Indoor Air Quality Real-Time Monitoring in Airport Terminal Areas: An Opportunity for Sustainable Management of Micro-Climatic Parameters

1
Department of Civil, Chemical, Environmental and Materials Engineering—DICAM, University of Bologna, via Terracini 28, 40131 Bologna, Italy
2
Department of Civil, Chemical, Environmental and Materials Engineering—DICAM, University of Bologna, viale del Risorgimento 2, 40136 Bologna, Italy
*
Author to whom correspondence should be addressed.
Sensors 2018, 18(11), 3798; https://doi.org/10.3390/s18113798
Submission received: 2 October 2018 / Revised: 23 October 2018 / Accepted: 2 November 2018 / Published: 6 November 2018
(This article belongs to the Section Remote Sensors)

Abstract

:
Indoor air quality (IAQ) management in public spaces is assuming a remarkable importance. Busy environments, like airport terminals, are currently regarded as possible hotspots and IAQ is a crucial element for passengers and staff protection, as well as a key aspect of airport passenger experience. A one-month monitoring period has been performed on IAQ in the airport of Bologna (Italy), as prototypal example of large regional airport. Four strategic areas within the airport have been equipped with electronic monitoring platforms, including different contaminants and two microclimatic sensors. Data suggest that daily variation in IAQ parameters typically follow the activity pattern of the different environments under study (i.e., passengers’ flows) for gaseous contaminants, where particulate matter counts oscillate in a definite range, with a significant role played by ventilation system. Gaseous contaminants show a correlation between indoor and outdoor concentrations, mainly due to airside activities. Micro-climatic comfort parameters have been tested to match with standards for commercial environments. As results appears in line with typical households IAQ values, the current air ventilation system appears to be adequate. Nevertheless, an integrated air management system, based on real-time monitoring, would lead to optimization and improvement in environmental and economical sustainability.

1. Introduction

Air transport plays a crucial role in global economic development and in the last decade air traffic has increased dramatically worldwide, with a significant growth in atmospheric emissions.
During the last forty years, the worldwide aviation industry has increased, on average, by 5% yearly. At the same time, emissions from civil aviation activities have increased accordingly and, in particular, greenhouse gas emissions from international aviation have grown by 87% since 1990 [1]. According to recent studies and forecasts [2,3,4,5], the annual rate of air traffic growth should be around 4–5% in the next years: this expected further growth of the sector and the parallel development of city airports—often included in urban areas—have increased the attention on the environmental effects that growing airport traffic could generate on the communities living around airports and, at the same time, have put even growing pressures on governments and regulators to improve the development of effective environmental policies.
The impacts produced by airport activities—from the aircraft Landing and Take-Off cycle (LTO) to handling operations and ground support equipment, concerning air-side activities, and to airport ground access systems to passenger, baggage, and freight terminal operations, concerning land-side activities—have received increasing attention during the last years [6,7,8,9,10,11]. In the airport surroundings, monitoring systems provide data used to build and manage models able to identify the contribution of airport activities to outdoor pollutant concentration, with special regard to nitrogen oxides (NOx), volatile organic compounds (VOCs), hydrocarbons (HC), particulate matter (PM), and carbon monoxide (CO) [12,13,14,15,16]. Evidences from the literature has shown that airport operations significantly contribute to annual pollutants concentration at the airport boundaries. In particular, CO concentrations in the vicinity of the terminals were found to be highly dependent on aircraft movement, whereas NOx concentrations were dominated by emissions from ground support vehicles [17,18,19].
Service quality and passenger satisfaction are topics of primary interest in the airport industry. Direct and indirect surveys campaigns have been systematically carried out by international agencies (Airport Council International and IATA), as well as frequent ad hoc initiatives by single airports [20]. Due to increasing traffic and changes in the air transport market, it has become more important for airport operators to monitor and analyze relevant data and information regarding passengers’ perception on Airport Service Quality (ASQ), by complying national and international rules. Even if the reduction of any negative environmental impacts is crucial for airport management, it is worthless if the airports are not healthy and comfortable places to live and work in. Indoor environmental quality, including indoor thermal, lighting, acoustic, and air quality, is of paramount importance for the well-being of travelers and airport workers. Therefore, the progressive evolution towards sustainable and low carbon airport terminal buildings should not be successfully performed without tackling these aspects.
Airport terminal buildings are composed by areas accomplishing different functions, such as the departure lounge with boarding gates and shopping areas, security control areas, check-in area, baggage claim hall, arrival hall, etc. Different zones have different heating and cooling demand, due to different occupant density, activity performed, or time spent by travelers. These issues make the management of indoor environmental conditions challenging. Moreover, the passenger flow in airport terminals varies significantly throughout the year or even throughout a single day, due to the flight schedule, leading to a worsening of the terminal indoor environment quality.
Indoor air quality (IAQ) assessment becomes, consequently, a key element for the environmental quality evaluation of airport terminals, but it is necessary to identify technological solutions suitable for the purpose. Several reviews of opportunities currently offered in the field are available [21,22,23] presenting analytical capabilities of the different monitoring methods, with particular regards to accuracy, precision, threshold levels for detection, time resolution, comparability, and data completeness.
The fluctuations in the level of activity and crowding, typical of terminal environment, would more likely be described by the application of a continuous monitoring method, able to identify possible repetitive patterns of contamination and, therefore, support best management options. This confirms the widely recognized need for a broader application of monitoring on short time intervals (i.e., continuous or semi-continuous) [24] to build consistent and statistically relevant database, even if spot monitoring would offer higher precision and more information on composition, growth, and characteristics of indoor air pollutants (e.g., particle mass spectrometers).
In the authors’ opinion, the literature concerning airport indoor air quality appears scarce and not exhaustive and it is mostly linked to energy efficiency. Balaras et al. [25] investigated the energy consumption and the indoor environment quality of Hellenic airport terminal buildings in 2003 by means of direct surveys. The results show that almost 70% of the surveyed people complained about the poor indoor air quality, and remarkable differences were highlighted at various areas of the terminal. Numerical simulations performed by Meng et al. [26] show that by enhancing vertical ventilation to discharge hot air near the ceiling, the average number of dissatisfied passengers can be reduced and the energy consumption for heating and cooling can be saved. Finally, an interesting work of Wang et al. [27] shows that thermal environment and air quality are the two crucial factors for the overall satisfaction level, and travelers’ air quality satisfactory level is highly correlated with the CO2 concentration.
Within the presented framework, a two-month period of IAQ and micro-climatic parameter characterization has been performed in different areas of a medium-size airport terminal with the aim of identifying possible criticality and opportunity to improve environmental management.

