Lectures Synchronous Machines
Lectures Synchronous Machines
Synchronous Machines
N Non-uniform
air-gap
D 10 m
q-axis S S
Turbine
N
Hydro (water)
Hydrogenerator
Salient-Pole Synchronous Generator
Stator
Cylindrical-Rotor Synchronous Generator
Turbine D1m
L 10 m
Steam d-axis
Stator winding
High speed N
Uniform air-gap
3600 r/min 2-pole
Stator
1800 r/min 4-pole
q-axis Rotor winding
Direct-conductor cooling (using
hydrogen or water as coolant) Rotor
Turbogenerator
Cylindrical-Rotor Synchronous Generator
Stator
Cylindrical rotor
Operation Principle
P nm
fe
120
E K c f fe
If
Saturation characteristic of a synchronous generator.
Voltage Regulation
A convenient way to compare the voltage behaviour of two
generators is by their voltage regulation (VR). The VR of a
synchronous generator at a given load, power factor, and at rated
speed is defined as
E nl V fl
VR 100%
V fl
Where Vfl is the full-load terminal voltage, and Enl (equal to Ef)
is the no-load terminal voltage (internal voltage) at rated speed
when the load is removed without changing the field current.
For lagging power factor (PF), VR is fairly positive, for unity
PF, VR is small positive and for leading PF, VR is negative.
Equivalent Circuit_1
motor
Ia
jX jXl Ra
+
+
Ia
+ generator
Ef Eres Vt
The voltages and currents of the three phases are 120o apart in angle,
but otherwise the three phases are identical.
+
VL-L
Vt
Ef1
+ jXs Ra
Ia1
VL-L =3Vt
Determination of the parameters of the equivalent
circuit from test data
• The equivalent circuit of a synchronous generator that has been
derived contains three quantities that must be determined in order
to completely describe the behaviour of a real synchronous
generator:
– The saturation characteristic: relationship between If and f (and
therefore between If and Ef)
– The synchronous reactance, Xs
– The armature resistance, Ra
•
If
+
Vdc Vt
Short-circuit test
If
+ A
A
Vdc Isc
DC Test
– The purpose of the DC test is to determine Ra. A variable DC voltage
source is connected between two stator terminals.
– The DC source is adjusted to provide approximately rated stator current,
and the resistance between the two stator leads is determined from the
voltmeter and ammeter readings
VDC
– then RDC
I DC
– If the stator is Y-connected, the per phase stator resistance is
RDC
Ra
2
– If the stator is delta-connected, the per phase stator resistance is
3
Ra RDC
2
Determination of Xs
• For a particular field current IfA, the internal voltage Ef (=VA) could
be found from the occ and the short-circuit current flow Isc,A could
be found from the scc.
• Then the synchronous reactance Xs could be obtained using
V A E f
Z s ,unsat R X
2
a
2
s ,unsat
I scA
Ef or Vt (V) Air-gap line
OCC Isc (A) X s ,unsat Z s2,unsat Ra2
Vrated
SCC
: Ra is known from the DC test.
VA
Isc,B
Since Xs,unsat>>Ra,
Isc, A
Ef Vt , oc
IfA IfB
If (A) X s ,unsat
I scA I scA
Xs under saturated condition
Ef or Vt (V) Air-gap line
OCC Isc (A)
At V = Vrated, Vrated SCC
Vrated E f VA
Isc,B
Z s , sat R X
2
a
2
s ,sat Isc, A
I scB If (A)
IfA IfB
Generator 1
b Load
c
Switch
a/
Generator 2 b/
c/
Synchronization
Generator Load
Rest of the
power system
Xs1
Ef1
Xs2
Generator Ef2
G
Xsn Infinite bus
Efn V, f are constant
Xs eq = 0
Concept of the infinite bus
Pm
Pe, Qe
Vt
Fig. Synchronous generator connected to an infinite bus.
Pm
Pe, Qe
Vt
Pm
Pe, Qe
The complex power output of the generator in volt- Vt
Vt E f sin d
P &
Xs
Vt E f cos d Vt2
Q
Xs
Active and reactive power-angle characteristics
Pm
Pe, Qe
Vt
• The above two equations for active and reactive powers hold
good for cylindrical-rotor synchronous machines for negligible
resistance
• To obtain the total power for a three-phase generator, the above
equations should be multiplied by 3 when the voltages are line-to-
neutral
• If the line-to-line magnitudes are used for the voltages, however,
these equations give the total three-phase power
Steady-state power-angle or torque-angle characteristic of a
cylindrical-rotor synchronous machine (with negligible
armature resistance).
Real power or torque
Pull-out torque
as a generator
generator
p p/2
d d
0 p/2 p
motor
Pull-out torque
as a motor
Steady-state stability limit
3Vt E f
Total three-phase power: P sin d
Xs
3Vt E f
P
Xs
The maximum power indicated by this equation is called steady-state stability
limit of the generator. If we try to exceed this limit (such as by admitting
more steam to the turbine), the rotor will accelerate and lose synchronism
with the infinite bus. In practice, this condition is never reached because the
circuit breakers trip as soon as synchronism is lost. We have to resynchronize
the generator before it can again pick up the load. Normally, real generators
never even come close to the limit. Full-load torque angle of 15o to 20o are
more typical of real machines.
Pull-out torque
The maximum torque or pull-out torque per phase that a two-pole
round-rotor synchronous motor can develop is
Pm ax Pm ax
Tm ax
m 2p s
n
60
where ns is the synchronous speed of the motor in rpm
P or Q
d
Fig. Active and reactive power as a function of the internal angle
Problem 2
Ef BR
Fig. The phasor diagram (leading PF: overexcited and |Vt|<|Ef|) and
the corresponding magnetic field diagram of a synchronous motor.
Vt
d jIa Xs
Ia Ef
Synchronous motors are usually used in large sizes because in small sizes
they are costlier as compared with induction machines. The principal
advantages of using synchronous machine are as follows: