c20 Ca 603 e - 10011999
c20 Ca 603 e - 10011999
c20 Ca 603 e - 10011999
Packaged Air Cooled Helical Rotary Liquid Chiller High Ambient (50 & 60 Hz) 125 to 400 Tons
C20 CA 603 E
Packaged Air Cooled Helical Rotary Liquid Chiller for High Ambient RTAA 213-434 (50 & 60 Hz - R22) - 125 to 400 Tons
RTAA 300 series chiller. cover photo: Tranes air-cooled Rotary chiller 300 series.
American Standard Inc. 1999
Contents
Trouble-Free Installation, Start-Up and Operation Small operating footprint insures easy retrofit capabilities. Factory testing insures trouble-free start-up. Factory-installed, fully-tested controls and options keep start-up time and expenses to minimum. Adaptive Control Microprocessor - optimizes efficiencies - prevents nuisance trip-outs - prevents unnecessary service calls and unhappy tenants Superior microprocessor control - over 90 diagnostic and operating conditions - display chiller temperatures and pressures - Trane Integrated Comfort system (ICS) interface
General Data
Selection Procedure
12
Application Considerations
13
16
Performance Data 50 Hz
18
Performance Data 60 Hz
22
Electrical Data
28
Controls
30
Dimensional Data
33
Weights
39
40
Mechanical Specifications
41
Unequaled Reliability
Proven Reliable Design The air-cooled Rotary chiller utilizes two, three, or four Trane Helirotor compressors that operate on two refrigeration circuits. The tonnages of these compressors are 70, 85, and 100 ton, and they are grouped together in different configurations to make up the air-cooled product line from 125 to 400 tons. Trane air-cooled Helirotor compressors were designed, tested and built to the same rugged standards as the CenTraVac chiller compressors. Since the introduction of Tranes Helirotor compressors to air-cooled applications, their reliability has been outstanding. This is proven by the fact that thousands of Rotary compressors have shipped and less than onehalf of one percent have failed. The Helirotor compressor design and reliability is outstanding when compared to a typical reciprocating compressor design which historically has had a failure rate of two to four percent in the first year alone. All air-cooled Rotary chillers use the highly reliable Helirotor compressor. Aircooled Rotary chillers from 125-400 tons utilize the CHHB compressor. These compressors unload from fully loaded to the minimum capacity of the compressor utilizing a single unloading method, the slide valve. This slide valve is positioned over both the male and female rotors.
Fewer Moving Parts The CHHB Helirotor compressor has only three moving parts: the two rotor assemblies and the capacity controlling slide valve. Unlike reciprocating compressors, the Trane Helirotor compressor has no pistons, connecting rods, rings valves or mechanical oil pump. In fact, a typical reciprocating compressor has 15 times as many critical parts as the Rotary compressor. Fewer moving parts lead to increased reliability and longer life. Helirotor screw compressor parts (above) versus reciprocating compressor components (below)
Resistance To Liquid Slugging The robust design of the Rotary compressor can ingest amounts of liquid refrigerant, wich in the case of reciprocating compressors would severely damage valves, piston rods and cylinders. Proven Design Through Testing and Research Test To Failure It takes a little getting used to, but we MUST fail a lot of compressors in the laboratory so they dont fail in the field. Without failures, there is no way to be certain whether the final design is
conservative or potentially unreliable. The Compressor Accelerated Life Test is proven to induce failure. This test is designed to overstess all parts and quickly identify any weak elements. The test conditions are far more extreme than actual field applications. Our leadership in helical compressor technology is recognized worldwide. It is the basis for the successful introduction of the reliable Trane Helirotor compressor right from the start!
End view showing male and female rotors and slide valve on an 85-ton CHHB compressor.
Optimum Efficiencies
Unsurpassed Full Load Efficiency
Precise Rotor Tip Clearances Higher energy efficiency in a helical rotary compressor is obtained by reducing the rotor tip clearances.This reduces the leakage between high and low pressure cavities during compression. Precise rotor tip clearance is achieved with the latest manufacturing and machining technology. Trane is the first helical rotary compressor manufacturer to electronically check compressor parts machining accuracy as part of the standard production process. Optimized Compressor Parts Profiles Rotor and slide valves are unique designs, optimized for the air conditioning application. The rotors are designed for the pressure ranges in the air conditioning application. Advanced Heat Transfer Surfaces Condenser and evaporator tubes use the latest heat transfer technology for increased efficiency.
Great Part Load Efficiency With Trane Helirotor Compressors And Electronic Expansion Valve
Trane Helirotor Compressor Means Superior Part Load Performance The air-cooled Rotary chiller has great part-load.The slide valve on the CHHB compressors has a Trane designed profile that resulted from computer modeling in typical part- load situations. The result is optimized part-load performance far superior to single reciprocating compressors.
80% 70% 60% 50% 40% 30% 20% 10% 0% 0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
Electronic Expansion Valve When coupled with Tranes Adaptive Control microprocessor, our electronic expansion valve significantly improves part-load performance of the Rotary chiller by minimizing superheat in the evaporator and allowing the chiller to run at reduced condensing temperatures. Chillers which use conventional TXVs
must run at higher head pressures and consume more power than necessary at part-loads. Additionally, the electronic expansion valve and its controls allow much better stability and control over dynamic load and head changes. Under these conditions, a conventional TXV may never achieve control stability.
Capacity Control and Load Matching Infinitely variable compressor modulation allows the compressor capacity to exactly match the building cooling load. Reciprocating chillers that rely on step capacity control must run at a capacity equal to or greater than the load. Much of this excess capacity is lost because overcooling goes toward building latent heat removal, causing the building to be dried beyond normal comfort requirements. The result is an increase in chiller energy costs, particularly at the part-load conditions at which the chiller operates most of the time.
Improved chiller and motor protection The control system integrates all the necessary functions to ensure safe operation of the chiller in all applications and duty conditions : System safeties, such as oil, water, refrigerant pressure and temperature faults. Motor safeties. By monitoring the motor current on each of the 3 phases, the control system ensures protection against : - Overload at start-up and in operation. - Phase loss/Power loss. - Phase unbalance or reversal. - Over/Undervoltage. - Welded contactors. If a fault occurs, one message will be displayed directly on the control module. The End Of Nuisance Trip-Outs And Unnecessary Service Calls? Unnecessary service calls are avoided. The unit does not trip on nuisance or unnecessarily shuts down. Only when the UCM has exhausted all the corrective actions it can take and if the unit is still violating an operating limit, the UCM will shut down the unit.
CONTROLS ON OTHER CHILLERS WILL TYPICALLY SHUT DOWN THE CHILLER, WHEN CHILLED WATER IS MOSTLY NEEDED. For example: A typical five-year-old chiller with dirty coils might trip-out on high pressure cutout on a hot day in August. A hot day is just when comfort cooling is needed the most. In contrast, the air-cooled Rotary chiller with an Adaptive Control microprocessor will stage fans on, modulate electronic expansion valve, and modulate slide valve as the chiller approaches a high pressure situation. Thereby KEEPING THE CHILLER ON-LINE JUST WHEN YOU NEED IT THE MOST.
Close Spacing Of Chiller The air-cooled Rotary chiller has the tightest recommended side clearances in the industry, 1.8 meters, but that is not all. In situations where equipment must be installed with less clearance than recommended, such as frequently occurs in retrofit and rooftop applications, restricted air flow is common. Conventional chillers may not work at all. However, the air-cooled Rotary chiller with its Adaptive Control microprocessor will simply make as much chilled water as possible given the actual conditions. It will stay on line during any unforeseen abnormal conditions and optimize its performance. Consult your Trane sales engineer for more details. Lower Service Expense Nuisance service calls are avoided. When there is a real problem that must be corrected, the UCMs extensive diagnostics help to assure that the problem is quickly identified. Down time and service expense are minimized. And with the ability to communicate with the Trane
Integrated Comfort system or a remote display panel, service problems can be identified and diagnosed remotly from the chiller. Factory Testing Means Trouble-Free Start-Up All air-cooled Rotary chillers are given a complete functional test at the factory. This is over and above the unit individual components tests done prior final assembly of the machine. All the units are fully performance runtested before shipment to verify capacity and power drawn under full load conditions.
2,40m
1,80m
Superior Control
Unit Control Module Tranes new Adaptive Control microprocessor control system enhances the aircooled Rotary chiller by providing the very latest chiller control technology. State-of-the-Art Equipment The new 125 to 400 air-cooled chillers offer the exclusive Trane Adaptive Control logic with the Clear Language Display (UCM). The Clear Language Display has various functions that allow the operator to read unit information and adjust setpoints. The Clear Language Display panel has 16 keys. The readout screen is a two-line, 40 character liquid crystal with a backlight. The backlight allows the operator to read the display in low-light conditions.
Unit Control Module Features Equal Compressor Sequencing Trane maximizes both compressor and motor life by equalizing the number of starts and the operating hours. The UCM will start the compressor with the least number of starts and turn off the compressor with the most operating hours. Conventional auto lead-lag control will equalize starts, but running hours will typically be unequal. Equalizing starts and running hours will provide equal compressor wear.
Internal Built-In Chiller Flow Protection The UCM automatically detects a no waterflow condition. An external flow switch is not a necessity for the safe operation of the chiller.
Easy Chiller System Logging The UCM displays data required to log the chiller system. The following information is available either as standard or as an option with the Air- Cooled Rotary Chiller microprocessor: Entering and leaving chilled water temperatures Ambient air temperature Evaporator and condenser refrigerant temperatures and pressures Compressor suction temperature Percent RLA for each compressor Percent line voltage Compressor starts and running hours Active setpoints: chilled water setpoint current limit setpoint low ambient lockout setpoint Over 90 diagnostic and operating conditions Part failure diagnostics: water temperature sensors refrigerant temperature sensors compressor contactors
Remote Display Panel Trane air-cooled Rotary chillers are available with a twisted pair connection to an optional remote display panel. Chiller operation can be controlled similarly to the control interface on the chiller itself. Through a twisted pair of wires the unit can be turned on or off, change the chilled water setpoint, and display over 90 operating and diagnostic conditions. The remote display panel can be mounted indoors, so, all can be accessed without the need to go to the chillers plant room. Remote clear language display has the ability to control multiple units. In a multiple unit configuration, the Remote Clear Language Display Panel has the capability to communicate with up to four units. Each unit requires a separate communication link with the Remote Display Panel. Easy Interface To The Building Management System Interfacing the air-cooled Rotary chiller with building management systems is state-of-the-art, yet simple. Chiller inputs include: Chiller enable/disable Circuit enable/disable Chilled water setpoint Current limit setpoint Chiller outputs include: Compressor running indication Alarm indication (CKt 1/CKt2) Maximum capacity
8
Trane Chiller Plant Manager ICS The Tracer Chiller Plant Manager Building Management System provides building automation and energy management functions through stand- alone control. The Chiller Plant Manager is capable of monitoring and controlling your entire chiller plant system. Application software available: Time-of-day scheduling Duty cycle Demand limiting Chiller sequencing Process control language Boolean processing Zone control Reports and logs Custom messages Run time and maintenance Trend log Totalizing PID control loops And of course, Tranes Chiller Plant Manager Panel can be used on a standalone basis or tied into a complete Building Automation System.