2. Materials and Methods

The goal of the study was identified, in accordance with the test-site “Aeroporto Guglielmo Marconi di Bologna”, Italy, in performing a preliminary study of air quality in potentially critical airport areas. In particular, the efforts have been aimed at identifying airborne contamination patterns and their possible relationship with the characteristic activities of the specific environment (i.e., passengers’ flow, boarding operations, baggage reclaim). Bologna Airport is a medium-size airport (a large regional, following the EU classification), very close to the city center of Bologna, in Northern Italy. In 2017 approximately 72,000 aircraft movements and 8.2 million passengers were registered.
From the operative point of view, the study aimed to assess the effectiveness of the currently used ventilation and air treatment systems, both for IAQ and micro-climatic comfort management. The ventilation system currently applied is set for continuous functioning, 24/7, without any exchange rate adjustment. The experiment has been structured into two main phases of IAQ monitoring in different areas of the airport (see Figure 1), regarded as potentially critical for IAQ management, i.e., security check, waiting area for boarding and baggage claim (both landside and airside).
A monitoring technology has been applied at pilot scale, in order to investigate the IAQ and evaluate the opportunity for the scaling-up of the implementation to a full-time monitoring network. The monitoring platform is manufactured by Ideas & Motion S.r.l., v. Moglia 19, 12062 Cherasco (CN), Italy, while data management and visualization software is developed by Microsys s.r.l., v. Antonio da Recanate 1, 20124 Milano (MI), Italy.
The electronic platform offers four slots for contaminants concentration sensors, together with two microclimatic sensors, for temperature and humidity. In particular, sensors equipped on each platform are:
Environmental parameters:
  • Temperature (°C): [−40 °C to 125 °C], ±2 °C worse accuracy;
  • Humidity (%RH): [0–100% RH], ±4%RH accuracy, referred to sensor’s reading;
  • Air contaminants/odorous gases (Figaro TGS2602, by Figaro Engineering Inc., 1-5-11 Senbanishi, Mino, Osaka 562-8505, Japan) (ppm): [1 to 30 ppm], C6H5CH3 (toluene), H2S (hydrogen sulphide), CH3CH2OH (ethanol), NH3 (ammonia), H2 (hydrogen);
  • Solvent gases/VOC (Figaro TGS2620, by Figaro Engineering Inc., 1-5-11 Senbanishi, Mino, Osaka 562-8505, Japan) (ppm): [50 to 5000 ppm], CH3CH2OH (ethanol), H2 (hydrogen), C4H10 (isobutene), CO (carbon monoxide), CH4 (methane);
  • Particulate matter (Shinyei PPD42NS, by SHINYEI Technology Co., Ltd., 77-1 Kyomachi, Chuo-ku, Kobe 651-0178, Japan) (pcs/L):
    PM1 (Shinyei PPD42NS): [0 to 28,000 pcs/L], detectable particle size 1–10 µm;
    PM2.5 (Shinyei PPD42NS): [0 to 280,000 pcs/L], detectable particle size 2.5–10 µm.
One of the two monitoring platform is also equipped with two sensors (MiCS-4514, by SGX Sensortech, Corcelles-Cormondreche, Switzerland) for gaseous contaminants typically related to outdoor environment and possibly linked with the airside activity of an airport, i.e., CO and NO2. Both the airborne contaminants are related to combustion processes, but, where the former is generated in the presence of incomplete combustion of hydrocarbon-based fuel at low reaction temperature (i.e., in winter conditions, contributing to the traditional “smog”), the latter is the result of combustion in air (where nitrogen and oxygen are the most abundant gases) at high temperature and it is involved in the photochemical smog formation. For both contaminants, traffic is typically regarded as a major source [28,29].
Semiconductor sensors, such as the Figaro TGS2602 and Figaro TGS2620, consist of two elements: the first one, made of tin dioxide (SnO2) with crystalline structure, and the second one acting as a heater. The first one presents an excess of electrons due to the charging effect triggered by the second unit, making it sensitive to different gases concentrations. Once electrically supplied, resistance detected at the sensor (precision of ±1% in the whole range) is proportional to gases concentration. Through software conversion, gas concentration is displayed as parts per million (ppm) on the web platform. Since sensors are non-selective, i.e., they are sensible to groups of gases, not to single ones, they can be calibrated both with single and mixture of gases (ethanol, hydrogen, control mixture UNI EN 12619:2002, i.e., methane 2.0 mg/m3, ethane 1.5 mg/m3, toluene 0.5 mg/m3, benzene 0.5 mg/m3, methylene chloride 0.5 mg/m3, with oxygen 11%, carbon dioxide 10%, carbon monoxide 50 mg/m3, and nitrogen as complementary). The calibration performed and cross-referenced against a single device calibrated through standard method returns a final accuracy of ±15%, including resistance detection and calibration errors.
The Shinyei PPD42NS laser scatter sensor detects particulate matter (PM), classifying them by size ranges, thanks to light beam alteration (Figure 2). A 100 Ω resistor provides a thermal plume, allowing particles inside the detection chamber, without ventilation. Through the projection of an infrared light beam, the sensor indirectly estimates the number of PM suspended in air by the scattering of the beam itself hitting particles traveling across the chamber. Photons are scattered with an approximate 45° angles, focused by a lens into a specific region where, finally, they are detected by a photodiode, translating light into a pulse signal, which is proportional to particles concentration. In this way, the measured parameter is the air opacity (opacity percentage or low pulse occupancy), defined as the percentage of time (relative to a predefined time interval, e.g., 1 s) in which particles are detected by the photo diode sensor. The particle detection threshold of the sensor is determined by a pass-band filter, removing part of the background noise and identifying the range of particles counted. In particular, the two channels allow two size ranges count (i.e., 1–10 microns and 2.5–10 microns) with accuracy related to PM concentration (±1.5% for concentrations below 5%; ±2.5% for concentrations above 15%, i.e., the sensor’s saturation limit), with no indication whether could be related to difference in the total mass, size distribution, or optical properties of the lens, or a combination of these phenomena.
Sensors may, therefore, present quite a remarkable drawback, due to relatively low accuracy and reading method (e.g., for particulate sensor), but it can be overcome in two ways:
  • statistical analysis of the broad population of data collected (one sample every five minutes per sensor, makes 288 concentration data per each sensor per day);
  • evaluation of trends and possible repetitive patterns in contamination: rather than treating data as absolute values, they are elaborated in comparison to a baseline (in the present study, in percentage increase over the minimum value detected). Each sensor collects data every five minutes, but it can be set to detect concentration and environmental data on five minutes to one-hour basis. Thanks to wireless sensor network (WSN) technology, it can communicate data to a server via Wi-Fi, GSM network or Ethernet, every determined interval, making them available almost in real-time for displaying.
The experimental set-up has been organized in two different monitoring periods, during summertime, within two different areas of the terminal, and developed as follows (Figure 3).

