Contents
Page Application Versions Typical uses Ratings Requirements Security of investment Cost-efficiency Service friendliness Technical Data Electrical data, dimensions Room planning Product Range NXAIR NXAIR M NXAIR P Design Basic panel design, operation, compartments Components NXACT vacuum circuit-breaker Other switching devices Current transformers, post insulators Low-voltage equipment Standards Standards, specifications, guidelines Notes 25 to 27 20 and 21 22 23 24 14 to 19 8 and 9 10 and 11 12 and 13
R-HA25-310 eps
Application
Versions
Withdrawable circuit-breaker switchgear types NXAIR, NXAIR M and NXAIR P are factory-assembled, type-tested, metal-enclosed and metal-clad switchgear for indoor installation according to IEC 60 298/ VDE 0670 Part 6.
2 3 and 4 4
6 and 7 7
R-HA25-311 eps
5 5 5
NXAIR P panel Maximum ratings 15 kV / 50 kA / 4000 A NXAIR M panel Maximum ratings 15 kV / 31.5 kA / 2500 A 17 kV / 25 kA / 2500 A .5 24 kV / 25 kA / 2500 A
Siemens AG 2003
R-HA25-312 eps
Application
Typical uses
R-HA25-326 eps
Application Industry
R-HA25-308 eps
R-HA25-328 eps
R-HA25-327 eps
NXAIR M switchgear
Application Industry
Application
Typical uses
NXAIR, NXAIR M and NXAIR P circuit-breaker switchgear types are used in transformer and switching substations, e.g. Application Public power supply system
Ratings
Electrical data (maximum values) of the NXAIR family
Ratings Switchgear up to 7.2 kV Rated voltage Rated frequency Rated short-duration power-frequency withstand voltage Rated lightning impulse withstand voltage Rated short-time withstand current, 3 s Rated peak withstand current at 50 Hz Rated short-circuit breaking current Rated short-circuit making current at 50 Hz Rated normal current of busbar Rated normal current of feeders Switchgear up to 12 kV Rated voltage Rated frequency Rated short-duration power-frequency withstand voltage Rated lightning impulse withstand voltage Rated short-time withstand current, 3 s Rated peak withstand current at 50 Hz Rated short-circuit breaking current Rated short-circuit making current at 50 Hz Rated normal current of busbar Rated normal current of feeders Switchgear up to 15 kV Rated voltage Rated frequency Rated short-duration power-frequency withstand voltage Rated lightning impulse withstand voltage Rated short-time withstand current, 3 s Rated peak withstand current at 50 Hz Rated short-circuit breaking current Rated short-circuit making current at 50 Hz Rated normal current of busbar Rated normal current of feeders Switchgear up to 17.5 kV Rated voltage Rated frequency Rated short-duration power-frequency withstand voltage Rated lightning impulse withstand voltage Rated short-time withstand current, 3 s Rated peak withstand current at 50 Hz Rated short-circuit breaking current Rated short-circuit making current at 50 Hz Rated normal current of busbar Rated normal current of feeders Switchgear up to 24 kV Rated voltage Rated frequency Rated short-duration power-frequency withstand voltage Rated lightning impulse withstand voltage Rated short-time withstand current, 3 s Rated peak withstand current at 50 Hz Rated short-circuit breaking current Rated short-circuit making current at 50 Hz Rated normal current of busbar Rated normal current of feeders 24 kV 50/60 Hz 50 kV 125 kV 25 kA 63 kA 25 kA 63 kA 2500 A 2500 A 17.5 kV 50/60 Hz 38 kV 95 kV 25 kA 63 kA 25 kA 63 kA 2500 A 2500 A 15 kV 50/60 Hz 35 kV 95 kV 50 kA 125 kA 50 kA 125 kA 4000 A 4000 A 12 kV 50/60 Hz 28 kV 75 kV 50 kA 125 kA 50 kA 125 kA 4000 A 4000 A 7.2 kV 50/60 Hz 20 kV 60 kV 50 kA 125 kA 50 kA 125 kA 4000 A 4000 A Rated values (max.)
