Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Construction Measurement III Week 4 Electrical Single Phase

Download as ppt, pdf, or txt
Download as ppt, pdf, or txt
You are on page 1of 102

Construction Measurement III(SBQ 3314)

Electrical Installations Single Phase


Lecture By Dr Sarajul Fikri Mohamed Department of Quantity Surveying, FAB, UTM Skudai Johor, Malaysia

05th January 2010

MAIN COURSE COMPONENTS

CIVIL WORKS ELECTRICAL WORKS

Pre-cast and Pre-stressed Concrete Electrical Installations


Single Phase Three Phase

MECHANICAL WORKS

Air Conditioning Installations


Unit/Split Package/Central

Fire Fighting Installations Gas Installations


LANDSCAPE WORKS

Landscape Works
Hard Landscape Soft Landscape

Table of contents

ELECTRICAL INSTALLATIONS: SINGLE PHASE


KNOWLEDGE PROJECT DRAWINGS

Building services technology Electrical components Measurement rules: SMM2 Description Taking Off Case Study

Read and check drawing Drawing numbering and scale used. Taking off list Heading and Description Take off Annotation / Side Cast Query list Final checking

Output

BQs FOR ELECTRICAL INSTALLATIONS SINGLE PHASE


3
2009 Sarajul Fikri Mohamed

Table of contents

ELECTRICAL INSTALLATIONS: SINGLE PHASE


1. Electrical installations: main components 2. SMM2 measurement rules for electrical installations 3. Taking off list for electrical installations 4. Heading and description. 5. Case study: CADANGAN MEMBINA DEWAN SERBAGUNA TAMAN KOTA JAYA, KOTA TINGGI, JOHOR 6. Studio work

2009 Sarajul Fikri Mohamed

Electrical installation and components

2009 Sarajul Fikri Mohamed

Electrical distribution

ELECTRICAL INSTALLATIONS

Electrical distribution

ELECTRICAL INSTALLATIONS
Power transmission and distributions

Types of electrical work

ELECTRICAL INSTALLATIONS

Two options Internal Supply


From DB to power points and fittings

From substation to substation

240V with a less load and domestic use

Three Phase
415V with a bigger load and supply needed for (comercial dan industrial)

External Supply

Single Phase

Single and three phase

ELECTRICAL INSTALLATIONS
Single Phase
 Bagi penggunaan rumah kediaman, voltan tiga fasa adalah terlalu tinggi dan merbahaya.  Oleh itu voltan rendah daripada satu fasa lebih sesuai digunakan untuk tujuan domestik.  Voltan piawai satu fasa ialah 240 v. Biasanya satu pengalir hidup digunakan bersama pengalir neutral iaitu:  RN  YN  BN

Three Phase
  
Voltan yang dikenakan ialah 415 v dan juga boleh mencecah 880 v bagi kilang yang menjalankan kerja berat seperti kilang besi dan kilang simen. Ia mempunyi tiga pengalir hidup dan neutral. Pengalir-pengalir hidup dikenalkan dengan kod-kod aksara berikut:  LI atau R (red): Fasa pertama  L2 ataU Y (yellow): Fasa kedua  L3 atau B (blue) : Fasa ketiga

Fakulti Alam Bina

VIDEO PRESENTATION I
SINGLE PHASE AND THREE PHASE : THE THEORY

Main components

ELECTRICAL INSTALLATIONS
INCOMING SERVICES MAIN INSTALLATION POWER INSTALLATION LIGHTING INSTALLATION ELECTRICAL APPLIANCES CONDUIT AND FITTING CABLES LIGHTNING PROTECTION SYSTEM TESTING
2009 Sarajul Fikri Mohamed

Electrical distribution

ELECTRICAL INSTALLATIONS
INCOMING SERVICES TESTING POWER INSTALLATION

FINAL SUB-CIRCUIT

ELECTRICAL APPLIANCES

LIGHTNING PROTECTION

MAIN INSTALLATION LIGHTING INSTALLATION CABLE

CONDUIT

Fakulti Alam Bina

VIDEO PRESENTATION 2
BASIC HOMES ELECTRICAL SYSTEM

Main components

ELECTRICAL INSTALLATIONS
POWER INSTALLATION 3 pin switch socket LIGHTING INSTALLATION Fluorescent light Wall light EXIT sign High bay light EL light CABLES ELECTRICAL APPLIANCES Exhaust fan Sweep ceiling fan

CONDUIT & FITTING Chased into brickwall Ceiling level

TESTING

2x1c/2.5mm PVC cable 2x1c/1.5mm PVC cable

On completion of the electrical installation test all switches, switch socket, wiring etc and make good all defects an leave everything perfect working order to the satisfaction of the S.O and TNB

Electrical typical legend in M&E drawings

ELECTRICAL INSTALLATIONS

DB & FUSES

ELCB MAIN SWITCH FUSE TNB METER CUT OFF FUSE

METERING BOARD


 

To monitor and record the total amount of electrical energy that is being consumed for the purpose of charging consumers through the issuance of electricity bills . Property of TNB 2 types of meter  Analog  Digital

TNB CUT OUT FUSE


Consumers back up protection 2 purposes: As a measure of back up protection to the fuse in the Distribution Board and also ELCB As mean of cutting of electrical supply to the consumers when required Cutout fuse is connected to live wire and it is use to control current supply. Both belong to TNB.

Main switch

ELECTRICAL INSTALLATIONS

Main switch

   

Locate at the main incoming supply of the consumers Distribution Board The purpose is to cut all of the power supply to the consumer in the event that any maintenance work needs to be carried out. Connect, cut off and control the current if their any excess current. A two terminal one way switch that contains fuse.

Circuit breaker : ELCB

ELECTRICAL INSTALLATIONS

ELCB

   

A mechanical device to connect and cutout circuit It will cut off any faulty circuit immediately Sensitive to lightning 2 types:  Earth Leakage Circuit Breaker: ELCB  Miniature Circuit Breaker: MCB

Distribution board

ELECTRICAL INSTALLATIONS

 

This is where distribution of electrical energy to various connected load take place inside the consumer premises. It also distributes the path for the earthing and neutral wire, and acts as means of flowing leakage and return current respectively.

Miniature circuit breaker : MCB

ELECTRICAL INSTALLATIONS

MCB & FUSE

Consumer unit: 1 row : 8-22 modules

ELECTRICAL INSTALLATIONS

No. Of Ways M.C.B. SIZE 8.0 10.0 14.0 18.0 22.0

Outline Dimensions (mm) L 143 175 175 182 210 W 215 255 320 380 460 H 71 71 71 71 71 H1 93 93 93 93 93

Consumer unit: 2 row : 28 modules

ELECTRICAL INSTALLATIONS

No. Of Ways M.C.B. SIZE 28

Outline Dimensions (mm) L 434 W 320 H 71 H1 93

Consumer unit: 3 rows : 42 modules

ELECTRICAL INSTALLATIONS

No. Of Ways M.C.B. SIZE 42

Outline Dimensions (mm) L 434 W 320 H 71 H1 93

RCCB AND RCBO INSIDE A DISTRIBUTION BOARD

WIRING IN DISTRIBUTION BOARD

MAIN SWITCH AND ELCB


MAIN SWITCH

4 POLE ELCB

WIRING TO DISTRIBUTION BOARD

SMM2 measurement rules

2009 Sarajul Fikri Mohamed

Measurement rules

ELECTRICAL INSTALLATIONS

Related SMM2 clauses

ELECTRICAL INSTALLATIONS
Clause R4-R5 R6-R8 R9-R13 R14-R17 R18 R19 R20-R21 R22 R23-R24 Description Equipments and Control Gear Fittings and Accessories Conduits, trunking and cable tray Cabling Final Sub-circuits Earthing Ancillaries Sundries Builder s Work

29

Measurement rules

ELECTRICAL INSTALLATIONS

Measurement rules

ELECTRICAL INSTALLATIONS
R.2 CLASIFICATION OF WORK a. b. c. d. e. f. g. h. k. I. m. n. p. q. r. s. Incoming services Standby equipment Mains installation-switch gears, sub-main cables. Power installation Lighting installation Heating installation Electrical appliances Electrical work Clock installation Sound distribution Alarm system Earthing system installation Lightning protection installation Special services Any other installation Trunking, ducting and cable trays

Measurement rules

ELECTRICAL INSTALLATIONS
LOCATION OF ELECTRICAL WORKS R3 - Location of work a. b. Internally Externally

Cadangan Membina Dan Menyiapkan Sebuah Makmal Komputer Di Sekolah Kebangsaan Sri Selangor, Petaling Jaya, Selangor. ELEMENT: ELECTRICAL SERVICES KETERANGAN BIL ubb/N/01 JUMLAH (RM)

UNIT

KUANTITI

HARGA (RM)

BILLS OF QUANTITIES FOR: INCOMING SERVICES

Preamble All quantities in this bill are provisional quantities subject to remeasurement upon construction of the said item. The tenderer must allow for testing the electrical installation and handling over of test certificate to S.O.