2.1. Phase 1

Two monitoring platforms have been placed into two different areas within the departure zone of the terminal for a period of 30 days. In particular, security check and waiting for boarding area have been investigated. IAQ data collected have been treated statistically, identifying possible singularity and repetitive patterns in the typical day of standard airport activity. For this purpose, instant concentration data, collected every 5 min by the monitoring platform, have been aggregated into hourly average values.
In order to evaluate the reliability of data registered, considering the peculiarity of the monitoring technology applied, results obtained have been compared with data collected into three indoor environments (i.e., households) located in the same urban area as the airport terminal, acting as control group. In particular, hourly average values have been compared with data collected into control environments.
Micro-climatic parameters (i.e., temperature and humidity) have been tested during the whole period and treated statistically in accordance with airborne contaminants concentrations. Additional information has been gathered on each area’s occupation, with particular regard to passengers’ flow data, organized on hourly basis, as to be compared with contaminants trends outlined.

2.2. Phase 2

Following the Phase 1 experimental set-up, two monitoring platforms has been installed for a period of 30 days on each side of a baggage claim belt, landside and airside, into the arrivals area of the terminal. IAQ data collected have been treated statistically, identifying possible singularity and repetitive patterns in the typical day of standard airport activity. Particular attention has been paid to possible correlation between indoor and outdoor air quality values, due to the connection between the two environments, represented by the portcullis for baggage delivery. For this purpose, two key parameters (VOC and particulate matter) have been evaluated as indoor and outdoor profiles over the typical day. Additional information has been gathered on each area’s occupation, with particular regard to baggage delivery registration and consequent passengers’ flows, organized on an hourly basis, as to be compared with contaminants trends outlined. Data collected by CO and NO2 sensors, equipped on a single monitoring platform, has been evaluated over the two testing periods, in order to compare contaminants profile over the typical day in indoor and outdoor conditions.
An additional step of the study is carried on temperature and humidity in order to investigate passenger’s thermal well-being. At first, a validation step for data collected has been performed, comparing dataset measured on landside terminal areas and the nearest Environmental Authority (Agenzia Regionale per l’Ambiente, Emilia-Romagna Region—ARPAE) long-term monitoring station. In particular, in order to overcome possible singularity and specific events, a statistical treatment of registered data, based on hourly average values, has been applied.
Once verified the reliability of data trends and set reference accordingly with ARPAE records, data have been evaluated in comparison with national standards on energy efficiency and environmental comfort. In particular, indoor environments treated with heating, cooling and venting systems (HVAC) are recommended to be conditioned, during summertime, i.e., the experimental monitoring period for the present study, to temperatures above 26 ± 2 °C and relative humidity ranging between 50% and 60%, following regional regulation, as well as national and international guidelines [30,31,32,33].

3. Results and Discussion

Results gathered and elaborated as presented in the previous section are reported in the following, accordingly with the stepwise experimental set-up.
In particular, the first round of monitoring (Phase 1) is reported in terms of environmental conditions (T and RH%) and airborne pollutants (VOC, odorous gases, PM1, PM2.5, and CO2 equivalent), with average weekly values and variation indexes (SD and SE) in both areas investigated (i.e., security check area and waiting for boarding area). Parameters detected have been, then, compared with passengers’ flow, in order to assess the influence of activity intensity in the area over IAQ. A statistical analysis of average values registered on daily basis has been performed to highlight fluctuations within the week. Finally, data collected have been compared with a set of households monitored in the same period and same urban area, as to provide a benchmark of exposure to airborne pollutants. The very same analysis has been performed on concentration and environmental data collected during the second phase (Section 3.2. Phase 2), during which the focus was set to baggage claim area, both landside and airside. In this case, a direct comparison between the two areas was carried out.
The study was completed with a micro-climatic assessment (Section 3.3. Microclimatic Evaluation), in terms of temperature and relative humidity.

3.1. Phase 1

The first validation step has been successfully concluded, with evidence of the general correspondence of data collected into airport environments with airborne contamination parameters detected into a three-household control group.
As security check area is characterized by a steady presence of staff, passengers’ flow is related to daily flights schedule. Contaminants’ trends have been registered and elaborated on an hourly basis. Table 1 reports the average weekly values and Figure 2 reports hourly average values recorded on daily basis for airborne contaminants, in relative terms of percentage ratio over the minimum value registered (typically correspondent to 3 a.m. value). VOCs and odorous gases sensors registered quite similar trends, while CO2eq follows early morning trend (from 5 a.m. to 9 a.m., approximately), displaying secondary peaks on 2 p.m. and 7 p.m., with lower variation compared with the minimum. Particulate matter sensors appear to register lower variations in the daily trends.
Passengers’ flows at security checks are reported as columns in Figure 4a. As evident from the overlapping and similarities between passengers’ and airborne contaminants data, the level of activity in the area seems to be reasonably imputed for the variation in IAQ. In particular, peaks registered in the number of passengers could be regarded as trigger for higher gases concentrations, initially recovered by the air treatment system and then, during the day, cumulating in the environment. As evident from the comparison between Figure 4a,b, the activity rate of the waiting for boarding area is quite discontinuous, as the specific boarding gates are involved only in medium-long range flights, with recurring crowding around 2 p.m. (Figure 4b).
Passengers’ flows resulted the main driving force in gaseous contaminants’ concentration trends (i.e., VOC, odorous gases (OD), and CO2 equivalent), displaying similar behavior during the typical day. The primary peak in the area’s activity, registered again, at 2 p.m., in this case outnumber the peak registered on airborne contaminants (e.g., 225% increase over the minimum registered value in passengers’ flow against 100% increase over the minimum registered value in VOC). Particulate matter, on the other hand, shows lower variability on the typical day profile (i.e., values range in a +8% range over the minimum).
In the following Table 2 and Table 3, a statistical evaluation of values monitored on the different days of the week has been performed in comparison with average values obtained on the standard week, in the security check area. The data show remarkable fluctuations; a t-test has been performed to evaluate if the differences between average daily values of concentration could have been generated by similar processes or arise from different determinants. The computed p-values highlights day-by-day significant differences due to environmental and/or external factors, in particular for PM10 (five days out of seven) which seems to be more closely related to the number of passengers present than the other pollutants considered (see Figure 4a).
Contamination patterns have been evaluated over the different days of the week, in terms of hourly averages, in order to spot possible significant difference between each day and the reference average, i.e., “standard week”, in the security check area.
As evident from Figure 5, trends appear remarkably similar, with higher differences around lunch time, when the weekend’s days show peaks, both for PM1 and VOC. Even in summer flight schedule, typically organized over vacations in fact, weekends are generally characterized by peculiar routines.
Considering the relative basis of values measured by sensors equipped, a reference set of values has been established by monitoring IAQ into three different households located in the same urban area as the terminal airport. Hourly average values have been calculated and a range of acceptability has been identified consequently. The following Table 4 reports interval limit values for each parameter monitored, together with average values calculated over the standard week. As evident from the values reported, terminal airport IAQ and micro-climatic parameters appear in line with household’s environment Even with a limited benchmark of households monitored and considering the intrinsic differences between airport terminal and household environment, in terms of ventilation and occupation, it is reasonable to assess that passengers’ exposure to airborne contaminants tested is basically similar in the two environments.

3.2. Phase 2

Airborne contaminants concentrations registered as hourly average on the typical day are reported in Table 5 and Figure 6, together with flights’ schedule and expected passengers’ flow in the area, treated accordingly.
VOC and odorous gases concentrations detected appear directly related to the level of activity in the area, supporting Phase 1 observations. CO2 equivalent, on the other hand, registers a peculiar trend, with minimum values correspondent with central hours of the typical day and maximum values at nighttime. This suggesting a direct correlation between CO2 equivalent concentration and area’s specific activity (i.e., baggage delivery), where portcullis opening for baggage delivery and consequent natural ventilation from outdoor interface appears to affect this parameter remarkably. PM trends appear scarcely affected by working conditions of the area, thus confirming Phase 1 results.
A comparison of airborne contaminants profile, detected at the interface outdoor/indoor, has been performed and the results obtained show, for VOC, an evident correlation between the two environments, with minimum values in the small hours and afternoon and peaks in the central hours of the typical day and at nighttime (possibly following what detected on CO2 equivalent sensor), but with higher variation over indoor values. This suggests that the indoor environment, in this case, is both affected by the anthropic activity indoor and outdoor (Figure 7a).
For particulate matter, on the other hand, a limited range of variation is identified both indoor and outdoor (Figure 7b). Nevertheless, the different shape of the curves suggests that, in the indoor environment, this class of contaminants is reasonably under control, regardless of the level of activity in the area.

3.3. Microclimatic Evaluation

The initial validation process applied over temperature and humidity sensors returned different results, depending on the parameter tested.
In particular, temperature sensor presented a systematic error of 2.6 °C, easily set in the post-processing phase, but a quite reliable detection of temperature variations. Therefore, considerations based on temperature detection could be reasonably regarded as reliable, even with the limited accuracy reported by manufacturer (i.e., ±2 °C), considering the scope of the present study.
On the other hand, relative humidity registered by monitoring platform implemented, returned flattened values for the upper range, compared with ARPAE results. It was not possible to discern whether differences are to be attributed to the different location of the two monitoring platforms, with consequences on local occurrences, or to lower sensibility of the implemented sensors in the upper range, at present stage of the study. Therefore, humidity data have been evaluated considering the limitation emerged.
The security check area (Figure 8a) shows a temperature trend comprised in the two grades tolerance range around 26 °C defined by the reference regulation, thus testifying the HVAC efficiency on this issue. Different scenario is registered at the boarding gate area (Figure 8b) in which no temperature below 24 °C (i.e., reference value) was registered: its values are much higher than ones registered into the security check area, due to:
  • direct solar irradiation by panoramic glass wall facing airside of the terminal;
  • typical difficulty in ventilating open spaces uniformly; and
  • heat generated by passengers waiting in the area for long periods: the average energetic metabolism by sedentary human activities is typically estimated in the range 105–180 watts [25].
The differences in structure and use of area investigated during Phase 2 are reflected in the temperature and relative humidity values registered. Temperature hourly average values results compliant with the reference only during afternoon (i.e., 1 p.m. to 7 p.m.), while the rest of the typical day profile is permanently lower (Figure 9). Relative humidity profile appears varying in a wider range than ones registered in Departures areas and permanently below the reference range.
A correct interpretation of such micro-climatic conditions profile required a focus on outdoor data registered during the same period, due to direct indoor/outdoor interface characterizing the area. A sudden change in meteorological conditions was registered by the outdoor monitoring platform during the second monitoring period, thus evidently affecting micro-climatic conditions indoor, even considering methodological limitations [34].