s Power stations s Cement industry s Automobile industry s Iron and steel works s Rolling mills s Mining industry s Textile, paper and food industries s Chemical industry s Petroleum industry s Pipeline installations s Offshore installations s Electrochemical plants s Petrochemical plants s Shipbuilding industry s Diesel power plants s Emergency power supply installations s Lignite open-cast mines s Traction power supplies
Requirements
Security of investment
Modular structure
Module compartment and/or
Cost-efficiency
Reliability
Type and routine-tested Standardized, NC production
Service friendliness
Flexibility
Wall-standing or free-
Maintenance-free design
Vacuum circuit-breakers
standing arrangement
Cable connection from front
processes
Quality assurance in accord-
or rear
Available as truck-type or
withdrawable switchgear
Optional left or right-hand
can be replaced
Flexibile operation as
symbols
Mechanical switch position
arc up to 31.5 kA in the connection compartment of a panel in combination with pressure-resistant compartmentalization without any additional measures NXACT
Maintenance-free vacuum
current transformers
Screw-type fixed contacts on
bushing-type current transformers can be easily replaced from front (from module compartment) Re-availability
Easy replacement of com-
indicators on panel front for circuit-breaker, movable part and earthing switch
Logical interlocks prevent
circuit-breaker
Circuit-breaking, disconnect-
maloperation
Option: Verification of safe
isolation from supply with high-voltage door closed, by means of a voltage detection system according to IEC 61 243-5 / VDE 0682 Part 415
Earthing of feeders by means
SIPROTEC 4 with integrated protection, control, communications, operating and monitoring functions
Can be integrated in overall
transformers offer selective shutdown for an arc up to 31.5 kA in the connection compartment of a panel
Busbar voltage transformer
and make-proof earthing switch up to 31.5 kA in a separate additional compartment with pressure-resistant partition to busbar compartment for 40 kA and 50 kA in metering panel
Confinement of an internal
openings, control elements and switch position indicators on high-voltage door, as well as secondary equipment in door of low-voltage compartment
each compartment
Option: Pressure-resistant
floor cover
Internal control cables run in
Technical Data
Electrical data, dimensions
NXAIR
Rated voltage frequency short-duration power-frequency withstand voltage kV 7.2 Hz 50 kV 20 12 50 28 ** 75 25 25 63 63 2500 2500 800 *
Ratings
NXAIR M Ratings
Rated voltage frequency short-duration power-frequency withstand voltage short-circuit breaking current kV 7.2 kV 20 12 28 75 31.5 31.5 80 80 2500 15 35 95 31.5 31.5 80 80 2500 17.5 38 95 25 25 63 63 2500 24 50 125 25 25 63 63 2500 Hz 50/60 50/60 50/60 50/60 50/60
lightning impulse withstand voltagekV 60 short-circuit breaking current max. kA 25 short-time withst. current, 3 s max. kA 25 short-circuit making current peak withstand current normal current of busbar normal current of feeders: with circuit-breaker with switch max. A max. A 2500 800 * max. kA 63 max. kA 63 max. A 2500
lightning impulse withstand voltage kV 60 max. kA 31.5 short-time withst. current, 3 s max. kA 31.5 short-circuit making current 1) max. kA 80 peak withstand current 1) normal current of busbar normal current of feeders: with circuit-breaker max. A with switch max. A with vacuum contactor max. A 1) Values for 50 Hz max. kA 80 max. A 2500
2500 2500 2500 2500 2500 800 * 800 * 800 * 800 * 800 * 400 *
NXAIR
Dimensions
NXAIR M Dimensions
HA25-2686a eps
H2
H1
H1
H2
H3
All panel types Width B For all panels Height H1 Standard H2 With high low-voltage compartment With natural ventilation With additional compartment for busbar fittings Depth T For all panels
HA25-2687b eps
All panel types Width B Standard At 24 kV / 2500 A For vacuum contactor panel Height H1 With standard low-voltage compartment H2 With mounted air guides (standard) With high low-voltage compartment With natural ventilation H3 With additional compartment for busbar fittings Depth T Single busbar Vacuum contactor panel Double busbar in back-to-back arrangement cubicle-type 2) metal-clad cubicle-type 2) metal-clad
1350
2) For 24 kV only
Technical Data
Electrical data, dimensions
NXAIR P
Rated voltage frequency short-duration power-frequency withstand voltage lightning impulse withstand voltage short-circuit breaking current short-time withst. current, 3 s short-circuit making current 1) peak withstand current 1) normal current of busbar normal current of feeders: with circuit-breaker with switch with vacuum contactor 1) Values for 50 Hz
HA25-2690c eps
Ratings
kV 7.2 Hz 50/60 kV 20 kV 60
Single-row arrangement (plan view) for single-busbar switchgear For dimensions B (width) and T (depth) refer to table on page 6 1) For panel replacement: Control aisle W 1410 mm
Single-row arrangement (plan view) for single-busbar switchgear For dimensions B (width) and T (depth) refer to table on page 6 2) For panel replacement: Control aisle W 1700 mm For back-to-back arrangement and face-to-face arrangement, the same room dimensions apply as for single-row arrangement. For back-to-back arrangement, a 1200 mm control aisle is required on the left or on the right of the switchgear.
H1
H2
H3
NXAIR P
HA25-2691c eps
B1 B2 All panel types (except vacuum contactor panel) Width B1 w 2000 A (standard) B2 > 2000 A (with panel ventilation) Height H1 With standard low-voltage compartment H2 With top-mounted pressure relief duct H3 With forced ventilation (4000 A) Depth T Single busbar Double busbar in back-to-back arrangement
800 1000 2225 2550 2710 1635 3320 Single-row arrangement (plan view) for single-busbar switchgear For dimensions B1, B2 (width) and T (depth) refer to table on the left 400 2225 2550 1650 3) For panel replacement: Control aisle W 1800 mm For back-to-back arrangement and face-to-face arrangement, the same room dimensions apply as for single-row arrangement. For back-to-back arrangement, a 1200 mm control aisle is required on the left or on the right of the switchgear.