322 60 Hz 3 70+70/85 2 225 117 275 780 322 12 168/192 3/2 50 Hz 3 85+85/100 2 225 117 275 780 324 14 168/192 3/2
324 60 Hz 3 85+85/100 2 225 117 275 780 324 14 168/192 3/2 50 Hz 3 100+100/100 2 250 110 307 875 328 16 168/192 3/2
3 CHHB 70+70/85 2 ES Gallons GPM GPM CAUW 225 117 275 780 322 12 168/192 3/2
126470 915 762 94/53 15+15/17 32/0 6360 6915 6800 7355 7600 2200 2183 168.3
145430 1130 762 94/53 15+15/17 32/0 6360 6915 6800 7355 7600 2200 2183 168.3
148700 915 762 117/53 17+17/20 32/0 6885 7505 7285 7905 8480 2200 2183 168.3
170910 1130 762 117/53 17+17/20 32/0 6885 7505 7285 7905 8480 2200 2183 168.3
160440 915 762 120/55 20+20/20 32/0 6885 7505 7285 7905 8480 2200 2183 168.3
184400 1130 762 120/55 20+20/20 32/0 6885 7505 7285 7905 8480 2200 2183 168.3
10
432 60 Hz 4 85+85/100+100 2 300 176 360 950 432 18 168 3 50 Hz 4 2 340 162 400 1090 434 20 168 3
4 CHHB 85+85/85+85 2 ES Gallons GPM GPM CAUW 300 176 360 950 430 16 168 3
100+100/100+100 100+100/100+100
174300 915 762 116/116 17+17/17+17 32/0 9110 9970 9750 10600 10285 2200 2223 168.3
200460 1130 762 116/116 17+17/17+17 32/0 9110 9970 9750 10600 10285 2200 2223 168.3
186040 915 762 116/116 17+17/20+20 32/0 9110 9970 9750 10600 10285 2200 2223 168.3
213950 1130 762 116/116 17+17/20+20 32/0 9110 9970 9750 10600 10285 2200 2223 168.3
197780 915 762 120/120 20+20/20+20 32/0 9110 9970 9750 10600 10285 2200 2223 168.3
227440 1130 762 120/120 20+20/20+20 32/0 9110 9970 9750 10600 10285 2200 2223 168.3
11
Selection Procedure
The chiller capacity tables presented on pages 18 to 25 cover the most frequently encountered leaving water temperatures. The tables reflect a 10F (5,6C) temperature drop through the evaporator. For temperature drops other than 10F (5,6C), refer to Table 4, and apply the appropriate Performance Data Adjustment Factors. To select a Trane air-cooled Rotary chiller, the following information is required: 1. Design load in tons of refrigeration 2. Design chilled water temperature drop 3. Design leaving chilled water temperature 4. Design ambient temperature Evaporator flow rates can be determined by using the following formulas: Tons x 24 GPM = Temperature Drop (F) OR L/S = kW (Capacity) x .239 Temperature Drop (C) Selection Example Given: Required System Load = 140 Tons Leaving Chilled Water Temperature (LCWT) = 45F Chilled Water Temperature Drop = 10F Design Ambient Temperature = 95F Evaporator Fouling Factor = 0.00025 1. From Table 5 (RTAA Performance Data)50 Hz, RTAA-214 at the given conditions will produce 141 tons with a compressor power input of 149 kW and a unit EER of 10.3. 2. To calculate the required chilled water flow rate we use the formula given below: GPM = 141 Tons x 24 = 338 GPM 10F 3. To determine the evaporator pressure drop we use the flow rate (GPM) and the evaporator water pressure drop curves, page 17. Entering the curve at 338 GPM, the pressure drop for a nominal 140 ton evaporator is 11.5 feet. 4. For selection of applications where the altitude is significantly greater than sea level or the temperature drop is different than 10F, the performance adjustment factors from Table 4 should be applied at this point. 5. The final unit selection is: QTY (1) RTAA 214 Cooling Capacity = 141 tons Entering/Leaving Chilled Water Temperatures = 55/45F Chilled Water Flow Rate = 338GPM Evaporator Water Pressure Drop = 11.5 ft. H2O Compressor Power Input = 149kW Unit EER = 10.3 Minimum Leaving Chilled Water Temperature Setpoint The minimum leaving chilled water temperature setpoint for water is 40F. For those applications requiring lower setpoints, a glycol solution must be used. Contact the local Trane sales office for additional information.
NOTE: Flow rates must fall within the limits specified in Tables 1,2 and 3 (for GPM).
12
Application Considerations
Application Considerations Certain application constraints should be considered when sizing, selecting and installing Trane air-cooled Rotary chillers. Unit and system reliability are often dependent upon properly and completely complying with these considerations. Where the application varies from the guidelines presented, it should be reviewed with your local Trane sales office. Unit Sizing Unit capacities are listed in the performance data section. Intentionally oversizing a unit to assure adequate capacity is not recommended. Erratic system operation and excessive compressor cycling are often a direct result of an oversized chiller. In addition, an oversized unit is usually more expensive to purchase, install, and operate. If oversizing is desired, consider using two units. Unit Placement 1. Setting The Unit A base or foundation is not required if the selected unit location is level and strong enough to support the unit operating weight as listed in Table 15. 2. Isolation and Sound Emission The most effective form of isolation is to locate the unit away from any sound-sensitive area. Structurally transmitted sound can be reduced by ELASTOMERIC vibration eliminators. Spring isolators have proven to be of little additional benefit when compare to elastomeric vibration eliminators. An acoustical engineer should always be consulted in critical sound applications. For maximum isolation effect, water lines and electrical conduit should also be isolated. Wall sleeves and rubber isolated pipes hangers can be used to reduce the sound transmitted through water piping. To reduce the sound transmitted through electrical conduit, use flexible electrical conduit. State and local codes on sound emissions should always be considered. Since the environment in which a sound source is located affects sound pressure, unit placement must be carefully evaluated. Sound power levels for Trane air-cooled Rotary chillers are available on request. 3. Servicing Adequate clearance for evaporator and compressor servicing should be provided. Recommended minimum space envelopes for servicing are located in the dimensional data section and can serve as a guideline for providing adequate clearance. The minimum space envelopes also allow for control panel swing and routine maintenance requirements. Local code requirements may take precedence. 4. Unit Location a. General Unobstructed flow of condenser air is essential to maintain chiller capacity and operating efficiency. When determining unit placement, careful consideration must be given to assure a sufficient flow of air across the condenser heat transfer surface. Two detrimental conditions are possible and must be avoided if optimum performance is to be achieved: warm air recirculation and coil starvation. Warm air recirculation occurs when discharge air from the condenser fans is recycled back to the condenser coil inlet. Coil starvation occurs when free airflow to the condenser is restricted. Both warm air recirculation and coil starvation cause reductions in unit efficiency and capacity because of the associated higher head pressures. The air-cooled Rotary chiller offers an advantage over competitive equipment in these situations. Performance is minimally affected in many restricted air flow situations due to its unique condensing coil geometry. Also, through its advanced Adaptive Control microprocessor logic, the chiller will stay on-line where competitive chillers would shut down. Tranes unique Adaptive Control microprocessor has the ability to understand the operating environment of the chiller and adapt to it by first optimizing its performance and second, staying on line during abnormal conditions. For example, high ambient temperatures combined with a restricted air flow situation will generally not lead the air-cooled Rotary chiller to shut down. Debris, trash, supplies, etc. should not be allowed to accumulate in the vicinity of the air-cooled Rotary chiller. Supply air movement may draw debris into the condenser coil, blocking spaces between coil fins and causing coil starvation.
13
b. Provide Vertical Clearance Vertical condenser air discharge must be unobstructed. While it is difficult to predict the degree of warm air circulation, a unit installed as shown on the left would have its capacity and efficiency significantly reduced. Performance data are based on free air discharge. c. Provide Lateral Clearance The condenser coil inlet must not be obstructed. A unit installed closer than the minimum recommended distance to a wall or other vertical riser may experience a combination of coil starvation and warm air recirculation, thus causing reduction in unit capacity and efficiency reductions. Once again, the Adaptive Control microprocessor will allow the chiller to stay on line, producing the maximum available capacity, even at less than recommended lateral clearances. The recommended lateral clearances are shown in the dimensional data section. d. Provide Sufficient Unit-to-Unit Clearance Units should be separated from each other by a sufficient distance to prevent warm air recirculation or coil starvation. The air-cooled Rotary chiller has the lowest recommended unit-tounit clearance in the industry, 2.4 meters. Consult the local Trane sales office for applications concerning closer spacings and restricted airflows situations. e. Walled Enclosure Installations When the unit is placed in an enclosure or small depression, the top of the fans should be no lower than the top of the enclosure or depression. If they are, consideration should be given to ducting the top of the unit. Such applications should always be reviewed with the local Trane sales office.
Water Treatment Dirt, scale, products of corrosion and other foreign material will adversely affect heat transfer between the water and system components. Foreign matter in the chilled water system can also increase pressure drop and, consequently, reduce waterflow. Proper water treatment must be determined locally, depending on the type of system and local water characteristics. Neither salt nor brackish water is recommended for use in Trane air-cooled Rotary chillers. The Trane Company encourages the employment of a reputable water treatment specialist, familiar with local water conditions, to assist in establishing the proper water treatment program. The capacities given in the performance data section of this catalog are based on water with a fouling factor of .00025. For capacities at other fouling factors, see adjustment factors in Table 4. Effect Of Altitude On Capacity Air-cooled Rotary chiller capacities given in the performance data tables, (Tables 5 through 12), are at sea level. For elevations substantially higher than sea level, the decreased air density will decrease condenser capacity and, therefore, unit capacity and efficiency. The adjustment factors in Table 4 can be applied directly to the catalog performance data to determine the units adjusted performance. Ambient Limitations Trane air-cooled Rotary chillers are designed for year-round applications in ambients from 32 F to 125 F. The minimum ambient temperatures are based on still weather conditions (winds not exceeding five mph). Greater wind velocities will result in a drop in head pressure, therefore increasing the minimum starting and operating ambient temperature. Once again, the Adaptive Control microprocessor will keep the chiller on line when high or low ambient conditions exist, making every effort to avoid nuisance trip-outs and provide the maximum allowable tonnage.
Waterflow Limits The minimum waterflow rates are given in Tables 1, 2 and 3. Evaporator flow rates below the tabulated values will result in laminar flow causing freeze-up problems, scaling, stratification and poor control. The maximum evaporator waterflow rate is also given in the general data section. Flow rates exceeding those listed may result in excessive tube erosion. The evaporator can handle variable flow down to 50 Pct as long as flow is equal or above the minimum requirement. Temperature Limits 1. Leaving Water Temperature Range Trane air-cooled Rotary chillers have a standard leaving water temperature range of 40 to 65 F. The maximum water temperature that can be circulated through an evaporator when the unit is not operating is 108 deg. F. The evaporator reaches its thermal stress limit at this temperature. 2. Supply Water Temperature Drop The performance data for the Trane air-cooled Rotary chiller are based on a chilled water temperature drop of 10F. Temperature drops outside this range will result in unit performance that differs from that cataloged. For performance data outside the 10F range, see Table 4 for adjustment factors. Chilled water temperature drops from 6 to 16F may be used as long as minimum and maximum leaving water temperature and minimum and maximum flow rates are not violated. Temperature drops outside the 6 to 18F range are beyond the optimum range for control and may adversely affect the microcomputers ability to maintain an acceptable supply water temperature.