Incoming Services-Externally (All Provisional)

100mm UPVC class 'D' pipe complete with long bend extended beyond drain for entry of TNB, incoming cable to MSB inclusive of excavation and backfilling. 4 x 25mm pilestas (AC) cable in UPVC class 'D' pipe (m/s) buried underground to TNB panel. C Incoming Services-Internally (All Provisional) M 3.05 M 3.05

75mm x 38mm electrical trunking from meter to DB/M3B. 25mm x 25mm Telekom PVC trunking from lighting arrestors run at high level and drops to computer server.

1.00

1.00

To Collection

Cl R.2.1(d) Classification of work

Cl R.3.1(a) Location of Work

ITEM

DESCRIPTION POWER INSTALLATION (INTERNALLY) Cable

UNIT

Cl R.14.2 Generally

A 2 x 1C-2.5mm2 PVC insulated colour coded cable as specified drawn into conduit.
Cl R.15.2(a) Cables

Measurement rules

ELECTRICAL INSTALLATIONS

Measurement rules

ELECTRICAL INSTALLATIONS
EQUIPMENT AND CONTROL GEAR (NO) R4 Equipment (generator, motors) Control gear (isolator, switch fuses)
 Packaged item described with a manufacturers detail.  Limiting dimension on size shall be given.  Connecting cable ends or cable tails shall be deemed to be included with the item.  Platework and supporting steelwork Section P.

Measurement rules

ELECTRICAL INSTALLATIONS Gear Equipment and Control


Manufacturers details and dimension on size

METERING BOARD

Distribution board

ELECTRICAL INSTALLATIONS

   

Usually for houses and small loaded. Situated inside building. Including equipment such as circuit breaker and fuse SMM2 Refer to clause R.4.1(NO.)

Measurement rules

ELECTRICAL INSTALLATIONS
EQUIPMENT SUPPORTS : R5  Equipment supports enumerated and described (NO)  Method of fixing given in the description with clauses R.1.5-6.

Measurement rules

ELECTRICAL INSTALLATIONS
FITTING AND ACCESSORIES (N0) R6 Fittings (clock , alarm bells) Accessories (socket outlets) Pendant fittings NO length stages 300mm Accessories - NO (in gang) a) rated capacity b) type c) no. accessories in each gang

R7 R8

Measurement rules

ELECTRICAL INSTALLATIONS

Measurement rules

ELECTRICAL INSTALLATIONS
Switch socket outlet & socket point. Different Types for different capacity. SMM2 Refer to clause R.18.2 (No.)

Power installation

ELECTRICAL INSTALLATIONS

SOCKET

Power installation

ELECTRICAL INSTALLATIONS

TV Co-axial socket outlet

1 gang 15A Switched Socket Outlet

13A 2 gang switched socket outlet

13A 2 gang switched socket outlet with neon

Power installation

ELECTRICAL INSTALLATIONS
13A 2 gang s/s/o Bell push switch

13A 2 gang s/s/o with neon

Telephone socket

Lighting installation

ELECTRICAL INSTALLATIONS
Fluorescents Lights and emergency light. Specification refer to manufacturer. SMM2 Refer to clause R.4.1(NO.)

Fluorescent light

KELUAR emergency sign

Measurement rules

ELECTRICAL INSTALLATIONS

Electrical appliance

ELECTRICAL INSTALLATIONS

Fan, MATV point and telephone point. SMM2 Refer to clause R.6, R.22.1 (NO.)

Measurement rules

ELECTRICAL INSTALLATIONS

Measurement rules

ELECTRICAL INSTALLATIONS
CONDUIT, TRUNKING AND CABLE TRAYS R9.1 Conduit and fittings. (m) a) type b) size c) specification d) saddles & crampets pattern e) nature of background Except for final sub-circuit (measured overall conduit fittings) e.g tees, elbows, bend, cover plates, bushes, locknuts, nipples, stopping-lugs and reducing bushes), short running lengths and branches).

