Faults
Indications
Methodology
Diagnostic tool
Trigger
localized high e-fields
that exceed a critical value
20-30 kV/cm
Generates
Audio noise
Corrosive materials
(O3, NO-)
Radio and TV
interferences
UV - corona
UV Ph
e
+
V e-
E field
e
+
e
UV Ph
)%(Filter Transmission
10
VISIBLE
IR
120
100
8
80
6
60
40
200
20
300
400
500
600
700
Wave length (nm)
800
900
100
0
UV
C B A
input - scenery
output - screen
External surface
Line of sight
Voltage dependent
Any weather
conditions
Indicator & Actor
Fault early stage
detection
30 dB over S9
RFI/TVI
1. Corona during hazy day
2. Camera depicts the exact
corona arcing location
3. Lineman from EMC takes down
the faulty arrestor
Case 2:
USA
1.RFI at FAA Control Tower
during wet weather
2. The source: Bad grounding
on 4.16kV, 12.47kV, 115kV
insulators
Case 3:
Czech Republic
1.RFI at Czech Radio Telecomm
Authority experienced TVI
2. The source: Pin of a
ceramic insulator was
wrongly installed
Brittle fracture:
corona cameras can clearly show
surface discharge that exists on
insulators with housing
imperfections in order to avoid
catastrophic failure.
Faulty designs
Faulty installations
Poor material
Existing processes
No corona ring
Cracked insulator
Wrong design
Corona- where?
Critical
component?
Yes
No
No
Critical
location?
Yes
No
Material type
Can it
be damaged by
corona?
Events per
Minute
Yes
AN, RI, TVI
concern?
Yes
Repair or replace
ASAP
No
Low<1000
Monitor for
additional signs
Corona
intensity?
1000<Medium<5000
High> 5000
Repair or replace
ASAP
Schedule repair or
replacement