1450 3)
32 100 32 100
Vacuum contactor panel Width B1 Standard Height H1 With standard low-voltage compartment H2 With top-mounted pressure relief duct Depth T Single busbar
Dimensions in mm
B1, B2
B1, B2
50
1350 2)
32 100
32 100
NXAIR P
Dimensions
1250 1)
32 100
32 100
50
Product Range
NXAIR Panels
Disconnecting panel Switch panel Spur panel
Circuit-breaker panel
and/or
and/or
and/or
and/or
and/or
and/or
and/or
and/or
or
and/or
or
and/or
or
and/or
HA25-2660c eps
and/or
or
and/or
or
and/or
or
and/or
HA25-2658a eps
and/or
HA25-2659a eps
and/or
or
and/or
or
and/or
and/or
Components
Current transformer Make-proof earthing switch Busbar connection (bars only) Panel ventilation as natural ventilation Capacitive voltage detection system Cable sealing ends 1) max. 4 x 500 mm2 per phase Bar feeder HV HRC fuse
NXACT vacuum circuit-breaker module Disconnecting module or fixed-mounted connection Vacuum switch module
For other components for busbar and connection compartments refer to page 15
1) The details refer to conventional RXS single-core sealing ends for XLPE cables or other makes with similar dimensions.
Voltage transformer
HA25-2692a eps
or
or
or
or
or
and/or
Product Range
NXAIR Panels
Metering panel
Withdrawable panel
and/or
and/or
or
or
or
and/or
or
or
or
HA25-2662a eps
Components
Current transformer Capacitive voltage detection system HV HRC fuse
For other components for busbar and connection compartments refer to page 15
NXACT vacuum circuit-breaker module Disconnecting module or fixed-mounted connection Withdrawable voltage transformer with primary fuses Withdrawable voltage transformer
HA25-2661a eps
and/or
and/or
Product Range
NXAIR M Panels
Circuit-breaker panel Disconnecting panel Switch panel Vacuum contactor panel (7.2 kV)
and/or
and/or
and/or
or
and/or
or
and/or or
and/or
or
and/or
or
and/or
or
and/or
or
or
or
and/or
HA25-2664a eps
Components
Current transformer Panel ventilation as natural ventilation Capacitive voltage detection system Cable sealing ends 1) max. 4 x 500 mm2 per phase Bar feeder NXACT vacuum circuit-breaker module Disconnecting module
HA25-2665a eps
and/or
and/or
and/or
HA25-2668a eps
Voltage transformer
For other components for busbar and connection compartments refer to page 17
1) The details refer to conventional RXS single-core sealing ends for XLPE cables or other makes with similar dimensions.
Vacuum switch module with HV HRC fuses Vacuum contactor module with HV HRC fuses
HV HRC fuse
10
HA25-2669a eps
and/or
or
and/or
or
and/or
and/or
and/or
Product Range
NXAIR M Panels
Bus sectionalizer (mirror-image installation also possible) Metering panel Panels for double-busbar applications Double-busbar switchgear consists of components from the range of single-busbar panels. It can have the following designs:
Face-to-face arrangement Back-to-back arrangement
Withdrawable panel Bus riser panel
Face-to-face arrangement
Panels from the range of
and/or
and/or
and/or
or
or
HA25-2666a eps
or
and/or
and/or
or
and/or
or
or
or
and/or
HA25-2670a eps
and/or
Circuit-breaker panel with current and voltage transformers Disconnecting panel, with optional current transformers Components
Current transformer Panel ventilation as natural ventilation Capacitive voltage detection system HV HRC fuse
Note For other components for busbar and connection compartments refer to page 17 Double-busbar switchgear with top-mounted busbar disconnector unit on request
Voltage transformer
11
Product Range
NXAIR P Panels
Circuit-breaker panel Disconnecting panel Switch panel Vacuum contactor panel (7.2 kV, 12 kV)
and/or
or
and/or
or
and/or
or
and/or or
and/or
and/or
and/or
and/or
and/or
and/or
and/or
or
or
HA25-2672a eps
Components
Current transformer Capacitive voltage detection system Cable sealing ends 1) max. 6 x 500 mm2 per phase 2) Bar feeder NXACT vacuum circuit-breaker module Disconnecting module or fixed-mounted connection Vacuum switch module with HV HRC fuses Vacuum contactor module with HV HRC fuses
HA25-2673a eps
and/or
and/or
HA25-2674a eps
Voltage transformer
For other components for busbar and connection compartments refer to page 19
1) The details refer to conventional RXS single-core sealing ends for XLPE cables or other makes with similar dimensions. 2) Exception: Switch panel
HV HRC fuse
12
HA25-2675a eps
and/or
and/or
and/or
and/or
Product Range
NXAIR P Panels
Bus sectionalizer (mirror-image installation also possible) Metering panel Panels for double-busbar applications Double-busbar switchgear consists of components from the range of single-busbar panels. It can have the following designs:
Face-to-face arrangement Back-to-back arrangement
Withdrawable panel Bus riser panel
Face-to-face arrangement
Panels from the range of
HA25-2676a eps
and/or
and/or
or
or
HA25-2679c eps
and/or
Circuit-breaker panel with current and voltage transformers Disconnecting panel, with optional current transformers Components
Current transformer Busbar connection (bars only) Capacitive voltage detection system NXACT vacuum circuit-breaker module Withdrawable voltage transformer with primary fuses Withdrawable voltage transformer
Voltage transformer