14
Typical Water Piping All building water piping must be flushed prior to making final connections to the chiller. To reduce heat loss and prevent condensation, insulation should be installed. Expansion tanks are also usually required so that chilled water volume changes can be accommodated. A typical piping arrangement is shown in Figure A-1. Short Water Loops The proper location of the temperature control sensor is in the supply (outlet) water. This location allows the building to act as a buffer and assures a slowly changing return water temperature. If there is not a sufficient volume of water in the system to provide an adequate buffer, temperature control can be lost, resulting in erratic system operation. A short water loop (less than two gallons/nominal ton) has the same effect as attempting to control from the building return water. To prevent the effect of a short water loop, the following items should be given careful consideration: A storage tank or larger header pipe to increase the volume of water in the system and, therefore, reduce the rate of change of the return water temperature. Multiple Unit Operation Whenever two or more units are used on one chilled water loop, Trane recommends that their operation be controlled from a single control device, such as a Trane Chiller Plant Manager.
1. Series Operation Some systems require large chilled water temperature drops (16 to 24F). For those installations, two units with their evaporators in series are usually required. Control of the units should be from a common temperature controller to prevent the separate thermostats fighting one another and continually hunting. It is possible to control from the two individual unit controls, but a common temperature controller provides a positive method for preventing control overlap, more closely matches system load, and simplifies compressor lead-lag capability. 2. Parallel Operation Some systems require more capacity or standby capability than a single machine can provide. For those installations, two units with their evaporators in a parallel configuration are typical. The only effective way of controlling two units in parallel is with a single temperature controller. Two individual temperature controllers are not capable of providing reliable system control and will often result in unsatisfactory operation.
Thermometer Thermometer
Air vent
Gate valve
Balancing valve Balancing valve Flow switch (optionnal) Flow switch (optionnal) Thermometer Thermometer
15
16
Performance Data
Figure 1 : Evaporator water pressure drop
Waterflow (l/s)
100 100
12.6
32.5
63.0
ES
225 -250
50 40
150 120
120
ES 2 ES 00 170 340
ES
30
90
20
ES
60
10 9 8 7 6 5 4
30 27 24 21 18 15 12
140
ES
ES
300
Waterflow (gpm)
17
Performance Data 50 Hz
Table 5 - Performance Data 200 Series
LWT (F) Model 40 42 RTAA 213 44 45 46 48 50 40 42 RTAA 214 44 45 46 48 50 40 42 RTAA 215 44 45 46 48 50 40 42 RTAA 216 44 45 46 48 50 40 42 RTAA 217 44 45 46 48 50 95 CAP INP Tons kW 118 122 126 128 130 134 139 129 133 138 141 143 148 153 134 139 145 147 150 155 160 149 154 159 162 165 170 176 161 167 172 175 178 184 189 134 136 138 139 140 142 144 144 146 148 149 150 152 155 155 157 159 161 162 164 166 170 173 176 177 178 181 184 185 188 191 192 194 197 200 EER 9.4 9.6 9.8 9.9 10.0 10.2 10.4 9.6 9.9 10.1 10.2 10.3 10.5 10.7 9.4 9.6 9.9 10.0 10.1 10.3 10.5 9.5 9.7 9.9 10.0 10.1 10.3 10.4 9.4 9.6 9.8 9.9 10.0 10.1 10.3 100 CAP INP Tons kW 114 141 118 143 122 145 124 146 126 147 130 149 134 151 125 150 129 153 134 155 136 156 139 158 143 160 148 162 130 163 135 165 140 167 143 168 145 170 150 172 156 174 144 178 149 181 155 184 157 185 160 187 165 189 171 192 157 194 162 197 168 200 170 201 173 203 179 206 184 209 EER 8.7 8.9 9.1 9.2 9.3 9.4 9.6 9.0 9.2 9.4 9.5 9.6 9.8 10.0 8.7 9.0 9.2 9.3 9.4 9.6 9.8 8.8 9.0 9.2 9.3 9.4 9.6 9.7 8.8 9.0 9.2 9.2 9.3 9.5 9.6 CAP Tons 110 114 118 120 122 126 130 121 125 129 132 134 139 143 126 131 136 138 141 146 151 140 145 150 153 155 160 166 152 158 163 165 168 174 179 AMBIENT TEMPERATURE ( F ) 105 INP kW 148 150 152 153 154 156 159 159 161 163 164 165 168 170 171 173 176 177 178 180 183 187 190 193 194 195 198 201 203 206 209 210 212 215 219 EER 8.0 8.2 8.4 8.5 8.6 8.7 8.9 8.3 8.5 8.7 8.8 8.9 9.1 9.2 8.1 8.3 8.5 8.6 8.7 8.9 9.1 8.2 8.4 8.5 8.6 8.7 8.9 9.1 8.2 8.4 8.5 8.6 8.7 8.9 9.0 110 CAP INP Tons kW 106 110 114 116 117 121 125 116 121 125 127 129 134 138 122 127 131 134 136 141 146 136 140 145 148 150 155 161 148 153 158 161 163 169 174 156 158 160 161 162 164 166 167 169 171 172 173 176 178 180 182 184 185 187 189 191 196 199 202 203 204 207 210 213 215 219 220 222 225 228 EER 7.4 7.6 7.7 7.8 7.9 8.1 8.2 7.6 7.8 8.0 8.1 8.2 8.4 8.6 7.5 7.7 7.9 7.9 8.0 8.2 8.4 7.6 7.8 7.9 8.0 8.1 8.3 8.4 7.6 7.8 7.9 8.0 8.1 8.3 8.4 CAP 102 106 109 111 113 117 121 112 116 120 123 125 129 133 118 122 127 129 131 136 140 131 136 141 143 145 150 155 143 148 153 156 158 164 169 115 INP EER 6.8 7.0 7.1 7.2 7.3 7.4 7.6 7.0 7.2 7.4 7.5 7.6 7.7 7.9 6.9 7.1 7.2 7.3 7.4 7.6 7.8 7.0 7.2 7.4 7.4 7.5 7.7 7.8 7.1 7.2 7.4 7.5 7.5 7.7 7.8 164 166 168 169 170 172 175 175 177 180 181 182 184 187 188 191 193 194 195 198 200 206 209 211 213 214 217 220 222 226 229 230 232 235 239 CAP Tons 98 101 105 107 108 112 116 108 112 116 117 118 124 128 113 117 122 122 122 124 125 123 125 126 127 128 130 131 131 132 133 134 136 136 137 Tons kW 120 INP kW 173 175 177 178 179 181 183 184 186 189 187 188 193 196 198 200 202 197 197 195 190 209 208 202 203 199 198 193 219 215 210 212 206 204 199 EER 6.2 6.4 6.5 6.6 6.7 6.8 7.0 6.5 6.6 6.8 6.9 7.0 7.1 7.3 6.4 6.5 6.7 6.9 6.9 7.1 7.3 6.5 6.7 6.8 6.9 7.1 7.2 7.4 6.6 6.8 6.9 7.0 7.2 7.3 7.5
English units
1. Ratings based on seal level altitude and evaporator fouling factor of .00025 per ARI 550-90 2. Interpolation is permissible 3. Extrapolation is not permissible 4. kW input is for compressors only 5. Ratings are based on an evaporator drop of 10 F 6. EER = Energy Efficiency Ratio (Btu/watt-hour).Power inputs include compressors, condenser fans and control power.
18
Performance Data 50 Hz
Table 6 - Performance Data 300 & 400 Series
English units
LWT (F) Model 40 42 RTAA 322 44 45 46 48 50 40 42 RTAA 324 44 45 46 48 50 40 42 RTAA 328 44 45 46 48 50 40 42 RTAA 430 44 45 46 48 50 40 42 RTAA 432 44 45 46 48 50 40 42 RTAA 434 44 45 46 48 50 95 CAP INP Tons kW 182 188 195 198 202 208 215 209 217 224 228 232 240 248 236 244 252 256 260 269 277 259 268 279 284 289 299 310 283 293 303 308 314 324 335 312 322 333 339 344 356 367 217 220 223 225 227 230 234 249 253 257 259 260 265 269 280 285 289 292 294 299 304 313 318 322 325 327 332 337 342 347 353 355 358 364 370 374 380 387 390 393 400 406 EER 9.0 9.2 9.4 9.5 9.6 9.8 10.0 9.0 9.2 9.4 9.5 9.7 9.8 10.0 9.1 9.2 9.4 9.5 9.6 9.7 9.9 9.0 9.2 9.4 9.5 9.6 9.8 10.1 9.0 9.2 9.3 9.4 9.5 9.7 9.9 9.0 9.2 9.4 9.5 9.5 9.7 9.9 100 CAP INP Tons kW 176 228 182 231 189 235 192 236 195 238 202 241 208 245 203 262 210 265 218 269 222 271 226 273 233 277 241 281 229 294 237 298 245 303 249 305 253 308 262 312 270 317 251 329 261 334 270 338 275 341 280 343 290 348 300 353 274 359 284 364 294 370 300 372 305 375 315 381 326 387 303 392 314 398 324 405 330 408 335 411 346 418 357 424 EER 8.4 8.6 8.7 8.8 8.9 9.1 9.3 8.4 8.6 8.8 8.9 9.0 9.2 9.4 8.5 8.6 8.8 8.9 9.0 9.1 9.3 8.3 8.5 8.7 8.8 8.9 9.2 9.3 8.3 8.5 8.7 8.8 8.9 9.1 9.2 8.4 8.6 8.7 8.8 8.9 9.1 9.2 CAP Tons 170 176 182 185 188 195 201 197 204 211 215 219 226 234 223 231 238 242 246 254 263 243 252 262 266 271 281 291 266 276 286 291 296 306 316 295 305 315 320 326 336 347 AMBIENT TEMPERATURE ( F ) 105 INP kW 240 243 246 248 250 253 257 275 278 282 284 286 290 294 308 312 317 319 322 327 332 346 350 355 357 360 365 370 377 382 388 390 393 399 405 411 417 424 427 430 437 444 EER 7.7 7.9 8.1 8.2 8.3 8.4 8.6 7.8 8.0 8.2 8.3 8.3 8.5 8.7 7.9 8.0 8.2 8.3 8.4 8.5 8.7 7.7 7.9 8.1 8.2 8.3 8.5 8.7 7.7 7.9 8.1 8.2 8.3 8.4 8.6 7.8 8.0 8.2 8.2 8.3 8.5 8.6 110 CAP INP Tons kW 164 170 176 179 182 188 194 191 198 205 208 212 219 227 217 224 232 235 239 247 255 235 244 253 258 262 271 281 258 267 277 282 286 296 306 286 296 306 311 316 327 337 252 255 258 260 262 265 269 288 292 296 298 300 304 308 322 327 332 334 337 342 347 363 368 373 375 377 382 388 395 401 406 409 412 418 424 431 437 444 447 450 457 464 EER 7.1 7.3 7.4 7.5 7.6 7.8 7.9 7.2 7.4 7.6 7.7 7.7 7.9 8.1 7.3 7.5 7.6 7.7 7.8 7.9 8.1 7.1 7.3 7.5 7.6 7.7 7.8 8.0 7.2 7.3 7.5 7.6 7.7 7.8 8.0 7.3 7.4 7.6 7.7 7.7 7.9 8.0 CAP 158 163 169 172 175 181 187 184 191 198 201 205 212 219 210 217 225 228 229 230 231 227 235 244 248 253 262 271 250 259 268 272 277 281 289 277 287 297 300 301 302 303 115 INP EER 6.5 6.7 6.9 6.9 7.0 7.2 7.3 6.7 6.8 7.0 7.1 7.2 7.3 7.5 6.8 7.0 7.1 7.2 7.4 7.4 7.7 6.6 6.7 6.9 7.0 7.1 7.2 7.4 6.6 6.8 6.9 7.0 7.1 7.3 7.4 6.8 6.9 7.1 7.1 7.3 7.4 7.6 265 268 271 273 275 276 282 302 306 310 312 314 318 323 338 343 348 350 342 339 328 381 386 391 393 396 401 406 415 420 426 429 432 427 429 452 458 465 468 457 449 439 CAP Tons 148 151 152 153 155 156 157 175 175 176 177 178 180 181 185 186 187 188 188 190 191 214 217 220 221 222 225 226 227 228 229 232 233 234 237 236 237 242 242 246 247 248 Tons kW 120 INP kW 270 269 261 261 261 255 249 311 303 295 293 288 285 278 319 312 305 303 298 294 286 391 382 378 374 370 365 356 406 396 387 386 382 372 368 410 400 398 393 395 385 374 EER 6.0 6.2 6.4 6.4 6.5 6.7 6.9 6.2 6.4 6.5 6.6 6.7 6.9 7.1 6.3 6.5 6.7 6.7 6.8 7.0 7.2 6.1 6.3 6.4 6.5 6.6 6.8 7.0 6.2 6.3 6.5 6.6 6.7 6.9 7.0 6.3 6.5 6.6 6.7 6.8 7.0 7.2
1. Ratings based on seal level altitude and evaporator fouling factor of .00025 per ARI 550-90 2. Interpolation is permissible 3. Extrapolation is not permissible 4. kW input is for compressors only 5. Ratings are based on an evaporator drop of 10 F 6. EER = Energy Efficiency Ratio (Btu/watt-hour).Power inputs include compressors, condenser fans and control power.
