Calculos Electricos
Calculos Electricos
Calculos Electricos
11
FM About
Lista de Cargas del Sistema POTENCIA TOTAL
Datos generales Alimentación Consumo unitario T. Uso Factor
N° TAG Descripción Ubicación Cant. Tipo Voltios Sist. Valor Unidad FP Eff % Horas Oper. VA W VAR
1 Bomba del SCI SCI 1 AC 480 3 Fases 100 HP 0.95 98 8 1.00 76091.84 72287.24 23759.67
2 Bomba Jockey SCI 1 AC 480 3 Fases 10 HP 0.95 98 8 1.00 7609.18 7228.72 2375.97
3 AC 240 1 Fase 0.2 A 0.00 0.00 0.00 0.00
4 AC 240 1 Fase 333 VA 0.00 0.00 0.00 0.00
5 110 0.00 0.00 0.00 0.00
6 110 0.00 0.00 0.00 0.00
7 110 0.00 0.00 0.00 0.00
8 110 0.00 0.00 0.00 0.00
9 110 0.00 0.00 0.00 0.00
10 110 0.00 0.00 0.00 0.00
11 110 0.00 0.00 0.00 0.00
12 110 0.00 0.00 0.00 0.00
13 110 0.00 0.00 0.00 0.00
14 110 0.00 0.00 0.00 0.00
15 110 0.00 0.00 0.00 0.00
16 110 0.00 0.00 0.00 0.00
17 110 0.00 0.00 0.00 0.00
18 110 0.00 0.00 0.00 0.00
19 110 0.00 0.00 0.00 0.00
20 110 0.00 0.00 0.00 0.00
21 110 0.00 0.00 0.00 0.00
22 110 0.00 0.00 0.00 0.00
23 110 0.00 0.00 0.00 0.00
24 110 0.00 0.00 0.00 0.00
25 110 0.00 0.00 0.00 0.00
26 110 0.00 0.00 0.00 0.00
27 110 0.00 0.00 0.00 0.00
28 110 0.00 0.00 0.00 0.00
29 110 0.00 0.00 0.00 0.00
30 110 0.00 0.00 0.00 0.00
Sub Total 79515.97 26135.64
Proyecto: TOMOPORO TOTAL [VA] 83701.02
Instalación: SCI kVA 83.70
Fecha: 3/20/2009 Reserva 10.00%
Corriente a plena carga en base a un motor de: 100 HP con un voltaje de operación de:
480 V la corriente a plena carga es: 109.51 A, según CEN 2004
Datos de Alimentador
4/97
Datos de Canalización
Aislante: TTU 90 (XLPE-PVC) 600 V 4
Diametro: 18.48 mm X Conductor 11
Area Total: 804.66 mm2
Diametro de Ducto: 4 11
Tipo: Tubo de PVC Rigido, Sch. 40 y tubo de PE-AD 10
Diametro: 101.5 mm
Area Total: 8091.37 mm2
Ocupacion: 9.94%
Protección y Arranque
5/97
Gabinete de control / potencia
Área de instalación
Clase: No Clasificada
División: N/A
Gabinete o Tablero
Ubicación: Exterior
Cerramiento: 4x NEMA
Tipo de protección: Sellado contra agua y resistente a la corrosión. Los
gabinetes tipo 4X tienen las mismas características
que los tipo 4, además de ser resistentes a la
corrosión.
Otras caracteristicas
Notas
V3.11 fm
6/97
480 V
Barra
480 V
NEMA 5
AC-3
Arrancador 120 V
136.89A (AT)
Circuito de Control
100 HP
Cálculos Eléctricos Para Transformador
Datos Eléctricos
Primario Secundario
Tipo de conexión: Delta Tipo de conexión: Estrella
Hilos: 2 Hilos: 3
Voltaje de línea: 0.48 kV L-L Voltaje de línea: 0.48 kV L-L (480 V)
Voltaje de fase: 0.48 kV Voltaje(s) de fase: 0.277128129 kV
Corriente de línea: 90.21 A kV L-N (0 V)
Corriente de Fase: 52.08 A Corriente de línea: 90.21 A
Conexión del neutro: No tiene Corriente de Fase: 90.21 A
Conexión del neutro: solidamente a tierra
Alimentadores
Primario Secundario
Factor mult. de corriente 125 % Factor mult. de corriente 125 %
Corriente de diseño: 112.76 A Corriente de diseño: 112.76 A
Material: COBRE Material: COBRE
Voltaje de Operación Cable: 5001-35000 V Voltaje de Operación Cable: 0 - 2000 V
Tabla aplicada: Tabla 310.73 CEN 2004 Tabla aplicada: Tabla 310.16 CEN 2004
Calibre 2 AWG / MCM Calibre 1/0 AWG / MCM
Temp. Op. 90°C 0 Temp. Op. 90°C
Fact. Temp 36-40 °C Fact. Temp 36-40 °C
Corriente nominal cable 150 A Corriente nominal cable 154.7 A
Conductores por fase 1 Conductores por fase 1
Cap. Total por fase 150 A Cap. Total por fase 154.7 A
% carga en el cable 75.18% % carga en el cable 72.89%
% Reserva 24.82% % Reserva 27.11%
Calibre del neutro: 4 AWG / MCM Calibre del neutro: 4/0 AWG / MCM 0
Conductores por neutro: 1 Conductores del neutro: 2 0
Datos de canalización
Primario Secundario
8/97
Protecciones
Primario Secundario
Limitaciones sobre el lugar: Cualquiera
% Impedancia del TX: Mas de 6% pero menos de 10%
Tipo de protección: Fusible Tipo de protección: Interruptor automático
Tabla 450.3(B) CEN 2004 Tabla 450.3(B) CEN 2004
Ajuste max. del dispositivo: 250 % I de diseño Ajuste max. del dispositivo: 125 % I de diseño
Cap. de corriente del dispositivo: 15 A AF Cap. de corriente del dispositivo: 200 A AF
Max corriente de ajuste: 281.91 A AD Max corriente de ajuste: 140.95 A AD
V3.11 fm
9/97
Proyecto: TX:
0
Tabla de carga
Tiempo Inicio Tiempo Fin Duracion Corriente Capacidad
Carga Descripcion
(min) (min) (min) (A) (A-H)
1 L1 0 30 30.00 37.18 18.59
2 L2 0 0 0.00 0 0.00
3 L3 0 0 0.00 0 0.00
4 L4 0 0 0.00 0 0.00
5 L5 0 0 0.00 0 0.00
6 L6 0 0 0.00 0 0.00
Curva de carga
Corriente (A)
40
35
30
25
20
15
10
0 Tiempo (min)
0 5 10 15 20 25 30 35
11/97
Demanda Maxima: 37.18 A
Demanda Minima: 37.18 A
Demanda Promedio: 37.18 A
2.5
2
Factor Tt
1s - 10 min
1.5
30 min
60 min
1 3H
5-8H
0.5
0
-29 -20 -10 0 10 20 25
°C
12/97
Hoja de selección de capacidad
Carga Cambio de carga Duracion Tiempo final de Factor de Factor de Valor positivo
Periodo Valor negativo (AH)
(A) (A) (min) seccion (min) capacidad (Kt) temperatura (Tt) (AH)
Tamaño de la sección mayor 51.57 AH + Sección aleatoria 0AH = Tamaño sin corrección: 51.57 AH
Capacidad final :TSC X FD X FE = 70.91 AH
V3.11 fm
13/97
Caída de tensión sistemas Trifasico (Conductor de Cobre)
Carga: 75000 VA 75 kVA
Longitud del circuito: 200 m (r×cos θ+ x×se
Tensión del sistema 480 V
k= 2
105×kV
FP: 0.8
Calibre del Cable: 1/0 1 Cond. por fase
Material de la tubería: PVC
R: 0.39 OHM/kM
X: 0.144 OHM/kM
ΔV ( )=( kVA×m
k=0.0001
V3.11
ofasicos (Conductor de cobre) Distancia
0
(r×cos θ+ x×sen θ ) 0
k= 0
5×kV 2
0.00017622
Cond. por fase
k=0.0001
%) = 2.9 3
1000 22 10 220
T.
