2 - Fan Assessment - Presentation
2 - Fan Assessment - Presentation
2 - Fan Assessment - Presentation
CTS-TPT/Jan Kaminsky
Power consumption – some definitions
Shaft power (as calculated process-wise)
pV
Pshaft
p = diff. Pressure over fan [mbar]
fan V
fan
= gas flow through fan [Am3/s]
= efficiency of impeller/casing
trans = efficiency of transmission
Ptot
Pshaft
transmotor
3
Holcim Group Support Fan Workshop Dec. 2004 09.07.2019/JK
Fan performance, what’s that.ppt
Differential pressure
0 mbar-Line Static pressure
Measured p is acceptable
0 mbar-Line
Turbulence
4
Holcim Group Support Fan Workshop Dec. 2004 09.07.2019/JK
Fan performance, what’s that.ppt
Gas flow
Gas flow
Not measurable
relevant for fan
performance
Gas flow
measured
5
Holcim Group Support Fan Workshop Dec. 2004 09.07.2019/JK
Fan performance, what’s that.ppt
Contradiction in pressures after fan (Hon Chong)
Pst = -2 mbar
Pst = +2 mbar
Bernoulli:
p const pstatic 2 v 2
Example: =0.8 kg/m3, v1=25 m/s, v2=40 m/s 63% of cross section
pdyn1 = 2.5 mbar, pdyn1 = 6.4 mbar
Further internal gas flow increase and pressure loss 6
Holcim Group Support Fan Workshop Dec. 2004 09.07.2019/JK
Fan performance, what’s that.ppt
Heat loss – energy dissipation
M motor: convection
trans: convection
fan: compression
7
Holcim Group Support Fan Workshop Dec. 2004 09.07.2019/JK
Fan performance, what’s that.ppt
Compression
Temperature increase due to isentropic compression
1
pout
Tout Tin …with T in [K] and ~1.41
pin
Heat loss
H = Vnwet * cp(Tavg) * T
…with cp [kJ/Nm3K] from 100 – 500°C
1.30 - 1.35 for air
1.40 - 1.45 for combustion gas
1.45 – 1.55 kiln exhaust @ 3%O2
8
Holcim Group Support Fan Workshop Dec. 2004 09.07.2019/JK
Fan performance, what’s that.ppt
Back to Fan Efficiency
pV
fan Ptot trans motor Hot?
Hot?
Help from electricians
Step 1: Step 2:
Take readings from the suppliers fan The temperature and static
curve (flow rate and diff. Pressure). Use pressure are important for further
the density for which the suppliers curve calculations. Put in the measured
is valid (here 0.725 kg/Am3). Use your data - NOT suppliers data. The
measured density for correcting the fan resulting gas densities are
curve (here 0.75 kg/Am3). estimates for kiln exhaust gas -
NOT for air or combustion gas.
Remark:
p across fan – NOT
across fan and control
damper
10
Holcim Group Support Fan Workshop Dec. 2004 09.07.2019/JK
Fan performance, what’s that.ppt
Using the fan assessment spreadsheet (2)
Step 3:
Put in the data from
actual measurement.
Step 4:
Adjust n_equiv. until the line for
measured fan speed crosses the
measured operating point. The
n_equiv. indicates the quality of the
fan compared to suppliers
specification.
11
Holcim Group Support Fan Workshop Dec. 2004 09.07.2019/JK
Fan performance, what’s that.ppt
Using the fan assessment spreadsheet (3)
Step 5:
Put in the data for a new
expected operating point.
Step 6:
Adjust the fan speed until the line for
this speed crosses the new
operating point.
12
Holcim Group Support Fan Workshop Dec. 2004 09.07.2019/JK
Fan performance, what’s that.ppt
Using the fan assessment spreadsheet (4)
Step 7:
Take readings from suppliers
power curve. Step 9:
Adjust this factor until the red
line crosses the red mark. This
figure represents the quality of
the suppliers specification for
the fan efficiency.
Step 10:
Adjust the efficiency for the
new operating point until the
Step 8: green/red mark is laying on the
Put in your measured power red line. This figure is the
consumption. expected fan efficiency for the
new operating point.
13
Holcim Group Support Fan Workshop Dec. 2004 09.07.2019/JK
Fan performance, what’s that.ppt
Using the fan assessment spreadsheet (5)
Remark:
If you want to see the motor
limit curve on the fan
characteristic diagram set 1,
otherwise set 0.
Remark:
Put in an estimate for the
motor/transmission efficiency.
14
Holcim Group Support Fan Workshop Dec. 2004 09.07.2019/JK
Fan performance, what’s that.ppt
Using the fan assessment spreadsheet (6)
Step 3*:
Use here the diff. Pressure
across control damper and
fan.
Step 4*:
Adjust until curve for actual damper position crosses the
measured operating point. The n_equiv. indicates the
quality of the fan compared to suppliers specification.
15
Holcim Group Support Fan Workshop Dec. 2004 09.07.2019/JK