19
Performance Data 50 Hz
Table 7 - Performance Data 200 Series
Metric units
LWT (C) Model 5 6 RTAA 213 7 8 9 10 5 6 RTAA 214 7 8 9 10 5 6 RTAA 215 7 8 9 10 5 6 RTAA 216 7 8 9 10 5 6 RTAA 217 7 8 9 10 CAP kW 421 434 449 460 474 488 461 477 490 499 511 538 481 499 513 522 536 564 532 551 565 574 589 619 577 596 611 621 636 666 35 INP kW 135 137 139 140 142 144 145 147 149 150 151 155 156 158 160 161 163 166 172 174 176 178 180 184 186 189 192 193 196 200 COP 2.8 2.8 2.9 2.9 3.0 3.0 2.9 2.9 3.0 3.0 3.1 3.1 2.8 2.9 2.9 2.9 3.0 3.1 2.8 2.9 2.9 2.9 3.0 3.1 2.8 2.8 2.9 2.9 2.9 3.0 CAP kW 396 408 423 434 447 460 435 449 465 478 493 508 455 470 488 501 517 533 504 520 538 553 570 587 548 565 584 599 616 633 AMBIENT TEMPERATURE ( C ) 40 INP kW 148 149 152 153 155 157 158 160 162 164 166 168 170 172 175 177 179 181 187 189 192 194 197 199 202 205 208 211 214 217 COP 2.4 2.5 2.5 2.6 2.6 2.7 2.5 2.5 2.6 2.6 2.7 2.8 2.4 2.5 2.6 2.6 2.7 2.7 2.5 2.5 2.6 2.6 2.6 2.7 2.5 2.5 2.6 2.6 2.6 2.7 CAP kW 381 393 406 417 430 442 419 440 451 460 474 489 439 453 470 483 498 514 487 503 520 534 550 567 531 547 565 580 597 614 43 INP kW 156 158 160 162 164 166 167 168 171 173 174 176 178 180 183 185 187 188 192 194 198 202 204 206 208 210 214 217 220 223 COP 2.2 2.3 2.3 2.3 2.4 2.4 2.3 2.4 2.4 2.4 2.5 2.5 2.3 2.3 2.4 2.4 2.5 2.5 2.3 2.4 2.4 2.4 2.5 2.5 2.3 2.4 2.4 2.4 2.5 2.5 CAP kW 366 377 390 401 413 424 402 431 438 442 456 470 422 436 452 465 479 494 470 485 502 516 531 547 513 529 547 561 578 594 46 INP kW 165 167 169 171 173 175 175 176 179 181 182 184 186 187 190 194 195 196 197 199 204 209 212 213 214 215 220 223 226 229 COP 2.0 2.1 2.1 2.1 2.2 2.2 2.1 2.2 2.2 2.2 2.3 2.3 2.1 2.1 2.2 2.2 2.3 2.3 2.2 2.2 2.3 2.3 2.3 2.4 2.2 2.2 2.3 2.3 2.3 2.4
1. Ratings based on seal level altitude and evaporator fouling factor of .0440 per ARI 550-90 2. Interpolation is permissible 3. Extrapolation is not permissible 4. Kw input is for compressors only 5. Ratings are based on an evaporator drop of 5.6 C 6. COP = Coefficient of performance (kW cooling/kW input).Power inputs include compressors, condenser fans and control power.
20
Performance Data 50 Hz
Table 8 - Performance Data 300 & 400 Series
Metric units
LWT (C) Model 5 6 RTAA 322 7 8 9 10 5 6 RTAA 324 7 8 9 10 5 6 RTAA 328 7 8 9 10 5 6 RTAA 430 7 8 9 10 5 6 RTAA 432 7 8 9 10 5 6 RTAA 434 7 8 9 10 CAP kW 650 671 695 714 735 757 748 775 796 810 831 873 843 872 894 908 931 975 927 962 988 1006 1034 1089 1011 1047 1075 1093 1121 1178 1115 1153 1181 1201 1230 1290 35 INP kW 219 221 225 227 231 234 251 255 258 260 262 269 283 287 291 293 297 304 315 320 323 326 329 337 345 350 354 357 361 370 377 384 388 392 396 406 COP 2.8 2.8 2.9 2.9 3.0 3.0 2.8 2.9 2.9 2.9 3.0 3.1 2.8 2.9 2.9 2.9 3.0 3.0 2.8 2.8 2.9 2.9 3.0 3.1 2.8 2.8 2.9 2.9 2.9 3.0 2.8 2.9 2.9 2.9 3.0 3.0 CAP kW 612 632 654 672 692 713 709 732 758 779 803 828 802 827 854 877 903 929 877 907 940 967 998 1029 959 990 1025 1053 1085 1118 1060 1092 1129 1159 1193 1227 AMBIENT TEMPERATURE ( C ) 40 INP kW 239 242 245 248 251 254 274 277 281 284 288 292 307 311 316 320 324 329 345 349 354 357 362 367 376 381 386 391 396 401 410 416 422 428 434 440 COP 2.4 2.4 2.5 2.5 2.6 2.6 2.4 2.5 2.5 2.6 2.6 2.7 2.5 2.5 2.6 2.6 2.6 2.7 2.4 2.5 2.5 2.6 2.6 2.7 2.4 2.5 2.5 2.6 2.6 2.7 2.5 2.5 2.6 2.6 2.6 2.7 CAP kW 589 608 629 646 665 685 685 707 732 753 776 799 777 801 828 844 858 872 845 874 906 932 962 992 927 957 991 1018 1040 1067 1027 1058 1094 1113 1131 1149 43 INP kW 252 255 258 261 264 268 289 292 296 299 303 307 323 328 332 331 332 329 364 368 373 377 381 386 396 401 407 411 411 415 432 438 445 443 441 440 COP 2.2 2.2 2.3 2.3 2.4 2.4 2.2 2.3 2.3 2.4 2.4 2.5 2.3 2.3 2.4 2.4 2.5 2.5 2.2 2.3 2.3 2.4 2.4 2.5 2.2 2.3 2.3 2.4 2.4 2.5 2.3 2.3 2.4 2.4 2.4 2.5 CAP kW 565 583 604 620 639 658 660 682 706 726 748 771 752 775 801 812 813 816 814 841 872 896 925 954 895 924 957 982 994 1017 993 1024 1059 1067 1068 1070 46 INP kW 266 269 272 275 276 281 304 307 311 314 318 322 340 344 349 342 339 329 383 387 392 396 401 405 417 422 428 432 427 428 454 460 467 458 449 440 COP 2.0 2.0 2.1 2.1 2.2 2.2 2.1 2.1 2.2 2.2 2.2 2.3 2.1 2.2 2.2 2.3 2.3 2.4 2.0 2.1 2.1 2.2 2.2 2.3 2.0 2.1 2.1 2.2 2.2 2.3 2.1 2.1 2.2 2.2 2.3 2.3
1. Ratings based on seal level altitude and evaporator fouling factor of .0440 per ARI 550-90 2. Interpolation is permissible 3. Extrapolation is not permissible 4. Kw input is for compressors only 5. Ratings are based on an evaporator drop of 5.6 C 6. COP = Coefficient of performance (kW cooling/kW input).Power inputs include compressors, condenser fans and control power.
21
Performance Data 60 Hz
Table 9 - Performance Data 200 Series
LWT (F) Model 40 42 RTAA 213 44 45 46 48 50 40 42 RTAA 214 44 45 46 48 50 40 42 RTAA 215 44 45 46 48 50 40 42 RTAA 216 44 45 46 48 50 40 42 RTAA 217 44 45 46 48 50 95 CAP INP Tons kW 143 147 153 155 158 163 168 152 158 163 166 169 175 180 160 166 172 175 179 185 191 175 182 188 191 194 201 207 189 195 202 205 208 215 222 165 167 170 171 173 175 178 176 179 182 183 185 187 190 187 190 192 194 195 198 201 203 206 209 211 213 216 220 223 227 231 233 235 239 243 EER 8.8 9.0 9.2 9.3 9.4 9.6 9.7 8.8 9.0 9.2 9.3 9.4 9.6 9.7 8.7 8.9 9.1 9.2 9.3 9.5 9.7 8.8 9.0 9.2 9.3 9.4 9.6 9.8 8.8 8.9 9.1 9.2 9.2 9.4 9.6 100 CAP INP Tons kW 138 174 143 176 147 179 150 180 152 182 157 185 162 187 147 186 153 188 158 190 161 192 163 194 169 197 175 200 155 196 161 199 167 202 170 204 173 205 179 208 185 211 170 213 176 216 182 220 186 221 189 223 195 227 201 230 184 234 190 238 196 242 199 244 202 246 209 250 215 254 EER 8.2 8.3 8.5 8.6 8.7 8.8 9.0 8.1 8.3 8.5 8.6 8.7 8.9 9.0 8.0 8.2 8.4 8.5 8.6 8.8 9.0 8.2 8.4 8.6 8.7 8.8 8.9 9.1 8.2 8.3 8.5 8.6 8.6 8.8 8.9 CAP Tons 133 138 142 144 147 152 156 142 147 153 155 158 163 169 150 156 161 164 167 173 179 165 171 177 180 183 189 195 178 184 190 193 197 203 209 AMBIENT TEMPERATURE ( F ) 105 INP kW 183 185 188 189 191 194 197 195 198 201 202 204 207 210 207 209 212 214 215 218 221 224 227 231 232 234 238 241 246 249 253 256 258 262 266 EER 7.5 7.7 7.9 7.9 8.0 8.2 8.3 7.5 7.7 7.9 8.0 8.0 8.2 8.4 7.4 7.6 7.8 7.9 8.0 8.2 8.4 7.6 7.8 8.0 8.1 8.1 8.3 8.5 7.6 7.8 7.9 8.0 8.0 8.2 8.3 110 CAP INP Tons kW 128 132 137 139 141 146 150 137 142 147 150 152 157 162 145 150 156 158 161 167 173 160 165 171 174 177 183 189 173 179 185 188 191 197 203 193 195 198 199 201 204 207 205 208 211 212 214 217 220 217 220 223 225 226 229 232 235 238 242 244 245 249 253 258 262 266 268 270 274 279 EER 6.9 7.1 7.2 7.3 7.4 7.5 7.7 6.9 7.1 7.3 7.3 7.4 7.6 7.7 6.9 7.1 7.2 7.3 7.4 7.6 7.7 7.1 7.2 7.4 7.5 7.6 7.7 7.9 7.1 7.2 7.4 7.4 7.5 7.6 7.8 CAP 123 127 131 134 136 140 144 132 137 141 144 146 151 155 140 145 150 153 155 161 166 154 160 163 166 169 171 174 167 173 177 177 178 179 182 115 INP EER 6.4 6.5 6.6 6.7 6.8 6.9 7.1 6.4 6.5 7.0 7.1 7.1 7.0 7.1 6.4 6.5 6.7 6.8 6.8 7.0 7.1 6.6 6.7 6.9 7.0 7.0 7.2 7.4 6.6 6.7 6.8 6.9 7.0 7.2 7.3 203 206 208 210 211 214 217 216 219 211 212 214 228 228 228 231 234 236 237 240 243 247 250 249 251 253 250 248 271 275 274 272 269 264 263 CAP Tons 111 113 112 114 114 119 119 123 124 125 126 125 127 128 131 132 133 134 134 137 138 139 142 145 144 146 147 150 143 146 146 147 147 150 150 Tons kW 120 INP kW 199 197 188 189 187 189 184 219 213 209 208 203 201 196 232 227 223 220 218 217 211 240 238 237 232 232 226 225 245 244 238 235 232 230 224 EER 5.9 6.0 6.2 6.3 6.4 6.5 6.7 5.9 6.0 6.2 6.3 6.4 6.5 6.7 5.9 6.0 6.2 6.3 6.4 6.5 6.7 6.1 6.2 6.4 6.5 6.6 6.7 6.9 6.1 6.3 6.4 6.5 6.6 6.8 6.9
English units
1. Ratings based on seal level altitude and evaporator fouling factor of .00025 per ARI 550-90 2. Interpolation is permissible 3. Extrapolation is not permissible 4. kW input is for compressors only 5. Ratings are based on an evaporator drop of 10 F 6. EER = Energy Efficiency Ratio (Btu/watt-hour).Power inputs include compressors, condenser fans and control power.