Caida de tension en sistemas DC
2
Resistividad del cobre: 0.018
Ω×mm
m
Distancia del tramo: 200 m
Vatios 2 W
Amperio
Regulación: 0.38 %
Calculo de corriente de corto circuito
Tension del sistema: 0.48 kV
Lugar: Barra 480
Total
Rt = 0.5680 Ω
Xt = 1.0582 Ω
Zt = 1.2010 Ω
Potencia:
Voltaje nominal:
Eficiencia:
FP:
100 HP
0.48 kV en el lado de la falla
90 %
0.8
Tipo: Motor de alta velocidad
A Sub Transitorio
Transitorio
Xd" Xd´ Xd
Motor de alta velocidad 15 25 80
Motor de Baja velocidad 35 50 100
Compensador 25 40 160
T1. Reactancias en % de motores y compensadores
Se tiene que: P
S n=
FP×η
Sn = 103.57 kW
Luego: X V 2
X m
100 S n
X= 25
Ralignl ¿ ¿¿ =0,2 X m ¿
Rm = 111.23 mOhm
Rm 0.20
=
Xm
0.567170104
Zt= 567.17 mOhm
Zt=√ R 2t + X 2t
2
Vn
I cc , sim=
√ 3×Z t
Por lo tanto: Icc, sim = 488.62 A simétricos
Transformador trifásico
Potencia: 75 kVA
Voltaje en lado de falla (V2): 0.48 kV V1: 13.8 kV
Voltaje de corto circuito %: 4 Tabla T1
Ra: 0.568032196 Ohm Rr 0.000687222 Ohm reflejada
Xa: 1.058234384 Ohm Xr 0.001280284 Ohm reflejada
T1. Tensión de cortocircuito Vcc normalizada para los transformadores MT/BT de distribución pública.
kVA 630 800 1000 1250 1600 2000
Vcc (%) 4 4.5 5 5.5 6 7
2
Vn
Se tiene que: Z t =V cc × Z del transformador
Sn
Rtotal
Luego: = 0.20 0.126704406
X total
2
Vn
Se tiene que: I cc , sim =
√ 3× Z t
Por lo tanto: Icc, sim = 2.19 kA simetricos
Rt
Luego tenemos que: K = 1.54 , para = 0.20 ( IEC 60909 )
Xt
Ra/Za: 0.239
Za: 0.812 Ω
Xa: 0.788 Ω
Ra: 0.194 Ω
Ra/Xa: 0.246
Factor K: 1.467 (IEC 60909)
Red electrica
Paso de Distancia
Potencia [VA] kVA x m
Nº Distancia [m] [m]
1 100 114 114 11.4 ( r×cos θ+ x×sen θ )
2 100 5 119 11.9 k=
3 100 5 124 12.4
5×kV 2
4 100 5 129 12.9
5 100 5 134 13.4 k = 0.005
6 100 5 139 13.9
7 100 5 144 14.4
8 100 5 149 14.9 ΔV ( )=( kVA×m )×k
9 100 5 154 15.4
10 100 5 159 15.9
11 100 5 164 16.4 ∆V(%) = 3.07
12 100 5 169 16.9
13 100 5 174 17.4
14 100 5 179 17.9 Voltaje Final:
15 100 5 184 18.4
16 100 5 189 18.9
17 100 5 194 19.4
18 100 5 199 19.9
19 100 5 204 20.4
20 100 5 209 20.9
21 100 5 214 21.4
22 100 5 219 21.9
23 100 5 224 22.4
24 100 5 229 22.9
25 100 5 234 23.4
26 100 5 239 23.9
27 100 5 244 24.4
28 100 5 249 24.9
29 100 5 254 25.4
30 0 5 0 0
1/0
PVC
0.39 Ω/km
0.144 Ω/km
( r×cos θ+ x×sen θ )
=
5×kV 2 3.07904976
0.005770333
0.317560429
0.3122499
116.31 V
Calculo de Alimentador
Datos de la Carga
Carga nominal: 92000 VA
Tension del sistema: 480 V
Fp: 0.85
Eff: 90 %
Factor de diseño: 125 %
Corriente: 110.66 A
Cant. Act.X
Distancia
Calibre
Calibre
Neutro
Fases
Fase
Tension Tension
COVENIN 398
(M)
TAG
Oper (V) Max (V)
Tipo Aislante Desdes Hasta
P-001 3(1#4/0 AWG) 13800 15000 XLPE-PVC 250 TEST TEST 4/0 AWG 3 1 16 AWG
3(1#16 AWG) 13800 15000 XLPE-PVC 300 TEST TEST 16 AWG 3 1
3(2#500 MCM) 220 600 XLPE-PVC 260 TEST TEST 500 MCM 3 2
3(2#16 AWG) 480 600 XLPE-PVC 100 TEST TEST 16 AWG 3 2
(3#16 AWG)+6N#16 AWG+3T#16 AWG 480 600 THHN 100 TEST TEST 16 AWG 3 3 16 AWG
(#)
(#)
(#)
(#)
(#)
(#)
(#)
(#)
(#)
(#)
(#)
(#)
(#)
(#)
(#)
(#)
(#)
(#)
(#)
(#)
(#)
(#)
(#)
(#)
(#)
Proyecto: Nomenclatura COVENIN
X ( n × Y ) + mN
¿ Y ' + pT ¿ Y '' ¿
Indicación de X fases de n conductores monopolares por fase, calibre Y, mas m conductores de neutro (N) calibre
Links
Aralven (Cables)
Cant. Neutro
Cond. Tierra
Cant. Tierra
Neutro (M)
Activo (M)
Cond Act.
Cantidad
Cantidad
Cantidad
Calibre
Cond.
Cond.
Tierra
X GF
X GF
(M)
Observaciones
0 3 750 0 0
3 900 0 0
6 1560 0 0
6 600 0 0
2 16 AWG 1 9 900 600 300
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
e Y, mas m conductores de neutro (N) calibre Y’, mas p conductores de tierra (T) calibre Y’’.
AISLANTES DE CONDUCTORES
Tipo Descripcion
THHN Los conductores de cobre tipo THHN o THWN-2 son utilizados para circuitos de fuerza y alumbrado en
industriales, comerciales y residenciales, son especialmente aptos para instalaciones especiales por d
usarse en zonas abrasivas o contaminadas con aceites, grasas, gasolinas, etc. y otras sustancias quím
como pinturas, solventes, etc., tal como se especifica en el National Electrical Code. Este tipo de cond
utilizado como THHN puede ser usado en lugares secos con temperatura máxima de operación de 90
utilizado como THWN-2 puede ser usado en lugares secos y húmedos con temperatura máxima de op
así mismo cuando están expuestos a aceites, grasas, pinturas, solventes químicos, etc., su temperatur
operación es 75 ºC. En cuanto a su tensión de servicio, para todas las aplicaciones, es de 600 V.
THW Los conductores de cobre tipo THW son utilizados para circuitos de fuerza y alumbrado en edificacione
comerciales y residenciales donde se requiera de mayor seguridad, tal como se especifica en el Nation
Este tipo de conductor puede ser usado en lugares secos y húmedos, su temperatura máxima de oper
su tensión de servicio para todas las aplicaciones es 600 V.
TTU Los conductores de cobre tipo TTU-0.6 KV. son utilizados para circuitos de fuerza y alumbrado en edifi
industriales y comerciales, son especialmente aptos para instalaciones a la intemperie o directamente
se especifica en el National Electrical Code. Este tipo de conductor puede ser usado en lugares secos
temperatura máxima de operación es 75 ºC y su tensión de servicio para todas las aplicaciones es 600
TW Los conductores de cobre tipo TW son utilizados para circuitos de fuerza y alumbrado en edificaciones
comerciales y residenciales, tal como se especifica en el National Electrical Code. Este tipo de conduc
en lugares secos y húmedos, su temperatura máxima de operación es 60 ºC y su tensión de servicio p
aplicaciones es 600 V
XHHW Los conductores de cobre tipo XHHW son utilizados para circuitos de fuerza y alumbrado en edificacio
comerciales, son especialmente aptos para instalaciones a la intemperie, tal como se especifica en el N
Code. Este tipo de conductor puede ser utilizados en lugares secos y húmedos, su temperatura máxim
90 ºC y su tensión de servicio para todas las aplicaciones es 600 V.
ORES
o
s para alambrado de aparatos, cableado de tableros
dustriales y comerciales donde se requiera de gran
es sometidos a continuo movimiento, tal como se
e ser usado en lugares secos y húmedos, su
ara todas las aplicaciones es 600 V.
NTILLAMA.