For other components for busbar and connection compartments refer to page 19
HA25-2698 eps
13
Design
NXAIR Panel design, operation
Basic panel design (example) Features
Integrated mechanical
HA25-2611c eps
tion indicators for circuitbreaker, movable part and earthing switch can be observed without opening the high-voltage door
Unambiguous assignment of
14 15 16 17
B A
22 23
access openings and control elements to the corresponding switch position indicators
All switching operations
24 25 26
C
28 29
safe isolation from supply of feeder or busbar by means of a capacitive voltage detection system on the panel front Interlocks
Interlocking conditions are
1 Door of low-voltage compartment 2 Protection device 3 Option: Capacitive voltage detection system for feeder and busbar 4 High-voltage door to module compartment 5 Door knob for opening the high-voltage door 7 Mechanical switch position indicator and access opening for movable part 8 Closing spring charged indicator and operating cycle counter 9 Mechanical switch position indicator for switching device 10 ON/OFF pushbuttons for switching device 11 Mechanical switch position indicator and access opening for make-proof earthing switch 12 Mimic diagram
14 Pressure relief duct 15 Busbars 16 Bushing-type insulator 17 Bushing-type current transformer 18 Make-proof earthing switch 19 Cable connection for 4 cables per phase 20 Cable sealing ends 21 Cable bracket 22 Low-voltage plug connector 23 Movable part 24 Combined operating and interlocking unit for circuit-breaker, movable part and earthing switch 25 Vacuum interrupters 26 Contact system 28 Earthing busbar 29 Option: Truck
switchgear module prevents insertion of similar switchgear modules for lower rated normal currents into panels with higher rated normal currents
Option: Interlocking of
A B C D E
Module compartment Busbar compartment Connection compartment Vacuum circuit-breaker module Low-voltage compartment
interlocks
14
Design
NXAIR Compartments
Busbar compartment
Enclosure made of
Module compartment
Enclosure made of
Connection compartment
Enclosure made of
sendzimir-galvanized sheet-steel
Pressure relief upwards Panel front powder-coated
sendzimir-galvanized sheet-steel
Pressure relief upwards Option: Busbar transverse
sendzimir-galvanized sheet-steel
Pressure relief upwards
bolted from panel to panel For rated normal currents up to 2500 A Option: Insulated busbars
Pressure-resistant partitions
supporting busbars and for accommodating upper fixed contacts for switchgear module
Option: Max. 3 bushing-type
low-voltage plug connector for connection of switchgear modules to auxiliary voltage circuits
Module compartment to ac-
current transformers
Option: Coupling electrode
floor cover
Option: Deep bottom pan,
for capacitive voltage detection system Additional compartments (optional) for busbar fittings
Separate, pressure-resistant
commodate components for implementing various panel versions with: NXACT vacuum circuit-breaker module Disconnecting module Vacuum switch module Metering module
With manual operating mechanism Option: With motor operating mechanism integrated in switchgear module In addition to standard interlocking of earthing switch/ movable part, optionally lockable or with electromagnetic interlock
Surge arresters or limiters
compartment
Pressure-resistant wall with
Surge arresters for protecting the switchgear against external overvoltages Surge limiters for protecting consumers against switching overvoltages
stalling the following components (but not for panels with natural ventilation): Voltage transformers Current transformers in run of busbar Surge arresters Busbar earthing switch Busbar connection (bars only)
15
Design
NXAIR M Panel design, operation
Operation at the panel Basic panel design (example) Features
Integrated mechanical switch
30
30
HA25-2641c eps
tion indicators for circuitbreaker, movable part and earthing switch can be observed without opening the high-voltage door
Unambiguous assignment of
1 2 3 4 5 7 8 9 10
1234
B
14 15
E A
22 23
access openings and control elements to the corresponding switch position indicators
All switching operations
16
D
17 18
24 25 26
safe isolation from supply of feeder or busbar by means of a capacitive voltage detection system on the panel front Interlocks
Interlocking conditions are
11 12
19 20 21
27 28 29
Circuit-breaker panel 1 Door of low-voltage compartment 2 Protection device 3 Option: Capacitive voltage detection system for feeder and busbar 4 High-voltage door to module compartment 5 Door knob for opening the high-voltage door 7 Mechanical switch position indicator and access opening for movable part 8 Closing spring charged indicator and operating cycle counter 9 Mechanical switch position indicator for switching device 10 ON/OFF pushbuttons for switching device 11 Mechanical switch position indicator and access opening for make-proof earthing switch 12 Mimic diagram 14 Pressure relief duct 15 Busbars 16 Bushing-type insulator 17 Bushing-type current transformer 18 Make-proof earthing switch 19 Cable connection for 4 cables per phase 20 Cable sealing ends 21 Cable bracket