22
Performance Data 60 Hz
Table 10 - Performance Data 300 & 400 Series
LWT (F) Model 40 42 RTAA 322 44 45 46 48 50 40 42 RTAA 324 44 45 46 48 50 40 42 RTAA 328 44 45 46 48 50 40 42 RTAA 430 44 45 46 48 50 40 42 RTAA 432 44 45 46 48 50 40 42 RTAA 434 44 45 46 48 50 95 CAP INP Tons kW 214 221 229 233 236 244 252 245 253 262 267 271 280 290 276 285 294 299 304 314 324 303 315 326 332 338 350 362 330 342 354 360 366 378 391 365 377 390 396 402 415 428 259 266 270 272 274 278 282 300 304 309 311 314 319 323 337 343 348 351 354 360 366 377 382 388 391 393 399 405 411 417 424 427 431 437 444 450 458 465 469 473 481 489 EER 8.5 8.6 8.8 8.9 8.9 9.1 9.3 8.4 8.6 8.8 8.9 9.0 9.1 9.3 8.4 8.6 8.7 8.8 8.9 9.0 9.2 8.4 8.6 8.8 8.9 9.0 9.2 9.4 8.3 8.5 8.7 8.8 8.9 9.1 9.2 8.4 8.6 8.7 8.8 8.9 9.0 9.2 100 CAP INP Tons kW 207 275 214 279 221 283 225 285 229 287 236 291 244 296 238 315 246 319 255 324 259 326 263 329 272 334 282 339 268 353 277 359 286 364 291 367 296 370 305 376 315 382 294 396 305 401 316 407 322 410 328 413 339 419 351 425 321 431 332 438 344 444 350 448 356 451 367 458 380 465 355 472 367 479 379 487 385 491 391 495 404 503 417 511 EER 7.8 8.0 8.2 8.2 8.3 8.5 8.7 7.8 8.0 8.2 8.3 8.3 8.5 8.7 7.9 8.0 8.2 8.2 8.3 8.5 8.6 7.8 8.0 8.2 8.3 8.4 8.6 8.7 7.8 7.9 8.1 8.2 8.3 8.4 8.6 7.8 8.0 8.2 8.2 8.3 8.4 8.6 CAP Tons 200 207 214 217 221 228 236 230 239 247 251 255 264 273 261 269 278 283 287 297 306 285 296 306 312 317 328 340 311 322 334 339 345 356 368 345 357 368 374 381 393 405 AMBIENT TEMPERATURE ( F ) 105 INP kW 289 293 297 299 301 305 310 330 335 340 342 344 349 354 370 376 381 384 387 393 399 416 421 427 430 433 439 445 453 459 466 469 473 480 487 494 502 510 514 518 526 534 EER 7.2 7.4 7.5 7.6 7.7 7.9 8.0 7.3 7.4 7.6 7.7 7.8 7.9 8.1 7.3 7.5 7.6 7.7 7.8 7.9 8.1 7.2 7.4 7.6 7.7 7.8 7.9 8.1 7.2 7.4 7.6 7.6 7.7 7.9 8.0 7.3 7.5 7.6 7.7 7.8 7.9 8.0 110 CAP INP Tons kW 193 199 206 210 213 220 227 223 231 239 243 247 256 264 253 262 270 275 279 288 297 276 286 296 301 307 317 328 302 312 323 329 334 345 357 335 346 358 364 369 381 394 304 308 312 314 316 320 325 347 351 356 358 361 366 371 388 394 399 402 405 412 418 437 442 448 451 454 460 466 475 482 488 492 495 502 510 518 526 534 538 542 550 558 EER 6.7 6.8 7.0 7.0 7.1 7.3 7.4 6.8 6.9 7.1 7.1 7.2 7.4 7.5 6.8 7.0 7.1 7.2 7.3 7.4 7.5 6.7 6.9 7.0 7.1 7.2 7.4 7.5 6.7 6.9 7.0 7.1 7.2 7.3 7.5 6.8 7.0 7.1 7.2 7.2 7.4 7.5 CAP 185 192 198 202 213 219 224 216 223 231 235 239 253 257 245 254 269 273 274 275 276 266 276 286 291 296 306 307 292 302 313 314 315 320 324 325 327 334 335 336 339 341 115 INP EER 6.1 6.3 6.4 6.5 6.9 7.1 7.2 6.3 6.4 6.6 6.6 6.7 7.2 7.4 6.4 6.5 7.0 7.1 7.2 7.4 7.5 6.2 6.3 6.5 6.6 6.7 6.8 7.0 6.2 6.4 6.5 6.6 6.7 6.8 7.0 6.3 6.5 6.6 6.7 6.8 7.0 7.1 319 323 327 329 327 328 329 364 368 373 376 378 371 367 407 412 405 408 398 388 384 459 464 470 473 476 482 469 499 505 512 507 502 496 490 543 534 533 528 523 512 501 CAP Tons 176 175 180 183 184 185 186 203 205 205 207 209 211 212 217 218 219 222 223 225 226 239 243 244 245 246 249 253 254 257 258 261 261 262 266 269 270 271 271 271 281 282 Tons kW 120 INP kW 311 299 301 301 292 285 282 350 342 332 331 329 323 318 363 354 346 348 336 338 328 438 432 423 419 414 408 400 462 453 443 442 434 423 417 476 465 453 447 441 446 432 EER 6.0 6.2 6.3 6.4 6.6 6.8 6.9 6.1 6.3 6.4 6.5 6.6 6.8 6.9 6.2 6.4 6.5 6.6 6.8 6.8 7.1 5.8 5.9 6.1 6.2 6.3 6.4 6.6 5.8 6.0 6.1 6.2 6.3 6.4 6.6 5.9 6.0 6.2 6.3 6.4 6.5 6.7
English units
1. Ratings based on seal level altitude and evaporator fouling factor of .00025 per ARI 550-90 2. Interpolation is permissible 3. Extrapolation is not permissible 4. Kw input is for compressors only 5. Ratings are based on an evaporator drop of 10 F 6. EER = Energy Efficiency Ratio (Btu/watt-hour).Power inputs include compressors, condenser fans and control power.
23
Performance Data 60 Hz
Table 11 - Performance Data 200 Series
LWT (C) Model 5 6 RTAA 213 7 8 9 10 5 6 RTAA 214 7 8 9 10 5 6 RTAA 215 7 8 9 10 5 6 RTAA 216 7 8 9 10 5 6 RTAA 217 7 8 9 10 CAP kW 509 525 544 558 574 590 545 565 579 589 604 635 574 595 611 622 638 672 628 650 666 678 695 729 676 698 715 727 744 779 35 INP kW 166 169 171 173 176 178 178 180 182 184 186 190 188 191 193 194 197 201 204 208 210 212 214 220 225 229 232 234 237 243 COP 2.6 2.7 2.7 2.8 2.8 2.9 2.6 2.7 2.7 2.7 2.8 2.9 2.6 2.6 2.7 2.7 2.8 2.8 2.6 2.7 2.7 2.7 2.8 2.9 2.6 2.6 2.7 2.7 2.7 2.8 CAP kW 479 494 510 523 539 554 513 530 548 563 580 597 542 560 580 596 614 633 594 613 634 652 671 691 641 661 682 700 719 740 AMBIENT TEMPERATURE ( C ) 40 INP kW 182 185 187 190 192 195 195 197 200 202 205 208 206 208 211 214 216 219 223 226 230 232 236 239 245 249 253 256 260 264 COP 2.3 2.3 2.4 2.4 2.4 2.5 2.3 2.3 2.4 2.4 2.4 2.5 2.2 2.3 2.3 2.4 2.4 2.5 2.3 2.3 2.4 2.4 2.5 2.5 2.3 2.3 2.4 2.4 2.4 2.5 CAP kW 447 460 476 488 502 516 480 495 512 526 542 555 508 524 543 558 575 593 560 578 593 609 620 634 606 625 641 647 657 670 45 INP kW 200 203 205 208 210 213 213 216 212 215 224 225 225 228 231 233 236 239 244 247 248 251 250 250 267 271 273 270 269 269 COP 2.0 2.0 2.0 2.1 2.1 2.1 2.0 2.0 2.1 2.1 2.1 2.2 1.9 2.0 2.0 2.1 2.1 2.2 2.0 2.0 2.1 2.1 2.2 2.2 2.0 2.0 2.1 2.1 2.2 2.2 CAP kW 367 367 367 373 378 384 391 394 396 402 408 409 418 426 430 434 438 442 459 461 472 474 473 485 457 464 463 470 477 484 50 INP kW 189 183 177 175 174 171 202 195 190 189 186 181 211 210 207 203 199 195 227 223 222 217 211 211 226 224 217 215 212 210 COP 1.7 1.7 1.8 1.8 1.9 1.9 1.7 1.7 1.8 1.8 1.9 1.9 1.7 1.7 1.8 1.8 1.9 1.9 1.7 1.8 1.8 1.9 1.9 2.0 1.8 1.8 1.8 1.9 1.9 2.0
Metric units
1. Ratings based on seal level altitude and evaporator fouling factor of .0440 per ARI 550-90 2. Interpolation is permissible 3. Extrapolation is not permissible 4. Kw input is for compressors only 5. Ratings are based on an evaporator drop of 5.6 C 6. COP = Coefficient of performance (kW cooling/kW input).Power inputs include compressors, condenser fans and control power.
