PASO 1 PUERTA AF m2

DETERMINAR LOS CAUDALES DE FUGA P1 0.025


P2 0.02
P3 0.02
P4 0.03
P5 0.02
P6 0.015
cte p max pa pmin pa DIF.P QF m3/h
3024 15 0 15 293
3024 25 15 10 191
3024 25 10 15 234
3024 5 0 5 203
3024 15 0 15 234
3024 10 5 5 101
1,256
ITEM DESCRIPCION AT
m2
1 CIRUGIA 1 72
2 CIRUGIA 2 54
3 CIRUGIA 3 54
4 LAVADO CIRUGIA 1 25
5 ESCLUSA CIRUGIA 1 25
6 LAVADO CIRUGIA 2 25
7 ESCLUSA CIRUGIA 2 25
8 LAVADO CIGUGIA 3 25
9 ESCLUSA CIRUGIA 3 25
10 PASILLO 240
11 ESCLUSA ENTRADA 1 6
12 ESCLUSA ENTRADA 2 6
13 ESTERILIZACION 20
14 SALA DE RECUPERACION 180

CAUDAL ENTRA
ITEM DESCRIPCION VI
m3/h
1 CIRUGIA 1 4,320
2 CIRUGIA 2 4,050
3 CIRUGIA 3 3,240
4 LAVADO CIRUGIA 1 1,125
5 ESCLUSA CIRUGIA 1 900
6 LAVADO CIRGUGIA 2 1,125
7 ESCLUSA CIRUGIA 2 900
8 LAVADO CIRGUGIA 3 1,125
9 ESCLUSA CIRUGIA 3 900
10 PASILLO 7,200
11 ESCLUSA ENTRADA 1 180
12 ESCLUSA ENTRADA 2 180
13 ESTERILIZACION 600
14 SALA DE RECUPERACION 6,480
32,325
H VR R/H QTS QTS VI1 VI2
m m3 BTU/H KW m3/h m3/h
3 216 20 0 0.0 4,320 0
3 162 25 0 0.0 4,050 0
3 162 20 0 0.0 3,240 0
3 75 15 0 0.0 1,125 0
3 75 12 0 0.0 900 0
3 75 15 0 0.0 1,125 0
3 75 12 0 0.0 900 0
3 75 15 0 0.0 1,125 0
3 75 12 0 0.0 900 0
3 720 10 0 0.0 7,200 0
3 18 10 0 0.0 180 0
3 18 10 0 0.0 180 0
3 60 10 0 0.0 600 0
3 540 12 0 0.0 6,480 0

CAUDAL SALE
INFILTRACIONES EXFILTRACIONES VE ISO
m3/h m3/h m3/h
0 191 4,129 ISO 5
0 203 3,847 ISO 7
0 101 3,139 ISO 7
0 1,256 -131 ISO 5
191 0 1,091 ISO 5
0 0 1,125 ISO 7
203 0 1,103 ISO 7
0 0 1,125 ISO 7
101 0 1,001 ISO 7
1,256 0 8,456 ISO 7
0 0 180 ISO 8
0 0 180 ISO 8
0 0 600 ISO 6
0 0 6,480 ISO 8
32,325
VI DISEÑO
m3/h
4,320
4,050
3,240
1,125
900
1,125
900
1,125
900
7,200
180
180
600
6,480
32,325
UMA 01 CIRUGIA 1

CAUDAL DE INYECCION
CAUDAL EXTRACCION
POTENCIA FRIO TOTAL
POTENCIA FRIO SENSIBLE
POTENCIA CALEFACCION
POTENCIA POST CALENTAMIENTO
MVAPOR

UMA-02 ESTERILIZACION

CAUDAL DE INYECCION
CAUDAL EXTRACCION
POTENCIA FRIO TOTAL
POTENCIA FRIO SENSIBLE
POTENCIA CALEFACCION
POTENCIA POST CALENTAMIENTO
MVAPOR

UMA-03 CIRUGIA 2

CAUDAL DE INYECCION
CAUDAL EXTRACCION
POTENCIA FRIO TOTAL
POTENCIA FRIO SENSIBLE
POTENCIA CALEFACCION
POTENCIA POST CALENTAMIENTO
MVAPOR

UMA-04 CIRUGIA 3

CAUDAL DE INYECCION
CAUDAL EXTRACCION
POTENCIA FRIO TOTAL
POTENCIA FRIO SENSIBLE
POTENCIA CALEFACCION
POTENCIA POST CALENTAMIENTO
MVAPOR