21 20 19 17 18 16 15
Metal-clad version
HA25-2642b eps
30
B A
22 23 24 25 26
module prevents insertion of similar switchgear modules for lower rated normal currents into panels with higher rated normal currents
Interlocking of high-voltage
interlocks
28 29
A B C D E
Module compartment Busbar compartment Connection compartment Vacuum circuit-breaker module Low-voltage compartment Siemens HA 25.71 2003
22 Low-voltage plug connector 23 Movable part 24 Combined operating and interlocking unit for circuit-breaker, movable part and earthing switch
Cubicle-type version (feature: common module and connection compartment) 25 Vacuum interrupters 26 Contact system 27 Lower partition 28 Earthing busbar 29 Option: Truck 30 Air guide
16
Design
NXAIR M Compartments
Module compartment
Enclosure made of
Busbar compartment
Enclosure made of
Connection compartment
Enclosure made of
sendzimir-galvanized sheet-steel
Pressure relief upwards Panel front powder-coated
sendzimir-galvanized sheet-steel
Pressure relief upwards Option: Busbar transverse
sendzimir-galvanized sheet-steel
Pressure relief upwards: In metal-clad panels through rear pressure relief duct In cubicle-type panels through module compartment Suitable for connection of:
bolted from panel to panel For rated normal currents up to 2500 A Option: Insulated busbars
Pressure-resistant partitions
supporting busbars and for accommodating upper fixed contacts for switchgear module
Option: Max. 3 bushing-type
current transformers
Option: Coupling electrode
for capacitive voltage detection system Additional compartments (optional) for busbar fittings
Separate, pressure-resistant
accommodate components for implementing various panel versions with: NXACT vacuum circuit-breaker module Disconnecting module Vacuum contactor module Vacuum switch module Metering module lower partition to connection compartment for 24 kV
floor cover
Option: Deep bottom pan,
With manual operating mechanism Option: With motor operating mechanism integrated in switchgear module In addition to standard interlocking of earthing switch/ movable part, optionally lockable or with electromagnetic interlock
Surge arresters or limiters
compartment
Pressure-resistant wall with
Surge arresters for protecting the switchgear against external overvoltages Surge limiters for protecting consumers against switching overvoltages
stalling the following components (but not for panels with natural ventilation): Voltage transformers Make-proof busbar earthing switch with manual operating mechanism Busbar connection (bars only)
17
Design
NXAIR P Panel design, operation
Operation at the panel Basic panel design (example) Features
Integrated mechanical switch
position indicators in the mimic diagram tion indicators for circuitbreaker, movable part and earthing switch can be observed without opening the high-voltage door
Unambiguous assignment of
HA25-2681c eps
1 2 3 4 5 6
14 15 16 17
E A
access openings and control elements to the corresponding switch position indicators
All switching operations
23
26 25
D
18 19 20
24 22 31
safe isolation from supply of feeder or busbar by means of a capacitive voltage detection system on the panel front Interlocks
Interlocking conditions are
C
21
28 29
13
Circuit-breaker panel
32
32
switchgear module prevents insertion of similar switchgear modules for lower rated normal currents into panels with higher rated normal currents
Option: Interlocking of
4000 A panel with forced ventilation 1 Door of low-voltage compartment 2 Protection device 3 Option: Capacitive voltage detection system for feeder and busbar 4 High-voltage door to module compartment 5 Mechanical lifting mechanism for opening the high-voltage door 6 Locking device for high-voltage door 9 ON/OFF pushbuttons for switching device 10 Mechanical switch position indicator and access opening for movable part 11 Mechanical switch position indicator and access opening for make-proof earthing switch 12 Mimic diagram 13 Ventilation duct 14 Pressure relief duct 15 Busbars 16 Bushing-type insulator 17 Bushing-type current transformer 18 Make-proof earthing switch 19 Cable connection for 6 cables per phase 20 Cable sealing ends 21 Cable bracket 22 Low-voltage plug connector 23 Movable part 24 Operating unit 25 Vacuum interrupters 26 Contact system 28 Earthing busbar 29 Option: Truck 31 Interlocking unit for circuitbreaker and earthing switch 32 Fan unit with fan
interlocks
A B C D E
Module compartment Busbar compartment Connection compartment Vacuum circuit-breaker module Low-voltage compartment Siemens HA 25.71 2003
8 Closing spring charged indicator, switch position indicator for switching device and operating cycle counter
18
HA25-2682b eps
Design
NXAIR P Compartments
Module compartment
Enclosure made of
Busbar compartment
Enclosure made of
Connection compartment
Enclosure made of
sendzimir-galvanized sheet-steel
Pressure relief upwards Panel front powder-coated
sendzimir-galvanized sheet-steel
Pressure relief upwards Inter unit bus support
sendzimir-galvanized sheet-steel
Pressure relief upwards Suitable for connection of: Bars Single-core cables Three-core cables Separately opening shutters