24
Performance Data 60 Hz
Table 12 - Performance Data 300 & 400 Series
LWT (C) Model 5 6 RTAA 322 7 8 9 10 5 6 RTAA 324 7 8 9 10 5 6 RTAA 328 7 8 9 10 5 6 RTAA 430 7 8 9 10 5 6 RTAA 432 7 8 9 10 5 6 RTAA 434 7 8 9 10 CAP kW 764 788 815 837 862 887 875 906 930 946 970 1019 986 1019 1043 1060 1086 1137 1086 1126 1157 1178 1209 1273 1182 1223 1255 1276 1308 1373 1304 1348 1381 1404 1437 1506 35 INP kW 262 267 271 275 278 282 302 307 310 313 316 323 340 345 350 353 357 366 379 385 389 392 396 405 414 421 425 429 434 444 454 461 467 471 477 489 COP 2.5 2.5 2.6 2.6 2.7 2.7 2.5 2.5 2.6 2.6 2.7 2.7 2.5 2.5 2.6 2.6 2.6 2.7 2.5 2.5 2.6 2.6 2.7 2.8 2.5 2.5 2.6 2.6 2.6 2.7 2.5 2.5 2.6 2.6 2.6 2.7 CAP kW 719 742 767 788 811 835 829 856 886 910 938 966 937 966 997 1023 1053 1083 1027 1062 1100 1131 1167 1203 1121 1157 1197 1229 1265 1303 1240 1278 1320 1354 1393 1433 AMBIENT TEMPERATURE ( C ) 40 INP kW 288 292 296 299 303 307 329 334 338 342 347 351 370 375 380 385 390 396 414 419 426 430 435 441 452 457 464 470 476 482 494 500 508 515 522 529 COP 2.2 2.2 2.3 2.3 2.3 2.4 2.2 2.2 2.3 2.3 2.4 2.4 2.2 2.2 2.3 2.3 2.4 2.4 2.2 2.2 2.3 2.3 2.4 2.4 2.2 2.2 2.3 2.3 2.3 2.4 2.2 2.2 2.3 2.3 2.3 2.4 CAP kW 673 694 718 754 773 792 782 807 835 858 897 914 889 916 959 977 988 1001 966 998 1034 1062 1095 1110 1059 1092 1130 1142 1164 1185 1167 1193 1224 1238 1255 1272 45 INP kW 315 318 323 323 325 327 359 363 368 372 369 369 402 407 405 402 398 397 453 458 464 468 474 468 492 498 505 500 499 498 532 534 537 532 528 524 COP 1.9 1.9 2.0 2.1 2.1 2.1 1.9 2.0 2.0 2.0 2.1 2.2 1.9 2.0 2.1 2.1 2.2 2.2 1.9 1.9 2.0 2.0 2.1 2.1 1.9 1.9 2.0 2.0 2.1 2.1 1.9 2.0 2.0 2.1 2.1 2.1 CAP kW 516 519 521 522 529 530 590 591 605 605 615 621 638 636 646 655 652 661 743 758 761 775 782 789 784 802 806 808 826 831 837 850 863 860 872 868 50 INP kW 274 267 260 253 249 242 306 298 297 288 285 279 325 316 312 308 297 293 393 391 380 376 368 359 411 410 400 389 387 378 431 426 422 408 403 388 COP 1.6 1.7 1.7 1.8 1.8 1.9 1.7 1.7 1.7 1.8 1.8 1.9 1.7 1.7 1.8 1.8 1.8 1.9 1.6 1.7 1.7 1.8 1.8 1.9 1.6 1.7 1.7 1.8 1.8 1.9 1.7 1.7 1.8 1.8 1.8 1.9
Metric units
1. Ratings based on seal level altitude and evaporator fouling factor of .0440 per ARI 550-90 2. Interpolation is permissible 3. Extrapolation is not permissible 4. kW input is for compressors only 5. Ratings are based on an evaporator drop of 5.6 C 6. COP = Coefficient of performance (kW cooling/kW input).Power inputs include compressors, condenser fans and control power.
25
Performance Data
Table 13 - ARI Part-Load Values 50 Hz (English units)
Power Input (kW) Unit Size 100 RTAA213 75 50 25 100 RTAA214 75 50 25 100 RTAA215 75 50 25 100 RTAA216 75 50 25 100 RTAA217 75 50 25 100 RTAA322 75 50 25 100 RTAA324 75 50 25 100 RTAA328 75 50 25 100 RTAA430 75 50 25 100 RTAA432 75 50 25 100 RTAA434 75 50 25 % Load Capacity Tons 126 95 63 32 138 104 69 35 145 108 72 36 159 119 80 40 172 129 86 43 195 146 97 49 224 168 112 56 252 189 126 63 279 209 139 70 303 227 152 76 331 248 166 83 ARI Temp. Relief 138 75 40 17 148 77 41 19 159 83 45 21 176 92 49 23 191 94 52 25 223 123 56 25 257 139 64 28 289 153 72 32 322 174 109 48 353 187 109 49 387 201 104 50 Constant Amb. Temp. 138 97 63 47 148 101 68 47 159 108 73 51 176 120 81 56 191 126 88 53 223 158 105 58 257 177 121 67 289 194 136 72 322 222 158 71 353 240 169 74 387 259 178 77 EER With Temp. Relief 9.8 12.5 15.5 14.9 10.1 13.3 16.5 14.8 9.9 13.1 16.3 14.7 9.8 13.1 16.5 15.1 9.8 13.6 16.6 14.5 9.4 11.9 16.1 17.2 9.4 12.1 16.6 16.2 9.4 12.2 16.3 16.8 9.4 12.2 13.2 12.7 9.3 12.2 14.1 13.2 9.3 12.4 15.8 13.9 14.1 100 RTAA213 75 50 25 100 RTAA214 75 50 25 100 RTAA215 75 50 25 100 RTAA216 75 50 25 100 RTAA217 75 50 25 100 RTAA322 75 50 25 100 RTAA324 75 50 25 100 RTAA328 75 50 25 100 RTAA430 75 50 25 100 RTAA432 75 50 25 100 RTAA434 75 50 25 153 115 77 38 163 122 82 41 172 129 86 43 188 141 94 47 202 152 101 51 229 172 115 57 262 197 131 66 294 221 147 74 326 245 163 82 354 266 177 89 390 293 195 98 IPLV Unit Size Tons
60 Hz
Power Input (kW) % Load Capacity ARI Temp. Relief 170 92 53 24 182 95 55 27 192 100 58 29 209 109 63 31 231 116 65 35 270 143 73 43 309 158 80 46 348 174 87 49 388 206 109 54 424 233 114 59 465 233 121 60 Constant Amb. Temp. 170 119 78 39 182 124 84 42 192 131 88 44 209 142 96 48 231 152 106 53 270 184 124 73 309 207 142 80 348 230 160 90 388 264 171 93 424 284 182 93 465 307 191 93 EER With Temp. Relief 9.2 11.4 13.6 11.8 9.1 11.6 14.1 11.6 9.1 11.4 13.6 10.9 9.2 11.7 13.9 11.3 9.1 12.0 14.6 11.4 8.8 11.1 13.4 11.7 8.8 11.4 14.3 11.4 8.7 11.5 14.3 12.4 8.8 11.2 14.1 11.6 8.7 10.7 14.4 11.5 8.7 11.6 14.9 12.1 12.4 IPLV
14.9
12.7
14.7
12.3
14.8
12.6
15.0
13.1
14.4
12.2
14.6
12.7
14.6
12.8
12.7
12.5
13.2
12.4
14.1
13.1
- ARI part load data: 95 F Ambient Temperature. 44 F Leaving water temperature - ARI Ambient temperature relief: 100 % load : 95 F 75% load : 80 F 50% load : 65 F 25% load : 55 F - Power kW is for compressors only.
26
Performance Data
Table 14 - ARI Part-Load Values 50 Hz (Metric units)
Power Input (kW) Unit Size 100 RTAA213 75 50 25 100 RTAA214 75 50 25 100 RTAA215 75 50 25 100 RTAA216 75 50 25 100 RTAA217 75 50 25 100 RTAA322 75 50 25 100 RTAA324 75 50 25 100 RTAA328 75 50 25 100 RTAA430 75 50 25 100 RTAA432 75 50 25 100 RTAA434 75 50 25 % Load Capacity Kw 443 332 222 111 486 364 243 121 508 381 254 127 560 420 280 140 606 454 303 151 685 514 343 171 789 592 394 197 886 665 443 222 980 735 490 245 1065 799 533 266 1164 873 582 291 ARI Temp. Relief 138 75 40 17 148 77 41 19 159 83 45 21 176 92 49 23 191 94 52 25 223 123 56 25 257 139 64 28 289 153 72 32 322 174 109 48 353 187 109 49 387 201 104 50 Constant Amb. Temp. 138 97 63 47 148 101 68 47 159 108 73 51 176 120 81 56 191 126 88 53 223 158 105 58 257 177 121 67 289 194 136 72 322 222 158 71 353 240 169 74 387 259 178 77 COP With Temp. Relief 2.9 3.7 4.5 4.4 3.0 3.9 4.8 4.3 2.9 3.9 4.8 4.3 2.9 3.8 4.8 4.4 2.9 4.0 4.9 4.3 2.8 3.5 4.7 5.0 2.8 3.5 4.9 4.7 2.8 3.6 4.8 4.9 2.8 3.6 3.9 3.7 2.7 3.6 4.1 3.9 2.7 3.6 4.6 4.1 4.4 100 RTAA213 75 50 25 100 RTAA214 75 50 25 100 RTAA215 75 50 25 100 RTAA216 75 50 25 100 RTAA217 75 50 25 100 RTAA322 75 50 25 100 RTAA324 75 50 25 100 RTAA328 75 50 25 100 RTAA430 75 50 25 100 RTAA432 75 50 25 100 RTAA434 75 50 25 538 403 269 134 573 430 287 143 605 454 302 151 661 496 331 165 710 533 355 178 805 604 403 201 921 691 461 230 1034 775 517 258 1146 860 573 287 1245 933 622 311 1371 1028 686 343 IPLV Unit Size Kw
60 Hz
Power Input (kW) % Load Capacity ARI Temp. Relief 170 92 53 24 182 95 55 27 192 100 58 29 209 109 63 31 231 116 65 35 270 143 73 43 309 158 80 46 348 174 87 49 388 206 109 54 424 233 114 59 465 233 121 60 Constant Amb. Temp. 170 119 78 39 182 124 84 42 192 131 88 44 209 142 96 48 231 152 106 53 270 184 124 73 309 207 142 80 348 230 160 90 388 264 171 93 424 284 182 93 465 307 191 93 COP With Temp. Relief 2.7 3.3 4.0 3.5 2.7 3.4 4.1 3.4 2.7 3.4 4.0 3.2 2.7 3.4 4.1 3.3 2.7 3.5 4.3 3.3 2.6 3.2 3.9 3.4 2.6 3.3 4.2 3.3 2.6 3.4 4.2 3.6 2.6 3.3 4.1 3.4 2.6 3.1 4.2 3.4 2.6 3.4 4.4 3.5 3.9 IPLV
4.6
4.0
4.6
3.8
4.6
3.9
4.7
4.1
4.5
3.8
4.5
3.9
4.5
4.0
4.0
3.9
4.1
3.9
4.4
4.1
- ARI part load data: 35 C Ambient Temperature. 6.7 C Leaving water temperature - ARI Ambient temperature relief: 100 % load : 35 C 75% load : 26.7 C 50% load : 18.3 C 25% load : 12.7 C - Power kW is for compressors only.
