB RX1 and DCUB LOG1 must be used. In two-bit applications, DCUB RX1 with DCUB LOG1
and DCUB RX2 with DCUB LOG2 must be used. In four-bit applications, all receive and loss-of-guard signals must be
used.
SETTING
DCUB SCHEME LOG = LOSS OF GUARD
FUNCTION:
Disabled = 0 AND
AND
SETTING
AND SETTINGS
DCUB BLOCKED:
DCUB SEAL-IN
Off = 0 DELAY:
FLEXLOGIC OPERANDS
SETTINGS 0
FLEXLOGIC OPERANDS OR DCUB OP
AND tRST
DCUB LOG PICKUP
GND DIST Z2 PKP DELAY:
PHS DIST Z2 PKP
tPKP DCUB NO OF COMM
SETTING OR AND BITS:
0
GND DIR O/C FWD: RUN
Phase
AND FLEXLOGIC OPERANDS
Selector
Off = 0 OR DCUB TRIP A
RX
AND DCUB TRIP B
SETTING LOG
AND TRIP TABLE DCUB TRIP C
DCUB NO OF COMM AND
DCUB TRIP 3P
BITS: FLEXLOGIC OPERANDS
AR FORCE 3P TRIP
DCUB RX1:
OPEN POLE OP
Off = 0 SETTINGS
OR AND
DCUB LOG TRIP
DCUB LOG1:
WINDOW:
Off = 0 tPKP
OR
DCUB RX2: 0
DCUB NO OF COMM
Off = 0 SETTINGS BITS:
RUN
DCUB LOG2: OR GUARD HEALTHY Phase
RESET DELAY: Selector
Off = 0
0
AND
DCUB RX3: tRST TRANSMIT TABLE
FLEXLOGIC OPERANDS
Off = 0
AR FORCE 3P TRIP FLEXLOGIC OPERANDS
0 DCUB TX1
DCUB LOG3: OPEN POLE OP
100ms SETTING DCUB TX2
Off = 0 RUN DCUB TX3
DCUB PERMISSIVE
Phase
SETTINGS ECHO: DCUB TX4
DCUB RX4: Selector
RX
TRANS BLOCK ECHO TABLE
Off = 0 SETTINGS
PICKUP DELAY: LOG
DCUB LOG4: Disabled LINE END OPEN
TRANS BLOCK Off = 0
PICKUP DELAY:
RESET DELAY: 837032A2.CDR
Off = 0 FLEXLOGIC OPERANDS
Enabled tPKP
tPKP LINE PICKUP LEO PKP
AND 0
5
SETTING tRST SETTING
OR SETTING
GND DIR O/C REV: Custom ECHO DURATION:
DCUB ECHO COND:
Off = 0 ECHO LOCKOUT:
Off = 0
AND
OR Echo duration/lockout logic
FLEXLOGIC OPERANDS OR AND
GND DIST Z4 PKP
PHS DIST Z4 PKP
GND DIST Z1 PKP
PHS DIST Z1 PKP
CONTACT INPUTS
CONTACT INPUT
THRESHOLDS
5 THRESHOLD: 33 Vdc
The contact inputs menu contains configuration settings for each contact input as well as voltage thresholds for each group
of four contact inputs. Upon startup, the relay processor determines (from an assessment of the installed modules) which
contact inputs are available and then display settings for only those inputs.
An alphanumeric ID may be assigned to a contact input for diagnostic, setting, and event recording purposes. The CON-
TACT IP X On” (Logic 1) FlexLogic operand corresponds to contact input “X” being closed, while CONTACT IP X Off corre-
sponds to contact input “X” being open. The CONTACT INPUT DEBNCE TIME defines the time required for the contact to
overcome ‘contact bouncing’ conditions. As this time differs for different contact types and manufacturers, set it as a maxi-
mum contact debounce time (per manufacturer specifications) plus some margin to ensure proper operation. If CONTACT
INPUT EVENTS is set to “Enabled”, every change in the contact input state will trigger an event.
A raw status is scanned for all Contact Inputs synchronously at the constant rate of 0.5 ms as shown in the figure below.
The DC input voltage is compared to a user-settable threshold. A new contact input state must be maintained for a user-
settable debounce time in order for the D60 to validate the new contact state. In the figure below, the debounce time is set
at 2.5 ms; thus the 6th sample in a row validates the change of state (mark no. 1 in the diagram). Once validated (de-
bounced), the contact input asserts a corresponding FlexLogic operand and logs an event as per user setting.
A time stamp of the first sample in the sequence that validates the new state is used when logging the change of the con-
tact input into the Event Recorder (mark no. 2 in the diagram).
Protection and control elements, as well as FlexLogic equations and timers, are executed eight times in a power system
cycle. The protection pass duration is controlled by the frequency tracking mechanism. The FlexLogic operand reflecting
the debounced state of the contact is updated at the protection pass following the validation (marks no. 3 and 4 on the fig-
ure below). The update is performed at the beginning of the protection pass so all protection and control functions, as well
as FlexLogic equations, are fed with the updated states of the contact inputs.
The FlexLogic operand response time to the contact input change is equal to the debounce time setting plus up to one pro-
tection pass (variable and depending on system frequency if frequency tracking enabled). If the change of state occurs just
after a protection pass, the recognition is delayed until the subsequent protection pass; that is, by the entire duration of the
protection pass. If the change occurs just prior to a protection pass, the state is recognized immediately. Statistically a delay
of half the protection pass is expected. Owing to the 0.5 ms scan rate, the time resolution for the input contact is below
1msec.
For example, 8 protection passes per cycle on a 60 Hz system correspond to a protection pass every 2.1 ms. With a con-
tact debounce time setting of 3.0 ms, the FlexLogic operand-assert time limits are: 3.0 + 0.0 = 3.0 ms and 3.0 + 2.1 = 5.1
ms. These time limits depend on how soon the protection pass runs after the debouncing time.
Regardless of the contact debounce time setting, the contact input event is time-stamped with a 1 s accuracy using the
time of the first scan corresponding to the new state (mark no. 2 below). Therefore, the time stamp reflects a change in the
DC voltage across the contact input terminals that was not accidental as it was subsequently validated using the debounce
timer. Keep in mind that the associated FlexLogic operand is asserted/de-asserted later, after validating the change.
The debounce algorithm is symmetrical: the same procedure and debounce time are used to filter the LOW-HIGH (marks
no.1, 2, 3, and 4 in the figure below) and HIGH-LOW (marks no. 5, 6, 7, and 8 below) transitions.
VOLTAGE
INPUT
USER-PROGRAMMABLE THRESHOLD
6
2 1 3 5
Time stamp of the first
5
TM
Time stamp of the first At this time, the The FlexLogic scan corresponding to the
At this time, the new
scan corresponding to new (HIGH) operand is going to new validated state is
(LOW) contact state is
the new validated state is contact state is be asserted at this logged in the SOE record
validated
logged in the SOE record validated protection pass
7
RAW CONTACT
The FlexLogicTM
operand is going to be
STATE
de-asserted at this
protection pass
DEBOUNCE TIME
(user setting)
4
The FlexLogicTM operand
DEBOUNCE TIME
The FlexLogicTM operand changes reflecting the
SCAN TIME (user setting)
changes reflecting the validated contact state
FLEXLOGICTM
PROTECTION PASS
(8 times a cycle controlled by the
frequency tracking mechanism)
842709A1.cdr
Figure 5–171: INPUT CONTACT DEBOUNCING MECHANISM AND TIME-STAMPING SAMPLE TIMING
Contact inputs are isolated in groups of four to allow connection of wet contacts from different voltage sources for each
group. The CONTACT INPUT THRESHOLDS determine the minimum voltage required to detect a closed contact input. This
value should be selected according to the following criteria: 17 for 24 V sources, 33 for 48 V sources, 84 for 110 to 125 V
sources and 166 for 250 V sources.
For example, to use contact input H5a as a status input from the breaker 52b contact to seal-in the trip relay and record it in
the Event Records menu, make the following settings changes:
CONTACT INPUT H5A ID: "Breaker Closed (52b)"
CONTACT INPUT H5A EVENTS: "Enabled"
Note that the 52b contact is closed when the breaker is open and open when the breaker is closed.
There are 64 virtual inputs that can be individually programmed to respond to input signals from the keypad (via the COM-
MANDS menu) and communications protocols. All virtual input operands are defaulted to “Off” (logic 0) unless the appropri-
ate input signal is received.
If the VIRTUAL INPUT x FUNCTION is to “Disabled”, the input will be forced to off (logic 0) regardless of any attempt to alter the
input. If set to “Enabled”, the input operates as shown on the logic diagram and generates output FlexLogic operands in
response to received input signals and the applied settings.
There are two types of operation: self-reset and latched. If VIRTUAL INPUT x TYPE is “Self-Reset”, when the input signal tran-
sits from off to on, the output operand will be set to on for only one evaluation of the FlexLogic equations and then return to
off. If set to “Latched”, the virtual input sets the state of the output operand to the same state as the most recent received
input.
5 The self-reset operating mode generates the output operand for a single evaluation of the FlexLogic equations. If
the operand is to be used anywhere other than internally in a FlexLogic equation, it will likely have to be lengthened
NOTE
in time. A FlexLogic timer with a delayed reset can perform this function.
SETTING
VIRTUAL INPUT 1
FUNCTION:
Enabled=1 S
AND
Latch
“Virtual Input 1 to ON = 1”
SETTING
“Virtual Input 1 to OFF = 0” R VIRTUAL INPUT 1 ID:
AND
SETTING (Flexlogic Operand)
OR
Virt Ip 1
VIRTUAL INPUT 1
TYPE:
Latched AND
Self - Reset 827080A3.CDR
a) DIGITAL OUTPUTS
PATH: SETTINGS INPUTS/OUTPUTS CONTACT OUTPUTS CONTACT OUTPUT H1
Upon startup of the relay, the main processor will determine from an assessment of the modules installed in the chassis
which contact outputs are available and present the settings for only these outputs.
An ID may be assigned to each contact output. The signal that can OPERATE a contact output may be any FlexLogic oper-
and (virtual output, element state, contact input, or virtual input). An additional FlexLogic operand may be used to SEAL-IN
the relay. Any change of state of a contact output can be logged as an Event if programmed to do so.
For example, the trip circuit current is monitored by providing a current threshold detector in series with some Form-A con-
tacts (see the trip circuit example in the Digital elements section). The monitor will set a flag (see the specifications for
Form-A). The name of the FlexLogic operand set by the monitor, consists of the output relay designation, followed by the
name of the flag; for example, CONT OP 1 ION.
In most breaker control circuits, the trip coil is connected in series with a breaker auxiliary contact used to interrupt current 5
flow after the breaker has tripped, to prevent damage to the less robust initiating contact. This can be done by monitoring
an auxiliary contact on the breaker which opens when the breaker has tripped, but this scheme is subject to incorrect oper-
ation caused by differences in timing between breaker auxiliary contact change-of-state and interruption of current in the
trip circuit. The most dependable protection of the initiating contact is provided by directly measuring current in the tripping
circuit, and using this parameter to control resetting of the initiating relay. This scheme is often called trip seal-in.
This can be realized in the D60 using the CONT OP 1 ION FlexLogic operand to seal-in the contact output as follows:
CONTACT OUTPUT H1 ID: “Cont Op 1"
OUTPUT H1 OPERATE: any suitable FlexLogic operand
OUTPUT H1 SEAL-IN: “Cont Op 1 IOn”
CONTACT OUTPUT H1 EVENTS: “Enabled”
b) LATCHING OUTPUTS
PATH: SETTINGS INPUTS/OUTPUTS CONTACT OUTPUTS CONTACT OUTPUT H1a
The D60 latching output contacts are mechanically bi-stable and controlled by two separate (open and close) coils. As such
they retain their position even if the relay is not powered up. The relay recognizes all latching output contact cards and pop-
ulates the setting menu accordingly. On power up, the relay reads positions of the latching contacts from the hardware
before executing any other functions of the relay (such as protection and control features or FlexLogic).
The latching output modules, either as a part of the relay or as individual modules, are shipped from the factory with all
latching contacts opened. It is highly recommended to double-check the programming and positions of the latching con-
tacts when replacing a module.
Since the relay asserts the output contact and reads back its position, it is possible to incorporate self-monitoring capabili-
ties for the latching outputs. If any latching outputs exhibits a discrepancy, the LATCHING OUTPUT ERROR self-test error is
declared. The error is signaled by the LATCHING OUT ERROR FlexLogic operand, event, and target message.
• OUTPUT H1a OPERATE: This setting specifies a FlexLogic operand to operate the ‘close coil’ of the contact. The
relay will seal-in this input to safely close the contact. Once the contact is closed and the RESET input is logic 0 (off),
any activity of the OPERATE input, such as subsequent chattering, will not have any effect. With both the OPERATE and
RESET inputs active (logic 1), the response of the latching contact is specified by the OUTPUT H1A TYPE setting.
• OUTPUT H1a RESET: This setting specifies a FlexLogic operand to operate the ‘trip coil’ of the contact. The relay will
seal-in this input to safely open the contact. Once the contact is opened and the OPERATE input is logic 0 (off), any
activity of the RESET input, such as subsequent chattering, will not have any effect. With both the OPERATE and RESET
inputs active (logic 1), the response of the latching contact is specified by the OUTPUT H1A TYPE setting.
• OUTPUT H1a TYPE: This setting specifies the contact response under conflicting control inputs; that is, when both the
OPERATE and RESET signals are applied. With both control inputs applied simultaneously, the contact will close if set to
“Operate-dominant” and will open if set to “Reset-dominant”.
Application Example 1:
5 A latching output contact H1a is to be controlled from two user-programmable pushbuttons (buttons number 1 and 2). The
following settings should be applied.
Program the Latching Outputs by making the following changes in the SETTINGS INPUTS/OUTPUTS CONTACT OUT-
PUTS CONTACT OUTPUT H1a menu (assuming an H4L module):
Program the pushbuttons by making the following changes in the PRODUCT SETUP USER-PROGRAMMABLE PUSHBUT-
TONS USER PUSHBUTTON 1 and USER PUSHBUTTON 2 menus:
Application Example 2:
A relay, having two latching contacts H1a and H1c, is to be programmed. The H1a contact is to be a Type-a contact, while
the H1c contact is to be a Type-b contact (Type-a means closed after exercising the operate input; Type-b means closed
after exercising the reset input). The relay is to be controlled from virtual outputs: VO1 to operate and VO2 to reset.
Program the Latching Outputs by making the following changes in the SETTINGS INPUTS/OUTPUTS CONTACT OUT-
PUTS CONTACT OUTPUT H1a and CONTACT OUTPUT H1c menus (assuming an H4L module):
Since the two physical contacts in this example are mechanically separated and have individual control inputs, they will not
operate at exactly the same time. A discrepancy in the range of a fraction of a maximum operating time may occur. There-
fore, a pair of contacts programmed to be a multi-contact relay will not guarantee any specific sequence of operation (such
as make before break). If required, the sequence of operation must be programmed explicitly by delaying some of the con-
trol inputs as shown in the next application example.
Application Example 3:
A make before break functionality must be added to the preceding example. An overlap of 20 ms is required to implement
this functionality as described below:
Both timers (Timer 1 and Timer 2) should be set to 20 ms pickup and 0 ms dropout.
Program the Latching Outputs by making the following changes in the SETTINGS INPUTS/OUTPUTS CONTACT OUT-
PUTS CONTACT OUTPUT H1a and CONTACT OUTPUT H1c menus (assuming an H4L module):
OUTPUT H1a OPERATE: “VO1” OUTPUT H1c OPERATE: “VO2”
OUTPUT H1a RESET: “VO4” OUTPUT H1c RESET: “VO3”
Application Example 4:
A latching contact H1a is to be controlled from a single virtual output VO1. The contact should stay closed as long as VO1
is high, and should stay opened when VO1 is low. Program the relay as follows.
Write the following FlexLogic equation (EnerVista UR Setup example shown):
5
Program the Latching Outputs by making the following changes in the SETTINGS INPUTS/OUTPUTS CONTACT OUT-
PUTS CONTACT OUTPUT H1a menu (assuming an H4L module):
OUTPUT H1a OPERATE: “VO1”
OUTPUT H1a RESET: “VO2”
There are 96 virtual outputs that may be assigned via FlexLogic. If not assigned, the output will be forced to ‘OFF’ (Logic 0).
An ID may be assigned to each virtual output. Virtual outputs are resolved in each pass through the evaluation of the Flex-
Logic equations. Any change of state of a virtual output can be logged as an event if programmed to do so.
For example, if Virtual Output 1 is the trip signal from FlexLogic and the trip relay is used to signal events, the settings
would be programmed as follows:
5 The IEC 61850 specification includes features that are used to cope with the loss of communication between transmitting
and receiving devices. Each transmitting device will send a GSSE/GOOSE message upon a successful power-up, when
the state of any included point changes, or after a specified interval (the default update time) if a change-of-state has not
occurred. The transmitting device also sends a ‘hold time’ which is set greater than four times the programmed default time
required by the receiving device.
Receiving devices are constantly monitoring the communications network for messages they require, as recognized by the
identification of the originating device carried in the message. Messages received from remote devices include the mes-
sage time allowed to live. The receiving relay sets a timer assigned to the originating device to this time interval, and if it
has not received another message from this device at time-out, the remote device is declared to be non-communicating, so
it will use the programmed default state for all points from that specific remote device. If a message is received from a
remote device before the time allowed to live expires, all points for that device are updated to the states contained in the
message and the hold timer is restarted. The status of a remote device, where “Offline” indicates non-communicating, can
be displayed.
The remote input/output facility provides for 32 remote inputs and 64 remote outputs.
Likewise, the device ID that represents the IEC 61850 GSSE application ID name string sent as part of each GSSE mes-
sage is programmed in the SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL GSSE/GOOSE
CONFIGURATION TRANSMISSION GSSE GSSE ID setting.
In D60 releases previous to 5.0x, these name strings were represented by the RELAY NAME setting.
Remote devices are available for setting purposes. A receiving relay must be programmed to capture messages from only
those originating remote devices of interest. This setting is used to select specific remote devices by entering (bottom row)
the exact identification (ID) assigned to those devices.
The REMOTE DEVICE 1 ETYPE APPID setting is only used with GOOSE messages; they are not applicable to GSSE mes-
sages. This setting identifies the Ethernet application identification in the GOOSE message. It should match the corre-
sponding settings on the sending device.
The REMOTE DEVICE 1 DATASET setting provides for the choice of the D60 fixed (DNA/UserSt) dataset (that is, containing
DNA and UserSt bit pairs), or one of the configurable datasets.
Note that the dataset for the received data items must be made up of existing items in an existing logical node. For this rea-
son, logical node GGIO3 is instantiated to hold the incoming data items. GGIO3 is not necessary to make use of the
received data. The remote input data item mapping takes care of the mapping of the inputs to remote input FlexLogic oper-
ands. However, GGIO3 data can be read by IEC 61850 clients.
Remote Inputs that create FlexLogic operands at the receiving relay are extracted from GSSE/GOOSE messages originat-
ing in remote devices. Each remote input can be selected from a list consisting of: DNA-1 through DNA-32, UserSt-1
through UserSt-32, and Dataset Item 1 through Dataset Item 32. The function of DNA inputs is defined in the IEC 61850
specification and is presented in the IEC 61850 DNA Assignments table in the Remote outputs section. The function of
UserSt inputs is defined by the user selection of the FlexLogic operand whose state is represented in the GSSE/GOOSE
message. A user must program a DNA point from the appropriate FlexLogic operand.
Remote input 1 must be programmed to replicate the logic state of a specific signal from a specific remote device for local
use. This programming is performed via the three settings shown above.
The REMOTE INPUT 1 ID setting allows the user to assign descriptive text to the remote input. The REMOTE IN 1 DEVICE setting
selects the remote device which originates the required signal, as previously assigned to the remote device via the setting
REMOTE DEVICE (16) ID (see the Remote devices section). The REMOTE IN 1 ITEM setting selects the specific bits of the
GSSE/GOOSE message required.
The REMOTE IN 1 DEFAULT STATE setting selects the logic state for this point if the local relay has just completed startup or
the remote device sending the point is declared to be non-communicating. The following choices are available:
• Setting REMOTE IN 1 DEFAULT STATE to “On” value defaults the input to logic 1.
• Setting REMOTE IN 1 DEFAULT STATE to “Off” value defaults the input to logic 0.
• Setting REMOTE IN 1 DEFAULT STATE to “Latest/On” freezes the input in case of lost communications. If the latest state is
not known, such as after relay power-up but before the first communication exchange, the input will default to logic 1.
When communication resumes, the input becomes fully operational.
• Setting REMOTE IN 1 DEFAULT STATE to “Latest/Off” freezes the input in case of lost communications. If the latest state is
not known, such as after relay power-up but before the first communication exchange, the input will default to logic 0.
When communication resumes, the input becomes fully operational.
For additional information on GSSE/GOOOSE messaging, refer to the Remote Devices section in this chapter.
NOTE
PATH: SETTINGS INPUTS/OUTPUTS REMOTE DPS INPUTS REMOTE DPS INPUT 1(5)
5
MESSAGE
EVENTS: Disabled
Remote double-point status inputs are extracted from GOOSE messages originating in the remote device. Each remote
double point status input must be programmed to replicate the logic state of a specific signal from a specific remote device
for local use. This functionality is accomplished with the five remote double-point status input settings.
• REM DPS IN 1 ID: This setting assigns descriptive text to the remote double-point status input.
• REM DPS IN 1 DEV: This setting selects a remote device ID to indicate the origin of a GOOSE message. The range is
selected from the remote device IDs specified in the Remote devices section.
• REM DPS IN 1 ITEM: This setting specifies the required bits of the GOOSE message.
The configurable GOOSE dataset items must be changed to accept a double-point status item from a GOOSE dataset
(changes are made in the SETTINGS COMMUNICATION IEC 61850 PROTOCOL GSSE/GOOSE CONFIGURATION
RECEPTION CONFIGURABLE GOOSE CONFIGURABLE GOOSE 1(16) CONFIG GSE 1 DATASET ITEMS menus). Dataset
items configured to receive any of “GGIO3.ST.IndPos1.stV” to “GGIO3.ST.IndPos5.stV” will accept double-point status
information that will be decoded by the remote double-point status inputs configured to this dataset item.
The remote double point status is recovered from the received IEC 61850 dataset and is available as through the RemDPS
Ip 1 BAD, RemDPS Ip 1 INTERM, RemDPS Ip 1 OFF, and RemDPS Ip 1 ON FlexLogic operands. These operands can then be
used in breaker or disconnect control schemes.
Remote outputs (1 to 32) are FlexLogic operands inserted into GSSE/GOOSE messages that are transmitted to remote
devices on a LAN. Each digital point in the message must be programmed to carry the state of a specific FlexLogic oper-
and. The above operand setting represents a specific DNA function (as shown in the following table) to be transmitted.
Remote outputs 1 to 32 originate as GSSE/GOOSE messages to be transmitted to remote devices. Each digital point in the
message must be programmed to carry the state of a specific FlexLogic operand. The setting above is used to select the
operand which represents a specific UserSt function (as selected by the user) to be transmitted.
For more information on GSSE/GOOSE messaging, refer to Remote Inputs/Outputs Overview in the Remote
Devices section.
NOTE
5.8.9 RESETTING
5
PATH: SETTINGS INPUTS/OUTPUTS RESETTING
Some events can be programmed to latch the faceplate LED event indicators and the target message on the display. Once
set, the latching mechanism will hold all of the latched indicators or messages in the set state after the initiating condition
has cleared until a RESET command is received to return these latches (not including FlexLogic latches) to the reset state.
The RESET command can be sent from the faceplate Reset button, a remote device via a communications channel, or any
programmed operand.
When the RESET command is received by the relay, two FlexLogic operands are created. These operands, which are
stored as events, reset the latches if the initiating condition has cleared. The three sources of RESET commands each cre-
ate the RESET OP FlexLogic operand. Each individual source of a RESET command also creates its individual operand
RESET OP (PUSHBUTTON), RESET OP (COMMS) or RESET OP (OPERAND) to identify the source of the command. The setting
shown above selects the operand that will create the RESET OP (OPERAND) operand.
a) DIRECT INPUTS
PATH: SETTINGS INPUTS/OUTPUTS DIRECT INPUTS DIRECT INPUT 1(32)
These settings specify how the direct input information is processed. The DIRECT INPUT 1 NAME setting allows the user to
assign a descriptive name to the direct input. The DIRECT INPUT 1 DEVICE ID represents the source of direct input 1. The
specified direct input is driven by the device identified here.
The DIRECT INPUT 1 BIT NUMBER is the bit number to extract the state for direct input 1. Direct Input 1 is driven by the bit
identified as DIRECT INPUT 1 BIT NUMBER. This corresponds to the direct output number of the sending device.
The DIRECT INPUT 1 DEFAULT STATE represents the state of the direct input when the associated direct device is offline. The
b) DIRECT OUTPUTS
PATH: SETTINGS INPUTS/OUTPUTS DIRECT OUTPUTS DIRECT OUTPUT 1(32)
The DIRECT OUT 1 NAME setting allows the user to assign a descriptive name to the direct output. The DIR OUT 1 OPERAND is
the FlexLogic operand that determines the state of this direct output.
c) APPLICATION EXAMPLES
The examples introduced in the earlier Direct inputs and outputs section (part of the Product Setup section) are continued
below to illustrate usage of the direct inputs and outputs.
TX1
UR IED 1
RX1
TX1
UR IED 2
RX1
Figure 5–173: INPUT AND OUTPUT EXTENSION VIA DIRECT INPUTS AND OUTPUTS
Assume contact input 1 from UR IED 2 is to be used by UR IED 1. The following settings should be applied (Direct Input 5
and bit number 12 are used, as an example):
UR IED 1: DIRECT INPUT 5 DEVICE ID = “2” UR IED 2: DIRECT OUT 12 OPERAND = “Cont Ip 1 On”
DIRECT INPUT 5 BIT NUMBER = “12”
The Cont Ip 1 On operand of UR IED 2 is now available in UR IED 1 as DIRECT INPUT 5 ON.
EXAMPLE 2: INTERLOCKING BUSBAR PROTECTION
A simple interlocking busbar protection scheme can be accomplished by sending a blocking signal from downstream
devices, say 2, 3 and 4, to the upstream device that monitors a single incomer of the busbar, as shown in the figure below.
5
UR IED 1 BLOCK
842712A1.CDR
UR IED 1 UR IED 2
UR IED 3
842713A1.CDR
RX1
UR IED 3
TX1
842714A1.CDR
UR IED 1 UR IED 2
DIRECT OUT 2 = HYB POTT TX1 DIRECT INPUT 5
DIRECT INPUT 5 DIRECT OUT 2 = HYB POTT TX1
DIRECT INPUT 6 DIRECT OUT 4 = DIRECT INPUT 6
DIRECT OUT 3 = DIRECT INPUT 5
DIRECT INPUT 6
842717A1.CDR
Figure 5–177: SIGNAL FLOW FOR DIRECT INPUT AND OUTPUT – EXAMPLE 3
In three-terminal applications, both the remote terminals must grant permission to trip. Therefore, at each terminal, direct
inputs 5 and 6 should be ANDed in FlexLogic and the resulting operand configured as the permission to trip (HYB POTT RX1
setting).
a) OVERVIEW
5
The relay provides sixteen teleprotection inputs on communications channel 1 (numbered 1-1 through 1-16) and sixteen
teleprotection inputs on communications channel 2 (on two-terminals two-channel and three-terminal systems only, num-
bered 2-1 through 2-16). The remote relay connected to channels 1 and 2 of the local relay is programmed by assigning
FlexLogic operands to be sent via the selected communications channel. This allows the user to create distributed protec-
tion and control schemes via dedicated communications channels. Some examples are directional comparison pilot
schemes and direct transfer tripping. It should be noted that failures of communications channels will affect teleprotection
functionality. The teleprotection function must be enabled to utilize the inputs.
b) TELEPROTECTION INPUTS
PATH: SETTINGS INPUTS/OUTPUTS TELEPROTECTION TELEPROT INPUTS
TELEPROT INPUTS TELEPROT INPUT 1-1 Range: Off, On, Latest/Off, Latest/On
DEFAULT: Off
TELEPROT INPUT 1-2 Range: Off, On, Latest/Off, Latest/On
MESSAGE
DEFAULT: Off
Setting the TELEPROT INPUT ~~ DEFAULT setting to “On” defaults the input to logic 1 when the channel fails. A value of “Off”
defaults the input to logic 0 when the channel fails.
The “Latest/On” and “Latest/Off” values freeze the input in case of lost communications. If the latest state is not known,
such as after relay power-up but before the first communication exchange, then the input defaults to logic 1 for “Latest/On”
and logic 0 for “Latest/Off”.
c) TELEPROTECTION OUTPUTS
PATH: SETTINGS INPUTS/OUTPUTS TELEPROTECTION TELEPROT OUTPUTS
5 MESSAGE
TELEPROT OUTPUT 2-16:
Off
Range: FlexLogic operand
As the following figure demonstrates, processing of the teleprotection inputs/outputs is dependent on the number of com-
munication channels and terminals. On two-terminal two-channel systems, they are processed continuously on each chan-
nel and mapped separately per channel. Therefore, to achieve redundancy, the user must assign the same operand on
both channels (teleprotection outputs at the sending end or corresponding teleprotection inputs at the receiving end). On
three-terminal two-channel systems, redundancy is achieved by programming signal re-transmittal in the case of channel
failure between any pair of relays.
UR-1 UR-2
ACTUAL VALUES SETTING
CHANNEL 1 STATUS: TELEPROT INPUT 1-1
DEFAULT:
SETTING (same for 1-2...1-16)
TELEPROT OUTPUT 1-1:
(same for 1-2...1-16) On FLEXLOGIC OPERAND
Fail
Off (Flexlogic Operand) Off TELEPRO INPUT 1-1 On
OK OR
(same for 1-2...1-16)
UR-2 or UR-3
ACTUAL VALUES SETTING
CHANNEL 2 STATUS: TELEPROT INPUT 2-1
DEFAULT:
SETTING (same for 2-2...2-16)
TELEPROT OUTPUT 2-1:
(same for 1-2...1-16) On FLEXLOGIC OPERAND
Fail
Off TELEPRO INPUT 2-1 On
Off (Flexlogic Operand) OK OR
(same for 2-2...2-16)
842750A2.CDR
The IEC 61850 GOOSE analog inputs feature allows the transmission of analog values between any two UR-series
devices. The following settings are available for each GOOSE analog input.
• ANALOG 1 DEFAULT: This setting specifies the value of the GOOSE analog input when the sending device is offline
and the ANALOG 1 DEFAULT MODE is set to “Default Value”.This setting is stored as an IEEE 754 / IEC 60559 floating
point number. Because of the large range of this setting, not all possible values can be stored. Some values may be
rounded to the closest possible floating point number.
• ANALOG 1 DEFAULT MODE: When the sending device is offline and this setting is “Last Known”, the value of the
GOOSE analog input remains at the last received value. When the sending device is offline and this setting value is
“Default Value”, then the value of the GOOSE analog input is defined by the ANALOG 1 DEFAULT setting.
• GOOSE ANALOG 1 UNITS: This setting specifies a four-character alphanumeric string that can is used in the actual
values display of the corresponding GOOSE analog input value.
• GOOSE ANALOG 1 PU: This setting specifies the per-unit base factor when using the GOOSE analog input FlexAna-
log values in other D60 features, such as FlexElements. The base factor is applied to the GOOSE analog input Flex-
Analog quantity to normalize it to a per-unit quantity. The base units are described in the following table.
The GOOSE analog input FlexAnalog values are available for use in other D60 functions that use FlexAnalog values.
5 PATH: SETTINGS INPUTS/OUTPUTS IEC 61850 GOOSE UINTEGERS GOOSE UINTEGER INPUT 1(16)
The IEC 61850 GOOSE uinteger inputs feature allows the transmission of FlexInteger values between any two UR-series
devices. The following settings are available for each GOOSE uinteger input.
• UINTEGER 1 DEFAULT: This setting specifies the value of the GOOSE uinteger input when the sending device is
offline and the UINTEGER 1 DEFAULT MODE is set to “Default Value”.This setting is stored as a 32-bit unsigned integer
number.
• UINTEGER 1 DEFAULT MODE: When the sending device is offline and this setting is “Last Known”, the value of the
GOOSE uinteger input remains at the last received value. When the sending device is offline and this setting value is
“Default Value”, then the value of the GOOSE uinteger input is defined by the UINTEGER 1 DEFAULT setting.
The GOOSE integer input FlexInteger values are available for use in other D60 functions that use FlexInteger values.
Hardware and software is provided to receive signals from external transducers and convert these signals into a digital for-
mat for use as required. The relay will accept inputs in the range of –1 to +20 mA DC, suitable for use with most common
transducer output ranges; all inputs are assumed to be linear over the complete range. Specific hardware details are con-
tained in chapter 3.
Before the dcmA input signal can be used, the value of the signal measured by the relay must be converted to the range
and quantity of the external transducer primary input parameter, such as DC voltage or temperature. The relay simplifies
this process by internally scaling the output from the external transducer and displaying the actual primary parameter.
5
dcmA input channels are arranged in a manner similar to CT and VT channels. The user configures individual channels
with the settings shown here.
The channels are arranged in sub-modules of two channels, numbered from 1 through 8 from top to bottom. On power-up,
the relay will automatically generate configuration settings for every channel, based on the order code, in the same general
manner that is used for CTs and VTs. Each channel is assigned a slot letter followed by the row number, 1 through 8 inclu-
sive, which is used as the channel number. The relay generates an actual value for each available input channel.
Settings are automatically generated for every channel available in the specific relay as shown above for the first channel of
a type 5F transducer module installed in slot H.
The function of the channel may be either “Enabled” or “Disabled”. If “Disabled”, no actual values are created for the chan-
nel. An alphanumeric “ID” is assigned to each channel; this ID will be included in the channel actual value, along with the
programmed units associated with the parameter measured by the transducer, such as volts, °C, megawatts, etc. This ID is
also used to reference the channel as the input parameter to features designed to measure this type of parameter. The
DCMA INPUT H1 RANGE setting specifies the mA DC range of the transducer connected to the input channel.
The DCMA INPUT H1 MIN VALUE and DCMA INPUT H1 MAX VALUE settings are used to program the span of the transducer in
primary units. For example, a temperature transducer might have a span from 0 to 250°C; in this case the DCMA INPUT H1
MIN VALUE value is “0” and the DCMA INPUT H1 MAX VALUE value is “250”. Another example would be a watts transducer with
a span from –20 to +180 MW; in this case the DCMA INPUT H1 MIN VALUE value would be “–20” and the DCMA INPUT H1 MAX
VALUE value “180”. Intermediate values between the min and max values are scaled linearly.
Hardware and software is provided to receive signals from external resistance temperature detectors and convert these
signals into a digital format for use as required. These channels are intended to be connected to any of the RTD types in
common use. Specific hardware details are contained in chapter 3.
RTD input channels are arranged in a manner similar to CT and VT channels. The user configures individual channels with
the settings shown here.
The channels are arranged in sub-modules of two channels, numbered from 1 through 8 from top to bottom. On power-up,
the relay will automatically generate configuration settings for every channel, based on the order code, in the same general
manner that is used for CTs and VTs. Each channel is assigned a slot letter followed by the row number, 1 through 8 inclu-
sive, which is used as the channel number. The relay generates an actual value for each available input channel.
Settings are automatically generated for every channel available in the specific relay as shown above for the first channel of
a type 5C transducer module installed in the first available slot.
The function of the channel may be either “Enabled” or “Disabled”. If “Disabled”, there will not be an actual value created for
5 the channel. An alphanumeric ID is assigned to the channel; this ID will be included in the channel actual values. It is also
used to reference the channel as the input parameter to features designed to measure this type of parameter. Selecting the
type of RTD connected to the channel configures the channel.
Actions based on RTD overtemperature, such as trips or alarms, are done in conjunction with the FlexElements feature. In
FlexElements, the operate level is scaled to a base of 100°C. For example, a trip level of 150°C is achieved by setting the
operate level at 1.5 pu. FlexElement operands are available to FlexLogic for further interlocking or to operate an output
contact directly.
Refer to the following table for reference temperature values for each RTD type.
DCMA OUTPUT H1 DCMA OUTPUT H1 Range: Off, any analog actual value parameter
SOURCE: Off
DCMA OUTPUT H1 Range: –1 to 1 mA, 0 to 1 mA, 4 to 20 mA
MESSAGE
RANGE: –1 to 1 mA
DCMA OUTPUT H1 Range: –90.000 to 90.000 pu in steps of 0.001
MESSAGE
MIN VAL: 0.000 pu
DCMA OUTPUT H1 Range: –90.000 to 90.000 pu in steps of 0.001
MESSAGE
MAX VAL: 1.000 pu
Hardware and software is provided to generate dcmA signals that allow interfacing with external equipment. Specific hard-
ware details are contained in chapter 3. The dcmA output channels are arranged in a manner similar to transducer input or
CT and VT channels. The user configures individual channels with the settings shown below.
The channels are arranged in sub-modules of two channels, numbered 1 through 8 from top to bottom. On power-up, the
relay automatically generates configuration settings for every channel, based on the order code, in the same manner used
for CTs and VTs. Each channel is assigned a slot letter followed by the row number, 1 through 8 inclusive, which is used as
the channel number.
Both the output range and a signal driving a given output are user-programmable via the following settings menu (an exam-
ple for channel M5 is shown).
5 The relay checks the driving signal (x in equations below) for the minimum and maximum limits, and subsequently re-
scales so the limits defined as MIN VAL and MAX VAL match the output range of the hardware defined as RANGE. The follow-
ing equation is applied:
The feature is intentionally inhibited if the MAX VAL and MIN VAL settings are entered incorrectly, e.g. when MAX VAL – MIN
VAL< 0.1 pu. The resulting characteristic is illustrated in the following figure.
Imax
OUTPUT CURRENT
Imin
DRIVING SIGNAL
MIN VAL MAX VAL 842739A1.CDR
The base unit for power (refer to the FlexElements section in this chapter for additional details) is:
P BASE = 115 V 120 1.2 kA = 16.56 MW (EQ 5.36)
The minimum and maximum power values to be monitored (in pu) are:
– 20.65 MW 20.65 MW
minimum power = ------------------------------ = – 1.247 pu, maximum power = --------------------------- = 1.247 pu (EQ 5.37)
16.56 MW 16.56 MW
The following settings should be entered:
DCMA OUTPUT H1 SOURCE: “SRC 1 P”
DCMA OUTPUT H1 RANGE: “–1 to 1 mA”
DCMA OUTPUT H1 MIN VAL: “–1.247 pu”
DCMA OUTPUT H1 MAX VAL: “1.247 pu”
With the above settings, the output will represent the power with the scale of 1 mA per 20.65 MW. The worst-case error for
this application can be calculated by superimposing the following two sources of error:
• ±0.5% of the full scale for the analog output module, or 0.005 1 – – 1 20.65 MW = 0.207 MW
• ±1% of reading error for the active power at power factor of 0.9
For example at the reading of 20 MW, the worst-case error is 0.01 20 MW + 0.207 MW = 0.407 MW.
EXAMPLE: CURRENT MONITORING
The phase A current (true RMS value) is to be monitored via the H2 current output working with the range from 4 to 20 mA.
The CT ratio is 5000:5 and the maximum load current is 4200 A. The current should be monitored from 0 A upwards, allow-
ing for 50% overload.
The phase current with the 50% overload margin is:
The base unit for current (refer to the FlexElements section in this chapter for additional details) is:
I BASE = 5 kA (EQ 5.39)
The minimum and maximum power values to be monitored (in pu) are:
0 kA 6.3 kA
minimum current = ------------ = 0 pu, maximum current = ----------------- = 1.26 pu (EQ 5.40)
5 kA 5 kA
The following settings should be entered:
DCMA OUTPUT H2 SOURCE: “SRC 1 Ia RMS”
DCMA OUTPUT H2 RANGE: “4 to 20 mA”
DCMA OUTPUT H2 MIN VAL: “0.000 pu”
DCMA OUTPUT H2 MAX VAL: “1.260 pu”
The worst-case error for this application could be calculated by superimposing the following two sources of error:
• ±0.5% of the full scale for the analog output module, or 0.005 20 – 4 6.3 kA = 0.504 kA
• ±0.25% of reading or ±0.1% of rated (whichever is greater) for currents between 0.1 and 2.0 of nominal
For example, at the reading of 4.2 kA, the worst-case error is max(0.0025 4.2 kA, 0.001 5 kA) + 0.504 kA = 0.515 kA.
EXAMPLE: VOLTAGE MONITORING
A positive-sequence voltage on a 400 kV system measured via source 2 is to be monitored by the dcmA H3 output with a
range of 0 to 1 mA. The VT secondary setting is 66.4 V, the VT ratio setting is 6024, and the VT connection setting is
“Delta”. The voltage should be monitored in the range from 70% to 110% of nominal.
5 The minimum and maximum positive-sequence voltages to be monitored are:
400 kV 400 kV
V min = 0.7 ------------------- = 161.66 kV, V max = 1.1 ------------------- = 254.03 kV (EQ 5.41)
3 3
The base unit for voltage (refer to the FlexElements section in this chapter for additional details) is:
V BASE = 0.0664 kV 6024 = 400 kV (EQ 5.42)
The minimum and maximum voltage values to be monitored (in pu) are:
161.66 kV 254.03 kV
minimum voltage = --------------------------- = 0.404 pu, maximum voltage = --------------------------- = 0.635 pu (EQ 5.43)
400 kV 400 kV
The following settings should be entered:
DCMA OUTPUT H3 SOURCE: “SRC 2 V_1 mag”
DCMA OUTPUT H3 RANGE: “0 to 1 mA”
DCMA OUTPUT H3 MIN VAL: “0.404 pu”
DCMA OUTPUT H3 MAX VAL: “0.635 pu”
The limit settings differ from the expected 0.7 pu and 1.1 pu because the relay calculates the positive-sequence quantities
scaled to the phase-to-ground voltages, even if the VTs are connected in “Delta” (refer to the Metering conventions section
in chapter 6), while at the same time the VT nominal voltage is 1 pu for the settings. Consequently the settings required in
this example differ from naturally expected by the factor of 3 .
The worst-case error for this application could be calculated by superimposing the following two sources of error:
• ±0.5% of the full scale for the analog output module, or 0.005 1 – 0 254.03 kV = 1.27 kV
• ±0.5% of reading
For example, under nominal conditions, the positive-sequence reads 230.94 kV and the worst-case error is
0.005 x 230.94 kV + 1.27 kV = 2.42 kV.
The D60 provides a test facility to verify the functionality of contact inputs and outputs, some communication channels and
the phasor measurement unit (where applicable), using simulated conditions. The test mode is indicated on the relay face-
plate by a Test Mode LED indicator.
The test mode may be in any of three states: disabled, isolated, or forcible.
In the “Disabled” mode, D60 operation is normal and all test features are disabled.
In the “Isolated” mode, the D60 is prevented from performing certain control actions, including tripping via contact outputs.
All relay contact outputs, including latching outputs, are disabled. Channel tests and phasor measurement unit tests remain
usable on applicable UR-series models.
In the “Forcible” mode, the operand selected by the TEST MODE FORCING setting controls the relay inputs and outputs. If the
test mode is forcible, and the operand assigned to the TEST MODE FORCING setting is “Off”, the D60 inputs and outputs oper-
ate normally. If the test mode is forcible, and the operand assigned to the TEST MODE FORCING setting is “On”, the D60 con-
tact inputs and outputs are forced to the values specified in the following sections. Forcing may be controlled by manually
changing the operand selected by the TEST MODE FORCING setting between on and off, or by selecting a user-programma-
ble pushbutton, contact input, or communication-based input operand. Channel tests and phasor measurement unit tests
remain usable on applicable UR-series models.
5
Communications based inputs and outputs remain fully operational in test mode. If a control action is programmed
using direct inputs and outputs or remote inputs and outputs, then the test procedure must take this into account.
NOTE
When in “Forcible” mode, the operand selected by the TEST MODE FORCING setting dictates further response of the D60 to
testing conditions. To force contact inputs and outputs through relay settings, set TEST MODE FORCING to “On”. To force con-
tact inputs and outputs through a user-programmable condition, such as FlexLogic operand (pushbutton, digital input, com-
munication-based input, or a combination of these), set TEST MODE FORCING to the desired operand. The contact input or
output is forced when the selected operand assumes a logic 1 state.
The D60 remains fully operational in test mode, allowing for various testing procedures. In particular, the protection and
control elements, FlexLogic, and communication-based inputs and outputs function normally.
The only difference between the normal operation and the test mode is the behavior of the input and output contacts. The
contact inputs can be forced to report as open or closed or remain fully operational, whereas the contact outputs can be
forced to open, close, freeze, or remain fully operational. The response of the digital input and output contacts to the test
mode is programmed individually for each input and output using the force contact inputs and force contact outputs test
functions described in the following sections.
The test mode state is indicated on the relay faceplate by a combination of the Test Mode LED indicator, the In-Service LED
indicator, and by the critical fail relay, as shown in the following table.
The TEST MODE FUNCTION setting can only be changed by a direct user command. Following a restart, power up, settings
upload, or firmware upgrade, the test mode will remain at the last programmed value. This allows a D60 that has been
placed in isolated mode to remain isolated during testing and maintenance activities. On restart, the TEST MODE FORCING
setting and the force contact input and force contact output settings all revert to their default states.
5 FORCE CONTACT
INPUTS
FORCE Cont Ip 1
:Disabled
Range: Disabled, Open, Closed
The relay digital inputs (contact inputs) could be pre-programmed to respond to the test mode in the following ways:
• If set to “Disabled”, the input remains fully operational. It is controlled by the voltage across its input terminals and can
be turned on and off by external circuitry. This value should be selected if a given input must be operational during the
test. This includes, for example, an input initiating the test, or being a part of a user pre-programmed test sequence.
• If set to “Open”, the input is forced to report as opened (Logic 0) for the entire duration of the test mode regardless of
the voltage across the input terminals.
• If set to “Closed”, the input is forced to report as closed (Logic 1) for the entire duration of the test mode regardless of
the voltage across the input terminals.
The force contact inputs feature provides a method of performing checks on the function of all contact inputs. Once
enabled, the relay is placed into test mode, allowing this feature to override the normal function of contact inputs. The Test
Mode LED will be on, indicating that the relay is in test mode. The state of each contact input may be programmed as “Dis-
abled”, “Open”, or “Closed”. All contact input operations return to normal when all settings for this feature are disabled.
The relay contact outputs can be pre-programmed to respond to the test mode.
If set to “Disabled”, the contact output remains fully operational. If operates when its control operand is logic 1 and will
resets when its control operand is logic 0. If set to “Energized”, the output will close and remain closed for the entire dura-
tion of the test mode, regardless of the status of the operand configured to control the output contact. If set to “De-ener-
gized”, the output will open and remain opened for the entire duration of the test mode regardless of the status of the
operand configured to control the output contact. If set to “Freeze”, the output retains its position from before entering the
test mode, regardless of the status of the operand configured to control the output contact.
These settings are applied two ways. First, external circuits may be tested by energizing or de-energizing contacts. Sec-
ond, by controlling the output contact state, relay logic may be tested and undesirable effects on external circuits avoided.
Example 1: Initiating test mode through user-programmable pushbutton 1
For example, the test mode can be initiated from user-programmable pushbutton 1. The pushbutton will be programmed as
“Latched” (pushbutton pressed to initiate the test, and pressed again to terminate the test). During the test, digital input 1
5
should remain operational, digital inputs 2 and 3 should open, and digital input 4 should close. Also, contact output 1 should
freeze, contact output 2 should open, contact output 3 should close, and contact output 4 should remain fully operational.
The required settings are shown below.
To enable user-programmable pushbutton 1 to initiate the test mode, make the following changes in the SETTINGS
TESTING TEST MODE menu: TEST MODE FUNCTION: “Enabled” and TEST MODE INITIATE: “PUSHBUTTON 1 ON”
Make the following changes to configure the contact inputs and outputs. In the SETTINGS TESTING FORCE CONTACT
INPUTS and FORCE CONTACT OUTPUTS menus, set:
FORCE Cont Ip 1: “Disabled”, FORCE Cont Ip 2: “Open”, FORCE Cont Ip 3: “Open”, and FORCE Cont Ip 4: “Closed”
FORCE Cont Op 1: “Freeze”, FORCE Cont Op 2: “De-energized”, FORCE Cont Op 3: “Energized”,
and FORCE Cont Op 4: “Disabled”
Example 2: Initiating a test from user-programmable pushbutton 1 or through remote input 1
In this example, the test can be initiated locally from user-programmable pushbutton 1 or remotely through remote input 1.
Both the pushbutton and the remote input will be programmed as “Latched”. Write the following FlexLogic equation:
Set the user-programmable pushbutton as latching by changing SETTINGS PRODUCT SETUP USER-PROGRAMMABLE
PUSHBUTTONS USER PUSHBUTTON 1 PUSHBUTTON 1 FUNCTION to “Latched”. To enable either pushbutton 1 or remote
input 1 to initiate the Test mode, make the following changes in the SETTINGS TESTING TEST MODE menu:
TEST MODE FUNCTION: “Enabled” and TEST MODE INITIATE: “VO1”
5 MESSAGE
ANGLE: 0.00°
PMU 1 IA TEST Range: 0.000 to 9.999 kA in steps of 0.001
MESSAGE
MAGNITUDE: 1.000 kA
PMU 1 IA TEST Range: –180.00 to 180.00° in steps of 0.05
MESSAGE
ANGLE: –10.00°
PMU 1 IB TEST Range: 0.000 to 9.999 kA in steps of 0.001
MESSAGE
MAGNITUDE: 1.000 kA
PMU 1 IB TEST Range: –180.00 to 180.00° in steps of 0.05
MESSAGE
ANGLE: –130.00°
PMU 1 IC TEST Range: 0.000 to 9.999 kA in steps of 0.001
MESSAGE
MAGNITUDE: 1.000 kA
PMU 1 IC TEST Range: –180.00 to 180.00° in steps of 0.05
MESSAGE
ANGLE: 110.00°
PMU 1 IG TEST Range: 0.000 to 9.999 kA in steps of 0.001
MESSAGE
MAGNITUDE: 0.000 kA
PMU 1 IG TEST Range: –180.00 to 180.00° in steps of 0.05
MESSAGE
ANGLE: 0.00°
PMU 1 TEST Range: 20.000 to 60.000 Hz in steps of 0.001
MESSAGE
FREQUENCY: 60.000 Hz
PMU 1 TEST Range: –10.000 to 10.000 Hz/s in steps of 0.001
MESSAGE
df/dt: 0.000 Hz/s
The relay must be in test mode to use the PMU test mode. That is, the TESTING TEST MODE FUNCTION setting must be
“Enabled” and the TESTING TEST MODE INITIATE initiating signal must be “On”.
During the PMU test mode, the physical channels (VA, VB, VC, VX, IA, IB, IC, and IG), frequency, and rate of change of fre-
quency are substituted with user values, while the symmetrical components are calculated from the physical channels. The
test values are not explicitly marked in the outgoing data frames. When required, it is recommended to use the user-pro-
grammable digital channels to signal the C37.118 client that test values are being sent in place of the real measurements.
The UR Synchrophasor Implementation defines a test mode which sends a pre-defined set of Synchrophasors out over the
communication channel when the test mode function setting is enabled. In test mode, the following actions take place:
a. The Data Invalid / Test Mode bit (bit 15 in the STAT word) is set.
b. The Sim bit in all output datasets is set.
IEC 61850
See page 6-21.
GOOSE ANALOGS
WATTMETRIC
See page 6-22.
GROUND FAULT 1
WATTMETRIC
See page 6-22.
6 GROUND FAULT 2
PHASOR MEASUREMENT
See page 6-22.
UNIT
PMU AGGREGATOR
See page 6-23.
TRANSDUCER I/O
See page 6-23.
DCMA INPUTS
TRANSDUCER I/O
See page 6-23.
RTD INPUTS
MAINTENANCE
See page 6-26.
6.2STATUS
For status reporting, ‘On’ represents Logic 1 and ‘Off’ represents Logic 0.
NOTE
The present status of the contact inputs is shown here. The first line of a message display indicates the ID of the contact
input. For example, ‘Cont Ip 1’ refers to the contact input in terms of the default name-array index. The second line of the
display indicates the logic state of the contact input.
6 Virt Ip 64
Range: On, Off
MESSAGE
Off
The present status of the 64 virtual inputs is shown here. The first line of a message display indicates the ID of the virtual
input. For example, ‘Virt Ip 1’ refers to the virtual input in terms of the default name. The second line of the display indicates
the logic state of the virtual input.
REMOTE DPS INPUTS REMOTE DPS INPUT 1 Range: On, Off, Intermediate, Bad
STATUS: Bad
REMOTE DPS INPUT 2 Range: On, Off, Intermediate, Bad
MESSAGE
STATUS: Bad
The present state of the remote double-point status inputs is shown here. The actual values indicate if the remote double-
point status inputs are in the on (close), off (open), intermediate, or bad state.
The present state of teleprotection inputs from communication channels 1 and 2 are shown here. The state displayed will
be that of corresponding remote output unless the channel is declared failed.
CONTACT OUTPUTS Cont Op 1 Range: On, Off, VOff, VOn, IOn, IOff
Off
Cont Op 2 Range: On, Off, VOff, VOn, IOn, IOff
MESSAGE
Off
The present state of the contact outputs is shown here. The first line of a message display indicates the ID of the contact
output. For example, ‘Cont Op 1’ refers to the contact output in terms of the default name-array index. The second line of
the display indicates the logic state of the contact output.
For form-A contact outputs, the state of the voltage and current detectors is displayed as Off, VOff, IOff, On, IOn,
and VOn. For form-C contact outputs, the state is displayed as Off or On.
NOTE
The present state of up to 96 virtual outputs is shown here. The first line of a message display indicates the ID of the virtual
output. For example, ‘Virt Op 1’ refers to the virtual output in terms of the default name-array index. The second line of the
display indicates the logic state of the virtual output, as calculated by the FlexLogic equation for that output.
6.2.8 AUTORECLOSE
The present state of the programmed remote devices is shown here. The ALL REMOTE DEVICES ONLINE message indicates
whether or not all programmed remote devices are online. If the corresponding state is "No", then at least one required
remote device is not online.
b) STATISTICS
PATH: ACTUAL VALUES STATUS REMOTE DEVICES STATISTICS REMOTE DEVICE 1(16)
Statistical data (two types) for up to 16 programmed remote devices is shown here.
The STNUM number is obtained from the indicated remote device and increments whenever a change of state of at least
one item occurs in the GSSE/GOOSE message. The SQNUM number is obtained from the indicated remote device and
increments whenever a GSSE/GOOSE message, without a state change, is sent. When the GSSE/GOOSE message
trasmits a state change, the SQNUM resets to 0. This number rolls over to zero when a count of 4,294,967,295 is incre-
mented.
PATH: ACTUAL VALUES STATUS DIGITAL COUNTERS DIGITAL COUNTERS Counter 1(8)
The present status of the eight digital counters is shown here. The status of each counter, with the user-defined counter
name, includes the accumulated and frozen counts (the count units label will also appear). Also included, is the date and
time stamp for the frozen count. The COUNTER 1 MICROS value refers to the microsecond portion of the time stamp.
6
6.2.11 SELECTOR SWITCHES
The display shows both the current position and the full range. The current position only (an integer from 0 through 7) is the
actual value.
There are 256 FlexStateTM bits available. The second line value indicates the state of the given FlexState bit.
6.2.13 ETHERNET
These values indicate the status of the first, second, and third Ethernet links.
REAL TIME CLOCK RTC Sync Source: Range: See text below
SYNCHRONIZING None
The RTC Sync Source actual value is the time synchronizing source the relay is using at present. Possible sources are:
Port 1 PTP Clock, Port 2 PTP Clock, Port 3 PTP Clock, IRIG-B, SNTP, and None.
The Grandmaster ID is the grandmasterIdentity code being received from the present PTP grandmaster, if any. When the
relay is not using any PTP grandmaster, this actual value is zero. The grandmasterIdentity code is specified by PTP to be
globally unique, so one can always know which clock is grandmaster in a system with multiple grandmaster-capable clocks.
Accuracy is the estimated maximum time error at present in the RTC, considering the quality information imbedded in the
received time signal. The value 999,999,999 indicates that the magnitude of the estimated error is one second or more, or
that the error cannot be estimated.
PORT 1…3 PTP STATE is the present state of the port’s PTP clock. The PTP clock state is:
• DISABLED is the port’s function setting is Disabled,
• NO SIGNAL if enabled but no signal from an active master has been found and selected,
• CALIBRATING if an active master has been selected but lock is not at present established,
• SYNCH’D (NO PDELAY) if the port is synchronized, but the peer delay mechanism is non-operational, and
• SYNCHRONIZED if synchronized.
PTP-— IRIG-B DELTA is the time difference, measured in nanoseconds, between the fractional seconds portion of the time
being received via PTP and that being received via IRIG-B. A positive value indicates that PTP time is fast compared to
IRIG-B time.