between panels
Busbars made of flat copper,
bolted from panel to panel: Powder-coated with epoxy resin Option: Insulated busbars
Connection bars between
busbars and bushing-type insulators or current transformers made of silver-plated flat copper
For rated normal currents:
floor cover
Option: Deep bottom pan,
capacitive voltage detection system located in lowvoltage compartment above the module compartment
Automatically coupling
low-voltage plug connector for connection of switchgear modules to auxiliary voltage circuits
Module compartment to
< 2500 A without ventilation, w 3150 A with natural ventilation, w 4000 A with forced ventilation
accommodate components for implementing various panel versions with: NXACT vacuum circuit-breaker module Disconnecting module Vacuum contactor module (for 7 kV and 12 kV) .2 Switch module
supporting busbars and for accommodating upper fixed contacts for switchgear module
Option: Max. 3 bushing-type
With manual operating mechanism Option: With motor operating mechanism integrated in switchgear module In addition to standard interlocking of earthing switch/ movable part, optionally lockable or with electromagnetic interlock
Surge arresters or limiters
current transformers
Option: Coupling electrode
modate max. 3 single-pole voltage transformers Withdrawable With or without primary fuses
(bars only)
Surge arresters for protecting the switchgear against external overvoltages Surge limiters for protecting consumers against switching overvoltages
19
Components
NXACT vacuum circuit-breaker module
for NXAIR for NXAIR M
4 7 8 11 1 2 3 12 9 9 10 13 10 13 7 8 9 14
R-HA25-313 eps R-HA25-314 eps
for NXAIR P
5 6
7 8 11 1 2 3 12 3 1 2 5 4 6
11
12
13
14
10
R-HA25-315 eps
14
NXACT vacuum circuit-breaker modules (mounted on truck for moving into the panel) Circuit-breaker function 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Hand crank opening for spring charging OFF pushbutton ON pushbutton Switch position indicator Closing spring charged indicator Operating cycle counter Switch position indicator Access opening Switch position indicator Access opening Pole columns with isolating contacts (included in the movable part of NXAIR and NXAIR M) Operating unit Interlocking unit Truck (optional)
Disconnecting function Earthing switch function Moving function of the withdrawable unit
Electrical data NXACT for NXAIR Rated operating voltage Max. rated short-circuit breaking current Rated normal current up to 12 kV 25 kA
Electrical data NXACT for NXAIR M Rated operating voltage Max. rated short-circuit breaking current Rated normal current up to 15 kV 17 .5/24 kV 31.5 kA 25 kA
Electrical data NXACT for NXAIR P Rated operating voltage Max. rated short-circuit breaking current Rated normal current up to 15 kV 50 kA
630 A to 2500 A
1250 A to 4000 A
Max. number of operating cycles: Mechanical At rated normal current At rated short-circuit breaking current Mechanical for movable part Mechanical for earthing switch 10000 10 000 25 (50 optionally)
Max. number of operating cycles: Mechanical At rated normal current At rated short-circuit breaking current Mechanical for movable part Mechanical for earthing switch 10 000 10 000 50 10 000 10 000 50
Max. number of operating cycles: Mechanical At rated normal current At rated short-circuit breaking current Mechanical for movable part Mechanical for earthing switch 10 000 10 000 50
1000 1000
1000 1000
1000 1000
1000 1000
20
Components
NXACT vacuum circuit-breaker module
for NXAIR Features
Integrated mechanical interlocks
plug connector with the panel as soon as the switchgear module is inserted into the panel
Maintenance-free operating mechanisms
plug connector with the panel as soon as the switchgear module is inserted into the panel
Maintenance-free operating mechanisms
manually
Maintenance-free operating mechanisms
within a specified number of operating cycles Switchgear module The module consists of the following three assemblies: Operating unit to accommodate
Control board with control, indicating
within a specified number of operating cycles Switchgear module The module consists of the following two assemblies: Movable part consisting of
Vacuum circuit-breaker Contact system Pole shells Operating unit:
within a specified number of operating cycles Switchgear module The module consists of the following three assemblies: Operating unit to accommodate
Control board with control, indicating
breaker, movable part, feeder earthing switch Movable part (pole column) consisting of
Vacuum interrupters Isolating contacts Pole shells
breaker, movable part, feeder earthing switch and busbar earthing switch Movable part (pole column) consisting of
Vacuum interrupters Isolating contacts Pole shells
consisting of Control, indicating and interlocking elements Operating mechanism for vacuum circuit-breaker Interlocking unit consisting of
Support element for movable part and
shafts
Adaptation possibilities for truck
Module versions
NXACT vacuum circuit-breaker module Disconnecting module for disconnecting
shafts
Adaptation possibilities for truck
panel
Vacuum contactor module
Module versions
NXACT vacuum circuit-breaker module Disconnecting module for disconnecting
Module versions
NXACT vacuum circuit-breaker module Disconnecting module for disconnecting
21
Components
Other switching devices
Vacuum switch module
Vacuum switch integra-
vacuum contactor
According to
IEC 60 470 IEC 60 632 VDE 0660 Parts 103 and 105
Up to 2 HV HRC fuses
R-HA25-323 eps
for NXAIR M
to pages 10 and 12
for NXAIR P
R-HA25-324 eps
R-HG11-085 eps
22
Components
Current transformers and post insulators
Bushing-type current transformers
According to
R-HA25-316 eps
from front
Secondary multiratio
R-HA25-317 eps
R-HA25-318 eps
possible
Screwed fixed contact
4
HA25-2684 eps
4
HA25-2685 eps
5 Section
8 Section
5 Section
1 Partition between module and connection compartment 2 Cup bushing 3 Mounting plate 4 Coupling electrode 5 Screwed fixed contact 6 Core with secondary winding 7 Primary conductor 8 Primary connection
1 Partition between module and connection compartment 2 Cup bushing 3 Mounting plate 4 Coupling electrode 5 Screwed fixed contact 6 Core with secondary winding 7 Primary conductor 8 Primary connection
1 Partition between module and connection compartment 2 Cup bushing 3 Mounting plate 4 Coupling electrode 5 Screwed fixed contact 6 Core with secondary winding 7 Primary conductor 8 Primary connection
R-HA25-319 eps
R-HA25-320 eps
R-HA25-321 eps
(example)
23
Components
Low-voltage equipment
Low-voltage compartment
Accommodates equip-
Electronic control board (example) Multifunction protection relay SIPROTEC 4 type 7SJ62 for control and protection Features 1 LCD for process and equipment data, e.g. for: Measuring and metering values Binary data on the status of panel and device Protection data General indications Alarm 2 Keys for navigation in menus and for entering values 3 Seven user-programmable LEDs with applicationspecific label, for displaying any desired process and equipment data 4 Four user-programmable function keys for frequently performed actions
ment for protection, control, measuring and metering, e.g. SIPROTEC 4 7SJ62
Separated from the
withdrawable unit and panel wiring to lowvoltage compartment via 10-pole coded module plug connectors
Bus wires pluggable
4
R-HA25-291 eps
SIPROTEC 4 7SJ62
24
R-HA25-292 eps
R-HA25-305a eps
ment can be removed, bus wires and control cables are plugged in
Standards
Standards, specifications, guidelines
Standards The switchgear complies with the relevant standards and specifications applicable at the time of type tests. In accordance with the harmonization agreement reached by the countries of the European Community, their national specifications conform to IEC 60 298. Switchgear according to ANSI The NXAIR P switchgear is also available as ANSI version according to the following ANSI standards:
Switchgear C37 .100 C37 .20.2 C37 .04 C37 .06 C37 .09 IEEE 1313.1 Current transformer Voltage transformer C57 .13 C57 .13 Degree of protection Insulation
VDE standard current IEC 60 694 * IEC 60 298 * in future IEC 62 271-1 current VDE 0670 Part 1000 in future VDE 0671-001 VDE 0671-200 VDE 0671-102 VDE 0671-103 VDE 0671-105 VDE 0670 Part 4 VDE 0470 Part 1 VDE 0111 VDE 0414 Part 1 VDE 0414 Part 2
EN standard current EN 60 694 EN 60 298 EN 60 056 EN 60 129 EN 60 265-1 EN 60 420 EN 60 282 EN 60 529 EN 60 071 EN 60 044-1 EN 60 044-2
IEC 60 056 ** IEC 62 271-100 IEC 62 271-100 VDE 0670 P 101 to 106 VDE 0671-100 . IEC 60 129 ** IEC 62 271-102 IEC 62 271-102 VDE 0670 Part 2 IEC 60 265-1 * IEC 62 265-1 * IEC 62 271-103 VDE 0670 Part 301 IEC 60 420 ** IEC 62 271-105 IEC 62 271-105 VDE 0670 Part 303 IEC 61 243-5 IEC 60 282 IEC 60 529 IEC 60 071 IEC 61 243-5 IEC 60 282 IEC 60 529 IEC 60 071 IEC 60 044-1 IEC 60 044-2 IEC 61 243-5 IEC 60 282 IEC 60 529 IEC 60 071 IEC 60 044-1 IEC 60 044-2 3) Switch 4) Switch - fuse combination VDE 0682 Part 415 VDE 0670 Part 4 VDE 0470 Part 1 VDE 0111 VDE 0414 Part 1 VDE 0414 Part 2
Insulating capacity
The insulating capacity is veri-
Type of service location The switchgear can be used for indoor installation in accordance with IEC 61 936 (Power installations exceeding 1 kV AC) and VDE 0101
Outside lockable electrical
Rated short-duration power-frequency withstand voltage (rms value) Across isolating distances Between phases and to earth kV kV 23 20 32 28 39 35 45 38 60 50
Rated lightning impulse withstand voltage (peak value) Across isolating distances Between phases and to earth kV kV 70 60 85 75 105 95 110 95 145 125
fied by testing the switchgear with rated values of shortduration power-frequency withstand voltage and lightning impulse withstand voltage according to IEC 60 694/ VDE 0670 Part 1000 (see table Insulating capacity).
The rated values are referred
service locations. A lockable electrical service location is a place outdoors or indoors that is reserved exclusively for housing electrical equipment and which is kept under lock and key. Access is restricted to authorized personnel and persons who have been properly instructed in electrical engineering. Untrained or unskilled persons may only enter under the supervision of authorized personnel or properly instructed persons.