4. Conclusions

Since the scope of the study was set in a preliminary characterization of IAQ into key areas of the terminal of a medium-sized airport, four areas have been selected as representative of possible criticalities in IAQ management. A WSN technology has been installed for a period of 30 days to evaluate a set of airborne contaminants, as well as micro-climatic parameters (i.e., temperature and humidity). IAQ data collected have been validated through comparison with references provided by a three-household control group characterized during the same period, placed in the same region. Micro-climatic parameters have been compared with a stable monitoring station powered by ARPAE in the proximity of the airport, finding a good correlation between the two temperature profiles, while humidity values displayed remarkable differences, especially in the upper range.
Phase 1 was aimed to assess the impact of passengers’ flow over IAQ in specific areas of Departure zone of the terminal. Results obtained allowed to identify an evident element of solicitation represented by the typical activity rate (i.e., passengers’ flow through security checks and waiting at the boarding gate) within the areas investigated for gaseous contaminants (i.e., VOC, CO2 equivalent, and odorous gases), while particulate matter presents a narrow range of variation of the typical day profile, with only limited dependence on areas occupation.
Phase 2 returned results in line with Phase 1, confirming the correlation between gaseous contaminants trends and the level of activity in the area, even at the outdoor interface (i.e., on the airside of baggage delivery belt). Nevertheless, a peculiar profile has been detected on CO2 equivalent sensor, partially coupled with VOC ones, showing an accumulation of gases in the indoor environment during nighttime and low operational periods (i.e., when indoor/outdoor interface is most likely closed). This would suggest the necessity of improving the efficiency of the air ventilation/treatment system to support the removal activity on the gaseous contaminants. At the same time, particulate matter counts result scarcely variated over the typical day profile, both with regards to the location of the sensor (indoor/outdoor, with almost undetectable variations in indoor) and to the activity level, thus testifying an adequate management of the specific contaminants performed by the actual HVAC system.
HVAC system’s performance appears, therefore, efficient in terms of filtration, following CDC-NIOSH definition [35], but it seems not able to provide an air cleaning (i.e., gases and vapors removal) sufficient to respond to solicitation deriving from anthropic activity in the area. Areas investigated, in fact, are characterized not only by passengers’ flow, but, in the case of the departures area, by commercial and food-preparing activities, such as coffee bars and restaurants. As widely documented [36], food preparation may be regarded as a major source of airborne contamination in indoor (not industrial) environments, in particular of VOCs and particulate matter [35,36,37,38,39]. A closer control on such emissions could lead to a better IAQ management in the departure area. CO and NO2 trends followed the expected complementary profile, related to temperature and solar radiation cycles during the day. The possibility of discerning the airside activity contribution from background traffic, considering the highly populated area where the case study airport is set, is left for future study developments. The evaluation of micro-climatic comfort within the investigated areas returned differentiated conditions: while security check area, in fact, presented quite consistent climatic conditions, waiting for boarding area, as well as baggage delivery area, appeared not completely compliant with reference temperature and, particularly, humidity range. These results should be evaluated considering several issues:
  • Reliability of results: discrepancy detected on humidity sensor readings compared with the standard ARPAE monitoring platform, suggests that further investigations would be required in order to draw definite conclusions on this point; and
  • Expected exposure rates for staff and travelers: The arrivals area (in our case, the baggage claim area) is generally characterized by shorter permanence of travelers and discontinuous activity performed by the staff, therefore the perception of micro-climatic comfort is limited, while a closer control over the same parameters into departure area would lead to more significant improvement in travelers’ experience and staff routine. In this sense, the present management over security check area appears satisfying.
On the basis of results obtained from this preliminary characterization phase, it is possible to outline the great opportunity offered by a real-time monitoring network for IAQ and micro-climatic comfort parameters in airport environment in the perspective both of the sustainable management of the facility and travelers experience improvement.

Author Contributions

Conceptualization: A.B. and L.M.; data curation: S.Z., F.L. and E.F.; formal analysis: S.Z., F.L. and E.F.; investigation: S.Z. and F.L.; methodology: A.B. and L.M.; software: S.Z.; supervision: A.B. and L.M.; validation: F.L. and E.F.; writing—original draft, S.Z., F.L. and E.F.; writing—review and editing: A.B. and L.M.

Funding

This research received no external funding.