Calibr
e 600 5000 15000 3500
/
V
18 AWG 0 0 0 0
16 AWG 2400 0 900 0
14 AWG 0 0 0 0
12 AWG 0 0 0 0
10 AWG 0 0 0 0
8 AWG 0 0 0 0
6 AWG 0 0 0 0
4 AWG 0 0 0 0
3 AWG 0 0 0 0
2 AWG 0 0 0 0
1 AWG 0 0 0 0
1/0 AWG 0 0 0 0
2/0 AWG 0 0 0 0
3/0 AWG 0 0 0 0
4/0 AWG 0 0 750 0
250 MCM 0 0 0 0
300 MCM 0 0 0 0
350 MCM 0 0 0 0
400 MCM 0 0 0 0
500 MCM 1560 0 0 0
600 MCM 0 0 0 0
700 MCM 0 0 0 0
750 MCM 0 0 0 0
800 MCM 0 0 0 0
900 MCM 0 0 0 0
1000 MCM 0 0 0 0
1250 MCM 0 0 0 0
1500 MCM 0 0 0 0
1750 MCM 0 0 0 0
2000 MCM 0 0 0 0
Ocupacion de ductos
Cable Monopolar
Diametro* Area por cable Total Grupo
N° Calibre Aislante Cantidad mm mm2 mm2
1 1/0 TTU 90 (XLPE-PVC) 600 V 3 14.53 165.81 497.44
2 12 TTU 90 (XLPE-PVC) 600 V 0 4.60 16.62 0.00
3 12 TTU 90 (XLPE-PVC) 600 V 0 4.60 16.62 0.00
4 12 TTU 90 (XLPE-PVC) 600 V 0 4.60 16.62 0.00
5 12 TTU 90 (XLPE-PVC) 600 V 0 4.60 16.62 0.00
Tipo de Ducto:
Tubo de PVC Rigido, Sch. 40 y tubo de PE-AD
Diametro:
4 Pulgadas
Diametro** 101.5 mm
Diámetro mínimo recomendado Area Total 8091.37 mm2
1 1/2 "
18600
30000
(VAR)
Activa [W] 10000
5000
S 31000.00 VA
0
P 18600.00 W 0
Reactiva [VAR] Q 24800.00 VAR
2
S P Q
VA 18600 11160 14880
W 31000 18600 24800
VAR 23250 13950 18600
x y
p 0 0
18600.00 0
Q 18600.00 0
18600.00 24800.00
S 0 0
18600.00 24800.00
eje 0 18600.00
24800.00 0
Triangulo de potencia
30000
25000
20000
15000
(VAR)
10000
5000
0
0 5000 10000 15000 20000 25000 30000
(W)
TABLERO ELECTRICO
Tipo de Tablero: Instalacion: C. Interrupción [kA]: Fases: Proyecto:
NLAB Auto soportado 22 3 ejemplo
Polos: Cerramiento NEMA: Color: Alimentador Principal: Instalacion:
18 3R GRIS INDUSTRIAL Calibre Aislante Cnd X fase Conduit Entrada ejemplo
Voltaje del Tablero [V]: Corriente de Barras [A]: Interruptor principal 3P [A]: Nombre del Tablero:
250 MCM THHN 1 4 Superior
240 100 400 ejemplo
A B C
1500 1 2 1000
Carga Nº 1 1500 PVC 2 1 THHN 6 AWG QC 20 3 4 30 THQC 250 MCM TTU 1 4 PVC 1000 Carga Nº 2
1500 5 6 1000
500 7 8 1250
CARGA 4 500 PVC 2 1 THHN 14 AWG QC 20 9 10 90 THQC 14 AWG TTU 1 2 PVC 1250 CARGA 3
500 11 12 1250
1000 13 14 1000
19 20
21 22
23 24
25 26
27 28
29 30
31 32
33 34
35 36
A B
carga 1 1500 PVC 2 1 THW 12 AWG QC 20 1 2 PVC 2 1 THW 12 AWG QC 20 1500 carga 2
carga 4 1500 PVC 2 1 THW 12 AWG QC 20 3 4 PVC 2 1 THW 12 AWG QC 20 1500 reserva ✘
✘ 5 6
✘ 7 8
✘ 9 10
✘ 11 12
✘ 13 14
✘ 15 16
✘ 17 18
✘ 19 20
✘ 21 22
✘ 23 24
✘ 25 26
✘ 27 28
✘ 29 30
✘ 31 32
✘ 33 34
✘ 35 36
NIVELES
CASO DE ESTUDIO
12 IN 30.48 CM
NOTAS
4 Las distancia mínimas de los ductos se indican en referencia al exterior de los mismos
5 Cuando señales de distintos niveles deban cruzarse, deben hacer en un ángulo de 90º. Cuando no sea posible mantener las distancias de
separación se debe interponer una barrera metálica aterrada.
6 Los niveles 3 y 4 pueden ser canalizados en la misma bandeja siempre que se coloque una barrea entre ellos
7 Cuando sea impractico separarlos, los niveles 1 y 2 pueden ser usados en la misma bandeja, siempre que tenga una barrera metálica aterrada
entre ellos.
8 Las bandejas de todos los niveles deben ser metálicas solidamente aterradas.
9 Bandejas y ductos de los niveles 1 y 2 no podrán ser llevadas en paralelo con equipos de alta potencia cerrados mayores a 100kVA a 150 cm de las
bandejas y 80 cm de los ductos.
10 Cunado no se posible mantener el espacio indicado arriba, se debe minimizar el recorrido en paralelo de las rutas, en tal caso, el recorrido no podrá
superar los 150 cm de longitud.
Fuentes:
PIP PCCEL001
IEEE 518
Caso...
BANDEJAS PORTACABLES
Lista de Cables
Espacio entre soportes: 8 ft. Cables Mayores a 1000kCMIL con menores a 1000 kCMIL
Bandejas
CABLE MONOPOLAR
Bandejas de fondo escalera o ventilado
1 3 C,TC 600 VAC CON CONDUCTORES XHHW DE COBRE 500 55.90 2454.22 2454.22 5.59
2 3 C,TC 600 VAC CON CONDUCTORES XHHW DE COBRE 1000 76.90 4644.54 9289.08 15.38
Los cables deben ser instalados en una sola capa 20% Reserva: 11.43
2 4 C,TC 600 VAC CON CONDUCTORES XHHW DE COBRE 8 18.90 280.55 561.10 1.85
3 4 C,TC 600 VAC CON CONDUCTORES XHHW DE COBRE 2/0 36.30 1034.91 3104.73 10.25
0 4 C,TC 600 VAC CON CONDUCTORES XHHW DE COBRE 2/0 36.30 1034.91 0.00 0.00
1 3 C,TC 600 VAC CON CONDUCTORES XHHW DE COBRE 1000 76.90 4644.54 4644.54 7.69
2 3 C,TC 600 VAC CON CONDUCTORES XHHW DE COBRE 1/0 30.40 725.83 1451.67 4.79
2 3 C,TC 600 VAC CON CONDUCTORES XHHW DE COBRE 1/0 30.40 725.83 1451.67 4.79
Todos los cables mayores a 4/0 se deben instalar en una sola capa 20% Reserva: 8.30
I Base = 1 A
1 3 5 7 9 11 13
% de Ib ### 50 83 10 10 10 20 283
Espectro
100
90
80
70
60
50
40
30
20
10
0
1 3 5 7
Armónico
In
I1
Corriente In
Armónico RMS
In I1
1 1 1
3 0.5 0.5