Correction factor a
0,9 0,8 0,7 0,6 0,1 0 0 2000 1000 3000 4000 Site altitude in m above sea level
HA40-2037 eps
service locations at places which are not accessible to the public. Enclosures of switchgear can only be removed with tools.
to sea level and to normal atmospheric conditions (1013 hPa, 20 C, 11 g/m3 humidity in accordance with IEC 60 071 and VDE 0111).
The insulating capacity
5000
decreases with increasing altitude. For site altitudes above 1000 m (above sea level) the standards do not provide any guidelines for the insulation rating. Instead, special regulations apply to these altitudes. Site altitude
Rated short-duration power-frequency withstand voltage to be selected W Rated short-dur. power-fre. withstand volt. (IEC 60 694 / VDE 0670 Part 1000) 1.1 a Rated lightning impulse withstand voltage to be selected W Rated lightning impulse withstand volt. (IEC 60 694 / VDE 0670 Part 1000) 1.1 a
As the altitude increases, the insulating capacity of insulation in air decreases due to the decreasing air density. For the switchgear the decreasing insulating capacity must be taken into account for site altitudes above 1000 m (above sea level), see also IEC 60 694 / VDE 0670 Part 1000.
Example: 3000 m site altitude above sea level 12 kV switchgear rated voltage 75 kV rated lightning impulse withstand voltage Rated lightning impulse 75 kV = 93 kV withstand volt. to be selected 1.1 0.73
Result:
According to the above table, a switchgear for a rated voltage of 15 kV is to be selected.
** Withdrawn standard
25
Standards
Standards, specifications, guidelines
Terms Make-proof earthing switches are earthing switches with short-circuit making capacity according to IEC 62 271-102 and VDE 0670 Part 2/ EN 60 129 Current-carrying capacity
According to IEC 60 694 /
VDE 0670 Part 1000 and IEC 60 298 / VDE 0670 Part 6 current-carrying capacities refer to the following ambient temperatures: Maximum of 24-hour mean + 35 C Maximum + 40 C
The current-carrying capacity
Protection against solid foreign bodies, electric shock and ingress of water NXAIR, NXAIR M and NXAIR P switchgear types fulfill acc. to the standards IEC 60 298 IEC 60 529 VDE 0470 Part 1 VDE 0670 Part 6 the following degrees of protection: NXAIR and NXAIR M panels without ventilation
Degree of protection Standard Enclosure IP 4X / IP 3XD Option IP 51
Aseismic capacity NXAIR and NXAIR P switchgear types are tested in accordance with internationally accepted requirements.
of the panels and busbars depends on the ambient temperature outside the enclosure.
To attain the maximum rated
normal currents, the panels are provided with natural or forced ventilation. Climate and ambient conditions The switchgear may be used, subject to possible additional measures under the following ambient conditions and climate classes: Ambient conditions Natural foreign materials Chemically active pollutants Small animals Climate classes 3K3 3K5 3KX The climate classes are classified according to IEC 60 721-3-3
Compartments IP 2X
Compartments IP 2X
Compartments IP 2X
26
Standards
Standards, specifications, guidelines
Resistance to internal arc faults
Safety of operating person Definitions of criteria: The switchgear up to 31.5 kA
Notes
is designed with resistance to internal arcs going beyond the scope of the mentioned standards; that means that in the event of an internal fault (arc) in a particular compartment, the effects of the arc remain confined to that compartment: No burn-through of partitions to adjacent compartments No burn-through of partition walls to adjacent panels Pressure-resistant walls between adjacent compartments and panels.
Resistance to internal arc
Criterion 1 Correctly secured doors, shutters etc. must not open Criterion 2 Parts of the enclosed switchgear which may cause a hazard must not fly off Criterion 3 No holes in the freely accessible external parts of the enclosure as the result of burning in or tearing open Criterion 4 Vertically arranged indicators must not ignite Criterion 5 Horizontally arranged indicators must not ignite Criterion 6 The effectiveness of the earth connection must not be detrimentally influenced
If not stated otherwise on the individual pages of this catalog, we reserve the right to include modifications, especially regarding the stated values, dimensions and weights. Drawings are not binding. All product designations used are trademarks or product names of Siemens AG or other suppliers. If not stated otherwise, all dimensions in this catalog are given in mm.
ance with IEC 60 298 / VDE 0670 Part 6 by agreement between operator and manufacturer
Internal arc tests performed in
with criteria 1 to 6 specified in the mentioned standards (page 25) for the basic version up to 50 kA.
faults prevents Restrike of an arc fault on live parts in adjacent compartments Impermissible deformation of partitions.
Responsible for: Technical contents: Tushar Rane Siemens AG, Dept. PTD M 1 S Erlangen General editing: Gabriele Pollok Siemens AG, Dept. PTD CC T, Erlangen
KGK 08.03 8.0 VO/- 24 En 100701 6101/D6291 Siemens HA 25.71 2003
27
If you have any questions about Power Transmission and Distribution, our Customer Support Center is available around the clock Tel: +49 180 / 524 70 00 Fax: +49 180 / 524 24 71 (Subject to charges, e.g.: 12 ct/min.)
Published by Siemens AG Power Transmission and Distribution Medium Voltage Division Postfach 32 20 91050 Erlangen Germany