Conduit, trunking and metal tray

ELECTRICAL INSTALLATIONS

PVC Conduit

Galvanized Iron Conduit

Measurement rules

ELECTRICAL INSTALLATIONS
CONDUIT, TRUNKING AND CABLE TRAYS Classification : a) conduits fixed to surfaces b) conduits fixed in chases c) conduits embedded in floor screeds d) conduits embedded in concrete

Conduit, trunking and metal tray

ELECTRICAL INSTALLATIONS

Conduit inside the suspended ceiling

Conduit, trunking and metal tray

ELECTRICAL INSTALLATIONS
Conduits fixed in chases brickwall

Conduit, trunking and metal tray

ELECTRICAL INSTALLATIONS

Drilling works to chases wiring to the brickwall

Measurement rules

ELECTRICAL INSTALLATIONS
CONDUIT, TRUNKING AND CABLE TRAYS R9.2 Special boxes, adaptable box, floor trap boxes, purposes made boxes, rectangular junction boxes required for drawing in cables , flameproof boxes & expansion joint ( N0 EXTRA OVER)

Conduit support

ELECTRICAL INSTALLATIONS
Munson ring

Conduit assecories

ELECTRICAL INSTALLATIONS

Coupling Flange Coupling

Long Nipple

Short Nipple

Solid Male Bend

Conduit Adaptor (Isometric to PG Thread)

Reducer

Conduit assecories

ELECTRICAL INSTALLATIONS

Stainless Steel Chain

Lead Washer

Neoprene Washer

Stopping Plug

Locking Ring

Locknut

Female Bush

Male Bush

Conduit assecories

ELECTRICAL INSTALLATIONS

Terminal Box

Angle Box

Through Box

Inspection Elbow

Branch Two Way Box

Tee Box

Electrical conduit

ELECTRICAL INSTALLATIONS

Measurement rules

ELECTRICAL INSTALLATIONS
CONDUIT, TRUNKING AND CABLE TRAYS R9.3 Flexible conduits & extensible conduit (NO) i) size ii) overall length iii) type iv) size & type termination glands (N0) R9.4 Components & special boxes ( for making connection of conduit in trunking )

Measurement rules

ELECTRICAL INSTALLATIONS
CONDUIT, TRUNKING AND CABLE TRAYS R10.1 Trunking (m)
i) type ii) size iii) no & size compartment iv) method of connecting

R10.2 Fitting (NO) and EXTRA OVER R10.3 Connection between trunking & item of equipment & control gear use flanges and or the forming of apertures (N0)

Trunking

ELECTRICAL INSTALLATIONS
A rectangular metal made system that either horizontally or vertically fixed to wall. A good mechanical protection. Made from 18 gauge steel sheet. Available size: 50mm x 50mm 70mm x 100mm 150mm x 75mm 150mm x 150mm Equipped with bend, tee, and junction.

Trunking

ELECTRICAL INSTALLATIONS

Cable and trunking use for connection from main to distribution board or distribution board to socket. Size and Material. SMM2 Refer to clause R.15, R.9 (M)

Trunking fittings

ELECTRICAL INSTALLATIONS

90r Gusset Bend Front Lid (Traditional)

90r Gusset Bend Inside Lid (Traditional)

45r Bend Outside Lid

45r Bend Front Lid

90r Gusset Bend Front Lid

45r Bend Inside Lid

Measurement rules

ELECTRICAL INSTALLATIONS
CONDUIT, TRUNKING AND CABLE TRAYS R10.4 Pin racks (NO) i) type; and ii) size R11.1 Busbar Trunking (m) Clauses R.10.1 a) type; b) width; c) rated capacity; and d) method of capacity R11.2 Tap-off units, feeder units, fire barries & the like (NO)

Measurement rules

ELECTRICAL INSTALLATIONS
CONDUIT, TRUNKING AND CABLE TRAYS R12.1 Trays (m) i) type; ii) width; and iii) method of jointing R12.2 Stools (NO) i) type; and ii) size R12.3 Fitting (NO and EXTRA OVER )

Cable tray

ELECTRICAL INSTALLATIONS

Measurement rules

ELECTRICAL INSTALLATIONS

Measurement rules

ELECTRICAL INSTALLATIONS
CABLES R15.1 Cables (m) measured as the net length of the conduit, trunking or tray. other cable measured as fix (without any allowance for sag) between boxes, equipment control gear, fittings, accessories etc. except for final sub-circuits.

Flexible PVC insulated cord

The conductors used in domestic installations are called cables and consist of a conductor of low resistance such as copper and aluminium surrounded by an insulator of high resistance such as rubber and plastic. Cable sizes are known by the nominal cross sectional area of the conductor and up to 2.5mm2 are usually of one strand.