5 0.83 0.83
7 0.1 0.1
9 0.1 0.1
11 0.1 0.1
13 0.2 0.2
%TDH-F
Algunos Valore
0 50 17 90 90 90 80
0 0 0 0 0 0 0 0 0
0.01 0 0.1 0.1 0.1 0.2 0.2 0.3 0.249
0.01 0 0.1 0.2 0.3 0.4 0.4 1 0.491
0.02 0.1 0.2 0.3 0.4 1 1 1 0.719
0.03 0.1 0.2 0.4 1 1 1 1 0.926
0.03 0.1 0.3 0.5 1 1 1 1 1.109
0.04 0.1 0.4 1 1 1 1 1 1.263
0.05 0.1 0.4 1 1 1 1 1 1.386
0.05 0.2 0.5 1 1 1 1 1 1.477
0.06 0.2 1 1 1 1 1 1 1.538
0.07 0.2 1 1 1 1 1 0.4 1.571
0.07 0.2 1 1 1 1 1 0.1 1.579
0.08 0.2 1 1 1 1 0.4 0 1.567
0.09 0.3 1 1 1 1 0.1 0 1.541
0.09 0.3 1 1 1 0.5 0 -1 1.504
0.1 0.3 1 1 1 0.3 0 -1 1.463
0.11 0.3 1 1 1 0.1 -1 -1 1.421
0.11 0.3 1 1 1 0 -1 -1 1.384
0.12 0.4 1 1 0.5 0 -1 -1 1.352
0.13 0.4 1 1 0.3 0 -1 -1 1.329
0.13 0.4 1 1 0.2 -1 -1 -1 1.315
0.14 0.4 1 1 0.1 -1 -1 -1 1.309
0.15 0.4 1 1 0 -1 -1 0 1.308
0.15 0.5 1 1 0 -1 -1 0 1.311
0.16 0.5 1 1 0 -1 -1 0.2 1.315
0.17 0.5 1 0.5 0 -1 -1 0.5 1.315
0.17 1 1 0.4 -1 -1 0 1 1.308
0.18 1 1 0.3 -1 -1 0 1 1.291
0.19 1 1 0.2 -1 -1 0.2 1 1.262
0.19 1 1 0.1 -1 -1 0.4 1 1.218
0.2 1 1 ### -1 -1 1 1 1.158
0.21 1 1 0 -1 0 1 1 1.084
0.21 1 1 0 -1 0 1 1 1
0.22 1 1 0 -1 0 1 0.4 0.896
0.23 1 1 0 -1 0.1 1 0.2 0.788
0.23 1 1 0 -1 0.3 1 0 0.675
0.24 1 1 -1 -1 0.5 1 0 0.563
0.25 1 1 -1 -1 1 1 -1 0.454
0.25 1 1 -1 -1 1 1 -1 0.354
0.26 1 1 -1 -1 1 0.4 -1 0.267
0.27 1 1 -1 0 1 0.2 -1 0.195
0.27 1 1 -1 0 1 0 -1 0.14
0.28 1 0.5 -1 0 1 0 -1 0.103
0.29 1 0.4 -1 0 1 0 -1 0.086
0.29 1 0.4 -1 0.2 1 -1 -1 0.086
0.3 1 0.3 -1 0.3 1 -1 0 0.103
0.31 1 0.2 -1 0.4 1 -1 0 0.132
0.31 1 0.2 -1 1 1 -1 0.2 0.172
0.32 1 0.1 -1 1 0.4 -1 0.5 0.219
0.33 1 0.1 -1 1 0.2 -1 1 0.27
0.33 1 ### -1 1 ### -1 1 0.32
0.34 1 0 -1 1 0 -1 1 0.368
0.35 1 0 -1 1 0 -1 1 0.412
0.35 1 0 -1 1 -1 0 1 0.449
0.36 1 0 -1 1 -1 0 1 0.48
0.37 1 0 -1 1 -1 0.1 1 0.505
0.37 1 0 0 1 -1 0.3 0.4 0.525
0.38 1 0 0 1 -1 1 0.2 0.542
0.39 1 0 0 1 -1 1 0 0.558
0.39 1 -1 0 1 -1 1 0 0.576
0.4 1 -1 ### 1 -1 1 -1 0.598
0.41 1 -1 0.1 0.5 -1 1 -1 0.627
0.41 1 -1 0.2 0.3 -1 1 -1 0.664
0.42 1 -1 0.3 0.2 -1 1 -1 0.71
0.43 1 -1 0.4 0 0 1 -1 0.766
0.43 1 -1 0.5 0 0 1 -1 0.831
0.44 1 -1 1 0 0 0.5 -1 0.905
0.45 1 -1 1 0 0.1 0.3 -1 0.983
0.45 1 -1 1 -1 0.2 0 0 1.065
0.46 1 -1 1 -1 0.4 0 0 1.146
0.47 1 -1 1 -1 1 0 0.2 1.223
0.47 1 -1 1 -1 1 -1 0.5 1.292
0.48 1 -1 1 -1 1 -1 1 1.35
0.49 1 -1 1 -1 1 -1 1 1.394
0.49 1 -1 1 -1 1 -1 1 1.421
0.5 1 -1 1 -1 1 -1 1 1.43
0.51 1 -1 1 -1 1 -1 1 1.421
0.51 1 -1 1 -1 1 -1 1 1.394
0.52 1 -1 1 -1 1 -1 1 1.35
0.53 1 -1 1 -1 1 -1 0.5 1.292
0.53 1 -1 1 -1 1 0 0.2 1.223
0.54 1 -1 1 -1 0.4 0 0 1.146
0.55 1 -1 1 -1 0.2 0 0 1.065
0.55 1 -1 1 0 0.1 0.3 -1 0.983
0.56 1 -1 1 0 0 0.5 -1 0.905
0.57 1 -1 0.5 0 0 1 -1 0.831
0.57 1 -1 0.4 0 0 1 -1 0.766
0.58 1 -1 0.3 0.2 -1 1 -1 0.71
0.59 1 -1 0.2 0.3 -1 1 -1 0.664
0.59 1 -1 0.1 0.5 -1 1 -1 0.627
0.6 1 -1 ### 1 -1 1 -1 0.598
0.61 1 -1 0 1 -1 1 0 0.576
0.61 1 0 0 1 -1 1 0 0.558
0.62 1 0 0 1 -1 1 0.2 0.542
0.63 1 0 0 1 -1 0.3 0.4 0.525
0.63 1 0 -1 1 -1 0.1 1 0.505
0.64 1 0 -1 1 -1 0 1 0.48
0.65 1 0 -1 1 -1 0 1 0.449
0.65 1 0 -1 1 0 -1 1 0.412
0.66 1 0 -1 1 0 -1 1 0.368
0.67 1 ### -1 1 ### -1 1 0.32
0.67 1 0.1 -1 1 0.2 -1 1 0.27
0.68 1 0.1 -1 1 0.4 -1 0.5 0.219
0.69 1 0.2 -1 1 1 -1 0.2 0.172
0.69 1 0.2 -1 0.4 1 -1 0 0.132
0.7 1 0.3 -1 0.3 1 -1 0 0.103
0.71 1 0.4 -1 0.2 1 -1 -1 0.086
0.71 1 0.4 -1 0 1 0 -1 0.086
0.72 1 0.5 -1 0 1 0 -1 0.103
0.73 1 1 -1 0 1 0 -1 0.14
0.73 1 1 -1 0 1 0.2 -1 0.195
0.74 1 1 -1 -1 1 0.4 -1 0.267
0.75 1 1 -1 -1 1 1 -1 0.354
0.75 1 1 -1 -1 1 1 -1 0.454
0.76 1 1 -1 -1 0.5 1 0 0.563
0.77 1 1 0 -1 0.3 1 0 0.675
0.77 1 1 0 -1 0.1 1 0.2 0.788
0.78 1 1 0 -1 0 1 0.4 0.896
0.79 1 1 0 -1 0 1 1 1
0.79 1 1 0 -1 0 1 1 1.084
0.8 1 1 ### -1 -1 1 1 1.158
0.81 1 1 0.1 -1 -1 0.4 1 1.218
0.81 1 1 0.2 -1 -1 0.2 1 1.262
0.82 1 1 0.3 -1 -1 0 1 1.291
0.83 1 1 0.4 -1 -1 0 1 1.308
0.83 0.5 1 0.5 0 -1 -1 0.5 1.315
0.84 0.5 1 1 0 -1 -1 0.2 1.315
0.85 0.5 1 1 0 -1 -1 0 1.311
0.85 0.4 1 1 0 -1 -1 0 1.308
0.86 0.4 1 1 0.1 -1 -1 -1 1.309
0.87 0.4 1 1 0.2 -1 -1 -1 1.315
0.87 0.4 1 1 0.3 0 -1 -1 1.329
0.88 0.4 1 1 0.5 0 -1 -1 1.352
0.89 0.3 1 1 1 0 -1 -1 1.384
0.89 0.3 1 1 1 0.1 -1 -1 1.421
0.9 0.3 1 1 1 0.3 0 -1 1.463
0.91 0.3 1 1 1 0.5 0 -1 1.504
0.91 0.3 1 1 1 1 0.1 0 1.541
0.92 0.2 1 1 1 1 0.4 0 1.567
0.93 0.2 1 1 1 1 1 0.1 1.579
0.93 0.2 1 1 1 1 1 0.4 1.571
0.94 0.2 1 1 1 1 1 1 1.538
0.95 0.2 0.5 1 1 1 1 1 1.477
1 0.1 0.4 1 1 1 1 1 1.386
0.96 0.1 0.4 1 1 1 1 1 1.263
1 0.1 0.3 0.5 1 1 1 1 1.109
1 0.1 0.2 0.4 1 1 1 1 0.926
0.98 0.1 0.2 0.3 0.4 1 1 1 0.719
1 0 0.1 0.2 0.3 0.4 0.4 1 0.491
1 0 0.1 0.1 0.1 0.2 0.2 0.3 0.249
1 ### ### ### ### ### ### ### ###
1 0 0 0 0 0 0 0 -0.25
1 0 0 0 0 0 0 -1 -0.49
1.02 0 0 0 0 -1 -1 -1 -0.72
1 0 0 0 -1 -1 -1 -1 -0.93
1 0 0 -1 -1 -1 -1 -1 -1.11
1.04 0 0 -1 -1 -1 -1 -1 -1.26
1 0 0 -1 -1 -1 -1 -1 -1.39
1.05 0 0 -1 -1 -1 -1 -1 -1.48
1.06 0 -1 -1 -1 -1 -1 -1 -1.54
1.07 0 -1 -1 -1 -1 -1 0 -1.57
1.07 0 -1 -1 -1 -1 -1 0 -1.58
1.08 0 -1 -1 -1 -1 0 0.1 -1.57
1.09 0 -1 -1 -1 -1 0 0.4 -1.54
1.09 0 -1 -1 -1 0 0.1 1 -1.5
1.1 0 -1 -1 -1 0 0.3 1 -1.46
1.11 0 -1 -1 -1 0 1 1 -1.42
1.11 0 -1 -1 -1 0.1 1 1 -1.38
1.12 0 -1 -1 0 0.2 1 1 -1.35
1.13 0 -1 -1 0 0.4 1 1 -1.33
1.13 0 -1 -1 0 1 1 1 -1.31
1.14 0 -1 -1 0 1 1 1 -1.31
1.15 0 -1 -1 0.1 1 1 0.3 -1.31
1.15 0 -1 -1 0.2 1 1 0 -1.31
1.16 0 -1 -1 0.4 1 1 0 -1.31
1.17 -1 -1 0 0.5 1 0.5 -1 -1.32
1.17 -1 -1 0 1 1 0.3 -1 -1.31
1.18 -1 -1 0 1 1 0.1 -1 -1.29
1.19 -1 -1 0 1 1 0 -1 -1.26
1.19 -1 -1 0 1 1 0 -1 -1.22
1.2 -1 -1 ### 1 1 -1 -1 -1.16
1.21 -1 -1 0.1 1 0.4 -1 -1 -1.08
1.21 -1 -1 0.2 1 0.2 -1 -1 -1
1.22 -1 -1 0.3 1 0.1 -1 0 -0.9
1.23 -1 -1 0.4 1 0 -1 0 -0.79
1.23 -1 -1 0.5 1 0 -1 0.1 -0.68
1.24 -1 -1 1 1 0 -1 0.4 -0.56
1.25 -1 -1 1 1 -1 -1 1 -0.45
1.25 -1 -1 1 1 -1 -1 1 -0.35
1.26 -1 -1 1 1 -1 0 1 -0.27
1.27 -1 -1 1 0.4 -1 0 1 -0.19
1.27 -1 -1 1 0.3 -1 0 1 -0.14
1.28 -1 0 1 0.1 -1 0.2 1 -0.1
1.29 -1 0 1 0 -1 0.5 1 -0.09
1.29 -1 0 1 0 -1 1 1 -0.09
1.3 -1 0 1 0 -1 1 0.3 -0.1
1.31 -1 0 1 0 -1 1 0 -0.13
1.31 -1 0 1 -1 -1 1 0 -0.17
1.32 -1 0 1 -1 0 1 0 -0.22
1.33 -1 0 1 -1 0 1 -1 -0.27
1.33 -1 ### 1 -1 ### 1 -1 -0.32
1.34 -1 0.1 1 -1 0.2 1 -1 -0.37
1.35 -1 0.1 1 -1 0.4 1 -1 -0.41
1.35 -1 0.2 1 -1 1 0.3 -1 -0.45
1.36 -1 0.2 1 -1 1 0.1 -1 -0.48
1.37 -1 0.3 0.5 -1 1 0 -1 -0.51
1.37 -1 0.4 0.4 -1 1 0 0 -0.53
1.38 -1 0.4 0.3 -1 1 -1 0 -0.54
1.39 -1 0.5 0.2 -1 1 -1 0.1 -0.56
1.39 -1 1 0.1 -1 1 -1 0.3 -0.58
1.4 -1 1 ### -1 1 -1 1 -0.6
1.41 -1 1 0 0 1 -1 1 -0.63
1.41 -1 1 0 0 1 -1 1 -0.66
1.42 -1 1 0 0 1 -1 1 -0.71
1.43 -1 1 0 0 0.5 -1 1 -0.77
1.43 -1 1 0 0.1 0.3 -1 1 -0.83
1.44 -1 1 -1 0.2 0.1 0 1 -0.9
1.45 -1 1 -1 0.4 0 0 1 -1
1.45 -1 1 -1 1 0 0 0.3 -1.07
1.46 -1 1 -1 1 0 0.2 0.1 -1.15
1.47 -1 1 -1 1 -1 0.4 0 -1.22
1.47 -1 1 -1 1 -1 1 0 -1.29
1.48 -1 1 -1 1 -1 1 -1 -1.35
1.49 -1 1 -1 1 -1 1 -1 -1.39
1.49 -1 1 -1 1 -1 1 -1 -1.42
1.5 -1 1 -1 1 -1 1 -1 -1.43
1.51 -1 1 -1 1 -1 1 -1 -1.42
1.51 -1 1 -1 1 -1 1 -1 -1.39
1.52 -1 1 -1 1 -1 1 -1 -1.35
1.53 -1 1 -1 1 -1 1 0 -1.29
1.53 -1 1 -1 1 -1 0.4 0 -1.22
1.54 -1 1 -1 1 0 0.2 0.1 -1.15
1.55 -1 1 -1 1 0 0 0.3 -1.07
1.55 -1 1 -1 0.4 0 0 1 -1
1.56 -1 1 -1 0.2 0.1 0 1 -0.9
1.57 -1 1 -1 0.1 0.3 -1 1 -0.83
1.57 -1 1 0 0 0.5 -1 1 -0.77
1.58 -1 1 0 0 1 -1 1 -0.71
1.59 -1 1 0 0 1 -1 1 -0.66
1.59 -1 1 0 0 1 -1 1 -0.63
1.6 -1 1 ### -1 1 -1 1 -0.6
1.61 -1 1 0.1 -1 1 -1 0.3 -0.58
1.61 -1 0.5 0.2 -1 1 -1 0.1 -0.56
1.62 -1 0.4 0.3 -1 1 -1 0 -0.54
1.63 -1 0.4 0.4 -1 1 0 0 -0.53
1.63 -1 0.3 0.5 -1 1 0 -1 -0.51
1.64 -1 0.2 1 -1 1 0.1 -1 -0.48
1.65 -1 0.2 1 -1 1 0.3 -1 -0.45
1.65 -1 0.1 1 -1 0.4 1 -1 -0.41
1.66 -1 0.1 1 -1 0.2 1 -1 -0.37
1.67 -1 ### 1 -1 ### 1 -1 -0.32
1.67 -1 0 1 -1 0 1 -1 -0.27
1.68 -1 0 1 -1 0 1 0 -0.22
1.69 -1 0 1 -1 -1 1 0 -0.17
1.69 -1 0 1 0 -1 1 0 -0.13
1.7 -1 0 1 0 -1 1 0.3 -0.1
1.71 -1 0 1 0 -1 1 1 -0.09
1.71 -1 0 1 0 -1 0.5 1 -0.09
1.72 -1 0 1 0.1 -1 0.2 1 -0.1
1.73 -1 -1 1 0.3 -1 0 1 -0.14
1.73 -1 -1 1 0.4 -1 0 1 -0.19
1.74 -1 -1 1 1 -1 0 1 -0.27
1.75 -1 -1 1 1 -1 -1 1 -0.35
1.75 -1 -1 1 1 -1 -1 1 -0.45
1.76 -1 -1 1 1 0 -1 0.4 -0.56
1.77 -1 -1 0.5 1 0 -1 0.1 -0.68
1.77 -1 -1 0.4 1 0 -1 0 -0.79
1.78 -1 -1 0.3 1 0.1 -1 0 -0.9
1.79 -1 -1 0.2 1 0.2 -1 -1 -1
1.79 -1 -1 0.1 1 0.4 -1 -1 -1.08
1.8 -1 -1 ### 1 1 -1 -1 -1.16
1.81 -1 -1 0 1 1 0 -1 -1.22
1.81 -1 -1 0 1 1 0 -1 -1.26
1.82 -1 -1 0 1 1 0.1 -1 -1.29
1.83 -1 -1 0 1 1 0.3 -1 -1.31
1.83 -1 -1 0 0.5 1 0.5 -1 -1.32
1.84 0 -1 -1 0.4 1 1 0 -1.31
1.85 0 -1 -1 0.2 1 1 0 -1.31
1.85 0 -1 -1 0.1 1 1 0.3 -1.31
1.86 0 -1 -1 0 1 1 1 -1.31
1.87 0 -1 -1 0 1 1 1 -1.31
1.87 0 -1 -1 0 0.4 1 1 -1.33
1.88 0 -1 -1 0 0.2 1 1 -1.35
1.89 0 -1 -1 -1 0.1 1 1 -1.38
1.89 0 -1 -1 -1 0 1 1 -1.42
1.9 0 -1 -1 -1 0 0.3 1 -1.46
1.91 0 -1 -1 -1 0 0.1 1 -1.5
1.91 0 -1 -1 -1 -1 0 0.4 -1.54
1.92 0 -1 -1 -1 -1 0 0.1 -1.57
1.93 0 -1 -1 -1 -1 -1 0 -1.58
1.93 0 -1 -1 -1 -1 -1 0 -1.57
1.94 0 -1 -1 -1 -1 -1 -1 -1.54
1.95 0 0 -1 -1 -1 -1 -1 -1.48
2 0 0 -1 -1 -1 -1 -1 -1.39
1.96 0 0 -1 -1 -1 -1 -1 -1.26
2 0 0 -1 -1 -1 -1 -1 -1.11
2 0 0 0 -1 -1 -1 -1 -0.93
1.98 0 0 0 0 -1 -1 -1 -0.72
2 0 0 0 0 0 0 -1 -0.49
2 0 0 0 0 0 0 0 -0.25
2 ### ### ### ### ### ### ### ###
a transformadores
Forma de Onda
Espectro
5 7 9 11 13
Armónico
2
2
�I n � In In
2
In
n
2
� �
�I1 � I I I
2
�I n �
2
In In
2
In
n
2
� � I
�I1 � I I
1 1 1 1
0.25 0.5 0.25 2.25
0.6889 0.83 0.6889 17.2225
0.01 0.1 0.01 0.49
0.01 0.1 0.01 0.81
0.01 0.1 0.01 1.21
0.04 0.2 0.04 6.76
Fuente:
Nota tecnica 2
Ing. Mauricio Ardón.