The AVERAGE MSG RETURN TIME is the time taken for direct output messages to return to the sender in a direct input/output
ring configuration (this value is not applicable for non-ring configurations). This is a rolling average calculated for the last
ten messages. There are two return times for dual-channel communications modules.
The UNRETURNED MSG COUNT values (one per communications channel) count the direct output messages that do not
make the trip around the communications ring. The CRC FAIL COUNT values (one per communications channel) count the
direct output messages that have been received but fail the CRC check. High values for either of these counts may indicate
on a problem with wiring, the communication channel, or one or more relays. The UNRETURNED MSG COUNT and CRC FAIL
COUNT values can be cleared using the CLEAR DIRECT I/O COUNTERS command.
The DIRECT INPUT 1 to DIRECT INPUT (32) values represent the state of each direct input.
These actual values represent the state of direct devices 1 through 16.
UINT INPUT 16
MESSAGE
0
The D60 Line Distance Protection System is provided with optional IEC 61850 communications capability.
This feature is specified as a software option at the time of ordering. Refer to the Ordering section of chap-
The IEC 61850 GGIO5 integer input data points are displayed in this menu. The GGIO5 integer data values are received
via IEC 61850 GOOSE messages sent from other devices.
• CHANNEL 1 STATUS: This represents the receiver status of each channel. If the value is “OK”, teleprotection is
enabled and data is being received from the remote terminal; If the value is “FAIL”, teleprotection enabled and data is
not being received from the remote terminal. If “n/a”, teleprotection is disabled.
• CHANNEL 1 LOST PACKETS: Data is transmitted to the remote terminals in data packets at a rate of two packets per
cycle. The number of lost packets represents data packets lost in transmission; this count can be reset to 0 through the
COMMANDS CLEAR RECORDS menu.
• VALIDITY OF CHANNEL CONFIGURATION: This value displays the current state of the communications channel
identification check, and hence validity. If a remote relay ID does not match the programmed ID at the local relay, the
“FAIL” message will be displayed. The “N/A” value appears if the local relay ID is set to a default value of “0”, the chan-
nel is failed, or if the teleprotection inputs/outputs are not enabled.
These values specify the remaining number of TCP connections still available for each protocol. Every time a connection is
used, the remaining number of connections decrements. When released, the remaining number of connections increments.
If no connection is made over the specific protocol, the number equals the maximum number available for the specific pro-
tocol. 6
For example, the maximum number of Modbus TCP connections is 4. Once an EnerVista session is opened on a computer
connected to the UR over Ethernet, the Modbus TCP status shows 3. If the EnerVista application is closed, the Modbus
TCP status shows 4.
Note that the maximum number of PMU TCP connections matches the number of aggregators.
The Parallel Redundancy Protocol (PRP) defines a redundancy protocol for high availability in substation automation net-
works.
PATH: ACTUAL VALUES STATUS PRP
TOTAL RECEIVED PORT A is a counter for total messages received (either from DANPs or from SANs) on Port A.
TOTAL RECEIVED PORT B is a counter for total messages received (either from DANPs or from SANs) on Port B.
TOTAL ERRORS is a counter for total messages received with an error (bad port code, frame length too short).
MISMATCHES PORT A is a counter for total messages received with an error on Port A (PRP frame, but port received through
and LAN ID in the frame do not match).
MISMATCHES PORT B is a counter for total messages received with an error on Port B (PRP frame, but port received through
and LAN ID in the frame do not match).
Voltage +Q
VCG
WATTS = Positive IC
PF = Lead PF = Lag
VARS = Positive
PF = Lag IA
VAG -P +P
Current
IB IA
PF = Lag PF = Lead
UR RELAY
VBG -Q
M LOAD
- 1
Inductive Resistive S=VI
Generator
VCG
+Q
Voltage
PF = Lead PF = Lag
WATTS = Positive
IA
VARS = Negative IC
PF = Lead VAG -P +P
IA
Current
PF = Lag PF = Lead
IB
UR RELAY
VBG -Q
LOAD S=VI
6
- 2
Resistive
Inductive Resistive
M LOAD
VCG +Q
Voltage
PF = Lead PF = Lag
IB
IA
WATTS = Negative
VAG
VARS = Negative -P +P
PF = Lag
IA
IC PF = Lag PF = Lead
Current
VBG
-Q
UR RELAY
G S=VI
- 3
Generator
Resistive
LOAD
VCG
+Q
Voltage IB
PF = Lead PF = Lag
WATTS = Negative IA
VARS = Positive VAG -P +P
PF = Lead
IC
IA
Current
PF = Lag PF = Lead
VBG -Q
UR RELAY
G 827239AC.CDR
- 4
S=VI
Generator
Figure 6–1: FLOW DIRECTION OF SIGNED VALUES FOR WATTS AND VARS
-270o
-225o -315o
positive
angle
direction
-180o 0o
UR phase angle
reference
-135o -45o
6 -90o 827845A1.CDR
The zero-sequence voltage is not measurable under the Delta connection of instrument transformers and is defaulted to
zero. The table below shows an example of symmetrical components calculations for the ABC phase rotation.
Table 6–1: SYMMETRICAL COMPONENTS CALCULATION EXAMPLE
SYSTEM VOLTAGES, SEC. V * VT RELAY INPUTS, SEC. V SYMM. COMP, SEC. V
CONN.
VAG VBG VCG VAB VBC VCA F5AC F6AC F7AC V0 V1 V2
13.9 76.2 79.7 84.9 138.3 85.4 WYE 13.9 76.2 79.7 19.5 56.5 23.3
0° –125° –250° –313° –97° –241° 0° –125° –250° –192° –7° –187°
UNKNOWN (only V1 and V2 84.9 138.3 85.4 DELTA 84.9 138.3 85.4 N/A 56.5 23.3
can be determined) 0° –144° –288° 0° –144° –288° –54° –234°
* The power system voltages are phase-referenced – for simplicity – to VAG and VAB, respectively. This, however, is a
relative matter. It is important to remember that the D60 displays are always referenced as specified under SETTINGS
SYSTEM SETUP POWER SYSTEM FREQUENCY AND PHASE REFERENCE.
The example above is illustrated in the following figure.
6
reference
1
UR phase angle
A
reference
WYE VTs
C
B
0
2
U
re R ph
fe a
re se
nc a
e ng
le
A U
1
re R ph
fe a
re se
nc a
e ng
DELTA VTs le
C
B
2
827844A1.CDR
6.3.2 SOURCES
a) MAIN MENU
PATH: ACTUAL VALUES METERING SOURCE SRC1
This menu displays the metered values available for each source.
Metered values presented for each source depend on the phase and auxiliary VTs and phase and ground CTs assignments
for this particular source. For example, if no phase VT is assigned to this source, then any voltage, energy, and power val-
ues will be unavailable.
The metered phase current values are displayed in this menu. The "SRC 1" text will be replaced by whatever name was
programmed by the user for the associated source (see SETTINGS SYSTEM SETUP SIGNAL SOURCES).
The metered ground current values are displayed in this menu. The "SRC 1" text will be replaced by whatever name was
programmed by the user for the associated source (see SETTINGS SYSTEM SETUP SIGNAL SOURCES).
The metered phase voltage values are displayed in this menu. The "SRC 1" text will be replaced by whatever name was
programmed by the user for the associated source (see SETTINGS SYSTEM SETUP SIGNAL SOURCES).
The metered auxiliary voltage values are displayed in this menu. The "SRC 1" text will be replaced by whatever name was
programmed by the user for the associated source (see SETTINGS SYSTEM SETUP SIGNAL SOURCES).
f) POWER METERING
PATH: ACTUAL VALUES METERING SOURCE SRC 1 POWER
6
SRC 1 REAL POWER
MESSAGE
b: 0.000 W
SRC 1 REAL POWER
MESSAGE
c: 0.000 W
SRC 1 REACTIVE PWR
MESSAGE
3: 0.000 var
SRC 1 REACTIVE PWR
MESSAGE
a: 0.000 var
SRC 1 REACTIVE PWR
MESSAGE
b: 0.000 var
SRC 1 REACTIVE PWR
MESSAGE
c: 0.000 var
SRC 1 APPARENT PWR
MESSAGE
3: 0.000 VA
SRC 1 APPARENT PWR
MESSAGE
a: 0.000 VA
SRC 1 APPARENT PWR
MESSAGE
b: 0.000 VA
SRC 1 APPARENT PWR
MESSAGE
c: 0.000 VA
The metered values for real, reactive, and apparent power, as well as power factor, are displayed in this menu. The "SRC
1" text will be replaced by whatever name was programmed by the user for the associated source (see SETTINGS SYS-
TEM SETUP SIGNAL SOURCES).
g) ENERGY METERING
PATH: ACTUAL VALUES METERING SOURCE SRC 1 ENERGY
The metered values for real and reactive energy are displayed in this menu. The "SRC 1" text will be replaced by whatever
name was programmed by the user for the associated source (see SETTINGS SYSTEM SETUP SIGNAL SOURCES).
Because energy values are accumulated, these values should be recorded and then reset immediately prior to changing
CT or VT characteristics. 6
h) FREQUENCY METERING
PATH: ACTUAL VALUES METERING SOURCE SRC 1 FREQUENCY
The metered frequency values are displayed in this menu. The "SRC 1" text will be replaced by whatever name was pro-
grammed by the user for the associated source (see SETTINGS SYSTEM SETUP SIGNAL SOURCES).
SOURCE FREQUENCY is measured via software-implemented zero-crossing detection of an AC signal. The signal is either a
Clarke transformation of three-phase voltages or currents, auxiliary voltage, or ground current as per source configuration
(see the SYSTEM SETUP POWER SYSTEM settings). The signal used for frequency estimation is low-pass filtered. The
final frequency measurement is passed through a validation filter that eliminates false readings due to signal distortions and
transients.
The effective operating quantities of the sensitive directional power elements are displayed here. The display may be useful
to calibrate the feature by compensating the angular errors of the CTs and VTs with the use of the RCA and CALIBRATION
settings.
6.3.4 SYNCHROCHECK
The actual values menu for synchrocheck 2 is identical to that of synchrocheck 1. If a synchrocheck function setting is "Dis-
abled", the corresponding actual values menu item will not be displayed.
The tracking frequency is displayed here. The frequency is tracked based on the selection of the reference source with the
FREQUENCY AND PHASE REFERENCE setting in the SETTINGS SYSTEM SETUP POWER SYSTEM menu. Refer to the
Power System section of chapter 5 for additional details.
The metered frequency rate of change for the frequency rate of change elements is shown here.
6.3.7 FLEXELEMENTS™
FLEXELEMENT 1 FLEXELEMENT 1
OpSig: 0.000 pu
The operating signals for the FlexElements are displayed in pu values using the following definitions of the base units.
ANALOG INPUT 32
MESSAGE
0.000
The D60 Line Distance Protection System is provided with optional IEC 61850 communications capability.
This feature is specified as a software option at the time of ordering. Refer to the Ordering section of chap-
ter 2 for additional details.
The IEC 61850 GGIO3 analog input data points are displayed in this menu. The GGIO3 analog data values are received
via IEC 61850 GOOSE messages sent from other devices.
This menu displays the wattmetric zero-sequence directional element operating power values.
The above actual values are displayed without the corresponding time stamp as they become available per the recording
rate setting. Also, the recording post-filtering setting is applied to these values.
Actual values for the IEC 61850-90-5 PDU size are provided. These values allow you to know the approximate Ethernet
frame size for the data streams from each aggregator. This can help to estimate network loading. The PDU size shown in
the displays does not include the Ethernet, UDP, or IP layers. PDU sizes approaching approximately 1500 bytes result in
fragmented data frames, causing increased network traffic.
PATH: ACTUAL VALUES METERING TRANSDUCER I/O DCMA INPUTS DCMA INPUT xx
Actual values for each dcmA input channel that is enabled are displayed with the top line as the programmed channel ID
and the bottom line as the value followed by the programmed units.
PATH: ACTUAL VALUES METERING TRANSDUCER I/O RTD INPUTS RTD INPUT xx
Actual values for each RTD input channel that is enabled are displayed with the top line as the programmed channel ID and
the bottom line as the value.
NO FAULTS TO REPORT
or
FAULT REPORT 1 FAULT 1 Range: SRC 1, SRC 2, SRC 3, SRC 4
LINE ID: SRC 1
FAULT 1 DATE: Range: YYYY/MM/DD
MESSAGE
2000/08/11
FAULT 1 TIME: Range: HH:MM:SS.ssssss
MESSAGE
00:00:00.000000
FAULT 1 TYPE: Range: not available if the source VTs are in the “Delta”
MESSAGE configuration
ABG
FAULT 1 LOCATION Range: not available if the source VTs are in the “Delta”
MESSAGE configuration
00.0 km
FAULT 1 RECLOSE Range: where applicable
MESSAGE
SHOT: 0
The latest 15 fault reports can be stored. The most recent fault location calculation (when applicable) is displayed in this
menu, along with the date and time stamp of the event which triggered the calculation. See the SETTINGS PRODUCT
SETUP FAULT REPORTS menu for assigning the source and trigger for fault calculations. Refer to the COMMANDS
CLEAR RECORDS menu for manual clearing of the fault reports and to the SETTINGS PRODUCT SETUP CLEAR RELAY
RECORDS menu for automated clearing of the fault reports.
EVENT: 3 EVENT 3
MESSAGE
POWER ON DATE: 2000/07/14
EVENT: 2 EVENT 3
MESSAGE
POWER OFF TIME: 14:53:00.03405
EVENT: 1
MESSAGE Date and Time Stamps
EVENTS CLEARED
The event records menu shows the contextual data associated with up to the last 1024 events, listed in chronological order
from most recent to oldest. If all 1024 event records have been filled, the oldest record will be removed as a new record is
added. Each event record shows the event identifier/sequence number, cause, and date/time stamp associated with the
event trigger. Refer to the COMMANDS CLEAR RECORDS menu for clearing event records.
6.4.3 OSCILLOGRAPHY
This menu allows the user to view the number of triggers involved and number of oscillography traces available. The
CYCLES PER RECORD value is calculated to account for the fixed amount of data storage for oscillography. See the Oscillog-
raphy section of chapter 5 for additional details.
A trigger can be forced here at any time by setting “Yes” to the FORCE TRIGGER? command. Refer to the COMMANDS
CLEAR RECORDS menu for information on clearing the oscillography records.
The number of triggers applicable to the phasor measurement unit recorder is indicated by the NUMBER OF TRIGGERS value.
The status of the phasor measurement unit recorder is indicated as follows:
There is an identical menu for each of the breakers. The BKR 1 ARCING AMP values are in units of kA2-cycles. Refer to the
COMMANDS CLEAR RECORDS menu for clearing breaker arcing current records. The BREAKER OPERATING TIME is
defined as the slowest operating time of breaker poles that were initiated to open.
MODEL INFORMATION ORDER CODE LINE 1: Range: standard GE Multilin order code format;
D60-E00-HCL-F8F-H6H example order code shown
The shown data is illustrative only. A modification file number of 0 indicates that, currently, no modifications have been
installed.
COMMANDS
COMMANDS
MESSAGE
VIRTUAL INPUTS
COMMANDS
MESSAGE
CLEAR RECORDS
COMMANDS
MESSAGE
SET DATE AND TIME
COMMANDS
MESSAGE
RELAY MAINTENANCE
COMMANDS
MESSAGE
PMU ONE-SHOT
COMMANDS
MESSAGE
SECURITY
The commands menu contains relay directives intended for operations personnel. All commands can be protected from
unauthorized access via the command password; see the Security section of chapter 5 for details. The following flash mes-
sage appears after successfully command entry:
COMMAND
EXECUTED
The states of up to 64 virtual inputs are changed here. The first line of the display indicates the ID of the virtual input. The
second line indicates the current or selected status of the virtual input. This status will be a state off (logic 0) or on (logic 1).
This menu contains commands for clearing historical data such as the event records. Data is cleared by changing a com-
mand setting to “Yes” and pressing the ENTER key. After clearing data, the command setting automatically reverts to “No”.
7 7.1.4 SET DATE AND TIME
The date and time can be entered here via the faceplate keypad, but if the relay is synchronizing to an external time source
such as PTP, IRIGB or SNTP, the manually entered time will be quickly over-written. The time setting is based on the 24-
hour clock. The complete date, as a minimum, must be entered to allow execution of this command. The new time (if
entered) and date will take effect at the moment the ENTER key is clicked.
The timescale of the entered time should be local time, including daylight time where and when applicable.
This menu contains commands for relay maintenance purposes. Commands for the lamp test and order code are activated
by changing a command setting to “Yes” and pressing the ENTER key. The command setting will then automatically revert
to “No”. The service command is activated by entering a numerical code and pressing the ENTER key.
The PERFORM LAMPTEST command turns on all faceplate LEDs and display pixels for a short duration. The UPDATE
ORDER CODE command causes the relay to scan the backplane for the hardware modules and update the order code to
match. If an update occurs, the following message is shown.
UPDATING...
PLEASE WAIT
There is no impact if there have been no changes to the hardware modules. When an update does not occur, the ORDER
CODE NOT UPDATED message will be shown.
The SERVICE COMMAND is used to perform specific D60 service actions. Presently, there is only one service action avail-
able. Code “101” is used to clear factory diagnostic information stored in the non-volatile memory. If a code other than “101”
is entered, the command will be ignored and no actions will be taken. Various self-checking diagnostics are performed in
the background while the D60 is running, and diagnostic information is stored on the non-volatile memory from time to time
based on the self-checking result. Although the diagnostic information is cleared before the D60 is shipped from the factory,
the user may want to clear the diagnostic information for themselves under certain circumstances. For example, it may be
desirable to clear diagnostic information after replacement of hardware. Once the diagnostic information is cleared, all self-
checking variables are reset to their initial state and diagnostics will restart from scratch.
The REBOOT RELAY COMMAND reboots the relay so that changes to configuration settings can take effect. In most cases, if
changes are made to the configuration settings these changes do not take effect unless the relay is rebooted.
With the CyberSentry option, the Administrator or Operator role can initiate the Reboot Relay command. 7
NOTE 7.1.6 PHASOR MEASUREMENT UNIT ONE-SHOT
This feature allows pre-scheduling a PMU measurement at a specific point in time. This functionality can be used to test for
accuracy of the PMU, and for manual collection of synchronized measurements through the system, as explained below.
When enabled, the function continuously compares the present time with the pre-set PMU ONE-SHOT TIME. When the two
times match, the function compares the present sequence number of the measured synchrophasors with the pre-set PMU
ONE-SHOT SEQUENCE NUMBER. When the two numbers match, the function freezes the synchrophasor actual values and
the corresponding protocol data items for 30 seconds. This allows manual read-out of the synchrophasor values for the
pre-set time and pre-set sequence number (via the faceplate display, supported communication protocols such as Modbus
or DNP, and the EnerVista UR Setup software).
When freezing the actual values the function also asserts a PMU ONE-SHOT OP FlexLogic operand. This operand may be
configured to drive an output contact and trigger an external measuring device such as a digital scope with the intent to ver-
ify the accuracy of the PMU under test.
With reference to the figure below, the PMU one-shot function (when enabled) controls three FlexLogic operands:
• The PMU ONE-SHOT EXPIRED operand indicates that the one-shot operation has been executed, and the present time
is at least 30 seconds past the scheduled one-shot time.
• The PMU ONE-SHOT PENDING operand indicates that the one-shot operation is pending; that is, the present time is
before the scheduled one-shot time.
• The PMU ONE-SHOT OP operand indicates the one-shot operation and remains asserted for 30 seconds afterwards.
When the function is disabled, all three operands are de-asserted. The one-shot function applies to all logical PMUs of a
given D60 relay.
7 both the time reference signal (rising edge of the 1 pps signal of the IRIG-B time reference), and the measured waveform.
The high-accuracy high-sampling rate record of the two signals captured by the scope can be processed using digital tools
to verify the magnitude and phase angle with respect to the time reference signal. As both the time reference and the mea-
sured signals are raw inputs to the PMU under test, their independently captured record, processed using third-party soft-
ware, is a good reference point for accuracy calculations. Such a record proves useful when discussing the test results, and
should be retained as a part of the testing documentation.
Note that the PMU under such test does not have to be connected to a real GPS receiver as the accuracy is measured with
respect to the timing reference provided to the PMU and not to the absolute UTC time. Therefore a simple IRIG-B genera-
tor could be used instead. Also, the test set does not have to support GPS synchronization. Any stable signal source can
be used. If both the PMU under test and the test set use the timing reference, they should be driven from the same IRIG-B
signal: either the same GPS receiver or IRIG-B generator. Otherwise, the setpoints of the test set and the PMU measure-
ments should not be compared as they are referenced to different time scales.
Figure 7–2: USING THE PMU ONE-SHOT FEATURE TO TEST SYNCHROPHASOR MEASUREMENT ACCURACY
COLLECTING SYNCHRONIZED MEASUREMENTS AD HOC:
The one-shot feature can be used for ad hoc collection of synchronized measurements in the network. Two or more PMU
can be pre-scheduled to freeze their measurements at the same time. When frozen the measurements could be collected
using EnerVista UR Setup or a protocol client.
7.1.7 SECURITY
TARGETS
DIGITAL ELEMENT 1: Displayed only if targets for this element are active.
MESSAGE Example shown.
LATCHED
DIGITAL ELEMENT 48: Displayed only if targets for this element are active.
MESSAGE Example shown.
LATCHED
MESSAGE
The status of any active targets will be displayed in the targets menu. If no targets are active, the display will read NO
ACTIVE TARGETS:
When there are no active targets, the first target to become active will cause the display to immediately default to that mes-
sage. If there are active targets and the user is navigating through other messages, and when the default message timer
times out (i.e. the keypad has not been used for a determined period of time), the display will again default back to the tar-
get message.
The range of variables for the target messages is described below. Phase information will be included if applicable. If a tar-
get message status changes, the status with the highest priority will be displayed.
If a self test error is detected, a message appears indicating the cause of the error. For example UNIT NOT PROGRAMMED
indicates that the minimal relay settings have not been programmed.
7
7.2.3 RELAY SELF-TESTS
a) DESCRIPTION
The relay performs a number of self-test diagnostic checks to ensure device integrity. The two types of self-tests (major and
minor) are listed in the tables below. When either type of self-test error occurs, the Trouble LED Indicator will turn on and a
target message displayed. All errors record an event in the event recorder. Latched errors can be cleared by pressing the
RESET key, providing the condition is no longer present.
Major self-test errors also result in the following:
• The critical fail relay on the power supply module is de-energized.
• All other output relays are de-energized and are prevented from further operation.
• The faceplate In Service LED indicator is turned off.
• A RELAY OUT OF SERVICE event is recorded.
INCOMPATIBLE H/W:
Contact Factory (xxx)
• Latched target message: Yes.
• Description of problem: One or more installed hardware modules is not compatible with the D60 order code.
• How often the test is performed: Module dependent.
• What to do: Contact the factory and supply the failure code noted in the display. The “xxx” text identifies the failed mod-
ule (for example, F8L).
EQUIPMENT MISMATCH:
with 2nd line detail
• Latched target message: No.
• Description of problem: The configuration of modules does not match the order code stored in the D60.
• How often the test is performed: On power up. Afterwards, the backplane is checked for missing cards every five sec-
onds.
• What to do: Check all modules against the order code, ensure they are inserted properly, and cycle control power. If
the problem persists, contact the factory.
FLEXLOGIC ERROR:
with 2nd line detail
• Latched target message: No. 7
• Description of problem: A FlexLogic equation is incorrect.
• How often the test is performed: The test is event driven, performed whenever FlexLogic equations are modified.
• What to do: Finish all equation editing and use self tests to debug any errors.
MAINTENANCE ALERT:
Replace Battery
• Latched target message: Yes.
• Description of problem: The battery is not functioning.
• How often the test is performed: The battery is monitored every five seconds. The error message displays after 60 sec-
onds if the problem persists.
• What to do: Replace the battery as outlined in the Maintenance chapter.
MAINTENANCE ALERT:
7 Direct I/O Ring Break
• Latched target message: No.
• Description of problem: Direct input and output settings are configured for a ring, but the connection is not in a ring.
• How often the test is performed: Every second.
• What to do: Check direct input and output configuration and wiring.
MAINTENANCE ALERT:
ENET PORT # OFFLINE
• Latched target message: No.
• Description of problem: The Ethernet connection has failed for the specified port.
• How often the test is performed: Every five seconds.
• What to do: Check the Ethernet port connection on the switch.
MAINTENANCE ALERT:
**Bad IRIG-B Signal**
MAINTENANCE ALERT:
**Bad PTP Signal**
MAINTENANCE ALERT:
Port ## Failure
MAINTENANCE ALERT:
4L Discrepancy
• Latched target message: No.
• Description of problem: A discrepancy has been detected between the actual and desired state of a latching contact
output of an installed type “4L” module.
• How often the test is performed: Upon initiation of a contact output state change.
• What to do: Verify the state of the output contact and contact the factory if the problem persists.
MAINTENANCE ALERT:
GGIO Ind xxx oscill
TEMP MONITOR:
OVER TEMPERATURE
• Latched target message: Yes.
• Description of problem: The ambient temperature is greater than the maximum operating temperature (+80°C).
7 •
•
How often the test is performed: Every hour.
What to do: Remove the D60 from service and install in a location that meets operating temperature standards.
UNEXPECTED RESTART:
Press “RESET” key
• Latched target message: Yes.
• Description of problem: Abnormal restart from modules being removed or inserted while the D60 is powered-up, when
there is an abnormal DC supply, or as a result of internal relay failure.
• How often the test is performed: Event driven.
• What to do: Contact the factory.
7 Description: Brick internal self-testing has detected a trouble internal to the Brick.
Severity: This self-test error does not directly inhibit protection. However, some or all of the affected Brick inputs/outputs
may not be available to the UR-series device.
If this message appears, check the Brick environment for over/under temperatures and the voltage of its power source. If
the ambient temperature and supply voltage are within Brick specifications, consult the factory. Troubles resulting from a
Brick output failing to respond to an output command can only be detected while the command is active, and so in this case
the target is latched. A latched target can be unlatched by pressing the faceplate reset key if the command has ended,
however the output may still be non-functional.
f)
The distance elements use memory voltage for polarization. Additional supervising functions – different for ground and
phase distance zones – complement a classical mho characteristic to enhance directional integrity and reach accuracy:
• To avoid overreaching during resistive faults under heavy pre-fault load conditions, the ground distance elements uti-
lize a load-adaptive (zero-sequence polarized) reactance characteristic to supervise the base mho characteristic.
• Both negative and zero-sequence currents are compared with the memory voltage to enhance directional integrity of
the ground distance elements.
• It is well known that ground distance elements – as per the principle of distance relaying – may have limited accuracy
during double-line-to-ground faults. In order to prevent maloperation in such cases the ground elements are blocked by
an extra “fault-type comparator” that utilizes the phase angle between the negative- and zero-sequence currents.
• The phase distance elements use reactance and memory polarized directional characteristics to supervise the mho
characteristic.
• Both ground and phase distance elements have the current supervision functions built-in.
The quadrilateral distance characteristic uses the reactance, directional, and current supervising functions as described
above. Right and left blinders adjustable as to both the resistive and angular positions complete the characteristic.
More information regarding the distance characteristics is found in the Distance characteristics section. An example of
analysis of the steady-state operation of the distance elements is found in the Distance elements analysis section.
The relay provides five zones of distance protection. All zones are identical in terms of settings. However, zone 1 has extra
adaptive mechanisms built-in to enhance the transient reach accuracy even when the voltage signals are supplied from
poor quality voltage sources such as capacitive voltage transformers (CVTs). Ground zones 2 through 5, in turn, have an
extra zero-sequence directional supervision implemented for their time-delayed operation after the memory expires. Con-
sequently, zone 1 is recommended as an underreaching element, and zones 2 through 5 are recommended as overreach-
ing elements and for time-delayed tripping.
The relay uses offset ground directional overcurrent functions as an optional supplement of the ground distance protection
for pilot-aided schemes. The elements are described in more details in the Ground directional overcurrent section.
The relay provides for an adaptive distance reach control to cope with the overreaching and sub-synchronous oscillations
when applied to, or in a near vicinity of series compensated lines. More details can be found in the Application on series
compensated lines section.
The distance elements use phase angle comparators to shape their characteristics as described in the Distance character-
istics section. The voltage and current phasors are estimated using optimized techniques as explained in the next section.
The relay samples its input AC signals at 64 samples per power system cycle. A fast and accurate frequency tracking
mechanism ensures accurate filtering and phasor estimation during off-nominal frequency conditions.
The phasor estimation process for both currents and voltages is based on the commonly used Fourier algorithm. Due to a
different nature of signal distortions in the current and voltage signals digital pre-filtering algorithms have been, however,
designed and optimized separately for the current and voltage channels. 8
The current signals are pre-filtered using an improved digital MIMIC filter. The filter removes effectively the DC compo-
nent(s) guaranteeing transient overshoot below 2% regardless of the initial magnitude and time constant of the dc compo-
nent(s). The filter has significantly better frequency response for higher frequencies as compared with a classical MIMIC
filter. This was possible without introducing any significant phase delay thanks to the high sampling rate used by the relay.
The voltage signals are pre-filtered using a special digital filter designed to cope with CVT transients. The patented filter
combines filtering and memory actions enabling the relay to cope with CVT noise under high Source Impedance Ratios
(SIRs). The filter controls underestimation of the fault voltage magnitude to less than 1% of the nominal and prevents cer-
tain phase angle anomalies that can be encountered under heavy CVT noise and high SIRs.
a) DEFINITIONS
The relay shapes its distance characteristics using phase angle comparators and voltage and current phasors estimated as
described in the previous section.
The following definitions pertain to all of the distance functions:
• IA, IB, IC: phase A, B, and C current phasors.
• IG: ground current from a parallel line.
• VA, VB, VC: phase A to ground, phase B to ground, and phase C to ground voltage phasors.
• ( )_1: positive-sequence phasor of ( ) derived from the phase quantities.
• ( )_2: negative-sequence phasor of ( ) derived from the phase quantities.
• ( )_0: zero-sequence phasor of ( ) derived from the phase quantities.
• ( )M: memorized value of ( ).
• Z: reach impedance (REACH RCA).
• ZREV: reverse reach impedance for non-directional applications (REV REACH REV REACH RCA + 180°).
• ZD: directional characteristic impedance (1 DIR RCA).
• ZR: right blinder characteristic impedance: ZR = RGT BLD sin (RGT BLD RCA) 1 (RGT BLD RCA – 90°).
• ZL: left blinder characteristic impedance: ZL = LFT BLD sin (LFT BLD RCA) 1 (LFT BLD RCA + 90°).
• K0: zero-sequence compensating factor: K0 = (Z0/Z1 MAG Z0/Z1 ANG) – 1.
• K0M: mutual zero-sequence compensating factor: K0M = 1/3 x Z0M/Z1 MAG Z0M/Z1 ANG.
• : non-homogeneity angle setting (NON-HOMOGEN ANG).
R 837715A2.CDR R 837714A2.CDR
The ground elements are polarized from either zero-sequence or negative-sequence current as per user-settings to maxi-
mize performance in non-homogenous systems. The polarizing current is additionally shifted by the user-selectable non-
homogeneity correction angle.
g) DIRECTIONAL CHARACTERISTIC
The directional characteristic is achieved by checking the angle between:
AB phase element: (IA – IB) ZD and (VA – VB)_1M
BC phase element: (IB – IC) ZD and (VB – VC)_1M
CA phase element: (IC – IA) ZD and (VC – VA)_1M
A ground element: I_0 ZD and VA_1M
IA_2 ZD and VA_1M
B ground element: I_0 ZD and VB_1M
IB_2 ZD and VB_1M
C ground element: I_0 ZD and VC_1M
IC_2 ZD and VC_1M
The characteristic and limit angles of the directional comparator are adjustable independently from the mho and reactance
comparators. The directional characteristic improves directional integrity of the distance functions.
h) RIGHT BLINDER
The right blinder characteristic is achieved by checking the angle between the following signals:
AB phase element: (IA – IB) ZR – (VA – VB) and (IA – IB) ZR
BC phase element: (IB – IC) ZR – (VB – VC) and (IB – IC) ZR
CA phase element: (IC – IA) ZR – (VC – VA) and (IC – IA) ZR
A ground element: IA ZR + I_0 K0 ZR + IG K0M ZR – VA and IA ZR + I_0 K0 ZR + IG K0M ZR
B ground element: IB ZR + I_0 K0 ZR + IG K0M ZR – VB and IB ZR + I_0 K0 ZR + IG K0M ZR
C ground element: IC ZR + I_0 K0 ZR + IG K0M ZR – VC and IC ZR + I_0 K0 ZR + IG K0M ZR
8 The blinders apply to the Quad characteristic only.
i) LEFT BLINDER
The left blinder characteristic is achieved by checking the angle between the following signals:
AB phase element: (IA – IB) ZL – (VA – VB) and (IA – IB) ZL
BC phase element: (IB – IC) ZL – (VB – VC) and (IB – IC) ZL
CA phase element: (IC – IA) ZL – (VC – VA) and (IC – IA) ZL
A ground element: IA ZL + I_0 K0 ZL + IG K0M ZL – VA and IA ZL + I_0 K0 ZL + IG K0M ZL
B ground element: IB ZL + I_0 K0 ZL + IG K0M ZL – VB and IB ZL + I_0 K0 ZL + IG K0M ZL
C ground element: IC ZL + I_0 K0 ZL + IG K0M ZL – VC and IC ZL + I_0 K0 ZL + IG K0M ZL
The blinders apply to the Quad characteristic only.
j) FAULT-TYPE CHARACTERISTIC
The fault-type characteristic applies to ground elements only and is achieved by checking the angle between:
A ground element: I_0 and IA_2;
B ground element: I_0 and IB_2
C ground element: I_0 and IC_2
The limit angle of the comparator is not adjustable and equals 50°. The fault-type characteristic is intended to block the
ground distance elements during double-line-to-ground faults.
l) OVERCURRENT SUPERVISION
The overcurrent supervision responds to the following currents:
AB phase element: (IA – IB) / 3
BC phase element: (IB – IC) / 3
CA phase element: (IC – IA) / 3
A, B, C ground element: | 3 I_0 – 0.05 × I_1 |
The following tables summarize the characteristics of the distance elements
All distance functions use memory polarization. The positive-sequence voltage – either memorized or actual – is used as a
polarizing signal. The memory is established when the positive-sequence voltage remains above 80% of its nominal value
for five power system cycles. The memory voltage is a three-cycle old voltage.
Once established, the memory is applied for the user-specified time interval. The memory timer is started when the voltage
drops below 80% of nominal or when the user-programmable condition is asserted to force memory polarization. After the
memory expires, the relay checks the magnitude of the actual positive-sequence voltage. If it is higher than 10% of nomi-
nal, the actual voltage is used; if lower, the memory voltage continues to be used.
A provision is added to force self-polarization from any user-programmable condition.
The memory-polarized mho has an extra directional integrity built-in as illustrated below. The self-polarized mho character-
istic is shifted in the reverse direction for a forward fault by an amount proportional to the source impedance, and in the for-
ward direction for a reverse fault.
Self-polarized mho
Memory-polarized mho
Memory-polarized mho (Forward fault)
(Reverse fault)
837719A2.CDR
Memory-
polarized
(Reverse fault)
Self-polarized
Memory-
polarized
837724A1.CDR
(Forward fault)
a) DESCRIPTION 8
This subsection shows how to analyze the operation of the distance elements in steady states using the results of short cir-
cuit studies. All quantities are secondary ohms, volts, and amperes. Ground phase A and phase AB distance elements are
analyzed.
Assume the following settings have been entered:
Phase Rotation: ABC
Right Blinder Reach: 10
Nominal Secondary Voltage: 69.28 V
Right Blinder RCA: 88°
Distance Reach: 14
Left Blinder Reach: 5
Distance RCA: 88°
As a Wye-Delta transformer introduces discontinuity for the zero-sequence circuit, the ground distance protection cannot
be applied, except special circumstances, to respond to faults behind the transformer.
The phase distance elements, however, could be developed so that both accurate reach and correct fault phase identifica-
tion is retained for faults behind the power transformer as seen from the relaying point. Without appropriate compensation,
the relay's reach would depend on a type of fault, creating considerable difficulties in applying the relay.
The D60 provides for any location of the VTs and CTs with respect to the involved power transformer and the direction of
any given zone.
In the following equations, the VT and CT locations are referenced as “None” if the transformer is not present between the
CT/VT and the intended reach point. Otherwise, the location is to be selected as a type of a transformer as seen from the
VT/CT position towards the intended reach point. The following figure explains the adopted rules.
(a) (b)
delta wye, 330o lag delta wye, 330o lag
Z4 Z4
Z1 Z1
(c) (e)
delta wye, 330o lag
L1 L2
Z4 Zone 4
Zone 1
Z4 XFRM VOL CONNECTION = None
Z4 XFRM CUR CONNECTION = Yd1 ZL1 ZT ZL2
Z1 8
Z1 XFRM VOL CONNECTION = Dy11
Z1 XFRM CUR CONNECTION = None
Figure 8–4: APPLICATIONS OF THE “PHS DIST XFMR VOL/CUR CONNECTION” SETTINGS
Equations from the “Current Transformation” and “Voltage Transformation” columns are used to derive inputs to the three
(AB, BC, and CA) phase distance elements. For example, if the CTs are located at the delta side of the Delta-Wye 11 trans-
former, and a given zone is set to look through the transformer into the system connected to the Wye winding, the CT loca-
tion setting for that zone shall be set to Dy11 and the relay would use – 3I B instead of a traditional I A – I B for the AB
phase distance element.
The current supervision pickup setting applies to the currents specified in the “Current Transformation” columns.
A distance zone originates at the location of the VTs (regardless of the location of the CTs). For more information on set-
tings please refer to Chapter 9: Application of Settings.
8.2.2 EXAMPLE
H X
VT = 13.8kV/120V VT = 315kV/120V
CT = 8000:5 CT = 300:5
0.688Ω∠85°
2.57Ω∠88.4°
837727A2.CDR
8 IB
IC
1.288 kA 152.4°
0
21.47 A 152.4°
0
If installed at the location X, the relay would use the following input signals for its phase AB distance element:
V = VAB = 77.402 kV 57.5° primary or 29.49 V 57.5° secondary
I = IA – IB = 2.576 kA –27.6° primary or 42.93 A –27.6° secondary
And consequently it would see an apparent impedance of:
Zapp = V / I = 30.05 85° primary or 0.687 85° secondary
Consequently, the following signals are applied to the phase AB distance element:
1
V = ------- V AB – V BC = 10.861 kV 59.9 primary or 94.45 V 59.9 secondary (EQ 8.1)
3
Thus, 0.127 90° + 0.05779 85° = 0.1847 88.4° primary side or 2.569 88.4° on the secondary side.
The above example illustrates how the relay maintains correct reach for fault behind power transformers. When installed at
X, the relay shall be set to 0.687 85° secondary in order to reach to the fault shown in the figure. When installed at H,
the relay shall be set to 2.569 88.4° to ensure exactly same coverage.
See Chapter 9: Application of Settings for more information on setting calculations.
Consider the negative-sequence directional overcurrent element. As illustrated below, the negative-sequence voltage could
be low during internal fault conditions.
(a) (b)
S_op
S_pol
V_2 ECA
UR I_2
(c) (d)
I_2
UR
8.3.2 EXAMPLE
Consider relay input signals as in the Distance Elements Analysis section and assume an offset impedance of 4 and
8 ECA and limit angles of 88° and 90°, respectively. The relay calculates the following negative-sequence quantities:
V_2 = 6.39 V –159.6°; I_2 = 1.37 A –68.1°; I_1 = 2.94 A –144.2°
and the following signals for the directional unit of the negative-sequence directional overcurrent element:
• Forward-looking element: S_pol = 11.87 V 20.2
S_op = 1.37 V 20.2
Faults on or in a close vicinity of series compensated lines may create problems for distance protection:
• Voltage and/or current inversion may lead to false direction discrimination by directional elements. This may potentially
include both a failure to operate on a forward in-zone fault as well as misoperation on a reverse fault. Both distance
and overcurrent directional elements can be affected.
• Series-capacitors and their overvoltage protection equipment (air gaps and/or Metal-Oxide Varistors) have a steady-
state overreaching effect on the apparent impedance seen by the relay - a forward fault may appear much closer to the
relay as compared with the actual fault location. The apparent impedance may be shifted towards the relay by as much
as the total reactance of the series capacitors placed between the potential source of the relay and the fault point. This
extreme steady-state overreach happens during low-current faults when the air-gaps do not flashover or the MOVs do
not conduct any significant current.
• In addition to the above steady-state overreach effect; sub-synchronous oscillations in both currents and voltages may
cause significant transient overreach.
Distance protection elements of the D60 deal with the problem of voltage inversion by using 100% memory polarized direc-
tional comparators. As the memory duration is set longer that the slowest fault clearing time for reverse faults, it is guaran-
teed that the distance element would not pick-up on reverse faults should the voltage inversion happen.
At the same time, it is guaranteed that the distance elements would pick-up for all forward faults regardless of any voltage
inversion as long as the memory voltage is used. Before the memory expires the relay would respond to any fault on the
protected line. Stepped distance backup zones operate after the memory voltage expires. But the backup protection
responds to distant faults that do not cause any inversion of the positive-sequence voltage. As a result, the time-delayed
stepped-distance zones are guaranteed to operate.
Distance protection elements of the D60 deal with the problem of current inversion by using a multi-input-comparator
approach as described in the Distance Characteristics subsection. Should the current inversion happen, the distance ele-
ments are secure on reverse faults because multiple conditions involving fault-loop, negative-sequence and zero-sequence
currents and the memory voltage are checked prior to declaring a forward fault.
On close-in forward faults beyond the series capacitors as seen from the relaying point, the current inversion phenomenon
may take place for a short period of time. The condition cannot sustain for a long time as very high fault currents would
occur causing large voltage drops across the series capacitors and prompting the overvoltage protection of the capacitors
to operate quickly. This would effectively remove the series compensation and eliminate the current inversion. However,
when the currents used by distance comparator (fault-loop current for ground and phase distance protection, and the nega-
tive- and zero-sequence currents for ground elements) stay shifted by more than 90 degrees from their natural fault position
determined by the user as the element characteristic angle, the distance elements may fail to pick-up on such a forward
fault for the brief period of current inversion. This is an inherent attribute of the 100% memory polarized mho element, and
not a weakness particular to the D60 relay.
Therefore, for dependability, it is recommended to use high-set phase overcurrent protection for direct tripping on close-in
faults potentially causing current inversion, and overreaching ground fault directional overcurrent functions (such as nega-
tive-sequence, ground or neutral) for communication-aided schemes.
The problem of steady-state overreaching due to the negative reactance of the series capacitors may be addressed in the
D60 in a traditional way by shortening the reach of an underreaching distance elements to the net inductive reactance of
8 the line between the potential source and the far end busbar(s). This generic approach has two major drawbacks. First, it
leaves large portion of the line uncovered by the directly tripping distance protection. Second, it does not solve the transient
overreaching problem caused by sub-synchronous oscillations.
Therefore, the D60 offers a unique option for dynamic reach control that is effectively based on the magnitude of the current
flowing through the series capacitor bank(s). The underreaching distance functions can be set as for plain uncompensated
line, i.e. using the impedance of the line alone, and the relay would control an effective reach accordingly using the current
magnitude as illustrated in the figure below.
The reach is reduced sufficiently to cope with both steady-state and transient overreach phenomena. For large degrees of
compensation and small-current faults, the transient overreach may be as high as 100%. This means that fast distance pro-
tection is not achievable. The adaptive D60's mechanism would guarantee security on external faults. Overreaching ground
fault directional overcurrent functions (such as negative-sequence, ground or neutral) shall be used for dependability.
X FAR
-E
BUS ND
BAR
SET REACH (ZR)
THE REACH IS
DYNAMICALLY ACTUAL REACH
REDUCED BY FOR VERY HIGH
VL/abs(I) CURRENTS
ACTUAL REACH IS
A FUNCTION OF
CURRENT
MAGNITUDE
ACTUAL REACH
FOR VERY SMALL
CURRENTS R
837729A1.CDR
Z SC&MOV
Steady-state
apparent
impedance
SC
The reach is safely
M OV
reduced
R
HIGH-CURRENT EXTERNAL
(b) FAULT
X
FAR-E
N
BUSB D Impedance
AR
RF Trajectory (no
Set reach subsynchronous
oscillations)
Steady-state
apparent
impedance
SC
reduced
8 RF
subsynchronous
oscillations)
Steady-state
apparent
impedance
SC
reduced
837730A1.CDR
a) INTRODUCTION
Single pole operations make use of many features of the relay. At the minimum, the trip output, recloser, breaker control,
open pole detector, and phase selector must be fully programmed and in service; and either protection elements or digital
inputs representing fault detection must be available for successful operation. When single pole trip-and-reclose is required
overall control within the relay is performed by the trip output element. This element includes interfaces with pilot aided
schemes, the line pickup, breaker control, and breaker failure elements.
Single pole operations are based on use of the phase selector to identify the type of the fault, to eliminate incorrect fault
identification that can be made by distance elements in some circumstances and to provide trip initiation from elements that
are not capable of any fault type identification, such as high-set negative-sequence directional overcurrent element. The
scheme is also designed to make use of the advantages provided by communications channels with multiple-bit capacities
for fault identification.
Phase selector
Volts Reset
and output Fault locator
amps
Block specific protection elements
Volts
and
Trip output amps
Protection Setting
elements
Single-pole
Single-pole
trip request
Inputs Setting trip
Open
Pilot-
pole
aided
detector
schemes
Trip
A or B or C
Setting Setting
Setting Permission
Breaker 1 and 2
Inputs
Setting
Reset Breaker
control
Outputs
Three-pole Three-pole
trip trip
request
Line pickup Setting
CLOSE 1
CLOSE 2
CLOSE 1
CLOSE 2
Multi-phase
Operator
Void Force Three-pole
three-oole operation
Setting operation Setting
AR FORCE 3-P
8
Initiate
Reclose request Trip
Initiate
AR Initiate 3-Pole Recloser
Multi-phase
837026A5.CDR
b) SLG FAULT
An AG fault occurs close to the considered relay. Immediately after the fault, the disturbance detector (50DD) picks-up and
activates the phase selector. The phase selector recognizes an AG fault by asserting its PHASE SELECT AG operand.
Ground distance zone 1 (AG element) responds to the fault. As the fault is close to the relay, phase distance zone 1 (AB,
CA elements) may respond to this fault as well. In any case, a single-pole operation is requested by zone 1 via the GND
DIST Z1 OP and/or PHS DIST Z1 OP operands.
At this moment the request to trip is placed for the trip output. As the fault is recognized as an AG fault, the TRIP PHASE A
operand is asserted by the trip output. This signal is passed to the breaker control scheme and results in tripping pole A of
the breaker.
Simultaneously with the TRIP PHASE A operand, the TRIP 1-POLE operand is asserted. This operand activates the open pole
detector. The latter detector responds to the TRIP PHASE A signal by declaring phase A open by asserting OPEN POLE OP
8 A (even before it is actually opened). The TRIP PHASE A signal resets only after the breaker actually operates as indicated
by its auxiliary contact. At this moment the open pole detector responds to the breaker position and continues to indicate
phase A opened. This indication results in establishing blocking signals for distance elements (OPEN POLE BLK AB, OPEN
POLE BLK CA operands are asserted). If neutral and negative-sequence overcurrent elements are mapped into the trip out-
put to trigger single-pole tripping, they must be blocked with the OPEN POLE BLK N operand, specifically provided for this
purpose. The OPEN POLE BLK N operand must be assigned through the block setting of the overcurrent element. The two
latter operands block phase distance AB and CA elements, respectively (all zones); the OPEN POLE A OP blocks the
ground distance AG elements (all zones). As a result, the Z1 OP and Z2 PKP operands that were picked-up reset immedi-
ately. The following distance elements remain operational guarding the line against evolving faults: BG, CG and BC.
As zone 2 and/or negative-sequence directional elements pick up due to the fault, the permission to trip is keyed to the
remote end. Assume here that a single-bit channel is used. If so, no extra information is sent to the remote end, just permis-
sion to trip sent over the TX1 operand. Upon receiving permission to trip over RX1, the POTT scheme decides to trip. The
scheme will check the phase selector for phase type identification and will issue a trip for phase A by asserting the POTT
TRIP A operand. This operand is passed to the trip output and results in exactly same action as described above for zone 1.
Depending on response times, the actual trip is initiated either by zone 1 or by the POTT scheme. At the moment TRIP 1-
POLE operand is asserted, the phase selector resets and no other trip action could take place. After the trip command is
issued all the picked up elements are forced to reset by the open pole detector.
The TRIP 1-POLE operand initiates automatically a single-pole autoreclose. The autoreclose is started and asserts the AR
RIP operand. This operand keeps blocking the phase selector so that it does not respond to any subsequent events. At the
same time the operand removes zero-sequence directional supervision from ground distance zones 2 and 3 so that they
could respond to a single-line-to-ground fault during open pole conditions.
The AR FORCE 3-P TRIP operand is asserted 1.25 cycles following autoreclose initiation. This operand acts as an enabler
for any existing trip request. In this case none of the protection elements is picked up at this time, therefore no more trips
are initiated.
When the recloser dead time interval is complete it signals the breaker control element to close the breaker. The breaker
control element operates output relays to close the breaker.
When pole A of the breaker closes this new status is reported to the breaker control element, which transfers this data to
the breaker failure, autorecloser, open pole detector and trip output elements. The response at breaker failure is dependent
on the programming of that element. The response at the autorecloser is not relevant to this discussion. At the open pole
detector, the blocking signals to protection elements are de-asserted.
If the fault was transient the reset time would expire at the autorecloser and the AR FORCE 3-P TRIP and RIP outputs would
be de-asserted, returning all features to the state described at the beginning of this description.
If the fault was permanent appropriate protection elements would detect it and place a trip request for the trip output ele-
ment. As the AR FORCE 3-P TRIP is still asserted, the request is executed as a three-pole trip.
The response of the system from this point is as described above for the second trip, except the autorecloser will go to lock-
out upon the next initiation (depending on the number of shots programmed).
The D60 uses phase relations between current symmetrical components for phase selection. First, the algorithm validates
if there is enough zero-sequence, positive-sequence, and negative-sequence currents for reliable analysis. The compari-
son is adaptive; that is, the magnitudes of the three symmetrical components used mutually as restraints confirm if a given
component is large enough to be used for phase selection. Once the current magnitudes are validated, the algorithm ana-
lyzes phase relations between the negative-sequence and positive-sequence currents and negative-sequence and zero-
sequence currents (when applicable) as illustrated below.
AB, CG,
BG ABG ABG
AG,
I2F AG I2F BCG
BC,
BCG
I1F I0F
CG CA, BG,
CAG CAG 837725A1.CDR
OPERAND DESCRIPTION
PHASE SELECT AG Asserted when a phase A to ground fault is detected.
PHASE SELECT BG Asserted when a phase B to ground fault is detected.
PHASE SELECT CG Asserted when a phase C to ground fault is detected.
PHASE SELECT AB Asserted when a phase A to B fault is detected.
PHASE SELECT BC Asserted when a phase B to C fault is detected.
PHASE SELECT CA Asserted when a phase C to A fault is detected.
PHASE SELECT ABG Asserted when a phase A to B to ground fault is detected.
PHASE SELECT BCG Asserted when a phase B to C to ground fault is detected.
PHASE SELECT CAG Asserted when a phase C to A to ground fault is detected.
If none of the fault types indicated above is determined, then three-phase fault conditions are checked to detect the pres-
ence of positive-sequence current and the absence of both zero-sequence and negative-sequence current. If these condi-
tions are met, then the PHASE SELECT 3P FlexLogic operand is asserted; otherwise, the PHASE SELECT VOID operand is
asserted, indicating that the phase selector failed to identify the fault type.
Finally, the states of the following additional FlexLogic operands are determined.
OPERAND DESCRIPTION
PHASE SELECT SLG Asserted if any of PHASE SELECT AG, PHASE SELECT BG, or PHASE SELECT CG
operands is active.
PHASE SELECT MULTI-P Asserted if neither the PHASE SELECT SLG nor PHASE SELECT VOID operands are being
asserted.
The phase selector operands are reset ½ cycle after the OPEN POLE OP FlexLogic operand is asserted or 500 ms after the
disturbance detector (50DD) initially operated. In the reset state, all phase selector FlexLogic operands are reset until reset
conditions are removed and the phase selector is ready for the next operation.
DELAY
FLEXLOGIC OPERAND
0.5 cycles
OPEN POLE OP RESET
0
DELAY
0 DELAY FLEXLOGIC OPERANDS
4 cycles 0 PHASE SELECT AG
FLEXLOGIC OPERAND AND START
500 ms PHASE SELECT BG
SRCn 50DD OP
PHASE SELECT CG
PHASE SELECT AB
FLEXLOGIC OPERAND
PHASE SELECTOR
PHASE SELECT BC
SRCn VT FUSE FAIL OP
PHASE SELECT CA
PHASE SELECT ABG
SETTING
PHASE SELECT BCG
DISTANCE SOURCE: PHASE SELECT CAG
PHASE SELECT 3P
I_0
8
PHASE SELECT SLG
I_1
PHASE SELECT MULTI-P
I_2
PHASE SELECT VOID
V_0
V_1
V_2
837027A5.CDR
a) DESCRIPTION
In the D60 relay pilot-aided schemes transmit a code representing the type of fault determined by the local phase selector
according to the scheme logic. At a receiving terminal the local and remote data is combined to determine the action to be
performed. Schemes can be used with channels that can carry one, two or four bits. Using a one-bit channel, the schemes
at all terminals of the line use their local phase selectors to identify the fault type and initiate appropriate tripping actions. In
single pole operation applications however, a three-pole trip can be performed in the event of an in-line single-phase fault
co-incident with a fault on a different phase (cross-country fault) that is within the reach of the local phase selector, which is
considerably longer than the line. This possibility can be reduced by using a two-bit channel, and eliminated by using a
four-bit channel.
Using two-bit channels, the relays can share limited information about their local phase selection, improving considerably
the accuracy of single-pole tripping on cross-country faults. Two-bit channels however can only provide four different mes-
sages, one of which must be “no fault has been detected.” With only three messages available it is not possible to transmit
sufficient information to eliminate the use of local phase selector data, so a three-pole operation can occur in a cross-coun-
try fault condition. Using four-bit channels, the relays share enough information about fault types seen from all the line ter-
minals that local fault selector data can be rejected. In addition, in multiple bit systems the relays do not respond to non-
valid bit combinations, making the protection system more immune to communication problems than in a single bit system.
Each scheme within the relay has a setting that specifies the number of bits available on the associated communications
channel. This setting defines the input (RX1, RX2, RX3, RX4) and output (TX1, TX2, TX3, TX4 for communications and
[Scheme Abbreviation] TRIP A, TRIP B, TRIP C, TRIP 3P for action) operands used by the scheme, the data codes used to
convey fault data between terminals, and the method of combining information from the local and remote terminals to pro-
duce an output.
The scheme initiates a three-phase trip if the phase selector fails to recognize the fault type or after the AR FORCE 3P
TRIP operand is asserted.
c) TWO-BIT CHANNELS
The TX1, TX2, RX1 and RX2 operands are used and fault data is coded per the following tables.
8 0
0
0
1
CG, AB, ABG, 3P, Unrecognized
AG, BC, BCG
CG, BC, BCG, CA, CAG
CG
DIR BLOCK TRIP C
d) FOUR-BIT CHANNELS 8
The TX1, TX2, TX3, TX4, RX1, RX2, RX3 and RX4 operands are used.
AG 0 1 1 1 1 0 0 0
BG 1 0 1 1 0 1 0 0
CG 1 1 0 1 0 0 1 0
AB, ABG, BC, BCG, CA, CAG, 1 1 1 0 0 0 0 1
3P, Unrecognized
The “echo” feature can reduce the response time of an over-reaching scheme when a terminal is disconnected from the
line. In this condition, a zone 2 element at the terminal that remains in-service can detect a fault, but cannot trip, as a per-
missive signal is not received from the remote terminal. This feature is provided in the permissive over-reaching transfer trip
and hybrid permissive over-reaching transfer trip schemes.
PERMISSIVE OVER-REACHING TRANSFER TRIP SCHEME:
When used this feature will “echo” a reliable received permissive signal back to the originating terminal when a line-
end-open condition is identified by the line pickup logic. The permissive echo is programmed as a one-shot logic. The
echo is sent only once and then the echo logic locks out for a settable period. The duration of the echo pulse does not
depend on the duration or shape of the received Rx signals but is settable.
The echo is sent back only if none of the overreaching protection elements operates.
HYBRID PERMISSIVE OVER-REACHING TRANSFER TRIP PERMISSIVE ECHO:
When used this feature will “echo” a reliable received permissive signal back to the originating terminal if the line-end-
open condition is recognized by the line pickup scheme and the fault is not identified as a reverse fault by the zone 4 or
the ground directional overcurrent function (if used). The permissive echo is programmed as a one-shot logic. The
echo is sent only once and then the echo logic locks out for a settable period. The duration of the echo pulse does not
depend on the duration or shape of the received RX signal but is settable as ECHO DURATION.