Acknowledgments

The authors acknowledge the Airport of Bologna for kindly making this study available. The authors also would like to acknowledge U-Earth Biotechnologies for supplying the monitoring system, Gabriella Motta, PhD, as technology developer, Ideas&Motions Srl, as technology manufacturer and Microsys srl, as software platform developer.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. EEA. European Aviation Environmental Report 2016. 2016. Available online: https://ec.europa.eu/transport/sites/transport/files/european-aviation-environmental-report-2016-72dpi.pdf (accessed on 2 November 2018).
  2. ICAO. Global Aviation CO2 Emission Projections to 2050. Information Paper. May 2009. Available online: https://www.icao.int/environmental-protection/GIACC/Giacc-4/Giacc4_ip01_en.pdf (accessed on 17 June 2018).
  3. Tyler, T. Annual Review, 2012; IATA: Montreal, QC, Canada, June 2012; Available online: http://www.iata.org/publications/Pages/annual-review.aspx (accessed on 17 June 2018).
  4. Boeing. Annual Report. 2016. Available online: http://investors.boeing.com/investors/financial-reports/default.aspx (accessed on 17 June 2018).
  5. Airbus. Global Market Forecast 2017–2036. Comm. Rep. 2017. Available online: http://www.airbus.com/aircraft/market/global-market-forecast.html (accessed on 17 June 2018).
  6. Yu, K.N.; Cheung, Y.P.; Cheung, T.; Henry, R.C. Identifying the impact of large urban airports on local air quality by nonparametric regression. Atmos. Environ. 2004, 38, 4501–4507. [Google Scholar] [CrossRef]
  7. Lu, C.; Morrell, P. Determination and applications of environmental costs at different sized airports—Aircraft noise and engine emissions. Transportation 2006, 33, 45–61. [Google Scholar] [CrossRef] [Green Version]
  8. Graham, A. Managing Airports: An International Prospective, 4th ed.; Routledge: London, UK, 2008. [Google Scholar]
  9. Simonetti, I.; Maltagliati, S.; Manfrida, G. Air quality impact of a middle size airport within an urban context through EDMS simulation. Transp. Res. Part D Transp. Environ. 2015, 40, 144–154. [Google Scholar] [CrossRef]
  10. Khammash, L.; Mantecchini, L.; Reis, V. Micro-simulation of airport taxiing procedures to improve operation sustainability: Application of semi-robotic towing tractor. In Models and Technologies for Intelligent Transportation Systems, Proceedings of 5th IEEE International Conference on Intelligent Transportation Systems, Napoli, Italy, 26–28 June 2017; IEEE: Toulouse, France, 2017; pp. 616–621. [Google Scholar]
  11. Lantieri, C.; Mantecchini, L.; Vignali, V. Application of noise abatement procedures at regional airports. Proc. Inst. Civ. Eng. Transp. 2016, 169, 42–52. [Google Scholar] [CrossRef]
  12. Unal, A.; Hu, Y.; Chang, M.E.; Odman, M.T.; Russell, A.G. Airport related emissions and impacts on air quality: Application to the Atlanta International Airport. Atmos. Environ. 2005, 39, 5787–5798. [Google Scholar] [CrossRef]
  13. Carslaw, D.C.; Beevers, S.D.; Ropkins, K.; Bell, M.C. Detecting and quantifying aircraft and other on-airport contributions to ambient nitrogen oxides in the vicinity of a large international airport. Atmos. Environ. 2006, 40, 5424–5434. [Google Scholar] [CrossRef]
  14. Schürmann, G.; Schäfer, K.; Jahn, C.; Hoffmann, H.; Bauerfeind, M.; Fleuti, E.; Rappenglück, B. The impact of NOx, CO and VOC emissions on the air quality of Zurich airport. Atmos. Environ. 2007, 41, 103–118. [Google Scholar] [CrossRef]
  15. Postorino, M.N.; Mantecchini, L. A transport carbon footprint methodology to assess airport carbon emissions. J. Air Transp. Manag. 2014, 37, 76–86. [Google Scholar] [CrossRef]
  16. Postorino, M.N.; Mantecchini, L.; Paganelli, F. Green airport investments to mitigate externalities: Procedural and technological strategies. In Sustainable Entrepreneurship and Investments in the Green Economy, 1st ed.; IGI Global: Hershey, PA, USA, 2017; pp. 231–256. [Google Scholar]
  17. Masiol, M.; Harrison, R.M. Quantification of air quality impacts of London Heathrow Airport (UK) from 2005 to 2012. Atmos. Environ. 2015, 116, 308–319. [Google Scholar] [CrossRef]
  18. Carslaw, D.C.; Williams, M.L.; Barratt, B. A short-term intervention study—Impact of airport closure due to the eruption of Eyjafjallajökull on near-field air quality. Atmos. Environ. 2012, 54, 328–336. [Google Scholar] [CrossRef]
  19. Koudis, G.S.; Hu, S.J.; Majumdar, A.; Jones, R.; Stettler, M.E. Airport emissions reductions from reduced thrust takeoff operations. Transp. Res. Part D Transp. Environ. 2017, 52, 15–28. [Google Scholar] [CrossRef]
  20. Bezerra, G.C.L.; Gomes, C.F. The effects of service quality dimensions and passenger characteristics on passenger’s overall satisfaction with an airport. J. Air Transp. Manag. 2015, 44, 77–81. [Google Scholar] [CrossRef]
  21. Chow, J.C.; Doraiswamy, P.; Watson, J.G.; Chen, L.W.A.; Ho, S.S.H.; Sodeman, D.A. Advances in Integrated and Continuous Measurements for Particle Mass and Chemical Composition. J. Air Waste Manag. Assoc. 2008, 58, 141–163. [Google Scholar] [CrossRef] [PubMed] [Green Version]
  22. Chow, J.C. Critical Review: Measurement Methods to Determine Compliance with Ambient Air Quality Standards for Suspended Particles. J. Air Waste Manag. Assoc. 1995, 45, 320–382. [Google Scholar] [CrossRef] [PubMed]
  23. McMurry, P.H. A Review of Atmospheric Aerosol Measurements. Atmos. Environ. 2000, 34, 1959–1999. [Google Scholar] [CrossRef]
  24. Solomon, P.A.; Sioutas, C. Continuous and Semicontinuous Monitoring Techniques for Particulate Matter Mass and Chemical Components: A Synthesis of Findings from EPA’s Particulate Matter Supersites Program and Related Studies. J. Air Waste Manag. Assoc. 2008, 58, 164–195. [Google Scholar] [CrossRef] [PubMed]
  25. Balaras, C.A.; Dascalaki, E.; Gaglia, A.; Droutsa, K. Energy conservation potential, HVAC installations and operational issues in Hellenic airports. Energy Build. 2003, 35, 1105–1120. [Google Scholar] [CrossRef]
  26. Meng, Q.L.; Li, Q.; Zhao, L.H.; Li, L.; Chen, Z.L.; Chen, Y.; Wang, S.X. A case study of the thermal environment in the airport terminal building under natural ventilation. J. Asian Archit. Build. Eng. 2009, 8, 221–227. [Google Scholar] [CrossRef]
  27. Wang, Z.; Zhao, H.; Lin, B.; Zhu, Y.; Ouyang, Q.; Yu, J. Investigation of indoor environment quality of Chinese large-hub airport terminal buildings through longitudinal field measurement and subjective survey. Build. Environ. 2015, 94, 593–605. [Google Scholar] [CrossRef]
  28. United States Environmental Protection Agency. State and County Emission Summaries: Carbon Monoxide; Air Emission Sources; United States Environmental Protection Agency: Washington, DC, USA, 2013.
  29. United States Environmental Protection Agency. State and County Emission Summaries: Nitrogen Oxides; Air Emission Sources; United States Environmental Protection Agency: Washington, DC, USA, 2013.
  30. Regolamento Regionale 3 aprile 2017, N.1 “Regolamento Regionale di Attuazione Delle Disposizioni in Materia di Esercizio, Conduzione, Controllo, Manutenzione e Ispezione Degli Impianti Termici per la Climatizzazione Invernale ed Estiva Degli Edifice e per la Preparazione Dell’acqua Calda per usi Igienici Sanitari, a Norma Dell’articolo 25-Quarter Della L.R. 23 Dicembre 2004, n. 26 e S.M.”. Available online: https://bur.regione.emilia-romagna.it/dettaglio-inserzione?i=66e0c80c0e4b42b084c9e00664b6886b (accessed on 2 November 2018).
  31. “Accordo tra il Ministero Della Salute, le Regioni e le Province Autonome sul Documento Concernente Linee-Guida per la Tutela e la Promozione Della Salute Negli Ambienti Confinati”, DPR 16/04/2013 n. 74. Available online: http://www.gazzettaufficiale.it/eli/gu/2001/11/27/276/so/252/sg/pdf (accessed on 2 November 2018).
  32. “Impianti Aeraulici ai fini di Benessere. Classificazione, Prescrizione e Requisiti Prestazionali per la Progettazione e la Fornitura”, UNI EN 10339. 1995. Available online: http://store.uni.com/catalogo/index.php/uni-10339-1995.html?josso_back_to=http://store.uni.com/josso-security-check.php&josso_cmd=login_optional&josso_partnerapp_host=store.uni.com (accessed on 18 October 2018).
