IntercambiadoresDeCalor DiseñoyCalculos
IntercambiadoresDeCalor DiseñoyCalculos
IntercambiadoresDeCalor DiseñoyCalculos
T1=95 C
t2= 40 C
Agua de mar
Datos:
Agua de mar Agua de rio
T media [C] 32.5 67.5
ρ [kg/m^3] 995 979.05
μ [Ns/m^2] 0.000769 0.0008
k [W/mK] 0.62 0.59
Pr 5.2 5.69
Cp [KJ/kg K] 4.18 4.2
PROCEDIMI
Agua de rio (Liquido caliente)
Q= 6416.66666666667 KJ/s
A= 256.62512 m^2
5) "Bundle- diameter" [mm]
Datos extra:
Uprom[W/m 1150 U[W/m^2C] 1000 di [mm] 16
m [kg/hr] 100000 Q [KJ/s] 6416.6667 do [mm] 20
m [kg/seg] 27.777778 Q [W] 6416667 n1 2.207
T1 [C] 95 π 3.1415927 K1 0.249
T2 [C] 40 longitud[m] 4.88 No, pasos 2
t1 [C] 25 di [m] 0.016 jh coraza 0.0065
t2 [C] 40 do [m] 0.02
PROCEDIMIENTO
Agua de mar (refrigerante)
m= 102.33918128655 kg/s
Do= 65 mm 0.065 Tenia 70, este valor depende de la grafica bundle diameter vs Shell inside…
Ds= 857.31972 mm 0.85731972 m
0.3429279 m
lb= 342.92789 mm pt= 25 mm 0.025
Vel masica:
G= 472.41305 kg/s m2 Re= 8385.9221 Error: capte mal la viscocidad de la tabla, el doble
hs= 4042.9778 W/m2 k Capte mal el valor de jh, error al leer la grafica
Capte mal el valor de k desde el inicio
u= 0.48252188 m/s
5/7/2020
ar será usada
Todos estos valores fueron mal tomados, error al leer las graficas
es fue de 2.44
Diferencia de T real:
836.9499262 tubos
ndle diameter vs Shell inside…