Types of wire

ELECTRICAL INSTALLATIONS

Measurement rules

ELECTRICAL INSTALLATIONS
Cables R15.2 Cables (m) i) type ii) size iii) classification CLASSIFICATION a) drawn into conduits or ducts b) laid or drawn into trunking c) laid or drawn into trunking and laced into ciucuit d) fixed to surfaces e) wrapped around pipework f) laid in trenches g) fixed to insulators in overhead lines h) suspended from catenary cables Cable joints (NO) Line taps (NO) i) size ii) type of cable iii) shrouds (type)

R15.4 R15.5

Cable classification

ELECTRICAL INSTALLATIONS

Underground cable

Fixed to wall

Fixed in ceiling

Measurement rules

ELECTRICAL INSTALLATIONS
CABLE R15.6 Cable termination glands (NO) i) type & size of cable ii) type of gland R15.7 Conduit: boxes, adaptable boxes & the like used with cable termination glands (NO - separately) i) type ii) size of cable iii) joint-boxes, sealing boxes (type) R16.1 Components for supporting cable given in the description of the cable stating type and spacing. Alternatively, components of combination system (NO)

Measurement rules

ELECTRICAL INSTALLATIONS
CABLE R17 Connections to public mains, making good public highway and other work which may only carried out by Public Undertaking or Local Authority PROVISIONAL SUM

Measurement rules

ELECTRICAL INSTALLATIONS
FINAL SUB-CIRCUITS R18.1 Distribution sheets and drawing showing layout shall be given. R18.2 Points (NO) i) cable & conduit installations ii) ampere rating iii) classification CLASSIFICATION a) Lighting points: one way or two way b) Socket or switch socket points c) Immersion heater points, cooker outlet points etc.

Measurement rules

ELECTRICAL INSTALLATIONS

Measurement rules

ELECTRICAL INSTALLATIONS
EARTHING R19.1 Tapes for earthing (m)
i) size; ii) type; and iii) type & spacing of saddles, cleats, clip holdfasts & the like

R19.2 Conductor connections & junctions (NO)


i) type; and ii) size

R19.4 Test clamps (NO)


i) type ii) size; and iii) method of connecting

Earthing installation

ELECTRICAL INSTALLATIONS

Typical earth-electrode pit

Earthing & Bonding requirement

Earthing using cooper strip

Earth electrode pit

Cooper strip

Measurement rules

ELECTRICAL INSTALLATIONS
EARTHING R19.5 Earth electrodes (NO)
i) type ii) size; and iii) driving electrode into ground

R19.6 Air termination points (NO)


i) type ii) size; and iii) method of connecting

Lightning protection installation

ELECTRICAL INSTALLATIONS

Air Termination (NO.) Copper Tape Roof Conductor. (M) SMM2 Refer to clause R.19.6, R.22.2, R.19.

Measurement rules

ELECTRICAL INSTALLATIONS
ANCILLARIES R20 Loose keys, tools, spares and the like (NO separately)
i) type; and ii) quantity

Rack for holding tools (NO)

Measurement rules

ELECTRICAL INSTALLATIONS
SUNDRIES R22.1 Marking the position of holes, mortice, chases & the like (ITEM) R22.2 General earth bonding & earthing (ITEM) R22.3 Disconnecting, setting aside & refixing equipment (ITEM) R22.4 Temporary operating each installation (ITEM) R22.5 Testing each installation (ITEM) R22.6 Preparing plans or diagrams of the installations (ITEM)

Summary of measurement rules

2009 Sarajul Fikri Mohamed

SUMMARY OF MEASUREMENT RULES


ITEM 1) Main Installation sub main cables meter panel M ETHOD OF M EASUREM ENT UNIT CLAUSE

distribution board cables conduits sundries mark the holes & etc. general bonding testing

stating the type and size shall be described with manufacture's detail specification ditto stating the type, size and the location ( net length ) stating the type, external size and the location stating the nature of works & relevant particulars each installation ditto and stating particulars of any special insurance cover required by Employer

m no

R.2.1.c R.4.2

no m m

R.15.2 R.9.1

item item item

R.22.1 R.22.2 R.22.5

SUMMARY OF MEASUREMENT RULES


ITEM 2) Power Installation fittings & accessories socket cables conduits final sub-circuit sundries mark the holes & etc. general bonding testing METHOD OF MEASUREMENT UNIT CLAUSE

unless stated all shall be enumerated stating the type, size and the location ( net length ) stating the type, external size and the location stating the ampere rating stating the nature of works & relevant particulars each installation ditto and stating particulars of any special insurance cover required by Employer