FASOR, S.A. de C.V.
Transformadores en Delta Abierta
Parametros Base:
En base a Tc=90 y Ta=20
Ft = 0.93
Tipo de Instalación:
Cable hasta 1000V en ducto subterráneo
Cantidad de Circuitos
1
Fth = 0.95
Numero de Columnas:
2
Fth = 0.77
Cable a emplear
A 90°C
260 A
o
y separación de 7.5" centro a centro.
Factor de corrección
F Ft �Fth �Fg
F = 0.93 X 0.95 X 0.77
F= 0.680295
176.88 A
Canalizacion
Tamaño 4"
Tuberia No Metalica Electrica
Diametro 0 mm
Area total 0.00 mm2
3/8 0 0 9.7 0
1/2 15.8 14.2 16.1 16.8
3/4 20.9 19.3 20.9 21.9
1 26.6 25.4 25.9 28.1
1 1/4 35 34 32.4 36.8
1 1/2 40.9 39.8 39 42.7
2 52.5 51.3 51.8 54.6
2 1/2 69.4 0 63.5 64.9
3 85.2 0 76.2 80.7
3 1/2 97.4 0 88.9 93.2
4 110 0 101.6 105.8
5 0 0 0 0
6 0 0 0 0
Tubo No Flexible Tubo No Flexible
Tubo No Flexible
hermetico a los hermetico a los Tubo Metalico Tubo de PVC
hermetico a los
liquidos (Tipo liquidos (Tipo Rigido Rigido, Sch. 80
liquidos
FNMC-B) FNMCA-A*)
0 0 0
15.2 17.8 0
20.4 23.1 0
26.1 29.8 0
34.5 38.1 0
40.4 43.7 0
52 54.7 56.4
62.1 66.9 0
77.3 82 84.8
89.4 93.7 96.6
101.5 106.6 108.9
127.4 0 135
153.2 0 160.9
CALIBRE AISLANTE Cant Cables
14 THW 1
Diametro 4.14 mm
Area 13.49 mm2
Area Total 13.49 mm2
Cap. Nominal 50 A
Factor Correc. 0.88
Capacidad 44 A
Tabla 310.16 CEN 1999
TEMP AMB.
21-25 1.08 1.05 1.04 1.08 1.05 1.04
26-30 1 1 1 1 1 1
31-35 0.91 0.94 0.96 0.91 0.94 0.96
36-40 0.82 0.88 0.91 0.82 0.88 0.91
41-45 0.71 0.82 0.87 0.71 0.82 0.87
46-50 0.58 0.75 0.82 0.58 0.75 0.82
51-55 0.41 0.67 0.76 0.41 0.67 0.76
56-60 0.58 0.71 0.58 0.71
61-70 0.33 0.58 0.33 0.58
71-80 0.41 0.41
CALIBRE TEMP. Tension
2 90°C 2001-5000 V
Capacidad 130 A
Tabla 310.73 CEN 1999
Ampacidades de cables triples aislados o de tres conductores de
cobre sencillos, en un conducto físicamente aislado, al aire libre,
basadas en temperaturas de conductor de 90°C en una temperatura
ambiente de 40°C
Calibre 2001-5000 V 5001-35000 V
AWG/kcmil 90°C 105°C 90°C 105°C
8 55 61
6 75 84 83 93
4 97 110 110 120
2 130 145 150 165
1 155 175 170 190
1/0 180 200 195 215
2/0 205 225 225 255
3/0 240 270 260 290
4/0 280 305 295 330
250 315 355 330 365
350 385 430 395 440
500 475 530 480 535
750 600 665 585 655
1000 690 770 675 755
CALIBRE TEMP. Tension
4/0 90°C 5001-35000 V
Capacidad 230 A
Tabla 310.74 CEN 1999
Ampacidades de cables triples aislados o de tres conductores de
aluminio sencillos, en un conducto físicamente aislado, al aire libre,
basadas en temperaturas de conductor de 90°C en una temperatura
ambiente de 40°C
Calibre 2001-5000 V 5001-35000 V
AWG/kcmil 90°C 105°C 90°C 105°C
8 43 48
6 58 65 65 72
4 76 85 84 94
2 100 115 115 130
1 120 135 130 150
1/0 140 155 150 170
2/0 160 175 175 200
3/0 190 210 200 225
4/0 215 240 230 260
250 250 280 255 290
350 305 340 310 350
500 380 425 385 430
750 490 545 485 540
1000 580 645 565 640
A
AAC
AACS
AC
ACSR
ACSR-AG AL
ACSR-AW
AF
Al
Alta frecuencia
AM
Amplitud
Ancho de
banda
Apertura
numérica
Armadura
Atenuación
ATM
AW
AWG
AWM
Baja Frecuencia
Bel
BIL
Bit
Blindaje
C
c.a.
c.c.
c.d.
Capacitador
Capacitancia
Capacitancia
mutua
Capacitor
CATV
CCS
CCTV
Circuito en serie
Circuito paralelo
CL2
CL3
CM
Conductividad
Constante
dieléctrica
CP
CPE
CSA
Cu
CuSn
CV
CW
CXC
DCS
DGN
Diafonía
Dieléctrico
Dispersión
Dispersión
cromática
Dispersión
modal
DIT
DRS
DS
Efecto piel
EIA/TIA
Electromagnétic
o
EP(R)
EPDM
f
FA
Fan-out
Fase
FCC
FDDI
FEP
FM
FOA
FOW
FTP
G
G-GC
HDPE
Higroscópico
Hilo dren
HMWP
HP
HPN
HPOF
Hz
I
I2R
IACS
ICEA
IEC
IEEE
Iexc
Impedancia
Indice de
refracción
Inductancia
ISO
ITU
Jumper
kCM
kV
l
LAN
LDPE
Línea
balanceada
Línea de
transmisión
Longitud de
onda de Malla
lpi Longitudinal
lpof
m.s.n.m
Malla
Mc
Mi
MIC
mp
mp-gc
MTW
Multimodo
Multiplexar
MV
mw
NEC
Neopreno
NFPA
NM
NM-B o NMC-B
NMC
NMX
NOM
NZ
OA
Ohm
OTDR
OW
Pantalla
PCC
PCG
PCM
PE
Pérdidas por
doblez
PFA
PFAH
PG
Pig-tail
PILC
Plástico
Plastificante
Plenum
PMD
Polietileno
celular
Polilam
Polímero
POT
psi
PVC
PVDF
RDI
REA (RUS)
Reactancia
Resistencia a la
abrasión
RG/U
RH/RW
RHH
RHW
RHW-2
SA
SBR
SDH
SE
SF
SFF
SH
SHD
SHD-GC SHD.
SIC
SIS
SJ
SJO
SJT SJ
SMT
SNM
SO
SONET
SPT
ST
STP
SU
SV
SVT
SVTO
TA
TAGA
TAGT
TC
TEFLON*
TF
TFE
TFF
TFFN
TFN
THHN
THHW
THW1
THW-21
THWN
TP
TPT TP
TTU
TW
UD
UF
UHF
UL
Unimodo
URD
USE
USG
UTP
V
VA
Velocidad de la
luz
Velocidad de
propagación
VHF
Volt
VW-1
W
WDM
XHHW
XHHW-2
XLP
XT
Ampere: Unidad utilizada para denominar la intensidad de corriente eléctrica.
All Aluminum Conductor: conductor o cable de hilos de aluminio.
Aluminum Alloy Standed Conductor: cable de aleación de aluminio.
Armored Cable: cables provistos de una armadura metálica flexible.
Aluminum Conductor Steel Reinforced: conductor de aluminio con centro de acero galvanizado.
