QUINT and MINI POWER DC-DC converters Primary switched-mode power supply units DC-DC converter If no regulated and stable 24 V direct voltage is available for supplying a load, the DC-DC converter ensures adaptation of the 24 V load to an unregulated direct voltage or direct voltage of another voltage level. Due to electrical isolation, the DC voltage circuits are electrically isolated from each other in a safe way.
Width 80 mm
UuFol Ex: U
DC OK 13 14
stranded AWG [mm2] 0.2-2.5 0.2-2.5 24-12 0.2-2.5 0.2-2.5 24-12 0.2-2.5 0.2-2.5 24-12
solid
M3 M3 M3 Pcs. / Pkt.
Type
Order No.
QUINT-PS- 24DC/24DC/10 Technical data Input data Input nominal voltage range Input voltage range AC/DC Current consumption (nominal load) Inrush current limitation at 25C (typ.) / I2t Input fuse Output data Nominal output voltage Setting range of the output voltage Output current Can be connected in parallel / series Max. power dissipation (idling/nominal load) Efficiency (typ.) Residual ripple Signaling Signaling DC OK General data Weight / Dimensions W x H x D Installation position Distance during assembly Type of connection Degree of protection / Class of protection MTBF (at nominal load, 40C) Ambient temperature (operation) Ambient temperature (storage/transport) Max. permissible relative humidity (operation) Standards/regulations Insulation voltage input/output Electromagnetic compatibility Electrical safety, safety transformer Electronic equipm. for electrical power installations Safe isolation UL approvals
2866378
24 V DC - / 18 V DC ... 32 V DC Approx. 11.4 A (24 V) / < 20 A / 0.3 A2s 25 A (slow-blow, internal) 24 V DC 1% 22.5 V DC ... 28.5 V DC (> 24 V constant capacity) 10 A Yes / Yes 2 W / 28 W > 88% (at 24 V DC and nominal values) < 30 mVPP LED, active switching output, relay contact 0.95 kg / 80 x 130 x 125 mm Horizontal DIN rail NS 35, EN 60715 Can be aligned: Horizontal 0 cm, vertical 5 cm Pluggable screw connection IP20 / III > 500 000 h in acc. with IEC 61709 (SN 29500) -25C ... 70C (> 60C derating) -40C ... 85C 95% (at 25C, no condensation) 1.5 kV (type test) / 1 kV (routine test) Conformance with EMC directive 89/336/EEC EN 60950/VDE 0805 (SELV), EN 61558-2-17 EN 50178/VDE 0160 (PELV) DIN VDE 0100-410, DIN VDE 0106-1010 UL/C-UL listed UL 508, UL/C-UL Recognized UL 60950, UL/C-UL Listed UL 1604 Class I, Division 2, Groups A, B, C, D
598
PHOENIX CONTACT
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370 Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Width 22.5 mm
UuF Ex: U
Width 22.5 mm
Uu Ex: U
NC NC DC OK
NC NC DC OK
stranded AWG [mm2] 0.2-2.5 0.2-2.5 24-12 0.2-2.5 0.2-2.5 24-12 0.2-2.5 0.2-2.5 24-12
solid
stranded [mm2] AWG 0.2-2.5 0.2-2.5 24-12 0.2-2.5 0.2-2.5 24-12 0.2-2.5 0.2-2.5 24-12
solid
M3 M3 M3 Pcs. / Pkt.
Type
Order No.
Type
Order No.
2866284
2866271
12 V DC ... 24 V DC - / 10 V DC ... 32 V DC Approx. 3.2 A (10 V DC) / 1 A (32 V DC) < 15 A / 1.8 A2s 6.3 A (slow-blow, internal) 24 V DC 1% 22.5 V DC ... 28.5 V DC (> 24 V constant capacity) 1A Yes / No 1.2 W / 5 W > 83% (at 24 V DC and nominal values) < 30 mVPP LED, active switching output 0.2 kg / 22.5 x 99 x 107 mm Horizontal DIN rail NS 35, EN 60715 Can be aligned: Horizontal 0 cm, vertical 5 cm Pluggable screw connection IP20 / II > 500 000 h in acc. with IEC 61709 (SN 29500) -25C ... 70C (> 60C derating) -40C ... 85C 95% (at 25C, no condensation) 1.5 kV (type test) / 1 kV (routine test) Conformance with EMC directive 89/336/EEC EN 60950/VDE 0805 (SELV), EN 61558-2-17 EN 50178/VDE 0160 (PELV) DIN VDE 0100-410, DIN VDE 0106-1010 UL/C-UL listed UL 508, UL/C-UL Recognized UL 60950, UL/C-UL Listed UL 1604 Class I, Division 2, Groups A, B, C, D
48 V DC ... 60 V DC - / 36 V DC ... 75 V DC Approx. 0.8 A (36 V DC) / 0.4 A (75 V DC) < 15 A / 1.8 A2s 3.15 A (slow-blow, internal) 24 V DC 1% 22.5 V DC ... 28.5 V DC (> 24 V constant capacity) 1A Yes / No 1.2 W / 5 W > 85% (at 60 V DC and nominal values) < 40 mVPP LED, active switching output 0.2 kg / 22.5 x 99 x 107 mm Horizontal DIN rail NS 35, EN 60715 Can be aligned: Horizontal 0 cm, vertical 5 cm Pluggable screw connection IP20 / II > 500 000 h in acc. with IEC 61709 (SN 29500) -25C ... 70C (> 60C derating) -40C ... 85C 95% (at 25C, no condensation) 1.5 kV (type test) / 1 kV (routine test) Conformance with EMC directive 89/336/EEC EN 60950/VDE 0805 (SELV), EN 61558-2-17 EN 50178/VDE 0160 (PELV) DIN VDE 0100-410, DIN VDE 0106-1010 UL/C-UL listed UL 508, UL/C-UL Recognized UL 60950, UL/C-UL Listed UL 1604 Class I, Division 2, Groups A, B, C, D
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370 Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
PHOENIX CONTACT
599