Tam3 2

Download as ppt, pdf, or txt
Download as ppt, pdf, or txt
You are on page 1of 19

Ofils proprietary material

Cannot be used without Ofil's explicit permission

Partial Discharge and the Corona Phenomenon

Solar Blind Imaging

Corona Inspection as a PDM tool in hand

Faults

Indications

Methodology

Ofils proprietary Material |


2011

Detect PD corona & arcing - in daylight

Diagnostic tool

Condition monitoring of critical components

Perform predictive maintenance

Ofils proprietary Material |


2011

Trigger
localized high e-fields
that exceed a critical value
20-30 kV/cm

Generates
Audio noise
Corrosive materials
(O3, NO-)
Radio and TV
interferences
UV - corona

In the presence of a strong E-field

Free electrons accelerate


Collide with air molecules and ionize them
Additional electrons are released
Photons are released with recombination
Procedure repeats itself
UV Ph

UV Ph

e
+

V e-

E field
e
+

e
UV Ph

Ozone blocks Solar UV Signals

)%(Filter Transmission

10

VISIBLE

IR
120
100

8
80
6

60

40

200

20

300

400

500
600
700
Wave length (nm)

800

900

100
0

Solar Radiation (W/cm2)

UV
C B A

Goal: Collect UV events & superimpose


Imaging
Black Box

input - scenery

output - screen

Ofils proprietary material


Cannot be used without Ofil's explicit permission

External surface
Line of sight
Voltage dependent
Any weather
conditions
Indicator & Actor
Fault early stage
detection

Corrosion and erosion


Pitted cement
Hydrophobicity
compromise
RFI/TVI

Case 1: A US Government Licensed Radio Amateur Operator: The


receiving equipment was reading a

noise level of some

30 dB over S9

(Signal strength is measured in S-units from


S1 to S9) and the noise blanking system of the receiving equipment
could not eliminate the noise.

RFI/TVI
1. Corona during hazy day
2. Camera depicts the exact
corona arcing location
3. Lineman from EMC takes down
the faulty arrestor

Case 2:

USA
1.RFI at FAA Control Tower
during wet weather
2. The source: Bad grounding
on 4.16kV, 12.47kV, 115kV
insulators
Case 3:

Czech Republic
1.RFI at Czech Radio Telecomm
Authority experienced TVI
2. The source: Pin of a
ceramic insulator was
wrongly installed

Tracking & loss of hydrophobicity

Brittle fracture:
corona cameras can clearly show
surface discharge that exists on
insulators with housing
imperfections in order to avoid
catastrophic failure.

Faulty designs
Faulty installations
Poor material
Existing processes

No corona ring

Grading ring installed backwards

Cracked insulator

Wrong design

Corona- where?
Critical
component?

Yes

No
No

Critical
location?

Yes
No

Material type

Can it
be damaged by
corona?

Events per
Minute

Yes
AN, RI, TVI
concern?
Yes

Repair or replace
ASAP

No

Low<1000

Monitor for
additional signs

Corona
intensity?

1000<Medium<5000

High> 5000
Repair or replace
ASAP

Schedule repair or
replacement

THANK YOU