  33. “Ventilazione Degli Edifici non Residenziali—Requisiti di Prestazione per i Sistemi di Ventilazione e di Climatizzazione per Edifici non Residenziali”, UNI EN 13779:2008. Available online: http://store.uni.com/catalogo/index.php/uni-en-13779-2008.html (accessed on 18 October 2018).
  34. Nguyen, J.L.; Schwartz, J.; Dockery, D.W. The Relationship between indoor and outdoor temperature, apparent temperature, relative humidity, and absolute humidity. Indoor Air 2015, 24, 103–112. [Google Scholar] [CrossRef] [PubMed]
  35. Department of Health and Human Services, Centers for Disease Control and Prevention (CDC), National Institute for Occupational Safety and Health (NIOSH). Guidance for Filtration and Air-Cleaning Systems to Protect Building Environments from Airborne Chemical, Biological, or Radiological Attacks; NIOSH: Cincinnati, OH, USA, 2003.
  36. Wang, H.; Xiang, Z.; Wang, L.; Jung, S.; Wiedensohler, A.; Chen, C. Emissions of volatile organic compounds (VOCs) from cooking and their speciation: A case study for Shanghai with implications for China. Sci. Total Environ. 2018, 621, 1300–1309. [Google Scholar] [CrossRef] [PubMed]
  37. Zhang, C.Y.; Ma, Y.L. Characterization of non-methane hydrocarbons emitted from Chinese cooking. Acta Sci. Circumst. 2003, 31, 768–1774. [Google Scholar] [CrossRef]
  38. Wang, L.; Xiang, Z.; Stevanovic, S.; Ristovski, Z.; Salimi, F.; Gao, J.; Li, L. Role of Chinese cooking emissions on ambient air quality and human health. Sci. Total Environ. 2017, 589, 173–181. [Google Scholar] [CrossRef] [PubMed]
  39. Peng, C.Y.; Lan, C.H.; Lin, P.C.; Kuo, Y.C. Effects of cooking method, cooking oil, and food type on aldehyde emissions in cooking oil fumes. J. Hazard. Mater. 2017, 24, 160–167. [Google Scholar] [CrossRef] [PubMed]
Figure 1. Terminal areas selected for monitoring phase: (a) security check lines and boarding gates (1st floor); and (b) baggage claim area (ground floor).
Figure 1. Terminal areas selected for monitoring phase: (a) security check lines and boarding gates (1st floor); and (b) baggage claim area (ground floor).
Sensors 18 03798 g001
Figure 2. Monitoring platform detail: wiring board and sensors (a); and wireless communication system (b) (courtesy of U-Earth Biotechnologies)
Figure 2. Monitoring platform detail: wiring board and sensors (a); and wireless communication system (b) (courtesy of U-Earth Biotechnologies)
Sensors 18 03798 g002
Figure 3. Experimental set-up and flow chart of activities, for phase 1 (a), when Departure area of the Terminal was involved, and phase 2 (b), when Arrival area was investigated.
Figure 3. Experimental set-up and flow chart of activities, for phase 1 (a), when Departure area of the Terminal was involved, and phase 2 (b), when Arrival area was investigated.
Sensors 18 03798 g003
Figure 4. Correlation between level of activity (i.e., passengers’ flow) and airborne contaminants in terms of variation from the minimum value: (a) security check area; and (b) waiting for boarding area.
Figure 4. Correlation between level of activity (i.e., passengers’ flow) and airborne contaminants in terms of variation from the minimum value: (a) security check area; and (b) waiting for boarding area.
Sensors 18 03798 g004
Figure 5. Hourly average values for particulate matter (a) and volatile organic compound (b) over different days of the week.
Figure 5. Hourly average values for particulate matter (a) and volatile organic compound (b) over different days of the week.
Sensors 18 03798 g005
Figure 6. Correlation between the level of activity (i.e., passengers’ flow) and airborne contaminants in terms of variation from the minimum value, baggage claim area.
Figure 6. Correlation between the level of activity (i.e., passengers’ flow) and airborne contaminants in terms of variation from the minimum value, baggage claim area.
Sensors 18 03798 g006
Figure 7. Concentrations in baggage delivery area, indoor (IN) and outdoor (OUT) in terms of increase from the minimum value registered, typical day: (a) VOC; and (b) particulate matter.
Figure 7. Concentrations in baggage delivery area, indoor (IN) and outdoor (OUT) in terms of increase from the minimum value registered, typical day: (a) VOC; and (b) particulate matter.
Sensors 18 03798 g007
Figure 8. Micro-climatic evaluation, Phase 1, in terms of temperature and relative humidity, typical day profile: (a) security check area; and (b) boarding gate area.
Figure 8. Micro-climatic evaluation, Phase 1, in terms of temperature and relative humidity, typical day profile: (a) security check area; and (b) boarding gate area.
Sensors 18 03798 g008
Figure 9. Micro-climatic evaluation, Phase 2, baggage claim area, in terms of temperature and relative humidity, typical day profile.
Figure 9. Micro-climatic evaluation, Phase 2, baggage claim area, in terms of temperature and relative humidity, typical day profile.
Sensors 18 03798 g009
Table 1. Average weekly values for T, RH%, CO2, PM10, PM2.5, OD gases, and VOC (Phase 1—departures area).
Table 1. Average weekly values for T, RH%, CO2, PM10, PM2.5, OD gases, and VOC (Phase 1—departures area).
Security Check AreaT (°C)RH%CO2eqPM1PM2.5OD GASVOC
Avg.2544.091776.925196.331789.440.81680.2238
SE0.00890.044813.74.960.93010.00260.0009
SD0.81724.091253.13454.4185.040.23380.0798
min23304504240.851538.230.33980.0625
max2851737012,156.162642.161.97660.8281
Wait Boarding Area
Avg.2736.381230.435467.781995.71.6290.051
SE0.0130.0386.5355.2131.460.0050
SD1.1693.5597.37476.52133.460.4770.023
min25254504226.451606.560.8750.011
max31475873.6612,991.383844.9615.450.546
Table 2. Statistical evaluation of average PM10 and VOC values obtained on the different days of the week and average values of the standard week in security check area (average value, standard deviation, and t-test p-value).
Table 2. Statistical evaluation of average PM10 and VOC values obtained on the different days of the week and average values of the standard week in security check area (average value, standard deviation, and t-test p-value).
PM10VOC
Avg.Std. Dev.p-ValueAvg.Std. Devp-Value
Standard week5196.33454.42 0.22380.0798
MON5189.73407.800.61950.22270.08080.6614
TUE5171.39417.980.07690.21640.08190.0033 *
WED5208.13440.050.39860.22090.06710.2391
THU5254.04470.110.0001 *0.24230.07100.0001 *
FRI5216.93488.380.16490.20350.06590.0001 *
SAT5200.46473.790.78030.21620.07020.0021 *
SUN5146.13466.150.0005 *0.24030.10160.0001 *
(*) Sign. for p < 0.05.
Table 3. Statistical evaluation of average PM2.5 and OD values obtained on the different days of the week and average values of the standard week in security check area (average value, standard deviation and t-test p-value).
Table 3. Statistical evaluation of average PM2.5 and OD values obtained on the different days of the week and average values of the standard week in security check area (average value, standard deviation and t-test p-value).
PM2.5OD
Avg.Std. Dev.p-ValueAvg.Std. Devp-Value
Standard week1789.4485.04 0.81680.2338
MON1796.0379.840.013 *0.81680.21840.9999
TUE1792.7778.020.20730.80090.23500.0306 *
WED1791.4281.710.45540.80190.23130.0423 *
THU1801.1687.080.0001 *0.83410.22500.0180 *
FRI1782.8788.220.0145 *0.78450.21060.0001 *
SAT1785.2591.260.12030.81610.21940.9236
SUN1779.1685.990.0001 *0.85420.27370.0001 *
(*) Sign. for p < 0.05.
Table 4. Results obtained on the standard week (average values) compared with control environments.
Table 4. Results obtained on the standard week (average values) compared with control environments.
T (°C)RH%CO2eqPM1PM2.5OD GASVOC
Avg_MIN_House2129.72471.754199.101458.950.70300.147
Avg_MAX_House3145.801518.727607.982065.183.0081.403
Standard week2544.091776.925196.331789.440.8160.223
Table 5. Average weekly values for T, W, CO2, PM10, PM2.5, OD gases, and VOC (Phase 2—arrivals area).
Table 5. Average weekly values for T, W, CO2, PM10, PM2.5, OD gases, and VOC (Phase 2—arrivals area).
Bag. Claim LandsideT (°C)RH%CO2eqPM1PM2.5OD GASVOC
Avg2344.373394.215594.751872.380.39710.1091
SE0.01500.05120.755.3410.98600.00110.0004
SD1.6545.6082280.85587.03108.370.12200.0405
min153004641.891659.900.09770.0391
max296311,329.3327,540.844066.012.23050.7344
Bag. Claim Airside
Avg2244.685526.167377.032579.100.420.022
SE0.0370.08331.397.971.00560.00230.0001
SD4.1149.2073465.24879.81111.010.25490.0095
min11214505828.052228.170.24610.0039
max366716,391.6618,107.583871.4516.480.2305

Share and Cite

MDPI and ACS Style

Zanni, S.; Lalli, F.; Foschi, E.; Bonoli, A.; Mantecchini, L. Indoor Air Quality Real-Time Monitoring in Airport Terminal Areas: An Opportunity for Sustainable Management of Micro-Climatic Parameters. Sensors 2018, 18, 3798. https://doi.org/10.3390/s18113798

AMA Style

Zanni S, Lalli F, Foschi E, Bonoli A, Mantecchini L. Indoor Air Quality Real-Time Monitoring in Airport Terminal Areas: An Opportunity for Sustainable Management of Micro-Climatic Parameters. Sensors. 2018; 18(11):3798. https://doi.org/10.3390/s18113798

Chicago/Turabian Style

Zanni, Sara, Francesco Lalli, Eleonora Foschi, Alessandra Bonoli, and Luca Mantecchini. 2018. "Indoor Air Quality Real-Time Monitoring in Airport Terminal Areas: An Opportunity for Sustainable Management of Micro-Climatic Parameters" Sensors 18, no. 11: 3798. https://doi.org/10.3390/s18113798

APA Style

Zanni, S., Lalli, F., Foschi, E., Bonoli, A., & Mantecchini, L. (2018). Indoor Air Quality Real-Time Monitoring in Airport Terminal Areas: An Opportunity for Sustainable Management of Micro-Climatic Parameters. Sensors, 18(11), 3798. https://doi.org/10.3390/s18113798

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop