Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

MVAJ053

Download as pdf or txt
Download as pdf or txt
You are on page 1of 38
At a glance
Powered by AI
The technical manual provides instructions for installation, commissioning and operation of equipment but cannot cover all scenarios. Users should contact Alstom Grid for any questions or issues and not modify equipment without permission.

To provide instructions for installation, commissioning and operation of equipment while noting limitations and emphasizing not modifying equipment without permission from Alstom Grid.

Electrostatic discharge can damage electronic components so personnel should ensure they are at the same electrostatic potential as equipment, handle modules by non-electronic parts and avoid unnecessary contact with components.

| AUTOMATION

MVAJ 05, 10, 20


Tripping & Control Relays

Technical Manual
R8141D

GRID

Note:

The technical manual for this device gives instructions for its installation, commissioning, and operation. However, the manual cannot cover all conceivable circumstances or include detailed information on all topics. In the event of questions or specific problems, do not take any action without proper authorization. Contact the appropriate Alstom Grid technical sales office and request the necessary information. Any agreements, commitments, and legal relationships and any obligations on the part of Alstom Grid including settlements of warranties, result solely from the applicable purchase contract, which is not affected by the contents of the technical manual. This device MUST NOT be modified. If any modification is made without the express permission of Alstom Grid, it will invalidate the warranty, and may render the product unsafe.

The Alstom Grid logo and any alternative version thereof are trademarks and service marks of Alstom Grid. All trade names or trademarks mentioned herein whether registered or not, are the property of their owners. This manual is provided for informational use only and is subject to change without notice. 2010, Alstom Grid. All rights reserved.

Technical Manual Types MVAJ 05, 10, 20

R8141D Page 1/34

HANDLING OF ELECTRONIC EQUIPMENT

A persons normal movements can easily generate electrostatic potentials of several thousand volts. Discharge of these voltages into semiconductor devices when handling circuits can cause serious damage, which often may not be immediately apparent but the reliability of the circuit will have been reduced. The electronic circuits of Alstom Grid products are immune to the relevant levels of electrostatic discharge when housed in their cases. Do not expose them to the risk of damage by withdrawing modules unnecessarily. Each module incorporates the highest practicable protection for its semiconductor devices. However, if it becomes necessary to withdraw a module, the following precautions should be taken to preserve the high reliability and long life for which the equipment has been designed and manufactured. 1. 2. 3. 4. 5. Before removing a module, ensure that you are a same electrostatic potential as the equipment by touching the case. Handle the module by its front-plate, frame, or edges of the printed circuit board. Avoid touching the electronic components, printed circuit track or connectors. Do not pass the module to any person without first ensuring that you are both at the same electrostatic potential. Shaking hands achieves equipotential. Place the module on an antistatic surface, or on a conducting surface which is at the same potential as yourself. Store or transport the module in a conductive bag.

More information on safe working procedures for all electronic equipment can be found in BS5783 and IEC 60147-0F. If you are making measurements on the internal electronic circuitry of an equipment in service, it is preferable that you are earthed to the case with a conductive wrist strap. Wrist straps should have a resistance to ground between 500k 10M ohms. If a wrist strap is not available you should maintain regular contact with the case to prevent the build up of static. Instrumentation which may be used for making measurements should be earthed to the case whenever possible. Alstom Grid strongly recommends that detailed investigations on the electronic circuitry, or modification work, should be carried out in a Special Handling Area such as described in BS5783 or IEC 60147-0F.

R8141D Page 2/34

Technical Manual Types MVAJ 05, 10, 20

Technical Manual Types MVAJ 05, 10, 20

R8141D Page 3/34

CONTENT
SAFETY SECTION 1.
1.1 1.2 1.3 1.4 1.5

5 9
9 9 9 9 9

INSTALLATION
General Receipt Unpacking Storage Installation

2.
2.1 2.2 2.3 2.4 2.5 2.6

COMMISSIONING
Commissioning preliminaries Preliminary checks Insulation tests Operate/reset operation Restoration of wiring Problem analysis

10
10 11 11 12 12 12

3. 4.
4.1 4.2 4.3 4.4 4.4.1

MAINTENANCE MECHANICAL SETTINGS


General Cleaning contacts Contact settings Settings Relay types MVAJ05

13 14
14 14 14 14 14

5.
5.1

SPARES
Repairs

16
16

6. 7.

CONNECTION DIAGRAMS COMMISSIONING TEST RECORD REPAIR FORM

17 32

R8141D Page 4/34

Technical Manual Types MVAJ 05, 10, 20

Technical Manual Types MVAJ 05, 10, 20

R8141D Page 5/34

1.

SAFETY SECTION
This Safety Section should be read before commencing any work on the equipment.

1.1

Health and safety The information in the Safety Section of the product documentation is intended to ensure that products are properly installed and handled in order to maintain them in a safe condition. It is assumed that everyone who will be associated with the equipment will be familiar with the contents of the Safety Section.

1.2

Explanation of symbols and labels The meaning of symbols and labels may be used on the equipment or in the product documentation, is given below.

Caution: refer to product documentation

Caution: risk of electric shock

Protective/safety *earth terminal

Functional *earth terminal Note: This symbol may also be used for a protective/safety earth terminal if that terminal is part of a terminal block or subassembly e.g. power supply.

*NOTE: THE TERM EARTH USED THROUGHOUT THE PRODUCT DOCUMENTATION IS THE DIRECT EQUIVALENT OF THE NORTH AMERICAN TERM GROUND.

2.

INSTALLING, COMMISSIONING AND SERVICING


Equipment connections Personnel undertaking installation, commissioning or servicing work on this equipment should be aware of the correct working procedures to ensure safety. The product documentation should be consulted before installing, commissioning or servicing the equipment. Terminals exposed during installation, commissioning and maintenance may present a hazardous voltage unless the equipment is electrically isolated. If there is unlocked access to the rear of the equipment, care should be taken by all personnel to avoid electrical shock or energy hazards.

R8141D Page 6/34

Technical Manual Types MVAJ 05, 10, 20

Voltage and current connections should be made using insulated crimp terminations to ensure that terminal block insulation requirements are maintained for safety. To ensure that wires are correctly terminated, the correct crimp terminal and tool for the wire size should be used. Before energising the equipment it must be earthed using the protective earth terminal, or the appropriate termination of the supply plug in the case of plug connected equipment. Omitting or disconnecting the equipment earth may cause a safety hazard. The recommended minimum earth wire size is 2.5mm2, unless otherwise stated in the technical data section of the product documentation. Before energising the equipment, the following should be checked: Voltage rating and polarity; CT circuit rating and integrity of connections; Protective fuse rating; Integrity of earth connection (where applicable) Remove front plate plastic film protection Remove insulating strip from battery compartment

3.

EQUIPMENT OPERATING CONDITIONS


The equipment should be operated within the specified electrical and environmental limits.

3.1

Current transformer circuits Do not open the secondary circuit of a live CT since the high level voltage produced may be lethal to personnel and could damage insulation.

3.2

External resistors Where external resistors are fitted to relays, these may present a risk of electric shock or burns, if touched.

3.3

Battery replacement Where internal batteries are fitted they should be replaced with the recommended type and be installed with the correct polarity, to avoid possible damage to the equipment.

3.4

Insulation and dielectric strength testing Insulation testing may leave capacitors charged up to a hazardous voltage. At the end of each part of the test, the voltage should be gradually reduced to zero, to discharge capacitors, before the test leads are disconnected.

3.5

Insertion of modules and pcb cards These must not be inserted into or withdrawn from equipment whist it is energised since this may result in damage.

3.6

Fibre optic communication Where fibre optic communication devices are fitted, these should not be viewed directly. Optical power meters should be used to determine the operation or signal level of the device.

Technical Manual Types MVAJ 05, 10, 20

R8141D Page 7/34

4.

OLDER PRODUCTS
Electrical adjustments Equipments which require direct physical adjustments to their operating mechanism to change current or voltage settings, should have the electrical power removed before making the change, to avoid any risk of electrical shock. Mechanical adjustments The electrical power to the relay contacts should be removed before checking any mechanical settings, to avoid any risk of electric shock. Draw out case relays Removal of the cover on equipment incorporating electromechanical operating elements, may expose hazardous live parts such as relay contacts. Insertion and withdrawal of extender cards When using an extender card, this should not be inserted or withdrawn from the equipment whilst it is energised. This is to avoid possible shock or damage hazards. Hazardous live voltages may be accessible on the extender card. Insertion and withdrawal of heavy current test plugs When using a heavy current test plug, CT shorting links must be in place before insertion or removal, to avoid potentially lethal voltages.

5.

DECOMMISSIONING AND DISPOSAL


Decommissioning: The auxiliary supply circuit in the relay may include capacitors across the supply or to earth. To avoid electric shock or energy hazards, after completely isolating the supplies to the relay (both poles of any dc supply), the capacitors should be safely discharged via the external terminals prior to decommissioning. It is recommended that incineration and disposal to water courses is avoided. The product should be disposed of in a safe manner. Any products containing batteries should have them removed before disposal, taking precautions to avoid short circuits. Particular regulations within the country of operation, may apply to the disposal of lithium batteries.

Disposal:

R8141D Page 8/34

Technical Manual Types MVAJ 05, 10, 20

6.

TECHNICAL SPECIFICATIONS
Protective fuse rating The recommended maximum rating of the external protective fuse for this equipment is 16A, Red Spot type or equivalent, unless otherwise stated in the technical data section of the product documentation. Insulation class: IEC 601010-1 : 1990/A2 : 2001 Class I EN 61010-1: 2001 Class I This equipment requires a protective (safety) earth connection to ensure user safety.

Insulation Category (Overvoltage):

IEC 601010-1 : 1990/A2 : 1995 Category III EN 61010-1: 2001 Category III

Distribution level, fixed insulation. Equipment in this category is qualification tested at 5kV peak, 1.2/50s, 500, 0.5J, between all supply circuits and earth and also between independent circuits.

Environment:

IEC 601010-1 : 1990/A2 : 1995 Pollution degree 2 EN 61010-1: 2001 Pollution degree 2

Compliance is demonstrated by reference to generic safety standards.

Product Safety:

72/23/EEC

Compliance with the European Commission Low Voltage Directive. Compliance is demonstrated by reference to generic safety standards.

EN 61010-1: 2001 EN 60950-1: 2002

Technical Manual Types MVAJ 05, 10, 20

R8141D Page 9/34

1.
1.1

INSTALLATION
General Protective relays, although generally of robust construction, require careful treatment prior to installation and a wise selection of site. By observing a few simple rules the possibility of premature failure is eliminated and a high degree of performance can be expected. The safety section should be read before any work takes place and should be referred to throughout. Special care should be taken to adhere to suitable electro-static discharge precautions.

1.2

Receipt The relays are either despatched individually or as part of a panel/rack mounted assembly in cartons specifically designed to protect them from damage. Relays should be examined immediately they are received to ensure that no damage has been sustained in transit. If damage due to rough handling is evident ,a claim should be made to the transport company concerned immediately and Alstom Grid should be promptly notified. Relays which are supplied un mounted and not intended for immediate installation should be returned to their protective polythene bags.

1.3

Unpacking Care must be taken when unpacking and installing the relays so that none of the parts are damaged or their settings altered and must only be handled by skilled persons. Relays should be examined for any wedges, clamps, or rubber bands necessary to secure moving parts to prevent damage during transit and these should be removed after installation and before commissioning. Relays which have been removed from their cases should not be left in situations where they are exposed to dust or damp. This particularly applies to installations which are being carried out at the same time as construction work.

1.4

Storage If relays are not installed immediately upon receipt they should be stored in a place free from dust and moisture in their original cartons and where de-humidifier bags have been included in the packing they should be retained. The action of the de-humidifier crystals will be impaired if the bag has been exposed to ambient conditions and may be restored by gently heating the bag for about an hour, prior to replacing it in the carton. Dust which collects on a carton may, on subsequent unpacking, find its way into the relay; in damp conditions the carton and packing may become impregnated with moisture and the dehumidifying agent will lose its efficiency. The storage temperature range is 40C to +70C.

1.5

Installation The installation should be clean, dry and reasonably free from dust and excessive vibration. The site should preferably be well illuminated to facilitate inspection. An outline diagram is normally supplied showing panel cut-outs and hole centres. For individually mounted relays these dimensions will also be found in publication R6141. Publication R7012, Parts Catalogue and Assembly Instructions, will be useful when individual relays are to be assembled as a composite rack or panel mounted assembly. Publication R6001 is a leaflet on the modular integrated draw out system of protective relays. Publication R6014 is a list of recommended suppliers for the pre-insulated connectors.

R8141D Page 10/34

Technical Manual Types MVAJ 05, 10, 20

2.
2.1 2.1.1

COMMISSIONING
Commissioning preliminaries Electrostatic discharge (ESD) The relay uses components which are sensitive to electrostatic discharges. Whenhandling the withdrawn module, care should be taken to avoid contact withcomponents and electrical connections. When removed from its case for storagethe module should be placed in an electrically conducting anti-static bag.

2.1.2

Inspection Carefully examine the module and case to see that no damage has occurredduring transit. Check that the relay serial number on the module, case and cover are identical,and also check that the rating information is correct for the system.

2.1.3

Wiring WARNING: EXPOSED TERMINALS MAY PRESENT A HAZARDOUS VOLTAGE UNLESSEQUIPMENT IS ELECTRICALLY ISOLATED.

Check that the external wiring is correct to the relevant relay diagram and/or scheme diagram. It is especially important that DC supplies are wired with thecorrect polarity. The relay external connection diagram number is given on therating label inside the case. 2.1.4 External links There are two external links as detailed in tables 1 and 2. All trip relays are supplied as high burden. With the exception of MVAJ102, 202,they may be converted to low burden by removing the link between case terminals 22 and 24. Relay type MVAJ 051, 053, 054, 055 MVAJ 101, 103, 104, 105 201, 203, 204, 205 MVAJ102, 202 NOTE: Feature Burden Cut-off Burden Cut-off Link in High Instantaneous High 40-60ms time delayed Link out Low Instantaneous Low Instantaneous

Link not necessary - configured as high burden models At the point at which the relay cut-off occurs the current drawn by the relayis either reduced to an economised level or is removed entirely (ie. zerowatt cut-off state).

Table 1: Configuration of high/low burden link (terminals 22 to 24) A second link is supplied fitted to selected 10 and 20 contact relays as detailed in Table 2. This link, connected between case terminals 21 and 23 enables a reset inhibitor feature to be introduced into the circuit of 10 and 20 contact electrical reset relays, ensuring that the reset circuit is disabled when the operate circuit is energised. On relay types 104, 105, 204 and 205 this link may be removed if this feature is not required. NOTE: This link must remain fitted to MVAJ101 and 201 relays to enable the economising circuit.

Technical Manual Types MVAJ 05, 10, 20 Relay type MVAJ 051, 053, 054, 055 101, 102 MVAJ 101, 201 MVAJ103, 203 MVAJ104, 105, 204, 205 Feature Link in Link out

R8141D Page 11/34

Link of available Link fitted (relay cut-off to economised state) Link not available (relay cut-off to zero watts) Cut-off state reset inhibitor Economised active Zero watts disablet

Table 2: Configuration of economising/reset inhibit link (terminals 21 to 23) 2.2 Preliminary checks Before leaving the factory all relays are accurately adjusted, tested and carefullypacked. There should be no need for any re-adjustment on commissioning. Moving parts are held in position during transit by rubber bands and packing.These should be removed carefully. 2.2.1 To gain access to the relay first loosen the captive cover screws, then carefullyremove the cover from the case. The module can then be removed from the case by grasping the handles at the topand bottom of the front plate and pulling forwards. Care must be taken to ensure that mechanical settings of the element are not disturbed. 2.2.2 2.2.3 2.2.4 Carefully remove the rubber band securing the flag mechanism. Check that the bottom end of the contact operating card has not been dislodgedfrom the slot in the armature extension. Check that all push-on connections to the PCB are secure. Check that all the push-on connections to the back of the contacts are secure. Check that all the push-on connections to terminal block are secure. 2.2.5 Carefully actuate the armature of each unit in turn with a small screwdriver/probe. On units fitted with hand reset flag indicators, check that the flag is free to fallbefore, or just as, any make contacts close. 2.2.6 Check that the serial number in the cover and the relay case match that of themodule. Replace the module in the case and refit the cover. Make sure that thereset mechanism in the cover is correctly located with respect to the relay elementand that the flag (or mechanism) can be reset. Check that the armature(s) are in the reset position by pressing the appropriatereset buttons; 2.3 Insulation tests The relay and its associated wiring may be insulation tested between: all electrically isolated circuits all circuits and earth

An electronic or brushless insulation tester should be used giving a dc voltage notexceeding 1000V. Accessible terminals of the same circuit should first be strappedtogether. Deliberate circuit earthing links removed for the tests must subsequentlybe replaced.

R8141D Page 12/34 2.4 Operate/reset operation WARNING:

Technical Manual Types MVAJ 05, 10, 20

EXPOSED TERMINALS MAY PRESENT A HAZARDOUS VOLTAGE UNLESSEQUIPMENT IS ELECTRICALLY ISOLATED.

