Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Air changes per hour, abbreviated ACPH or ACH, or air change rate is the number of times that the total air volume in a room or space is completely removed and replaced in an hour. If the air in the space is either uniform or perfectly mixed, air changes per hour is a measure of how many times the air within a defined space is replaced each hour. Perfectly mixed air refers to a theoretical condition where supply air is instantly and uniformly mixed with the air already present in a space, so that conditions such as age of air and concentration of pollutants are spatially uniform.[1]

In many air distribution arrangements, air is neither uniform nor perfectly mixed. The actual percentage of an enclosure's air which is exchanged in a period depends on the airflow efficiency of the enclosure and the methods used to ventilate it. These systems range from a conceptual system of perfect displacement, which removes and replaces all air in a space, to a short circuit flow in which very little of the existing air is replaced.[2] The actual amount of air changed in a well mixed ventilation scenario will be 63.2% after 1 hour and 1 ACH.[3] In order to achieve equilibrium pressure, the amount of return air (air leaving the space) and the amount of supply air (air entering the space) must be the same.

Definitions

edit
Age of air
The average time elapsed since molecules of air in a given volume of air entered the building from outside.
Concentration
The quantity of one constituent dispersed in a defined amount of another.
Concentration, tracer gas
The volume or mass of tracer gas divided by the volume or mass of air plus tracer gas.
Outdoor air
Air outside a building or taken from outdoors and not previously circulated through the system.
Perfect mixing
A theoretical airflow distribution pattern within a ventilated space where the supply air is instantaneously and uniformly mixed with the air in the space such that the concentration of all constituents in the air, and the age of air, are spatially uniform.
Return air
Air extracted from a space and totally or partially returned to an air conditioner, furnace, or other heat source.
Supply air
Air entering a space from an air-conditioning, heating, or ventilating apparatus.

Source:[1]

Formulas

edit

Air changes per hour

edit

In Imperial units:  

where:

  • ACPH = number of air changes per hour; higher values correspond to more ventilation
  • Q = Volumetric flow rate of air in cubic feet per minute (cfm)
  • Vol = Space volume L × W × H, in cubic feet

In metric units  

where:

  • ACPH = number of air changes per hour; higher values correspond to more ventilation
  • Q = Volumetric flow rate of air in liters per second (L/s)
  • Vol = Space volume L × W × H, in cubic meters

For a given room or building size and number of air changes per hour, the volumetric flow requirement is usually specified in cubic meters per hour when using metric units.[4]

Ventilation rates

edit

Ventilation rates are often expressed as a volume rate per person (CFM per person, L/s per person). The conversion between air changes per hour and ventilation rate per person is as follows:

 

where:

  • Rp = ventilation rate per person (cubic feet per minute (CFM) per person or cubic meters per minute per person)
  • ACPH = Air changes per hour
  • D = Occupant density (square feet per occupant or square meters per occupant)
  • h = Ceiling height (feet or meters)

One cubic meter per minute = 16.67 liter/second

Air change rate recommendations

edit

Air change rates are often used as rules of thumb in ventilation design. However, they are seldom used as the actual basis of design or calculation. For example, residential ventilation rates are calculated based on area of the residence and number of occupants.[5] Non-residential ventilation rates are based on floor area and number of occupants, or a calculated dilution of known contaminants.[6] Hospital design standards use air changes per hour.[7] Recommended air changes rates can be found in relevant standards.[5][6][7] Recent research indicates that Air Changes per Hour (ACH) alone may not be a reliable parameter for making ventilation recommendations. A new parameter, effective Air Changes per Hour (called ACHH by Mojtaba Zabihi et. al.[8]), which incorporates both the flow rate and large-scale airflow patterns, could provide a more accurate measure of how efficiently air is supplied and circulated within a room. This is particularly important for effectively managing airborne disease spread.[9]

Methods of measurement

edit

Air changes per hour is a measurement intended to communicate the air change effectiveness of a space’s ventilation system. Discussion around the ASHRAE standard 62, Ventilation for Acceptable Indoor Air Quality led to the development of a more direct method of measuring air change effectiveness with the use of a tracer gas.[1] A tracer gas is a small amount of easily-detected gas which is mixed with air in order to study airflow patterns. This method directly compares the age of the air where occupants breathe to the age of air that would occur were the air of the space perfectly mixed. The method is designed to more accurately understand the effects of air-flow patterns within a space, to identify or avoid such occurrences as short-circuiting airflow patterns, in which most of the supply air goes directly to the exhaust, and fails to mix with the air already present.[2][1]

There are two ways to apply this method; the most commonly used technique, Tracer Gas Decay (step-down), consists of a short burst of gas injected into the space to establish a constant concentration within the building, then injection is stopped and concentration decay at a certain position is recorded, and second Tracer Gas Step-Up, where tracer gas is injected at a constant rate and the concentration response at a certain position is recorded[10]

Airtightness in building

edit

The most common technique to measure airtightness is the fan pressurization method, also known as the blower door test. It is measured by the number of air changes per hour (ACH) that occur when there is a differential pressure of 50 pascals between outside and inside the building. If an air volume equal to the inside volume of the building flows across the envelope in one hour, then ACH = 1.[11] Airtightness improves buildings' energy performance since low airtightness levels imply high infiltration rates, draughts, risk of condensation, and moisture accumulation, and other effects.[12] For this reason, the Passive House standard established performance requirements for airtightness requiring be less than 0.6 ACH with a pressure difference between inside and outside of 50 Pa.[13]

Effects of ACH due to forced ventilation in a dwelling

edit

Forced ventilation to increase ACH becomes a necessity to maintain acceptable air quality as occupants become reluctant to open windows due to behavioural changes such as keeping windows closed for security.[14]

Air changes are often cited as a means of preventing condensation in houses with forced ventilation systems often rated 3–5 ACH though without referencing the size of the house. However, where ACH is already greater than 0.75 a forced ventilation system is unlikely to be of use at controlling condensation and instead insulation or heating are better remedies.[14] Seven out of eight houses studied in NZ in 2010 had an ACH (corrected for ventilation factors) of 0.75 or greater.[14] The presence of forced ventilation systems has been shown in some cases to actually increase the humidity rather than lower it.[14] By displacing air inside a dwelling with infiltrated air (air brought in from outside the dwelling), positive pressure ventilation systems can increase heating (in winter) or cooling (in summer) requirements in a house.[14][15] For example, to maintain a 15 °C temperature in a certain dwelling about 3.0 kW of heating are required at 0 ACH (no heat loss due to warmed air leaving the dwelling, instead heat is lost due to conduction or radiation), 3.8 kW at 1 ACH and 4.5 kW are required at 2 ACH.[14] The use of roof space for heating or cooling was seen as ineffectual with the maximum heating benefits occurring in winter in more southerly regions (being close to the South Pole in these southern hemisphere reports) but being equivalent only to about 0.5 kW or the heating provided by about five 100 W incandescent light bulbs; cooling effects in summer were similarly small and were more pronounced for more northerly homes (being closer to the equator); in all cases the values assumed that the ventilation system automatically disengaged when the infiltrating air was warmer or cooler (as appropriate) than the air already in the dwelling as it would otherwise exacerbate the undesirable conditions in the house.[15]

References

edit
  1. ^ a b c d "ASHRAE Standard 129-1997 (RA 2002): Measuring Air-Change Effectiveness". Atlanta, GA: American Society of Heating, Refrigerating and Air-Conditioning Engineers. 2002. {{cite journal}}: Cite journal requires |journal= (help)
  2. ^ a b Fisk, William J.; Faulkner, David; Sullivan, Douglas; Bauman, Fred (1997-06-01). "Air change effectiveness and pollutant removal efficiency during adverse mixing conditions". Indoor Air. 7 (1): 55–63. Bibcode:1997InAir...7...55F. doi:10.1111/j.1600-0668.1997.t01-3-00007.x. ISSN 0905-6947. OSTI 803749.
  3. ^ Bearg, David W. (1993). Indoor Air Quality and HVAC Systems. CRC Press. p. 64. ISBN 0-87371-574-8.
  4. ^ § 13-2. Ventilasjon i boligbygning - Direktoratet for byggkvalitet
  5. ^ a b "ANSI/ASHRAE Standard 62.2-2022: Ventilation and Acceptable Indoor Air Quality in Low-Rise Residential Buildings". Atlanta, GA: American Society of Heating, Refrigerating and Air-Conditioning Engineers. 2022: 58. ISSN 1041-2336. {{cite journal}}: Cite journal requires |journal= (help)
  6. ^ a b "ANSI/ASHRAE Standard 62.1-2022: Ventilation and Acceptable Indoor Air Quality". Atlanta, GA: American Society of Heating, Refrigerating and Air-Conditioning Engineers. 2022: 90. ISSN 1041-2336. {{cite journal}}: Cite journal requires |journal= (help)
  7. ^ a b "ANSI/ASHRAE/ASHE Standard 170-2021: Ventilation of Health Care Facilities". Atlanta, GA: American Society of Heating, Refrigerating and Air-Conditioning Engineers. 2021: 54. ISSN 1041-2336. {{cite journal}}: Cite journal requires |journal= (help)
  8. ^ Zabihi, Mojtaba; Li, Ri; Brinkerhoff, Joshua (1 March 2024). "Influence of indoor airflow on airborne disease transmission in a classroom". Building Simulation. 17 (3): 355–370. doi:10.1007/s12273-023-1097-y. ISSN 1996-8744.
  9. ^ Zabihi, Mojtaba; Li, Ri; Brinkerhoff, Joshua (1 March 2024). "Influence of indoor airflow on airborne disease transmission in a classroom". Building Simulation. 17 (3): 355–370. doi:10.1007/s12273-023-1097-y. ISSN 1996-8744.
  10. ^ Van Buggenhout, S.; Van Brecht, A.; Eren Özcan, S.; Vranken, E.; Van Malcot, W.; Berckmans, D. (October 2009). "Influence of sampling positions on accuracy of tracer gas measurements in ventilated spaces". Biosystems Engineering. 104 (2): 216–223. Bibcode:2009BiSyE.104..216V. doi:10.1016/j.biosystemseng.2009.04.018.
  11. ^ Jelley, Nick (2017-01-19), "airtightness", A Dictionary of Energy Science, Oxford University Press, ISBN 978-0-19-182627-6, retrieved 2022-11-16
  12. ^ Gillott, M.C.; Loveday, D.L.; White, J.; Wood, C.J.; Chmutina, K.; Vadodaria, K. (January 2016). "Improving the airtightness in an existing UK dwelling: The challenges, the measures and their effectiveness". Building and Environment. 95: 227–239. Bibcode:2016BuEnv..95..227G. doi:10.1016/j.buildenv.2015.08.017. S2CID 56109406.
  13. ^ Building a Passive House. Green Energy and Technology. 2018. doi:10.1007/978-3-319-69938-7. ISBN 978-3-319-69937-0.
  14. ^ a b c d e f Pollard, AR and McNeil, S, Forced Air Ventilation Systems, June 2010, Report IEQ7570/3 for Beacon Pathway Limited
  15. ^ a b Warren Fitzgerald, Dr Inga Smith and Muthasim Fahmy, Heating and cooling potential of roof space air: implications for ventilation systems, May 2011, Prepared for the Energy Efficiency and Conservation Authority (EECA)