27
Electrical Data 50 Hz
Table 15 - Electrical Data
RTAA Compressor Quantity Model (Circuit 1+2) RLA (1) Power Supply (3) CHHB 220/3/50 380/3/50 415/3/50 220/3/50 380/3/50 415/3/50 213 2 70/70 243/243 140/140 129/129 800 400 400 1112 609 639 1300 200 2 x 150 8 4.2 14.7 1.3 1.88 322 3 70+70 85 243/243 278 140/140 161 129/129 147 1000 630 630 1552 861 888 2000 400 3 x 150 12 4.2 14.7 1.3 1.88 214 2 70/85 243/278 140/161 129/149 800 400 400 1293 705 743 1300 200 2 x 150 8 4.2 14.7 1.3 1.88 324 3 85+85 100 278/278 325 161/161 188 147/147 172 1250 800 800 1735 966 996 2000 400 3 x 150 14 4.2 14.7 1.3 1.88 215 2 85/85 278/278 161/161 149/149 800 500 500 1328 726 763 1300 200 2 x 150 8 4.2 14.7 1.3 1.88 328 3 100+100 100 325/325 325 188/188 188 172/172 172 1600 800 800 1837 1028 1056 2000 400 3 x 150 16 4.2 14.7 1.3 1.88 216 2 85/100 278/325 161/188 149/175 800 500 500 1436 784 826 1300 200 2 x 150 9 4.2 14.7 1.3 1.88 430 4 85+85 85+85 278/278 278/278 161/161 161/161 147/147 147/147 1600 1000 1000 1917 1081 1094 2600 400 4 x 150 16 4.2 14.7 1.3 1.88 217 2 100/100 325/325 188/188 175/175 1000 500 500 1487 815 856 1300 200 2 x 150 10 4.2 14.7 1.3 1.88 432 4 85+85 100+100 278/278 325/325 161/161 188/188 147/147 172/172 1600 1000 1000 2077 1171 1188 2600 400 4 x 150 18 4.2 14.7 1.3 1.88 434 4 100+100 100+100 325/325 325/325 188/188 188/188 172/172 172/172 2000 1000 1000 2179 1233 1248 2600 400 4 x 150 20 4.2 14.7 1.3 1.88
Unit inrush Current (2) Power Supply (3) 220/3/50 Starting Mode: 380/3/50 Part Winding 415/3/50 Control Power Required (110V) VA Evaporator Heater W Oil Heater W Number Of Fans FLA 380/415 V , Each A Starting Amps 380/415 A Fan Motor Shaft Power kW Fan Motor Rated KW kW RTAA Compressor Quantity Model (Circuit 1) Model (Circuit 2) RLA (1) Power Supply (3) CHHB CHHB 220/3/50 380/3/50 415/3/50 Recommended Fuse size ( A ) 220/3/50 380/3/50 415/3/50
Unit inrush Current (2) Power Supply (3) 220/3/50 Starting Mode: 380/3/50 Part Winding 415/3/50 Control Power Required (110V) VA Evaporator Heater W Oil Heater W Number Of Fans FLA 380/415 V , Each A Starting Amps 380/415 A Fan Motor Shaft Power kW Fan Motor Rated KW kW
NOTES: (1) Rated Load Amperes - RLA 50 Hz - Rated at 5 Bar suction Pressure and 25 Bar discharge pressure. (2) Unit Inrush Current = Starting amps of the circuit with the larger compressor circuit including fans. plus RLA of the second circuit including fans (3) Voltage Utilisation Range : 220/3/50 (198-242), 400/3/50 (360-440).
28
Electrical Data 60 Hz
Table 16 - Electrical Data
RTAA Compressor Quantity Model (Circuit 1+2) RLA (1) Power Supply (3) CHHB 220/3/60 380/3/60 460/3/60 220/3/60 380/3/60 460/3/60 213 2 70/70 291/291 168/168 139/139 800 500 400 1301 772 647 1300 200 2 x 150 8 6.2 34 2.6 3.42 322 3 70/70 85 291/291 333 168/168 193 139/139 159 1250 800 630 1826 1087 911 2000 400 3 x 150 12 6.2 34 2.6 3.42 214 2 70/85 291/333 168/193 139/159 1000 500 400 1517 901 754 1300 200 2 x 150 9 6.2 34 2.6 3.42 324 3 85/85 100 333/333 391 193/193 226 159/159 187 1600 800 800 2041 1218 1020 2000 400 3 x 150 14 6.2 34 2.6 3.42 215 2 85/85 333/333 193/193 159/159 1000 500 500 1565 932 780 1300 200 2 x 150 10 6.2 34 2.6 3.42 328 3 100/100 100 391/391 391 226/226 226 187/187 187 1600 1000 800 2169 1296 1088 2000 400 3 x 150 16 6.2 34 2.6 3.42 216 2 85/100 333/391 193/226 159/187 1000 630 500 1683 1000 836 1300 200 2 x 150 10 6.2 34 2.6 3.42 430 4 85/85 85/85 333/333 333/333 193/193 193/193 159/159 159/159 2000 1000 1000 2268 1355 1135 2600 400 4 x 150 16 6.2 34 2.6 3.42 217 2 100/100 391/391 226/226 187/187 1250 630 500 1741 1033 864 1300 200 2 x 150 10 6.2 34 2.6 3.42 432 4 85/85 100/100 333/333 391/391 193/193 226/226 159/159 187/187 2000 1250 1000 2457 1436 1232 2600 400 4 x 150 18 6.2 34 2.6 3.42 434 4 100/100 100/100 391/391 391/391 226/226 226/226 187/187 187/187 2000 1250 1000 2585 1547 1300 2600 400 4 x 150 20 6.2 34 2.6 3.42
Unit inrush Current (2) Power Supply (3) 220/3/60 Starting Mode: 380/3/60 Part Winding 460/3/60 Control Power Required (110V) VA Evaporator Heater W Oil Heater W Number of Fans FLA 380/3/60 , Each A Starting Amps 380/3/60 A Fan Motor Shaft Power kW Fan Motor Rated KW kW RTAA Compressor Quantity Model (Circuit 1) Model (Circuit 2) RLA (1) Power Supply (3) CHHB CHHB 220/3/60 380/3/60 460/3/60 Recommended Fuse size ( A ) 220/3/60 380/3/60 460/3/60
Unit inrush Current (2) Power Supply (3) 220/3/60 Starting Mode: 380/3/60 Part Winding 460/3/60 Control Power Required (110V) VA Evaporator Heater W Oil Heater W Number Of Fans FLA 380/3/60 , Each A Starting Amps 380/3/60 A Fan Motor Shaft Power kW Fan Motor Rated KW kW
NOTES: (1) Rated Load Amperes - RLA 60 Hz - Rated in accordance to UL Standard 465 (2) Unit Inrush Current = Starting amps of the circuit with the larger compressor circuit including fans plus RLA of the second circuit including fans (3) Voltage Utilisation Range : 200-230/3/60 (180-253), 380/3/60 (342-418), 460/3/60 (414-506)
29
Optional features Tracer communication interface. Hardware interface with BMS system.(External chilled water setpoint). External current limit setpoint. Chilled water temperature reset. If a fault occurs, one of 90 individual diagnostic and operating codes will display directly on the control module.
Communication
The Unit Control Module (UCM-CLD) of the RTAA offers several communication levels which considerably simplify the implementation of a telemonitoring of the chiller or its integration in a Building Management System (BMS).
Application flexibility
The UCM-CLD is available with the output in six languages and in either English or metric (SI) units.
Integration into a Trane Building Management System through the Serial link
The unit can be equipped upon request with a serial link communication card. All the data and functions available at the UCM front panel can be transmitted or accessed through the serial link. The integration in a Building Management or the chiller operation optimization in order to reduce the overal energy consumption are thus considerably simplified.
Operator interface
With easy front panel programmability of daily, service start-up and machine configuration settings and setpoints, the building manager and service technician can customize the use of the UCM-CLD microcontroller to the unique conditions of the chiller plant whether the purpose of the chilled water is comfort cooling or process cooling. All the data that is necessary for the improved operation and easy serviceability of the chiller is called up by simple keypad instructions and presented on a highly readable screen.
Convenience
Enunciation of all information is at the front panel display (including power, voltage, amps, temperatures, pressures, number of starts and operating hours). Messages are displayed using clear language.
Readability
LCD, super twist, double line 40 character display is easy to read. It is backlit so that the diplay can be read in a variety of equipment room lighting conditions.
30
PC Workstation
Chiller N1
Chiller N1
Chiller N1
Universal PCM
31
Superior control
The diagram indicates the numerous control variables that are centralised by the unit control module in order to ensure trouble free operation.
UCM
8 9
P W
17 14 15 1 13 16 18 10 4 11 2 19 20 5
7 12
23 6 22 3
21
5 Oil separator 6 Circuit de lubrification Oil cooler Sparateur d'huile. 7 5 Oil filter.
6 7
Control circuit Circuit de contrle et de rgulation 17 Motor windings temperature 8 Part-winding starter 16 Rgulation de la capacit frigorifiqu 8 Dmarreur part-winding 18 Evaporato entering water temperature 9 Phase loss/imbalance, under/over voltage 17 Temprature bobinages moteur. 9 Perte/dsquilibre de phase, sur/sous tension. 19 Evaporator leaving water temperature pro tection 18 Temprature d'entre d'eau vapo 10 Auto-diagnostic/position de la vanne de dtente, 20 Chilled water circuit flow switch(option, field 10 Electronic expansion valve self diagnostic and 19 wired ) Temprature de sortie d'eau vapo dbit de flux de fluide frigorigne. prepositionning, refrigerant flow metering 20 Dbit d'eau vaporateur 11 Temprature d'entre refrigerant temperature 21 11 Evaporator entering fluide frigorigne vaporateur.Condenser refrigerant temperature (option, ca 22 Condenser entering water temperature 12 Temprature de sortie fluide frigorigne vaporateur. 21 Pression de fluide frigorigne cond 12 Evaporator leaving refrigerant temperature 23 Condenser leaving water temperature 13 Oil tank heating 22 Rgulation dbit d'air. 13 Chauffage du carter d'huile. 14 Oil circuit solenoid valve 23 Temprature ambiante. 14 Vanne solnode alimentation huile. 15 Oil pressure 15 Pression d'huile.