ACSR con aleación de aluminio para alta temperatura (150°C) y acero de alta resistencia. Símbolo del al
ACSR con centro de acero recubierto con aluminio (Alumo-Weld). También conocido como ACSR-AS.
Audio Frecuencia: Rango de frecuencias que caen dentro del rango perceptible del oído humano: aproxim
20 a 20, 000 Hz
Símbolo del aluminio.
La banda de 3 MHz a 1 GHz.
Amplitud Modulada.
El valor máximo de variación de una onda.
Es la diferencia entre los valores superior e inferior de una banda de frecuencias dada. Se expresa en He
Es la medida de aceptación angular de una fibra óptica, que es aproximadamente el seno de la mitad del
cono de aceptación de la fibra.
Cinta corrugada de acero que tiene la función de proteger el cable contra maltrato mecánico y ataque de
aplicaciones especiales se llegan a usar armaduras de cinta engargolada o de alambres de acero.
Es el decremento en magnitud de una onda mientras esta viaja en medio transmisor, sea un cable o un c
atenuación se mide como una razón o como logartimo de la razón (decibel).
Siglas en inglés para la técnica de codificación y conmutación en bloques llamada Asynchronous Transfe
permite multiplexar señales de velocidades distintas en un mismo canal digital.
American Wire Gauge: escala de calibres americanos para alambres y cables, también conocida como b
and Sharpe) Wire Gauge.
American Wire Gauge: Escala de calibres americanos para alambres y cables, también conocida como B
and Sharpe) Wire Gauge.
Appliance Wiring Material: Conductores destinados al alambrado interno de aparatos electrodomésticos.
La banda de 30-300 KHz.
Dos superficies conductoras separadas por un material dieléctrico. La capacitancia es determinada por e
superficies, tipo de dieléctrico y el espaciamiento entre los conductores.
Community Antena TeleVision: término empleado para los cables coaxiales destinados a los sistemas de
comunitaria.
Siglas en lnglés para conductores de acero cubierto cle cobre (Copper Cladded Steel).
Circuito Cerrado cle TeleVisión.
Es un circuito cuyos componentes distribuidos a lo largo de camino común.
Es un circuito en el cual un mismo voltaje se presenta en todos los componentes, con corriente dividida e
acuerdo a su resistencia o impedancias.
Cables para circuitos Clase 2, según NEC-725, bajo voltaje y potencia.
Idem a CL2, para 300 volts máximo, bajo potencia.
Circular Mil: área de un circuito con un diámetro de 1/1000 de pulgada.
La capacidad de un material para permitir el flujo de electrones, medido por la corriente por unidad de vo
Es el recíproco de la resistividad.
También se llama permitividad. Es aquella propiedad del dieléctrico que determina la cantidad de energía
electróstatica que puede almacenarse cuando es aplicado un voltaje.
Caballos de Potencia: también conocido como HP.
Chlorinated PolyEthylene: polietileno clorado.
Canadian Standard Association: Institución canadiense para la certificación de equipo eléctrico y electrón
las normas que ellos mismos publican.
Símbolo del cobre.
Símbolo que denota cobre estañado.
Continuous Vulcanization: proceso de vulcanización en línea con la extrusión.
CopperWeld: varilla de acero, con recubrimiento de cobre.
Designación de cable coaxial por CSA (Canadian Standars Association).
Cables para Distribución Comercial Subterránea.
Dirección General de Normas de la Secretaría de Comercio y Fomento Industrial.
Transferencia no deseada de señal entre distintos canales de un equipo a cable.
Es un medio aislante (no-conductivo).
Fenómeno por el cual componentes de la luz transmitida por la fibra sufren retrasos distintos. Es la suma
efectos, principalmente dispersión modal y dispersión cromática. Puede limitar la velocidad de transmisió
Es el retraso diferente que sufren las distintas longitudes de onda que componen a luz portadora, por ten
velocidades distintas en la fibra. En fibras con diseño estándar la dispersión cromática tiene un valor mín
la ventana de 1310 nm.
Es el retraso diferente que presentan los modos de propagación en una fibra multimodo por viajar en áng
no existe en las fibras unimodo en las que se transmite un modo de propagación.
Dispositivo de Interconexión Terminal: es el límite entre la red pública y la que es responsabilidad del usu
Cables para Distribución Residencial Subterránea (tipo URD).
Siglas en inglés para dispersión corrida, son las fibras unimodo con dispersión mínima enla ventana de 1
Es la tendencia que tiene la corriente alterna de viajar en el perímetro del conductor con el incremento de
frecuencia.
Asociación de las industrias electrónica y de comunicaciones en EUA.
Se reflere a la combinación de campos eléctricos y magnéticos originado por el movimiento de los electro
conductor.
Fluorinated Ethylene Propylene: aislamiento de etileno-propileno fluorado.Ethylene Propylene (Rubber): a
base de etileno-propileno.
Ethylene Propylene Dionomer: etileno-propileno dieno monómero.
Frecuencia: El número de veces que una acción periódica ocurre en un lapso de tiempo: Es el número de
que una corriente eléctrica completa 1 seg.
Forced Air: enfriamiento con aire forzado.
Cable óptlco para conectorizar, que permite separar las fibras individuales sin necesidad de darles protec
adicional.
Es la relación angular entre ondas.
Flexible Control Cable: cable control, flexible.
Fiber Distribution Digital Interface: especificación para la red de datos 100% óptica a 100 Mb/s.
Nombre abreviado para tetrafluoruroetileno-exafluoruropropileno, material aislante con excelentes propie
eléctricas y químicas que se usan en cables categoría plenum.
Frecuencia modulada.
Forced Oil and Air: enfriamiento con aceite forzado y aire.
Forced Oil and Water: enfriamiento con aceite forzado y agua.
Foiled Twisted Pair: cables multipares para datos blindados por medio de una cinta plástica aluminizada c
Ground: cable flexible para minas con conductores para conexión a tierra, 600 ó 2000 volts.
Ground-Ground Check: cable flexible para minas, con conductores para conexión a tierra y un conductor
verificar la continuidad de los conductores de tierra, 600 ó 2000 volts.
rio de términos relacionados con conductores eléctricos y cables para telecomunicaciones
Henry: Es la unidad práctica de inductancia que producirá un incremento de voltaje de 1 Volt cuando la c
cambie a razón de un ampere/seg.
High Density PolyEthylene (PE): polietileno de alto densidad.
Propiedad de algunos materiales de absorber agua del ambiente. Las cintas e hilos usados en cables no
hacerlo.
Es un alambre desnudo que está en contacto con el blindaje del cable a lo largo de toda su longitud.
High Molecular Weight Polyethylene: polietileno de alto peso molecualr.
Horse Power: caballo de potencia.
Heater Cord Parallel Neoprene: cordón paralelo de dos conductores flexibles con aislamiento elastoméric
aparatos electrodomésticos resistentes al calor, 90 °C, 600 volts.
High Pressure Oil Filled: cables tipo Pipe (tubo) de alta tensión con aislamiento de papel impregnado inst
de un tubo de acero con aceite a alta presión.
Hertz: Es la unidad de medida de frecuencia: 1 ciclo por segundo.
Símbolo utilizado para designar corriente.
Fórmula de potencia en Watts, donde I=corriente en amperes, R=resistencia en Ohms.
International Annealed Copper Standard: patrón internacional para la conductividad del cobre (igual al 10
cobre electrolítico recocido).
Insulated Cable Engineers Association: nombre actual de IPCEA (Power), asociación norteamericana par
normalización de conductores eléctricos.
International Electrotechnical Commission: organización internacional encargada de la normalización de
eléctricos.
Institute of Electrical and Electronic Engineers: principal asociación a nivel mundial de ingenieros en elec
electrónica y materias afines.
Corriente de excitación.
Es la oposición total de un circuito, cable, o algún componente al paso de la corriente alterna. Esta incluy
resistencia y a la reactancia. La unidad de medida es el Ohm y su símbolo es la Z.
Es un promedio del índice de refracción para las longitudes de onda en la ventana de transmisión; es un
necesario que se debe conocer para medir la distancia de un enlace en un OTDR.
Es la propiedad de un conductor o un circuito que se resiste al cambio de corriente. Su unidad de medida
y su símbolo es L.
International Standards Organization: organización internacional de normalización.
International Telecomunication Union: organización para normalización internacional en
Cable para conexiones en un distribuidor, puede ser un par de cobre o una fibra Monotel con conectores.
kiloCircularMil:unidad de área del sistema norteamericano de calibres de conductores eléctricos, igual a 1
mils (CM). Anteriormente conocida como MCM.
kiloVolt: unidad de medida de tensión eléctrica igual a 1000 volts.
Símbolo utilizado para designar corriente.
