CSL 214200 MC 356 6 003
CSL 214200 MC 356 6 003
CSL 214200 MC 356 6 003
CSL-214200-MC-356-6-003
Rev. 1
APROBADO POR:
214200
Proyecto: "SERVICIO EPCM - PLANTA DE TUBOS LURIN - NAVE 4" Fecha: 20/07/22
FEEDER Tension COND. DEMAND VOLTAGE DROP CURRENT DESIG CIRCUIT TOTAL VOLTAGE
FEEDER (F-F) SPACE (I*L*FCT/1000)
DESCRIPCION FEEDER GROUND DUCTO Cap. en A FCT LENGTH
LOAD (Conductor) en PER REAL TYPE TRAY LOAD D.F. MAXIM. PHASES CURRENT CAPACITY CURRENT BREAKER DROP (460 V)
A/mm2
BANDEJ
A (%)
(mm2) Volts PHASE (mm2) (mm2) (mm f) de Cable (m) INST (KW) DEM.(KW) (A) (V) (%) CAPACITY
Ancho
(cm)
02
FUERZA TOMACORRIENTES 3Ø, 460VAC,
6 460 1 3-1x6 mm2 1x4 mm2 (T) N2XOH 25 30 70 5.009
1 160 5.50 1.00 5.50 3 Ø 8.63 6.92 1.50% 1.44 Ok 10.79 3x16 1.50% 453.08 CAIDA OK
LINEA TUBERA 02
03 COMPRESOR DE AIRE 1, 3Ø, 460VAC 16 460 1 3-1x16 mm2 1x10 mm2 (T) N2XOH 40 38 125 2.012 70 45.00 1.00 45.00 3 Ø 70.60 9.95 2.16% 4.41 Ok 77.66 3x80 2.16% 450.05 CAIDA OK
04 COMPRESOR DE AIRE 2, 3Ø, 460VAC 25 460 1 3-1x25 mm2 1x16 mm2 (T) N2XOH 55 44 160 1.350 70 74.60 1.00 74.60 3 Ø 117.04 11.06 2.40% 4.68 Ok 124.06 3x125 2.40% 448.94 CAIDA OK
05 COMPRESOR DE AIRE 3, 3Ø, 460VAC 25 460 1 3-1x25 mm2 1x16 mm2 (T) N2XOH 55 44 160 1.350 70 74.60 1.00 74.60 3 Ø 117.04 11.06 2.40% 4.68 Ok 124.06 3x125 2.40% 448.94 CAIDA OK
EXTRACTOR DE GASES 1
06 25 460 1 3-1x25 mm2 1x16 mm2 (T) N2XOH 55 44 160 1.350 130 37.30 1.00 37.30 3 Ø 58.52 10.27 2.23% 2.34 Ok 73.15 3x80 2.23% 449.73 CAIDA OK
LINEA TUBERA 01
EXTRACTOR DE GASES 2
07 25 460 1 3-1x25 mm2 1x16 mm2 (T) N2XOH 55 44 160 1.350 130 37.30 1.00 37.30 3 Ø 58.52 10.27 2.23% 2.34 Ok 73.15 3x80 2.23% 449.73 CAIDA OK
LINEA TUBERA 01