2.4.1

Self, hand, electrical and hand/electrical reset 1. 2. 3. 4. The operate circuit is terminated to case terminals 27(+), 28(-). The electrical reset circuit is terminated to case terminals 25(+), 26(-). Disconnect external wiring from these terminals to allow application of the test supply. Check operation of operate circuit by energising the relay with 60% of the lower nominal supply voltage. Please note that the supply voltage applied across the relay case terminals should be directly at 60% of the lower nominal supply voltage ( for example LNV= 110 V , so you have to inject 66 V ) and this voltage should not be applied gradually to reach 60% of the lower nominal supply voltage. The relays should switch cleanly with one movement. With the relay set check the continuity of the closed contacts, Contact continuity test should be done by applying 5A current & measuring the voltage across the output contact terminals after that you can check the impedance of the relay. Check the operating time of the relay at 100% lower nominal supply voltage and check the continuity of the closed contacts.

5.

6. 2.4.2

Self-reset 2.5s delayed reset 1. 2. 3. The operate circuit is terminated to case terminals 25(+), 27(+), 28(-). Disconnect external wiring from these terminals to allow application of the test supply. Check operation of operate circuit by energising the relay with 60% of the lower nominal supply voltage. Please note that the supply voltage applied across the relay case terminals should be directly at 60% of the lower nominal supply voltage ( for example LNV= 110 V , so you have to inject 66 V ) and this voltage should not be applied gradually to reach 60% of the lower nominal supply voltage. The relays should switch cleanly with one movement. With the relay set check the continuity of the closed contacts, Contact continuity test should be done by applying 5A current & measuring the voltage across the output contact terminals. Check the operating time of the relay at 100% lower nominal supply voltage and check the continuity of the closed contacts. Check the delayed reset time by energising the relay with full rated supply volts to case terminations 25(+), 27(+), 28(-), then remove energisation from the case termination 27(+). Time the closure of a normally closed contact from this point in time. The reset time shall be between 2 - 2.8s.

4.

5. 6.

2.5

Restoration of wiring Restore any external wiring connections that may have been disturbed during the above tests.

2.6

Problem analysis Repeat Section 2.2 with particular attention to the connection of external links. If the relay is found to be faulty it should be returned to Alstom Grid for repair and recalibration. There are no user serviceable parts inside.

Technical Manual Types MVAJ 05, 10, 20

R8141D Page 13/34

3.

MAINTENANCE
Periodic maintenance is not necessary, however routine testing should be carriedout the meet the customer requirements. Check the relay for operation at 60% lower nominal supply voltage and forcontact wear. If required, the mechanical settings may be checked against thoseshown in Section 4.

R8141D Page 14/34

Technical Manual Types MVAJ 05, 10, 20

4.
4.1

MECHANICAL SETTINGS
General Contacts are set at the factory and should not require adjustment. If contacts show signs of contamination during maintenance it may be necessary toclean contacts and check settings. CONTACTS MUST BE CHECKED BY QUALIFIED PERSONNEL ONLY TO ENSURE THAT SETTINGS ARE NOT DISTURBED. The safety section should be read before attempting any adjustments.

4.2

Cleaning contacts Contacts should be cleaned with the burnishing tool, supplied in relay tool kits. On no account should cleaning fluids, knives, files or abrasive materials be used.

4.3

Contact settings Armature gap measurements should be made with the top of the feeler gauge levelwith the centre line of the core. Contact pressures are measured with a gramme gauge at the contact tips. In general contact gaps and follow through are defined by quoting an armaturegap at which the tips should be just closed or just open. Follow through should bemeasured at the centre of the armature. Some mechanically operated contact gapsmust be measured directly with feeler gauges at the contact tips. The relay contact state is always defined with the relay in the reset position unlessotherwise specified on the appropriate circuit diagram. Symbols used on diagrams Contact type Make (normally open) Break (normally closed) Normal duty M B

4.4

Settings Settings should be within those specified in the following tables.

4.4.1

Relay types MVAJ05 Standard armature gap Make Follow through just closed just open Force to make Break Contact gaps Force to break Break 1.5 to 1.25 0.5 0.6 25 to 30 1.25 to 1.5 25 to 30 mm mm mm grammes Mm grammes

Cut off contact (top left-hand viewed from front) Force to break Contact gap (measured at armature) 25 to 30 0.2 to 0.5 grammes mm

Technical Manual Types MVAJ 05, 10, 20 4.4.2 Relay types MVAJ10, MVAJ20 Standard flag Standard armature gap Make Follow through just closed just open Force to make Force to make (when less than 4 make) Break Contact gaps Force to break 1.5 to 1.4 0.5 0.6 26 to 29 30 to 35 1.25 to 1.5 26 to 29 Break Following flag 1.5 to 1.25 0.5 0.6 20 to 25 25 to 30 1.25 to 1.5 20 to 25

R8141D Page 15/34

Units mm mm mm grammes grammes

Mm grammes

Cut off contact (bottom right-hand viewed from front) Force to break Contact gap measured at the armature centre 25 to 30 0.4 to 0.6 20 to 25 0.4 to 0.6 Grammes mm

R8141D Page 16/34

Technical Manual Types MVAJ 05, 10, 20

5.

SPARES
When ordering spares, quote the full relay model number and any componentreference numbers, or briefly describe the part required.

5.1

Repairs Should the need arise for the equipment to be returned to Alstom Grid for repair, then the form at the back of this manual should be completed and sent with the equipment together with a copy of any commissioning test results.

Technical Manual Types MVAJ 05, 10, 20

R8141D Page 17/34

6.