no m m no item item item

R.6.1 R.15.2 R.9.1 R.18.2 R.22.1 R.22.2 R.22.5

SUMMARY OF MEASUREMENT RULES


ITEM 3) Lighting Installation fittings & accessories switch cables conduits final sub-circuit sundries mark the holes & etc. general bonding testing METHOD OF MEASUREMENT UNIT CLAUSE

unless stated all shall be enumerated stating the type, size and the location ( net length ) stating the type, external size and the location stating the ampere rating stating the nature of works & relevant particulars each installation ditto and stating particulars of any special insurance cover required by Employer

no m m no item item item

R.6.1 R.15.2 R.9.1 R.18.2 R.22.1 R.22.2 R.22.5

SUMMARY OF MEASUREMENT RULES


ITEM METHOD OF MEASUREMENT UNIT CLAUSE

4) Electrical Appliances fittings & accessories switch unless stated all shall be enumerated cables stating the type, size and the location ( net length ) conduits stating the type, external size and the location final sub-circuit stating the ampere rating sundries mark the holes & etc. stating the nature of works & relevant particulars general bonding each installation testing ditto and stating particulars of any special insurance cover required by Employer

no m m no item item item

R.6.1 R.15.2 R.9.1 R.18.2 R.22.1 R.22.2 R.22.5

SUMMARY OF MEASUREMENT RULES


ITEM 5) Earthing System Installation cables copper tape conductor connection test clamps earth electrodes air termination sundries mark the holes & etc. testing METHOD OF MEASUREMENT UNIT CLAUSE

given in accordance with clause R.15 stating the type & size stating the type & size ditto & method of connecting ditto & driving electrodes into groundshall be given stating the type & size & method of connection stating the nature of works & relevant particulars each installation and stating particulars ofany special insurance cover required by Employer

m m no no no no

R.19.1 R.19.1 R.19.2 R.19.4 R.19.5 R.19.6

item item

R.22.1 R.22.5

SUMMARY OF MEASUREMENT RULES


ITEM 6) Builder's Work excavating trenches METHOD OF MEASUREMENT UNIT CLAUSE

cable covers

for cables and pipe ducts n. exc. 55mm nominal size refer to clause D.12.9 & exc. 55mm refer to clause V.2 stating the type & size

R.24.1

R.24.2

Taking off list

2009 Sarajul Fikri Mohamed

Taking off list

ELECTRICAL INSTALLATIONS
Preamble General notes Main installation Meter panel (no) Main Switch Board (no) Distribution Board (no) Main & sub main cabling (m) Conduit and trunking (m) Sundries (no) Testing (item) Power installation Fittings and accessories Socket (no) Point (no) Cables (m) Conduits (m) Final sub circuit (no) Sundries Mark the holes (item) General earth bonding (item) Testing (item)

2009 Sarajul Fikri Mohamed

Taking off list

ELECTRICAL INSTALLATIONS
Lighting installation Fittings & accessories Swicth (no) Point (no) Final sub-circuit (no) Sundries Mark the holes (item) General earth bonding (item) Testing (item) Lightning installation Copper tape (no) Test clamps (no) Air termination (no) Earth chamber(no) Sundries Mark the holes (item) Testing (item) Builders work Excavation trenches (m)

2009 Sarajul Fikri Mohamed

TAKING OFF LISTS DOMESTIC HOUSING SINGLE PHASE


1.Main Installation
- sub main cables - meter panel - distribution board - cables - conduits - sundries = mark holes = general bonding = testing m no no m no item item item

TAKING OFF LISTS DOMESTIC HOUSING SINGLE PHASE


2. Power Installation
- fitting & accessories = socket - cables - conduits - final sub-circuit - sundries = mark holes = general bonding = testing no m m no item item item

TAKING OFF LISTS DOMESTIC HOUSING SINGLE PHASE


3. Lighting Installation
- fittings & accessories = switch no - cables m - conduits m - final sub circuit no - sundries = mark holes item = general bonding item = testing item

TAKING OFF LISTS DOMESTIC HOUSING SINGLE PHASE


4. Electrical Appliances
- fitting & accessories = switch - cables - conduits - final sub circuit - sundries = mark holes = general bonding = testing no m m no item item item

TAKING OFF LISTS DOMESTIC HOUSING SINGLE PHASE


5. Earthing System Installation
cables copper tape test clamps conductor connection earth electrodes air termination sundries = mark holes = testing m no no no no no item item

You might also like