Local Area Network: red de datos de corta longitud en un edificio o conjunto de edificios.
Low Density PolyEthylene (PE): polietileno de bajo densidad,
Es un cable que tiene 2 conductores idénticos con las mismas características electromagnéticas en relac
demás conductores y tierra.
Es el arreglo de dos o más conductores o una guía de onda que se utiliza para transferir señales de un lu
Paper Insulated: proceso para la fabricación de cables telefónicos con aislamiento de papel aplicado
longitudinalmente.
Low Pressure Oil Filled: cables con aislamiento de papel impregnado tipo Autocontenidos para alta tensió
. Metros sobre el nivel del mar.
Es un grupo de filamentos metálicos entretejidos para formar una esfructura tubular la
Metal Clad: cable armado con una cubierta metálica del tipo interlock o tubo corrugado.
Mineral Insulated: cable con aislamiento mineral de óxido de magnesio y cubierta de tubo de cobre o ace
temperatura y resistencia al fuego, 90 a 250 °C.
Técnica de modulación en que la amplitud de una señal analógica en cierto momento se expresa con un
binario de 8 cifras.
Mine Power Feeder Cable: cable alimentador para minas con tres conductores de fase y tres conductores
conexión a tierra.
MP-Ground Check: MP con un conductor aislado para verificar la continuidad de los conductores de tierra
Machine Tool Wire: conductor con aislamiento termoplástico para alambrado de máquinas herramientas.
Fibras que tienen un núcleo relativamente grande (50 micras o más), que permiten transmitir varios hace
llamados modos de propagación.
Combinación de varias señales para enviarlas por un solo canal de transmisión.
Medium Voltage Cable: cables cona aislamiento sólido para tensiones de 2001 a 35,000 volts.
Micro m Wave: microonda.
Natinal Electrical Code: Norma general sobre productos e instalaciones
Policloropreno, hule sintético empleado como aislamiento y cubierta de cables flexibles.
National Fire Protection Association: asociación americana para la protección contra incendios responsab
publicación del NEC.
Non-Metallic Sheathed Cable: conductores aislados y con cubierta no metálica resistente a la humedad,
la flama; sugerido para ambientes secos.
NM o NMC con aislamiento de THHN.
Cable óptico para distribución en edificios en el que las fibras no tienen protección individual para separa
Fibras ópticas de baja dispersión cromática, pero nunca igual a una de 1530 a 1560 mm, permite transmi
varios portadores (ver WDM).
Oil and Air: enfriamiento natural aire-aceite.
Es la unidad eléctrica de resistencia. Es el valor de resistencia a través del cual una diferencia de potenc
mantendrá una corriente de un ampere.
Reflectómetro óptico en dominio de tiempo, es un equipo que inyecta un pulso de luz a la fibra y detecta
reflexiones, permite medir atenuación y longitud de un enlace.
Oil and Water: enfriamiento con aceite-agua.
Vea blindaje.
Designación de CSA para los cables de uso interior (Premises Comunication Cable).
Portable Cable Control and Ground conductors: cable flexible para minas con conductores de control y pa
a tierra, 600 ó 2000 volts.
Siglas en inglés para la técnica de modulación llamada en español MIC (Modulación por Impulsos Codific
Polietileno, puede ser de los tipos HMWP,HDPE y LDPE.
Es la forma que toma la curva de atenuación que es causada por: a)Una fibra óptica curveada alrededor
de curvatura cerrado, o b) Microdobleces causados por esfuerzo mecánico de la fibra.
PerFluoro-Alkoxy: cables para alta temperatura; ambiente seco, con aislamiento de Perfluoro-Alkoxy, has
Cinta de aluminio ó de acero con espesor entre 0. 15 y 0.2 mm que tiene un recubrimiento plástico en un
caras, lo que permite que se adhiera a la cubierta de polietileno de un cable formando una barrera contra
Es una substancia hecha de muchas unidades químicas moleculares. El término polímero es regularmen
vez de plástico, hule o elastómero.
Cordón paralelo con aislamiento termoplástico para 300 volts, 60 °C.
pounds per square inch: libras por pulgada cuadrada.
PolyVinyl Chloride: cloruro cle poli-vinilo, compuesto ampliamente usado como aislamiento y cubierta.
PolyVinyliDene Fluoride: compuesto termoplástico a base de fluor usado generalmente como cubierta en
construcción.
Red Digital Integrada; servicio de alta velocidad para grandes usuarios a través de la red pública.
Rural Electrification Administracion: oficina norteamericana del Departamento de Agricultura encargada d
normalización de equipos ofrecidos por las compañías telefónicas independientes.
Es una medida de los efectos combinados de capacitancia e inductancia en corriente alterna. Es la variac
dicha oposición tiene con la frecuencia de la corriente. Su símbolo es X.
Capacidad de resistir desgaste superficial.
Radio Frecuency Guide, Universal: designación para cables coaxiales para radiofrecuencias.
Rubber Heat, Rubber Moisture (Water): cables con aislamiento y cubierta de hules sintéticos para 75 °C e
seco y 60 °C en húmedo, 600 volts.
Rubber High Heat: cables con aislamiento y cubierta de hule sintético, para 90 °C, 600 V.
Rubber Heat Moisture (Water): cables con aislamiento y cubierta de hules sintéticos para75 °C en ambien
húmedo.
Igual a RHW pero con aislamiento de 90 °C en ambiente seco y húmedo.
Silicone Asbestos: cables aislados con hule silicón y malla de asbesto o fibra de vidrio.
Styrene Butadiene Rubber: elastómero sintético a base de Estireno y Butadieno, empleado para aislamie
de cordones flexibles, se conocía como GRS (Government Rubber Standard).
Siglas en inglés pare el sistema de transmisión óptica sincrono (Synchronous Digital Hierarchy).
Service Entrance: uno o más conductores con o sin cubierta exterior usados para alimentación de servici
Silicone Rubber Fiber Glass: alambre o cable de 7 hilos aislados con hule silicón y malla de fibra de vidrio
Silicone Rubber Fiber Glass Flexible: SF con conductor más flexible, 150 °C.
Shielded Mining Cable Single Conductor: cable monopolar flexible para minas con pantalla y cubierta par
pesado.
Shielded mining Cable with Ground Conductors: cable trifásico flexible para minas con pantalla. "D" signi
conductor de fase lleva pantalla y que el cable tres conductores para conexión a tierra.
Ground Check: SHD con un conductor aislado para el circuito de comprobación de continuidad de conex
dos conductores de tierra.
Specific Inductive Capacity: inductancia capacitiva específica, constante dieléctrica de un material que es
que existe entre un condensador con el material como dieléctrico y el mismo condensador con aire como
Synthetic Insulated Switchboard Cable: cable para tableros con aislamiento elastomérico sintético, 90 °C
Hard Service Cord Junior: cordón uso rudo para servicio ligero con aislamiento elastomérico, 300 volts.
SJ Oil Resistant: SJ con aislamiento resistente al aceite.
Thermoplastic: SJ con aislamiento y cubierta termoplástica, 60 °C, 300 volts (90 y105 °C con aislamiento
Underground Service Entrance: cable para acometidas subterráneas en baja tensión, aislamiento y cubie
elastoméricas.
United States Standard Gauge: escala para calibres de lámina de acero.
Unshielded Twisted Pair: cables multipares para datos, sin blindaje.
Volt: unidad utilizada para denominar tensión eléctrica.
Volt Ampere: unidad de potencia aparente para transformadores.
2.998x108 m/seg.
La velocidad de transmisión de la energía eléctrica en una longitud de cable comparado con la velocidad
en el aire. Se estima generalmente en porcentaje.
Very High Frecuency: extra alta frecuencia, 30 a 300 MHz.
Es la unidad de tensión eléctrica: 1 Volt será la tensión eléctrica que causará que 1 ampere de corriente f
de una resistencia de 1 Ohm.
Vertical Wire Flame Test: prueba de resistencia a la flama colocando el especimen en posición vertical.
Cables flexibles para minas: redondos o planos de uno o varios conductores con aislamiento y cubiertas
para servicio extrapesado.
Siglas en inglés para la multiplexación por división de longitud de onda. En estos sistemas se transmiten
simultánea varias longitudes de onda independientes.
Cross (X)-Linked Polyethylene High Heat and Moisture (Water) Resistant: cable con aislamiento de poliet
cadena cruzada, 90 °C ambiente seco y 75 °C en ambiente húmedo, 600 volts.
XHHW para 90 °C en ambientes secos y húmedos.
Cross (X)-Linked Polyethylene: polietileno de cadena cruzada, también conocida como polietileno vulcan
XLPE.
Xmas Tree Cord: cordón paralelo, dos conductores aislados con PVC para series de árboles de navidad.
CÁLCULOS ELÉCTRICOS
Para Jessica