The echo is sent back only if none of the overreaching protection elements operates.
PERMISSIVE ECHO OPERANDS AND TRANSMIT CODES:
In single-pole tripping, single-bit channel applications the signal received on bit no. 1 (Rx1) is echoed back on bit no. 1
(Tx1). In two- and four-bit applications the following echo tables apply.
For local fault type identification the pilot schemes use the Phase Selector. The latter may fail to respond to certain fault
scenarios. Examples are: simultaneous forward and reverse fault, simultaneous SLG and LL fault involving different phases
(e.g. AG and BC) or two simultaneous faults in the same direction but at very different locations. The Phase Selector is opti-
mized to either indicate correctly the forward fault or to assert the Void flag. For example, a combination of AG and BC is
not a valid fault type - it is two different simultaneous faults and as such cannot be described by any single fault pattern,
therefore, the Phase Selector would assert the Void flag.
The VOID phase selection combined with a local trip request (such as high-set directional overcurrent) will result in three-
pole trip as per the Trip Output logic.
The Pilot Schemes, however, try to recover more information from the distance elements. Each scheme uses a forward
looking, either underreaching or overreaching, distance zone. A given Pilot Scheme analyzes this zone for fault type identi-
fication if the Phase Selector asserts its Void flag: the DUTT scheme uses Z1; all the other schemes use Z2. The schemes
analyze all six fault loops of the zone to determine the fault type.
For example, simultaneous forward AG and reverse BG faults may result in the Void indication. The POTT scheme would
analyze the Z2 response. As only the AG element is picked up, the local phase selection is determined as AG. This is a cor-
rect indication.
Depending on the number of bits used for communications, the accuracy of the overall response will be further improved as
illustrated in the next subsection.
This enhanced operation of the pilot-aided schemes is the reason to use a short pilot scheme priority time when setting the
Trip Output logic. The timer will force the scheme to wait for a decision from the pilot scheme for a short period of time
before accepting any local trip request. The advantage, however, materializes only if more than one-bit communications
channels are used, and is important only on parallel lines or when the application requires maximum accuracy of single-
pole tripping. In other cases, it is not recommended to delay the local trip decision.
Assume a single pole operation application where D60 relays are used to protect a two terminal line, (terminals T1 and T2)
using phase and ground distance zone 1, 2 and 3 elements in a permissive over-reaching transfer trip scheme. The perfor-
mance of the system with one- two and four-bit communications channels is outlined for a mid-line phase A-to-ground fault
and a co-incident phase B-to-ground fault just behind terminal T2. Assume also that the reclosers are enabled and reset.
At T1 the following protection elements will pickup:
• Ground Distance Zone 1, 2, and 3 for an AG fault
• Ground Distance Zone 2 and 3 for a BG fault
• Phase Distance Zone 2 and 3 for an AB fault
At T1 the phase selector will determine the fault is type ABG. This response is independent from the distance elements –
the Phase Selector sees two forward faults.
At T2 the following protection elements will pickup:
• Ground Distance Zone 1, 2, and 3 for an AG fault
At T2 the phase selector will determine the fault is type AG. The reverse BG fault is likely to be ignored.
If a one-bit channel is used, terminal T1 will trip three poles but terminal T2 will trip phase A only, (see the Tables below)
which is undesirable.
If a two-bit channel is used both terminals will trip phase A only, (see the Tables below) which is the desired outcome.
If a four-bit channel is used both terminals will trip phase A only, (see the Tables below) which is the desired outcome.
T1
RX1
0
RX2
0
RX3
0
RX4
1 AG ABG Trip Phase A
8
T2 1 0 0 0 ABG AG Trip Phase A
Fault type determination is required for calculation of fault location – the algorithm uses the angle between the negative and
positive sequence components of the relay currents. To improve accuracy and speed of operation, the fault components of
the currents are used; that is, the pre-fault phasors are subtracted from the measured current phasors. In addition to the
angle relationships, certain extra checks are performed on magnitudes of the negative and zero-sequence currents.
The single-ended fault location method assumes that the fault components of the currents supplied from the local (A) and
remote (B) systems are in phase. The figure below shows an equivalent system for fault location.
distance to fault
Remote
Local bus bus
ZA IA mZ (1-m)Z IB ZB
EA VF RF EB
VA VB
842780A1.CDR
Inserting the IA and IB equations into the VA equation and solving for the fault resistance yields:
VA – m Z IA
R F = ----------------------------------- (EQ 8.10)
I BF
I AF 1 + --------
I AF
Assuming the fault components of the currents, IAF and IBF are in phase, and observing that the fault resistance, as imped-
ance, does not have any imaginary part gives:
VA – m Z IA
Im ----------------------------------- = 0 (EQ 8.11)
8 I AF
where: Im() represents the imaginary part of a complex number. Solving the above equation for the unknown m creates the
following fault location algorithm:
Im V A I AF
m = ---------------------------------------- (EQ 8.12)
Im Z I A I AF
For BG faults:
B B
VA = VA , I A = I A + K 0 I 0A (EQ 8.14)
For CG faults:
C BC
VA = VA , I A = I A + K 0 I 0A (EQ 8.15)
where K0 is the zero sequence compensation factor (for the first six equations above)
For ABC faults, all three AB, BC, and CA loops are analyzed and the final result is selected based upon consistency of the
results
The element calculates the distance to the fault (with m in miles or kilometers) and the phases involved in the fault.
The relay allows locating faults from delta-connected VTs. If the FAULT REPORT 1 VT SUBSTITUTION setting is set to “None”,
and the VTs are connected in wye, the fault location is performed based on the actual phase to ground voltages. If the VTs
are connected in delta, fault location is suspended.
If the FAULT REPORT 1 VT SUBSTITUTION setting value is “V0” and the VTs are connected in a wye configuration, the fault
location is performed based on the actual phase to ground voltages. If the VTs are connected in a delta configuration, fault
location is performed based on the delta voltages and externally supplied neutral voltage:
1
V A = --- V N + V AB – V CA
3
1
V B = --- V N + V BC – V AB (EQ 8.19)
3
1
V B = --- V N + V CA – V BC
3
If the FAULT REPORT 1 VT SUBSTITUTION setting value is “I0” and the VTs are connected in a wye configuration, the fault loca-
tion is performed based on the actual phase to ground voltages. If the VTs are connected in a delta configuration, fault loca-
tion is performed based on the delta voltages and zero-sequence voltage approximated based on the zero-sequence
current:
1
V A = --- V AB – V CA – Z SYS0 I 0
3
1
V B = --- V BC – V AB – Z SYS0 I 0 (EQ 8.20)
8
3
1
V B = --- V CA – V BC – Z SYS0 I 0
3
where ZSYS0 is the equivalent zero-sequence impedance behind the relay as entered under the fault report setting menu.
SETTINGS
FAULT REPORT 1 Z1
MAG:
FAULT REPORT 1 Z1
ANGLE:
FAULT REPORT 1 Z0
MAG:
FAULT REPORT 1 Z0
ANGLE:
FAULT REPORT 1
LENGTH UNITS:
FAULT REPORT 1
LENGTH:
SHOT # FROM
AUTO RECLOSURE 827094A5.CDR
This chapter provides general application guidelines for stepped distance, overcurrent and pilot protection. Where relevant,
design details and performance characteristics of the D60 are given to facilitate the process of setting the relay for a given
application.
As explained in Chapter 8, the D60 uses a memorized positive sequence voltage as a polarizing signal in order to achieve
dependable operation for forward faults and secure non-operation for reverse faults.
The dynamic shift of the characteristic ensures improved directionality, but it also means that if a backup function is
required for a reverse fault on the bus, then it is appropriate to reverse Zone 4 so that a time delayed backup function may
be obtained. As mentioned earlier, it may be beneficial to also avoid extremely large reach settings by setting a remote
backup so that it is reverse looking. This strategy can be beneficial if the reduced reach enhances the discrimination
between the load and fault conditions.
Especially at low SIR values, fast fault clearance times may be seen as extremely important, both from system stability, and
from equipment damage viewpoints. The high-set overcurrent element, when set appropriately, can be extremely useful in
achieving these goals. It helps the setting calculations if the system impedances are reasonably well known.
The overcurrent pick up should be set to the greater of the following values:
1. The maximum infeed seen by the relay, for a close in reverse fault.
2. The maximum fault level seen by the relay for a fault at 100% of the protected line.
The maximum error of the phase overcurrent elements is below 2%. A safety factor of 1.25 should be used to account for
relay errors and system impedance uncertainty.
If CT saturation is an issue such as close to a generation where long lasting dc components are likely to saturate the CTs, it
should be noted that the instantaneous overcurrent elements require 1.33 cycle of data to operate for a multiple of pickup of
1.01. For higher multiples of pickup, the relation between the multiple of pickup and the amount of data required for opera-
tion before complete CT saturation is approximately linear. For example, for a multiple of pickup of 4, approximately 1.33 /
4 = 0.332 of power cycle is required by the phase instantaneous overcurrent element to operate. The above information
should not be confused with the operating time, which includes some inherent delays such as a trip rated output contact.
ation should also be given to a situation where the load impedance may enter into the relay characteristic for a time longer
than the chosen time delay, which could occur transiently during a system power swing. For this reason the power swing
blocking function should be used.
The relay could only approximate the unknown fault current by the zero-sequence or the negative-sequence currents mea-
sured at the relaying point. Depending on system parameters, either the zero-sequence or the negative-sequence current
presents better approximation of the fault current angle.
Given the equivalent systems shown in the figure below, the angular difference between the zero-sequence or negative-
sequence currents at the relay, and the fault current can be calculated as follows:
IF Z 0A + Z 0L + Z 0B
0 = angle ---------------------- = angle ------------------------------------------- (EQ 9.2)
I 0_RELAY Z 0B + 1 – d Z 0L
IF Z 1A + Z 1L + Z 1B
2 = angle ---------------------- = angle ------------------------------------------- (EQ 9.3)
I 2_RELAY Z 1B + 1 – d Z 1L
IF
I0
I0
IF
I2
DEPENDING ON SYSTEM
Z1A dZ1L (1 – d)Z1L Z1B PARAMETERS, I0 OR I2 MAYBE A
BETTER APPROXIMATION OF THE
FAULT CURRENT ANGLE
I2
IF
842742A1.CDR
9 the mutual compensation feature of the ground distance elements can be used instead of a drastic reduction in the reach.
However, even in this case, there is more uncertainty as compared with the phase distance elements because the zero-
sequence impedance of the line and thus the zero-sequence-compensating factors may vary significantly due to weather
and other conditions.
This scheme uses an under-reaching Zone 1 distance element to key a transfer trip signal to the remote end(s), where on
receipt, the DUTT pilot scheme operates without any additional supervision.
For proper operation of the scheme the Zone 1 phase and ground distance elements must be enabled, configured and set
per rules of distance relaying.
The scheme generates an output operand (DUTT TX) that is used to transmit the signal to the remote end. Choices of com-
munications channel include Remote Inputs/Outputs and telecommunications interfaces. When used with telecommunica-
tions facilities the output operand should be assigned to operate an output contact connected to key the transmitter at the
interface.
Note that the same protection signaling may be used by a breaker failure scheme, in which case the signal can be sealed
in by breaker fail for a time longer than the auto-reclose “reclaim” time which then prevents auto-reclose when not required.
A provision for an optional seal-in of the send signal is made to cover those situations where PLC (Power Line Carrier) sig-
naling is used and the signal must be transmitted in a potentially noisy situation due to the fault.
The scheme output operand (DUTT OP) must be configured to interface with other relay functions, output contacts in par-
ticular, in order to make the scheme fully operational. Typically, the output operand should be programmed to initiate a trip,
breaker fail, and auto-reclose, and drive a user-programmable LED as per user application.
This scheme uses an under-reaching Zone 1 distance element to key a transfer trip signal to the remote end where it is
supervised by the over-reaching Zone 2 distance elements.
For proper operation of the scheme the Zone 1 and 2 phase and ground distance elements must be enabled, configured
and set per rules of distance relaying.
The scheme generates an output operand (PUTT TX) that is used to transmit the signal to the remote end. Choices of com-
munications channel include Remote Inputs/Outputs and telecommunications interfaces. When used with telecommunica-
tions facilities the output operand should be assigned to operate an output contact connected to key the transmitter at the
interface.
The PUTT RX PICKUP DELAY timer can be used to ride through spurious PLC receive signals.
The scheme output operand (PUTT OP) must be configured to interface with other relay functions, output contacts in partic-
ular, in order to make the scheme fully operational. Typically, the output operand should be programmed to initiate a trip,
breaker fail, and auto-reclose, and drive a user-programmable LED as per user application.
9 9.3.4 PERMISSIVE OVER-REACHING TRANSFER TRIP (POTT)
Ground directional overcurrent functions available in the relay can be used in conjunction with the Zone 2 distance element
to key the scheme and initiate its operation. This provides increased coverage for high-resistance faults.
Good directional integrity is the key requirement for an over-reaching forward-looking protection element used to supple-
ment Zone 2. Even though any FlexLogic operand could be used for this purpose allowing the user to combine responses
of various protection elements, or to apply extra conditions through FlexLogic™ equations, this extra signal is primarily
meant to be the output operand from either the Negative-Sequence Directional IOC or Neutral Directional IOC. Both of
these elements have separate forward (FWD) and reverse (REV) output operands. The forward indication should be used
(NEG SEQ DIR OC1 FWD or NEUTRAL DIR OC1 FWD).
An important consideration is when one of the line terminals is open. It is then necessary to identify this condition and
arrange for a continuous sending of the permissive signal or use a slower but more secure echo feature to send a signal to
the other terminal, which is producing the fault infeed. With any echo scheme however, a means must be provided to avoid
a permanent lock up of the transmit/receive loop. The echo co-ordination (ECHO DURATION) and lock-out (ECHO LOCK-
OUT) timers perform this function by ensuring that the permissive signal is echoed once for a guaranteed duration of time
before going to a lockout for a settable period of time.
It should be recognized that in ring bus or breaker and a half situations, it may be the line disconnect or a combination of
the disconnect and/or the breaker(s) status that is the indication that the terminal is open.
The POTT RX PICKUP DELAY timer is included in the permissive receive path to ride through spurious receive outputs that
may be produced during external faults, when power line carrier is utilized as the communications medium.
No current reversal logic is included for the overreaching phase and ground distance elements, because long reaches are
not usually required for two terminal lines. A situation can occur however, where the ground distance element will have an
extended reach. This situation is encountered when it is desired to account for the zero sequence inter-circuit mutual cou-
pling. This is not a problem for the ground distance elements in the D60 which do have a current reversal logic built into
their design as part of the technique used to improve ground fault directionality.
Unlike the distance protection elements the ground directional overcurrent functions do not have their reach well defined,
therefore the current reversal logic is incorporated for the extra signal supplementing Zone 2 in the scheme. The transient
blocking approach for this POTT scheme is to recognize that a permissive signal has been received and then allow a setta-
ble time TRANS BLOCK PICKUP DELAY for the local forward looking directional element to pick up.
The scheme generates an output operand (POTT TX) that is used to transmit the signal to the remote end. Choices of com-
munications channel include Remote Inputs/Outputs and telecommunications interfaces. When used with telecommunica-
tions facilities the output operand should be assigned to operate an output contact connected to key the transmitter at the
interface. Power Line Carrier (PLC) channels are not recommended for this scheme since the PLC signal can be inter-
rupted by a fault.
For proper operation of the scheme the Zone 2 phase and ground distance elements must be enabled, configured and set
per rules of distance relaying. The Line Pickup element should be enabled, configured and set properly to detect line-end-
open/weak-infeed conditions.
If used by this scheme, the selected ground directional overcurrent function(s) must be enabled, configured and set accord-
ingly The output operand from the scheme (POTT OP) must be configured to interface with other relay functions, output
contacts in particular, in order to make the scheme fully operational. Typically, the output operand should be programmed to
initiate a trip, breaker fail, and auto-reclose, and drive a user-programmable LED as per user application.
Generally, this scheme uses an over-reaching Zone 2 distance element to essentially compare the direction to a fault at
both ends of the line. Ground directional overcurrent functions available in the relay can be used in conjunction with the
Zone 2 distance element to key the scheme and initiate its operation. This increases the coverage for high-resistance
faults.
The scheme is intended for three-terminal applications and for weak-infeed conditions. As a long reach of the overreaching
9
distance element may be required for three-terminal applications, transient blocking logic is provided for both distance and
ground directional overcurrent elements. In order to cope with weak-infeed conditions an echo feature is made available.
By default the scheme uses the reverse-looking Zone 4 distance element to identify reverse faults. Additionally, reverse-
looking ground directional overcurrent functions can be used in conjunction with Zone 4.
For proper operation of the scheme the Zone 2 and 4 phase and ground distance elements must be enabled, configured
and set per rules of distance relaying. The Line Pickup element should be enabled, configured and set properly to detect
line-end-open/weak-infeed and undervoltage conditions.
If used by this scheme, the selected ground directional overcurrent function(s) must be enabled, configured, and set
accordingly.
The scheme generates an output operand (HYBRID POTT TX) that is used to transmit the signal to the remote end.
Choices of communications channel include Remote Inputs/Outputs and telecommunications interfaces. When used with
telecommunications facilities the output operand should be assigned to operate an output contact connected to key the
transmitter at the interface.
For more application recommendation refer to the POTT scheme.
The output operand from the scheme (HYBRID POTT OP) must be configured to interface with other relay functions, output
contacts in particular, in order to make the scheme fully operational. Typically, the output operand should be programmed to
initiate a trip, breaker fail, and auto-reclose, and drive a user-programmable LED as per user application.
Generally, the scheme compares the direction to a fault at both ends of the line. Unlike the permissive schemes, the
absence of a blocking signal permits operation of the scheme. Consequently, the scheme is biased toward dependability
and requires an “on/off” type of signaling.
By default this scheme uses only a forward-looking over-reaching Zone 2 distance element to identify forward faults.
Ground directional overcurrent functions available in the relay can be used in conjunction with the Zone 2 distance element
to increase the coverage for high-resistance faults.
By default the scheme uses only a reverse-looking Zone 4 distance element to identify reverse faults. Ground directional
overcurrent functions available in the relay can be used in conjunction with the Zone 4 distance element for better time and
sensitivity coordination.
For proper operation of the scheme the Zone 2 and 4 phase and ground distance elements must be enabled, configured
and set per rules of distance relaying.
If used by this scheme, the selected ground directional overcurrent function(s) must be enabled, configured and set accord-
ingly.
The scheme generates output operands (BLOCKING SCHEME TX INIT and BLOCKING SCHEME TX STOP) that are
used control the transmission of signals to the remote end. Choices of communications channel include Remote Inputs/
Outputs and telecommunications interfaces. When used with telecommunications facilities the output operand should be
assigned to operate an output contact connected to key the transmitter at the interface.
A blocking scheme may be preferred over a Hybrid POTT scheme, because of shorter reach settings for the Zone 2 ele-
ments. This follows from the fundamental difference that all zone 2 elements are required to see an internal fault for the
POTT approach, under all system conditions, which in turn, means that the reversed Zone 4 block initiate elements must
also have an increased reach. A blocking scheme on the other hand, can have much shorter Zone 2 reach settings if
sequential clearance can be accepted. The simple rule to ensure that all faults can be cleared, is for each terminal to have
a reach setting equal to the distance to the tap plus twice the distance from the tap to the remote terminal.
The Zone 2 element must have a coordinating timer BLOCK RX CO-ORD PKP DELAY, to ensure that the blocking signal is
received for all external faults that are within the set reach of the local overreaching Zone 2.
Transient blocking logic is implemented via the TRANS BLOCK timer, which continues to send a blocking signal for a settable
time TRANS BLOCK RESET DELAY, if it was being sent for at least 30 ms during the initial reverse fault set via TRANS BLOCK
PICKUP DELAY.
9 The output operand from the scheme (BLOCKING SCHEME OP) must be configured to interface with other relay functions,
output contacts in particular, in order to make the scheme fully operational. Typically, the output operand should be pro-
grammed to initiate a trip, breaker fail, and auto-reclose, and drive a user-programmable LED as per user application.
a) OVERVIEW
The directional comparison unblocking scheme is used with a frequency shift keying (FSK) PLC that produces a loss-of-
guard output during an actual loss-of-guard signal condition and during reception of the permissive keyed frequency when
the received carrier signal changed from guard to permissive frequency. The loss-of-guard signal should preferably be a
normally-closed contact, allowing the scheme to get this signal if the communications equipment failed. This loss-of-guard
output should be connected to a contact input of the D60. The power line carrier should also provide an output contact
when the permissive frequency is received. This output should be wired to any other contact input of the D60.
The directional comparison unblocking scheme allows a window of opportunity for tripping the breaker fast if the permissive
signal gets attenuated by the fault to a level below the receiver's threshold. The guard signal is monitored, and the relay is
allowed to trip for a loss of guard without receipt of the permissive signal, if the relay sees the fault in the forward, and not
reverse direction by means of the forward looking distance zone 2 and ground directional forward, if configured, and
reverse looking distance zone 4 and ground directional reverse, if configured.
The scheme is active and ready for operation when the DCUB BLOCK setting is “Off” the DCUB SCHEME FUNCTION setting is
“Enabled”. The user can disable or block the scheme by assigning any FlexLogic operand to the DCUB BLOCK setting. This
operand can consist of any pre-defined logic, including a pilot cutout switch connected to any contact input of the D60. With
this pilot cutout switch and the pre-defined logic state on and assigned to DCUB BLOCK, the scheme will be disabled. The
directional comparison unblocking scheme supervises the operation and keying of all scheme functions. The lockout fea-
ture of the scheme also supervises all scheme functions. All timers are fully adjustable, with typical values indicated.
Lockout of the directional comparison unblocking scheme is established as follows. Lockout of the scheme is started for a
time duration set by DCUB LOG TRIP WINDOW setting if:
• The scheme is enabled and not blocked (that is, the scheme is active), and
• no permissive RX signal is received, and
• any loss-of-guard signal is received.
Lockout is sealed-in through an AND gate with the directional comparison unblocking scheme active and any loss-of-guard
through GUARD HEALTHY RESET DELAY timer. The scheme will thus remain blocked during longer loss-of-guard or channel
conditions for any of the configured channels. The GUARD HEALTHY RESET DELAY timer ensures that the scheme will remain
locked out slightly longer after the loss-of-guard signal(s) is reset. This allows for all channel(s) stabilizing and contact
denouncing. This timer determines how long the logic waits before enabling the directional comparison unblocking scheme
when the communications channel is restored.
Operating of the directional comparison unblocking scheme consists of two parts: normal operation and loss-of-guard oper-
ation.
b) NORMAL OPERATION
Normal operation picks up under the following conditions:
• The scheme is enabled (DCUB FUNCTION is “Enabled” and DCUB BLOCK is “Off”), and
• any permissive signal is received with its associated loss-of-guard signal (e.g. DCUB RX1 and DCUB LOG1), and
• a fault is seen in the forward zone 2 distance elements or ground directional forward function (if configured), and
• the reverse zone 4 distance elements or ground directional reverse function (if configured) did not pickup to set the
transient blocking, and
• the scheme is not locked out.
If these conditions are met, the trip table is run, operating the scheme and asserting DCUB OP FlexLogic operand. The trip
table with the aid of the local phase selector and received RX signals will determine what tripping operands will be oper-
ated. During normal operation, the loss-of-guard signal will be seen momentarily before the permissive DCUB RX signal is
9
received for each channel being operated, as the channel transitions from guard to permissive frequency, but the scheme
operates instantaneously after any DCUB RX signal is received.
c) LOSS-OF-GUARD OPERATION
The loss-of-guard operation picks under the following conditions:
• The scheme is enabled (DCUB FUNCTION is “Enabled” and DCUB BLOCK is “Off”), and
• any loss-of-guard signal is received without its associated RX signal, and
• a fault is seen in the forward zone 2 distance elements or ground directional forward function (if configured), and
• the reverse zone 4 distance elements or ground directional reverse function (if configured) did not pickup to set the
transient blocking.
If these conditions are met, then the DCUB LOG PICKUP DELAY timer is started. After this timer times out, the trip table is run,
operating the scheme and asserting the DCUB OP FlexLogic operand. The trip table with the aid of the local phase selector
and loss-of-guard signals will determine what tripping operands will be operated. The DCUB LOG PICKUP DELAY timer allows
for any and all channel(s) to transition from guard to permissive before operating due to loss-of-guard in the presence of a
forward fault. The time window of allowing the scheme to operate when no DCUB RX signal is received when any loss-of-
guard was received is the difference between the DCUB LOG TRIP WINDOW and DCUB LOG PICKUP DELAY timers. When using
default settings, this value is 150 – 8 = 142ms. This means the scheme is unblocked and can trip during this time window if
a forward fault is sensed.
• any permissive signal DCUB RX1 through DCUB RX4 is received and any LOG1 to LOG4 is received, and
• a fault is not seen in the forward zone 2 distance elements or ground directional forward function (if configured) for at
least 100 ms, and
• the reverse zone 4 distance elements or ground directional reverse function (if configured) did not pickup to set the
transient blocking.
If these conditions are met, then the scheme will echo (transmit the DCUB TX1 through DCUB TX4 operands) the received
permissive DCUB RX signal(s) back to the remote relay based on the echo table.
The keying or transmit signals DCUB TX1 through DCUB TX4 consist of all normal keying or echo keying conditions.
9 The scheme DCUB TRIP A, DCUB TRIB B, DCUB TRIP C, and DCUB TRIP 3P output operands are hard-wired to the trip output
scheme. As such, if the trip output or breaker control operands (if the breaker control function is used) are used for tripping,
the scheme fully operational. The permissive key carrier signals DCUB TX1 through DCUB TX4 must still be assigned to the
tripping/operating logic, and to output contacts as per the usual D60 logic/output assignments.
For reasons described in Chapter 8: Theory of Operation, it is recommended to apply a combination of distance, ground
directional overcurrent and high-set overcurrent functions for protection of series compensated lines.
The setting rules described below must take into account variety of system configurations, particularly a status of series
capacitors (in-service, by-passed). Either the worst-case topology shall be considered or - if possible - adaptive settings
shall be applied though the multiple settings groups mechanism.
A line compensating capacitor is a bank of three physical capacitors and their overvoltage protecting devices (air gaps and/
or MOVs). If none of the MOV/gaps conducts any significant current, the positive-, negative- and zero-sequence reactance
of the three-phase bank equal the reactance of the actual (phase) capacitors. Under asymmetrical conditions, however,
such as a single line to ground fault, when only one MOV/gap may operate, the series capacitor bank would create extra
(series) asymmetry in addition to the fault (shunt) asymmetry. The positive-, negative- and zero-sequence impedances will
differ from each other and will not equal the impedance of the phase capacitors. Moreover, there may be mutual coupling
between the sequence networks representing the series capacitor bank. This makes analytical analysis of fault conditions
very burdensome. For setting calculations, however, it is justified to assume the zero-, positive-, and negative-sequence
reactance of the capacitor bank equal the reactance of the actual (phase) capacitors. This represents a worst-case low-cur-
rent fault scenario, when the steady-state effects of series compensation are most weighty.
9.4.2 DISTANCE
Traditionally, the reach setting of an underreaching distance function shall be set based on the net inductive impedance
between the potential source of the relay and the far-end busbar, or location for which the zone must not overreach. Faults
behind series capacitors on the protected and adjacent lines need to be considered for this purpose. For further illustration
a sample system shown in the figure below is considered.
voltage
SENDING RECEIVING
protection reactance
BUS BUS
level
0.5 pu 0.6 pu 0.5 pu 0.7 pu
-2 Ω -4 Ω -3 Ω -5 Ω
INFINITE
INFINITE
3Ω 10 Ω 7Ω
BUS
BUS
F2 A B B A F1
Protected Line
Figure 9–2: SAMPLE SERIES COMPENSATED SYSTEM
Assuming 20% security margin, the underreaching zone shall be set as follows.
At the Sending Bus, one must consider an external fault at F1 as the 5 capacitor would contribute to the overreaching
effect. Any fault behind F1 is less severe as extra inductive line impedance increases the apparent impedance:
Reach Setting: 0.8 x (10 – 3 – 5) = 1.6 if the line-side (B) VTs are used
Reach Setting: 0.8 x (10 – 4 – 3 – 5) = –1.6 if the bus-side (A) VTs are used
The negative value means that an underreaching zone cannot be used as the circuit between the potential source of the
relay and an external fault for which the relay must not pick-up, is overcompensated, i.e. capacitive.
At the Receiving Bus, one must consider a fault at F2:
Reach Setting: 0.8 x (10 – 4 – 2) = 3.2 if the line-side (B) VTs are used
Reach Setting: 0.8 x (10 – 4 – 3 – 2) = 0.8 if the bus-side (A) VTs are used 9
Practically, however, to cope with the effect of sub-synchronous oscillations, one may need to reduce the reach even more.
As the characteristics of sub-synchronous oscillations are in complex relations with fault and system parameters, no solid
setting recommendations are given with respect to extra security margin for sub-synchronous oscillations. It is strongly rec-
ommended to use a power system simulator to verify the reach settings or to use an adaptive D60 feature for dynamic
reach control.
If the adaptive reach control feature is used, the PHS DIST Z1 VOLT LEVEL setting shall be set accordingly.
This setting is a sum of the overvoltage protection levels for all the series capacitors located between the relay potential
source and the far-end busbar, or location for which the zone must not overreach. The setting is entered in pu of the phase
VT nominal voltage (RMS, not peak value).
If a minimum fault current level (phase current) is causing a voltage drop across a given capacitor that prompts its air gap to
flash over or its MOV to carry practically all the current, then the series capacitor shall be excluded from the calculations
(the capacitor is immediately by-passed by its overvoltage protection system and does not cause any overreach problems).
If a minimum fault current does not guarantee an immediate capacitor by-pass, then the capacitor must be included in the
calculation: its overvoltage protection level, either air gap flash-over voltage or MOV knee-point voltage, shall be used
(RMS, not peak value).
Assuming none of the series capacitors in the sample system is guaranteed to get by-passed, the following calculations
apply:
For the Sending Bus: 0.5 + 0.7 = 1.2 pu if the line-side (B) VTs are used
0.6 + 0.5 + 0.7 = 1.8 pu if the bus-side (A) VTs are used
For the Receiving Bus: 0.6 + 0.5 = 1.1 pu if the line-side (B) VTs are used
0.6 + 0.5 + 0.5 = 1.6 pu if the bus-side (A) VTs are used
Ground directional overcurrent function (negative-sequence or neutral) uses an offset impedance to guarantee correct fault
direction discrimination. The following setting rules apply.
1. If the net impedance between the potential source and the local equivalent system is inductive, then there is no need
for an offset. Otherwise, the offset impedance shall be at least the net capacitive reactance.
2. The offset cannot be higher than the net inductive reactance between the potential source and the remote equivalent
system. For simplicity and extra security, the far-end busbar may be used rather than the remote equivalent system.
As the ground directional functions are meant to provide maximum fault resistance coverage, it is justified to assume that
the fault current is very low and none of the series capacitors is guaranteed to get by-passed. Consider settings of the neg-
ative-sequence directional overcurrent protection element for the Sample Series Compensated System.
For the Sending Bus relay, bus-side VTs:
• Net inductive reactance from the relay into the local system = –2 + 3 = 1 > 0; there is no need for offset.
• Net inductive reactance from relay through far-end busbar = –4 + 10 – 3 = 3 ; the offset cannot be higher than 3 .
• It is recommended to use 1.5 offset impedance.
For the Sending Bus relay, line-side VTs:
• Net inductive reactance from relay into local system = –2 + 3 – 4 = –3 < 0; an offset impedance 3 must be used.
• Net inductive reactance from relay through far-end busbar = 10 – 3 = 7 ; the offset cannot be higher than 7 .
• It is recommended to use 5 offset impedance.
For the Receiving Bus relay, bus-side VTs:
• Net inductive reactance from relay into local system = –5 + 7 = 2 > 0; there is no need for offset.
• Net inductive reactance from relay through far-end busbar = –3 + 10 – 4 = 3 ; the offset cannot be higher than 3 .
• It is recommended to use 1.5 offset impedance.
For the Receiving Bus relay, line-side VTs:
9 • Net inductive reactance from relay into local system = –3 – 5 + 7 = –1 < 0; an offset impedance 1 must be used.
• Net inductive reactance from relay through far-end busbar = 10 – 4 = 6 ; the offset cannot be higher than 6 .
• It is recommended to use 3.5 offset impedance.
The setting rules for high-set overcurrent protection are explained in the High-Set Overcurrent Elements section.
a) DESCRIPTION
Phase distance elements of the D60 could be set to respond to faults beyond any three-phase power transformer. The
relay guarantees accurate reach and targeting for any phase fault. Moreover, the current and voltage transformers may be
located independently on different sides of the transformer.
The following setting rules apply to this feature:
1. A given distance zone is terminated by location of the VTs, not the CTs.
2. Consequently, the positive-sequence impedance of a transformer must be included in the reach setting only if the
transformer is located between the potential source and the intended reach point.
3. The current signals require compensation if the transformer is located between the CTs and the intended reach point.
If this is the case the CT connection setting shall be set to transformer connection and vector group as seen from the
CTs toward the reach point. Otherwise, the CT connection setting shall be set to "None".
4. The voltage signals require compensation if the transformer is located between the VTs and the intended reach point.
If this is the case the VT connection setting shall be set to transformer connection and vector group as seen from the
VTs toward the reach point. Otherwise, the VT connection setting shall be set to "None".
5. The reach setting is entered in secondary ohms and as such must take into account location and ratios of VTs and CTs
as well as voltage ratio of the involved power transformer.
The following equations explain the setting rules. Consider two applications as shown in the figure below:
(a) (b)
ZH ZT ZX ZH ZT ZX
H X H X
Z4 Z1 Z4 Z1
9.5.2 EXAMPLE
Given the following for the system shown in the previous section:
ZX = 30 85° (intended reach of Zone 1)
ZH = 0.06 88° (intended reach of Zone 4)
nCT = 8000:5 = 1600 (located at H)
nVT = 315000:120 = 2625 (located at X)
Transformer: 13.8/315 kV, 150 MVA, 10%, delta/wye, 315 kV side lagging 30°
Transformer impedance:
2
10 13.8
Z T at H = ---------- ------------------- = 0.127 90 (EQ 9.8)
100 150
The Zone 1 settings are:
13.8 1600
Z 1 = 30 ----------- ------------- = 0.8011 85 (EQ 9.9)
315 2625
PHS DIST Z1 REACH: "0.80"
PHS DIST Z1 RCA: "85"
PHS DIST Z1 XMFR VOL CONNECTION: "None"
PHS DIST Z1 XMFR CUR CONNECTION: "Dy1"
Withdraw or insert a module only when control power has been removed from the unit, and be
sure to insert only the correct module type into a slot, else personal injury, damage to the unit
or connected equipment, or undesired operation can result.
To avoid damage to the equipment, use proper electrostatic discharge protection (for example, a
static strap) when coming in contact with modules while the relay is energized.
The relay, being modular in design, allows for the withdrawal and insertion of modules. Modules must only be replaced with
like modules in their original factory configured slots.
The enhanced faceplate can be opened to the left, once the thumb screw has been removed, as shown below. This allows
for easy accessibility of the modules for withdrawal. The new wide-angle hinge assembly in the enhanced front panel opens
completely and allows easy access to all modules in the D60.
842812A1.CDR
To properly insert a module, ensure that the correct module type is inserted into the correct slot position. The ejector/
inserter clips located at the top and at the bottom of each module must be in the disengaged position as the module is
smoothly inserted into the slot. Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously.
When the clips have locked into position, the module will be fully inserted.
CPU connections must be individually disconnected from the module before the module can be removed from the
chassis.
NOTE
The new CT/VT modules can only be used with new CPUs; similarly, old CT/VT modules can only be used with old
CPUs. In the event that there is a mismatch between the CPU and CT/VT module, the relay does not function and
NOTE a DSP ERROR or HARDWARE MISMATCH error displays.
10
When required, the battery can be replaced. The power supply module contains the battery.
To avoid injury, ensure that the unit has been powered off for a minimum of three minutes
before replacing the battery.
Risk of fire if battery is replaced with incorrect type or polarity.
To replace the battery:
1. Turn off the power to the unit.
2. Wait a minimum of three minutes to ensure that there is no power to the battery.
3. As outlined in the previous section, open the unit by sliding up the latch on the right side of the front panel and opening
the panel to the left.
4. Unscrew the bracket on the front left of the unit so that you can open fully the front panel to access the power supply
module, which is typically in the first slot on the left side.
5. Simultaneously pull the ejector clips at the top and bottom of the power supply module and remove the module.
6. Unscrew the screw that attaches the metal cover to the module.
7. Slide the metal cover away from the clips about 1 cm (1/4 inch) and remove the cover.
8. Unclip the black plastic holder that keeps the battery in place. The plastic clips into the socket at the bottom on both
sides. Use a flat-head screwdriver if you cannot unclip the plastic with your fingers.
9. Observe the + and - polarity of the battery and replace it with the same polarity as marked on the battery holder.
Replace the battery with the identical make and model. For example, do not use a rechargeable battery.
Figure 10–3: BATTERY LOCATION ON POWER SUPPLY MODULE
10. Reinstall the battery clip and the metal cover, and reinsert the power supply module into the unit.
11. Power on the unit.
12. Dispose of the old battery as outlined in the next section.
10
EN Battery Disposal
This product contains a battery that cannot be disposed of as unsorted municipal waste in the European Union. See the product
documentation for specific battery information. The battery is marked with this symbol, which may include lettering to indicate cadmium
(Cd), lead (Pb), or mercury (Hg). For proper recycling return the battery to your supplier or to a designated collection point. For more
information see: www.recyclethis.info.
CS Nakládání s bateriemi
Tento produkt obsahuje baterie, které nemohou být zneškodněny v Evropské unii jako netříděný komunální odpadu. Viz dokumentace k
produktu pro informace pro konkrétní baterie. Baterie je označena tímto symbolem, který může zahrnovat i uvedena písmena, kadmium
(Cd), olovo (Pb), nebo rtuť (Hg). Pro správnou recyklaci baterií vraťte svémudodavateli nebo na určeném sběrném místě. Pro více informací
viz: www.recyclethis.info.
DA Batteri affald
Dette produkt indeholder et batteri som ikke kan bortskaffes sammen med almindeligt husholdningsaffald i Europa. Se
produktinformation for specifikke informationer om batteriet. Batteriet er forsynet med indgraveret symboler for hvad batteriet
indeholder: kadmium (Cd), bly (Pb) og kviksølv (Hg). Europæiske brugere af elektrisk udstyr skal aflevere kasserede produkter til genbrug
eller til leverandøren. Yderligere oplysninger findes på webstedet www.recyclethis.info.
DE Entsorgung von Batterien
Dieses Produkt beinhaltet eine Batterie, die nicht als unsortierter städtischer Abfall in der europäischen Union entsorgt werden darf.
Beachten Sie die spezifischen Batterie-informationen in der Produktdokumentation. Die Batterie ist mit diesem Symbol gekennzeichnet,
welches auch Hinweise auf möglicherweise enthaltene Stoffe wie Kadmium (Cd), Blei (Pb) oder Quecksilber (Hektogramm) darstellt. Für
die korrekte Wiederverwertung bringen Sie diese Batterie zu Ihrem lokalen Lieferanten zurück oder entsorgen Sie das Produkt an den
gekennzeichneten Sammelstellen. Weitere Informationen hierzu finden Sie auf der folgenden Website: www.recyclethis.info.
EL Απόρριψη μπαταριών
Αυτό το προϊόν περιέχει μια μπαταρία που δεν πρέπει να απορρίπτεται σε δημόσια συστήματα απόρριψης στην Ευρωπαϊκή
Κοινότητα. ∆είτε την τεκμηρίωση του προϊόντος για συγκεκριμένες πληροφορίες που αφορούν τη μπαταρία. Η μπαταρία είναι φέρει
σήμανση με αυτό το σύμβολο, το οποίο μπορεί να περιλαμβάνει γράμματα για να δηλώσουν το κάδμιο (Cd), τον μόλυβδο (Pb), ή τον
υδράργυρο (Hg). Για την κατάλληλη ανακύκλωση επιστρέψτε την μπαταρία στον προμηθευτή σας ή σε καθορισμένο σημείο συλλογής.
Για περισσότερες πληροφορίες δείτε: www.recyclethis.info.
ES Eliminacion de baterias
Este producto contiene una batería que no se pueda eliminar como basura normal sin clasificar en la Unión Europea. Examine la
documentación del producto para la información específica de la batería. La batería se marca con este símbolo, que puede incluir siglas
para indicar el cadmio (Cd), el plomo (Pb), o el mercurio (Hg ). Para el reciclaje apropiado, devuelva este producto a su distribuidor ó
deshágase de él en los puntos de reciclaje designados. Para mas información : wwwrecyclethis.info.
ET Patareide kõrvaldamine
Käesolev toode sisaldab patareisid, mida Euroopa Liidus ei tohi kõrvaldada sorteerimata olmejäätmetena. Andmeid patareide kohta
vaadake toote dokumentatsioonist. Patareid on märgistatud käesoleva sümboliga, millel võib olla kaadmiumi (Cd), pliid (Pb) või
elavhõbedat (Hg) tähistavad tähed. Nõuetekohaseks ringlusse võtmiseks tagastage patarei tarnijale või kindlaksmääratud
vastuvõtupunkti. Lisainformatsiooni saab Internetist aadressil: www.recyclethis.info.
FI Paristoje ja akkujen hävittäminen
Tuote sisältää pariston, jota ei saa hävittää Euroopan Unionin alueella talousjätteen mukana. Tarkista tuoteselosteesta tuotteen tiedot.
Paristo on merkitty tällä symbolilla ja saattaa sisältää cadmiumia (Cd), lyijyä (Pb) tai elohopeaa (Hg). Oikean kierrätystavan
varmistamiseksi palauta tuote paikalliselle jälleenmyyjälle tai palauta se paristojen keräyspisteeseen. Lisätietoja sivuilla
www.recyclethis.info.
FR Élimination des piles
Ce produit contient une batterie qui ne peuvent être éliminés comme déchets municipaux non triés dans l'Union européenne. Voir la
documentation du produit au niveau des renseignements sur la pile. La batterie est marqué de ce symbole, qui comprennent les
indications cadmium (Cd), plomb (Pb), ou mercure (Hg). Pour le recyclage, retourner la batterie à votre fournisseur ou à un point de
collecte. Pour plus d'informations, voir: www.recyclethis.info.
10
SV Kassering av batteri
Denna produkt innehåller ett batteri som inte får kastas i allmänna sophanteringssytem inom den europeiska unionen. Se
produktdokumentationen för specifik batteriinformation. Batteriet är märkt med denna symbol, vilket kan innebära att det innehåller
kadmium (Cd), bly (Pb) eller kvicksilver (Hg). För korrekt återvinning skall batteriet returneras till leverantören eller till en därför avsedd
deponering. För mer information, se: www.recyclethis.info.
TR Pil Geri Dönüşümü
Bu ürün Avrupa Birliği genel atık sistemlerine atılmaması gereken pil içermektedir. Daha detaylı pil bilgisi için ürünün kataloğunu
inceleyiniz. Bu sembolle işaretlenmiş piller Kadmiyum(Cd), Kurşun(Pb) ya da Civa(Hg) içerebilir. Doğru geri dönüşüm için ürünü yerel
tedarikçinize geri veriniz ya da özel işaretlenmiş toplama noktlarına atınız. Daha fazla bilgi için: www.recyclethis.info.
Global Contacts
North America 905-294-6222
Latin America +55 11 3614 1700
Europe, Middle East, Africa +(34) 94 485 88 00
Asia +86-21-2401-3208
India +91 80 41314617
10
FlexAnalog items are also viewable in a web browser. In the browser, enter the IP address of the UR, access the Device
A
Information Menu option, then the FlexAnalog Parameter Listing option.
A ADDRESS
6212
FLEXANALOG NAME
SRC 2 Ic RMS
UNITS
Amps
DESCRIPTION
Source 2 phase C current RMS
6214 SRC 2 In RMS Amps Source 2 neutral current RMS
6216 SRC 2 Ia Mag Amps Source 2 phase A current magnitude
6218 SRC 2 Ia Angle Degrees Source 2 phase A current angle
6219 SRC 2 Ib Mag Amps Source 2 phase B current magnitude
6221 SRC 2 Ib Angle Degrees Source 2 phase B current angle
6222 SRC 2 Ic Mag Amps Source 2 phase C current magnitude
6224 SRC 2 Ic Angle Degrees Source 2 phase C current angle
6225 SRC 2 In Mag Amps Source 2 neutral current magnitude
6227 SRC 2 In Angle Degrees Source 2 neutral current angle
6228 SRC 2 Ig RMS Amps Source 2 ground current RMS
6230 SRC 2 Ig Mag Degrees Source 2 ground current magnitude
6232 SRC 2 Ig Angle Amps Source 2 ground current angle
6233 SRC 2 I_0 Mag Degrees Source 2 zero-sequence current magnitude
6235 SRC 2 I_0 Angle Amps Source 2 zero-sequence current angle
6236 SRC 2 I_1 Mag Degrees Source 2 positive-sequence current magnitude
6238 SRC 2 I_1 Angle Amps Source 2 positive-sequence current angle
6239 SRC 2 I_2 Mag Degrees Source 2 negative-sequence current magnitude
6241 SRC 2 I_2 Angle Amps Source 2 negative-sequence current angle
6242 SRC 2 Igd Mag Degrees Source 2 differential ground current magnitude
6244 SRC 2 Igd Angle Amps Source 2 differential ground current angle
6272 SRC 3 Ia RMS Amps Source 3 phase A current RMS
6274 SRC 3 Ib RMS Amps Source 3 phase B current RMS
6276 SRC 3 Ic RMS Amps Source 3 phase C current RMS
6278 SRC 3 In RMS Amps Source 3 neutral current RMS
6280 SRC 3 Ia Mag Amps Source 3 phase A current magnitude
6282 SRC 3 Ia Angle Degrees Source 3 phase A current angle
6283 SRC 3 Ib Mag Amps Source 3 phase B current magnitude
6285 SRC 3 Ib Angle Degrees Source 3 phase B current angle
6286 SRC 3 Ic Mag Amps Source 3 phase C current magnitude
6288 SRC 3 Ic Angle Degrees Source 3 phase C current angle
6289 SRC 3 In Mag Amps Source 3 neutral current magnitude
6291 SRC 3 In Angle Degrees Source 3 neutral current angle
6292 SRC 3 Ig RMS Amps Source 3 ground current RMS
6294 SRC 3 Ig Mag Degrees Source 3 ground current magnitude
6296 SRC 3 Ig Angle Amps Source 3 ground current angle
6297 SRC 3 I_0 Mag Degrees Source 3 zero-sequence current magnitude
6299 SRC 3 I_0 Angle Amps Source 3 zero-sequence current angle
6300 SRC 3 I_1 Mag Degrees Source 3 positive-sequence current magnitude
6302 SRC 3 I_1 Angle Amps Source 3 positive-sequence current angle
6303 SRC 3 I_2 Mag Degrees Source 3 negative-sequence current magnitude
6305 SRC 3 I_2 Angle Amps Source 3 negative-sequence current angle
6306 SRC 3 Igd Mag Degrees Source 3 differential ground current magnitude
6308 SRC 3 Igd Angle Amps Source 3 differential ground current angle
6336 SRC 4 Ia RMS Amps Source 4 phase A current RMS
6338 SRC 4 Ib RMS Amps Source 4 phase B current RMS
6340 SRC 4 Ic RMS Amps Source 4 phase C current RMS
A ADDRESS
6720
FLEXANALOG NAME
SRC 2 Vag RMS
UNITS
Volts
DESCRIPTION
Source 2 phase AG voltage RMS
6722 SRC 2 Vbg RMS Volts Source 2 phase BG voltage RMS
6724 SRC 2 Vcg RMS Volts Source 2 phase CG voltage RMS
6726 SRC 2 Vag Mag Volts Source 2 phase AG voltage magnitude
6728 SRC 2 Vag Angle Degrees Source 2 phase AG voltage angle
6729 SRC 2 Vbg Mag Volts Source 2 phase BG voltage magnitude
6731 SRC 2 Vbg Angle Degrees Source 2 phase BG voltage angle
6732 SRC 2 Vcg Mag Volts Source 2 phase CG voltage magnitude
6734 SRC 2 Vcg Angle Degrees Source 2 phase CG voltage angle
6735 SRC 2 Vab RMS Volts Source 2 phase AB voltage RMS
6737 SRC 2 Vbc RMS Volts Source 2 phase BC voltage RMS
6739 SRC 2 Vca RMS Volts Source 2 phase CA voltage RMS
6741 SRC 2 Vab Mag Volts Source 2 phase AB voltage magnitude
6743 SRC 2 Vab Angle Degrees Source 2 phase AB voltage angle
6744 SRC 2 Vbc Mag Volts Source 2 phase BC voltage magnitude
6746 SRC 2 Vbc Angle Degrees Source 2 phase BC voltage angle
6747 SRC 2 Vca Mag Volts Source 2 phase CA voltage magnitude
6749 SRC 2 Vca Angle Degrees Source 2 phase CA voltage angle
6750 SRC 2 Vx RMS Volts Source 2 auxiliary voltage RMS
6752 SRC 2 Vx Mag Volts Source 2 auxiliary voltage magnitude
6754 SRC 2 Vx Angle Degrees Source 2 auxiliary voltage angle
6755 SRC 2 V_0 Mag Volts Source 2 zero-sequence voltage magnitude
6757 SRC 2 V_0 Angle Degrees Source 2 zero-sequence voltage angle
6758 SRC 2 V_1 Mag Volts Source 2 positive-sequence voltage magnitude
6760 SRC 2 V_1 Angle Degrees Source 2 positive-sequence voltage angle
6761 SRC 2 V_2 Mag Volts Source 2 negative-sequence voltage magnitude
6763 SRC 2 V_2 Angle Degrees Source 2 negative-sequence voltage angle
6784 SRC 3 Vag RMS Volts Source 3 phase AG voltage RMS
6786 SRC 3 Vbg RMS Volts Source 3 phase BG voltage RMS
6788 SRC 3 Vcg RMS Volts Source 3 phase CG voltage RMS
6790 SRC 3 Vag Mag Volts Source 3 phase AG voltage magnitude
6792 SRC 3 Vag Angle Degrees Source 3 phase AG voltage angle
6793 SRC 3 Vbg Mag Volts Source 3 phase BG voltage magnitude
6795 SRC 3 Vbg Angle Degrees Source 3 phase BG voltage angle
6796 SRC 3 Vcg Mag Volts Source 3 phase CG voltage magnitude
6798 SRC 3 Vcg Angle Degrees Source 3 phase CG voltage angle
6799 SRC 3 Vab RMS Volts Source 3 phase AB voltage RMS
6801 SRC 3 Vbc RMS Volts Source 3 phase BC voltage RMS
6803 SRC 3 Vca RMS Volts Source 3 phase CA voltage RMS
6805 SRC 3 Vab Mag Volts Source 3 phase AB voltage magnitude
6807 SRC 3 Vab Angle Degrees Source 3 phase AB voltage angle
6808 SRC 3 Vbc Mag Volts Source 3 phase BC voltage magnitude
6810 SRC 3 Vbc Angle Degrees Source 3 phase BC voltage angle
6811 SRC 3 Vca Mag Volts Source 3 phase CA voltage magnitude
6813 SRC 3 Vca Angle Degrees Source 3 phase CA voltage angle
6814 SRC 3 Vx RMS Volts Source 3 auxiliary voltage RMS
6816 SRC 3 Vx Mag Volts Source 3 auxiliary voltage magnitude
A ADDRESS
7193
FLEXANALOG NAME
SRC 1 Phase A PF
UNITS
---
DESCRIPTION
Source 1 phase A power factor
7194 SRC 1 Phase B PF --- Source 1 phase B power factor
7195 SRC 1 Phase C PF --- Source 1 phase C power factor
7200 SRC 2 P Watts Source 2 three-phase real power
7202 SRC 2 Pa Watts Source 2 phase A real power
7204 SRC 2 Pb Watts Source 2 phase B real power
7206 SRC 2 Pc Watts Source 2 phase C real power
7208 SRC 2 Q Vars Source 2 three-phase reactive power
7210 SRC 2 Qa Vars Source 2 phase A reactive power
7212 SRC 2 Qb Vars Source 2 phase B reactive power
7214 SRC 2 Qc Vars Source 2 phase C reactive power
7216 SRC 2 S VA Source 2 three-phase apparent power
7218 SRC 2 Sa VA Source 2 phase A apparent power
7220 SRC 2 Sb VA Source 2 phase B apparent power
7222 SRC 2 Sc VA Source 2 phase C apparent power
7224 SRC 2 PF --- Source 2 three-phase power factor
7225 SRC 2 Phase A PF --- Source 2 phase A power factor
7226 SRC 2 Phase B PF --- Source 2 phase B power factor
7227 SRC 2 Phase C PF --- Source 2 phase C power factor
7232 SRC 3 P Watts Source 3 three-phase real power
7234 SRC 3 Pa Watts Source 3 phase A real power
7236 SRC 3 Pb Watts Source 3 phase B real power
7238 SRC 3 Pc Watts Source 3 phase C real power
7240 SRC 3 Q Vars Source 3 three-phase reactive power
7242 SRC 3 Qa Vars Source 3 phase A reactive power
7244 SRC 3 Qb Vars Source 3 phase B reactive power
7246 SRC 3 Qc Vars Source 3 phase C reactive power
7248 SRC 3 S VA Source 3 three-phase apparent power
7250 SRC 3 Sa VA Source 3 phase A apparent power
7252 SRC 3 Sb VA Source 3 phase B apparent power
7254 SRC 3 Sc VA Source 3 phase C apparent power
7256 SRC 3 PF --- Source 3 three-phase power factor
7257 SRC 3 Phase A PF --- Source 3 phase A power factor
7258 SRC 3 Phase B PF --- Source 3 phase B power factor
7259 SRC 3 Phase C PF --- Source 3 phase C power factor
7264 SRC 4 P Watts Source 4 three-phase real power
7266 SRC 4 Pa Watts Source 4 phase A real power
7268 SRC 4 Pb Watts Source 4 phase B real power
7270 SRC 4 Pc Watts Source 4 phase C real power
7272 SRC 4 Q Vars Source 4 three-phase reactive power
7274 SRC 4 Qa Vars Source 4 phase A reactive power
7276 SRC 4 Qb Vars Source 4 phase B reactive power
7278 SRC 4 Qc Vars Source 4 phase C reactive power
7280 SRC 4 S VA Source 4 three-phase apparent power
7282 SRC 4 Sa VA Source 4 phase A apparent power
7284 SRC 4 Sb VA Source 4 phase B apparent power
7286 SRC 4 Sc VA Source 4 phase C apparent power
A ADDRESS
9538
FLEXANALOG NAME
PMU 1 Va Angle
UNITS
Degrees
DESCRIPTION
Phasor measurement unit 1 phase A voltage angle
9539 PMU 1 Vb Mag Volts Phasor measurement unit 1 phase B voltage magnitude
9541 PMU 1 Vb Angle Degrees Phasor measurement unit 1 phase B voltage angle
9542 PMU 1 Vc Mag Volts Phasor measurement unit 1 phase C voltage magnitude
9544 PMU 1 Vc Angle Degrees Phasor measurement unit 1 phase C voltage angle
9545 PMU 1 Vx Mag Volts Phasor measurement unit 1 auxiliary voltage magnitude
9547 PMU 1 Vx Angle Degrees Phasor measurement unit 1 auxiliary voltage angle
9548 PMU 1 V1 Mag Volts Phasor measurement unit 1 positive-sequence voltage magnitude
9550 PMU 1 V1 Angle Degrees Phasor measurement unit 1 positive-sequence voltage angle
9551 PMU 1 V2 Mag Volts Phasor measurement unit 1 negative-sequence voltage magnitude
9553 PMU 1 V2 Angle Degrees Phasor measurement unit 1 negative-sequence voltage angle
9554 PMU 1 V0 Mag Volts Phasor measurement unit 1 zero-sequence voltage magnitude
9556 PMU 1 V0 Angle Degrees Phasor measurement unit 1 zero-sequence voltage angle
9557 PMU 1 Ia Mag Amps Phasor measurement unit 1 phase A current magnitude
9559 PMU 1 Ia Angle Degrees Phasor measurement unit 1 phase A current angle
9560 PMU 1 Ib Mag Amps Phasor measurement unit 1 phase B current magnitude
9562 PMU 1 Ib Angle Degrees Phasor measurement unit 1 phase B current angle
9563 PMU 1 Ic Mag Amps Phasor measurement unit 1 phase C current magnitude
9565 PMU 1 Ic Angle Degrees Phasor measurement unit 1 phase C current angle
9566 PMU 1 Ig Mag Amps Phasor measurement unit 1 ground current magnitude
9568 PMU 1 Ig Angle Degrees Phasor measurement unit 1 ground current angle
9569 PMU 1 I1 Mag Amps Phasor measurement unit 1 positive-sequence current magnitude
9571 PMU 1 I1 Angle Degrees Phasor measurement unit 1 positive-sequence current angle
9572 PMU 1 I2 Mag Amps Phasor measurement unit 1 negative-sequence current magnitude
9574 PMU 1 I2 Angle Degrees Phasor measurement unit 1 negative-sequence current angle
9575 PMU 1 I0 Mag Amps Phasor measurement unit 1 zero-sequence current magnitude
9577 PMU 1 I0 Angle Degrees Phasor measurement unit 1 zero-sequence current angle
9578 PMU 1 Freq Hz Phasor measurement unit 1 frequency
9580 PMU 1 df dt Hz/s Phasor measurement unit 1 rate of change of frequency
9581 PMU 1 Conf Ch --- Phasor measurement unit 1 configuration change counter
12306 Oscill Num Triggers --- Oscillography number of triggers
13504 DCMA Inputs 1 Value mA dcmA input 1 actual value
13506 DCMA Inputs 2 Value mA dcmA input 2 actual value
13508 DCMA Inputs 3 Value mA dcmA input 3 actual value
13510 DCMA Inputs 4 Value mA dcmA input 4 actual value
13512 DCMA Inputs 5 Value mA dcmA input 5 actual value
13514 DCMA Inputs 6 Value mA dcmA input 6 actual value
13516 DCMA Inputs 7 Value mA dcmA input 7 actual value
13518 DCMA Inputs 8 Value mA dcmA input 8 actual value
13520 DCMA Inputs 9 Value mA dcmA input 9 actual value
13522 DCMA Inputs 10 Value mA dcmA input 10 actual value
13524 DCMA Inputs 11 Value mA dcmA input 11 actual value
13526 DCMA Inputs 12 Value mA dcmA input 12 actual value
13528 DCMA Inputs 13 Value mA dcmA input 13 actual value
13530 DCMA Inputs 14 Value mA dcmA input 14 actual value
13532 DCMA Inputs 15 Value mA dcmA input 15 actual value
13534 DCMA Inputs 16 Value mA dcmA input 16 actual value
A ADDRESS
13591
FLEXANALOG NAME
RTD Inputs 40 Value
UNITS
---
DESCRIPTION
RTD input 40 actual value
13592 RTD Inputs 41 Value --- RTD input 41 actual value
13593 RTD Inputs 42 Value --- RTD input 42 actual value
13594 RTD Inputs 43 Value --- RTD input 43 actual value
13595 RTD Inputs 44 Value --- RTD input 44 actual value
13596 RTD Inputs 45 Value --- RTD input 45 actual value
13597 RTD Inputs 46 Value --- RTD input 46 actual value
13598 RTD Inputs 47 Value --- RTD input 47 actual value
13599 RTD Inputs 48 Value --- RTD input 48 actual value
13600 Ohm Inputs 1 Value Ohms Ohm inputs 1 value
13601 Ohm Inputs 2 Value Ohms Ohm inputs 2 value
14189 PTP–IRIG-B Delta ns PTP time minus IRIG-B time
24447 Active Setting Group --- Current setting group
32768 Tracking Frequency Hz Tracking frequency
39168 FlexElement 1 Value --- FlexElement 1 actual value
39170 FlexElement 2 Value --- FlexElement 2 actual value
39172 FlexElement 3 Value --- FlexElement 3 actual value
39174 FlexElement 4 Value --- FlexElement 4 actual value
39176 FlexElement 5 Value --- FlexElement 5 actual value
39178 FlexElement 6 Value --- FlexElement 6 actual value
39180 FlexElement 7 Value --- FlexElement 7 actual value
39182 FlexElement 8 Value --- FlexElement 8 actual value
39184 FlexElement 9 Value --- FlexElement 9 actual value
39186 FlexElement 10 Value --- FlexElement 10 actual value
39188 FlexElement 11 Value --- FlexElemen 11 actual value
39190 FlexElement 12 Value --- FlexElement 12 actual value
39192 FlexElement 13 Value --- FlexElement 13 actual value
39194 FlexElement 14 Value --- FlexElement 14 actual value
39196 FlexElement 15 Value --- FlexElement 15 actual value
39198 FlexElement 16 Value --- FlexElement 16 actual value
41132 VTFF 1 V0 3rd Harmonic --- V0 3rd Harmonic 1
41134 VTFF 2 V0 3rd Harmonic --- V0 3rd Harmonic 2
41136 VTFF 3 V0 3rd Harmonic --- V0 3rd Harmonic 3
41138 VTFF 4 V0 3rd Harmonic --- V0 3rd Harmonic 4
41140 VTFF 5 V0 3rd Harmonic --- V0 3rd Harmonic 5
41142 VTFF 6 V0 3rd Harmonic --- V0 3rd Harmonic 6
45584 GOOSE Analog In 1 --- IEC 61850 GOOSE analog input 1
45586 GOOSE Analog In 2 --- IEC 61850 GOOSE analog input 2
45588 GOOSE Analog In 3 --- IEC 61850 GOOSE analog input 3
45590 GOOSE Analog In 4 --- IEC 61850 GOOSE analog input 4
45592 GOOSE Analog In 5 --- IEC 61850 GOOSE analog input 5
45594 GOOSE Analog In 6 --- IEC 61850 GOOSE analog input 6
45596 GOOSE Analog In 7 --- IEC 61850 GOOSE analog input 7
45598 GOOSE Analog In 8 --- IEC 61850 GOOSE analog input 8
45600 GOOSE Analog In 9 --- IEC 61850 GOOSE analog input 9
45602 GOOSE Analog In 10 --- IEC 61850 GOOSE analog input 10
45604 GOOSE Analog In 11 --- IEC 61850 GOOSE analog input 11
FlexInteger items are also viewable in a web browser. In the browser, enter the IP address of the UR, access the Device
Information Menu option, then the FlexInteger Parameter Listing option.
Table A–2: FLEXINTEGER DATA ITEMS
ADDRESS FLEXINTEGER NAME UNITS DESCRIPTION
9736 PMU 1 SOC seconds PMU 1 SOC timestamps
9738 PMU 1 FRACSEC seconds PMU 1 FRACSEC timestamps
9740 PMU 1 STAT --- PMU 1 STAT flags
9968 GOOSE UInt Input 1 --- IEC61850 GOOSE UInteger input 1
9970 GOOSE UInt Input 2 --- IEC61850 GOOSE UInteger input 2
9972 GOOSE UInt Input 3 --- IEC61850 GOOSE UInteger input 3
9974 GOOSE UInt Input 4 --- IEC61850 GOOSE UInteger input 4
9976 GOOSE UInt Input 5 --- IEC61850 GOOSE UInteger input 5
9978 GOOSE UInt Input 6 --- IEC61850 GOOSE UInteger input 6
9980 GOOSE UInt Input 7 --- IEC61850 GOOSE UInteger input 7
9982 GOOSE UInt Input 8 --- IEC61850 GOOSE UInteger input 8
9984 GOOSE UInt Input 9 --- IEC61850 GOOSE UInteger input 9
9986 GOOSE UInt Input 10 --- IEC61850 GOOSE UInteger input 10
9988 GOOSE UInt Input 11 --- IEC61850 GOOSE UInteger input 11
9990 GOOSE UInt Input 12 --- IEC61850 GOOSE UInteger input 12
9992 GOOSE UInt Input 13 --- IEC61850 GOOSE UInteger input 13
9994 GOOSE UInt Input 14 --- IEC61850 GOOSE UInteger input 14
9996 GOOSE UInt Input 15 --- IEC61850 GOOSE UInteger input 15
9998 GOOSE UInt Input 16 --- IEC61850 GOOSE UInteger input 16
The UR-series relays support a number of communications protocols to allow connection to equipment such as personal
computers, RTUs, SCADA masters, and programmable logic controllers. The Modicon Modbus RTU protocol is the most
basic protocol supported by the UR. Modbus is available via RS232 or RS485 serial links or via ethernet (using the Mod-
bus/TCP specification). The following description is intended primarily for users who wish to develop their own master com-
munication drivers and applies to the serial Modbus RTU protocol. Note that:
• The UR always acts as a slave device, meaning that it never initiates communications; it only listens and responds to
requests issued by a master computer.
• For Modbus, a subset of the Remote Terminal Unit (RTU) protocol format is supported that allows extensive monitor-
ing, programming, and control functions using read and write register commands.
Communications takes place in packets which are groups of asynchronously framed byte data. The master transmits a
packet to the slave and the slave responds with a packet. The end of a packet is marked by dead-time on the communica-
tions line. The following describes general format for both transmit and receive packets. For exact details on packet format-
ting, refer to subsequent sections describing each function code.
• SLAVE ADDRESS: This is the address of the slave device that is intended to receive the packet sent by the master
and to perform the desired action. Each slave device on a communications bus must have a unique address to prevent
bus contention. All of the relay’s ports have the same address which is programmable from 1 to 254; see chapter 5 for
details. Only the addressed slave will respond to a packet that starts with its address. Note that the faceplate port is an
exception to this rule; it will act on a message containing any slave address.
A master transmit packet with slave address 0 indicates a broadcast command. All slaves on the communication link
take action based on the packet, but none respond to the master. Broadcast mode is only recognized when associated
with function code 05h. For any other function code, a packet with broadcast mode slave address 0 will be ignored.
• FUNCTION CODE: This is one of the supported functions codes of the unit which tells the slave what action to per-
form. See the Supported Function Codes section for complete details. An exception response from the slave is indi-
cated by setting the high order bit of the function code in the response packet. See the Exception Responses section
for further details.
• DATA: This will be a variable number of bytes depending on the function code. This may include actual values, set-
tings, or addresses sent by the master to the slave or by the slave to the master.
• CRC: This is a two byte error checking code. The RTU version of Modbus includes a 16-bit cyclic redundancy check
(CRC-16) with every packet which is an industry standard method used for error detection. If a Modbus slave device
receives a packet in which an error is indicated by the CRC, the slave device will not act upon or respond to the packet
thus preventing any erroneous operations. See the CRC-16 Algorithm section for details on calculating the CRC.
• DEAD TIME: A packet is terminated when no data is received for a period of 3.5 byte transmission times (about 15 ms
at 2400 bps, 2 ms at 19200 bps, and 300 µs at 115200 bps). Consequently, the transmitting device must not allow gaps
B between bytes longer than this interval. Once the dead time has expired without a new byte transmission, all slaves
start listening for a new packet from the master except for the addressed slave.
The CRC-16 algorithm essentially treats the entire data stream (data bits only; start, stop and parity ignored) as one contin-
uous binary number. This number is first shifted left 16 bits and then divided by a characteristic polynomial
(11000000000000101B). The 16-bit remainder of the division is appended to the end of the packet, MSByte first. The
resulting packet including CRC, when divided by the same polynomial at the receiver will give a zero remainder if no trans-
mission errors have occurred. This algorithm requires the characteristic polynomial to be reverse bit ordered. The most sig-
nificant bit of the characteristic polynomial is dropped, since it does not affect the value of the remainder.
A C programming language implementation of the CRC algorithm will be provided upon request.
Modbus officially defines function codes from 1 to 127 though only a small subset is generally needed. The relay supports
some of these functions, as summarized in the following table. Subsequent sections describe each function code in detail.
This function code allows the master to read one or more consecutive data registers (actual values or settings) from a relay.
Data registers are always 16-bit (two-byte) values transmitted with high order byte first. The maximum number of registers
that can be read in a single packet is 125. See the Modbus memory map table for exact details on the data registers.
Since some PLC implementations of Modbus only support one of function codes 03h and 04h. The D60 interpretation
allows either function code to be used for reading one or more consecutive data registers. The data starting address will
determine the type of data being read. Function codes 03h and 04h are therefore identical.
The following table shows the format of the master and slave packets. The example shows a master device requesting
three register values starting at address 4050h from slave device 11h (17 decimal); the slave device responds with the val-
ues 40, 300, and 0 from registers 4050h, 4051h, and 4052h, respectively.
This function code allows the master to perform various operations in the relay. Available operations are shown in the Sum-
mary of operation codes table below.
The following table shows the format of the master and slave packets. The example shows a master device requesting the
slave device 11h (17 decimal) to perform a reset. The high and low code value bytes always have the values “FF” and “00”
respectively and are a remnant of the original Modbus definition of this function code.
This function code allows the master to modify the contents of a single setting register in an relay. Setting registers are
always 16 bit (two byte) values transmitted high order byte first. The following table shows the format of the master and
slave packets. The example shows a master device storing the value 200 at memory map address 4051h to slave device
11h (17 dec).
This function code allows the master to modify the contents of a one or more consecutive setting registers in a relay. Setting
registers are 16-bit (two byte) values transmitted high order byte first. The maximum number of setting registers that can be
stored in a single packet is 60. The following table shows the format of the master and slave packets. The example shows
a master device storing the value 200 at memory map address 4051h, and the value 1 at memory map address 4052h to
slave device 11h (17 decimal).
Programming or operation errors usually happen because of illegal data in a packet. These errors result in an exception
response from the slave. The slave detecting one of these errors sends a response packet to the master with the high order
bit of the function code set to 1.
The following table shows the format of the master and slave packets. The example shows a master device sending the
unsupported function code 39h to slave device 11.
a) DESCRIPTION
The UR relay has a generic file transfer facility, meaning that you use the same method to obtain all of the different types of
files from the unit. The Modbus registers that implement file transfer are found in the "Modbus File Transfer (Read/Write)"
and "Modbus File Transfer (Read Only)" modules, starting at address 3100 in the Modbus Memory Map. To read a file from
the UR relay, use the following steps:
1. Write the filename to the "Name of file to read" register using a write multiple registers command. If the name is shorter
than 80 characters, you may write only enough registers to include all the text of the filename. Filenames are not case
sensitive.
2. Repeatedly read all the registers in "Modbus File Transfer (Read Only)" using a read multiple registers command. It is
not necessary to read the entire data block, since the UR relay will remember which was the last register you read. The
B "position" register is initially zero and thereafter indicates how many bytes (2 times the number of registers) you have
read so far. The "size of..." register indicates the number of bytes of data remaining to read, to a maximum of 244.
3. Keep reading until the "size of..." register is smaller than the number of bytes you are transferring. This condition indi-
cates end of file. Discard any bytes you have read beyond the indicated block size.
4. If you need to re-try a block, read only the "size of.." and "block of data", without reading the position. The file pointer is
only incremented when you read the position register, so the same data block will be returned as was read in the pre-
vious operation. On the next read, check to see if the position is where you expect it to be, and discard the previous
block if it is not (this condition would indicate that the UR relay did not process your original read request).
The UR relay retains connection-specific file transfer information, so files may be read simultaneously on multiple Modbus
connections.
b) OTHER PROTOCOLS
All the files available via Modbus may also be retrieved using the standard file transfer mechanisms in other protocols (for
example, TFTP or MMS).
Command and setting passwords each have a 30 minute timer. Each timer starts when you enter the particular password,
and is re-started whenever you use it. For example, writing a setting re-starts the setting password timer and writing a com-
mand register or forcing a coil re-starts the command password timer. The value read at memory location 4010 can be used
to confirm whether a command password is enabled or disabled (a value of 0 represents disabled). The value read at mem-
ory location 4011 can be used to confirm whether a setting password is enabled or disabled.
Command or setting password security access is restricted to the particular port or particular TCP/IP connection on which
the entry was made. Passwords must be entered when accessing the relay through other ports or connections, and the
passwords must be re-entered after disconnecting and re-connecting on TCP/IP.
The map is also viewable in a web browser. In the browser, enter the IP address of the UR and click the option.
B
0420 Virtual Input 33 State 0 to 1 --- 1 F108 0 (Off)
0421 Virtual Input 34 State 0 to 1 --- 1 F108 0 (Off)
0422 Virtual Input 35 State 0 to 1 --- 1 F108 0 (Off)
0423 Virtual Input 36 State 0 to 1 --- 1 F108 0 (Off)
0424 Virtual Input 37 State 0 to 1 --- 1 F108 0 (Off)
0425 Virtual Input 38 State 0 to 1 --- 1 F108 0 (Off)
0426 Virtual Input 39 State 0 to 1 --- 1 F108 0 (Off)
0427 Virtual Input 40 State 0 to 1 --- 1 F108 0 (Off)
0428 Virtual Input 41 State 0 to 1 --- 1 F108 0 (Off)
0429 Virtual Input 42 State 0 to 1 --- 1 F108 0 (Off)
042A Virtual Input 43 State 0 to 1 --- 1 F108 0 (Off)
042B Virtual Input 44 State 0 to 1 --- 1 F108 0 (Off)
042C Virtual Input 45 State 0 to 1 --- 1 F108 0 (Off)
042D Virtual Input 46 State 0 to 1 --- 1 F108 0 (Off)
042E Virtual Input 47 State 0 to 1 --- 1 F108 0 (Off)
042F Virtual Input 48 State 0 to 1 --- 1 F108 0 (Off)
0430 Virtual Input 49 State 0 to 1 --- 1 F108 0 (Off)
0431 Virtual Input 50 State 0 to 1 --- 1 F108 0 (Off)
0432 Virtual Input 51 State 0 to 1 --- 1 F108 0 (Off)
0433 Virtual Input 52 State 0 to 1 --- 1 F108 0 (Off)
0434 Virtual Input 53 State 0 to 1 --- 1 F108 0 (Off)
0435 Virtual Input 54 State 0 to 1 --- 1 F108 0 (Off)
0436 Virtual Input 55 State 0 to 1 --- 1 F108 0 (Off)
0437 Virtual Input 56 State 0 to 1 --- 1 F108 0 (Off)
0438 Virtual Input 57 State 0 to 1 --- 1 F108 0 (Off)
0439 Virtual Input 58 State 0 to 1 --- 1 F108 0 (Off)
043A Virtual Input 59 State 0 to 1 --- 1 F108 0 (Off)
043B Virtual Input 60 State 0 to 1 --- 1 F108 0 (Off)
043C Virtual Input 61 State 0 to 1 --- 1 F108 0 (Off)
043D Virtual Input 62 State 0 to 1 --- 1 F108 0 (Off)
043E Virtual Input 63 State 0 to 1 --- 1 F108 0 (Off)
043F Virtual Input 64 State 0 to 1 --- 1 F108 0 (Off)
Digital Counter States (Read Only Non-Volatile) (8 modules)
0800 Digital Counter 1 Value -2147483647 to --- 1 F004 0
2147483647
0802 Digital Counter 1 Frozen -2147483647 to --- 1 F004 0
2147483647
0804 Digital Counter 1 Frozen Time Stamp 0 to 4294967295 --- 1 F050 0
0806 Digital Counter 1 Frozen Time Stamp us 0 to 4294967295 --- 1 F003 0
0808 ...Repeated for Digital Counter 2
0810 ...Repeated for Digital Counter 3
0818 ...Repeated for Digital Counter 4
0820 ...Repeated for Digital Counter 5
0828 ...Repeated for Digital Counter 6
0830 ...Repeated for Digital Counter 7
B
1612 Ethernet tertiary fibre channel status 0 to 2 --- 1 F134 0 (Fail)
Data Logger Actuals (Read Only)
1618 Data logger channel count 0 to 16 channel 1 F001 0
1619 Time of oldest available samples 0 to 4294967295 seconds 1 F050 0
161B Time of newest available samples 0 to 4294967295 seconds 1 F050 0
161D Data logger duration 0 to 999.9 days 0.1 F001 0
Sensitive Directional Power Actuals (Read Only) (2 modules)
1680 Sensitive Directional Power 1 Power -2147483647 to 2147483647 W 1 F060 0
1682 Sensitive Directional Power 2 Power -2147483647 to 2147483647 W 1 F060 0
Field Unit RTD Actuals (Read Only) (8 modules)
16C0 Field RTD x Value -32768 to 32767 °C 1 F002 0
16C1 ...Repeated for module number 2
16C2 ...Repeated for module number 3
16C3 ...Repeated for module number 4
16C4 ...Repeated for module number 5
16C5 ...Repeated for module number 6
16C6 ...Repeated for module number 7
16C7 ...Repeated for module number 8
Field Unit Transducer Actuals (Read Only) (8 modules)
16C8 Field Transducer x Value -32.768 to 32.767 --- 0.001 F004 0
16CA ...Repeated for module number 2
16CC ...Repeated for module number 3
16CE ...Repeated for module number 4
16D0 ...Repeated for module number 5
16D2 ...Repeated for module number 6
16D4 ...Repeated for module number 7
16D6 ...Repeated for module number 8
Frequency Rate of Change Actuals (Read Only) (4 modules)
16E0 Frequency Rate of Change 1 -327.67 to 327.67 Hz/s 0.01 F002 0
16E1 Reserved (3 items) 0 to 65535 --- 1 F001 0
16E4 ...Repeated for Frequency Rate of Change 2
16E8 ...Repeated for Frequency Rate of Change 3
16EC ...Repeated for Frequency Rate of Change 4
Source Current (Read Only) (6 modules)
1800 Source 1 Phase A Current RMS 0 to 999999.999 A 0.001 F060 0
1802 Source 1 Phase B Current RMS 0 to 999999.999 A 0.001 F060 0
1804 Source 1 Phase C Current RMS 0 to 999999.999 A 0.001 F060 0
1806 Source 1 Neutral Current RMS 0 to 999999.999 A 0.001 F060 0
1808 Source 1 Phase A Current Magnitude 0 to 999999.999 A 0.001 F060 0
180A Source 1 Phase A Current Angle -359.9 to 0 degrees 0.1 F002 0
180B Source 1 Phase B Current Magnitude 0 to 999999.999 A 0.001 F060 0
180D Source 1 Phase B Current Angle -359.9 to 0 degrees 0.1 F002 0
180E Source 1 Phase C Current Magnitude 0 to 999999.999 A 0.001 F060 0
1810 Source 1 Phase C Current Angle -359.9 to 0 degrees 0.1 F002 0
B
2357 Fault 1 Phase B Current Angle -359.9 to 0 degrees 0.1 F002 0
2358 Fault 1 Phase C Current Magnitude 0 to 999999.999 A 0.001 F060 0
235A Fault 1 Phase C Current Angle -359.9 to 0 degrees 0.1 F002 0
235B Fault 1 Phase A Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
235D Fault 1 Phase A Voltage Angle -359.9 to 0 degrees 0.1 F002 0
235E Fault 1 Phase B Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
2360 Fault 1 Phase B Voltage Angle -359.9 to 0 degrees 0.1 F002 0
2361 Fault 1 Phase C Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
2363 Fault 1 Phase C Voltage Angle -359.9 to 0 degrees 0.1 F002 0
2364 Fault 1 Type 0 to 11 --- 1 F148 0 (NA)
2365 Fault 1 Location based on Line length units (km or miles) -3276.7 to 3276.7 --- 0.1 F002 0
2366 ...Repeated for Fault 2
238C ...Repeated for Fault 3
23B2 ...Repeated for Fault 4
23D8 ...Repeated for Fault 5
Synchrocheck Actuals (Read Only) (4 modules)
2400 Synchrocheck 1 Delta Voltage -1000000000000 to V 1 F060 0
1000000000000
2402 Synchrocheck 1 Delta Frequency 0 to 655.35 Hz 0.01 F001 0
2403 Synchrocheck 1 Delta Phase 0 to 359.9 degrees 0.1 F001 0
2404 ...Repeated for Synchrocheck 2
2408 ...Repeated for Synchrocheck 3
240C ...Repeated for Synchrocheck 4
Autoreclose Status (Read Only) (6 modules)
2410 Autoreclose 1 Count 0 to 65535 --- 1 F001 0
2411 Autoreclose 2 Count 0 to 65535 --- 1 F001 0
2412 Autoreclose 3 Count 0 to 65535 --- 1 F001 0
2413 Autoreclose 4 Count 0 to 65535 --- 1 F001 0
2414 Autoreclose 5 Count 0 to 65535 --- 1 F001 0
2415 Autoreclose 6 Count 0 to 65535 --- 1 F001 0
Field Unit Raw Data Settings (Read/Write Setting)
2460 Field Raw Data Port 0 to 7 --- 1 F244 6 (H1a)
2461 Field Raw Data Freeze 0 to 1 --- 1 F102 0 (Disabled)
Phasor Measurement Unit actual values (Read Only) (4 modules)
2540 PMU 1 Phase A Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
2542 PMU Unit 1 Phase A Voltage Angle -359.9 to 0 ° 0.1 F002 0
2543 PMU 1 Phase B Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
2545 PMU 1 Phase B Voltage Angle -359.9 to 0 ° 0.1 F002 0
2546 PMU 1 Phase C Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
2548 PMU 1 Phase C Voltage Angle -359.9 to 0 ° 0.1 F002 0
2549 PMU 1 Auxiliary Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
254B PMU 1 Auxiliary Voltage Angle -359.9 to 0 ° 0.1 F002 0
254C PMU 1 Positive Sequence Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
254E PMU 1 Positive Sequence Voltage Angle -359.9 to 0 ° 0.1 F002 0
B
2702 IEC 61850 received uinteger 10 0 to 4294967295 --- 1 F003 0
2704 IEC 61850 received uinteger 11 0 to 4294967295 --- 1 F003 0
2706 IEC 61850 received uinteger 12 0 to 4294967295 --- 1 F003 0
2708 IEC 61850 received uinteger 13 0 to 4294967295 --- 1 F003 0
270A IEC 61850 received uinteger 14 0 to 4294967295 --- 1 F003 0
270C IEC 61850 received uinteger 15 0 to 4294967295 --- 1 F003 0
270E IEC 61850 received uinteger 16 0 to 4294967295 --- 1 F003 0
Expanded FlexStates (Read Only)
2B00 FlexStates, one per register (256 items) 0 to 1 --- 1 F108 0 (Off)
Expanded Digital Input/Output states (Read Only)
2D00 Contact Input States, one per register (96 items) 0 to 1 --- 1 F108 0 (Off)
2D80 Contact Output States, one per register (64 items) 0 to 1 --- 1 F108 0 (Off)
2E00 Virtual Output States, one per register (96 items) 0 to 1 --- 1 F108 0 (Off)
Expanded Remote Input/Output Status (Read Only)
2F00 Remote Device States, one per register (16 items) 0 to 1 --- 1 F155 0 (Offline)
2F80 Remote Input States, one per register (64 items) 0 to 1 --- 1 F108 0 (Off)
Oscillography Values (Read Only)
3000 Oscillography Number of Triggers 0 to 65535 --- 1 F001 0
3001 Oscillography Available Records 0 to 65535 --- 1 F001 0
3002 Oscillography Last Cleared Date 0 to 400000000 --- 1 F050 0
3004 Oscillography Number Of Cycles Per Record 0 to 65535 --- 1 F001 0
Oscillography Commands (Read/Write Command)
3005 Oscillography Force Trigger 0 to 1 --- 1 F126 0 (No)
3011 Oscillography Clear Data 0 to 1 --- 1 F126 0 (No)
3012 Oscillography Number of Triggers 0 to 32767 --- 1 F001 0
Fault Report Indexing (Read Only Non-Volatile)
3020 Number of Fault Reports 0 to 65535 --- 1 F001 0
Fault Report Actuals (Read Only Non-Volatile) (15 modules)
3030 Fault Report 1 Time 0 to 4294967295 --- 1 F050 0
3032 Fault Report 2 Time 0 to 4294967295 --- 1 F050 0
3034 Fault Report 3 Time 0 to 4294967295 --- 1 F050 0
3036 Fault Report 4 Time 0 to 4294967295 --- 1 F050 0
3038 Fault Report 5 Time 0 to 4294967295 --- 1 F050 0
303A Fault Report 6 Time 0 to 4294967295 --- 1 F050 0
303C Fault Report 7 Time 0 to 4294967295 --- 1 F050 0
303E Fault Report 8 Time 0 to 4294967295 --- 1 F050 0
3040 Fault Report 9 Time 0 to 4294967295 --- 1 F050 0
3042 Fault Report 10 Time 0 to 4294967295 --- 1 F050 0
3044 Fault Report 11 Time 0 to 4294967295 --- 1 F050 0
3046 Fault Report 12 Time 0 to 4294967295 --- 1 F050 0
3048 Fault Report 13 Time 0 to 4294967295 --- 1 F050 0
304A Fault Report 14 Time 0 to 4294967295 --- 1 F050 0
304C Fault Report 15 Time 0 to 4294967295 --- 1 F050 0
B
34D6 DCMA Inputs 12 Value -9999999 to 9999999 --- 1 F004 0
34D8 DCMA Inputs 13 Value -9999999 to 9999999 --- 1 F004 0
34DA DCMA Inputs 14 Value -9999999 to 9999999 --- 1 F004 0
34DC DCMA Inputs 15 Value -9999999 to 9999999 --- 1 F004 0
34DE DCMA Inputs 16 Value -9999999 to 9999999 --- 1 F004 0
34E0 DCMA Inputs 17 Value -9999999 to 9999999 --- 1 F004 0
34E2 DCMA Inputs 18 Value -9999999 to 9999999 --- 1 F004 0
34E4 DCMA Inputs 19 Value -9999999 to 9999999 --- 1 F004 0
34E6 DCMA Inputs 20 Value -9999999 to 9999999 --- 1 F004 0
34E8 DCMA Inputs 21 Value -9999999 to 9999999 --- 1 F004 0
34EA DCMA Inputs 22 Value -9999999 to 9999999 --- 1 F004 0
34EC DCMA Inputs 23 Value -9999999 to 9999999 --- 1 F004 0
34EE DCMA Inputs 24 Value -9999999 to 9999999 --- 1 F004 0
RTD Input Values (Read Only) (48 modules)
34F0 RTD Input 1 Value -32768 to 32767 °C 1 F002 0
34F1 RTD Input 2 Value -32768 to 32767 °C 1 F002 0
34F2 RTD Input 3 Value -32768 to 32767 °C 1 F002 0
34F3 RTD Input 4 Value -32768 to 32767 °C 1 F002 0
34F4 RTD Input 5 Value -32768 to 32767 °C 1 F002 0
34F5 RTD Input 6 Value -32768 to 32767 °C 1 F002 0
34F6 RTD Input 7 Value -32768 to 32767 °C 1 F002 0
34F7 RTD Input 8 Value -32768 to 32767 °C 1 F002 0
34F8 RTD Input 9 Value -32768 to 32767 °C 1 F002 0
34F9 RTD Input 10 Value -32768 to 32767 °C 1 F002 0
34FA RTD Input 11 Value -32768 to 32767 °C 1 F002 0
34FB RTD Input 12 Value -32768 to 32767 °C 1 F002 0
34FC RTD Input 13 Value -32768 to 32767 °C 1 F002 0
34FD RTD Input 14 Value -32768 to 32767 °C 1 F002 0
34FE RTD Input 15 Value -32768 to 32767 °C 1 F002 0
34FF RTD Input 16 Value -32768 to 32767 °C 1 F002 0
3500 RTD Input 17 Value -32768 to 32767 °C 1 F002 0
3501 RTD Input 18 Value -32768 to 32767 °C 1 F002 0
3502 RTD Input 19 Value -32768 to 32767 °C 1 F002 0
3503 RTD Input 20 Value -32768 to 32767 °C 1 F002 0
3504 RTD Input 21 Value -32768 to 32767 °C 1 F002 0
3505 RTD Input 22 Value -32768 to 32767 °C 1 F002 0
3506 RTD Input 23 Value -32768 to 32767 °C 1 F002 0
3507 RTD Input 24 Value -32768 to 32767 °C 1 F002 0
3508 RTD Input 25 Value -32768 to 32767 °C 1 F002 0
3509 RTD Input 26 Value -32768 to 32767 °C 1 F002 0
350A RTD Input 27 Value -32768 to 32767 °C 1 F002 0
350B RTD Input 28 Value -32768 to 32767 °C 1 F002 0
350C RTD Input 29 Value -32768 to 32767 °C 1 F002 0
350D RTD Input 30 Value -32768 to 32767 °C 1 F002 0
B
381E ...Repeated for Filed Unit 3
382D ...Repeated for Filed Unit 4
383C ...Repeated for Filed Unit 5
384B ...Repeated for Filed Unit 6
385A ...Repeated for Filed Unit 7
3869 ...Repeated for Filed Unit 8
Field Unit Process Card Ports (Read/Write Setting)
3878 Field Unit 1 Process Card Port 0 to 7 --- 1 F244 6 (H1a)
3879 Field Unit 2 Process Card Port 0 to 7 --- 1 F244 4 (H2a)
387A Field Unit3 Process Card Port 0 to 7 --- 1 F244 2 (H3a)
387B Field Unit 4 Process Card Port 0 to 7 --- 1 F244 0 (H4a)
387C Field Unit 5 Process Card Port 0 to 7 --- 1 F244 7 (H1b)
387D Field Unit 6 Process Card Port 0 to 7 --- 1 F244 5 (H2b)
387E Field Unit 7 Process Card Port 0 to 7 --- 1 F244 3 (H3b)
387F Field Unit 8 Process Card Port 0 to 7 --- 1 F244 1 (H4b)
Field Unit CT VT Settings (Read/Write Setting) (6 modules)
3890 Remote Phase CT x Origin 1 0 to 16 --- 1 F247 0 (none)
3891 Remote Phase CT x Origin 2 0 to 16 --- 1 F247 0 (none)
3892 Remote Ground CT x Origin 1 0 to 16 --- 1 F248 0 (none))
3893 Remote Ground CT x Origin 2 0 to 16 --- 1 F248 0 (none)
3894 AC Bank Redundancy Type 0 to 2 --- 1 F261 1 (Dependability
Biased)
3895 Remote Phase CT 1 Primary 1 to 65000 --- 1 F001 1
3896 Remote Phase CT 1 Secondary 0 to 1 --- 1 F123 0 (1 A)
3897 Remote Ground CT 1 Primary 1 to 65000 --- 1 F001 1
3898 Remote Ground CT 1 Secondary 0 to 1 --- 1 F123 0 (1 A)
3899 Remote Phase VT 1 Connection 0 to 1 --- 1 F100 0 (Wye)
389A Remote Phase VT 1 Secondary 25 to 240 --- 0.1 F001 664
389B Remote Phase VT 1 Ratio 1 to 24000 --- 1 F060 1
389D Remote Auxiliary VT 1 Connection 0 to 6 --- 1 F166 1 (Vag)
389E Remote Auxiliary VT 1 Secondary 25 to 240 --- 0.1 F001 664
389F Remote Auxiliary VT 1 Ratio 1 to 24000 --- 1 F060 1
38A1 ...Repeated for module number 2
38B2 ...Repeated for module number 3
38C3 ...Repeated for module number 4
38D4 ...Repeated for module number 5
38E5 ...Repeated for module number 6
Field Unit Contact Inputs (Read/Write Setting) (40 modules)
3900 Field Contact Input 1 ID --- --- 1 F205 "FCI 1"
3906 Field Contact Input 1 Origin 0 to 8 --- 1 F256 0 (none)
3907 Field Contact Input 1 Input 1 to 18 --- 1 F001 1
3908 Field Contact Input 1 Failsafe Value 0 to 1 --- 1 F108 0 (Off)
3909 Field Contact Input 1 Debounce Time 0 to 16 ms 0.5 F001 20
390A Field Contact Input 1 Events 0 to 1 --- 1 F102 1 (Enabled)
B
3BD2 ...Repeated for Field Contact Output 2
3C14 ...Repeated for Field Contact Output 3
3C56 ...Repeated for Field Contact Output 4
3C98 ...Repeated for Field Contact Output 5
3CDA ...Repeated for Field Contact Output 6
3D1C ...Repeated for Field Contact Output 7
3D5E ...Repeated for Field Contact Output 8
Field Unit Latching Outputs (Read/Write Setting) (8 modules)
3DC7 Field Latching Output 1 ID 0 to 1 --- --- F205 "FLO Ux /LO"
3DCD Field Latching Output 1 Open 0 to 4294967295 --- 1 F300 0
3DCF Field Latching Output 1 Close 0 to 4294967295 --- 1 F300 0
3DD1 Field Latching Output 1 Events 0 to 1 --- 1 F102 1 (Enabled)
3DD2 Field Latching Output 1 Reserved (2 items) 0 to 1 --- 1 F001 0
3DD4 ...Repeated for Fielding Latching Output 2
3DE1 ...Repeated for Field Contact Output 3
3DEE ...Repeated for Field Contact Output 4
3DFB ...Repeated for Field Contact Output 5
3E08 ...Repeated for Field Contact Output 6
3E15 ...Repeated for Field Contact Output 7
3E22 ...Repeated for Field Contact Output 8
Field Unit Shared Outputs (Read/Write Setting) (16 modules)
3E30 Field Shared Output 1 ID 0 to 65535 --- --- F205 "SO 1"
3E36 Field Shared Output 1 Operate 0 to 4294967295 --- 1 F300 0
3E38 Field Shared Output 1 Unit Dest 1 0 to 8 --- 1 F256 0 (none)
3E39 Field Shared Output 1 Channel Dest 1 0 to 15 --- 1 F001 1
3E3A Field Shared Output 1 Unit Dest 2 0 to 8 --- 1 F256 0 (none)
3E3B Field Shared Output 1 Channel Dest 2 1 to 15 --- 1 F001 1
3E3C Field Shared Output 1 Events 0 to 1 --- 1 F102 1 (Enabled)
3E3D ...Repeated for Field Shared Output 2
3E4A ...Repeated for Field Shared Output 3
3E57 ...Repeated for Field Shared Output 4
3E64 ...Repeated for Field Shared Output 5
3E71 ...Repeated for Field Shared Output 6
3E7E ...Repeated for Field Shared Output 7
3E8B ...Repeated for Field Shared Output 8
3E98 ...Repeated for Field Shared Output 9
3EA5 ...Repeated for Field Shared Output 10
3EB2 ...Repeated for Field Shared Output 11
3EBF ...Repeated for Field Shared Output 12
3ECC ...Repeated for Field Shared Output 13
3ED9 ...Repeated for Field Shared Output 14
3EE6 ...Repeated for Field Shared Output 15
3EF3 ...Repeated for Field Shared Output 16
B
4049 LED Test Control 0 to 4294967295 --- 1 F300 0
Preferences (Read/Write Setting)
404F Language 0 to 3 --- 1 F531 0 (English)
4050 Flash Message Time 0.5 to 10 s 0.1 F001 10
4051 Default Message Timeout 10 to 900 s 1 F001 300
4052 Default Message Intensity 0 to 3 --- 1 F101 0 (25%)
4053 Screen Saver Feature 0 to 1 --- 1 F102 0 (Disabled)
4054 Screen Saver Wait Time 1 to 65535 min 1 F001 30
4055 Current Cutoff Level 0.002 to 0.02 pu 0.001 F001 20
4056 Voltage Cutoff Level 0.1 to 1 V 0.1 F001 10
Communications (Read/Write Setting)
407D COM2 Selection 0 to 3 --- 1 F601 0 (RS485)
407F COM2 Minimum Response Time 0 to 1000 ms 10 F001 0
4080 Modbus Slave Address 1 to 254 --- 1 F001 254
4085 RS485 Com2 Baud Rate 0 to 11 --- 1 F112 8 (115200)
4086 RS485 Com2 Parity 0 to 2 --- 1 F113 0 (None)
4087 IP Address 0 to 4294967295 --- 1 F003 56554706
4089 IP Subnet Mask 0 to 4294967295 --- 1 F003 4294966272
408B Port 1 Gateway IP Address 0 to 4294967295 --- 1 F003 56554497
4097 Port 1 Link Loss Alert 0 to 1 --- 1 F102 0 (Disabled)
4098 Port 2 Link Loss Alert 0 to 1 --- 1 F102 0 (Disabled)
4099 Port 3 Link Loss Alert 0 to 1 --- 1 F102 0 (Disabled)
409A DNP Channel 1 Port 0 to 5 --- 1 F177 0 (None)
409B DNP Channel 2 Port 0 to 5 --- 1 F177 0 (None)
409C DNP Address 0 to 65519 --- 1 F001 1
409E DNP Client Addresses (2 items) 0 to 4294967295 --- 1 F003 0
40A3 TCP Port Number for the Modbus protocol 0 to 65535 --- 1 F001 502
40A4 TCP/UDP Port Number for the DNP Protocol 0 to 65535 --- 1 F001 20000
40A5 TCP Port Number for the HTTP (Web Server) Protocol 0 to 65535 --- 1 F001 80
40A6 Main UDP Port Number for the TFTP Protocol 0 to 65535 --- 1 F001 69
40A7 Data Transfer UDP Port Numbers for the TFTP Protocol 0 to 65535 --- 1 F001 0
(zero means “automatic”) (2 items)
40A9 DNP Unsolicited Responses Function 0 to 1 --- 1 F102 0 (Disabled)
40AA DNP Unsolicited Responses Timeout 0 to 60 s 1 F001 5
40AB DNP unsolicited responses maximum retries 1 to 255 --- 1 F001 10
40AC DNP unsolicited responses destination address 0 to 65519 --- 1 F001 1
40AD Ethernet operation mode 0 to 1 --- 1 F192 1 (Half-Duplex)
40AE DNP current scale factor 0 to 8 --- 1 F194 2 (1)
40AF DNP voltage scale factor 0 to 8 --- 1 F194 2 (1)
40B0 DNP power scale factor 0 to 8 --- 1 F194 2 (1)
40B1 DNP energy scale factor 0 to 8 --- 1 F194 2 (1)
40B2 DNP power scale factor 0 to 8 --- 1 F194 2 (1)
40B3 DNP other scale factor 0 to 8 --- 1 F194 2 (1)
40B4 DNP current default deadband 0 to 100000000 --- 1 F003 30000
B
4192 Data Logger Trigger 0 to 4294967295 --- 1 F300 0
4194 Data Logger Rate 15 to 3600000 ms 1 F003 60000
Clock (Read/Write Setting)
419F Synchronizing Source 0 to 3 --- 1 F623 0 (none)
Clock (Read/Write Command)
41A0 Real Time Clock Set Time 0 to 235959 --- 1 F050 0
Clock (Read/Write Setting)
41A2 SR Date Format 0 to 4294967295 --- 1 F051 0
41A4 SR Time Format 0 to 4294967295 --- 1 F052 0
41A6 IRIG-B Signal Type 0 to 2 --- 1 F114 0 (None)
41A7 Clock Events Enable / Disable 0 to 1 --- 1 F102 0 (Disabled)
41A8 Time Zone Offset from UTC –24 to 24 hours 0.5 F002 0
41A9 Daylight Savings Time (DST) Function 0 to 1 --- 1 F102 0 (Disabled)
41AA Daylight Savings Time (DST) Start Month 0 to 11 --- 1 F237 0 (January)
41AB Daylight Savings Time (DST) Start Day 0 to 6 --- 1 F238 0 (Sunday)
41AC Daylight Savings Time (DST) Start Day Instance 0 to 4 --- 1 F239 0 (First)
41AD Daylight Savings Time (DST) Start Hour 0 to 23 --- 1 F001 2
41AE Daylight Savings Time (DST) Stop Month 0 to 11 --- 1 F237 0 (January)
41AF Daylight Savings Time (DST) Stop Day 0 to 6 --- 1 F238 0 (Sunday)
41B0 Daylight Savings Time (DST) Stop Day Instance 0 to 4 --- 1 F239 0 (First)
41B1 Daylight Savings Time (DST) Stop Hour 0 to 23 --- 1 F001 2
Fault Report Commands (Read/Write Command)
41B2 Fault Reports Clear Data Command 0 to 1 --- 1 F126 0 (No)
Oscillography (Read/Write Setting)
41C0 Oscillography Number of Records 3 to 64 --- 1 F001 15
41C1 Oscillography Trigger Mode 0 to 1 --- 1 F118 0 (Auto.
Overwrite)
41C2 Oscillography Trigger Position 0 to 100 % 1 F001 50
41C3 Oscillography Trigger Source 0 to 4294967295 --- 1 F300 0
41C5 Oscillography AC Input Waveforms 0 to 4 --- 1 F183 2 (16 samples/
cycle)
41D0 Oscillography Analog Channel n (16 items) 0 to 65535 --- 1 F600 0
4200 Oscillography Digital Channel n (63 items) 0 to 4294967295 --- 1 F300 0
Trip and Alarm LEDs (Read/Write Setting)
42B0 Trip LED Input FlexLogic Operand 0 to 4294967295 --- 1 F300 0
42B2 Alarm LED Input FlexLogic Operand 0 to 4294967295 --- 1 F300 0
User Programmable LEDs (Read/Write Setting) (48 modules)
42C0 FlexLogic Operand to Activate LED 0 to 4294967295 --- 1 F300 0
42C2 User LED type (latched or self-resetting) 0 to 1 --- 1 F127 1 (Self-Reset)
42C3 ...Repeated for User-Programmable LED 2
42C6 ...Repeated for User-Programmable LED 3
42C9 ...Repeated for User-Programmable LED 4
42CC ...Repeated for User-Programmable LED 5
42CF ...Repeated for User-Programmable LED 6
42D2 ...Repeated for User-Programmable LED 7
B 4445
4446
User Programmable Secondary Ethernet Fail Function
User Programmable Battery Fail Function
0 to 1
0 to 1
---
---
1
1
F102
F102
0 (Disabled)
1 (Enabled)
4447 User Programmable SNTP Fail Function 0 to 1 --- 1 F102 1 (Enabled)
4448 User Programmable IRIG-B Fail Function 0 to 1 --- 1 F102 1 (Enabled)
444A Process Bus Failure Operand 0 to 4294967295 --- 1 F300 0
444C PTP Fail Function 0 to 1 --- 1 F102 1 (Enabled)
444D User Programmable Third Ethernet Fail Function 0 to 1 --- 1 F102 0 (Disabled)
444E User Programmable SFP Fail Function 0 to 1 --- 1 F102 0 (Disabled)
CT Settings (Read/Write Setting) (6 modules)
4480 Phase CT 1 Primary 1 to 65000 A 1 F001 1
4481 Phase CT 1 Secondary 0 to 1 --- 1 F123 0 (1 A)
4482 Ground CT 1 Primary 1 to 65000 A 1 F001 1
4483 Ground CT 1 Secondary 0 to 1 --- 1 F123 0 (1 A)
4484 ...Repeated for CT Bank 2
4488 ...Repeated for CT Bank 3
448C ...Repeated for CT Bank 4
4490 ...Repeated for CT Bank 5
4494 ...Repeated for CT Bank 6
VT Settings (Read/Write Setting) (3 modules)
4500 Phase VT 1 Connection 0 to 1 --- 1 F100 0 (Wye)
4501 Phase VT 1 Secondary 25 to 240 V 0.1 F001 664
4502 Phase VT 1 Ratio 1 to 24000 :1 1 F060 1
4504 Auxiliary VT 1 Connection 0 to 6 --- 1 F166 1 (Vag)
4505 Auxiliary VT 1 Secondary 25 to 240 V 0.1 F001 664
4506 Auxiliary VT 1 Ratio 1 to 24000 :1 1 F060 1
4508 ...Repeated for VT Bank 2
4510 ...Repeated for VT Bank 3
4518 ...Repeated for VT Bank 4
4520 ...Repeated for VT Bank 5
4528 ...Repeated for VT Bank 6
Source Settings (Read/Write Setting) (6 modules)
4580 Source 1 Name 0 to 1 --- --- F206 “SRC 1"
4583 Source 1 Phase CT 0 to 63 --- 1 F400 0
4584 Source 1 Ground CT 0 to 63 --- 1 F400 0
4585 Source 1 Phase VT 0 to 63 --- 1 F400 0
4586 Source 1 Auxiliary VT 0 to 63 --- 1 F400 0
4587 ...Repeated for Source 2
458E ...Repeated for Source 3
4595 ...Repeated for Source 4
459C ...Repeated for Source 5
45A3 ...Repeated for Source 6
Power System (Read/Write Setting)
4600 Nominal Frequency 25 to 60 Hz 1 F001 60
B
4D60 ...Repeated for User-Definable Display 12
4D80 ...Repeated for User-Definable Display 13
4DA0 ...Repeated for User-Definable Display 14
4DC0 ...Repeated for User-Definable Display 15
4DE0 ...Repeated for User-Definable Display 16
Field Unit Raw Data Actuals (Read Only) (8 modules)
4E00 Raw Field Data AC1 Mag 0 to 0.001 A 0.001 F003 0
4E02 Raw Field Data AC1 Angle 0 to 0.1 degree 0.1 F002 0
4E03 Raw Field Data AC2 Mag 0 to 0.001 A 0.001 F003 0
4E05 Raw Field Data AC2 Angle 0 to 0.1 degree 0.1 F002 0
4E06 Raw Field Data AC3 Mag 0 to 0.001 A 0.001 F003 0
4E08 Raw Field Data AC3 Angle 0 to 0.01 degree 0.1 F002 0
4E09 Raw Field Data AC4 Mag 0 to 0.001 A 0.001 F003 0
4E0B Raw Field Data AC4 Angle 0 to 0.01 degree 0.1 F002 0
4E0C Raw Field Data AC5 Mag 0 to 0.001 A/V 0.001 F003 0
4E0E Raw Field Data AC5 Angle 0 to 0.01 degree 0.1 F002 0
4E0F Raw Field Data AC6 Mag 0 to 0.001 A/V 0.001 F003 0
4E11 Raw Field Data AC6 Angle 0 to 0.01 degree 0.1 F002 0
4E12 Raw Field Data AC7 Mag 0 to 0.001 A/V 0.001 F003 0
4E14 Raw Field Data AC7 Angle 0 to 0.01 degree 0.1 F002 0
4E15 Raw Field Data AC8 Mag 0 to 0.001 A/V 0.001 F003 0
4E17 Raw Field Data AC8 Angle 0 to 0.01 degree 0.1 F002 0
4E18 Raw Field Data DC1 0 to 0.001 V 0.001 F002 0
4E19 Raw Field Data DC2 0 to 0.001 V 0.001 F002 0
4E1A Raw Field Data DC3 0 to 0.001 V 0.001 F002 0
4E1B Raw Field Data FCI States (2 items) 0 to 1 --- 1 F500 0
4E1D Raw Field Data SI States 0 to 1 --- 1 F500 0
4E1E Raw Field Data SI Test States 0 to 1 --- 1 F500 0
4E1F Raw Field Data Brick ADC Temperature 0 to 1 degree 1 F002 0
4E20 Raw Field Data Brick Transceiver Temperature 0 to 1 degree 1 F002 0
4E21 Raw Field Data Brick Transceiver Voltage 0 to 0.01 V 0.01 F001 0
4E22 Raw Field Data Brick Transceiver Current 0 to 1 mA 1 F001 0
4E23 Raw Field Data Brick Tx Power 0 to 0.01 dBm 0.1 F002 0
4E24 Raw Field Data Brick Rx Power 0 to 0.1 dBm 0.1 F002 0
4E25 Raw Field Data Brick Diagnostics (2 items) 0 to 65535 --- 1 F500 0
4E27 Raw Field Data Local Transceiver Temperature 0 to 1 degree 1 F002 0
4E28 Raw Field Data Local Transceiver Voltage 0 to 0.01 V 0.01 F001 0
4E29 Raw Field Data Local Transceiver Current 0 to 1 mA 1 F001 0
4E2A Raw Field Data Local Tx Power 0 to 0.1 dBm 0.1 F002 0
4E2B Raw Field Data Local Rx Power 0 to 0.1 dBm 0.1 F002 0
4E2C Repeated for module number 2
4E58 Repeated for module number 3
4E84 Repeated for module number 4
4E80 Repeated for module number 5
B
5818 ...Repeated for FlexLogic Timer 4
5820 ...Repeated for FlexLogic Timer 5
5828 ...Repeated for FlexLogic Timer 6
5830 ...Repeated for FlexLogic Timer 7
5838 ...Repeated for FlexLogic Timer 8
5840 ...Repeated for FlexLogic Timer 9
5848 ...Repeated for FlexLogic Timer 10
5850 ...Repeated for FlexLogic Timer 11
5858 ...Repeated for FlexLogic Timer 12
5860 ...Repeated for FlexLogic Timer 13
5868 ...Repeated for FlexLogic Timer 14
5870 ...Repeated for FlexLogic Timer 15
5878 ...Repeated for FlexLogic Timer 16
5880 ...Repeated for FlexLogic Timer 17
5888 ...Repeated for FlexLogic Timer 18
5890 ...Repeated for FlexLogic Timer 19
5898 ...Repeated for FlexLogic Timer 20
58A0 ...Repeated for FlexLogic Timer 21
58A8 ...Repeated for FlexLogic Timer 22
58B0 ...Repeated for FlexLogic Timer 23
58B8 ...Repeated for FlexLogic Timer 24
58C0 ...Repeated for FlexLogic Timer 25
58C8 ...Repeated for FlexLogic Timer 26
58D0 ...Repeated for FlexLogic Timer 27
58D8 ...Repeated for FlexLogic Timer 28
58E0 ...Repeated for FlexLogic Timer 29
58E8 ...Repeated for FlexLogic Timer 30
58F0 ...Repeated for FlexLogic Timer 31
58F8 ...Repeated for FlexLogic Timer 32
Phase Time Overcurrent (Read/Write Grouped Setting) (6 modules)
5900 Phase Time Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
5901 Phase Time Overcurrent 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
5902 Phase Time Overcurrent 1 Input 0 to 1 --- 1 F122 0 (Phasor)
5903 Phase Time Overcurrent 1 Pickup 0 to 30 pu 0.001 F001 1000
5904 Phase Time Overcurrent 1 Curve 0 to 16 --- 1 F103 0 (IEEE Mod Inv)
5905 Phase Time Overcurrent 1 Multiplier 0 to 600 --- 0.01 F001 100
5906 Phase Time Overcurrent 1 Reset 0 to 1 --- 1 F104 0 (Instantaneous)
5907 Phase Time Overcurrent 1 Voltage Restraint 0 to 1 --- 1 F102 0 (Disabled)
5908 Phase TOC 1 Block For Each Phase (3 items) 0 to 4294967295 --- 1 F300 0
590F Phase Time Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
5910 Phase Time Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
5911 Reserved (3 items) 0 to 1 --- 1 F001 0
5914 ...Repeated for Phase Time Overcurrent 2
5928 ...Repeated for Phase Time Overcurrent 3
B
5D01 Ground Time Overcurrent 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
5D02 Ground Time Overcurrent 1 Input 0 to 1 --- 1 F122 0 (Phasor)
5D03 Ground Time Overcurrent 1 Pickup 0 to 30 pu 0.001 F001 1000
5D04 Ground Time Overcurrent 1 Curve 0 to 16 --- 1 F103 0 (IEEE Mod Inv)
5D05 Ground Time Overcurrent 1 Multiplier 0 to 600 --- 0.01 F001 100
5D06 Ground Time Overcurrent 1 Reset 0 to 1 --- 1 F104 0 (Instantaneous)
5D07 Ground Time Overcurrent 1 Block 0 to 4294967295 --- 1 F300 0
5D09 Ground Time Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
5D0A Ground Time Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
5D0B Reserved (6 items) 0 to 1 --- 1 F001 0
5D11 ...Repeated for Ground Time Overcurrent 2
5D22 ...Repeated for Ground Time Overcurrent 3
5D33 ...Repeated for Ground Time Overcurrent 4
5D44 ...Repeated for Ground Time Overcurrent 5
5D55 ...Repeated for Ground Time Overcurrent 6
Ground Instantaneous Overcurrent (Read/Write Grouped Setting) (12 modules)
5DA0 Ground Instantaneous Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
5DA1 Ground Instantaneous Overcurrent 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
5DA2 Ground Instantaneous Overcurrent 1 Pickup 0 to 30 pu 0.001 F001 1000
5DA3 Ground Instantaneous Overcurrent 1 Delay 0 to 600 s 0.01 F001 0
5DA4 Ground Instantaneous Overcurrent 1 Reset Delay 0 to 600 s 0.01 F001 0
5DA5 Ground Instantaneous Overcurrent 1 Block 0 to 4294967295 --- 1 F300 0
5DA7 Ground Instantaneous Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
5DA8 Ground Instantaneous Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
5DA9 Reserved (8 items) 0 to 1 --- 1 F001 0
5DB1 ...Repeated for Ground Instantaneous Overcurrent 2
5DC2 ...Repeated for Ground Instantaneous Overcurrent 3
5DD3 ...Repeated for Ground Instantaneous Overcurrent 4
5DE4 ...Repeated for Ground Instantaneous Overcurrent 5
5DF5 ...Repeated for Ground Instantaneous Overcurrent 6
5E06 ...Repeated for Ground Instantaneous Overcurrent 7
5E17 ...Repeated for Ground Instantaneous Overcurrent 8
5E28 ...Repeated for Ground Instantaneous Overcurrent 9
5E39 ...Repeated for Ground Instantaneous Overcurrent 10
5E4A ...Repeated for Ground Instantaneous Overcurrent 11
5E5B ...Repeated for Ground Instantaneous Overcurrent 12
Setting Groups (Read/Write Setting)
5F70 Setting Group for Modbus Comms (0 means group 1) 0 to 5 --- 1 F001 0
5F71 Setting Groups Block 0 to 4294967295 --- 1 F300 0
5F73 FlexLogic to Activate Groups 2 through 6 (5 items) 0 to 4294967295 --- 1 F300 0
5F7D Setting Group Function 0 to 1 --- 1 F102 0 (Disabled)
5F7E Setting Group Events 0 to 1 --- 1 F102 0 (Disabled)
Setting Groups (Read Only)
5F7F Current Setting Group 0 to 5 --- 1 F001 0
B
65C9 Power Swing Detect Middle Limit Angle 40 to 140 degrees 1 F001 90
65CA Power Swing Detect Inner Limit Angle 40 to 140 degrees 1 F001 60
65CB Power Swing Detect Delay 1 Pickup 0 to 65.535 s 0.001 F001 30
65CC Power Swing Detect Delay 1 Reset 0 to 65.535 s 0.001 F001 50
65CD Power Swing Detect Delay 2 Pickup 0 to 65.535 s 0.001 F001 17
65CE Power Swing Detect Delay 3 Pickup 0 to 65.535 s 0.001 F001 9
65CF Power Swing Detect Delay 4 Pickup 0 to 65.535 s 0.001 F001 17
65D0 Power Swing Detect Seal In Delay 0 to 65.535 s 0.001 F001 400
65D1 Power Swing Detect Trip Mode 0 to 1 --- 1 F514 0 (Delayed)
65D2 Power Swing Detect Block 0 to 4294967295 --- 1 F300 0
65D4 Power Swing Detect Target 0 to 2 --- 1 F109 0 (Self-reset)
65D5 Power Swing Detect Event 0 to 1 --- 1 F102 0 (Disabled)
65D6 Power Swing Detect Shape 0 to 1 --- 1 F085 0 (Mho Shape)
65D7 Power Swing Detect Quad Forward Middle 0.1 to 500 ohms 0.01 F001 6000
65D8 Power Swing Detect Quad Forward Outer 0.1 to 500 ohms 0.01 F001 7000
65D9 Power Swing Detect Quad Reverse Middle 0.1 to 500 ohms 0.01 F001 6000
65DA Power Swing Detect Quad Reverse Outer 0.1 to 500 ohms 0.01 F001 7000
65DB Power Swing Detect Outer Right Blinder 0.1 to 500 ohms 0.01 F001 10000
65DC Power Swing Detect Outer Left Blinder 0.1 to 500 ohms 0.01 F001 10000
65DD Power Swing Detect Middle Right Blinder 0.1 to 500 ohms 0.01 F001 10000
65DE Power Swing Detect Middle Left Blinder 0.1 to 500 ohms 0.01 F001 10000
65DF Power Swing Detect Inner Right Blinder 0.1 to 500 ohms 0.01 F001 10000
65E0 Power Swing Detect Inner Left Blinder 0.1 to 500 ohms 0.01 F001 10000
Sensitive Directional Power (Read/Write Grouped Setting) (2 modules)
6680 Sensitive Directional Power 1 Function 0 to 1 --- 1 F102 0 (Disabled)
6681 Sensitive Directional Power 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
6682 Sensitive Directional Power 1 RCA 0 to 359 degrees 1 F001 0
6683 Sensitive Directional Power 1 Calibration 0 to 0.95 degrees 0.05 F001 0
6684 Sensitive Directional Power 1 STG1 SMIN -1.2 to 1.2 pu 0.001 F002 100
6685 Sensitive Directional Power 1 STG1 Delay 0 to 600 s 0.01 F001 50
6686 Sensitive Directional Power 1 STG2 SMIN -1.2 to 1.2 pu 0.001 F002 100
6687 Sensitive Directional Power 1 STG2 Delay 0 to 600 s 0.01 F001 2000
6688 Sensitive Directional Power 1 Block 0 to 4294967295 --- --- F300 0
668A Sensitive Directional Power 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
668B Sensitive Directional Power 1 Events 0 to 1 --- 1 F102 0 (Disabled)
668C Reserved (5 items) 0 to 65535 --- 1 F001 0
6691 ...Repeated for Sensitive Directional Power 2
Load Encroachment (Read/Write Grouped Setting)
66C0 Load Encroachment Function 0 to 1 --- 1 F102 0 (Disabled)
66C1 Load Encroachment Source 0 to 5 --- 1 F167 0 (SRC 1)
66C2 Load Encroachment Minimum Voltage 0 to 3 pu 0.001 F001 250
66C3 Load Encroachment Reach 0.02 to 250 ohms 0.01 F001 100
66C4 Load Encroachment Angle 5 to 50 degrees 1 F001 30
66C5 Load Encroachment Pickup Delay 0 to 65.535 s 0.001 F001 0
B
67DD DUTT 1P Block 0 to 4294967295 --- 1 F300 0
67DF Reserved (6 items) 0 to 1 --- 1 F001 0
Pilot PUTT (1P) (Read/Write Setting)
67EA PUTT 1P Scheme Function 0 to 1 --- 1 F102 0 (Disabled)
67EB PUTT 1P Rx Pickup Delay 0 to 65.535 s 0.001 F001 0
67EC PUTT 1P Seal In Delay 0 to 65.535 s 0.001 F001 0
67ED PUTT 1P Number of Communication Bits 0 to 2 --- 1 F198 0 (1)
67EE PUTT 1P Rx1 0 to 4294967295 --- 1 F300 0
67F0 PUTT 1P Rx2 0 to 4294967295 --- 1 F300 0
67F2 PUTT 1P Rx3 0 to 4294967295 --- 1 F300 0
67F4 PUTT 1P Rx4 0 to 4294967295 --- 1 F300 0
67F6 PUTT 1P Target 0 to 2 --- 1 F109 0 (Self-reset)
67F7 PUTT 1P Event 0 to 1 --- 1 F102 0 (Disabled)
67F8 PUTT 1P Block 0 to 4294967295 --- 1 F300 0
67FA Reserved (5 items) 0 to 1 --- 1 F001 0
Pilot Hybrid POTT (1P) (Read/Write Setting)
6820 Hybrid POTT 1P Scheme Function 0 to 1 --- 1 F102 0 (Disabled)
6821 Hybrid POTT 1P Permissive Echo 0 to 2 --- 1 F199 0 (Disabled)
6822 Hybrid POTT 1P Rx Pickup Delay 0 to 65.535 s 0.001 F001 0
6823 Hybrid POTT 1P Trans Block Pickup Delay 0 to 65.535 s 0.001 F001 20
6824 Hybrid POTT 1P Trans Block Reset Delay 0 to 65.535 s 0.001 F001 90
6825 Hybrid POTT 1P Echo Duration 0 to 65.535 s 0.001 F001 100
6826 Hybrid POTT 1P Echo Lockout 0 to 65.535 s 0.001 F001 250
6827 Hybrid POTT 1P Seal In Delay 0 to 65.535 --- 0.001 F001 0
6828 Hybrid POTT 1P Ground Directional Overcurrent Forward 0 to 4294967295 --- 1 F300 0
682A Hybrid POTT 1P Gnd Directional Overcurrent Reverse 0 to 4294967295 --- 1 F300 0
682C Hybrid POTT 1P Number of Communication Bits 0 to 2 --- 1 F198 0 (1)
682D Hybrid POTT 1P Rx1 0 to 4294967295 --- 1 F300 0
682F Hybrid POTT 1P Rx2 0 to 4294967295 --- 1 F300 0
6831 Hybrid POTT 1P Rx3 0 to 4294967295 --- 1 F300 0
6833 Hybrid POTT 1P Rx4 0 to 4294967295 --- 1 F300 0
6835 Hybrid POTT 1P Target 0 to 2 --- 1 F109 0 (Self-reset)
6836 Hybrid POTT 1P Event 0 to 1 --- 1 F102 0 (Disabled)
68737 Hybrid POTT 1P Echo Condition 0 to 4294967295 --- 1 F300 0
6839 Hybrid POTT 1P Weak Infeed 0 to 2 --- 1 F199 1 (Enabled)
683A Hybrid POTT 1P Weak Infeed Condition 0 to 4294967295 --- 1 F300 0
683C Hybrid POTT 1P Block 0 to 4294967295 --- 1 F300 0
683E Reserved (3 items) 0 to 1 --- 1 F001 0
Pilot Blocking (1P) (Read/Write Setting)
6845 Blocking Scheme 1P Function 0 to 1 --- 1 F102 0 (Disabled)
6846 Block 1P Rx Coord Pickup Delay 0 to 65.535 s 0.001 F001 10
6847 Block 1P Transient Block Pickup Delay 0 to 65.535 s 0.001 F001 30
6848 Block 1P Transient Block Reset Delay 0 to 65.535 s 0.001 F001 90
6849 Blocking Scheme 1P Seal In Delay 0 to 65.535 s 0.001 F001 0
B
68AC Directional Comparison Unblocking Echo Duration 0 to 65.535 s 0.001 F001 100
68AD Directional Comparison Unblocking Echo Lockout 0 to 65.535 s 0.001 F001 250
68AE DCUB Line End Open Pickup Delay 0 to 65.535 s 0.001 F001 50
68AF DCUB Loss-of-Guard Pickup Delay 0 to 65.535 s 0.001 F001 8
68B0 DCUB Guard Healthy Reset Delay 0 to 65.535 s 0.001 F001 15
68B1 DCUB Loss-of-Guard Trip Window 0 to 65.535 s 0.001 F001 150
68B2 Directional Comparison Unblocking Seal-In Delay 0 to 65.535 s 0.001 F001 10
68B3 Directional Comparison Unblocking Communication Bits 0 to 2 --- 1 F198 0 (1 bit)
68B4 Directional Comparison Unblocking Rx1 0 to 4294967295 --- 1 F300 0
68B6 Directional Comparison Unblocking LOG1 0 to 4294967295 --- 1 F300 0
68B8 Directional Comparison Unblocking Rx2 0 to 4294967295 --- 1 F300 0
68BA Directional Comparison Unblocking LOG2 0 to 4294967295 --- 1 F300 0
68BC Directional Comparison Unblocking Rx3 0 to 4294967295 --- 1 F300 0
68BE Directional Comparison Unblocking LOG3 0 to 4294967295 --- 1 F300 0
68C0 Directional Comparison Unblocking Rx4 0 to 4294967295 --- 1 F300 0
68C2 Directional Comparison Unblocking LOG4 0 to 4294967295 --- 1 F300 0
68C4 Directional Comparison Unblocking Target 0 to 2 --- 1 F109 0 (Self-Reset)
68C5 Directional Comparison Unblocking Event 0 to 1 -- 1 F102 0 (Disabled)
68C6 Reserved (6 items) 0 to 1 -- 1 F001 0
Phase Undervoltage (Read/Write Grouped Setting) (2 modules)
7000 Phase Undervoltage 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7001 Phase Undervoltage 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
7002 Phase Undervoltage 1 Pickup 0 to 3 pu 0.001 F001 1000
7003 Phase Undervoltage 1 Curve 0 to 1 --- 1 F111 0 (Definite Time)
7004 Phase Undervoltage 1 Delay 0 to 600 s 0.01 F001 100
7005 Phase Undervoltage 1 Minimum Voltage 0 to 3 pu 0.001 F001 100
7006 Phase Undervoltage 1 Block 0 to 4294967295 --- 1 F300 0
7008 Phase Undervoltage 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7009 Phase Undervoltage 1 Events 0 to 1 --- 1 F102 0 (Disabled)
700A Phase Undervoltage 1 Measurement Mode 0 to 1 --- 1 F186 0 (Phase to
Ground)
700A Reserved (6 items) 0 to 1 --- 1 F001 0
7013 ...Repeated for Phase Undervoltage 2
7015 ...Repeated for Phase Undervoltage 2
7017 ...Repeated for Phase Undervoltage 2
701B ...Repeated for Phase Undervoltage 2
701C ...Repeated for Phase Undervoltage 2
7022 ...Repeated for Phase Undervoltage 3
7025 ...Repeated for Phase Undervoltage 3
7027 ...Repeated for Phase Undervoltage 3
7028 ...Repeated for Phase Undervoltage 3
702A ...Repeated for Phase Undervoltage 3
Phase Overvoltage (Read/Write Grouped Setting)
7040 Phase Overvoltage 1 Function 0 to 1 --- 1 F102 0 (Disabled)
B
70F4 ...Repeated for Phase Distance Zone 5
7101 ...Repeated for Phase Distance Zone 5
7104 ...Repeated for Phase Distance Zone 5
7106 ...Repeated for Phase Distance Zone 5
7107 ...Repeated for Phase Distance Zone 5
710A ...Repeated for Phase Distance Zone 5
Ground Distance (Read/Write Grouped Setting) (5 modules)
7130 Ground Distance Zone 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7131 Ground Distance Zone 1 Current Supervision 0.05 to 30 pu 0.001 F001 200
7132 Ground Distance Zone 1 Reach 0.02 to 500 ohms 0.01 F001 200
7133 Ground Distance Zone 1 Direction 0 to 2 --- 1 F154 0 (Forward)
7134 Ground Distance Zone 1 Comparator Limit 30 to 90 degrees 1 F001 90
7135 Ground Distance Zone 1 Delay 0 to 65.535 s 0.001 F001 0
7136 Ground Distance Zone 1 Block 0 to 4294967295 --- 1 F300 0
7138 Ground Distance Zone 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7139 Ground Distance Zone 1 Events 0 to 1 --- 1 F102 0 (Disabled)
713A Ground Distance Zone 1 Shape 0 to 1 --- 1 F120 0 (Mho)
713B Ground Distance Zone 1 Z0 Z1 Magnitude 0 to 10 --- 0.01 F001 270
713C Ground Distance Zone 1 Z0 Z1 Angle -90 to 90 degrees 1 F002 0
713D Ground Distance Zone 1 RCA 30 to 90 degrees 1 F001 85
713E Ground Distance Zone 1 DIR RCA 30 to 90 degrees 1 F001 85
713F Ground Distance Zone 1 DIR Comp Limit 30 to 90 degrees 1 F001 90
7140 Ground Distance Zone 1 Quad Right Blinder 0.02 to 500 ohms 0.01 F001 1000
7141 Ground Distance Zone 1 Quad Right Blinder RCA 60 to 90 degrees 1 F001 85
7142 Ground Distance Zone 1 Quad Left Blinder 0.02 to 500 ohms 0.01 F001 1000
7143 Ground Distance Zone 1 Quad Left Blinder RCA 60 to 90 degrees 1 F001 85
7144 Ground Distance Zone 1 Z0M Z1 Magnitude 0 to 7 --- 0.01 F001 0
7145 Ground Distance Zone 1 Z0M Z1 Angle -90 to 90 degrees 1 F002 0
7146 Ground Distance Zone 1 Voltage Level 0 to 5 pu 0.001 F001 0
7147 Ground Distance Zone 1 Non-Homogeneous Angle -40 to 40 degrees 0.1 F002 0
7148 Ground Distance Zone 1 POL Current 0 to 1 --- 1 F521 0 (Zero-seq)
7149 Ground Distance Zone 1 Reverse Reach 0.02 to 500 ohms 0.01 F001 200
717A Ground Distance Zone 1 Reverse Reach RCA 30 to 90 degrees 1 F001 85
714B Reserved (7 items) 0 to 65535 --- 1 F001 0
7152 ...Repeated for Ground Distance Zone 2
7164 ...Repeated for Ground Distance Zone 2
7166 ...Repeated for Ground Distance Zone 2
7168 ...Repeated for Ground Distance Zone 2
7169 ...Repeated for Ground Distance Zone 2
716C ...Repeated for Ground Distance Zone 2
7174 ...Repeated for Ground Distance Zone 3
7196 ...Repeated for Ground Distance Zone 4
71B8 ...Repeated for Ground Distance Zone 5
B
74A0 Disconnect switch 1 function 0 to 1 --- 1 F102 0 (Disabled)
74A1 Disconnect switch 1 name --- --- --- F206 “SW 1"
74A4 Disconnect switch 1 mode 0 to 1 --- 1 F157 0 (3-Pole)
74A5 Disconnect switch 1 open 0 to 4294967295 --- 1 F300 0
74A7 Disconnect switch 1 block open 0 to 4294967295 --- 1 F300 0
74A9 Disconnect switch 1 close 0 to 4294967295 --- 1 F300 0
74AB Disconnect switch 1 block close 0 to 4294967295 --- 1 F300 0
74AD Disconnect switch 1 phase A / three-pole closed 0 to 4294967295 --- 1 F300 0
74AF Disconnect switch 1 phase A / three-pole opened 0 to 4294967295 --- 1 F300 0
74B1 Disconnect switch 1 phase B closed 0 to 4294967295 --- 1 F300 0
74B3 Disconnect switch 1 phase B opened 0 to 4294967295 --- 1 F300 0
74B5 Disconnect switch 1 phase C closed 0 to 4294967295 --- 1 F300 0
74B7 Disconnect switch 1 phase C opened 0 to 4294967295 --- 1 F300 0
74B9 Disconnect switch 1 operate time 0 to 65.535 s 0.001 F001 70
74BA Disconnect switch 1 alarm delay 0 to 65.535 s 0.001 F003 0
74BC Disconnect switch 1 events 0 to 1 --- 1 F102 0 (Disabled)
74BD Reserved (2 items) --- --- --- --- ---
74BF ...Repeated for module number 2
Thermal Overload Protection (Read/Write Settings) (2 modules)
7788 Thermal Protection 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7789 Thermal Protection 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
778A Thermal Protection 1 Base Current 0.2 to 3 pu 0.01 F001 80
778B Thermal Protection 1 K Factor 1 to 1.2 --- 0.05 F001 110
778C Thermal Protection 1 Trip Time Constant 0 to 1000 min. 1 F001 45
778D Thermal Protection 1 Reset Time Constant 0 to 1000 min. 1 F001 45
778E Thermal Protection 1 Minimum Reset Time 0 to 1000 min. 1 F001 20
778F Thermal Protection 1 Reset 0 to 4294967295 --- 1 F300 0
7791 Thermal Protection 1 Block 0 to 4294967295 --- 1 F300 0
7793 Thermal Protection 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7794 Thermal Protection 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7795 Reserved (2 items) --- --- --- F001 0
7797 Repeated for Thermal Protection 2
Broken conductor detection (Read/Write Settings) (6 modules)
77AA Broken Conductor 1 Function 0 to 1 --- 1 F102 0 (Disabled)
77AB Broken Conductor 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
77AC Broken Conductor 1 I2/I1 Ratio 20 to 100 % 0.1 F001 200
77AD Broken Conductor 1 I1 Minimum 0.05 to 1 pu 0.01 F001 10
77AE Broken Conductor 1 I1 Maximum 0.05 to 5 pu 0.01 F001 150
77AF Broken Conductor 1 Pickup Delay 0 to 65.535 s 0.001 F001 20000
77B0 Broken Conductor 1 Block 0 to 4294967295 --- 1 F300 0
77B2 Broken Conductor 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
77B3 Broken Conductor 1 Events 0 to 1 --- 1 F102 0 (Disabled)
77B4 Reserved (2 items) --- --- --- F001 0
77B6 ...Repeated for Broken Conductor 2
B
791C PMU Vb Calibration Magnitude 95 to 105 % 0.1 F002 1000
791D PMU Vc Calibration Angle -5 to 5 ° 0.05 F002 0
791E PMU Vc Calibration Magnitude 95 to 105 % 0.1 F002 1000
791F PMU Vx Calibration Angle -5 to 5 ° 0.05 F002 0
7920 PMU Vx Calibration Magnitude 95 to 105 % 0.1 F002 1000
7921 PMU Ia Calibration Angle -5 to 5 ° 0.05 F002 0
7922 PMU Ia Calibration Magnitude 95 to 105 % 0.1 F002 1000
7923 PMU Ib Calibration Angle -5 to 5 ° 0.05 F002 0
7924 PMU Ib Calibration Magnitude 95 to 105 % 0.1 F002 1000
7925 PMU Ic Calibration Angle -5 to 5 ° 0.05 F002 0
7926 PMU Ic Calibration Magnitude 95 to 105 % 0.1 F002 1000
7927 PMU Ig Calibration Angle -5 to 5 ° 0.05 F002 0
7928 PMU Ig Calibration Magnitude 95 to 105 % 0.1 F002 1000
7929 PMU Sequence Voltage Shift Angle -180 to 180 ° 30 F002 0
792A PMU Sequence Current Shift Angle -180 to 180 ° 30 F002 0
Phasor Measurement Unit Triggering (Read/Write Setting) (4 modules)
7970 PMU 1 User Trigger 0 to 4294967295 --- 1 F300 0
Phasor Measurement Unit Current Trigger (Read/Write Setting) (4 modules)
7980 PMU 1 Current Trigger Function 0 to 1 --- 1 F102 0 (Disabled)
7981 PMU 1 Current Trigger Pickup 0.1 to 30 pu 0.001 F001 1800
7982 PMU 1 Current Trigger Pickup Time 0 to 600 s 0.01 F001 10
7983 PMU 1 Current Trigger Dropout Time 0 to 600 s 0.01 F001 100
7984 PMU 1 Current Trigger Block (3 items) 0 to 4294967295 --- 1 F300 0
798A PMU 1 Current Trigger Target 0 to 2 --- 1 F109 0 (Self-reset)
798B PMU 1 Current Trigger Events 0 to 1 --- 1 F102 0 (Disabled)
Phasor Measurement Unit df/dt Trigger (Read/Write Setting)
79B0 PMU 1 df/dt Trigger Function 0 to 1 --- 1 F102 0 (Disabled)
79B1 PMU 1 df/dt Trigger Raise 0.1 to 15 Hz/s 0.01 F001 25
79B2 PMU 1 df/dt Trigger Fall 0.1 to 15 Hz/s 0.01 F001 25
79B3 PMU 1 df/dt Trigger Pickup Time 0 to 600 s 0.01 F001 10
79B4 PMU 1 df/dt Trigger Dropout Time 0 to 600 s 0.01 F001 100
79B5 PMU 1 df/dt Trigger Block (3 items) 0 to 4294967295 --- 1 F300 0
79BB PMU 1 df/dt Trigger Target 0 to 2 --- 1 F109 0 (Self-reset)
79BC PMU 1 df/dt Trigger Events 0 to 1 --- 1 F102 0 (Disabled)
Underfrequency (Read/Write Setting) (6 modules)
7A80 Underfreqency Function 0 to 1 --- 1 F102 0 (Disabled)
7A81 Underfrequency Block 0 to 4294967295 --- 1 F300 0
7A83 Min Current 0.1 to 1.25 pu 0.01 F001 10
7A84 Underfrequency Pickup 20 to 65 Hz 0.01 F001 5950
7A85 Pickup Delay 0 to 65.535 s 0.001 F001 2000
7A86 Reset Delay 0 to 65.535 s 0.001 F001 2000
7A87 Underfrequency Source 0 to 5 --- 1 F167 0 (SRC 1)
7A88 Underfrequency Events 0 to 1 --- 1 F102 0 (Disabled)
7A89 Underfrequency Target 0 to 2 --- 1 F109 0 (Self-reset)
B
Auxiliary Overvoltage (Read/Write Grouped Setting) (3 modules)
7FA0 Auxiliary Overvoltage 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7FA1 Auxiliary Overvoltage 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
7FA2 Auxiliary Overvoltage 1 Pickup 0 to 3 pu 0.001 F001 300
7FA3 Auxiliary Overvoltage 1 Pickup Delay 0 to 600 s 0.01 F001 100
7FA4 Auxiliary Overvoltage 1 Reset Delay 0 to 600 s 0.01 F001 100
7FA5 Auxiliary Overvoltage 1 Block 0 to 4294967295 --- 1 F300 0
7FA7 Auxiliary Overvoltage 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7FA8 Auxiliary Overvoltage 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7FA9 Reserved (8 items) 0 to 65535 --- 1 F001 0
7FB1 ...Repeated for Auxiliary Overvoltage 2
7FC2 ...Repeated for Auxiliary Overvoltage 3
Frequency (Read Only)
8000 Tracking Frequency --- Hz --- F001 0
Temp Monitor Actual Values (Read Only Non-Volatile)
81C0 Reserved Register T1 -55 to 125 C 1 F002 -55
81C1 Reserved Register T2 -55 to 125 C 1 F002 125
81C2 Reserved Register T3 -2147483647 to --- 1 F004 0
2147483647
81C4 Reserved Register T4 0 to 4294967295 --- 1 F003 0
81C6 Reserved Register T5 0 to 4294967295 --- 1 F003 0
81C8 Reserved Register T6 0 to 4294967295 --- 1 F003 0
81CA Reserved Register T7 0 to 4294967295 --- 1 F003 0
81CC Reserved Register T8 0 to 4294967295 --- 1 F003 0
Breaker Failure (Read/Write Grouped Setting) (4 or 6 modules)
8600 Breaker Failure 1 Function 0 to 1 --- 1 F102 0 (Disabled)
8601 Breaker Failure 1 Mode 0 to 1 --- 1 F157 0 (3-Pole)
8602 Breaker Failure 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
8603 Breaker Failure 1 Amp Supervision 0 to 1 --- 1 F126 1 (Yes)
8604 Breaker Failure 1 Use Seal-In 0 to 1 --- 1 F126 1 (Yes)
8605 Breaker Failure 1 Three Pole Initiate 0 to 4294967295 --- 1 F300 0
8607 Breaker Failure 1 Block 0 to 4294967295 --- 1 F300 0
8609 Breaker Failure 1 Phase Amp Supv Pickup 0.001 to 30 pu 0.001 F001 1050
860A Breaker Failure 1 Neutral Amp Supv Pickup 0.001 to 30 pu 0.001 F001 1050
860B Breaker Failure 1 Use Timer 1 0 to 1 --- 1 F126 1 (Yes)
860C Breaker Failure 1 Timer 1 Pickup 0 to 65.535 s 0.001 F001 0
860D Breaker Failure 1 Use Timer 2 0 to 1 --- 1 F126 1 (Yes)
860E Breaker Failure 1 Timer 2 Pickup 0 to 65.535 s 0.001 F001 0
860F Breaker Failure 1 Use Timer 3 0 to 1 --- 1 F126 1 (Yes)
8610 Breaker Failure 1 Timer 3 Pickup 0 to 65.535 s 0.001 F001 0
8611 Breaker Failure 1 Breaker Status 1 Phase A/3P 0 to 4294967295 --- 1 F300 0
8613 Breaker Failure 1 Breaker Status 2 Phase A/3P 0 to 4294967295 --- 1 F300 0
8615 Breaker Failure 1 Breaker Test On 0 to 4294967295 --- 1 F300 0
8617 Breaker Failure 1 Phase Amp Hiset Pickup 0.001 to 30 pu 0.001 F001 1050
B
8CD6 ...Repeated for Digital Element 34
8CEC ...Repeated for Digital Element 35
8D02 ...Repeated for Digital Element 36
8D18 ...Repeated for Digital Element 37
8D2E ...Repeated for Digital Element 38
8D44 ...Repeated for Digital Element 39
8D5A ...Repeated for Digital Element 40
8D70 ...Repeated for Digital Element 41
8D86 ...Repeated for Digital Element 42
8D9C ...Repeated for Digital Element 43
8DB2 ...Repeated for Digital Element 44
8DC8 ...Repeated for Digital Element 45
8DDE ...Repeated for Digital Element 46
8DF4 ...Repeated for Digital Element 47
8E0A ...Repeated for Digital Element 48
Trip Bus (Read/Write Setting) (6 modules)
8E00 Trip Bus 1 Function 0 to 1 --- 1 F102 0 (Disabled)
8ED1 Trip Bus 1 Block 0 to 4294967295 --- --- F300 0
8ED3 Trip Bus 1 Pickup Delay 0 to 600 s 0.01 F001 0
8ED4 Trip Bus 1 Reset Delay 0 to 600 s 0.01 F001 0
8ED5 Trip Bus 1 Input (16 items) 0 to 4294967295 --- 1 F300 0
8EF5 Trip Bus 1 Latching 0 to 1 --- 1 F102 0 (Disabled)
8EF6 Trip Bus 1 Reset 0 to 65535 --- 1 F300 0
8EF8 Trip Bus 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
8EF9 Trip Bus 1 Events 0 to 1 --- 1 F102 0 (Disabled)
8EFA Reserved (8 items) --- --- --- F001 0
8F02 ...Repeated for Trip Bus 2
8F34 ...Repeated for Trip Bus 3
8F66 ...Repeated for Trip Bus 4
8F98 ...Repeated for Trip Bus 5
8FCA ...Repeated for Trip Bus 6
FlexElement (Read/Write Setting) (16 modules)
9000 FlexElement 1 Function 0 to 1 --- 1 F102 0 (Disabled)
9001 FlexElement 1 Name --- --- --- F206 “FxE 1”
9004 FlexElement 1 InputP 0 to 65535 --- 1 F600 0
9005 FlexElement 1 InputM 0 to 65535 --- 1 F600 0
9006 FlexElement 1 Compare 0 to 1 --- 1 F516 0 (LEVEL)
9007 FlexElement 1 Input 0 to 1 --- 1 F515 0 (SIGNED)
9008 FlexElement 1 Direction 0 to 1 --- 1 F517 0 (OVER)
9009 FlexElement 1 Hysteresis 0.1 to 50 % 0.1 F001 30
900A FlexElement 1 Pickup -90 to 90 pu 0.001 F004 1000
900C FlexElement 1 DeltaT Units 0 to 2 --- 1 F518 0 (Milliseconds)
900D FlexElement 1 DeltaT 20 to 86400 --- 1 F003 20
900F FlexElement 1 Pickup Delay 0 to 65.535 s 0.001 F001 0
B
93D2 ...Repeated for dcmA Output 20
93D8 ...Repeated for dcmA Output 21
93DE ...Repeated for dcmA Output 22
93E4 ...Repeated for dcmA Output 23
93EA ...Repeated for dcmA Output 24
Direct Input/Output Names (Read/Write Setting) (96 modules)
9400 Direct Input 1 Name 0 to 96 --- 1 F205 “Dir Ip 1”
9406 Direct Output 1 Name 1 to 96 --- 1 F205 “Dir Out 1”
940C ...Repeated for Direct Input/Output 2
9418 ...Repeated for Direct Input/Output 3
9424 ...Repeated for Direct Input/Output 4
9430 ...Repeated for Direct Input/Output 5
943C ...Repeated for Direct Input/Output 6
9448 ...Repeated for Direct Input/Output 7
9454 ...Repeated for Direct Input/Output 8
9460 ...Repeated for Direct Input/Output 9
946C ...Repeated for Direct Input/Output 10
9478 ...Repeated for Direct Input/Output 11
9484 ...Repeated for Direct Input/Output 12
9490 ...Repeated for Direct Input/Output 13
949C ...Repeated for Direct Input/Output 14
94A8 ...Repeated for Direct Input/Output 15
94B4 ...Repeated for Direct Input/Output 16
94C0 ...Repeated for Direct Input/Output 17
94CC ...Repeated for Direct Input/Output 18
94D8 ...Repeated for Direct Input/Output 19
94E4 ...Repeated for Direct Input/Output 20
94F0 ...Repeated for Direct Input/Output 21
94FC ...Repeated for Direct Input/Output 22
9508 ...Repeated for Direct Input/Output 23
9514 ...Repeated for Direct Input/Output 24
9520 ...Repeated for Direct Input/Output 25
952C ...Repeated for Direct Input/Output 26
9538 ...Repeated for Direct Input/Output 27
9544 ...Repeated for Direct Input/Output 28
9550 ...Repeated for Direct Input/Output 29
955C ...Repeated for Direct Input/Output 30
9568 ...Repeated for Direct Input/Output 31
9574 ...Repeated for Direct Input/Output 32
IEC 61850 Received Integers (Read/Write Setting) (16 modules)
98A0 IEC61850 GOOSE UInteger 1 default value 0 to 429496295 --- 1 F003 1000
98A2 IEC61850 GOOSE UInteger input 1 mode 0 to 1 --- 1 F491 0 (Default
Value)
98A3 ...Repeated for IEC61850 GOOSE UInteger 2
B
A09C VT Fuse Failure Neutral Wire Open 3rd Harmonic Pickup 0 to 3 pu 0.001 F001 100
A09D ...Repeated for module number 2
A0A0 ...Repeated for module number 3
A0A3 ...Repeated for module number 4
A0A6 ...Repeated for module number 5
A0A9 ...Repeated for module number 6
A0AC VTFF x V0 3rd harmonic 0 to 999999.999 V 0.001 F060 0
Selector switch actual values (read only)
A210 Selector switch 1 position 1 to 7 --- 1 F001 0
A211 Selector switch 2 position 1 to 7 --- 1 F001 1
Selector switch settings (read/write, 2 modules)
A280 Selector 1 Function 0 to 1 --- 1 F102 0 (Disabled)
A281 Selector 1 Range 1 to 7 --- 1 F001 7
A282 Selector 1 Timeout 3 to 60 s 0.1 F001 50
A283 Selector 1 Step Up 0 to 4294967295 --- 1 F300 0
A285 Selector 1 Step Mode 0 to 1 --- 1 F083 0 (Time-out)
A286 Selector 1 Acknowledge 0 to 4294967295 --- 1 F300 0
A288 Selector 1 Bit0 0 to 4294967295 --- 1 F300 0
A28A Selector 1 Bit1 0 to 4294967295 --- 1 F300 0
A28C Selector 1 Bit2 0 to 4294967295 --- 1 F300 0
A28E Selector 1 Bit Mode 0 to 1 --- 1 F083 0 (Time-out)
A28F Selector 1 Bit Acknowledge 0 to 4294967295 --- 1 F300 0
A291 Selector 1 Power Up Mode 0 to 2 --- 1 F084 0 (Restore)
A292 Selector 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
A293 Selector 1 Events 0 to 1 --- 1 F102 0 (Disabled)
A294 Reserved (10 items) --- --- 1 F001 0
A29E ...Repeated for Selector 2
Digital Counter (Read/Write Setting) (8 modules)
A300 Digital Counter 1 Function 0 to 1 --- 1 F102 0 (Disabled)
A301 Digital Counter 1 Name --- --- --- F205 “Counter 1"
A307 Digital Counter 1 Units --- --- --- F206 (none)
A30A Digital Counter 1 Block 0 to 4294967295 --- 1 F300 0
A30C Digital Counter 1 Up 0 to 4294967295 --- 1 F300 0
A30E Digital Counter 1 Down 0 to 4294967295 --- 1 F300 0
A311 Digital Counter 1 Preset –2147483647 to --- 1 F004 0
2147483647
A313 Digital Counter 1 Compare –2147483647 to --- 1 F004 0
2147483647
A315 Digital Counter 1 Reset 0 to 4294967295 --- 1 F300 0
A317 Digital Counter 1 Freeze/Reset 0 to 4294967295 --- 1 F300 0
A319 Digital Counter 1 Freeze/Count 0 to 4294967295 --- 1 F300 0
A31B Digital Counter 1 Set To Preset 0 to 4294967295 --- 1 F300 0
A31D Reserved (11 items) --- --- --- F001 0
A328 ...Repeated for Digital Counter 2
A350 ...Repeated for Digital Counter 3
B
A839 POTT1 1P Ground Directional Overcurrent Forward 0 to 4294967295 --- 1 F300 0
A83B POTT1 1P Number of Communication Bits 0 to 2 --- 1 F198 0 (1)
A83C POTT1 1P Rx1 0 to 4294967295 --- 1 F300 0
A83E POTT1 1P Rx2 0 to 4294967295 --- 1 F300 0
A840 POTT1 1P Rx3 0 to 4294967295 --- 1 F300 0
A842 POTT1 1P Rx4 0 to 4294967295 --- 1 F300 0
A844 POTT1 1P Target 0 to 2 --- 1 F109 0 (Self-reset)
A845 POTT1 1P Event 0 to 1 --- 1 F102 0 (Disabled)
A846 POTT1 1P Echo Condition 0 to 4294967295 --- 1 F300 0
A848 POTT1 1P Scheme Block 0 to 4294967295 --- 1 F300 0
A84A POTT1 1P OC Fwd2 0 to 4294967295 --- 1 F300 0
A84C POTT1 1P OC Fwd2 0 to 4294967295 --- 1 F300 0
A84E Reserved (22 items) 0 to 1 --- 1 F001 0
Frequency Rate of Change (Read/Write Setting) (4 modules)
A900 Frequency Rate of Change 1 Function 0 to 1 --- 1 F102 0 (Disabled)
A901 Frequency Rate of Change 1 OC Supervision 0 to 30 pu 0.001 F001 200
A902 Frequency Rate of Change 1 Min 20 to 80 Hz 0.01 F001 4500
A903 Frequency Rate of Change 1 Max 20 to 80 Hz 0.01 F001 6500
A904 Frequency Rate of Change 1 Pickup Delay 0 to 65.535 s 0.001 F001 0
A905 Frequency Rate of Change 1 Reset Delay 0 to 65.535 s 0.001 F001 0
A906 Frequency Rate of Change 1 Block 0 to 4294967295 --- 1 F300 0
A908 Frequency Rate of Change 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
A909 Frequency Rate of Change 1 Events 0 to 1 --- 1 F102 0 (Disabled)
A90A Frequency Rate of Change 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
A90B Frequency Rate of Change 1 Trend 0 to 2 --- 1 F224 0 (Increasing)
A90C Frequency Rate of Change 1 Pickup 0.1 to 15 Hz/s 0.01 F001 50
A90D Frequency Rate of Change 1 OV Supervision 0.1 to 3 pu 0.001 F001 700
A90E Frequency Rate of Change 1 Reserved (3 items) 0 to 1 --- 1 F001 0
A911 ...Repeated for Frequency Rate of Change 2
A922 ...Repeated for Frequency Rate of Change 3
A933 ...Repeated for Frequency Rate of Change 4
IEC 61850 received analog settings (read/write) (32 modules)
AA00 IEC 61850 GOOSE analog 1 default value –1000000 to 1000000 --- 0.001 F060 1000
AA02 IEC 61850 GOOSE analog input 1 mode 0 to 1 --- 1 F491 0 (Default Value)
AA03 IEC 61850 GOOSE analog input 1 units --- --- --- F207 (none)
AA05 IEC 61850 GOOSE analog input 1 per-unit base 0 to 999999999.999 --- 0.001 F060 1
AA07 ...Repeated for IEC 61850 GOOSE analog input 2
AA0E ...Repeated for IEC 61850 GOOSE analog input 3
AA15 ...Repeated for IEC 61850 GOOSE analog input 4
AA1C ...Repeated for IEC 61850 GOOSE analog input 5
AA23 ...Repeated for IEC 61850 GOOSE analog input 6
AA2A ...Repeated for IEC 61850 GOOSE analog input 7
AA31 ...Repeated for IEC 61850 GOOSE analog input 8
AA38 ...Repeated for IEC 61850 GOOSE analog input 9
B
B232 ...Repeated for Received Analog 18
B234 ...Repeated for Received Analog 19
B236 ...Repeated for Received Analog 20
B238 ...Repeated for Received Analog 21
B23A ...Repeated for Received Analog 22
B23C ...Repeated for Received Analog 23
B23E ...Repeated for Received Analog 24
B240 ...Repeated for Received Analog 25
B242 ...Repeated for Received Analog 26
B244 ...Repeated for Received Analog 27
B246 ...Repeated for Received Analog 28
B248 ...Repeated for Received Analog 29
B24A ...Repeated for Received Analog 30
B24C ...Repeated for Received Analog 31
B24E ...Repeated for Received Analog 32
IEC 61850 Configurable Report Settings (Read/Write Setting)
B290 IEC 61850 configurable reports dataset items (64 items) 0 to 848 --- 1 F615 0 (None)
Wattmetric ground fault settings (read/write grouped, 2 modules)
B300 Wattmetric ground fault 1 function 0 to 1 --- 1 F102 0 (Disabled)
B301 Wattmetric ground fault 1 source 0 to 5 --- 1 F167 0 (SRC 1)
B302 Wattmetric ground fault 1 voltage 0 to 1 --- 1 F234 0 (Calculated VN)
B303 Wattmetric ground fault 1 overvoltage pickup 0.02 to 3.00 pu 0.01 F001 20
B304 Wattmetric ground fault 1 current 0 to 1 --- 1 F235 (Calculated IN)
B305 Wattmetric ground fault 1 overcurrent pickup 0.002 to 30.000 pu 0.001 F001 60
B306 Wattmetric ground fault 1 overcurrent pickup delay 0 to 600 s 0.01 F001 20
B307 Wattmetric ground fault 1 power pickup 0.001 to 1.2 pu 0.001 F001 100
B308 Wattmetric ground fault 1 ECA 0 to 360 ° Lag 1 F001 0
B309 Wattmetric ground fault 1 power pickup delay 0 to 600 s 0.01 F001 20
B30A Wattmetric ground fault 1 curve 0 to 5 --- 1 F236 0 (Definite Time)
B30B Wattmetric ground fault 1 multiplier 0.01 to 2 s 0.01 F001 100
B30C Wattmetric ground fault 1 block 0 to 65535 --- 1 F300 0
B30E Wattmetric ground fault 1 target 0 to 2 --- 1 F109 0 (Self-reset)
B30F Wattmetric ground fault 1 events 0 to 1 --- 1 F102 0 (Disabled)
B310 Wattmetric ground fault 1 reference power 0.001 to 1.2 pu 0.001 F001 500
B311 Wattmetric ground fault x Reserved 0 to 1 --- 1 F001 0
B312 ...Repeated for wattmetric ground fault 2
B324 ...Repeated for wattmetric ground fault 3
B336 ...Repeated for wattmetric ground fault 4
B348 ...Repeated for wattmetric ground fault 5
Wattmetric ground fault actual values (read only) (5 modules)
B360 Wattmetric ground fault 1 operating power 0 to 999999.999 W 0.001 F060 0
B362 ...Repeated for wattmetric ground fault 2
B364 ...Repeated for wattmetric ground fault 3
B366 ...Repeated for wattmetric ground fault 4
B
BB88 ...Repeated for Contact Input 18
BB90 ...Repeated for Contact Input 19
BB98 ...Repeated for Contact Input 20
BBA0 ...Repeated for Contact Input 21
BBA8 ...Repeated for Contact Input 22
BBB0 ...Repeated for Contact Input 23
BBB8 ...Repeated for Contact Input 24
BBC0 ...Repeated for Contact Input 25
BBC8 ...Repeated for Contact Input 26
BBD0 ...Repeated for Contact Input 27
BBD8 ...Repeated for Contact Input 28
BBE0 ...Repeated for Contact Input 29
BBE8 ...Repeated for Contact Input 30
BBF0 ...Repeated for Contact Input 31
BBF8 ...Repeated for Contact Input 32
BC00 ...Repeated for Contact Input 33
BC08 ...Repeated for Contact Input 34
BC10 ...Repeated for Contact Input 35
BC18 ...Repeated for Contact Input 36
BC20 ...Repeated for Contact Input 37
BC28 ...Repeated for Contact Input 38
BC30 ...Repeated for Contact Input 39
BC38 ...Repeated for Contact Input 40
BC40 ...Repeated for Contact Input 41
BC48 ...Repeated for Contact Input 42
BC50 ...Repeated for Contact Input 43
BC58 ...Repeated for Contact Input 44
BC60 ...Repeated for Contact Input 45
BC68 ...Repeated for Contact Input 46
BC70 ...Repeated for Contact Input 47
BC78 ...Repeated for Contact Input 48
BC80 ...Repeated for Contact Input 49
BC88 ...Repeated for Contact Input 50
BC90 ...Repeated for Contact Input 51
BC98 ...Repeated for Contact Input 52
BCA0 ...Repeated for Contact Input 53
BCA8 ...Repeated for Contact Input 54
BCB0 ...Repeated for Contact Input 55
BCB8 ...Repeated for Contact Input 56
BCC0 ...Repeated for Contact Input 57
BCC8 ...Repeated for Contact Input 58
BCD0 ...Repeated for Contact Input 59
BCD8 ...Repeated for Contact Input 60
BCE0 ...Repeated for Contact Input 61
B
BF38 ...Repeated for Virtual Input 23
BF44 ...Repeated for Virtual Input 24
BF50 ...Repeated for Virtual Input 25
BF5C ...Repeated for Virtual Input 26
BF68 ...Repeated for Virtual Input 27
BF74 ...Repeated for Virtual Input 28
BF80 ...Repeated for Virtual Input 29
BF8C ...Repeated for Virtual Input 30
BF98 ...Repeated for Virtual Input 31
BFA4 ...Repeated for Virtual Input 32
BFB0 ...Repeated for Virtual Input 33
BFBC ...Repeated for Virtual Input 34
BFC8 ...Repeated for Virtual Input 35
BFD4 ...Repeated for Virtual Input 36
BFE0 ...Repeated for Virtual Input 37
BFEC ...Repeated for Virtual Input 38
BFF8 ...Repeated for Virtual Input 39
C004 ...Repeated for Virtual Input 40
C010 ...Repeated for Virtual Input 41
C01C ...Repeated for Virtual Input 42
C028 ...Repeated for Virtual Input 43
C034 ...Repeated for Virtual Input 44
C040 ...Repeated for Virtual Input 45
C04C ...Repeated for Virtual Input 46
C058 ...Repeated for Virtual Input 47
C064 ...Repeated for Virtual Input 48
C070 ...Repeated for Virtual Input 49
C07C ...Repeated for Virtual Input 50
C088 ...Repeated for Virtual Input 51
C094 ...Repeated for Virtual Input 52
C0A0 ...Repeated for Virtual Input 53
C0AC ...Repeated for Virtual Input 54
C0B8 ...Repeated for Virtual Input 55
C0C4 ...Repeated for Virtual Input 56
C0D0 ...Repeated for Virtual Input 57
C0DC ...Repeated for Virtual Input 58
C0E8 ...Repeated for Virtual Input 59
C0F4 ...Repeated for Virtual Input 60
C100 ...Repeated for Virtual Input 61
C10C ...Repeated for Virtual Input 62
C118 ...Repeated for Virtual Input 63
C124 ...Repeated for Virtual Input 64
Virtual Outputs (Read/Write Setting) (96 modules)
C130 Virtual Output 1 Name --- --- --- F205 “Virt Op 1 “
B
C328 ...Repeated for Virtual Output 64
C330 ...Repeated for Virtual Output 65
C338 ...Repeated for Virtual Output 66
C340 ...Repeated for Virtual Output 67
C348 ...Repeated for Virtual Output 68
C350 ...Repeated for Virtual Output 69
C358 ...Repeated for Virtual Output 70
C360 ...Repeated for Virtual Output 71
C368 ...Repeated for Virtual Output 72
C370 ...Repeated for Virtual Output 73
C378 ...Repeated for Virtual Output 74
C380 ...Repeated for Virtual Output 75
C388 ...Repeated for Virtual Output 76
C390 ...Repeated for Virtual Output 77
C398 ...Repeated for Virtual Output 78
C3A0 ...Repeated for Virtual Output 79
C3A8 ...Repeated for Virtual Output 80
C3B0 ...Repeated for Virtual Output 81
C3B8 ...Repeated for Virtual Output 82
C3C0 ...Repeated for Virtual Output 83
C3C8 ...Repeated for Virtual Output 84
C3D0 ...Repeated for Virtual Output 85
C3D8 ...Repeated for Virtual Output 86
C3E0 ...Repeated for Virtual Output 87
C3E8 ...Repeated for Virtual Output 88
C3F0 ...Repeated for Virtual Output 89
C3F8 ...Repeated for Virtual Output 90
C400 ...Repeated for Virtual Output 91
C408 ...Repeated for Virtual Output 92
C410 ...Repeated for Virtual Output 93
C418 ...Repeated for Virtual Output 94
C420 ...Repeated for Virtual Output 95
C428 ...Repeated for Virtual Output 96
Mandatory (Read/Write Setting)
C430 Test Mode Function 0 to 2 --- 1 F245 0 (Disabled)
C431 Force VFD and LED 0 to 1 --- 1 F126 0 (No)
C432 Test Mode Initiate 0 to 4294967295 --- 1 F300 1
Clear commands (read/write)
C434 Clear All Relay Records Command 0 to 1 --- 1 F126 0 (No)
Mandatory (Read Only)
C435 DSP Advanced Diagnostics Active 0 to 1 -- 1 F126 0 (No)
C436 Synchrophasor Feature Active 0 to 1 -- 1 F126 0 (No)
Mandatory (Read/Write Command)
C434 Relay Reboot Command 0 to 1 --- 1 F126 0 (No)
B
C881 Direct I/O Channel 1 Ring Configuration Function 0 to 1 --- 1 F126 0 (No)
C882 Platform Direct I/O Data Rate 64 to 128 kbps 64 F001 64
C883 Direct I/O Channel 2 Ring Configuration Function 0 to 1 --- 1 F126 0 (No)
C884 Platform Direct I/O Crossover Function 0 to 1 --- 1 F102 0 (Disabled)
Direct input/output commands (Read/Write Command)
C888 Direct input/output clear counters command 0 to 1 --- 1 F126 0 (No)
Direct inputs (Read/Write Setting) (96 modules)
C890 Direct Input 1 Device Number 0 to 16 --- 1 F001 0
C891 Direct Input 1 Number 0 to 96 --- 1 F001 0
C892 Direct Input 1 Default State 0 to 3 --- 1 F086 0 (Off)
C893 Direct Input 1 Events 0 to 1 --- 1 F102 0 (Disabled)
C894 ...Repeated for Direct Input 2
C898 ...Repeated for Direct Input 3
C89C ...Repeated for Direct Input 4
C8A0 ...Repeated for Direct Input 5
C8A4 ...Repeated for Direct Input 6
C8A8 ...Repeated for Direct Input 7
C8AC ...Repeated for Direct Input 8
C8B0 ...Repeated for Direct Input 9
C8B4 ...Repeated for Direct Input 10
C8B8 ...Repeated for Direct Input 11
C8BC ...Repeated for Direct Input 12
C8C0 ...Repeated for Direct Input 13
C8C4 ...Repeated for Direct Input 14
C8C8 ...Repeated for Direct Input 15
C8CC ...Repeated for Direct Input 16
C8D0 ...Repeated for Direct Input 17
C8D4 ...Repeated for Direct Input 18
C8D8 ...Repeated for Direct Input 19
C8DC ...Repeated for Direct Input 20
C8E0 ...Repeated for Direct Input 21
C8E4 ...Repeated for Direct Input 22
C8E8 ...Repeated for Direct Input 23
C8EC ...Repeated for Direct Input 24
C8F0 ...Repeated for Direct Input 25
C8F4 ...Repeated for Direct Input 26
C8F8 ...Repeated for Direct Input 27
C8FC ...Repeated for Direct Input 28
C900 ...Repeated for Direct Input 29
C904 ...Repeated for Direct Input 30
C908 ...Repeated for Direct Input 31
C90C ...Repeated for Direct Input 32
Direct Input/Output Alarms (Read/Write Setting)
CAD0 Direct Input/Output Channel 1 CRC Alarm Function 0 to 1 --- 1 F102 0 (Disabled)
B
CFBE ...Repeated for Remote Input 4
CFC8 ...Repeated for Remote Input 5
CFD2 ...Repeated for Remote Input 6
CFDC ...Repeated for Remote Input 7
CFE6 ...Repeated for Remote Input 8
CFF0 ...Repeated for Remote Input 9
CFFA ...Repeated for Remote Input 10
D004 ...Repeated for Remote Input 11
D00E ...Repeated for Remote Input 12
D018 ...Repeated for Remote Input 13
D022 ...Repeated for Remote Input 14
D02C ...Repeated for Remote Input 15
D036 ...Repeated for Remote Input 16
D040 ...Repeated for Remote Input 17
D04A ...Repeated for Remote Input 18
D054 ...Repeated for Remote Input 19
D05E ...Repeated for Remote Input 20
D068 ...Repeated for Remote Input 21
D072 ...Repeated for Remote Input 22
D07C ...Repeated for Remote Input 23
D086 ...Repeated for Remote Input 24
D090 ...Repeated for Remote Input 25
D09A ...Repeated for Remote Input 26
D0A4 ...Repeated for Remote Input 27
D0AE ...Repeated for Remote Input 28
D0B8 ...Repeated for Remote Input 29
D0C2 ...Repeated for Remote Input 30
D0CC ...Repeated for Remote Input 31
D0D6 ...Repeated for Remote Input 32
D0E0 ...Repeated for Remote Input 33
D0EA ...Repeated for Remote Input 34
D0F4 ...Repeated for Remote Input 35
D0FE ...Repeated for Remote Input 36
D108 ...Repeated for Remote Input 37
D112 ...Repeated for Remote Input 38
D11C ...Repeated for Remote Input 39
D126 ...Repeated for Remote Input 40
D130 ...Repeated for Remote Input 41
D13A ...Repeated for Remote Input 42
D144 ...Repeated for Remote Input 43
D14E ...Repeated for Remote Input 44
D158 ...Repeated for Remote Input 45
D162 ...Repeated for Remote Input 46
D16C ...Repeated for Remote Input 47
B
D2C4 ...Repeated for Remote Output 10
D2C8 ...Repeated for Remote Output 11
D2CC ...Repeated for Remote Output 12
D2D0 ...Repeated for Remote Output 13
D2D4 ...Repeated for Remote Output 14
D2D8 ...Repeated for Remote Output 15
D2DC ...Repeated for Remote Output 16
D2E0 ...Repeated for Remote Output 17
D2E4 ...Repeated for Remote Output 18
D2E8 ...Repeated for Remote Output 19
D2EC ...Repeated for Remote Output 20
D2F0 ...Repeated for Remote Output 21
D2F4 ...Repeated for Remote Output 22
D2F8 ...Repeated for Remote Output 23
D2FC ...Repeated for Remote Output 24
D300 ...Repeated for Remote Output 25
D304 ...Repeated for Remote Output 26
D308 ...Repeated for Remote Output 27
D30C ...Repeated for Remote Output 28
D310 ...Repeated for Remote Output 29
D314 ...Repeated for Remote Output 30
D318 ...Repeated for Remote Output 31
D31C ...Repeated for Remote Output 32
IEC 61850 GGIO2 Control Configuration (Read/Write Setting) (64 modules)
D320 IEC 61850 GGIO2.CF.SPCSO1.ctlModel Value 0 to 2 --- 1 F001 2
D321 IEC 61850 GGIO2.CF.SPCSO2.ctlModel Value 0 to 2 --- 1 F001 2
D322 IEC 61850 GGIO2.CF.SPCSO3.ctlModel Value 0 to 2 --- 1 F001 2
D323 IEC 61850 GGIO2.CF.SPCSO4.ctlModel Value 0 to 2 --- 1 F001 2
D324 IEC 61850 GGIO2.CF.SPCSO5.ctlModel Value 0 to 2 --- 1 F001 2
D325 IEC 61850 GGIO2.CF.SPCSO6.ctlModel Value 0 to 2 --- 1 F001 2
D326 IEC 61850 GGIO2.CF.SPCSO7.ctlModel Value 0 to 2 --- 1 F001 2
D327 IEC 61850 GGIO2.CF.SPCSO8.ctlModel Value 0 to 2 --- 1 F001 2
D328 IEC 61850 GGIO2.CF.SPCSO9.ctlModel Value 0 to 2 --- 1 F001 2
D329 IEC 61850 GGIO2.CF.SPCSO10.ctlModel Value 0 to 2 --- 1 F001 2
D32A IEC 61850 GGIO2.CF.SPCSO11.ctlModel Value 0 to 2 --- 1 F001 2
D32B IEC 61850 GGIO2.CF.SPCSO12.ctlModel Value 0 to 2 --- 1 F001 2
D32C IEC 61850 GGIO2.CF.SPCSO13.ctlModel Value 0 to 2 --- 1 F001 2
D32D IEC 61850 GGIO2.CF.SPCSO14.ctlModel Value 0 to 2 --- 1 F001 2
D32E IEC 61850 GGIO2.CF.SPCSO15.ctlModel Value 0 to 2 --- 1 F001 2
D32F IEC 61850 GGIO2.CF.SPCSO16.ctlModel Value 0 to 2 --- 1 F001 2
D330 IEC 61850 GGIO2.CF.SPCSO17.ctlModel Value 0 to 2 --- 1 F001 2
D331 IEC 61850 GGIO2.CF.SPCSO18.ctlModel Value 0 to 2 --- 1 F001 2
D332 IEC 61850 GGIO2.CF.SPCSO19.ctlModel Value 0 to 2 --- 1 F001 2
D333 IEC 61850 GGIO2.CF.SPCSO20.ctlModel Value 0 to 2 --- 1 F001 2
B
D3C8 ...Repeated for Remote Device 19
D3CC ...Repeated for Remote Device 20
D3D0 ...Repeated for Remote Device 21
D3D4 ...Repeated for Remote Device 22
D3D8 ...Repeated for Remote Device 23
D3DC ...Repeated for Remote Device 24
D3E0 ...Repeated for Remote Device 25
D3E4 ...Repeated for Remote Device 26
D3E8 ...Repeated for Remote Device 27
D3EC ...Repeated for Remote Device 28
D3F0 ...Repeated for Remote Device 29
D3F4 ...Repeated for Remote Device 30
D3F8 ...Repeated for Remote Device 31
D3FC ...Repeated for Remote Device 32
Phasor Measurement Unit Basic Configuration (Read/Write Setting) (4 modules)
D400 PMU x Function 0 to 1 --- 1 F102 0 (Disabled)
D401 PMU x LDInst --- --- 1 F214 "PMUx \040"
D422 PMU x IDcode 1 to 65534 --- 1 F001 1
D423 PMU x STN --- --- --- F203 "GE-UR-PMU"
D42B PMU x Source 0 to 5 --- 1 F167 0 (SRC 1)
D42C PMU x Class 0 to 2 --- 1 F549 1 (Class M)
D42D PMU x Format 0 to 1 --- 1 F547 0 (Integer)
D42E PMU x Style 0 to 1 --- 1 F546 0 (Polar)
D42F PMU x Rate 0 to 13 --- 1 F544 4 (10/sec)
D430 PMU x PHS-x (14 items) 0 to 14 --- 1 F543 1 (Va)
D43E PMU x PHS-x Name (14 items) --- --- --- F203 "GE-UR-PMU-
PHS 1 "
D4AE PMU x A-CH-x (16 items) 0 to 65535 --- 1 F600 0
D4BE PMU x A-CH-x (16 items) --- --- --- F203 "AnalogChannel 1
"
D53E PMU x D-CH-x (16 items) 0 to 4294967295 --- 1 F300 0
D55E PMU x D-CH-x Name (16 items) --- --- --- F203 "Dig Channel 1 "
D5DE PMU x D-CH-x Normal State (16 items) 0 to 1 --- 1 F108 0 (Off)
D5EE PMU x Reserved (16 items) 0 to 1 --- 1 F001 0
Contact Outputs (Read/Write Setting) (64 modules)
DC90 Contact Output 1 Name --- --- --- F205 “Cont Op 1"
DC96 Contact Output 1 Operation 0 to 4294967295 --- 1 F300 0
DC98 Contact Output 1 Seal In 0 to 4294967295 --- 1 F300 0
DC9A Latching Output 1 Reset 0 to 4294967295 --- 1 F300 0
DC9C Contact Output 1 Events 0 to 1 --- 1 F102 1 (Enabled)
DC9D Latching Output 1 Type 0 to 1 --- 1 F090 0 (Operate-
dominant)
DC9E Reserved --- --- --- F001 0
DC9F ...Repeated for Contact Output 2
DCAE ...Repeated for Contact Output 3
B
E057 Reserved 1 (4 items) 0 to 65535 --- 1 F001 0
E05B dcmA Inputs 1 Units --- --- --- F206 “mA”
E05E dcmA Inputs 1 Range 0 to 6 --- 1 F173 6 (4 to 20 mA)
E05F dcmA Inputs 1 Minimum Value -9999.999 to 9999.999 --- 0.001 F004 4000
E061 dcmA Inputs 1 Maximum Value -9999.999 to 9999.999 --- 0.001 F004 20000
E063 ...Repeated for dcmA Inputs 2
E076 ...Repeated for dcmA Inputs 3
E089 ...Repeated for dcmA Inputs 4
E09C ...Repeated for dcmA Inputs 5
E0AF ...Repeated for dcmA Inputs 6
E0C2 ...Repeated for dcmA Inputs 7
E0D5 ...Repeated for dcmA Inputs 8
E0E8 ...Repeated for dcmA Inputs 9
E0FB ...Repeated for dcmA Inputs 10
E10E ...Repeated for dcmA Inputs 11
E121 ...Repeated for dcmA Inputs 12
E134 ...Repeated for dcmA Inputs 13
E147 ...Repeated for dcmA Inputs 14
E15A ...Repeated for dcmA Inputs 15
E16D ...Repeated for dcmA Inputs 16
E180 ...Repeated for dcmA Inputs 17
E193 ...Repeated for dcmA Inputs 18
E1A6 ...Repeated for dcmA Inputs 19
E1B9 ...Repeated for dcmA Inputs 20
E1CC ...Repeated for dcmA Inputs 21
E1DF ...Repeated for dcmA Inputs 22
E1F2 ...Repeated for dcmA Inputs 23
E205 ...Repeated for dcmA Inputs 24
Phasor Measurement Unit Aggregator (Read/Write Setting) (4 modules)
E220 PMU Aggregator 1 Name --- --- 1 F209 "MSVID 1 "
E241 Aggregator 1 IDcode 1 to 65534 --- 1 F001 1
E242 Aggregator 1 Protocol 0 to 2 --- 1 F001 0 (NONE)
E243 Aggregator 1 TCP Port 0 to 65534 --- 1 F001 4712
E244 Aggregator 1 UDP Port 0 to 65534 --- 1 F001 4713
E245 PMU Aggregator 1 90-5 UDP Port 0 to 65534 --- 1 F001 102
E246 PMU Aggregator 1 PDC Network Control 0 to 1 --- 1 F102 0 (Disabled)
E247 Aggregator 1 Include PMU1 0 to 1 --- 1 F126 0 (No)
E248 Aggregator 1 Include PMU2 0 to 1 --- 1 F126 0 (No)
E249 Aggregator 1 Include PMU3 0 to 1 --- 1 F126 0 (No)
E24A Aggregator 1 Include PMU4 0 to 1 --- 1 F126 0 (No)
E24B PMU Aggregator 1 ASDUS 1 to 4 --- 1 F001 1
E24C PMU Aggregator 1 Port 1 to 3 --- 1 F001 1
E24D PMU Aggregator 1 Reserved (3 items) 1 to 3 --- 1 F001 0
E250 ...Repeated for PMU Aggregator 2
F001 F040
UR_UINT16 UNSIGNED 16 BIT INTEGER UR_UINT48 48-BIT UNSIGNED INTEGER
F002 F050
UR_SINT16 SIGNED 16 BIT INTEGER UR_UINT32 TIME and DATE (UNSIGNED 32 BIT INTEGER)
Gives the current time in seconds elapsed since 00:00:00 January
1, 1970.
F003
UR_UINT32 UNSIGNED 32 BIT INTEGER (2 registers)
High order word is stored in the first register.
Low order word is stored in the second register.
F051
UR_UINT32 DATE in SR format (alternate format for F050) B
First 16 bits are Month/Day (MM/DD/xxxx). Month: 1=January,
2=February,...,12=December; Day: 1 to 31 in steps of 1
F004
Last 16 bits are Year (xx/xx/YYYY): 1970 to 2106 in steps of 1
UR_SINT32 SIGNED 32 BIT INTEGER (2 registers)
High order word is stored in the first register/
Low order word is stored in the second register. F052
UR_UINT32 TIME in SR format (alternate format for F050)
First 16 bits are Hours/Minutes (HH:MM:xx.xxx).
F005
Hours: 0=12am, 1=1am,...,12=12pm,...23=11pm;
UR_UINT8 UNSIGNED 8 BIT INTEGER
Minutes: 0 to 59 in steps of 1
Last 16 bits are Seconds (xx:xx:.SS.SSS): 0=00.000s,
F006 1=00.001,...,59999=59.999s)
UR_SINT8 SIGNED 8 BIT INTEGER
F060
F011 FLOATING_POINT IEEE FLOATING POINT (32 bits)
UR_UINT16 FLEXCURVE DATA (120 points)
A FlexCurve is an array of 120 consecutive data points (x, y) which
F070
are interpolated to generate a smooth curve. The y-axis is the user
HEX2 2 BYTES - 4 ASCII DIGITS
defined trip or operation time setting; the x-axis is the pickup ratio
and is pre-defined. Refer to format F119 for a listing of the pickup
ratios; the enumeration value for the pickup ratio indicates the off-
F071
set into the FlexCurve base address where the corresponding time HEX4 4 BYTES - 8 ASCII DIGITS
value is stored.
F072
F012
HEX6 6 BYTES - 12 ASCII DIGITS
DISPLAY_SCALE DISPLAY SCALING
(unsigned 16-bit integer)
MSB indicates the SI units as a power of ten. LSB indicates the F073
number of decimal points to display. HEX8 8 BYTES - 16 ASCII DIGITS
Example: Current values are stored as 32 bit numbers with three
decimal places and base units in Amps. If the retrieved value is
F074
12345.678 A and the display scale equals 0x0302 then the dis-
HEX20 20 BYTES - 40 ASCII DIGITS
played value on the unit is 12.35 kA.
F081
F013
ENUMERATION: AUTORECLOSE 1P/3P BKR FAIL OPTION
POWER_FACTOR (SIGNED 16 BIT INTEGER)
0 = Continue, 1 = Lockout
Positive values indicate lagging power factor; negative values
indicate leading.
F082 F103
ENUMERATION: AUTORECLOSE SINGLE-PHASE / ENUMERATION: CURVE SHAPES
THREE-PHASE BREAKER SEQUENCE
bitmask curve shape bitmask curve shape
0 = 1, 1 = 2, 2 = 1 & 2, 3 = 1 – 2, 4 = 2 – 1
0 IEEE Mod Inv 9 IAC Inverse
1 IEEE Very Inv 10 IAC Short Inv
F083 2 IEEE Ext Inv 11 I2t
ENUMERATION: SELECTOR MODES 3 IEC Curve A 12 Definite Time
0 = Time-Out, 1 = Acknowledge 4 IEC Curve B 13 FlexCurve A
5 IEC Curve C 14 FlexCurve B
6 IEC Short Inv 15 FlexCurve C
F084
7 IAC Ext Inv 16 FlexCurve D
ENUMERATION: SELECTOR POWER UP
B 0 = Restore, 1 = Synchronize, 2 = Sync/Restore
8 IAC Very Inv
F104
F085 ENUMERATION: RESET TYPE
ENUMERATION: POWER SWING SHAPE
0 = Instantaneous, 1 = Timed, 2 = Linear
0 = Mho Shape, 1 = Quad Shape
F105
F086 ENUMERATION: LOGIC INPUT
ENUMERATION: DIGITAL INPUT DEFAULT STATE
0 = Disabled, 1 = Input 1, 2 = Input 2
0 = Off, 1 = On, 2= Latest/Off, 3 = Latest/On
F106
F090 ENUMERATION: PHASE ROTATION
ENUMERATION: LATCHING OUTPUT TYPE
0 = ABC, 1 = ACB
0 = Operate-dominant, 1 = Reset-dominant
F108
F100 ENUMERATION: OFF/ON
ENUMERATION: VT CONNECTION TYPE
0 = Off, 1 = On
0 = Wye; 1 = Delta
F109
F101 ENUMERATION: CONTACT OUTPUT OPERATION
ENUMERATION: MESSAGE DISPLAY INTENSITY
0 = Self-reset, 1 = Latched, 2 = Disabled
0 = 25%, 1 = 50%, 2 = 75%, 3 = 100%
F110
F102 ENUMERATION: CONTACT OUTPUT LED CONTROL
ENUMERATION: DISABLED/ENABLED
0 = Trip, 1 = Alarm, 2 = None
0 = Disabled; 1 = Enabled
F111
ENUMERATION: UNDERVOLTAGE CURVE SHAPES
0 = Definite Time, 1 = Inverse Time
F112 F119
ENUMERATION: RS485 BAUD RATES ENUMERATION: FLEXCURVE PICKUP RATIOS
bitmask value bitmask value bitmask value mask value mask value mask value mask value
0 300 4 9600 8 115200 0 0.00 30 0.88 60 2.90 90 5.90
1 1200 5 19200 9 14400 1 0.05 31 0.90 61 3.00 91 6.00
2 2400 6 38400 10 28800 2 0.10 32 0.91 62 3.10 92 6.50
3 4800 7 57600 11 33600 3 0.15 33 0.92 63 3.20 93 7.00
4 0.20 34 0.93 64 3.30 94 7.50
5 0.25 35 0.94 65 3.40 95 8.00
F113
6 0.30 36 0.95 66 3.50 96 8.50
ENUMERATION: PARITY
7 0.35 37 0.96 67 3.60 97 9.00
0 = None, 1 = Odd, 2 = Even
8
9
0.40
0.45
38
39
0.97
0.98
68
69
3.70
3.80
98
99
9.50
10.00
B
F114 10 0.48 40 1.03 70 3.90 100 10.50
ENUMERATION: IRIG-B SIGNAL TYPE 11 0.50 41 1.05 71 4.00 101 11.00
F122
ENUMERATION: ELEMENT INPUT SIGNAL TYPE
0 = Phasor, 1 = RMS
F123
ENUMERATION: CT SECONDARY
0 = 1 A, 1 = 5 A
bitmask element
F124
225 SRC2 VT Fuse Failure
ENUMERATION: LIST OF ELEMENTS
226 SRC3 VT Fuse Failure
B 48
49
Neutral Time Overcurrent 1
Neutral Time Overcurrent 2
281
282
Breaker Failure 2
Breaker Failure 3
176 Ground Distance Zone 5 374 Directional Comparison Blocking Pilot Scheme
B 867
868
RTD Input 19
RTD Input 20
926
927
Disconnect switch 7
Disconnect switch 8
869 RTD Input 21 928 Disconnect switch 9
870 RTD Input 22 929 Disconnect switch 10
871 RTD Input 23 930 Disconnect switch 11
872 RTD Input 24 931 Disconnect switch 12
873 RTD Input 25 932 Disconnect switch 13
874 RTD Input 26 933 Disconnect switch 14
875 RTD Input 27 934 Disconnect switch 15
876 RTD Input 28 935 Disconnect switch 16
877 RTD Input 29 968 Breaker 1
878 RTD Input 30 969 Breaker 2
879 RTD Input 31 970 Breaker 3
880 RTD Input 32 971 Breaker 4
881 RTD Input 33 980 Breaker restrike 1
882 RTD Input 34 981 Breaker restrike 2
883 RTD Input 35 1012 Thermal overload protection 1
884 RTD Input 36 1013 Thermal overload protection 2
885 RTD Input 37 1014 Broken conductor detection 1
886 RTD Input 38 1015 Broken conductor detection 2
887 RTD Input 39 1020 Wattmetric 1
888 RTD Input 40 1021 Wattmetric 2
889 RTD Input 41
890 RTD Input 42
F125
891 RTD Input 43
ENUMERATION: ACCESS LEVEL
892 RTD Input 44
0 = Restricted; 1 = Command, 2 = Setting, 3 = Factory Service
893 RTD Input 45
894 RTD Input 46
895 RTD Input 47 F126
896 RTD Input 48 ENUMERATION: NO/YES CHOICE
900 User-Programmable Pushbutton 1 0 = No, 1 = Yes
901 User-Programmable Pushbutton 2
902 User-Programmable Pushbutton 3
F127
903 User-Programmable Pushbutton 4
ENUMERATION: LATCHED OR SELF-RESETTING
904 User-Programmable Pushbutton 5
905 User-Programmable Pushbutton 6 0 = Latched, 1 = Self-Reset
906 User-Programmable Pushbutton 7
907 User-Programmable Pushbutton 8 F128
908 User-Programmable Pushbutton 9 ENUMERATION: CONTACT INPUT THRESHOLD
909 User-Programmable Pushbutton 10
0 = 17 V DC, 1 = 33 V DC, 2 = 84 V DC, 3 = 166 V DC
910 User-Programmable Pushbutton 11
F129 F141
ENUMERATION: FLEXLOGIC TIMER TYPE ENUMERATION: SELF TEST ERRORS
0 = millisecond, 1 = second, 2 = minute
Bitmask Error
0 Any Self Tests
F130 1 IRIG-B Failure
ENUMERATION: SIMULATION MODE 2 Port 1 Offline
B 93
94
FGM Failure
FGM Failure
24
25
Ethernet Port 5 Offline
Ethernet Port 6 Offline
95 FGM Error 26 Test Mode Isolated
96 Maintenance Alert 27 Test Mode Forcible
97 PHY Monitor 28 Test Mode Disabled
98 Storage Media Alarm 29 Temperature Warning On
99 Wrong Transceiver 30 Temperature Warning Off
31 Unauthorized Access
32 System Integrity Recovery
F142
33 System Integrity Recovery 06
ENUMERATION: EVENT RECORDER ACCESS FILE TYPE
34 System Integrity Recovery 07
0 = All Record Data, 1 = Headers Only, 2 = Numeric Event Cause
F147
F143 ENUMERATION: LINE LENGTH UNITS
UR_UINT32: 32 BIT ERROR CODE (F141 specifies bit number)
0 = km, 1 = miles
A bit value of 0 = no error, 1 = error
F148
F144 ENUMERATION: FAULT TYPE
ENUMERATION: FORCED CONTACT INPUT STATE
bitmask fault type bitmask fault type
0 = Disabled, 1 = Open, 2 = Closed
0 NA 6 AC
1 AG 7 ABG
F146 2 BG 8 BCG
ENUMERATION: MISCELLANEOUS EVENT CAUSES 3 CG 9 ACG
4 AB 10 ABC
bitmask definition
5 BC 11 ABCG
0 Events Cleared
1 Oscillography Triggered
2 Date/time Changed
3 Default Settings Loaded
4 Test Mode Forcing On
5 Test Mode Forcing Off
6 Power On
7 Power Off
8 Relay In Service
9 Relay Out Of Service
10 Watchdog Reset
11 Oscillography Clear
12 Reboot Command
F151 F156
ENUMERATION: RTD SELECTION ENUMERATION: REMOTE INPUT BIT PAIRS
bitmask RTD# bitmask RTD# bitmask RTD#
bitmask value bitmask value
0 NONE 17 RTD 17 33 RTD 33
0 NONE 35 UserSt-3
1 RTD 1 18 RTD 18 34 RTD 34
1 DNA-1 36 UserSt-4
2 RTD 2 19 RTD 19 35 RTD 35
2 DNA-2 37 UserSt-5
3 RTD 3 20 RTD 20 36 RTD 36
3 DNA-3 38 UserSt-6
4 RTD 4 21 RTD 21 37 RTD 37
4 DNA-4 39 UserSt-7
5 RTD 5 22 RTD 22 38 RTD 38
5 DNA-5 40 UserSt-8
6 RTD 6 23 RTD 23 39 RTD 39
6 DNA-6 41 UserSt-9
7 RTD 7 24 RTD 24 40 RTD 40
7 DNA-7 42 UserSt-10
B
8 RTD 8 25 RTD 25 41 RTD 41
8 DNA-8 43 UserSt-11
9 RTD 9 26 RTD 26 42 RTD 42
9 DNA-9 44 UserSt-12
10 RTD 10 27 RTD 27 43 RTD 43
10 DNA-10 45 UserSt-13
11 RTD 11 28 RTD 28 44 RTD 44
11 DNA-11 46 UserSt-14
12 RTD 12 29 RTD 29 45 RTD 45
12 DNA-12 47 UserSt-15
13 RTD 13 30 RTD 30 46 RTD 46
13 DNA-13 48 UserSt-16
14 RTD 14 31 RTD 31 47 RTD 47
14 DNA-14 49 UserSt-17
15 RTD 15 32 RTD 32 48 RTD 48
15 DNA-15 50 UserSt-18
16 RTD 16
16 DNA-16 51 UserSt-19
17 DNA-17 52 UserSt-20
18 DNA-18 53 UserSt-21
F152
ENUMERATION: SETTING GROUP 19 DNA-19 54 UserSt-22
20 DNA-20 55 UserSt-23
0 = Active Group, 1 = Group 1, 2 = Group 2, 3 = Group 3
4 = Group 4, 5 = Group 5, 6 = Group 6 21 DNA-21 56 UserSt-24
22 DNA-22 57 UserSt-25
23 DNA-23 58 UserSt-26
F153 24 DNA-24 59 UserSt-27
ENUMERATION: DISTANCE TRANSFORMER CONNECTION
25 DNA-25 60 UserSt-28
bitmask type bitmask type bitmask type 26 DNA-26 61 UserSt-29
0 None 5 Dy9 10 Yd7 27 DNA-27 62 UserSt-30
1 Dy1 6 Dy11 11 Yd9 28 DNA-28 63 UserSt-31
2 Dy3 7 Yd1 12 Yd11 29 DNA-29 64 UserSt-32
3 Dy5 8 Yd3 30 DNA-30 65 Dataset Item 1
4 Dy7 9 Yd5 31 DNA-31 66 Dataset Item 2
32 DNA-32 67 Dataset Item 3
33 UserSt-1
F154
34 UserSt-2 96 Dataset Item 32
ENUMERATION: DISTANCE DIRECTION
0 = Forward, 1 = Reverse, 2 = Non-Directional
F157
ENUMERATION: BREAKER MODE
F155
ENUMERATION: REMOTE DEVICE STATE 0 = 3-Pole, 1 = 1-Pole
0 = Offline, 1 = Online
F158
ENUMERATION: SCHEME CALIBRATION TEST
0 = Normal, 1 = Symmetry 1, 2 = Symmetry 2, 3 = Delay 1
4 = Delay 2
F159
ENUMERATION: BREAKER AUX CONTACT KEYING
0 = 52a, 1 = 52b, 2 = None
F166 F175
ENUMERATION: AUXILIARY VT CONNECTION TYPE ENUMERATION: PHASE LETTERS
0 = Vn, 1 = Vag, 2 = Vbg, 3 = Vcg, 4 = Vab, 5 = Vbc, 6 = Vca 0 = A, 1 = B, 2 = C
F167 F176
ENUMERATION: SIGNAL SOURCE ENUMERATION: SYNCHROCHECK DEAD SOURCE SELECT
0 = SRC 1, 1 = SRC 2, 2 = SRC 3, 3 = SRC 4,
bitmask synchrocheck dead source
4 = SRC 5, 5 = SRC 6
0 None
1 LV1 and DV2
F168 2 DV1 and LV2
ENUMERATION: INRUSH INHIBIT FUNCTION
B 0 = Disabled, 1 = Adapt. 2nd, 2 = Trad. 2nd
3
4
DV1 or DV2
DV1 Xor DV2
5 DV1 and DV2
F170
ENUMERATION: LOW/HIGH OFFSET and GAIN F177
TRANSDUCER INPUT/OUTPUT SELECTION ENUMERATION: COMMUNICATION PORT
0 = LOW, 1 = HIGH 0 = None, 1 = COM1-RS485 (not applicable to UR firmware 7.00),
2 = COM2-RS485, 3 = Front Panel-RS232, 4 = Network - TCP,
5 = Network - UDP
F171
ENUMERATION: TRANSDUCER CHANNEL INPUT TYPE
0 = dcmA IN, 1 = Ohms IN, 2 = RTD IN, 3 = dcmA OUT, F178
4 = RRTD IN ENUMERATION: DATA LOGGER RATES
0 = 1 sec, 1 = 1 min, 2 = 5 min, 3 = 10 min, 4 = 15 min,
5 = 20 min, 6 = 30 min, 7 = 60 min, 8 = 15 ms, 9 = 30 ms,
F172 10 = 100 ms, 11 = 500 ms
ENUMERATION: SLOT LETTERS
F180
F173 ENUMERATION: PHASE/GROUND
ENUMERATION: DCMA INPUT/OUTPUT RANGE
0 = PHASE, 1 = GROUND
bitmask dcmA input/output range
0 0 to –1 mA
F181
1 0 to 1 mA ENUMERATION: ODD/EVEN/NONE
2 –1 to 1 mA
0 = ODD, 1 = EVEN, 2 = NONE
3 0 to 5 mA
4 0 to 10 mA
5 0 to 20 mA F183
6 4 to 20 mA ENUMERATION: AC INPUT WAVEFORMS
bitmask definition
F174 0 Off
ENUMERATION: TRANSDUCER RTD INPUT TYPE 1 8 samples/cycle
3 GooseIn 3
4 GooseIn 4
F192
5 GooseIn 5 ENUMERATION: ETHERNET OPERATION MODE
6 GooseIn 6
0 = Half-Duplex, 1 = Full-Duplex
7 GooseIn 7
8
9
GooseIn 8
GooseIn 9 F194
B
10 GooseIn 10 ENUMERATION: DNP SCALE
11 GooseIn 11 0 = 0.01, 1 = 0.1, 2 = 1, 3 = 10, 4 = 100, 5 = 1000, 6 = 10000,
12 GooseIn 12 7 = 100000, 8 = 0.001
13 GooseIn 13
14 GooseIn 14
F195
15 GooseIn 15 ENUMERATION: SINGLE POLE TRIP MODE
16 GooseIn 16
0 = Disabled, 1 = 3 Pole Only, 2 = 3 Pole & 1 Pole
F185
F196
ENUMERATION: PHASE A,B,C, GROUND SELECTOR
ENUMERATION: NEUTRAL DIRECTIONAL OVERCURRENT
0 = A, 1 = B, 2 = C, 3 = G OPERATING CURRENT
0 = Calculated 3I0, 1 = Measured IG
F186
ENUMERATION: MEASUREMENT MODE F198
0 = Phase to Ground, 1 = Phase to Phase ENUMERATION: PILOT SCHEME COMMUNICATION BITS
0 = 1, 1 = 2, 2 = 4
F190
ENUMERATION: SIMULATED KEYPRESS
F199
ENUMERATION: DISABLED/ENABLED/CUSTOM
bitmsk keypress bitmsk keypress
0 --- 23 Reset 0 = Disabled, 1 = Enabled, 2 = Custom
use between real keys
24 User 1
1 1 25 User 2
F200
2 2 26 User 3 TEXT40: 40-CHARACTER ASCII TEXT
3 3 27 User-programmable key 1
20 registers, 16 Bits: 1st Char MSB, 2nd Char. LSB
4 4 28 User-programmable key 2
5 5 29 User-programmable key 3
6 6 30 User-programmable key 4 F201
7 7 31 User-programmable key 5 TEXT8: 8-CHARACTER ASCII PASSCODE
8 8 32 User-programmable key 6 4 registers, 16 Bits: 1st Char MSB, 2nd Char. LSB
9 9 33 User-programmable key 7
10 0 34 User-programmable key 8
F202
11 Decimal Point 35 User-programmable key 9
TEXT20: 20-CHARACTER ASCII TEXT
12 Plus/Minus 36 User-programmable key 10
10 registers, 16 Bits: 1st Char MSB, 2nd Char. LSB
13 Value Up 37 User-programmable key 11
14 Value Down 38 User-programmable key 12
15 Message Up 43 User-programmable key 13 F203
16 Message Down 44 User-programmable key 14 TEXT16: 16-CHARACTER ASCII TEXT
F204 F228
TEXT80: 80-CHARACTER ASCII TEXT ENUMERATION: SETTINGS CONTROL EVENT TYPE
0 = Unknown, 1 = Setting Change, 2 = Firmware Upgrade, 3 =
Hardware Change
F205
TEXT12: 12-CHARACTER ASCII TEXT
F229
ENUMERATION: SETTINGS CONTROL CHANGE METHOD
F206
TEXT6: 6-CHARACTER ASCII TEXT 0 = None, 1 = Keypad, 2 = Front Port, 3 = COM1, 4 = COM2, 5 =
Ethernet
F207
TEXT4: 4-CHARACTER ASCII TEXT F230
B ENUMERATION: DIRECTIONAL POLARIZING
0 = Voltage, 1 = Current, 2 = Dual, 3 = Dual-V, 4 = Dual-I
F208
TEXT2: 2-CHARACTER ASCII TEXT
F231
ENUMERATION: POLARIZING VOLTAGE
F211
ENUMERATION: SOURCE SELECTION 0 = Calculated V0, 1 = Measured VX
0 = None, 1 = SRC 1, 2 = SRC 2, 3 = SRC 3, 4 = SRC 4,
5 = SRC 5, 6 = SRC 6
F232
ENUMERATION: CONFIGURABLE GOOSE DATASET ITEMS
FOR TRANSMISSION
F213
TEXT32: 32-CHARACTER ASCII TEXT
value GOOSE dataset item
0 None
F220 1 GGIO1.ST.Ind1.q
ENUMERATION: PUSHBUTTON MESSAGE PRIORITY 2 GGIO1.ST.Ind1.stVal
3 GGIO1.ST.Ind2.q
value priority
4 GGIO1.ST.Ind2.stVal
0 Disabled
1 Normal
255 GGIO1.ST.Ind128.q
2 High Priority
256 GGIO1.ST.Ind128.stVal
257 MMXU1.MX.TotW.mag.f
F222 258 MMXU1.MX.TotVAr.mag.f
ENUMERATION: TEST ENUMERATION 259 MMXU1.MX.TotVA.mag.f
B 395
396
MMXU4.MX.W.phsC.cVal.mag.f
MMXU4.MX.VAr.phsA.cVal.mag.f
448
449
MMXU6.MX.PPV.phsAB.cVal.ang.f
MMXU6.MX.PPV.phsBC.cVal.mag.f
397 MMXU4.MX.VAr.phsB.cVal.mag.f 450 MMXU6.MX.PPV.phsBC.cVal.ang.f
398 MMXU4.MX.VAr.phsC.cVal.mag.f 451 MMXU6.MX.PPV.phsCA.cVal.mag.f
399 MMXU4.MX.VA.phsA.cVal.mag.f 452 MMXU6.MX.PPV.phsCA.cVal.ang.f
400 MMXU4.MX.VA.phsB.cVal.mag.f 453 MMXU6.MX.PhV.phsA.cVal.mag.f
401 MMXU4.MX.VA.phsC.cVal.mag.f 454 MMXU6.MX.PhV.phsA.cVal.ang.f
402 MMXU4.MX.PF.phsA.cVal.mag.f 455 MMXU6.MX.PhV.phsB.cVal.mag.f
403 MMXU4.MX.PF.phsB.cVal.mag.f 456 MMXU6.MX.PhV.phsB.cVal.ang.f
404 MMXU4.MX.PF.phsC.cVal.mag.f 457 MMXU6.MX.PhV.phsC.cVal.mag.f
405 MMXU5.MX.TotW.mag.f 458 MMXU6.MX.PhV.phsC.cVal.ang.f
406 MMXU5.MX.TotVAr.mag.f 459 MMXU6.MX.A.phsA.cVal.mag.f
407 MMXU5.MX.TotVA.mag.f 460 MMXU6.MX.A.phsA.cVal.ang.f
408 MMXU5.MX.TotPF.mag.f 461 MMXU6.MX.A.phsB.cVal.mag.f
409 MMXU5.MX.Hz.mag.f 462 MMXU6.MX.A.phsB.cVal.ang.f
410 MMXU5.MX.PPV.phsAB.cVal.mag.f 463 MMXU6.MX.A.phsC.cVal.mag.f
411 MMXU5.MX.PPV.phsAB.cVal.ang.f 464 MMXU6.MX.A.phsC.cVal.ang.f
412 MMXU5.MX.PPV.phsBC.cVal.mag.f 465 MMXU6.MX.A.neut.cVal.mag.f
413 MMXU5.MX.PPV.phsBC.cVal.ang.f 466 MMXU6.MX.A.neut.cVal.ang.f
414 MMXU5.MX.PPV.phsCA.cVal.mag.f 467 MMXU6.MX.W.phsA.cVal.mag.f
415 MMXU5.MX.PPV.phsCA.cVal.ang.f 468 MMXU6.MX.W.phsB.cVal.mag.f
416 MMXU5.MX.PhV.phsA.cVal.mag.f 469 MMXU6.MX.W.phsC.cVal.mag.f
417 MMXU5.MX.PhV.phsA.cVal.ang.f 470 MMXU6.MX.VAr.phsA.cVal.mag.f
418 MMXU5.MX.PhV.phsB.cVal.mag.f 471 MMXU6.MX.VAr.phsB.cVal.mag.f
419 MMXU5.MX.PhV.phsB.cVal.ang.f 472 MMXU6.MX.VAr.phsC.cVal.mag.f
420 MMXU5.MX.PhV.phsC.cVal.mag.f 473 MMXU6.MX.VA.phsA.cVal.mag.f
421 MMXU5.MX.PhV.phsC.cVal.ang.f 474 MMXU6.MX.VA.phsB.cVal.mag.f
422 MMXU5.MX.A.phsA.cVal.mag.f 475 MMXU6.MX.VA.phsC.cVal.mag.f
423 MMXU5.MX.A.phsA.cVal.ang.f 476 MMXU6.MX.PF.phsA.cVal.mag.f
424 MMXU5.MX.A.phsB.cVal.mag.f 477 MMXU6.MX.PF.phsB.cVal.mag.f
425 MMXU5.MX.A.phsB.cVal.ang.f 478 MMXU6.MX.PF.phsC.cVal.mag.f
426 MMXU5.MX.A.phsC.cVal.mag.f 479 GGIO4.MX.AnIn1.mag.f
427 MMXU5.MX.A.phsC.cVal.ang.f 480 GGIO4.MX.AnIn2.mag.f
428 MMXU5.MX.A.neut.cVal.mag.f 481 GGIO4.MX.AnIn3.mag.f
429 MMXU5.MX.A.neut.cVal.ang.f 482 GGIO4.MX.AnIn4.mag.f
430 MMXU5.MX.W.phsA.cVal.mag.f 483 GGIO4.MX.AnIn5.mag.f
431 MMXU5.MX.W.phsB.cVal.mag.f 484 GGIO4.MX.AnIn6.mag.f
432 MMXU5.MX.W.phsC.cVal.mag.f 485 GGIO4.MX.AnIn7.mag.f
433 MMXU5.MX.VAr.phsA.cVal.mag.f 486 GGIO4.MX.AnIn8.mag.f
434 MMXU5.MX.VAr.phsB.cVal.mag.f 487 GGIO4.MX.AnIn9.mag.f
435 MMXU5.MX.VAr.phsC.cVal.mag.f 488 GGIO4.MX.AnIn10.mag.f
436 MMXU5.MX.VA.phsA.cVal.mag.f 489 GGIO4.MX.AnIn11.mag.f
B 181
182
GGIO3.ST.UIntIn8.stVal
GGIO3.ST.UIntIn9.q
8
9
September
October
183 GGIO3.ST.UIntIn9.stVal 10 November
184 GGIO3.ST.UIntIn10.q 11 December
185 GGIO3.ST.UIntIn10.stVal
186 GGIO3.ST.UIntIn11.q
187 GGIO3.ST.UIntIn11.stVal F238
ENUMERATION: REAL TIME CLOCK DAY
188 GGIO3.ST.UIntIn12.q
189 GGIO3.ST.UIntIn12.stVal value day
190 GGIO3.ST.UIntIn13.q 0 Sunday
191 GGIO3.ST.UIntIn13.stVal 1 Monday
192 GGIO3.ST.UIntIn14.q 2 Tuesday
193 GGIO3.ST.UIntIn14.stVal 3 Wednesday
194 GGIO3.ST.UIntIn15.q 4 Thursday
195 GGIO3.ST.UIntIn15.stVal 5 Friday
196 GGIO3.ST.UIntIn16.q 6 Saturday
197 GGIO3.ST.UIntIn16.stVal
F239
F234 ENUMERATION: REAL TIME CLOCK DAYLIGHT SAVINGS
ENUMERATION: WATTMETRIC GROUND FAULT VOLTAGE TIME START DAY INSTANCE
value current
0 Calculated IN
1 Measured IG
F243
ENUMERATION: FIELD UNIT TYPE
F236
ENUMERATION: WATTMETRIC GRN FLT CURVE 0 = CC-05, 1 = CV-05, 2 = CC-01, 3 = CV-01
0 = Definite Time, 1 = Inverse, 2 = FlexCurve A, 3 = FlexCurve B,
4 = FlexCurve C, 5 = FlexCurve D
F244
ENUMERATION: PROCESS CARD PORT
0 = H4a, 1 = H4b 2 = H3a, 3 = H3b, 4 = H2a, 5 = H2b, 6 = H1a,
7 = H1b
The values in square brackets indicate the base type with P prefix
F245 [PTTTTTTT] and the values in round brackets indicate the descrip-
ENUMERATION: TEST MODE FUNCTION tor range. The right most T bit indicates whether the type is an ON
or OFF type. There can be a total of 64 types (plus protection ele-
Value Function ments). There can be a total of 256 descriptors of each type.
0 Disabled [0] Off (0) – this is boolean FALSE value
1 Isolated [1] On (1) – this is boolean TRUE value
2 Forcible [2] CONTACT INPUTS (1 to 96)
[3] CONTACT INPUTS OFF (1 to 96)
[4] VIRTUAL INPUTS (1 to 32)
[6] VIRTUAL OUTPUTS (1 to 64
[8] CONTACT OUTPUTS
F257
[10] CONTACT OUTPUTS VOLTAGE DETECTED (1 to 64)
ENUMERATION: PROCESS CARD DSP CONFIGURATION
[11] CONTACT OUTPUTS VOLTAGE OFF DETECTED (1 to 64)
value
0
instance
CC
[12] CONTACT OUTPUTS CURRENT DETECTED (1 to 64)
[13] CONTACT OUTPUTS CURRENT OFF DETECTED (1 to 64) B
[14] REMOTE INPUTS (1 to 32)
1 CV
[16] DIRECT INPUTS (1 to 96)
2 CD
[18] REMOTE OUTPUT DNA BIT PAIRS (1 to 32)
3 VC [20] REMOTE OUTPUT UserSt BIT PAIRS (1 to 32)
4 VV [22] REMOTE DEVICE ONLINE (1 to 16)
5 VD [24] MISCELLANEOUS EQUATION
[26] TELEPROTECTION INPUTS
6 DC
[28] INSERT (via keypad only)
7 DV
[30] DELETE (via keypad only)
8 DD [32] END
[34] NOT (1 INPUT)
[36] 2 INPUT XOR (0)
F260 [38] LATCH SET/RESET (2 inputs)
ENUMERATION: DATA LOGGER MODE [40] OR (2 to 16 inputs)
[42] AND (2 to 16 inputs)
0 = Continuous, 1 = Trigger
[44] NOR (2 to 16 inputs)
[46] NAND (2 to 16 inputs)
[48] TIMER (1 to 32)
F261
[50] ASSIGN VIRTUAL OUTPUT (1 to 64)
ENUMERATION: BANK REDUNDANCY TYPE
[52] ONE SHOT
0 = None, 1 = Dependability Biased, 2 = Security Biased [54] SELF-TEST ERROR (see F141 for range)
[56] PLATFORM DIRECT INPUT (1 to 96)
[58] PLATFORM DIRECT OUTPUT (1 to 96)
F263 [60] PLATFORM DIRECT DEVICE (1 to 8)
ENUMERATION: PROCESS BUS SYSTEM STATUS [62] MISCELLANEOUS EVENTS (see F146 for range)
[64] PDC NETWORK CONTROL
0 = N/A, 1 = OK, 2 = Fail
[66] PMU RECORDERE OUT OF MEMORY
[68] PMU RECORDER STOPPED
[128 to 255] ELEMENT STATES (see memory map element states
F270
section)
ENUMERATION: FAULT REPORT VT SUBSTITUTION
Value Description
F400
0 None UR_UINT16: CT/VT BANK SELECTION
1 I_0
bitmask bank selection
2 V_0
0 Card 1 Contact 1 to 4
1 Card 1 Contact 5 to 8
F300 2 Card 2 Contact 1 to 4
UR_UINT32: FLEXLOGIC BASE TYPE (15-bit type) 3 Card 2 Contact 5 to 8
The FlexLogic BASE type is 7 bits and is combined with an 8-bit 4 Card 3 Contact 1 to 4
descriptor and 1 bit for protection element to form a 16-bit value. 5 Card 3 Contact 5 to 8
The combined bits are of the form: PTTTTTTTDDDDDDDD,
where P bit if set, indicates that the FlexLogic type is associated
with a protection element state and T represents bits for the BASE F491
type, and D represents bits for the descriptor. ENUMERATION: ANALOG INPUT MODE
0 = Default Value, 1 = Last Known
F508
F500 BITFIELD: DISTANCE ELEMENT STATE
UR_UINT16: PACKED BITFIELD bitmask distance element state
First register indicates input/output state with bits 0 (MSB) to 15 0 Pickup
(LSB) corresponding to input/output state 1 to 16. The second reg- 1 Operate
ister indicates input/output state with bits 0 to 15 corresponding to 2 Pickup AB
input/output state 17 to 32 (if required) The third register indicates
3 Pickup BC
input/output state with bits 0 to 15 corresponding to input/output
state 33 to 48 (if required). The fourth register indicates input/out- 4 Pickup CA
put state with bits 0 to 15 corresponding to input/output state 49 to 5 Operate AB
64 (if required). 6 Operate BC
The number of registers required is determined by the specific 7 Operate CA
data item. A bit value of 0 = Off and 1 = On.
B
8 Timed
9 Operate IAB
10 Operate IBC
F501
UR_UINT16: LED STATUS 11 Operate ICA
F504 F512
BITFIELD: 3-PHASE ELEMENT STATE ENUMERATION: HARMONIC NUMBER
bitmask element state
bitmask harmonic bitmask harmonic
0 Pickup
0 2ND 12 14TH
1 Operate
1 3RD 13 15TH
2 Pickup Phase A
2 4TH 14 16TH
3 Pickup Phase B
3 5TH 15 17TH
4 Pickup Phase C
4 6TH 16 18TH
5 Operate Phase A
5 7TH 17 19TH
6 Operate Phase B
6 8TH 18 20TH
7 Operate Phase C
7 9TH 19 21ST
8 10TH 20 22ND
9 11TH 21 23RD
F505
BITFIELD: CONTACT OUTPUT STATE 10 12TH 22 24TH
11 13TH 23 25TH
0 = Contact State, 1 = Voltage Detected, 2 = Current Detected
F513
F506|
ENUMERATION: POWER SWING MODE
BITFIELD: SINGLE-PHASE ELEMENT STATE
0 = Two Step, 1 = Three Step
0 = Pickup, 1 = Operate
F514
F507
BITFIELD: COUNTER ELEMENT STATE ENUMERATION: POWER SWING TRIP MODE
0 = Count Greater Than, 1 = Count Equal To, 2 = Count Less Than 0 = Delayed, 1 = Early
F515 F525
ENUMERATION ELEMENT INPUT MODE ENUMERATION: DNP OBJECT 32 DEFAULT VARIATION
0 = Signed, 1 = Absolute
bitmask default variation
0 1
F516 1 2
ENUMERATION ELEMENT COMPARE MODE 2 3
0 = Level, 1 = Delta 3 4
4 5
5 7
F517
ENUMERATION: ELEMENT DIRECTION OPERATION
F530
0 = Over, 1 = Under
ENUMERATION: FRONT PANEL INTERFACE KEYPRESS B
value keypress value keypress value keypress
F518 0 None 15 3 33 User PB 3
ENUMERATION: FLEXELEMENT UNITS
1 Menu 16 Enter 34 User PB 4
0 = Milliseconds, 1 = Seconds, 2 = Minutes 2 Message Up 17 Message 35 User PB 5
Down
3 7 ~
18 0 ~
36 User PB 6
F519 4 8 19 Decimal 37 User PB 7
ENUMERATION: NON-VOLATILE LATCH
5 9 20 +/– 38 User PB 8
0 = Reset-Dominant, 1 = Set-Dominant 6 Help 21 Value Up 39 User PB 9
7 Message Left 22 Value Down 40 User PB 10
8 4 23 Reset 41 User PB 11
F521
ENUMERATION: GROUND DISTANCE POLARIZING CURRENT 9 5 24 User 1 42 User PB 12
10 6 25 User 2 44 User 4
0 = Zero-Sequence; 1 = Negative-Sequence
11 Escape 26 User 3 45 User 5
12 Message 31 User PB 1 46 User 6
Right
F522
ENUMERATION: TRANSDUCER DCMA OUTPUT RANGE 13 1 32 User PB 2 47 User 7
14 2
0 = –1 to 1 mA; 1 = 0 to 1 mA; 2 = 4 to 20 mA
F523 F531
ENUMERATION: LANGUAGE
ENUMERATION: DNP OBJECTS 20, 22, AND 23 DEFAULT
VARIATION 0 = English, 1 = French, 2 = Chinese, 3 = Russian, 4 = Turkish
F524 F542
ENUMERATION: DNP OBJECT 21 DEFAULT VARIATION ENUMERATION: PMU TRIGGERING MODE
0 = Automatic Overwrite, 1 = Protected
bitmask Default Variation
0 1
1 2
2 9
3 10
F543 F605
ENUMERATION: PMU PHASORS ENUMERATION: REMOTE DOUBLE-POINT STATUS INPUT
STATUS
value phasor value phasor
0 Off 8 Ig Enumeration Remote DPS input status
1 Va 9 V_1 0 Intermediate
2 Vb 10 V_2 1 Off
3 Vc 11 V_0 2 On
4 Vx 12 I_1 3 Bad
5 Ia 13 I_2
6 Ib 14 I_0
F606
7 Ic ENUMERATION: REMOTE DOUBLE-POINT STATUS INPUT
1 2/second 8 25/second
3 5/second 10 50/second
4 10/second 11 60/second
F607
5 12/second 12 100/second ENUMERATION: OPEN POLE DETECTOR MODE
6 15/second 13 120/second
Enumeration Open Pole Mode
0 Accelerated
F545 1 Traditional
ENUMERATION: PMU COM PORT TYPE
0 = Network, 1 = RS485, 2 = Dir Comm Ch1, 3 = Dir Comm Ch2,
4 = GOOSE, 5 = None F608
ENUMERATION: OPEN POLE DETECTION FUNCTION
F547 F609
ENUMERATION: TRIP OUTPUT TRIP RESET FUNCTION
ENUMERATION: PMU REPORTING FORMAT
0 = Integer, 1 = Floating Enumeration Trip Reset
0 Pole Curr OR Custom
1 CBaux OR Custom
F600
2 Custom
UR_UINT16: FLEXANALOG PARAMETER
Corresponds to the Modbus address of the value used when this
parameter is selected. Only certain values may be used as Flex- F610
Analogs (basically all metering quantities used in protection). ENUMERATION: SINGLE-POLE AUTORECLOSE INITIATION
MODE
0 None 52 PIOC12.ST.Op.general
1 PDIF1.ST.Str.general 53 PIOC13.ST.Str.general
2 PDIF1.ST.Op.general 54 PIOC13.ST.Op.general
3 PDIF2.ST.Str.general 55 PIOC14.ST.Str.general
4 PDIF2.ST.Op.general 56 PIOC14.ST.Op.general
5 PDIF3.ST.Str.general 57 PIOC15.ST.Str.general
6 PDIF3.ST.Op.general 58 PIOC15.ST.Op.general
7 PDIF4.ST.Str.general 59 PIOC16.ST.Str.general
8 PDIF4.ST.Op.general 60 PIOC16.ST.Op.general
9 PDIS1.ST.Str.general 61 PIOC17.ST.Str.general
10 PDIS1.ST.Op.general 62 PIOC17.ST.Op.general
11 PDIS2.ST.Str.general 63 PIOC18.ST.Str.general
12 PDIS2.ST.Op.general 64 PIOC18.ST.Op.general
13 PDIS3.ST.Str.general 65 PIOC19.ST.Str.general
14 PDIS3.ST.Op.general 66 PIOC19.ST.Op.general
15 PDIS4.ST.Str.general 67 PIOC20.ST.Str.general
16 PDIS4.ST.Op.general 68 PIOC20.ST.Op.general
17 PDIS5.ST.Str.general 69 PIOC21.ST.Str.general
18 PDIS5.ST.Op.general 70 PIOC21.ST.Op.general
19 PDIS6.ST.Str.general 71 PIOC22.ST.Str.general
20 PDIS6.ST.Op.general 72 PIOC22.ST.Op.general
21 PDIS7.ST.Str.general 73 PIOC23.ST.Str.general
22 PDIS7.ST.Op.general 74 PIOC23.ST.Op.general
23 PDIS8.ST.Str.general 75 PIOC24.ST.Str.general
24 PDIS8.ST.Op.general 76 PIOC24.ST.Op.general
25 PDIS9.ST.Str.general 77 PIOC25.ST.Str.general
26 PDIS9.ST.Op.general 78 PIOC25.ST.Op.general
27 PDIS10.ST.Str.general 79 PIOC26.ST.Str.general
28 PDIS10.ST.Op.general 80 PIOC26.ST.Op.general
29 PIOC1.ST.Str.general 81 PIOC27.ST.Str.general
30 PIOC1.ST.Op.general 82 PIOC27.ST.Op.general
31 PIOC2.ST.Str.general 83 PIOC28.ST.Str.general
32 PIOC2.ST.Op.general 84 PIOC28.ST.Op.general
33 PIOC3.ST.Str.general 85 PIOC29.ST.Str.general
86 PIOC29.ST.Op.general
Enumeration IEC 61850 report dataset items Enumeration IEC 61850 report dataset items
87 PIOC30.ST.Str.general 140 PIOC56.ST.Op.general
88 PIOC30.ST.Op.general 141 PIOC57.ST.Str.general
89 PIOC31.ST.Str.general 142 PIOC57.ST.Op.general
90 PIOC31.ST.Op.general 143 PIOC58.ST.Str.general
91 PIOC32.ST.Str.general 144 PIOC58.ST.Op.general
92 PIOC32.ST.Op.general 145 PIOC59.ST.Str.general
93 PIOC33.ST.Str.general 146 PIOC59.ST.Op.general
94 PIOC33.ST.Op.general 147 PIOC60.ST.Str.general
95 PIOC34.ST.Str.general 148 PIOC60.ST.Op.general
96 PIOC34.ST.Op.general 149 PIOC61.ST.Str.general
97 PIOC35.ST.Str.general 150 PIOC61.ST.Op.general
B 98
99
PIOC35.ST.Op.general
PIOC36.ST.Str.general
151
152
PIOC62.ST.Str.general
PIOC62.ST.Op.general
100 PIOC36.ST.Op.general 153 PIOC63.ST.Str.general
101 PIOC37.ST.Str.general 154 PIOC63.ST.Op.general
102 PIOC37.ST.Op.general 155 PIOC64.ST.Str.general
103 PIOC38.ST.Str.general 156 PIOC64.ST.Op.general
104 PIOC38.ST.Op.general 157 PIOC65.ST.Str.general
105 PIOC39.ST.Str.general 158 PIOC65.ST.Op.general
106 PIOC39.ST.Op.general 159 PIOC66.ST.Str.general
107 PIOC40.ST.Str.general 160 PIOC66.ST.Op.general
108 PIOC40.ST.Op.general 161 PIOC67.ST.Str.general
109 PIOC41.ST.Str.general 162 PIOC67.ST.Op.general
110 PIOC41.ST.Op.general 163 PIOC68.ST.Str.general
111 PIOC42.ST.Str.general 164 PIOC68.ST.Op.general
112 PIOC42.ST.Op.general 165 PIOC69.ST.Str.general
113 PIOC43.ST.Str.general 166 PIOC69.ST.Op.general
114 PIOC43.ST.Op.general 167 PIOC70.ST.Str.general
115 PIOC44.ST.Str.general 168 PIOC70.ST.Op.general
116 PIOC44.ST.Op.general 169 PIOC71.ST.Str.general
117 PIOC45.ST.Str.general 170 PIOC71.ST.Op.general
118 PIOC45.ST.Op.general 171 PIOC72.ST.Str.general
119 PIOC46.ST.Str.general 172 PIOC72.ST.Op.general
120 PIOC46.ST.Op.general 173 PTOC1.ST.Str.general
121 PIOC47.ST.Str.general 174 PTOC1.ST.Op.general
122 PIOC47.ST.Op.general 175 PTOC2.ST.Str.general
123 PIOC48.ST.Str.general 176 PTOC2.ST.Op.general
124 PIOC48.ST.Op.general 177 PTOC3.ST.Str.general
125 PIOC49.ST.Str.general 178 PTOC3.ST.Op.general
126 PIOC49.ST.Op.general 179 PTOC4.ST.Str.general
127 PIOC50.ST.Str.general 180 PTOC4.ST.Op.general
128 PIOC50.ST.Op.general 181 PTOC5.ST.Str.general
129 PIOC51.ST.Str.general 182 PTOC5.ST.Op.general
130 PIOC51.ST.Op.general 183 PTOC6.ST.Str.general
131 PIOC52.ST.Str.general 184 PTOC6.ST.Op.general
132 PIOC52.ST.Op.general 185 PTOC7.ST.Str.general
133 PIOC53.ST.Str.general 186 PTOC7.ST.Op.general
134 PIOC53.ST.Op.general 187 PTOC8.ST.Str.general
135 PIOC54.ST.Str.general 188 PTOC8.ST.Op.general
136 PIOC54.ST.Op.general 189 PTOC9.ST.Str.general
137 PIOC55.ST.Str.general 190 PTOC9.ST.Op.general
138 PIOC55.ST.Op.general 191 PTOC10.ST.Str.general
139 PIOC56.ST.Str.general 192 PTOC10.ST.Op.general
Enumeration IEC 61850 report dataset items Enumeration IEC 61850 report dataset items
193 PTOC11.ST.Str.general 246 PTRC3.ST.Op.general
194 PTOC11.ST.Op.general 247 PTRC4.ST.Tr.general
195 PTOC12.ST.Str.general 248 PTRC4.ST.Op.general
196 PTOC12.ST.Op.general 249 PTRC5.ST.Tr.general
197 PTOC13.ST.Str.general 250 PTRC5.ST.Op.general
198 PTOC13.ST.Op.general 251 PTRC6.ST.Tr.general
199 PTOC14.ST.Str.general 252 PTRC6.ST.Op.general
200 PTOC14.ST.Op.general 253 PTUV1.ST.Str.general
201 PTOC15.ST.Str.general 254 PTUV1.ST.Op.general
202 PTOC15.ST.Op.general 255 PTUV2.ST.Str.general
203 PTOC16.ST.Str.general 256 PTUV2.ST.Op.general
204
205
PTOC16.ST.Op.general
PTOC17.ST.Str.general
257
258
PTUV3.ST.Str.general
PTUV3.ST.Op.general
B
206 PTOC17.ST.Op.general 259 PTUV4.ST.Str.general
207 PTOC18.ST.Str.general 260 PTUV4.ST.Op.general
208 PTOC18.ST.Op.general 261 PTUV5.ST.Str.general
209 PTOC19.ST.Str.general 262 PTUV5.ST.Op.general
210 PTOC19.ST.Op.general 263 PTUV6.ST.Str.general
211 PTOC20.ST.Str.general 264 PTUV6.ST.Op.general
212 PTOC20.ST.Op.general 265 PTUV7.ST.Str.general
213 PTOC21.ST.Str.general 266 PTUV7.ST.Op.general
214 PTOC21.ST.Op.general 267 PTUV8.ST.Str.general
215 PTOC22.ST.Str.general 268 PTUV8.ST.Op.general
216 PTOC22.ST.Op.general 269 PTUV9.ST.Str.general
217 PTOC23.ST.Str.general 270 PTUV9.ST.Op.general
218 PTOC23.ST.Op.general 271 PTUV10.ST.Str.general
219 PTOC24.ST.Str.general 272 PTUV10.ST.Op.general
220 PTOC24.ST.Op.general 273 PTUV11.ST.Str.general
221 PTOV1.ST.Str.general 274 PTUV11.ST.Op.general
222 PTOV1.ST.Op.general 275 PTUV12.ST.Str.general
223 PTOV2.ST.Str.general 276 PTUV12.ST.Op.general
224 PTOV2.ST.Op.general 277 PTUV13.ST.Str.general
225 PTOV3.ST.Str.general 278 PTUV13.ST.Op.general
226 PTOV3.ST.Op.general 279 RBRF1.ST.OpEx.general
227 PTOV4.ST.Str.general 280 RBRF1.ST.OpIn.general
228 PTOV4.ST.Op.general 281 RBRF2.ST.OpEx.general
229 PTOV5.ST.Str.general 282 RBRF2.ST.OpIn.general
230 PTOV5.ST.Op.general 283 RBRF3.ST.OpEx.general
231 PTOV6.ST.Str.general 284 RBRF3.ST.OpIn.general
232 PTOV6.ST.Op.general 285 RBRF4.ST.OpEx.general
233 PTOV7.ST.Str.general 286 RBRF4.ST.OpIn.general
234 PTOV7.ST.Op.general 287 RBRF5.ST.OpEx.general
235 PTOV8.ST.Str.general 288 RBRF5.ST.OpIn.general
236 PTOV8.ST.Op.general 289 RBRF6.ST.OpEx.general
237 PTOV9.ST.Str.general 290 RBRF6.ST.OpIn.general
238 PTOV9.ST.Op.general 291 RBRF7.ST.OpEx.general
239 PTOV10.ST.Str.general 292 RBRF7.ST.OpIn.general
240 PTOV10.ST.Op.general 293 RBRF8.ST.OpEx.general
241 PTRC1.ST.Tr.general 294 RBRF8.ST.OpIn.general
242 PTRC1.ST.Op.general 295 RBRF9.ST.OpEx.general
243 PTRC2.ST.Tr.general 296 RBRF9.ST.OpIn.general
244 PTRC2.ST.Op.general 297 RBRF10.ST.OpEx.general
245 PTRC3.ST.Tr.general 298 RBRF10.ST.OpIn.general
Enumeration IEC 61850 report dataset items Enumeration IEC 61850 report dataset items
299 RBRF11.ST.OpEx.general 352 CSWI3.ST.Pos.stVal
300 RBRF11.ST.OpIn.general 353 CSWI4.ST.Loc.stVal
301 RBRF12.ST.OpEx.general 354 CSWI4.ST.Pos.stVal
302 RBRF12.ST.OpIn.general 355 CSWI5.ST.Loc.stVal
303 RBRF13.ST.OpEx.general 356 CSWI5.ST.Pos.stVal
304 RBRF13.ST.OpIn.general 357 CSWI6.ST.Loc.stVal
305 RBRF14.ST.OpEx.general 358 CSWI6.ST.Pos.stVal
306 RBRF14.ST.OpIn.general 359 CSWI7.ST.Loc.stVal
307 RBRF15.ST.OpEx.general 360 CSWI7.ST.Pos.stVal
308 RBRF15.ST.OpIn.general 361 CSWI8.ST.Loc.stVal
309 RBRF16.ST.OpEx.general 362 CSWI8.ST.Pos.stVal
B 310
311
RBRF16.ST.OpIn.general
RBRF17.ST.OpEx.general
363
364
CSWI9.ST.Loc.stVal
CSWI9.ST.Pos.stVal
312 RBRF17.ST.OpIn.general 365 CSWI10.ST.Loc.stVal
313 RBRF18.ST.OpEx.general 366 CSWI10.ST.Pos.stVal
314 RBRF18.ST.OpIn.general 367 CSWI11.ST.Loc.stVal
315 RBRF19.ST.OpEx.general 368 CSWI11.ST.Pos.stVal
316 RBRF19.ST.OpIn.general 369 CSWI12.ST.Loc.stVal
317 RBRF20.ST.OpEx.general 370 CSWI12.ST.Pos.stVal
318 RBRF20.ST.OpIn.general 371 CSWI13.ST.Loc.stVal
319 RBRF21.ST.OpEx.general 372 CSWI13.ST.Pos.stVal
320 RBRF21.ST.OpIn.general 373 CSWI14.ST.Loc.stVal
321 RBRF22.ST.OpEx.general 374 CSWI14.ST.Pos.stVal
322 RBRF22.ST.OpIn.general 375 CSWI15.ST.Loc.stVal
323 RBRF23.ST.OpEx.general 376 CSWI15.ST.Pos.stVal
324 RBRF23.ST.OpIn.general 377 CSWI16.ST.Loc.stVal
325 RBRF24.ST.OpEx.general 378 CSWI16.ST.Pos.stVal
326 RBRF24.ST.OpIn.general 379 CSWI17.ST.Loc.stVal
327 RFLO1.MX.FltDiskm.mag.f 380 CSWI17.ST.Pos.stVal
328 RFLO2.MX.FltDiskm.mag.f 381 CSWI18.ST.Loc.stVal
329 RFLO3.MX.FltDiskm.mag.f 382 CSWI18.ST.Pos.stVal
330 RFLO4.MX.FltDiskm.mag.f 383 CSWI19.ST.Loc.stVal
331 RFLO5.MX.FltDiskm.mag.f 384 CSWI19.ST.Pos.stVal
332 RPSB1.ST.Str.general 385 CSWI20.ST.Loc.stVal
333 RPSB1.ST.Op.general 386 CSWI20.ST.Pos.stVal
334 RPSB1.ST.BlkZn.stVal 387 CSWI21.ST.Loc.stVal
335 RREC1.ST.Op.general 388 CSWI21.ST.Pos.stVal
336 RREC1.ST.AutoRecSt.stVal 389 CSWI22.ST.Loc.stVal
337 RREC2.ST.Op.general 390 CSWI22.ST.Pos.stVal
338 RREC2.ST.AutoRecSt.stVal 391 CSWI23.ST.Loc.stVal
339 RREC3.ST.Op.general 392 CSWI23.ST.Pos.stVal
340 RREC3.ST.AutoRecSt.stVal 393 CSWI24.ST.Loc.stVal
341 RREC4.ST.Op.general 394 CSWI24.ST.Pos.stVal
342 RREC4.ST.AutoRecSt.stVal 395 CSWI25.ST.Loc.stVal
343 RREC5.ST.Op.general 396 CSWI25.ST.Pos.stVal
344 RREC5.ST.AutoRecSt.stVal 397 CSWI26.ST.Loc.stVal
345 RREC6.ST.Op.general 398 CSWI26.ST.Pos.stVal
346 RREC6.ST.AutoRecSt.stVal 399 CSWI27.ST.Loc.stVal
347 CSWI1.ST.Loc.stVal 400 CSWI27.ST.Pos.stVal
348 CSWI1.ST.Pos.stVal 401 CSWI28.ST.Loc.stVal
349 CSWI2.ST.Loc.stVal 402 CSWI28.ST.Pos.stVal
350 CSWI2.ST.Pos.stVal 403 CSWI29.ST.Loc.stVal
351 CSWI3.ST.Loc.stVal 404 CSWI29.ST.Pos.stVal
Enumeration IEC 61850 report dataset items Enumeration IEC 61850 report dataset items
405 CSWI30.ST.Loc.stVal 458 GGIO1.ST.Ind52.stVal
406 CSWI30.ST.Pos.stVal 459 GGIO1.ST.Ind53.stVal
407 GGIO1.ST.Ind1.stVal 460 GGIO1.ST.Ind54.stVal
408 GGIO1.ST.Ind2.stVal 461 GGIO1.ST.Ind55.stVal
409 GGIO1.ST.Ind3.stVal 462 GGIO1.ST.Ind56.stVal
410 GGIO1.ST.Ind4.stVal 463 GGIO1.ST.Ind57.stVal
411 GGIO1.ST.Ind5.stVal 464 GGIO1.ST.Ind58.stVal
412 GGIO1.ST.Ind6.stVal 465 GGIO1.ST.Ind59.stVal
413 GGIO1.ST.Ind7.stVal 466 GGIO1.ST.Ind60.stVal
414 GGIO1.ST.Ind8.stVal 467 GGIO1.ST.Ind61.stVal
415 GGIO1.ST.Ind9.stVal 468 GGIO1.ST.Ind62.stVal
416
417
GGIO1.ST.Ind10.stVal
GGIO1.ST.Ind11.stVal
469
470
GGIO1.ST.Ind63.stVal
GGIO1.ST.Ind64.stVal
B
418 GGIO1.ST.Ind12.stVal 471 GGIO1.ST.Ind65.stVal
419 GGIO1.ST.Ind13.stVal 472 GGIO1.ST.Ind66.stVal
420 GGIO1.ST.Ind14.stVal 473 GGIO1.ST.Ind67.stVal
421 GGIO1.ST.Ind15.stVal 474 GGIO1.ST.Ind68.stVal
422 GGIO1.ST.Ind16.stVal 475 GGIO1.ST.Ind69.stVal
423 GGIO1.ST.Ind17.stVal 476 GGIO1.ST.Ind70.stVal
424 GGIO1.ST.Ind18.stVal 477 GGIO1.ST.Ind71.stVal
425 GGIO1.ST.Ind19.stVal 478 GGIO1.ST.Ind72.stVal
426 GGIO1.ST.Ind20.stVal 479 GGIO1.ST.Ind73.stVal
427 GGIO1.ST.Ind21.stVal 480 GGIO1.ST.Ind74.stVal
428 GGIO1.ST.Ind22.stVal 481 GGIO1.ST.Ind75.stVal
429 GGIO1.ST.Ind23.stVal 482 GGIO1.ST.Ind76.stVal
430 GGIO1.ST.Ind24.stVal 483 GGIO1.ST.Ind77.stVal
431 GGIO1.ST.Ind25.stVal 484 GGIO1.ST.Ind78.stVal
432 GGIO1.ST.Ind26.stVal 485 GGIO1.ST.Ind79.stVal
433 GGIO1.ST.Ind27.stVal 486 GGIO1.ST.Ind80.stVal
434 GGIO1.ST.Ind28.stVal 487 GGIO1.ST.Ind81.stVal
435 GGIO1.ST.Ind29.stVal 488 GGIO1.ST.Ind82.stVal
436 GGIO1.ST.Ind30.stVal 489 GGIO1.ST.Ind83.stVal
437 GGIO1.ST.Ind31.stVal 490 GGIO1.ST.Ind84.stVal
438 GGIO1.ST.Ind32.stVal 491 GGIO1.ST.Ind85.stVal
439 GGIO1.ST.Ind33.stVal 492 GGIO1.ST.Ind86.stVal
440 GGIO1.ST.Ind34.stVal 493 GGIO1.ST.Ind87.stVal
441 GGIO1.ST.Ind35.stVal 494 GGIO1.ST.Ind88.stVal
442 GGIO1.ST.Ind36.stVal 495 GGIO1.ST.Ind89.stVal
443 GGIO1.ST.Ind37.stVal 496 GGIO1.ST.Ind90.stVal
444 GGIO1.ST.Ind38.stVal 497 GGIO1.ST.Ind91.stVal
445 GGIO1.ST.Ind39.stVal 498 GGIO1.ST.Ind92.stVal
446 GGIO1.ST.Ind40.stVal 499 GGIO1.ST.Ind93.stVal
447 GGIO1.ST.Ind41.stVal 500 GGIO1.ST.Ind94.stVal
448 GGIO1.ST.Ind42.stVal 501 GGIO1.ST.Ind95.stVal
449 GGIO1.ST.Ind43.stVal 502 GGIO1.ST.Ind96.stVal
450 GGIO1.ST.Ind44.stVal 503 GGIO1.ST.Ind97.stVal
451 GGIO1.ST.Ind45.stVal 504 GGIO1.ST.Ind98.stVal
452 GGIO1.ST.Ind46.stVal 505 GGIO1.ST.Ind99.stVal
453 GGIO1.ST.Ind47.stVal 506 GGIO1.ST.Ind100.stVal
454 GGIO1.ST.Ind48.stVal 507 GGIO1.ST.Ind101.stVal
455 GGIO1.ST.Ind49.stVal 508 GGIO1.ST.Ind102.stVal
456 GGIO1.ST.Ind50.stVal 509 GGIO1.ST.Ind103.stVal
457 GGIO1.ST.Ind51.stVal 510 GGIO1.ST.Ind104.stVal
Enumeration IEC 61850 report dataset items Enumeration IEC 61850 report dataset items
511 GGIO1.ST.Ind105.stVal 564 MMXU1.MX.VAr.phsB.cVal.mag.f
512 GGIO1.ST.Ind106.stVal 565 MMXU1.MX.VAr.phsC.cVal.mag.f
513 GGIO1.ST.Ind107.stVal 566 MMXU1.MX.VA.phsA.cVal.mag.f
514 GGIO1.ST.Ind108.stVal 567 MMXU1.MX.VA.phsB.cVal.mag.f
515 GGIO1.ST.Ind109.stVal 568 MMXU1.MX.VA.phsC.cVal.mag.f
516 GGIO1.ST.Ind110.stVal 569 MMXU1.MX.PF.phsA.cVal.mag.f
517 GGIO1.ST.Ind111.stVal 570 MMXU1.MX.PF.phsB.cVal.mag.f
518 GGIO1.ST.Ind112.stVal 571 MMXU1.MX.PF.phsC.cVal.mag.f
519 GGIO1.ST.Ind113.stVal 572 MMXU2.MX.TotW.mag.f
520 GGIO1.ST.Ind114.stVal 573 MMXU2.MX.TotVAr.mag.f
521 GGIO1.ST.Ind115.stVal 574 MMXU2.MX.TotVA.mag.f
B 522
523
GGIO1.ST.Ind116.stVal
GGIO1.ST.Ind117.stVal
575
576
MMXU2.MX.TotPF.mag.f
MMXU2.MX.Hz.mag.f
524 GGIO1.ST.Ind118.stVal 577 MMXU2.MX.PPV.phsAB.cVal.mag.f
525 GGIO1.ST.Ind119.stVal 578 MMXU2.MX.PPV.phsAB.cVal.ang.f
526 GGIO1.ST.Ind120.stVal 579 MMXU2.MX.PPV.phsBC.cVal.mag.f
527 GGIO1.ST.Ind121.stVal 580 MMXU2.MX.PPV.phsBC.cVal.ang.f
528 GGIO1.ST.Ind122.stVal 581 MMXU2.MX.PPV.phsCA.cVal.mag.f
529 GGIO1.ST.Ind123.stVal 582 MMXU2.MX.PPV.phsCA.cVal.ang.f
530 GGIO1.ST.Ind124.stVal 583 MMXU2.MX.PhV.phsA.cVal.mag.f
531 GGIO1.ST.Ind125.stVal 584 MMXU2.MX.PhV.phsA.cVal.ang.f
532 GGIO1.ST.Ind126.stVal 585 MMXU2.MX.PhV.phsB.cVal.mag.f
533 GGIO1.ST.Ind127.stVal 586 MMXU2.MX.PhV.phsB.cVal.ang.f
534 GGIO1.ST.Ind128.stVal 587 MMXU2.MX.PhV.phsC.cVal.mag.f
535 MMXU1.MX.TotW.mag.f 588 MMXU2.MX.PhV.phsC.cVal.ang.f
536 MMXU1.MX.TotVAr.mag.f 589 MMXU2.MX.A.phsA.cVal.mag.f
537 MMXU1.MX.TotVA.mag.f 590 MMXU2.MX.A.phsA.cVal.ang.f
538 MMXU1.MX.TotPF.mag.f 591 MMXU2.MX.A.phsB.cVal.mag.f
539 MMXU1.MX.Hz.mag.f 592 MMXU2.MX.A.phsB.cVal.ang.f
540 MMXU1.MX.PPV.phsAB.cVal.mag.f 593 MMXU2.MX.A.phsC.cVal.mag.f
541 MMXU1.MX.PPV.phsAB.cVal.ang.f 594 MMXU2.MX.A.phsC.cVal.ang.f
542 MMXU1.MX.PPV.phsBC.cVal.mag.f 595 MMXU2.MX.A.neut.cVal.mag.f
543 MMXU1.MX.PPV.phsBC.cVal.ang.f 596 MMXU2.MX.A.neut.cVal.ang.f
544 MMXU1.MX.PPV.phsCA.cVal.mag.f 597 MMXU2.MX.W.phsA.cVal.mag.f
545 MMXU1.MX.PPV.phsCA.cVal.ang.f 598 MMXU2.MX.W.phsB.cVal.mag.f
546 MMXU1.MX.PhV.phsA.cVal.mag.f 599 MMXU2.MX.W.phsC.cVal.mag.f
547 MMXU1.MX.PhV.phsA.cVal.ang.f 600 MMXU2.MX.VAr.phsA.cVal.mag.f
548 MMXU1.MX.PhV.phsB.cVal.mag.f 601 MMXU2.MX.VAr.phsB.cVal.mag.f
549 MMXU1.MX.PhV.phsB.cVal.ang.f 602 MMXU2.MX.VAr.phsC.cVal.mag.f
550 MMXU1.MX.PhV.phsC.cVal.mag.f 603 MMXU2.MX.VA.phsA.cVal.mag.f
551 MMXU1.MX.PhV.phsC.cVal.ang.f 604 MMXU2.MX.VA.phsB.cVal.mag.f
552 MMXU1.MX.A.phsA.cVal.mag.f 605 MMXU2.MX.VA.phsC.cVal.mag.f
553 MMXU1.MX.A.phsA.cVal.ang.f 606 MMXU2.MX.PF.phsA.cVal.mag.f
554 MMXU1.MX.A.phsB.cVal.mag.f 607 MMXU2.MX.PF.phsB.cVal.mag.f
555 MMXU1.MX.A.phsB.cVal.ang.f 608 MMXU2.MX.PF.phsC.cVal.mag.f
556 MMXU1.MX.A.phsC.cVal.mag.f 609 MMXU3.MX.TotW.mag.f
557 MMXU1.MX.A.phsC.cVal.ang.f 610 MMXU3.MX.TotVAr.mag.f
558 MMXU1.MX.A.neut.cVal.mag.f 611 MMXU3.MX.TotVA.mag.f
559 MMXU1.MX.A.neut.cVal.ang.f 612 MMXU3.MX.TotPF.mag.f
560 MMXU1.MX.W.phsA.cVal.mag.f 613 MMXU3.MX.Hz.mag.f
561 MMXU1.MX.W.phsB.cVal.mag.f 614 MMXU3.MX.PPV.phsAB.cVal.mag.f
562 MMXU1.MX.W.phsC.cVal.mag.f 615 MMXU3.MX.PPV.phsAB.cVal.ang.f
563 MMXU1.MX.VAr.phsA.cVal.mag.f 616 MMXU3.MX.PPV.phsBC.cVal.mag.f
Enumeration IEC 61850 report dataset items Enumeration IEC 61850 report dataset items
617 MMXU3.MX.PPV.phsBC.cVal.ang.f 670 MMXU4.MX.A.neut.cVal.ang.f
618 MMXU3.MX.PPV.phsCA.cVal.mag.f 671 MMXU4.MX.W.phsA.cVal.mag.f
619 MMXU3.MX.PPV.phsCA.cVal.ang.f 672 MMXU4.MX.W.phsB.cVal.mag.f
620 MMXU3.MX.PhV.phsA.cVal.mag.f 673 MMXU4.MX.W.phsC.cVal.mag.f
621 MMXU3.MX.PhV.phsA.cVal.ang.f 674 MMXU4.MX.VAr.phsA.cVal.mag.f
622 MMXU3.MX.PhV.phsB.cVal.mag.f 675 MMXU4.MX.VAr.phsB.cVal.mag.f
623 MMXU3.MX.PhV.phsB.cVal.ang.f 676 MMXU4.MX.VAr.phsC.cVal.mag.f
624 MMXU3.MX.PhV.phsC.cVal.mag.f 677 MMXU4.MX.VA.phsA.cVal.mag.f
625 MMXU3.MX.PhV.phsC.cVal.ang.f 678 MMXU4.MX.VA.phsB.cVal.mag.f
626 MMXU3.MX.A.phsA.cVal.mag.f 679 MMXU4.MX.VA.phsC.cVal.mag.f
627 MMXU3.MX.A.phsA.cVal.ang.f 680 MMXU4.MX.PF.phsA.cVal.mag.f
628
629
MMXU3.MX.A.phsB.cVal.mag.f
MMXU3.MX.A.phsB.cVal.ang.f
681
682
MMXU4.MX.PF.phsB.cVal.mag.f
MMXU4.MX.PF.phsC.cVal.mag.f
B
630 MMXU3.MX.A.phsC.cVal.mag.f 683 MMXU5.MX.TotW.mag.f
631 MMXU3.MX.A.phsC.cVal.ang.f 684 MMXU5.MX.TotVAr.mag.f
632 MMXU3.MX.A.neut.cVal.mag.f 685 MMXU5.MX.TotVA.mag.f
633 MMXU3.MX.A.neut.cVal.ang.f 686 MMXU5.MX.TotPF.mag.f
634 MMXU3.MX.W.phsA.cVal.mag.f 687 MMXU5.MX.Hz.mag.f
635 MMXU3.MX.W.phsB.cVal.mag.f 688 MMXU5.MX.PPV.phsAB.cVal.mag.f
636 MMXU3.MX.W.phsC.cVal.mag.f 689 MMXU5.MX.PPV.phsAB.cVal.ang.f
637 MMXU3.MX.VAr.phsA.cVal.mag.f 690 MMXU5.MX.PPV.phsBC.cVal.mag.f
638 MMXU3.MX.VAr.phsB.cVal.mag.f 691 MMXU5.MX.PPV.phsBC.cVal.ang.f
639 MMXU3.MX.VAr.phsC.cVal.mag.f 692 MMXU5.MX.PPV.phsCA.cVal.mag.f
640 MMXU3.MX.VA.phsA.cVal.mag.f 693 MMXU5.MX.PPV.phsCA.cVal.ang.f
641 MMXU3.MX.VA.phsB.cVal.mag.f 694 MMXU5.MX.PhV.phsA.cVal.mag.f
642 MMXU3.MX.VA.phsC.cVal.mag.f 695 MMXU5.MX.PhV.phsA.cVal.ang.f
643 MMXU3.MX.PF.phsA.cVal.mag.f 696 MMXU5.MX.PhV.phsB.cVal.mag.f
644 MMXU3.MX.PF.phsB.cVal.mag.f 697 MMXU5.MX.PhV.phsB.cVal.ang.f
645 MMXU3.MX.PF.phsC.cVal.mag.f 698 MMXU5.MX.PhV.phsC.cVal.mag.f
646 MMXU4.MX.TotW.mag.f 699 MMXU5.MX.PhV.phsC.cVal.ang.f
647 MMXU4.MX.TotVAr.mag.f 700 MMXU5.MX.A.phsA.cVal.mag.f
648 MMXU4.MX.TotVA.mag.f 701 MMXU5.MX.A.phsA.cVal.ang.f
649 MMXU4.MX.TotPF.mag.f 702 MMXU5.MX.A.phsB.cVal.mag.f
650 MMXU4.MX.Hz.mag.f 703 MMXU5.MX.A.phsB.cVal.ang.f
651 MMXU4.MX.PPV.phsAB.cVal.mag.f 704 MMXU5.MX.A.phsC.cVal.mag.f
652 MMXU4.MX.PPV.phsAB.cVal.ang.f 705 MMXU5.MX.A.phsC.cVal.ang.f
653 MMXU4.MX.PPV.phsBC.cVal.mag.f 706 MMXU5.MX.A.neut.cVal.mag.f
654 MMXU4.MX.PPV.phsBC.cVal.ang.f 707 MMXU5.MX.A.neut.cVal.ang.f
655 MMXU4.MX.PPV.phsCA.cVal.mag.f 708 MMXU5.MX.W.phsA.cVal.mag.f
656 MMXU4.MX.PPV.phsCA.cVal.ang.f 709 MMXU5.MX.W.phsB.cVal.mag.f
657 MMXU4.MX.PhV.phsA.cVal.mag.f 710 MMXU5.MX.W.phsC.cVal.mag.f
658 MMXU4.MX.PhV.phsA.cVal.ang.f 711 MMXU5.MX.VAr.phsA.cVal.mag.f
659 MMXU4.MX.PhV.phsB.cVal.mag.f 712 MMXU5.MX.VAr.phsB.cVal.mag.f
660 MMXU4.MX.PhV.phsB.cVal.ang.f 713 MMXU5.MX.VAr.phsC.cVal.mag.f
661 MMXU4.MX.PhV.phsC.cVal.mag.f 714 MMXU5.MX.VA.phsA.cVal.mag.f
662 MMXU4.MX.PhV.phsC.cVal.ang.f 715 MMXU5.MX.VA.phsB.cVal.mag.f
663 MMXU4.MX.A.phsA.cVal.mag.f 716 MMXU5.MX.VA.phsC.cVal.mag.f
664 MMXU4.MX.A.phsA.cVal.ang.f 717 MMXU5.MX.PF.phsA.cVal.mag.f
665 MMXU4.MX.A.phsB.cVal.mag.f 718 MMXU5.MX.PF.phsB.cVal.mag.f
666 MMXU4.MX.A.phsB.cVal.ang.f 719 MMXU5.MX.PF.phsC.cVal.mag.f
667 MMXU4.MX.A.phsC.cVal.mag.f 720 MMXU6.MX.TotW.mag.f
668 MMXU4.MX.A.phsC.cVal.ang.f 721 MMXU6.MX.TotVAr.mag.f
669 MMXU4.MX.A.neut.cVal.mag.f 722 MMXU6.MX.TotVA.mag.f
Enumeration IEC 61850 report dataset items Enumeration IEC 61850 report dataset items
723 MMXU6.MX.TotPF.mag.f 776 GGIO4.MX.AnIn20.mag.f
724 MMXU6.MX.Hz.mag.f 777 GGIO4.MX.AnIn21.mag.f
725 MMXU6.MX.PPV.phsAB.cVal.mag.f 778 GGIO4.MX.AnIn22.mag.f
726 MMXU6.MX.PPV.phsAB.cVal.ang.f 779 GGIO4.MX.AnIn23.mag.f
727 MMXU6.MX.PPV.phsBC.cVal.mag.f 780 GGIO4.MX.AnIn24.mag.f
728 MMXU6.MX.PPV.phsBC.cVal.ang.f 781 GGIO4.MX.AnIn25.mag.f
729 MMXU6.MX.PPV.phsCA.cVal.mag.f 782 GGIO4.MX.AnIn26.mag.f
730 MMXU6.MX.PPV.phsCA.cVal.ang.f 783 GGIO4.MX.AnIn27.mag.f
731 MMXU6.MX.PhV.phsA.cVal.mag.f 784 GGIO4.MX.AnIn28.mag.f
732 MMXU6.MX.PhV.phsA.cVal.ang.f 785 GGIO4.MX.AnIn29.mag.f
733 MMXU6.MX.PhV.phsB.cVal.mag.f 786 GGIO4.MX.AnIn30.mag.f
B 734
735
MMXU6.MX.PhV.phsB.cVal.ang.f
MMXU6.MX.PhV.phsC.cVal.mag.f
787
788
GGIO4.MX.AnIn31.mag.f
GGIO4.MX.AnIn32.mag.f
736 MMXU6.MX.PhV.phsC.cVal.ang.f 789 XSWI1.ST.Loc.stVal
737 MMXU6.MX.A.phsA.cVal.mag.f 790 XSWI1.ST.Pos.stVal
738 MMXU6.MX.A.phsA.cVal.ang.f 791 XSWI2.ST.Loc.stVal
739 MMXU6.MX.A.phsB.cVal.mag.f 792 XSWI2.ST.Pos.stVal
740 MMXU6.MX.A.phsB.cVal.ang.f 793 XSWI3.ST.Loc.stVal
741 MMXU6.MX.A.phsC.cVal.mag.f 794 XSWI3.ST.Pos.stVal
742 MMXU6.MX.A.phsC.cVal.ang.f 795 XSWI4.ST.Loc.stVal
743 MMXU6.MX.A.neut.cVal.mag.f 796 XSWI4.ST.Pos.stVal
744 MMXU6.MX.A.neut.cVal.ang.f 797 XSWI5.ST.Loc.stVal
745 MMXU6.MX.W.phsA.cVal.mag.f 798 XSWI5.ST.Pos.stVal
746 MMXU6.MX.W.phsB.cVal.mag.f 799 XSWI6.ST.Loc.stVal
747 MMXU6.MX.W.phsC.cVal.mag.f 800 XSWI6.ST.Pos.stVal
748 MMXU6.MX.VAr.phsA.cVal.mag.f 801 XSWI7.ST.Loc.stVal
749 MMXU6.MX.VAr.phsB.cVal.mag.f 802 XSWI7.ST.Pos.stVal
750 MMXU6.MX.VAr.phsC.cVal.mag.f 803 XSWI8.ST.Loc.stVal
751 MMXU6.MX.VA.phsA.cVal.mag.f 804 XSWI8.ST.Pos.stVal
752 MMXU6.MX.VA.phsB.cVal.mag.f 805 XSWI9.ST.Loc.stVal
753 MMXU6.MX.VA.phsC.cVal.mag.f 806 XSWI9.ST.Pos.stVal
754 MMXU6.MX.PF.phsA.cVal.mag.f 807 XSWI10.ST.Loc.stVal
755 MMXU6.MX.PF.phsB.cVal.mag.f 808 XSWI10.ST.Pos.stVal
756 MMXU6.MX.PF.phsC.cVal.mag.f 809 XSWI11.ST.Loc.stVal
757 GGIO4.MX.AnIn1.mag.f 810 XSWI11.ST.Pos.stVal
758 GGIO4.MX.AnIn2.mag.f 811 XSWI12.ST.Loc.stVal
759 GGIO4.MX.AnIn3.mag.f 812 XSWI12.ST.Pos.stVal
760 GGIO4.MX.AnIn4.mag.f 813 XSWI13.ST.Loc.stVal
761 GGIO4.MX.AnIn5.mag.f 814 XSWI13.ST.Pos.stVal
762 GGIO4.MX.AnIn6.mag.f 815 XSWI14.ST.Loc.stVal
763 GGIO4.MX.AnIn7.mag.f 816 XSWI14.ST.Pos.stVal
764 GGIO4.MX.AnIn8.mag.f 817 XSWI15.ST.Loc.stVal
765 GGIO4.MX.AnIn9.mag.f 818 XSWI15.ST.Pos.stVal
766 GGIO4.MX.AnIn10.mag.f 819 XSWI16.ST.Loc.stVal
767 GGIO4.MX.AnIn11.mag.f 820 XSWI16.ST.Pos.stVal
768 GGIO4.MX.AnIn12.mag.f 821 XSWI17.ST.Loc.stVal
769 GGIO4.MX.AnIn13.mag.f 822 XSWI17.ST.Pos.stVal
770 GGIO4.MX.AnIn14.mag.f 823 XSWI18.ST.Loc.stVal
771 GGIO4.MX.AnIn15.mag.f 824 XSWI18.ST.Pos.stVal
772 GGIO4.MX.AnIn16.mag.f 825 XSWI19.ST.Loc.stVal
773 GGIO4.MX.AnIn17.mag.f 826 XSWI19.ST.Pos.stVal
774 GGIO4.MX.AnIn18.mag.f 827 XSWI20.ST.Loc.stVal
775 GGIO4.MX.AnIn19.mag.f 828 XSWI20.ST.Pos.stVal
Enumeration IEC 61850 report dataset items Enumeration GOOSE dataset items
829 XSWI21.ST.Loc.stVal 28 GGIO1.ST.Ind14.stVal
830 XSWI21.ST.Pos.stVal 29 GGIO1.ST.Ind15.q
831 XSWI22.ST.Loc.stVal 30 GGIO1.ST.Ind15.stVal
832 XSWI22.ST.Pos.stVal 31 GGIO1.ST.Ind16.q
833 XSWI23.ST.Loc.stVal 32 GGIO1.ST.Ind16.stVal
834 XSWI23.ST.Pos.stVal 33 GGIO1.ST.Ind17.q
835 XSWI24.ST.Loc.stVal 34 GGIO1.ST.Ind17.stVal
836 XSWI24.ST.Pos.stVal 35 GGIO1.ST.Ind18.q
837 XCBR1.ST.Loc.stVal 36 GGIO1.ST.Ind18.stVal
838 XCBR1.ST.Pos.stVal 37 GGIO1.ST.Ind19.q
839 XCBR2.ST.Loc.stVal 38 GGIO1.ST.Ind19.stVal
840
841
XCBR2.ST.Pos.stVal
XCBR3.ST.Loc.stVal
39
40
GGIO1.ST.Ind20.q
GGIO1.ST.Ind20.stVal
B
842 XCBR3.ST.Pos.stVal 41 GGIO1.ST.Ind21.q
843 XCBR4.ST.Loc.stVal 42 GGIO1.ST.Ind21.stVal
844 XCBR4.ST.Pos.stVal 43 GGIO1.ST.Ind22.q
845 XCBR5.ST.Loc.stVal 44 GGIO1.ST.Ind22.stVal
846 XCBR5.ST.Pos.stVal 45 GGIO1.ST.Ind23.q
847 XCBR6.ST.Loc.stVal 46 GGIO1.ST.Ind23.stVal
848 XCBR6.ST.Pos.stVal 47 GGIO1.ST.Ind24.q
48 GGIO1.ST.Ind24.stVal
49 GGIO1.ST.Ind25.q
F616
50 GGIO1.ST.Ind25.stVal
ENUMERATION: IEC 61850 GOOSE DATASET ITEMS
51 GGIO1.ST.Ind26.q
Enumeration GOOSE dataset items 52 GGIO1.ST.Ind26.stVal
0 None 53 GGIO1.ST.Ind27.q
1 GGIO1.ST.Ind1.q 54 GGIO1.ST.Ind27.stVal
2 GGIO1.ST.Ind1.stVal 55 GGIO1.ST.Ind28.q
3 GGIO1.ST.Ind2.q 56 GGIO1.ST.Ind28.stVal
4 GGIO1.ST.Ind2.stVal 57 GGIO1.ST.Ind29.q
5 GGIO1.ST.Ind3.q 58 GGIO1.ST.Ind29.stVal
6 GGIO1.ST.Ind3.stVal 59 GGIO1.ST.Ind30.q
7 GGIO1.ST.Ind4.q 60 GGIO1.ST.Ind30.stVal
8 GGIO1.ST.Ind4.stVal 61 GGIO1.ST.Ind31.q
9 GGIO1.ST.Ind5.q 62 GGIO1.ST.Ind31.stVal
10 GGIO1.ST.Ind5.stVal 63 GGIO1.ST.Ind32.q
11 GGIO1.ST.Ind6.q 64 GGIO1.ST.Ind32.stVal
12 GGIO1.ST.Ind6.stVal 65 GGIO1.ST.Ind33.q
13 GGIO1.ST.Ind7.q 66 GGIO1.ST.Ind33.stVal
14 GGIO1.ST.Ind7.stVal 67 GGIO1.ST.Ind34.q
15 GGIO1.ST.Ind8.q 68 GGIO1.ST.Ind34.stVal
16 GGIO1.ST.Ind8.stVal 69 GGIO1.ST.Ind35.q
17 GGIO1.ST.Ind9.q 70 GGIO1.ST.Ind35.stVal
18 GGIO1.ST.Ind9.stVal 71 GGIO1.ST.Ind36.q
19 GGIO1.ST.Ind10.q 72 GGIO1.ST.Ind36.stVal
20 GGIO1.ST.Ind10.stVal 73 GGIO1.ST.Ind37.q
21 GGIO1.ST.Ind11.q 74 GGIO1.ST.Ind37.stVal
22 GGIO1.ST.Ind11.stVal 75 GGIO1.ST.Ind38.q
23 GGIO1.ST.Ind12.q 76 GGIO1.ST.Ind38.stVal
24 GGIO1.ST.Ind12.stVal 77 GGIO1.ST.Ind39.q
25 GGIO1.ST.Ind13.q 78 GGIO1.ST.Ind39.stVal
26 GGIO1.ST.Ind13.stVal 79 GGIO1.ST.Ind40.q
27 GGIO1.ST.Ind14.q 80 GGIO1.ST.Ind40.stVal
B 92
93
GGIO1.ST.Ind46.stVal
GGIO1.ST.Ind47.q
145
146
GGIO1.ST.Ind73.q
GGIO1.ST.Ind73.stVal
94 GGIO1.ST.Ind47.stVal 147 GGIO1.ST.Ind74.q
95 GGIO1.ST.Ind48.q 148 GGIO1.ST.Ind74.stVal
96 GGIO1.ST.Ind48.stVal 149 GGIO1.ST.Ind75.q
97 GGIO1.ST.Ind49.q 150 GGIO1.ST.Ind75.stVal
98 GGIO1.ST.Ind49.stVal 151 GGIO1.ST.Ind76.q
99 GGIO1.ST.Ind50.q 152 GGIO1.ST.Ind76.stVal
100 GGIO1.ST.Ind50.stVal 153 GGIO1.ST.Ind77.q
101 GGIO1.ST.Ind51.q 154 GGIO1.ST.Ind77.stVal
102 GGIO1.ST.Ind51.stVal 155 GGIO1.ST.Ind78.q
103 GGIO1.ST.Ind52.q 156 GGIO1.ST.Ind78.stVal
104 GGIO1.ST.Ind52.stVal 157 GGIO1.ST.Ind79.q
105 GGIO1.ST.Ind53.q 158 GGIO1.ST.Ind79.stVal
106 GGIO1.ST.Ind53.stVal 159 GGIO1.ST.Ind80.q
107 GGIO1.ST.Ind54.q 160 GGIO1.ST.Ind80.stVal
108 GGIO1.ST.Ind54.stVal 161 GGIO1.ST.Ind81.q
109 GGIO1.ST.Ind55.q 162 GGIO1.ST.Ind81.stVal
110 GGIO1.ST.Ind55.stVal 163 GGIO1.ST.Ind82.q
111 GGIO1.ST.Ind56.q 164 GGIO1.ST.Ind82.stVal
112 GGIO1.ST.Ind56.stVal 165 GGIO1.ST.Ind83.q
113 GGIO1.ST.Ind57.q 166 GGIO1.ST.Ind83.stVal
114 GGIO1.ST.Ind57.stVal 167 GGIO1.ST.Ind84.q
115 GGIO1.ST.Ind58.q 168 GGIO1.ST.Ind84.stVal
116 GGIO1.ST.Ind58.stVal 169 GGIO1.ST.Ind85.q
117 GGIO1.ST.Ind59.q 170 GGIO1.ST.Ind85.stVal
118 GGIO1.ST.Ind59.stVal 171 GGIO1.ST.Ind86.q
119 GGIO1.ST.Ind60.q 172 GGIO1.ST.Ind86.stVal
120 GGIO1.ST.Ind60.stVal 173 GGIO1.ST.Ind87.q
121 GGIO1.ST.Ind61.q 174 GGIO1.ST.Ind87.stVal
122 GGIO1.ST.Ind61.stVal 175 GGIO1.ST.Ind88.q
123 GGIO1.ST.Ind62.q 176 GGIO1.ST.Ind88.stVal
124 GGIO1.ST.Ind62.stVal 177 GGIO1.ST.Ind89.q
125 GGIO1.ST.Ind63.q 178 GGIO1.ST.Ind89.stVal
126 GGIO1.ST.Ind63.stVal 179 GGIO1.ST.Ind90.q
127 GGIO1.ST.Ind64.q 180 GGIO1.ST.Ind90.stVal
128 GGIO1.ST.Ind64.stVal 181 GGIO1.ST.Ind91.q
129 GGIO1.ST.Ind65.q 182 GGIO1.ST.Ind91.stVal
130 GGIO1.ST.Ind65.stVal 183 GGIO1.ST.Ind92.q
131 GGIO1.ST.Ind66.q 184 GGIO1.ST.Ind92.stVal
132 GGIO1.ST.Ind66.stVal 185 GGIO1.ST.Ind93.q
133 GGIO1.ST.Ind67.q 186 GGIO1.ST.Ind93.stVal
B 304
305
MMXU2.MX.PPV.phsCA.cVal.ang.f
MMXU2.MX.PhV.phsA.cVal.mag.f
357
358
MMXU3.MX.W.phsB.cVal.mag.f
MMXU3.MX.W.phsC.cVal.mag.f
306 MMXU2.MX.PhV.phsA.cVal.ang.f 359 MMXU3.MX.VAr.phsA.cVal.mag.f
307 MMXU2.MX.PhV.phsB.cVal.mag.f 360 MMXU3.MX.VAr.phsB.cVal.mag.f
308 MMXU2.MX.PhV.phsB.cVal.ang.f 361 MMXU3.MX.VAr.phsC.cVal.mag.f
309 MMXU2.MX.PhV.phsC.cVal.mag.f 362 MMXU3.MX.VA.phsA.cVal.mag.f
310 MMXU2.MX.PhV.phsC.cVal.ang.f 363 MMXU3.MX.VA.phsB.cVal.mag.f
311 MMXU2.MX.A.phsA.cVal.mag.f 364 MMXU3.MX.VA.phsC.cVal.mag.f
312 MMXU2.MX.A.phsA.cVal.ang.f 365 MMXU3.MX.PF.phsA.cVal.mag.f
313 MMXU2.MX.A.phsB.cVal.mag.f 366 MMXU3.MX.PF.phsB.cVal.mag.f
314 MMXU2.MX.A.phsB.cVal.ang.f 367 MMXU3.MX.PF.phsC.cVal.mag.f
315 MMXU2.MX.A.phsC.cVal.mag.f 368 MMXU4.MX.TotW.mag.f
316 MMXU2.MX.A.phsC.cVal.ang.f 369 MMXU4.MX.TotVAr.mag.f
317 MMXU2.MX.A.neut.cVal.mag.f 370 MMXU4.MX.TotVA.mag.f
318 MMXU2.MX.A.neut.cVal.ang.f 371 MMXU4.MX.TotPF.mag.f
319 MMXU2.MX.W.phsA.cVal.mag.f 372 MMXU4.MX.Hz.mag.f
320 MMXU2.MX.W.phsB.cVal.mag.f 373 MMXU4.MX.PPV.phsAB.cVal.mag.f
321 MMXU2.MX.W.phsC.cVal.mag.f 374 MMXU4.MX.PPV.phsAB.cVal.ang.f
322 MMXU2.MX.VAr.phsA.cVal.mag.f 375 MMXU4.MX.PPV.phsBC.cVal.mag.f
323 MMXU2.MX.VAr.phsB.cVal.mag.f 376 MMXU4.MX.PPV.phsBC.cVal.ang.f
324 MMXU2.MX.VAr.phsC.cVal.mag.f 377 MMXU4.MX.PPV.phsCA.cVal.mag.f
325 MMXU2.MX.VA.phsA.cVal.mag.f 378 MMXU4.MX.PPV.phsCA.cVal.ang.f
326 MMXU2.MX.VA.phsB.cVal.mag.f 379 MMXU4.MX.PhV.phsA.cVal.mag.f
327 MMXU2.MX.VA.phsC.cVal.mag.f 380 MMXU4.MX.PhV.phsA.cVal.ang.f
328 MMXU2.MX.PF.phsA.cVal.mag.f 381 MMXU4.MX.PhV.phsB.cVal.mag.f
329 MMXU2.MX.PF.phsB.cVal.mag.f 382 MMXU4.MX.PhV.phsB.cVal.ang.f
330 MMXU2.MX.PF.phsC.cVal.mag.f 383 MMXU4.MX.PhV.phsC.cVal.mag.f
331 MMXU3.MX.TotW.mag.f 384 MMXU4.MX.PhV.phsC.cVal.ang.f
332 MMXU3.MX.TotVAr.mag.f 385 MMXU4.MX.A.phsA.cVal.mag.f
333 MMXU3.MX.TotVA.mag.f 386 MMXU4.MX.A.phsA.cVal.ang.f
334 MMXU3.MX.TotPF.mag.f 387 MMXU4.MX.A.phsB.cVal.mag.f
335 MMXU3.MX.Hz.mag.f 388 MMXU4.MX.A.phsB.cVal.ang.f
336 MMXU3.MX.PPV.phsAB.cVal.mag.f 389 MMXU4.MX.A.phsC.cVal.mag.f
337 MMXU3.MX.PPV.phsAB.cVal.ang.f 390 MMXU4.MX.A.phsC.cVal.ang.f
338 MMXU3.MX.PPV.phsBC.cVal.mag.f 391 MMXU4.MX.A.neut.cVal.mag.f
339 MMXU3.MX.PPV.phsBC.cVal.ang.f 392 MMXU4.MX.A.neut.cVal.ang.f
340 MMXU3.MX.PPV.phsCA.cVal.mag.f 393 MMXU4.MX.W.phsA.cVal.mag.f
341 MMXU3.MX.PPV.phsCA.cVal.ang.f 394 MMXU4.MX.W.phsB.cVal.mag.f
342 MMXU3.MX.PhV.phsA.cVal.mag.f 395 MMXU4.MX.W.phsC.cVal.mag.f
343 MMXU3.MX.PhV.phsA.cVal.ang.f 396 MMXU4.MX.VAr.phsA.cVal.mag.f
344 MMXU3.MX.PhV.phsB.cVal.mag.f 397 MMXU4.MX.VAr.phsB.cVal.mag.f
345 MMXU3.MX.PhV.phsB.cVal.ang.f 398 MMXU4.MX.VAr.phsC.cVal.mag.f
B 516
517
GGIO5.ST.UIntIn3.stVal
GGIO5.ST.UIntIn4.q
569
570
PDIS10.ST.Str.general
PDIS10.ST.Op.general
518 GGIO5.ST.UIntIn4.stVal 571 PIOC1.ST.Str.general
519 GGIO5.ST.UIntIn5.q 572 PIOC1.ST.Op.general
520 GGIO5.ST.UIntIn5.stVal 573 PIOC2.ST.Str.general
521 GGIO5.ST.UIntIn6.q 574 PIOC2.ST.Op.general
522 GGIO5.ST.UIntIn6.stVal 575 PIOC3.ST.Str.general
523 GGIO5.ST.UIntIn7.q 576 PIOC3.ST.Op.general
524 GGIO5.ST.UIntIn7.stVal 577 PIOC4.ST.Str.general
525 GGIO5.ST.UIntIn8.q 578 PIOC4.ST.Op.general
526 GGIO5.ST.UIntIn8.stVal 579 PIOC5.ST.Str.general
527 GGIO5.ST.UIntIn9.q 580 PIOC5.ST.Op.general
528 GGIO5.ST.UIntIn9.stVal 581 PIOC6.ST.Str.general
529 GGIO5.ST.UIntIn10.q 582 PIOC6.ST.Op.general
530 GGIO5.ST.UIntIn10.stVal 583 PIOC7.ST.Str.general
531 GGIO5.ST.UIntIn11.q 584 PIOC7.ST.Op.general
532 GGIO5.ST.UIntIn11.stVal 585 PIOC8.ST.Str.general
533 GGIO5.ST.UIntIn12.q 586 PIOC8.ST.Op.general
534 GGIO5.ST.UIntIn12.stVal 587 PIOC9.ST.Str.general
535 GGIO5.ST.UIntIn13.q 588 PIOC9.ST.Op.general
536 GGIO5.ST.UIntIn13.stVal 589 PIOC10.ST.Str.general
537 GGIO5.ST.UIntIn14.q 590 PIOC10.ST.Op.general
538 GGIO5.ST.UIntIn14.stVal 591 PIOC11.ST.Str.general
539 GGIO5.ST.UIntIn15.q 592 PIOC11.ST.Op.general
540 GGIO5.ST.UIntIn15.stVal 593 PIOC12.ST.Str.general
541 GGIO5.ST.UIntIn16.q 594 PIOC12.ST.Op.general
542 GGIO5.ST.UIntIn16.stVal 595 PIOC13.ST.Str.general
543 PDIF1.ST.Str.general 596 PIOC13.ST.Op.general
544 PDIF1.ST.Op.general 597 PIOC14.ST.Str.general
545 PDIF2.ST.Str.general 598 PIOC14.ST.Op.general
546 PDIF2.ST.Op.general 599 PIOC15.ST.Str.general
547 PDIF3.ST.Str.general 600 PIOC15.ST.Op.general
548 PDIF3.ST.Op.general 601 PIOC16.ST.Str.general
549 PDIF4.ST.Str.general 602 PIOC16.ST.Op.general
550 PDIF4.ST.Op.general 603 PIOC17.ST.Str.general
551 PDIS1.ST.Str.general 604 PIOC17.ST.Op.general
552 PDIS1.ST.Op.general 605 PIOC18.ST.Str.general
553 PDIS2.ST.Str.general 606 PIOC18.ST.Op.general
554 PDIS2.ST.Op.general 607 PIOC19.ST.Str.general
555 PDIS3.ST.Str.general 608 PIOC19.ST.Op.general
556 PDIS3.ST.Op.general 609 PIOC20.ST.Str.general
557 PDIS4.ST.Str.general 610 PIOC20.ST.Op.general
B 728
729
PTOC7.ST.Op.general
PTOC8.ST.Str.general
781
782
PTOV10.ST.Str.general
PTOV10.ST.Op.general
730 PTOC8.ST.Op.general 783 PTRC1.ST.Tr.general
731 PTOC9.ST.Str.general 784 PTRC1.ST.Op.general
732 PTOC9.ST.Op.general 785 PTRC2.ST.Tr.general
733 PTOC10.ST.Str.general 786 PTRC2.ST.Op.general
734 PTOC10.ST.Op.general 787 PTRC3.ST.Tr.general
735 PTOC11.ST.Str.general 788 PTRC3.ST.Op.general
736 PTOC11.ST.Op.general 789 PTRC4.ST.Tr.general
737 PTOC12.ST.Str.general 790 PTRC4.ST.Op.general
738 PTOC12.ST.Op.general 791 PTRC5.ST.Tr.general
739 PTOC13.ST.Str.general 792 PTRC5.ST.Op.general
740 PTOC13.ST.Op.general 793 PTRC6.ST.Tr.general
741 PTOC14.ST.Str.general 794 PTRC6.ST.Op.general
742 PTOC14.ST.Op.general 795 PTUV1.ST.Str.general
743 PTOC15.ST.Str.general 796 PTUV1.ST.Op.general
744 PTOC15.ST.Op.general 797 PTUV2.ST.Str.general
745 PTOC16.ST.Str.general 798 PTUV2.ST.Op.general
746 PTOC16.ST.Op.general 799 PTUV3.ST.Str.general
747 PTOC17.ST.Str.general 800 PTUV3.ST.Op.general
748 PTOC17.ST.Op.general 801 PTUV4.ST.Str.general
749 PTOC18.ST.Str.general 802 PTUV4.ST.Op.general
750 PTOC18.ST.Op.general 803 PTUV5.ST.Str.general
751 PTOC19.ST.Str.general 804 PTUV5.ST.Op.general
752 PTOC19.ST.Op.general 805 PTUV6.ST.Str.general
753 PTOC20.ST.Str.general 806 PTUV6.ST.Op.general
754 PTOC20.ST.Op.general 807 PTUV7.ST.Str.general
755 PTOC21.ST.Str.general 808 PTUV7.ST.Op.general
756 PTOC21.ST.Op.general 809 PTUV8.ST.Str.general
757 PTOC22.ST.Str.general 810 PTUV8.ST.Op.general
758 PTOC22.ST.Op.general 811 PTUV9.ST.Str.general
759 PTOC23.ST.Str.general 812 PTUV9.ST.Op.general
760 PTOC23.ST.Op.general 813 PTUV10.ST.Str.general
761 PTOC24.ST.Str.general 814 PTUV10.ST.Op.general
762 PTOC24.ST.Op.general 815 PTUV11.ST.Str.general
763 PTOV1.ST.Str.general 816 PTUV11.ST.Op.general
764 PTOV1.ST.Op.general 817 PTUV12.ST.Str.general
765 PTOV2.ST.Str.general 818 PTUV12.ST.Op.general
766 PTOV2.ST.Op.general 819 PTUV13.ST.Str.general
767 PTOV3.ST.Str.general 820 PTUV13.ST.Op.general
768 PTOV3.ST.Op.general 821 RBRF1.ST.OpEx.general
769 PTOV4.ST.Str.general 822 RBRF1.ST.OpIn.general
B 940
941
CSWI26.ST.Pos.stVal
CSWI27.ST.Loc.stVal
991
992
XSWI22.ST.Loc.stVal
XSWI22.ST.Pos.stVal
942 CSWI27.ST.Pos.stVal 993 XSWI23.ST.Loc.stVal
943 CSWI28.ST.Loc.stVal 994 XSWI23.ST.Pos.stVal
944 CSWI28.ST.Pos.stVal 995 XSWI24.ST.Loc.stVal
945 CSWI29.ST.Loc.stVal 996 XSWI24.ST.Pos.stVal
946 CSWI29.ST.Pos.stVal 997 XCBR1.ST.Loc.stVal
947 CSWI30.ST.Loc.stVal 998 XCBR1.ST.Pos.stVal
948 CSWI30.ST.Pos.stVal 999 XCBR2.ST.Loc.stVal
949 XSWI1.ST.Loc.stVal 1000 XCBR2.ST.Pos.stVal
950 XSWI1.ST.Pos.stVal 1001 XCBR3.ST.Loc.stVal
951 XSWI2.ST.Loc.stVal 1002 XCBR3.ST.Pos.stVal
952 XSWI2.ST.Pos.stVal 1003 XCBR4.ST.Loc.stVal
953 XSWI3.ST.Loc.stVal 1004 XCBR4.ST.Pos.stVal
954 XSWI3.ST.Pos.stVal 1005 XCBR5.ST.Loc.stVal
955 XSWI4.ST.Loc.stVal 1006 XCBR5.ST.Pos.stVal
956 XSWI4.ST.Pos.stVal 1007 XCBR6.ST.Loc.stVal
957 XSWI5.ST.Loc.stVal 1008 XCBR6.ST.Pos.stVal
958 XSWI5.ST.Pos.stVal
959 XSWI6.ST.Loc.stVal
F617
960 XSWI6.ST.Pos.stVal
ENUMERATION: LOGIN ROLES
961 XSWI7.ST.Loc.stVal
962 XSWI7.ST.Pos.stVal Enumeration Role
963 XSWI8.ST.Loc.stVal 0 None
964 XSWI8.ST.Pos.stVal 1 Administrator
965 XSWI9.ST.Loc.stVal 2 Supervisor
966 XSWI9.ST.Pos.stVal 3 Engineer
967 XSWI10.ST.Loc.stVal 4 Operator
968 XSWI10.ST.Pos.stVal 5 Factory
969 XSWI11.ST.Loc.stVal
970 XSWI11.ST.Pos.stVal
F620
971 XSWI12.ST.Loc.stVal ENUMERATION: PASSWORD CHANGE ROLES
972 XSWI12.ST.Pos.stVal
973 XSWI13.ST.Loc.stVal Enumeration Role
979 XSWI16.ST.Loc.stVal
F621 F625
ENUMERATION: MODBUS LOGIN ROLES ENUMERATION: PTP STATE
Enumeration Item
F624
0 Disabled
ENUMERATION: RTC SYNCHRONZING SOURCE ACTUALS
1 Local and Remote
Enumeration Item 2 Local
0 None 3 Remote
1 Port 1 PTP Clock
2 Port 2 PTP Clock
3 Port 3 PTP Clock
4 IRIG-B
5 SNTP
The IEC 61850 standard is the result of electric utilities and vendors of electronic equipment to produce standardized com-
munications systems. IEC 61850 is a series of standards describing client/server and peer-to-peer communications, sub-
station design and configuration, testing, environmental and project standards. The complete set includes:
• IEC 61850-1: Introduction and overview
• IEC 61850-2: Glossary
• IEC 61850-3: General requirements
• IEC 61850-4: System and project management
• IEC 61850-5: Communications and requirements for functions and device models
•
•
IEC 61850-6: Configuration description language for communication in electrical substations related to IEDs
IEC 61850-7-1: Basic communication structure for substation and feeder equipment - Principles and models
C
• IEC 61850-7-2: Basic communication structure for substation and feeder equipment - Abstract communication service
interface (ACSI)
• IEC 61850-7-3: Basic communication structure for substation and feeder equipment – Common data classes
• IEC 61850-7-4: Basic communication structure for substation and feeder equipment – Compatible logical node classes
and data classes
• IEC 61850-8-1: Specific Communication Service Mapping (SCSM) – Mappings to MMS (ISO 9506-1 and ISO 9506-2)
and to ISO/IEC 8802-3
• IEC 61850-9-1: Specific Communication Service Mapping (SCSM) – Sampled values over serial unidirectional multi-
drop point to point link
• IEC 61850-9-2: Specific Communication Service Mapping (SCSM) – Sampled values over ISO/IEC 8802-3
• IEC 61850-10: Conformance testing
These documents can be obtained from the IEC (http://www.iec.ch). It is strongly recommended that all those involved with
any IEC 61850 implementation obtain this document set.
IEC 61850 specifies the use of the Manufacturing Message Specification (MMS) at the upper (application) layer for transfer
of real-time data. This protocol has been in existence for several of years and provides a set of services suitable for the
transfer of data within a substation LAN environment. Actual MMS protocol services are mapped to IEC 61850 abstract ser-
vices in IEC 61850-8-1.
The D60 relay supports IEC 61850 server services over TCP/IP. The TCP/IP profile requires the D60 to have an IP address
to establish communications. These addresses are located in the SETTINGS PRODUCT SETUP COMMUNICATIONS
NETWORK menu. It is possible to have up to five simultaneous connections (in addition to DNP and Modbus/TCP (non-IEC
61850) connections).
• Client/server: This is a connection-oriented type of communication. The connection is initiated by the client, and com-
munication activity is controlled by the client. IEC 61850 clients are often substation computers running HMI programs
or SOE logging software. Servers are usually substation equipment such as protection relays, meters, RTUs, trans-
former tap changers, or bay controllers.
• Peer-to-peer: This is a non-connection-oriented, high speed type of communication usually between substation equip-
ment such as protection relays. GSSE and GOOSE are methods of peer-to-peer communication.
• Substation configuration language (SCL): A substation configuration language is a number of files used to describe
the configuration of substation equipment. Each configured device has an IEC Capability Description (ICD) file. The
substation single line information is stored in a System Specification Description (SSD) file. The entire substation con-
figuration is stored in a Substation Configuration Description (SCD) file. The SCD file is the combination of the individ-
ual ICD files and the SSD file.
IEC 61850 defines an object-oriented approach to data and services. An IEC 61850 physical device can contain one or
more logical device(s). Each logical device can contain many logical nodes. Each logical node can contain many data
objects. Each data object is composed of data attributes and data attribute components. Services are available at each
level for performing various functions, such as reading, writing, control commands, and reporting.
Each D60 IED represents one IEC 61850 physical device. The physical device contains one logical device, and the logical
device contains many logical nodes. The logical node LPHD1 contains information about the D60 IED physical device. The
logical node LLN0 contains information about the D60 IED logical device.
C The GGIO1 logical node is available in the D60 to provide access to as many 128 digital status points and associated time-
stamps and quality flags. The data content must be configured before the data can be used. GGIO1 provides digital status
points for access by clients.
It is intended that clients use GGIO1 in order to access digital status values from the D60. Configuration settings are pro-
vided to allow the selection of the number of digital status indications available in GGIO1 (8 to 128), and to allow the choice
of the D60 FlexLogic operands that drive the status of the GGIO1 status indications. Clients can utilize the IEC 61850 buff-
ered and unbuffered reporting features available from GGIO1 in order to build sequence of events (SOE) logs and HMI dis-
play screens. Buffered reporting should generally be used for SOE logs since the buffering capability reduces the chances
of missing data state changes. Unbuffered reporting should generally be used for local status display.
The GGIO2 logical node is available to provide access to the D60 virtual inputs. Virtual inputs are single-point control
(binary) values that can be written by clients. They are generally used as control inputs. GGIO2 provides access to the vir-
tual inputs through the IEC 61850 standard control model (ctlModel) services:
• Status only.
• Direct control with normal security.
• SBO control with normal security.
Configuration settings are available to select the control model for each point. Each virtual input used through GGIO2
should have its VIRTUAL INPUT 1(64) FUNCTION setting programmed as “Enabled” and its corresponding GGIO2 CF SPSCO1(64)
CTLMODEL setting programmed to the appropriate control configuration.
C.2.4 GGIO3: DIGITAL STATUS AND ANALOG VALUES FROM GOOSE DATA
The GGIO3 logical node is available to provide access for clients to values received via configurable GOOSE messages.
The values of the digital status indications and analog values in GGIO3 originate in GOOSE messages sent from other
devices.
The GGIO4 logical node provides access to as many as 32 analog value points, as well as associated timestamps and
quality flags. The data content must be configured before the data can be used. GGIO4 provides analog values for access
by clients.
It is intended that clients use GGIO4 to access generic analog values from the D60. Configuration settings allow the selec-
tion of the number of analog values available in GGIO4 (4 to 32) and the choice of the FlexAnalog values that determine
the value of the GGIO4 analog inputs. Clients can utilize polling or the IEC 61850 unbuffered reporting feature available
from GGIO4 in order to obtain the analog values provided by GGIO4.
A limited number of measured analog values are available through the MMXU logical nodes.
Each MMXU logical node provides data from a D60 current and voltage source. There is one MMXU available for each
configurable source (programmed in the SETTINGS SYSTEM SETUP SIGNAL SOURCES menu). MMXU1 provides data
from D60 source 1, and MMXU2 provides data from D60 source 2.
MMXU data is provided in two forms: instantaneous and deadband. The instantaneous values are updated every time a
read operation is performed by a client. The deadband values are calculated as described in IEC 61850 parts 7-1 and 7-3.
The selection of appropriate deadband settings for the D60 is described in chapter 5 of this manual.
IEC 61850 buffered and unbuffered reporting capability is available in all MMXU logical nodes. MMXUx logical nodes pro-
vide the following data for each source:
•
•
MMXU1.MX.TotW: three-phase real power
MMXU1.MX.TotVAr: three-phase reactive power
C
• MMXU1.MX.TotVA: three-phase apparent power
• MMXU1.MX.TotPF: three-phase power factor
• MMXU1.MX.Hz: frequency
• MMXU1.MX.PPV.phsAB: phase AB voltage magnitude and angle
• MMXU1.MX.PPV.phsBC: phase BC voltage magnitude and angle
• MMXU1.MX.PPV.phsCA: Phase CA voltage magnitude and angle
• MMXU1.MX.PhV.phsA: phase AG voltage magnitude and angle
• MMXU1.MX.PhV.phsB: phase BG voltage magnitude and angle
• MMXU1.MX.PhV.phsC: phase CG voltage magnitude and angle
• MMXU1.MX.A.phsA: phase A current magnitude and angle
• MMXU1.MX.A.phsB: phase B current magnitude and angle
• MMXU1.MX.A.phsC: phase C current magnitude and angle
• MMXU1.MX.A.neut: ground current magnitude and angle
• MMXU1.MX.W.phsA: phase A real power
• MMXU1.MX.W.phsB: phase B real power
• MMXU1.MX.W.phsC: phase C real power
• MMXU1.MX.VAr.phsA: phase A reactive power
• MMXU1.MX.VAr.phsB: phase B reactive power
• MMXU1.MX.VAr.phsC: phase C reactive power
• MMXU1.MX.VA.phsA: phase A apparent power
• MMXU1.MX.VA.phsB: phase B apparent power
• MMXU1.MX.VA.phsC: phase C apparent power
• MMXU1.MX.PF.phsA: phase A power factor
• MMXU1.MX.PF.phsB: phase B power factor
• MMXU1.MX.PF.phsC: phase C power factor
The following list describes the protection elements for all UR-series relays. The D60 relay will contain a subset of protec-
tion elements from this list.
• PDIF: bus differential, transformer instantaneous differential, transformer percent differential, current differential
IEC 61850 buffered and unbuffered reporting is provided in the GGIO1 logical nodes (for binary status values) and MMXU1
to MMXU6 (for analog measured values). Report settings can be configured using the EnerVista UR Setup software, sub-
station configurator software, or via an IEC 61850 client. The following items can be configured:
• TrgOps: Trigger options. The following bits are supported by the D60:
– Bit 1: data-change
– Bit 4: integrity
– Bit 5: general interrogation
• OptFlds: Option Fields. The following bits are supported by the D60:
–
–
Bit 1: sequence-number
Bit 2: report-time-stamp
C
– Bit 3: reason-for-inclusion
– Bit 4: data-set-name
– Bit 5: data-reference
– Bit 6: buffer-overflow (for buffered reports only)
– Bit 7: entryID (for buffered reports only)
– Bit 8: conf-revision
– Bit 9: segmentation
• IntgPd: Integrity period.
• BufTm: Buffer time.
MMS file services are supported to allow transfer of oscillography, event record, or other files from a D60 relay.
The timestamp values associated with all IEC 61850 data items represent the time of the last change of either the value or
quality flags of the data item. To accomplish this functionality, all IEC 61850 data items must be regularly scanned for data
changes, and the timestamp updated when a change is detected, regardless of the connection status of any IEC 61850 cli-
ents. For applications where there is no IEC 61850 client in use, the IEC 61850 SERVER SCANNING setting can be pro-
grammed as “Disabled”. If a client is in use, this setting should be programmed as “Enabled” to ensure the proper
generation of IEC 61850 timestamps.
The logical device name is used to identify the IEC 61850 logical device that exists within the D60. This name is composed
of two parts: the IED name setting and the logical device instance. The complete logical device name is the combination of
the two character strings programmed in the IEDNAME and LD INST settings. The default values for these strings are “IED-
Name” and “LDInst”. These values should be changed to reflect a logical naming convention for all IEC 61850 logical
devices in the system.
C.3.5 LOCATION
The LPHD1 logical node contains a data attribute called location (LPHD1.DC.PhyNam.location). This is a character string
meant to describe the physical location of the D60. This attribute is programmed through the LOCATION setting and its
default value is “Location”. This value should be changed to describe the actual physical location of the D60.
IEC 61850 specifies that each logical node can have a name with a total length of 11 characters. The name is composed of:
• A five or six-character name prefix.
• A four-character standard name (for example, MMXU, GGIO, PIOC, etc.).
• A one or two-character instantiation index.
Complete names are of the form xxxxxxPIOC1, where the xxxxxx character string is configurable. Details regarding the
logical node naming rules are given in IEC 61850 parts 6 and 7-2. It is recommended that a consistent naming convention
be used for an entire substation project.
C A built-in TCP/IP connection timeout of two minutes is employed by the D60 to detect ‘dead’ connections. If there is no data
traffic on a TCP connection for greater than two minutes, the connection will be aborted by the D60. This frees up the con-
nection to be used by other clients. Therefore, when using IEC 61850 reporting, clients should configure report control
block items such that an integrity report will be issued at least every 2 minutes (120000 ms). This ensures that the D60 will
not abort the connection. If other MMS data is being polled on the same connection at least once every 2 minutes, this
timeout will not apply.
The D60 relay makes available a number of non-IEC 61850 data items. These data items can be accessed through the
“UR” MMS domain. IEC 61850 data can be accessed through the standard IEC 61850 logical device. To access the non-
IEC data items, the INCLUDE NON-IEC DATA setting must be “Enabled”.
The exact structure and values of the supported IEC 61850 logical nodes can be seen by connecting to a D60 relay with an
MMS browser, such as the “MMS Object Explorer and AXS4-MMS” DDE/OPC server from Sisco Inc.
IEC 61850 specifies two types of peer-to-peer data transfer services: Generic Substation State Events (GSSE) and Generic
Object Oriented Substation Events (GOOSE). GSSE services are compatible with UCA 2.0 GOOSE. IEC 61850 GOOSE
services provide virtual LAN (VLAN) support, Ethernet priority tagging, and Ethertype Application ID configuration. The sup-
port for VLANs and priority tagging allows for the optimization of Ethernet network traffic. GOOSE messages can be given
a higher priority than standard Ethernet traffic, and they can be separated onto specific VLANs. Because of the additional
features of GOOSE services versus GSSE services, it is recommended that GOOSE be used wherever backwards com-
patibility with GSSE (or UCA 2.0 GOOSE) is not required.
Devices that transmit GSSE and/or GOOSE messages also function as servers. Each GSSE publisher contains a “GSSE
control block” to configure and control the transmission. Each GOOSE publisher contains a “GOOSE control block” to con-
figure and control the transmission. The transmission is also controlled via device settings. These settings can be seen in
the ICD and/or SCD files, or in the device configuration software or files.
IEC 61850 recommends a default priority value of 4 for GOOSE. Ethernet traffic that does not contain a priority tag has a
C
default priority of 1. More details are specified in IEC 61850 part 8-1.
IEC 61850 recommends that the Ethertype Application ID number be configured according to the GOOSE source. In the
D60, the transmitted GOOSE Application ID number must match the configured receive Application ID number in the
receiver. A common number may be used for all GOOSE transmitters in a system. More details are specified in IEC 61850
part 8-1.
IEC 61850 Generic Substation Status Event (GSSE) communication is compatible with UCA GOOSE communication.
GSSE messages contain a number of double point status data items. These items are transmitted in two pre-defined data
structures named DNA and UserSt. Each DNA and UserSt item is referred to as a ‘bit pair’. GSSE messages are transmit-
ted in response to state changes in any of the data points contained in the message. GSSE messages always contain the
same number of DNA and UserSt bit pairs. Depending the on the configuration, only some of these bit pairs may have val-
ues that are of interest to receiving devices.
The GSSE FUNCTION, GSSE ID, and GSSE DESTINATION MAC ADDRESS settings are used to configure GSSE transmission.
GSSE FUNCTION is set to “Enabled” to enable the transmission. If a valid multicast Ethernet MAC address is entered for the
GSSE DESTINATION MAC ADDRESS setting, this address will be used as the destination MAC address for GSSE messages. If
a valid multicast Ethernet MAC address is not entered (for example, 00 00 00 00 00 00), the D60 will use the source Ether-
net MAC address as the destination, with the multicast bit set.
The D60 supports two types of IEC 61850 Generic Object Oriented Substation Event (GOOSE) communication: fixed
GOOSE and configurable GOOSE. All GOOSE messages contain IEC 61850 data collected into a dataset. It is this dataset
that is transferred using GOOSE message services. The dataset transferred using the D60 fixed GOOSE is the same data
that is transferred using the GSSE feature; that is, the DNA and UserSt bit pairs. The FlexLogic operands that determine
the state of the DNA and UserSt bit pairs are configurable via settings, but the fixed GOOSE dataset always contains the
same DNA/UserSt data structure. Upgrading from GSSE to GOOSE services is simply a matter of enabling fixed GOOSE
and disabling GSSE. The remote inputs and outputs are configured in the same manner for both GSSE and fixed GOOSE.
It is recommended that the fixed GOOSE be used for implementations that require GOOSE data transfer between UR-
series IEDs. Configurable GOOSE may be used for implementations that require GOOSE data transfer between UR-series
IEDs and devices from other manufacturers.
The configurable GOOSE feature allows for the configuration of the datasets to be transmitted or received from the D60.
The D60 supports the configuration of eight (8) transmission and reception datasets, allowing for the optimization of data
transfer between devices.
Items programmed for dataset 1 and 2 will have changes in their status transmitted as soon as the change is detected.
Dataset 1 should be used for high-speed transmission of data that is required for applications such as transfer tripping,
blocking, and breaker fail initiate. At least one digital status value needs to be configured in dataset 1 to enable transmis-
sion of all data configured for dataset 1. Configuring analog data only to dataset 1 will not activate transmission.
Items programmed for datasets 3 through 8 will have changes in their status transmitted at a maximum rate of every
100 ms. Datasets 3 through 8 will regularly analyze each data item configured within them every 100 ms to identify if any
changes have been made. If any changes in the data items are detected, these changes will be transmitted through a
GOOSE message. If there are no changes detected during this 100 ms period, no GOOSE message will be sent.
For all datasets 1 through 8, the integrity GOOSE message will still continue to be sent at the pre-configured rate even if no
changes in the data items are detected.
The GOOSE functionality was enhanced to prevent the relay from flooding a communications network with GOOSE mes-
sages due to an oscillation being created that is triggering a message.
C The D60 has the ability of detecting if a data item in one of the GOOSE datasets is erroneously oscillating. This can be
caused by events such as errors in logic programming, inputs improperly being asserted and de-asserted, or failed station
components. If erroneously oscillation is detected, the D60 will stop sending GOOSE messages from the dataset for a min-
imum period of one second. Should the oscillation persist after the one second time-out period, the D60 will continue to
block transmission of the dataset. The D60 will assert the MAINTENANCE ALERT: GGIO Ind XXX oscill self-test error mes-
sage on the front panel display, where XXX denotes the data item detected as oscillating.
The configurable GOOSE feature is recommended for applications that require GOOSE data transfer between UR-series
IEDs and devices from other manufacturers. Fixed GOOSE is recommended for applications that require GOOSE data
transfer between UR-series IEDs.
IEC 61850 GOOSE messaging contains a number of configurable parameters, all of which must be correct to achieve the
successful transfer of data. It is critical that the configured datasets at the transmission and reception devices are an exact
match in terms of data structure, and that the GOOSE addresses and name strings match exactly. Manual configuration is
possible, but third-party substation configuration software may be used to automate the process. The EnerVista UR Set-
upsoftware can produce IEC 61850 ICD files and import IEC 61850 SCD files produced by a substation configurator (refer
to the IEC 61850 IED configuration section later in this appendix).
Use independent ports for IEC 61850 communication and take care when configuring the settings,
else loss of protection or misoperation of the relay can result.
The following example illustrates the configuration required to transfer IEC 61850 data items between two devices. The
general steps required for transmission configuration are:
1. Configure the transmission dataset.
2. Configure the GOOSE service settings.
3. Configure the data.
The general steps required for reception configuration are:
1. Configure the reception dataset.
2. Configure the GOOSE service settings.
3. Configure the data.
This example shows how to configure the transmission and reception of three IEC 61850 data items: a single point status
value, its associated quality flags, and a floating point analog value.
The following procedure illustrates the transmission configuration.
1. Configure the transmission dataset by making the following changes in the PRODUCT SETUP COMMUNICATION
IEC 61850 PROTOCOL GSSE/GOOSE CONFIGURATION TRANSMISSION CONFIGURABLE GOOSE CONFIGURABLE
GOOSE 1 CONFIG GSE 1 DATASET ITEMS settings menu:
– Set ITEM 1 to “GGIO1.ST.Ind1.q” to indicate quality flags for GGIO1 status indication 1.
– Set ITEM 2 to “GGIO1.ST.Ind1.stVal” to indicate the status value for GGIO1 status indication 1.
The transmission dataset now contains a set of quality flags and a single point status Boolean value. The reception
dataset on the receiving device must exactly match this structure.
2. Configure the GOOSE service settings by making the following changes in the PRODUCT SETUP COMMUNICATION
IEC 61850 PROTOCOL GSSE/GOOSE CONFIGURATION TRANSMISSION CONFIGURABLE GOOSE CONFIGU-
RABLE GOOSE 1 settings menu:
– Set ITEM 1 to “GGIO3.ST.Ind1.q” to indicate quality flags for GGIO3 status indication 1.
– Set ITEM 2 to “GGIO3.ST.Ind1.stVal” to indicate the status value for GGIO3 status indication 1.
The reception dataset now contains a set of quality flags, a single point status Boolean value, and a floating point ana-
log value. This matches the transmission dataset configuration above.
2. Configure the GOOSE service settings by making the following changes in the INPUTS/OUTPUTS REMOTE DEVICES
REMOTE DEVICE 1 settings menu:
– Set REMOTE DEVICE 1 ID to match the GOOSE ID string for the transmitting device. Enter “GOOSEOut_1”.
– Set REMOTE DEVICE 1 ETYPE APPID to match the Ethertype application ID from the transmitting device. This is “0” in
the example above.
– Set the REMOTE DEVICE 1 DATASET value. This value represents the dataset number in use. Since we are using
configurable GOOSE 1 in this example, program this value as “GOOSEIn 1”.
3. Configure the data by making the following changes in the INPUTS/OUTPUTS REMOTE INPUTS REMOTE INPUT 1
settings menu:
– Set REMOTE IN 1 DEVICE to “GOOSEOut_1”.
– Set REMOTE IN 1 ITEM to “Dataset Item 2”. This assigns the value of the GGIO3.ST.Ind1.stVal single point status
item to remote input 1.
Remote input 1 can now be used in FlexLogic equations or other settings. The D60 must be rebooted (control power
removed and re-applied) before these settings take effect.
The value of remote input 1 (Boolean on or off) in the receiving device will be determined by the GGIO1.ST.Ind1.stVal value
in the sending device. The above settings will be automatically populated by the EnerVista UR Setup software when a com-
plete SCD file is created by third party substation configurator software.
Ethernet capable devices each contain a unique identifying address called a Media Access Control (MAC) address. This
address cannot be changed and is unique for each Ethernet device produced worldwide. The address is six bytes in length
and is usually represented as six hexadecimal values (for example, 00 A0 F4 01 02 03). It is used in all Ethernet frames as
the ‘source’ address of the frame. Each Ethernet frame also contains a destination address. The destination address can
be different for each Ethernet frame depending on the intended destination of the frame.
A special type of destination address called a multicast address is used when the Ethernet frame can be received by more
than one device. An Ethernet MAC address is multicast when the least significant bit of the first byte is set (for example, 01
00 00 00 00 00 is a multicast address).
GSSE and GOOSE messages must have multicast destination MAC addresses.
By default, the D60 is configured to use an automated multicast MAC scheme. If the D60 destination MAC address setting
C is not a valid multicast address (that is, the least significant bit of the first byte is not set), the address used as the destina-
tion MAC will be the same as the local MAC address, but with the multicast bit set. Thus, if the local MAC address is 00 A0
F4 01 02 03, then the destination MAC address will be 01 A0 F4 01 02 03.
GSSE messages contain an identifier string used by receiving devices to identify the sender of the message, defined in IEC
61850 part 8-1 as GsID. This is a programmable 65-character string. This string should be chosen to provide a descriptive
name of the originator of the GSSE message.
GOOSE messages contain an identifier string used by receiving devices to identify the sender of the message, defined in
IEC 61850 part 8-1 as GoID. This programmable 65-character string should be a descriptive name of the originator of the
GOOSE message. GOOSE messages also contain two additional character strings used for identification of the message:
DatSet - the name of the associated dataset, and GoCBRef - the reference (name) of the associated GOOSE control block.
These strings are automatically populated and interpreted by the D60; no settings are required.
The D60 can be configured for IEC 61850 via the EnerVista UR Setup software as follows.
1. An ICD file is generated for the D60 by the EnerVista UR Setup software that describe the capabilities of the IED.
2. The ICD file is then imported into a system configurator along with other ICD files for other IEDs (from GE or other ven-
dors) for system configuration.
3. The result is saved to a SCD file, which is then imported back to EnerVista UR Setup to create one or more settings
file(s). The settings file(s) can then be used to update the relay(s) with the new configuration information.
The configuration process is illustrated below.
Before creating an ICD file, the user can customize the IEC 61850 related settings for the IED. For example, the IED name
and logical device instance can be specified to uniquely identify the IED within the substation, or transmission GOOSE
datasets created so that the system configurator can configure the cross-communication links to send GOOSE messages
from the IED. Once the IEC 61850 settings are configured, the ICD creation process will recognize the changes and gener-
ate an ICD file that contains the updated settings.
Some of the IED settings will be modified during they system configuration process. For example, a new IP address may be
assigned, line items in a Transmission GOOSE dataset may be added or deleted, or prefixes of some logical nodes may be
changed. While all new configurations will be mapped to the D60 settings file when importing an SCD file, all unchanged
settings will preserve the same values in the new settings file.
These settings can be configured either directly through the relay panel or through the EnerVista UR Setup software (pre-
ferred method). The full list of IEC 61850 related settings for are as follows:
• Network configuration: IP address, IP subnet mask, and default gateway IP address (access through the Settings >
Product Setup > Communications > Network menu tree in EnerVista UR Setup).
• Server configuration: IED name and logical device instance (access through the Settings > Product Setup > Com-
munications > IEC 61850 > Server Configuration menu tree in EnerVista UR Setup).
• Logical node prefixes, which includes prefixes for all logical nodes except LLN0 (access through the Settings > Prod-
uct Setup > Communications > IEC 61850 > Logical Node Prefixes menu tree in EnerVista UR Setup).
• MMXU deadbands, which includes deadbands for all available MMXUs. The number of MMXUs is related to the num-
ber of CT/VT modules in the relay. There are two MMXUs for each CT/VT module. For example, if a relay contains two
CT/VT modules, there will be four MMXUs available (access through the Settings > Product Setup > Communica-
tions > IEC 61850 > MMXU Deadbands menu tree in EnerVista UR Setup).
• GGIO1 status configuration, which includes the number of status points in GGIO1 as well as the potential internal map-
pings for each GGIO1 indication. However only the number of status points will be used in the ICD creation process
(access through the Settings > Product Setup > Communications > IEC 61850 > GGIO1 Status Configuration
menu tree in EnerVista UR Setup).
• GGIO2 control configuration, which includes ctlModels for all SPCSOs within GGIO2 (access through the Settings >
Product Setup > Communications > IEC 61850 > GGIO2 Control Configuration menu tree in EnerVista UR
Setup).
• Configurable transmission GOOSE, which includes eight configurable datasets that can be used for GOOSE transmis-
sion. The GOOSE ID can be specified for each dataset (it must be unique within the IED as well as across the whole
substation), as well as the destination MAC address, VLAN priority, VLAN ID, ETYPE APPID, and the dataset items.
C
The selection of the dataset item is restricted by firmware version; for version 7.1x, only GGIO1.ST.Indx.stVal and
GGIO1.ST.Indx.q are valid selection (where x is between 1 to N, and N is determined by number of GGIO1 status
points). Although configurable transmission GOOSE can also be created and altered by some third-party system con-
figurators, we recommend configuring transmission GOOSE for GE Multilin IEDs before creating the ICD, and strictly
within EnerVista UR Setup software or the front panel display (access through the Settings > Product Setup > Com-
munications > IEC 61850 > GSSE/GOOSE Configuration > Transmission > Tx Configurable GOOSE menu tree
in EnerVista UR Setup).
• Configurable reception GOOSE, which includes eight configurable datasets that can be used for GOOSE reception.
However, unlike datasets for transmission, datasets for reception only contains dataset items, and they are usually cre-
ated automatically by process of importing the SCD file (access through the Settings > Product Setup > Communi-
cations > IEC 61850 > GSSE/GOOSE Configuration > Reception > Rx Configurable GOOSE menu tree in
EnerVista UR Setup).
• Remote devices configuration, which includes remote device ID (GOOSE ID or GoID of the incoming transmission
GOOSE dataset), ETYPE APPID (of the GSE communication block for the incoming transmission GOOSE), and
DATASET (which is the name of the associated reception GOOSE dataset). These settings are usually done automat-
ically by process of importing SCD file (access through the Settings > Inputs/Outputs > Remote Devices menu tree
in EnerVista UR Setup).
• Remote inputs configuration, which includes device (remote device ID) and item (which dataset item in the associated
reception GOOSE dataset to map) values. Only the items with cross-communication link created in SCD file should be
mapped. These configurations are usually done automatically by process of importing SCD file (access through the
Settings > Inputs/Outputs > Remote Inputs menu tree in EnerVista UR Setup).
The SCL language is based on XML, and its syntax definition is described as a W3C XML Schema. ICD is one type of SCL
file (which also includes SSD, CID and SCD files). The ICD file describes the capabilities of an IED and consists of four
major sections:
• Header
• Communication
• IEDs
• DataTypeTemplates
SCL
Communication
DataTypeTemplates
842795A1.CDR
Communication
SubNetwork (name)
Address
P (type)
Text
Other P elements
Address
P (type)
Text
Services
AccessPoint (name)
Server
Authentication (none) C
LDevice (inst)
DataSet (name)
DOI (name)
DataSet (name)
DOI (name)
The DataTypeTemplates node defines instantiable logical node types. A logical node type is an instantiable template of the
data of a logical node. A LnodeType is referenced each time that this instantiable type is needed with an IED. A logical
node type template is built from DATA (DO) elements, which again have a DO type, which is derived from the DATA classes
(CDC). DOs consist of attributes (DA) or of elements of already defined DO types (SDO). The attribute (DA) has a func-
tional constraint, and can either have a basic type, be an enumeration, or a structure of a DAType. The DAType is built from
BDA elements, defining the structure elements, which again can be BDA elements of have a base type such as DA.
DataTypeTemplates
DO (name, type)
Other DO elements
DAType (id)
EnumType (id)
An ICD file can be created directly from a connected D60 IED or from an offline D60 settings file with the EnerVista UR
Setup software using the following procedure:
1. Right-click the connected UR-series relay or settings file and select Create ICD File.
2. The EnerVista UR Setup will prompt to save the file. Select the file path and enter the name for the ICD file, then click
OK to generate the file.
The time to create an ICD file from the offline D60 settings file is typically much quicker than create an ICD file directly from
the relay.
System configuration is performed in the system configurator. While many vendors (including GE Multilin) are working their
own system configuration tools, there are some system configurators available in the market (for example, Siemens DIGSI
version 4.6 or above and ASE Visual SCL Beta 0.12).
Although the configuration tools vary from one vendor to another, the procedure is pretty much the same. First, a substation
project must be created, either as an empty template or with some system information by importing a system specification
file (SSD). Then, IEDs are added to the substation. Since each IED is represented by its associated ICD, the ICD files are
imported into the substation project, and the system configurator validates the ICD files during the importing process. If the
ICD files are successfully imported into the substation project, it may be necessary to perform some additional minor steps
to attach the IEDs to the substation (see the system configurator manual for details).
Once all IEDs are inserted into the substation, further configuration is possible, such as:
• Assigning network addresses to individual IEDs.
• Customizing the prefixes of logical nodes.
• Creating cross-communication links (configuring GOOSE messages to send from one IED to others).
When system configurations are complete, the results are saved to an SCD file, which contains not only the configuration
for each IED in the substation, but also the system configuration for the entire substation. Finally, the SCD file is passed
back to the IED configurator (vendor specific tool) to update the new configuration into the IED.
The SCD file consists of at least five major sections:
• Header.
• Substation.
• Communication.
• IED section (one or more).
• DataTypeTemplates.
The root file structure of an SCD file is illustrated below.
SCL
C Substation
Communication
DataTypeTemplates
842791A1.CDR
Substation
PowerSystemResource
GeneralEquipment
EquipmentContainer
VoltageLevel Bay
Voltage
PowerSystemResource
Function SubFunction
GeneralEquipment
842792A1.CDR
The Communication node describes the direct communication connection possibilities between logical nodes by means of
logical buses (sub-networks) and IED access ports. The communication section is structured as follows.
Communication
SubNetwork (name)
ConnectedAP (IED 1)
Address
P (type)
Text
Other P elements
P (type)
Other P elements
ConnectedAP (IED 2)
Address
P (type)
Text
Other P elements
Address
P (type)
Text
Other P elements
Other GSE elements
AccessPoint (name)
Server
Authentication (none)
LDevice (inst)
DataSet elements
C ReportControl elements
DOI elements
Inputs
GSEControl elements
842794A1.CDR
The following procedure describes how to update the D60 with the new configuration from an SCD file with the EnerVista
UR Setup software.
1. Right-click anywhere in the files panel and select the Import Contents From SCD File item.
3. The software will open the SCD file and then prompt the user to save a UR-series settings file. Select a location and
name for the URS (UR-series relay settings) file.
If there is more than one GE Multilin IED defined in the SCD file, the software prompt the user to save a UR-series set-
tings file for each IED.
4. After the URS file is created, modify any settings (if required).
5. To update the relay with the new settings, right-click on the settings file in the settings tree and select the Write Set-
tings File to Device item.
6. The software will prompt for the target device. Select the target device from the list provided and click Send. The new
settings will be updated to the selected device.
c1: shall be "M" if support for LOGICAL-DEVICE model has been declared
O: Optional
NOTE M: Mandatory
c2: shall be "M" if support for LOGICAL-NODE model has been declared
c3: shall be "M" if support for DATA model has been declared
NOTE c4: shall be "M" if support for DATA-SET, Substitution, Report, Log Control, or Time models has been declared
c5: shall be "M" if support for Report, GSE, or SMV models has been declared
M: Mandatory
In the table below, the acronym AA refers to Application Associations (TP: Two Party / MC: Multicast). The c6 to c10 entries
are defined in the notes following the table.
The UR-series of relays supports IEC 61850 logical nodes as indicated in the following table. Note that the actual instantia-
tion of each logical node is determined by the product order code. For example. the logical node “PDIS” (distance protec-
tion) is available only in the D60 Line Distance Relay.
This document is adapted from the IEC 60870-5-104 standard. For this section the boxes indicate the following: – used
in standard direction; – not used; – cannot be selected in IEC 60870-5-104 standard.
1. SYSTEM OR DEVICE:
System Definition
Controlling Station Definition (Master)
Controlled Station Definition (Slave)
2. NETWORK CONFIGURATION:
Point-to-Point Multipoint
Multiple Point-to-Point Multipoint Star
3. PHYSICAL LAYER
Transmission Speed (control direction):
Unbalanced Interchange Unbalanced Interchange Balanced Interchange Circuit
Circuit V.24/V.28 Standard: Circuit V.24/V.28 Recommended X.24/X.27:
if >1200 bits/s: D
100 bits/sec. 2400 bits/sec. 2400 bits/sec.
200 bits/sec. 4800 bits/sec. 4800 bits/sec.
300 bits/sec. 9600 bits/sec. 9600 bits/sec.
600 bits/sec. 19200 bits/sec.
1200 bits/sec. 38400 bits/sec.
56000 bits/sec.
64000 bits/sec.
Transmission Speed (monitor direction):
Unbalanced Interchange Unbalanced Interchange Balanced Interchange Circuit
Circuit V.24/V.28 Standard: Circuit V.24/V.28 Recommended X.24/X.27:
if >1200 bits/s:
100 bits/sec. 2400 bits/sec. 2400 bits/sec.
200 bits/sec. 4800 bits/sec. 4800 bits/sec.
300 bits/sec. 9600 bits/sec. 9600 bits/sec.
600 bits/sec. 19200 bits/sec.
1200 bits/sec. 38400 bits/sec.
56000 bits/sec.
64000 bits/sec.
4. LINK LAYER
Link Transmission Procedure: Address Field of the Link:
Balanced Transmission Not Present (Balanced Transmission Only)
Unbalanced Transmission One Octet
Two Octets
Structured
Unstructured
Frame Length (maximum length, number of octets): Not selectable in companion IEC 60870-5-104 standard
When using an unbalanced link layer, the following ADSU types are returned in class 2 messages (low priority) with the
indicated causes of transmission:
The standard assignment of ADSUs to class 2 messages is used as follows:
5. APPLICATION LAYER
Transmission Mode for Application Data:
Mode 1 (least significant octet first), as defined in Clause 4.10 of IEC 60870-5-4, is used exclusively in this companion
standard.
Common Address of ADSU:
One Octet
Two Octets
Information Object Address:
One Octet Structured
Either the ASDUs of the set <2>, <4>, <6>, <8>, <10>, <12>, <14>, <16>, <17>, <18>, and <19> or of the set
<30> to <40> are used.
Process information in control direction
<45> := Single command C_SC_NA_1
D
<46> := Double command C_DC_NA_1
<47> := Regulating step command C_RC_NA_1
<48> := Set point command, normalized value C_SE_NA_1
<49> := Set point command, scaled value C_SE_NB_1
<50> := Set point command, short floating point value C_SE_NC_1
<51> := Bitstring of 32 bits C_BO_NA_1
Either the ASDUs of the set <45> to <51> or of the set <58> to <64> are used.
System information in monitor direction
<70> := End of initialization M_EI_NA_1
File transfer
<120> := File Ready F_FR_NA_1
<121> := Section Ready F_SR_NA_1
<122> := Call directory, select file, call file, call section F_SC_NA_1
<123> := Last section, last segment F_LS_NA_1
<124> := Ack file, ack section F_AF_NA_1
<125> := Segment F_SG_NA_1
<126> := Directory (blank or X, available only in monitor [standard] direction) C_CD_NA_1
ACTIVATION TERMINATION
REQUEST OR REQUESTED
BACKGROUND SCAN
PERIODIC, CYCLIC
FILE TRANSFER
SPONTANEOUS
DEACTIVATION
ACTIVATION
INITIALIZED
20 37
NO. MNEMONIC 1 2 3 4 5 6 7 8 9 10 11 12 13 to to 44 45 46 47
36 41
<1> M_SP_NA_1 X X X X X
<2> M_SP_TA_1
<3> M_DP_NA_1
<4> M_DP_TA_1
<5> M_ST_NA_1
<6> M_ST_TA_1
<7> M_BO_NA_1
<8> M_BO_TA_1
<9> M_ME_NA_1
ACTIVATION TERMINATION
REQUEST OR REQUESTED
BACKGROUND SCAN
PERIODIC, CYCLIC
FILE TRANSFER
SPONTANEOUS
DEACTIVATION
ACTIVATION
INITIALIZED
20 37
NO. MNEMONIC 1 2 3 4 5 6 7 8 9 10 11 12 13 to to 44 45 46 47
36 41
<10> M_ME_TA_1 D
<11> M_ME_NB_1
<12> M_ME_TB_1
<13> M_ME_NC_1 X X X X
<14> M_ME_TC_1
<15> M_IT_NA_1 X X
<16> M_IT_TA_1
<17> M_EP_TA_1
<18> M_EP_TB_1
<19> M_EP_TC_1
<20> M_PS_NA_1
<21> M_ME_ND_1
<30> M_SP_TB_1 X X X
<31> M_DP_TB_1
<32> M_ST_TB_1
<33> M_BO_TB_1
<34> M_ME_TD_1
<35> M_ME_TE_1
<36> M_ME_TF_1
<37> M_IT_TB_1 X X
<38> M_EP_TD_1
<39> M_EP_TE_1
<40> M_EP_TF_1
<45> C_SC_NA_1 X X X X X
<46> C_DC_NA_1
<47> C_RC_NA_1
<48> C_SE_NA_1
<49> C_SE_NB_1
<50> C_SE_NC_1
<51> C_BO_NA_1
<58> C_SC_TA_1 X X X X X
<59> C_DC_TA_1
<60> C_RC_TA_1
ACTIVATION TERMINATION
REQUEST OR REQUESTED
BACKGROUND SCAN
PERIODIC, CYCLIC
FILE TRANSFER
SPONTANEOUS
DEACTIVATION
ACTIVATION
INITIALIZED
20 37
NO. MNEMONIC 1 2 3 4 5 6 7 8 9 10 11 12 13 to to 44 45 46 47
36 41
D <61>
<62>
C_SE_TA_1
C_SE_TB_1
<63> C_SE_TC_1
<64> C_BO_TA_1
<70> M_EI_NA_1*) X
<100> C_IC_NA_1 X X X X X
<101> C_CI_NA_1 X X X
<102> C_RD_NA_1 X
<103> C_CS_NA_1 X X X
<104> C_TS_NA_1
<105> C_RP_NA_1 X X
<106> C_CD_NA_1
<107> C_TS_TA_1
<110> P_ME_NA_1
<111> P_ME_NB_1
<112> P_ME_NC_1 X X X
<113> P_AC_NA_1
<120> F_FR_NA_1
<121> F_SR_NA_1
<122> F_SC_NA_1
<123> F_LS_NA_1
<124> F_AF_NA_1
<125> F_SG_NA_1
<126> F_DR_TA_1*)
Spontaneous Transmission:
Spontaneous transmission
Double transmission of information objects with cause of transmission spontaneous:
The following type identifications may be transmitted in succession caused by a single status change of an information
object. The particular information object addresses for which double transmission is enabled are defined in a project-
specific list.
Single point information: M_SP_NA_1, M_SP_TA_1, M_SP_TB_1, and M_PS_NA_1
Double point information: M_DP_NA_1, M_DP_TA_1, and M_DP_TB_1
Step position information: M_ST_NA_1, M_ST_TA_1, and M_ST_TB_1
Bitstring of 32 bits: M_BO_NA_1, M_BO_TA_1, and M_BO_TB_1 (if defined for a specific project)
Measured value, normalized value: M_ME_NA_1, M_ME_TA_1, M_ME_ND_1, and M_ME_TD_1
Measured value, scaled value: M_ME_NB_1, M_ME_TB_1, and M_ME_TE_1
Measured value, short floating point number: M_ME_NC_1, M_ME_TC_1, and M_ME_TF_1
Station interrogation:
Global D
Group 1 Group 5 Group 9 Group 13
Group 2 Group 6 Group 10 Group 14
Group 3 Group 7 Group 11 Group 15
Group 4 Group 8 Group 12 Group 16
Clock synchronization:
Clock synchronization (optional, see Clause 7.6)
Command transmission:
Direct command transmission
Direct setpoint command transmission
Select and execute command
Select and execute setpoint command
C_SE ACTTERM used
No additional definition
Short pulse duration (duration determined by a system parameter in the outstation)
Long pulse duration (duration determined by a system parameter in the outstation)
Persistent output
Counter read
Counter freeze without reset
APPENDIX E DNP COMMUNICATIONSE.1DEVICE PROFILE DOCUMENT E.1.1 DNP V3.00 DEVICE PROFILE
The following table provides a ‘Device Profile Document’ in the standard format defined in the DNP 3.0 Subset Definitions
Document.
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported (the complete
list is described in the attached table):
Binary Inputs (Object 1)
Binary Input Changes (Object 2)
Binary Outputs (Object 10)
Control Relay Output Block (Object 12)
Binary Counters (Object 20)
E
Frozen Counters (Object 21)
Counter Change Event (Object 22)
Frozen Counter Event (Object 23)
Analog Inputs (Object 30)
Analog Input Changes (Object 32)
Analog Deadbands (Object 34)
Time and Date (Object 50)
File Transfer (Object 70)
Internal Indications (Object 80)
Maximum Data Link Frame Size (octets): Maximum Application Fragment Size (octets):
Transmitted: 292 Transmitted: configurable up to 2048
Received: 292 Received: 2048
Others:
Transmission Delay: No intentional delay
Need Time Interval: Configurable (default = 24 hrs.)
Select/Operate Arm Timeout: 10 s
Binary input change scanning period: 8 times per power system cycle
Analog input change scanning period: 500 ms
Explanation of ‘Sometimes’: Object 12 points are mapped to UR Virtual Inputs. The persistence of Virtual Inputs is
determined by the VIRTUAL INPUT X TYPE settings. Both “Pulse On” and “Latch On” operations perform the same func-
tion in the UR; that is, the appropriate Virtual Input is put into the “On” state. If the Virtual Input is set to “Self-Reset”,
it will reset after one pass of FlexLogic. The On/Off times and Count value are ignored. “Pulse Off” and “Latch Off”
operations put the appropriate Virtual Input into the “Off” state. “Trip” and “Close” operations both put the appropriate
Virtual Input into the “On” state.
Reports Binary Input Change Events when no Reports time-tagged Binary Input Change Events when no
specific variation requested: specific variation requested:
Never Never
Only time-tagged Binary Input Change With Time
Only non-time-tagged Binary Input Change With Relative Time
Configurable Configurable (attach explanation)
The following table identifies the variations, function codes, and qualifiers supported by the D60 in both request messages
and in response messages. For static (non-change-event) objects, requests sent with qualifiers 00, 01, 06, 07, or 08, will be
responded with qualifiers 00 or 01. Static object requests sent with qualifiers 17 or 28 will be responded with qualifiers 17 or
28. For change-event objects, qualifiers 17 or 28 are always responded.
3 Binary Input Change with Relative Time 1 (read) 06 (no range, or all)
07, 08 (limited quantity)
10 0 Binary Output Status (Variation 0 is used to 1 (read) 00, 01(start-stop)
request default variation) 06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
2 Binary Output Status 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index)
07, 08 (limited quantity) (see Note 2)
17, 28 (index)
12 1 Control Relay Output Block 3 (select) 00, 01 (start-stop) 129 (response) echo of request
4 (operate) 07, 08 (limited quantity)
5 (direct op) 17, 28 (index)
6 (dir. op, noack)
20 0 Binary Counter 1 (read) 00, 01(start-stop)
(Variation 0 is used to request default 7 (freeze) 06(no range, or all)
variation) 8 (freeze noack) 07, 08(limited quantity)
9 (freeze clear) 17, 28(index)
10 (frz. cl. noack)
22 (assign class)
1 32-Bit Binary Counter 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
7 (freeze) 06 (no range, or all) 17, 28 (index)
8 (freeze noack) 07, 08 (limited quantity) (see Note 2)
9 (freeze clear) 17, 28 (index)
10 (frz. cl. noack)
22 (assign class)
Note 1: A default variation refers to the variation responded when variation 0 is requested and/or in class 0, 1, 2, or 3 scans. The default varia-
tions for object types 1, 2, 20, 21, 22, 23, 30, and 32 are selected via relay settings. Refer to the Communications section in Chapter 5
for details. This optimizes the class 0 poll data size.
Note 2: For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request is sent with qualifiers 17 or 28, respec-
tively. Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change-
event objects, qualifiers 17 or 28 are always responded.)
Note 3: Cold restarts are implemented the same as warm restarts – the D60 is not restarted, but the DNP process is restarted.
The DNP binary input data points are configured through the PRODUCT SETUP COMMUNICATIONS DNP / IEC104 POINT
LISTS BINARY INPUT / MSP POINTS menu. Refer to the Communications section of Chapter 5 for additional details. When a
freeze function is performed on a binary counter point, the frozen value is available in the corresponding frozen counter
point.
Supported Control Relay Output Block fields: Pulse On, Pulse Off, Latch On, Latch Off, Paired Trip, Paired Close.
E.2.3 COUNTERS
The following table lists both Binary Counters (Object 20) and Frozen Counters (Object 21). When a freeze function is per-
formed on a Binary Counter point, the frozen value is available in the corresponding Frozen Counter point.
BINARY COUNTERS
Static (Steady-State) Object Number: 20
Change Event Object Number: 22
Request Function Codes supported: 1 (read), 7 (freeze), 8 (freeze noack), 9 (freeze and clear),
10 (freeze and clear, noack), 22 (assign class)
Static Variation reported when variation 0 requested: 1 (32-Bit Binary Counter with Flag)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Counter Change Event without time)
Change Event Buffer Size: 10
Default Class for all points: 3
FROZEN COUNTERS
Static (Steady-State) Object Number: 21
Change Event Object Number: 23
Request Function Codes supported: 1 (read)
Static Variation reported when variation 0 requested: 1 (32-Bit Frozen Counter with Flag)
E Change Event Variation reported when variation 0 requested: 1 (32-Bit Frozen Counter Event without time)
Change Event Buffer Size: 10
Default Class for all points: 3
A counter freeze command has no meaning for counters 8 and 9. D60 Digital Counter values are represented as 32-bit
integers. The DNP 3.0 protocol defines counters to be unsigned integers. Care should be taken when interpreting negative
counter values.
The DNP analog input data points are configured through the PRODUCT SETUP COMMUNICATIONS DNP / IEC104 POINT
LISTS ANALOG INPUT / MME POINTS menu. Refer to the Communications section of Chapter 5 for additional details.
It is important to note that 16-bit and 32-bit variations of analog inputs are transmitted through DNP as signed numbers.
Even for analog input points that are not valid as negative values, the maximum positive representation is 32767 for 16-bit
values and 2147483647 for 32-bit values. This is a DNP requirement.
The deadbands for all Analog Input points are in the same units as the Analog Input quantity. For example, an Analog Input
quantity measured in volts has a corresponding deadband in units of volts. This is in conformance with DNP Technical Bul-
letin 9809-001: Analog Input Reporting Deadband. Relay settings are available to set default deadband values according to
data type. Deadbands for individual Analog Input Points can be set using DNP Object 34.
APPENDIX F RADIUS SERVERF.1 RADIUS SERVER CONFIGURATION F.1.1 RADIUS SERVER CONFIGURATION
The following procedure is an example of how to set up a simple RADIUS server, where the third-party tool used is also an
example.
1. Download and install FreeRADIUS as the RADIUS server.
2. In the RADIUSD.CONF file, locate the "bind_address" field and enter your RADIUS server IP address.
3. In the USERS.CONF file in the <Path_to_Radius>\etc\raddb folder, add the following text to configure a user "Tester"
with an Administrator role.
Tester:
->User-Password == "Testing1!1"
->GE-UR-Role = Administrator
4. In the CLIENTS.CONF file in the <Path_to_Radius>\etc\raddb folder, add the following text to define a RADIUS client,
where the client IP address is 10.0.0.2, the subnet mask is 255.255.255.0, the shared secret specified here is also
configured on the UR device for successful authentication, and the shortname is a short, optional alias that can be
used in place of the IP address.
client 10.0.0.2/24 {
secret = testing123
shortname = private-network-1
}
5. In the <Path_to_Radius>\etc\raddb folder, create a file called dictionary.ge and add the following content.
# ##########################################################
# GE VSAs
############################################################
VENDOR GE 2910
# Management authorization
BEGIN-VENDOR GE
# Role ID F
ATTRIBUTE GE-UR-Role 1 integer
# GE-UR-ROLE values
VALUE GE-UR-Role Administrator 1
VALUE GE-UR-Role Supervisor 2
VALUE GE-UR-Role Engineer 3
VALUE GE-UR-Role Operator 4
VALUE GE-UR-Role Observer 5
END-VENDOR GE
#############################################################
6. In the dictionary file in the <Path_to_Radius>\etc\raddb folder, add the following line.
$INCLUDE dictionary.ge
7. For the first start, run the RADIUS server in debug mode by entering
<Path_to_Radius>/start_radiusd_debug.bat
8. Set up the RADIUS client on the UR as follows. Access Device > Settings > Product Setup > Security. Configure the
IP address and ports for the RADIUS server. Leave the GE vendor ID field at the default of 2910. Update the RADIUS
shared secret as specified in the CLIENTS.CONF file.
5-108 5-108 Update Updated hysteresis numbers and logic diagrams in section 5.4.7 Phasor Measurement Unit
5-231 5-231 Update Updated Figure 5-122 Negative-Sequence Overvoltage Scheme Logic
G 8- --- Delete Security chapter - Moved content to other parts of manual and deleted the Security chapter
--- 10- Add Added Maintenance chapter, moving module replacement content from chapter 3, adding battery
replacement instructions, and moving battery disposal instructions from beginning of manual
1-1 1-1 Add Added General Cautions and Warnings to section 1.1.1
1-5 1-5 Update Revised section 1.3.1 on system requirements, including addition of support for Windows 7 and
Windows Server 2008
5-242 5-242 Update Updated Figure 5-135 Trip Output Scheme Logic (Sheet 1 of 2)
5-304 5-304 Add/Update Added and updated Block Scheme Target and Block Scheme Event in section 5.7g Directional
Comparison Blocking
5-1 5-1 Update Updated the front panel main menu to include the CyberSentry security menu
5-15 5-15 Update Update Communications main menu to remove the SNTP Protocol submenu
5-16 5-16 Delete Deleted references to COM 1 RS485 port in section 5.2.4b Serial Ports
5-16 5-16 Add Added section 5.2.4c Ethernet Network Topology
5-17 5-17 Update Updated Networks section 5.2.4d to include all three Ethernet ports
5-17 5-17 Update Added 0 as valid number to section 5.2.4e Modbus Protocol section
5-38 5- Delete Deleted Local Time Offset, Daylight Savings Time, DST (start/stop for month/day/hour) from Real
Time Clock menu
5- 5-37 Add Added submenus Precision Time Protocol, SNTP Protocol, and Local Time and Synchronizing
Source settings to Real Time Clock menu
5- 5-38 Add Added new Precision Time Protocol (1588) menu and setting descriptions
5-40 5-40 Update Changed Communication to Real Time Clock in SNTP protocol settings path. Moved SNTP
Protocol menu and settings descriptions to Real Time Clock subsection
5-37 5- Delete Deleted section k) SNTP Protocol and the settings descriptions
5- 5-41 Add Added new section for Local Time menu settings and settings description
5- 5-50 Add Added new PTP Fail menu item to the User-Programmable Self Tests menu
5- 5- Add Added PTP Failure and CLOCK UNSYNCHRONIZED to Flexlogic Operands table
5-91 5-91 Update Updated PMU main menu to add aggregator and control block menu items
G
5-315 5-315 Delete Deleted section 5.8.5c Remote Devices: ID of Device for Receiving GSSE/GOOSE Messages,
meaning the Settings > Input/Outputs > Remote Devices settings
5- 5- Add Added new CyberSentry security section and main menu, local passwords, session settings,
restore defaults, and supervisory subsections to Chapter 5
5- 5- Update Changed main menu for Pilot schemes to add POTT1 and submenu descriptions
6-1 6-1 Update Update Actual Values main menu to include Real Time Clock Synchronization submenu
6- 6-7 Add Added new section for Real Time Clock synchronizing consisting of the menu of settings and the
setting descriptions
6-11 6-11 Delete Deleted section 6.2.19 Ethernet Switch
6- 6-11 Add Added new section 6.2.20 Remaining Connection Status
8- 8-4 Add Added new section for CyberSentry software option with overview and security menu subsections
A- A- Add Added FlexAnalog item PTP–IRIG-B Delta to Table A-1: FlexAnalog Data Items
B-8 B-8 Update Updated Modbus memory map table to include port 0 for Modbus slave address, TCP, DNP,
HTTP, TFTP, MMS, and removed references to COM 1 RS485 port
C-23 C-23 Update Updated tables in sections C.6.3 ACSI Services Conformance Statement and C.7.1 Logical
Nodes Table
G Statement
PKP ................ Pickup
PLC ................ Power Line Carrier
UR.................. Universal Relay
URC ............... Universal Recloser Control
.URS .............. Filename extension for settings files
POS................ Positive UV.................. Undervoltage
POTT.............. Permissive Over-reaching Transfer Trip
PRESS ........... Pressure V/Hz ............... Volts per Hertz
PRI ................. Primary V_0 ................ Zero Sequence voltage
PROT ............. Protection V_1 ................ Positive Sequence voltage
PSEL .............. Presentation Selector V_2 ................ Negative Sequence voltage
pu ................... Per Unit VA .................. Phase A voltage
PUIB............... Pickup Current Block VAB ................ Phase A to B voltage
PUIT ............... Pickup Current Trip VAG................ Phase A to Ground voltage
PUSHBTN ...... Pushbutton VARH ............. Var-hour voltage
PUTT.............. Permissive Under-reaching Transfer Trip VB .................. Phase B voltage
PWM .............. Pulse Width Modulated VBA................ Phase B to A voltage
PWR............... Power VBG ............... Phase B to Ground voltage
VC.................. Phase C voltage
QUAD............. Quadrilateral VCA ............... Phase C to A voltage
VCG ............... Phase C to Ground voltage
R..................... Rate, Reverse VF .................. Variable Frequency
RCA................ Reach Characteristic Angle VIBR .............. Vibration
REF ................ Reference VT .................. Voltage Transformer
REM ............... Remote VTFF.............. Voltage Transformer Fuse Failure
REV................ Reverse VTLOS ........... Voltage Transformer Loss Of Signal
RI.................... Reclose Initiate
RIP ................. Reclose In Progress WDG .............. Winding
RGT BLD........ Right Blinder WH................. Watt-hour
ROD ............... Remote Open Detector w/ opt ............. With Option
RST ................ Reset WRT............... With Respect To
RSTR ............. Restrained
RTD ................ Resistance Temperature Detector X .................... Reactance
RTU ................ Remote Terminal Unit XDUCER........ Transducer
RX (Rx) .......... Receive, Receiver XFMR............. Transformer
In the event of a failure covered by warranty, GE Multilin will undertake to repair or replace the relay
providing the warrantor determined that it is defective and it is returned with all transportation
charges prepaid to an authorized service centre or the factory. Repairs or replacement under war-
ranty will be made without charge.
Warranty shall not apply to any relay which has been subject to misuse, negligence, accident,
incorrect installation or use not in accordance with instructions nor any unit that has been altered
outside a GE Multilin authorized factory outlet.
GE Multilin is not liable for special, indirect or consequential damages or for loss of profit or for
expenses sustained as a result of a relay malfunction, incorrect application or adjustment.
G
For complete text of Warranty (including limitations and disclaimers), refer to GE Multilin Standard
Conditions of Sale.
POTT RECLOSING
application of settings ...................................................... 9-6 description ...................................................................5-265
FlexLogic operands ...................................................... 5-139 logic .......................................................5-272, 5-274, 5-275
hybrid POTT ................................................................ 5-313 sequence ..................................................................... 5-276
logic ..................................................................5-310, 5-312 settings ............................. 5-264, 5-267, 5-268, 5-270, 5-271
Modbus registers ..................................................B-57, B-58 REDUNDANCY
settings ....................................... 5-307, 5-308, 5-309, 5-311 PRP actual values ..........................................................6-11
POWER METERING PRP explained ...............................................................5-30
Modbus registers ...........................................................B-14 settings ..........................................................................5-29
specifications................................................................. 2-23 specifications .................................................................2-26
values ........................................................................... 6-18 RELAY ACTIVATION ........................................................4-27
POWER SUPPLY RELAY ARCHITECTURE ................................................ 5-131
description....................................................................... 3-9 RELAY MAINTENANCE ..................................................... 7-3
low range ...................................................................... 2-24 RELAY NAME ...................................................................5-88
specifications................................................................. 2-24 RELAY NOT PROGRAMMED ............................................1-19
POWER SWING BLOCKING .................................. 2-20, 5-178 REMOTE DEVICES
POWER SWING DETECT actual values ................................................................... 6-6
FlexLogic operands ...................................................... 5-139 device ID ..................................................................... 5-333
logic ..................................................................5-183, 5-184 error messages ..............................................................7-10
Modbus registers ...........................................................B-38 FlexLogic operands ...................................................... 5-142
settings .............................................................5-176, 5-180 Modbus registers ................................ B-11, B-18, B-71, B-75
specifications................................................................. 2-20 settings ........................................................................ 5-332
POWER SYSTEM statistics ......................................................................... 6-7
Modbus registers ...........................................................B-30 REMOTE DPS INPUTS
PREFERENCES actual values ................................................................... 6-5
Modbus registers ...........................................................B-26 settings ........................................................................ 5-334
PROCESS BUS REMOTE INPUTS
overview ........................................................................ 3-11 actual values ................................................................... 6-4
PRODUCT INFORMATION ........................................ 6-27, B-9 FlexLogic operands ...................................................... 5-142
PRODUCT SETUP .................................................... 5-8, 5-19 Modbus registers ......................................... B-11, B-18, B-72
PRODUCTION TESTS ...................................................... 2-28 settings ........................................................................ 5-333
PROTECTION ELEMENTS ................................................. 5-4 specifications .................................................................2-24
PRP REMOTE OUTPUTS
actual values ................................................................. 6-11 DNA-1 bit pair .............................................................. 5-334
explained....................................................................... 5-30 Modbus registers ........................................................... B-73
settings ......................................................................... 5-29 UserSt-1 bit pair ........................................................... 5-335
specifications................................................................. 2-26 REPLACEMENT MODULES ..................................... 2-14, 2-15
PU QUANTITY ................................................................... 5-4 REQUIREMENTS FOR INSTALLATION .............................. 1-6
PUSHBUTTONS, USER-PROGRAMMABLE RESETTING ................................................. 5-8, 5-142, 5-335
see USER-PROGRAMMABLE PUSHBUTTONS REVISION HISTORY ......................................................... G-1
PUTT RF IMMUNITY ..................................................................2-28
application of settings ...................................................... 9-6 RFI, CONDUCTED ............................................................2-28
FlexLogic operands ...................................................... 5-139 RMS CURRENT ................................................................2-23
logic ............................................................................ 5-306 RMS VOLTAGE ................................................................2-23
Modbus registers ...........................................................B-40 RS232
settings ....................................................................... 5-305 configuration ..................................................................1-10
specifications .................................................................2-26
wiring .............................................................................3-21
RS422
Q configuration ..................................................................3-31
timing ............................................................................3-32
QUAD DISTANCE CHARACTERISTIC 5-162, 5-163, 5-170, 8-5,
two-channel application ..................................................3-31
8-6
with fiber interface ..........................................................3-33
RS485
description .....................................................................3-23
R specifications .................................................................2-26
RTD INPUTS
REACTIVE POWER ................................................. 2-23, 6-18 actual values ..................................................................6-23
REAL POWER ......................................................... 2-23, 6-18 Modbus registers .................................................. B-20, B-33
REAL TIME CLOCK settings ........................................................................ 5-344
Modbus registers ...........................................................B-28 specifications .................................................................2-24
settings ......................................................................... 5-56
REAR TERMINAL ASSIGNMENTS ...................................... 3-7
RECLOSER CURVES ...........................................5-105, 5-191
S
SALES OFFICE ................................................................. 1-2
SBO .................................................................................5-52
Z
ZERO SEQUENCE CORE BALANCE ................................ 3-11