16 Compressor capacity control
32
Dimensional Data
RTAA 213 50 Hz Unit Dimensions
33
34
35
36
37
SIZE 213-50 Hz 213-60 Hz 214-50 Hz 214-60 Hz 215-50 Hz 215-60 Hz 216-50 Hz 216-60 Hz 217-50 Hz 217-60 Hz 322-50/60 Hz 324-50/60 Hz 328-50/60 Hz 430-50/60 Hz 432-50/60 Hz 434-50/60 Hz
1 2 X CHHB070 2 X CHHB070 CHHB085 +CHHB070 CHHB085 +CHHB070 2 X CHHB085 2 X CHHB085 CHHB085 +CHHB100 CHHB085 +CHHB100 2 X CHHB100 2 X CHHB100 2 X CHHB070 + 1 X CHHB085 2 X CHHB085 + 1 X CHHB100 3 X CHHB100 4 X CHHB085 2 X CHHB085 + 2 X CHHB100 4 X CHHB100
2 ES 120 ES 140 ES 140 ES 170 ES 140 ES 170 ES 170 ES 200 ES 170 ES 200 ES 225 ES 225 ES 250 ES 300 ES 300 ES 340
3 CAUW213 CAUW215 CAUW214 CAUW216 CAUW215 CAUW217 CAUW216 CAUW218 CAUW217 CAUW218 CAUW322 CAUW324 CAUW328 CAUW430 CAUW432 CAUW434 AL CU AL CU AL CU AL CU AL CU AL CU AL CU AL CU AL CU AL CU AL CU AL CU AL CU AL CU AL CU AL CU
11 3900 4350 4570 5110 4640 5180 4720 5260 4710 5250
13 2 x 15 2 x 15 2 x 17 2 x 17 2 x 17 2 x 17 20 + 17 20 + 17 2 x 20 2 x 20 2 x 15 1 x 17 2 x 17 1 x 20 3 x 20 4 x 17 2 x 20 2 x 17 4 x 20
4830 5370 4810 5350 5130 5860 4890 5430 5130 5870 6800 7355 7285 7905
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Compressor Evaporator Condenser Evaporator water inlet connection Evaporator water outlet connection Control panel Starter panel Power supply inlet : (155 x 400) on 200 serie , (230 x 750) on 300 and 400 series Rigging eyes 80 x 50 Drain evaporator (3 / 4 ) Operating weight ( kg ) Refrigerant charge ( kg ) Oil charge ( liters ) Minimum recommended clearance ( for maintenance) Recommended clearance ( evaporator tubes removal and air entering ) Options Pressure gauges Compressor sound attenuator Power disconnect switch Vibration isolators locations
17 18 19 20
38
Weights
Table 15 - Weights
Isolators Location Unit Size RTAA213 50 Hz 50 Hz 60 Hz 60 Hz RTAA214 50 Hz 50 Hz 60 Hz 60 Hz RTAA215 50 Hz 50 Hz 60 Hz 60 Hz RTAA216 50 Hz 50 Hz 60 Hz 60 Hz RTAA217 50 Hz 50 Hz 60 Hz 60 Hz RTAA322 50 Hz 50 Hz 60 Hz 60 Hz RTAA324 50 Hz 50 Hz 60 Hz 60 Hz RTAA328 50 Hz 50 Hz 60 Hz 60 Hz RTAA430 50 Hz 50 Hz 60 Hz 60 Hz RTAA432 50 Hz 50 Hz 60 Hz 60 Hz RTAA434 50 Hz 50 Hz 60 Hz 60 Hz AL CU AL CU AL CU AL CU AL CU AL CU AL CU AL CU AL CU AL CU AL CU AL CU AL CU AL CU AL CU AL CU AL CU AL CU AL CU AL CU AL CU AL CU Units kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg 1 410 490 564 694 564 674 572 679 571 678 591 698 594 694 648 786 608 706 641 783 695 753 695 753 775 843 775 843 775 843 775 843 900 985 900 985 900 985 900 985 900 985 900 985 2 430 505 598 739 598 709 602 710 600 708 620 728 628 728 682 820 642 740 670 813 615 673 615 673 695 760 695 760 695 760 695 760 900 985 900 985 900 985 900 985 900 985 900 985 3 640 730 731 844 748 841 769 854 767 852 789 874 784 870 836 965 796 885 840 961 835 898 835 898 900 974 900 974 900 974 900 974 940 1020 940 1020 940 1020 940 1020 940 1020 940 1020 4 680 755 781 884 798 891 814 900 812 898 834 920 824 914 876 1005 836 925 885 1007 735 803 735 803 805 878 805 878 805 878 805 878 940 1020 940 1020 940 1020 940 1020 940 1020 940 1020 5 845 910 918 907 936 1005 956 1033 955 1032 973 1050 965 1044 1018 1117 978 1062 1022 1128 970 1043 970 1043 1020 1104 1020 1104 1020 1104 1020 1104 975 1060 975 1060 975 1060 975 1060 975 1060 975 1060 6 895 960 978 1042 996 1060 1007 1084 1005 1082 1023 1100 1015 1100 1070 1167 1030 1112 1072 1178 860 933 860 933 915 995 915 995 915 995 915 995 975 1060 975 1060 975 1060 975 1060 975 1060 975 1060 7 1110 1189 1110 1189 1145 1255 1145 1255 1145 1255 1145 1255 1010 1100 1010 1100 1010 1100 1010 1100 1010 1100 1010 1100 8 980 1063 980 1063 1025 1114 1025 1114 1025 1114 1025 1114 1010 1100 1010 1100 1010 1100 1010 1100 1010 1100 1010 1100 9 1050 1135 1050 1135 1050 1135 1050 1135 1050 1135 1050 1135 10 1050 1135 1050 1135 1050 1135 1050 1135 1050 1135 1050 1135 Operating Weight (kg) 3900 4350 4570 5110 4640 5180 4720 5260 4710 5250 4830 5370 4810 5350 5130 5860 4890 5430 5130 5870 6800 7355 6800 7355 7280 7923 7280 7923 7280 7923 7280 7923 9750 10600 9750 10600 9750 10600 9750 10600 9750 10600 9750 10600
Notes: 1. Operating weight includes refrigerant and water. 2. 200 serie have 6 isolator locations. 300 Serie have 8 isolator location, 400 Series have 10 isolator locations.
Options
Communication Card Permits either bi-directional communication to the Trane Integrated Comfort system or permits remote chilled water setpoint reset or demand limiting (mutually exclusive) by accepting a 4-20 mA or 2-10 Vdc analog signal. Remote Clear Language Display In addition to controlling chiller operation from a location within the building, the remote clear language display can provide the capability to monitor unit alarms and messages. Only one twisted pair is required between the chiller and the remote display (requires Communication Package on 130-400 ton only). Chilled Water Reset This option provides the control logic and field installed sensors for either load based (return water temperature) or temperature based (ambient or zone) reset of leaving chilled water temperature (requires Communication Card). Protection grids evaporator and compressor section Grids to cover the service area beneath the coils. Coil Protection Grids which protect the condenser coils only. Power Disconnect Switch A fused disconnect switch with through the door handle is provided to disconnect main power. Discharge Service Valves Factory installed valves to isolate refrigerant charge. Vibration Isolators Spring or rubber isolators help isolate the chiller from the building structure. Compressor sound attenuating enclosure Copper fins condenser coils Pressure gauges
Features summary
Trane RTAA Air-Cooled Rotary Chiller Designed To Perform, Built To Last
Reliability Proven Helirotor compressor design for longer life and greater dependability. Fewer moving parts means less parts to fail. Typical reciprocating compressors have 4 times as many total parts and 15 times as many critical parts. Adaptive Control protects the chiller when any of the system variables approaches a limit condition that may damage the unit or cause a shutdown. The Unit Control Module takes corrective action to keep the unit running. Dual circuit design increases overall system reliability. Unlike reciprocating designs, this compressor can handle liquid slugging. Suction gas cooling allows the motor to operate at lower temperatures for longer life. Performance Superior full load efficiency. Excellent part load performance. Use of an electronic expansion valve significantly improves part load performance by minimizing superheat in the evaporator and allowing the chiller to run at reduced condensing temperatures. Unique compressor sequencing equalizes not only starts, but operating hours as well. Trouble-free Operation and Start-up Adaptive Control microprocessor keeps the Rotary chiller on-line when others would shut down. Fewer nuisance trips means less expense from unnecessary service calls. Factory installed and tested options keep start-up time and expenses minimized. Easy interface capability with the Trane Integrated Comfort system via a single twisted pair of wires. Optional remote display panel simplifies chiller monitoring/ control.
40
Mechanical specification
TRANE Series RTAA packaged air cooled liquid chiller consisting of accessible hermetic, directdrive screw compressors, with two independant circuits evaporator, condenser, microprocessorbased controls and a unit-mounted motor starter, refrigerant charged, factory runtested and ready for operation. Unit are rated in accordance with ARI 550-90. Compressor motor assembly TRANE screw compressors, accessiblehermetic, direct-drive, 2950/3600 rpm (50/60 Hz). Separately housed, pressure-lubricated rolling element bearing groups at each end of both rotors. Fully modulating capacity control by use of a slide valve in the rotor section of the compressors positioned by hydraulic action. Squirrel-cage two-pole induction motor, suction gas cooled. Oil separator and filtration devices provided separate from the compressor. Evaporator Shell-and-tube heat exchanger with internally finned copper tubes, roller expanded into the tubes sheets. Refrigerant inside the tubes and water circulating in the shell. Maximum operating pressure refrigerant side 16 Bar (232 psig), water side 14 Bar (203) psig. 19 mm thermal insulation of flexible closed cell foam. Water flanged connections on 200 serie and victaulic grooved on 300 and 400 series. Heater cable for freeze protection. Condenser W-configuration air cooled condenser coils of seamless copper tubes, expanded into aluminium fins. Integral oil cooler and subcooler circuits. Direct drive discharge fans with totally enclosed air over motors, having class F insulation and IP 55 protections. Fan guards. Leak tested at 21 Bar (304 psig), pressure rated at 35 Bar (500 psig). Two refrigerant circuits Each circuit including removable core filter dryer, liquid line shut-off valve, high pressure relief valve. Electronic expansion valve minimizing superheat in the evaporator and allowing chiller to run at reduced condensing temperature. Control panel Microprocessor-based unit control module UCM utilizing the Adaptive Control concept. The UCM provides all control and safety functions including start-up and shut down, leaving chilled water control, compressor and electronic expansion valve modulation, fans sequencing, anti-recycle logic, automatic lead/lag compressor starting and load limiting. Unit protective functions include loss of chilled water flow, evaporator freezing, loss of refrigerant, low and high refrigerant pressure, reverse rotation, compressor starting and running overcurrent, phase loss, phase unbalance, phase reversal and loss of oil flow. Clear language display (2 lines, 40 characters), door mounted, indicates over 20 operating data points including chilled water setpoint, current limit setpoint,, leaving chilled water temperature, evaporator and condenser refrigerant pressures and temperatures. Over 60 messages are displayed when a problem is detected. Starter panel Unit mounted starter panel, protection class IP 55. Panel contains part winding type motor starter, single source power supply, 3-phase current transformer for motor overload protection. Unit structure Welded steel base frame, structural steel profiles and panels, made of galvanized sheet steel, protected with a primary coating and finished with an acrylic paint. The paint can withstand 650 hours of salt spray test Accessories and options Compressor sound attenuating enclosure Condenser copper fins Communication card Vibration isolators Disconnect switch Reversed water connections Remote clear language display. Pressure gauges Flow switch Communication card + load based chilled water reset Communication card Plexiglass door (starter and control panel) Under , over voltage protection Condenser protection grids Compressor, evaporator grids Discharge service valve Factory testing All RTAA chilers are fully run tested under load before shipment. Unit operation and all control functions are factory checked and set. Shipment Units ship fully assembled and single point wired ready for operation after field connection of power supply, electric interlocks and chilled water piping. Units ship on a wooden skid with refrigerant and oil operating charges. Quality assurance The Quality Management System applied by TRANE has been subject to independant third party assesment and approval to ISO 9001: 1994, EN ISO 9001 : 1994, BS EN ISO 9001 :1994. The products described in this catalogue are designed, manufactured and tested in accordance with the approved system requirements as defined in the TRANE Quality Manual.
41
Notes
42
Notes
43
Trane reserves the right to alter any information without prior notice.
Socit Trane - Socit Anonyme au capital de 41 500 000 F - Route de Chamagne - 88130 Charmes - France Siret 306 050 188-00011 - RCS Epinal B 306 050 188 - Numro d'identification taxe intracommunautaire : FR 83 306050188 An American Standard Company
Printed in France
Imprimeur