CONNECTION DIAGRAMS
5 contact versions 01 MVAJ051 01 01 MVAJ053 01 01 MVAJ054 01 01 MVAJ055 01 10 contact versions 01 MVAJ101 01 01 MVAJ102 01 01 MVAJ103 01 01 MVAJ104 01 01 MVAJ105 01 20 contact versions 01 MVAJ201 01 01 MVAJ202 01 01 MVAJ203 01 01 MVAJ204 01 01 MVAJ205 01 self reset self reset (2s delayed reset) hand reset electrical reset hand and electrical reset self reset self reset (2s delayed reset) hand reset electrical reset hand and electrical reset self reset hand reset electrical reset hand and electrical reset

Where required, any specific diagram may be supplied on request. If the actual diagram number is not known, please provide the full model number and serial number. Typical diagrams follow.

Case earth Combination of output contacts


5M 4M 3M 2M 3B B B 2B B M M M 1B B M M M B B 1 3 5 7 9 11 2 4 6 8 M M M M M M M M

R8141D

Page 18/34

Output contacts to module terminals

10

11

12

Viewed from front

Contact description M: Make B: Break

22

24

25

26

Vx

27

28

A 2 4 6 8

1 3 5 7 9 11 RL1 5 (OP)

Module terminal block viewed from rear T1 RL1-A T3 T4 PR 27 T27

FIGURE 1: TYPICAL APPLICATION DIAGRAM MVAJ 051

Notes

T2 T22 T24 ZJ0401 T28 22 See Note 2 24 28

1 (a)

CT shorting links make before (b) and (c) disconnect

(b)

short terminals break before (c)

Technical Manual

(c)

long terminals

Types MVAJ 05, 10, 20

2 Link in for high burden Link out for low burden

Case earth Combination of output contacts Output contacts to module terminals

5 5M 4M 3M 2M 1B 2B 3B M B B B M M M B M M M M

1 3 5 7 9 11 2 4 6 8

Technical Manual

10

Types MVAJ 05, 10, 20

11

12

M M B B

M M M M

Viewed from front

Contact description M: Make B: Break

22

24

25

26

Vx

27

28

A 2 4 6 8

1 3 5 7 9 11 RL1 5 (OP)

Module terminal block viewed from rear T1 RL1-A T3 T4 PR 27 T27

FIGURE 2: TYPICAL APPLICATION DIAGRAM MVAJ 053


T2 T22 T24 ZJ0401 T28 22 24 28

Notes

1 (a)

CT shorting links make before (b) and (c) disconnect

See Note 2

(b)

short terminals break before (c)

(c)

long terminals

R8141D

Page 19/34

2 Link in for high burden Link out for low burden

R8141D

Case earth

Page 20/34

1 5M 4M 3M 2M 3B B B M B M 2B B M M B M 1B B M M M M 1 3 5 7 9 11 2 4 6 8 M M M M M

Combination of output contacts

Output contacts to module terminals

10

11

12

+
A 2 4 6 8 RL1 5 (OP) RL1-A T1 T3 T4 T6 (Reset) PR Reset 25 27 T5 T27 ZJ0401 T25 T26 T28 T2 T22

Vx

Viewed from front

Contact description M: Make B: Break

22

24

1 3 5 7 9 11

22 24 See Note 2

25

26

27

28

Module terminal block viewed from rear RL1

T24

FIGURE 3: TYPICAL APPLICATION DIAGRAM MVAJ 054


28 26

Notes

(a)

(b)

CT shorting links make before (b) and (c) disconnect

short terminals break before (c)

(c)

long terminals

Technical Manual

Types MVAJ 05, 10, 20

2 Link in for high burden Link out for low burden

Case earth

1 5M 4M 3M 2M 3B B B M B 2B B M M B 1B B M M M M M M 1 3 5 7 9 11 2 4 6 8 M M M M M

Combination of output contacts

Output contacts to module terminals

Technical Manual

Types MVAJ 05, 10, 20

10

11

12

+
A 2 4 6 8 RL1 5 (OP) RL1-A T1 T3 T4 RL1 (Reset) PR Reset 25 27 T6 T5 T27 ZJ0401 T25 T26 T28 T2 T22

Vx
1 3 5 7 9 11

Viewed from front

Contact description M: Make B: Break

22

22 24 T24 See Note 2

24

25

26

27

28

Module terminal block viewed from rear

Notes

FIGURE 4: TYPICAL APPLICATION DIAGRAM MVAJ 055

(a)

(b)

CT shorting links make before (b) and (c) disconnect

short terminals break before (c)

(c)

long terminals

28

2 Link in for high burden Link out for low burden

R8141D

Page 21/34

26

R8141D

Page 22/34

Case earth
10M 8M 6M 4M 2B 4B 6B
1 3 5 17 7 9 11 13 15 19 2 4 6 8 10 1214 1618 20

Combination of output contacts Output contacts to module terminals


M B B B M M B B M M M B M M M M M M M M M B B B M M B B M M M B M M M M M M M M

Viewed from front

1 3 5 7 9 11 13 15 17 19 21 23

2 4 6 8 10 12 14 16 18 20 22 24

25
B A

+
RL1 10 (OP) RL1-A T1 T3 T4 T2 T22

Vx

Contact description M: Make B: Break

26

27

28

2 4 6 8 10 12 14 16 18 20 1 3 5 7 9 11 13 15 17 19

22 24 See Note 2

Module terminal block viewed from rear

Notes

(a)

(b)

CT shorting links make before (b) and (c) disconnect

short terminals break before (c)

