Diseño de Muros

a. Datos del diseño

F'c = 280 Kg/cm2 Tipo de Suelo


Fy = 4200 Kg/cm2
L = 370.00 cm PD = 330.15 Tn
t = 15.00 cm PL = 177.39 Tn
Nº de Pisos = 4
Piso PD PL
Muro Absorbe = 23%V 1 114.72 Tn 75.78 Tn
hm = 3.20 m 2 114.72 Tn 75.78 Tn
lm = 3.70 m 3 100.71 Tn 25.83 Tn
4 100.71 Tn 25.83 Tn

Tabla Nº3
FACTOR DE SUELO "S"

SUELO ZONA
S0 S1 S2

Z4 0.80 1.00 1.05


Z3 0.80 1.00 1.15
Z2 0.80 1.00 1.20
Z1 0.80 1.00 1.60

Z = 0.45 𝑇=ℎ𝑛/𝐶𝑡
U = 1.3
S = 1.00
T = 0.21 T=

Tabla Nº4 Periodos


"Tp" y "TL"
Perfil del suelo
S0 S1 S2 S3
Tp (s) 0.3 0.4 0.6 1
TL (s) 3 2.5 2 1.6

Tp = 0.4
TL = 2.5

T < Tp C= 2.5

Tp < T > TL C= 2.5 .


(𝑇𝑝/𝑇)

2.5 .
((𝑇𝑝.𝑇𝐿)/𝑇^2
)
T > TL C= 2.5 .
((𝑇𝑝.𝑇𝐿)/𝑇^2
)

C= 2.5
R= 7 Absorbe mas < 70%

Ia = 1
IP = 1.65

Pesis = 418.85 Tn es 50% por ser cat B

𝑉=(𝑍.𝑈.𝐶.𝑆)/𝑅.𝑃

v= 53.04 Tn

P= PD+50% PV Por que es cat B H4 = 11.20 m


P4 = 113.625 H3= 8.00 m
P3 = 113.625 H2= 4.80 m
P2 = 152.61 H1= 1.60 m
P1 = 152.61

∝4 = 0.40
∝3 = 0.29
∝2 = 0.23
∝1 = 0.08
suma = 1.00

F= ∝ * V
F4 = 21.37 Tn
F3 = 15.26 Tn
F2 = 12.30 Tn
F1 = 4.10 Tn

V4 = 21.37 Tn
V3 = 36.63 Tn
V2= 48.94 Tn
V1 = 53.04 Tn
Resistencia al corte de concreto hm =
Absorbe 23% lm =
t (espesor)=
Vu muro = 12.20 Tn

hm/Lm= 0.865
∝c = 0.25
Vc = 23.22 Tn

Resistencia al corte de Acero

∅= 0.85

Vu = ∅Vn ρhmin = 0.0025


Vu = ∅(Vc+Vs) Vs = 39.18 Tn
(Vu/∅) - Vc =Vs ρh = 0.002
ρv = 0.0025 > 0.0025

Ash = 13.88 cm²


Asv= 13.88 cm²

S = ( varilla*Lmuro)/As

Sh = 34.40 cm
Sv= 34.40 cm

1∅ de 1/2" @0.35 cm
= muy rígido Zona = Z4
Suelo = S1

Uso= comercio

S3 Z

1.10 0.45
1.20 0.35
1.40 0.25
2.00 0.1

12.80 m
60
Distribución en Altura

T= 0.21
K= 1
3.20 m
3.70 m
15.00 cm

ρh = 0.0025 Por ser mínima


Area Diam.
ф3/8'' 0.71 0.9525
ф1/2'' 1.29 1.27
ф5/8'' 1.99 1.5875
ф3/4'' 2.84 1.91
ф1'' 5.1 2.54
h piso 1 3.20 m
h piso 2 3.20 m
h piso 3 3.20 m
h piso 4 3.20 m
h piso 5
Diseño de Muros

a. Datos del diseño

F'c = 280 Kg/cm2 Tipo de Suelo =


Fy = 4200 Kg/cm2
L = 370.00 cm PD = 330.15 Tn
t = 20.00 cm PL = 177.39 Tn
Nº de Pisos = 4
Piso PD PL
Muro Absorbe = 45%V 1 114.72 Tn 75.78 Tn
hm = 3.20 m 2 114.72 Tn 75.78 Tn
lm = 3.70 m 3 100.71 Tn 25.83 Tn
4 100.71 Tn 25.83 Tn

Tabla Nº3
FACTOR DE SUELO "S"

SUELO ZONA S0 S1 S2 S3
Z4 0.80 1.00 1.05 1.10
Z3 0.80 1.00 1.15 1.20
Z2 0.80 1.00 1.20 1.40
Z1 0.80 1.00 1.60 2.00

Z = 0.45 𝑇=ℎ𝑛/𝐶𝑡
U = 1.3
S = 1.00
T = 0.21 T= 12.80 m
60

Tabla Nº4 Periodos


"Tp" y "TL"
Perfil del suelo
S0 S1 S2 S3
Tp (s) 0.3 0.4 0.6 1
TL (s) 3 2.5 2 1.6

Tp = 0.4
TL = 2.5

T < Tp C= 2.5

Tp < T > TL C= 2.5 .


(𝑇𝑝/𝑇)
2.5 .
(𝑇𝑝/𝑇)

T > TL C= 2.5 .
((𝑇𝑝.𝑇𝐿)/𝑇^2
)

C= 2.5
R= 7 Absorbe mas < 70%

Ia = 1
IP = 1.65

Pesis = 418.85 Tn es 50% por ser cat B

𝑉=(𝑍.𝑈.𝐶.𝑆)/𝑅.𝑃

v= 53.04 Tn

P= PD+50% PV Por que es cat B H4 = 11.20 m


P4 = 113.625 H3= 8.00 m
P3 = 113.625 H2= 4.80 m
P2 = 152.61 H1= 1.60 m
P1 = 152.61

∝4 = 0.40
∝3 = 0.29
∝2 = 0.23
∝1 = 0.08
suma = 1.00

F= ∝ * V
F4 = 21.37 Tn
F3 = 15.26 Tn
F2 = 12.30 Tn
F1 = 4.10 Tn

V4 = 21.37 Tn
V3 = 36.63 Tn
V2= 48.94 Tn
V1 = 53.04 Tn
Resistencia al corte de concreto hm = 3.20 m
Absorbe 45% lm = 3.70 m
t (espesor)= 20.00 cm
Vu muro = 23.87 Tn

hm/Lm= 0.865
∝c = 0.25
Vc = 30.96 Tn

Resistencia al corte de Acero

∅= 0.85

Vu = ∅Vn ρhmin = 0.0025


Vu = ∅(Vc+Vs) Vs = 31.44 Tn ρh =
(Vu/∅) - Vc =Vs ρh = 0.001
ρv = 0.0025 > 0.0025

Ash = 18.50 cm²


Asv= 18.50 cm² ф3/8''
ф1/2''
S = ( varilla*Lmuro)/As ф5/8''
ф3/4''
Sh = 25.80 cm ф1''
Sv= 25.80 cm

1∅ de 1/2" @0.35 cm
h piso 1 3.20 m
h piso 2 3.20 m
h piso 3 3.20 m
muy rígido Zona = Z4 h piso 4 3.20 m
Suelo = S1 h piso 5

Uso= comercio

Z
0.45
0.35
0.25
0.1
Distribución en Altura

T= 0.21
K= 1
0.0025 Por ser mínima
Area Diam.
0.71 0.9525
1.29 1.27
1.99 1.5875
2.84 1.91
5.1 2.54
Zona
1 0.5
2 0.5
3 0.75
4 0.75