FIGURE 5: TYPICAL APPLICATION DIAGRAM MVAJ 101


T24 T21 T23 PR 27 T27 ZJ0393 T28 21 23 28

(c)

long terminals

2 Link in for high burden Link out for low burden

See Note 3

Technical Manual

Types MVAJ 05, 10, 20

3 Link for economising must be fitted.

Case earth
10M 8M 6M 4M 2B 4B 6B M B B B M M B B M M M B M M M M M M M M M B B B M M B B M M M B M M M M

Combination of output contacts Output contacts to module terminals


1 3 5 7 9 11 13 17 19 2 10 1214 1618 20 4 6 8 15

Technical Manual

M M M M

Types MVAJ 05, 10, 20

1 3 5 7 9 11

4 6 8 10 12

Viewed from front

Contact description M: Make B: Break

13 15

14 16

17 19 21
B A

18 20 22

+
RL1 10 (OP) T4 RL1-A T3 T1 25 RL1-B T9 ZJ0394 T2

Vx

2 4 6 8 10 12 14 16 18 20 1 3 5 7 9 11 13 15 17 19

23

24

25

26

27

28

Module terminal block viewed from rear

Notes

FIGURE 6: TYPICAL APPLICATION DIAGRAM MVAJ 102


PR 27 T27 T28

(a)

CT shorting links make before (b) and (c) disconnect

(b)

short terminals break before (c)

(c)

long terminals

R8141D

Page 23/34

28

Case earth Output contacts to module terminals

R8141D

1 10M 8M 6M 4M 2M 8B B B B B M B B B 6B B B B M M B B B M B 4B B B M M M B B M M 2B B M M M M B M M M M M M M 1 3 5 7 9 11 13 10 12 14 16 18 15 17 19 2 4 6 8 20 M M M M M M M M M M

Combinations of output contacts

Page 24/34

10

11

12

13

14

15

16

Viewed from front

17

18

Contact description M: Make B: Break

19

20

21

22

23

24

25

26

Vx

27

28

+
B

2 4 6 8 10 12 14 16 18 20 1 3 5 7 9 11 13 15 17 19 A

RL1 10 (OP) T2 22 T22 24

Module terminal block viewed from rear

Notes RL1-A T1 T3 T4

1. (a)

CT shorting links make before (b) and (c) disconnect

(b)

Short terminals break before (c)

FIGURE 7: TYPICAL APPLICATION DIAGRAM MVAJ 103


T24 T21 T23 PR 27 T27 ZJ0393 T28 21 23 28

See Note 2 See Note 3

(c)

Long terminals

2. Link in for high burden. Link out for low burden.

Technical Manual

Types MVAJ 05, 10, 20

3.

Do not fit link.

Combination of output contacts Output contacts to module terminals


1 3 5 7 9 11 13 15 17 19 2 4 6 8 10 1214 1618 20

Technical Manual

Case earth

10M 8M 6M 4M 2M

2B 4B 6B 8B

M B B B B

M M B B B

M M M B B

M M M M B

M M M M M

M B B B B

M M B B B

M M M B B

M M M M B

M M M M M

Types MVAJ 05, 10, 20

Viewed from front See Note 3

1 3 5 7 9 11 13 15 17 19 21 23

2 4 6 8 10 12 14 16 18 20 22 24

+
B A

Vx

Contact description M: Make B: Break

2 4 6 8 10 12 14 16 18 20 1 3 5 7 9 11 13 15 17 19

RL1 10 (OP) T2 22 T22 24 See Note 2

25

26

27

28

Module terminal block viewed from rear RL1-A

T1 T3 T4

Notes

1 RL1

(a)

(b)

CT shorting links make before (b) and (c) disconnect

T24 RL1-B (Reset) T11 T5 T21 T23

FIGURE 8: TYPICAL APPLICATION DIAGRAM MVAJ 104


PR Reset 25 27 T27 ZJ0393 T25 T26 T28

short terminals break before (c)

21 23 28 See Note 3

(c)

long terminals

2 Link in for high burden Link out for low burden

3 Link to enable reset inhibitor/economising coil.

R8141D

Page 25/34

26

R8141D

Case earth
10M 8M 6M 4M 2M 2B 4B 6B 8B
1 3 5 7 9 11 13 17 19 2 10 1214 1618 20 4 6 8 15

Combination of output contacts Output contacts to module terminals


M B B B B M M B B B M M M B B M M M M B M M M M M M B B B B M M B B B M M M B B M M M M B M M M M M

Page 26/34

1 3 5 7 9 11

4 6 8 10 12

Viewed from front

13 15

14 16

17 19 21

18 20 22
B A

+
RL1 10 (OP) RL1-A T1 T3 T4 RL1-B (Reset) PR Reset 25 27 T11 T5 T27 ZJ0393 T25 T26 T2 T22

Vx

Contact description M: Make B: Break

23

24

2 4 6 8 10 12 14 16 18 20 1 3 5 7 9 11 13 15 17 19

22 24 See Note 2

25

26

27

28

Module terminal block viewed from rear

Notes RL1

(a)

CT shorting links make before (b) and (c) disconnect

T24 T21 T23 T28

21 23 28 26 See Note 3

FIGURE 9: TYPICAL APPLICATION DIAGRAM MVAJ 105

(b)

short terminals break before (c)

(c)

2.

Technical Manual

Types MVAJ 05, 10, 20

3.

long terminals Link in for high burden Link out for low burden Link to enable reset inhibitor/economising coil

Case earth Table 2 Output contacts to module terminals


Cont. stack

Table 1 Combinations of output contacts (See Note 4)


Combination L/h R/h
stack stack L/h 29 3133 3537 3941 4345 4730 3234 3638 4042 4446 48 R/h 1 3 5 7 9 1113 1517 19 2 4 6 8 10 1214 1618 20
1 M M M M M M M M M M 2 3 4 B B B M M B B B M M B B M M M B B M M M B M M M M B M M M M 20M 18M 16M 14M 12M 10M 8M 12B 4 4 10B 4 3 8B 3 3 6B 3 2 4B 2 2 2B 2 1 1 1

Technical Manual

Types MVAJ 05, 10, 20

29 31 33 35 37 39 41 43 45 47

30 32 34 36 38 40 42 44 46 48

Module terminals Contact description: M: Make B: Break

1 3 5 7 9 11 13 15 17 19 21 23

2 4 6 8 10 12 14 16 18 20 22 24

Left hand

Right hand

25

26

27

28

Module terminal block viewed from rear

30 32 34 36 38 40 42 44 46 48 29 31 33 35 37 39 41 43 45 47 A B A

2 4 6 8 10 12 14 16 18 20 1 3 5 7 9 11 13 15 17 19

Contact stacks viewed from front

Notes

1
RL1 10 (OP)

(a)

(b)

CT shorting links make before (b) and (c) disconnect

Vx

short terminals break before (c) T1 RL1-A RL3-A T4/T9 T3/T8

RL3 10 (OP)

(c)

long terminals T2 T7 T20 22 T22 24 T24 T21 T23 ZJ0393


PR 27

2 Link in for high burden Link out for low burden

FIGURE 10: TYPICAL APPLICATION DIAGRAM MVAJ 201


21 23 T27 T28 28

3 Link for economising must be fitted.

4 The numbers quoted for left hand and right hand stacks in Table 1 are code numbers used for cross references to module terminals in Table 2.

See Note 2 See Note 3

R8141D Page 27/34

R8141D

Table 1 Combinations of output contacts Output contacts to module terminals


R/h Combination L/h stack stack 20M 18M 16M 14M 12M 10M 8M 12B 4 4 10B 4 3 8B 3 3
4 B B B M M B B B M M

Table 2

Case earth

Page 28/34

29

30

31

32

Cont. Module terminals stack L/h 29 31 33 3537 39 41 43 45 47 30 32 34 36 38 40 42 44 46 48 R/h

33

34

2B 4B 6B 3 2
3 B B M M M B B M M M

1 2 2 2
2 B M M M M B M M M M

1 1
1

35

36

1 3 5 7 9 11 13 10 12 14 16 18 15 17 19 2 4 6 8 20 M M M M M M M M M M

See Note 2

10

37

38

11

12

39

40

13

14

41

42

Contact description M: Make B: Break

15

16

43

44

17

18

45

46

Left hand

Right hand

19

20

47

48

21

22

49

50

23

24

51

52

25

26

53

54

Contact stacks viewed from front

27

28

55

56

30 32 34 36 38 40 42 44 46 48 29 31 33 35 37 39 41 43 45 47 A B A

2 4 6 8 10 12 14 16 18 20 1 3 5 7 9 11 13 15 17 19

Module terminal block viewed from rear

Notes

Vx
RL1 10 (OP)

1. (a)

CT shorting links make before (b) and (c) disconnect

RL3 10 (OP)

(b)

Short terminals break before (c)

T4 RL1-A RL3-A T5/T1 RL1-B T9


27

T2

T6

T8

(c)

Long terminals

FIGURE 11: TYPICAL APPLICATION DIAGRAM MVAJ 202


T3/T7
25 PR

2.

The numbers quoted for left hand and right hand stacks in Table 1 are code numbers used for cross references to module terminals in Table 2.

ZJ0393 T27 T28 28

Technical Manual Types MVAJ 05, 10, 20

Table 1 Combinations of output contacts Output contacts to module terminals (see Note 3) Combination
20M 18M 1 2 3 4 5 B B B B M B B B B M B B B M M B B B M M B B M M M B B M M M B M M M M B M M M M M M M M M M M M M M 16M 14M 12M 10M 8M 6M 4M 16B 5 5 14B 5 4 12B 4 4 10B 4 3 8B 3 3 6B 3 2 4B 2 2 2B 2 1 1 1 L/h R/h stack stack

Table 2

Case earth

29

30

31

32

33

34

35

36

Cont. Module terminals stack L/h 2931 3335 3739 4143 4547 3032 3436 3840 4244 4648 R/h 1 3 5 7 9 11 1315 1719 2 4 6 8 1012 1416 1820

Contact description M: Make B: Break

Technical Manual

10

37

38

11

12

39

40

Types MVAJ 05, 10, 20

13

14

41

42

15

16

43

44

17

18

45

46

19

20

47

48

Left hand

Right hand

21

22

23

24

25

26

27

28

Module terminal block viewed from rear

30 32 34 36 38 40 42 44 46 48 B A B A

29 31 33 35 37 39 41 43 45 47

2 4 6 8 10 12 14 16 18 20

1 3 5 7 9 11 13 15 17 19

Contact stacks viewed from front

Vx
RL1 10 (OP)

Notes

1 (a)

CT shorting links make before (b) and (c) disconnect

RL3 10 (OP)

(b)

short terminals break before (c)

(c)

long terminals

T1 RL1-A RL3-A T4/T9 T3/T8

T2

T7

T20 22 T22 24 T24 T21 T23 ZJ0393 21 23 See Note 3 See Note 2

FIGURE 12: TYPICAL APPLICATION DIAGRAM MVAJ 203


PR 27

2 Link in for high burden Link out for low burden

3 Do not fit link

4 The numbers quoted for left hand and right hand stacks in Table 1 are codenumbers used for cross references to module terminals in Table 2.

R8141D

Page 29/34

T27

T28

28

Case earth Table 2 Output contacts to module terminals


Cont. stack

R8141D

Table 1 Combinations of output contacts


Combination L/h R/h
stack stack L/h 29 3133 3537 39 41 4345 4730 3234 3638 40 42 4446 48 R/h 1 3 5 7 9 1113 1517 19 2 4 6 8 10 1214 16 18 20
M B B B B B B B M B B B B M B B M M B B B M M B M M M B B M M M M M M M B M M M M M M M M M M M M M 1 2 3 4 5

Page 30/34

Module terminals (See Note 4) Contact description M: Make B: Break

20M 18M 16M 14M 12M 10M 8M 6M 4M 16B 5 5 14B 5 4 12B 4 4 10B 4 3 8B 3 3 6B 3 2 4B 2 2 2B 2 1

1 3 5 7 9 11 13 15 17 19 21 23 2 4 6 8 10 12 14 16 18 20 22 24 Left hand Right hand 26 28 55 56 53 54 25 27

29 31 33 35 37 39 41 43 45 47 49 51 30 32 34 36 38 40 42 44 46 48 50 52

Contact stacks viewed from front

Module terminal block viewed from rear

30 32 34 36 38 40 42 44 46 48 29 31 33 35 37 39 41 43 45 47 1 3 5 7 9 11 13 15 17 19 A A B 2 4 6 8 10 12 14 16 18 20 B

Notes

Vx
CT shorting links make before (b) and (c) disconnect short terminals break before (c) long terminals
RL1 20 (OP) RL3 20 (OP)

(a)

(b)

(c)

2 Link in for high burden Link out for low burden

T1 RL1-A T3/T8 RL3-A T4/T9 RL1 RL3 RL3-B T5/T6 RL1-B T10/T11 ZJ0393

T2

T7

T20 22 T22 24 T24 T21 T23 21 23 See Note 3 See Note 2

3 Link for economising must be fitted.

4 The numbers quoted for left hand and right hand stacks in Table 1 are code numbers used for cross references to module terminals in Table 2.

FIGURE 13: TYPICAL APPLICATION DIAGRAM MVAJ 204


(Reset coils)
PR 27

T27
Reset 25

T28

28

Technical Manual

Types MVAJ 05, 10, 20

T25

T26

26

Case earth Output contacts to module terminals


Cont. stack

Table 1 Combinations of output contacts


Combination L/h R/h
stack stack L/h 29 3133 3537 39 41 4345 4730 3234 3638 40 42 4446 48 R/h 1 3 5 7 9 1113 1517 19 2 4 6 8 10 1214 16 18 20
M B B B B B B B M B B B B M B B M M B B B M M B M M M B B M M M M M M M B M M M M M M M M M M M M M 1 2 3 4 5

Table 2

Module terminals (See Note 4) Contact description M: Make B: Break

20M 18M 16M 14M 12M 10M 8M 6M 4M 16B 5 5 14B 5 4 12B 4 4 10B 4 3 8B 3 3 6B 3 2 4B 2 2 2B 2 1

Technical Manual

Types MVAJ 05, 10, 20

1 3 5 7 9 11 13 15 17 19 21 23
1 1

2 4 6 8 10 12 14 16 18 20 22 24 Left hand Right hand 26 28


30 32 34 36 38 40 42 44 46 48 29 31 33 35 37 39 41 43 45 47 A B A B 2 4 6 8 10 12 14 16 18 20 1 3 5 7 9 11 13 15 17 19

29 31 33 35 37 39 41 43 45 47 30 32 34 36 38 40 42 44 46 48

25

27

Contact stacks viewed from front

Module terminal block viewed from rear

Vx
RL1 20 (OP)

Notes CT shorting links make before (b) and (c) disconnect short terminals break before (c)

RL3 20 (OP)

(a)

(b)

T1 RL1-A T3/T8 RL3-A T4/T9 RL1 RL3 RL1-B RL3-B (Reset coils) T5/T6 T10/T11

T2

T7

T20 22 T22 24 T24 T21 T23 ZJ0393 21 23 See Note 3 See Note 2

(c) long terminals

2 Link in for high burden Link out for low burden

3 Link for economising must be fitted.

FIGURE 14: TYPICAL APPLICATION DIAGRAM MVAJ 205


PR 27

4 The numbers quoted for left hand and right hand stacks in Table 1 are code numbers used for cross references to module terminals in Table 2.

T27
Reset 25

T28

28

R8141D

Page 31/34

T25

T26

26

R8141D Page 32/34

Technical Manual Types MVAJ 05, 10, 20

7.

COMMISSIONING TEST RECORD


Date Station Relay Model No. Relay Rated Lower Nominal Voltage: LNV Visual inspection Operational tests Operating coil Check operation at 60% LNV Check operating time at 100% LNV Check contact continuity* Resetting coil Check electrical reset at 60% LNV Check reset time at 100% LNV (MVAJ102 only) Check unit resets correctly Check flags / cover All Voltage tests to be applied as step changes from zero Volts *Contact continuity test should be done by applying 5A current & measuring the voltage across the output contact terminals. Remarks: _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ ms ms Site Circuit Serial No.

___________________

Tested by

Company

Witness

Company

Date

Technical Manual Types MVAJ 05, 10, 20

R8141D Page 33/34

REPAIR FORM
Please complete this form and return it to Alstom Grid with the equipment to be repaired. This form may also be used in the case of application queries. Alstom Grid St. Leonards Works Stafford ST17 4LX England For : After Sales Service Department

Customer Ref:

___________________

Model No: Serial No:

_________________ _________________

Alstom Grid Contract Ref: ___________________ Date: ___________________

1. What parameters were in use at the time the fault occurred? AC Volts DC Volts AC current Frequency ___________________ ___________________ ___________________ ___________________ Main VT/Test set Battery/Power supply Main CT/Test set

2. Which type of test was being used? 3. Were all the external components fitted where required? (Delete as appropriate) 4. List the relay settings being used Yes / No

5. What did you expect to happen?

continued overleaf

R8141D Page 34/34

Technical Manual Types MVAJ 05, 10, 20

6. What did happen?

7. When did the fault occur? Instant Time delayed By how long? Yes / No Yes / No _________________ Intermittent (Delete as appropriate) Yes / No

8. What indications if any did the relay show?

9. Was there any visual damage?

10. Any other remarks which may be useful:

Signature

Title

Name (in capitals)

Company name

PUBLICATION: R8141D Alstom Grid Substation Automation Solutions Business www.alstom.com/grid Alstom Grid Worldwide Contact Centre online 24 hours a day: +44 (0) 1785 250 070 www.alstom.com/grid/contactcentre/

You might also like