UMA-05 PASILLO

CAUDAL DE INYECCION
CAUDAL EXTRACCION
POTENCIA FRIO TOTAL
POTENCIA FRIO SENSIBLE
POTENCIA CALEFACCION
POTENCIA POST CALENTAMIENTO
MVAPOR
UMA-06

CAUDAL DE INYECCION
CAUDAL EXTRACCION
POTENCIA FRIO TOTAL
POTENCIA FRIO SENSIBLE
POTENCIA CALEFACCION
POTENCIA POST CALENTAMIENTO
MVAPOR
ISO 5 UMA 01

6,345 M3/H CAUDAL DE AIRE 6,345 m3/h


5,089 M3/H PRESION ESTATICA EXTERNA Pa
168 KW
70 KW VEX-01
58 KW
26.91 KW CAUDAL DE AIRE 5,089 m3/h
46.95 kgv/h PRESION ESTATICA EXTERNA Pa

ISO 6 UMA 02

600 M3/H CAUDAL DE AIRE 600 m3/h


600 M3/H PRESION ESTATICA EXTERNA Pa
9.97 KW
4.22 KW VEX-02
4.92 KW
1.97 KW CAUDAL DE AIRE 600 m3/h
4.92 kgv/h PRESION ESTATICA EXTERNA Pa

ISO 7 UMA 03

6,075 M3/H CAUDAL DE AIRE 6,075 m3/h


6,075 M3/H PRESION ESTATICA EXTERNA Pa
111 KW
46 KW VEX-03
46 KW
KW CAUDAL DE AIRE 6,075 m3/h
41.26 kgv/h PRESION ESTATICA EXTERNA Pa

ISO 7 UMA 03

5,265 M3/H CAUDAL DE AIRE 5,265 m3/h


5,265 M3/H PRESION ESTATICA EXTERNA Pa
88 KW
37 KW VEX-03
43 KW
KW CAUDAL DE AIRE 5,265 m3/h
43 kgv/h PRESION ESTATICA EXTERNA Pa

ISO 7 UMA 03

7,200 M3/H CAUDAL DE AIRE 7,200 m3/h


8,456 M3/H PRESION ESTATICA EXTERNA Pa
120 KW
KW VEX-03
59 KW
KW CAUDAL DE AIRE 8,456 m3/h
59.1 kgv/h PRESION ESTATICA EXTERNA Pa
ISO 8 UMA 04

6,840 M3/H CAUDAL DE AIRE 6,840 m3/h


6,840 M3/H PRESION ESTATICA EXTERNA Pa
114 KW
48 KW VEX-04
56 KW
22.43 KW CAUDAL DE AIRE 6,840 m3/h
56.14 kgv/h PRESION ESTATICA EXTERNA Pa
CAUDALES DE AGUA FRIA Y CALIENTE

DIFERENCIAL DT AGUA FRIA 5 °C


DIFERENCIAL DT AGUA CALIENTE 15 °C
DIF. ENTALPIA DEL VAPOR PV

UMA 01

CAUDAL DE AGUA FRIA 28.9 m3/h T AGUA FRIA 7.6


CAUDAL DE AGUA CALIENTE 3.3 m3/h T AGUA CALIENTE 38

UMA 02

CAUDAL DE AGUA FRIA 1.7 m3/h T AGUA FRIA 9.6


CAUDAL DE AGUA CALIENTE 0.3 m3/h T AGUA CALIENTE 42

UMA 03

CAUDAL DE AGUA FRIA 19.0 m3/h T AGUA FRIA 9.6


CAUDAL DE AGUA CALIENTE 2.6 m3/h T AGUA CALIENTE 42

UMA 04

CAUDAL DE AGUA FRIA 15.1 m3/h T AGUA FRIA 9.6


CAUDAL DE AGUA CALIENTE 2.5 m3/h T AGUA CALIENTE 42

UMA 05

CAUDAL DE AGUA FRIA 20.6 m3/h T AGUA FRIA 9.6


CAUDAL DE AGUA CALIENTE 3.4 m3/h T AGUA CALIENTE 42

UMA 06

CAUDAL DE AGUA FRIA 19.5 m3/h T AGUA FRIA 9.6


CAUDAL DE AGUA CALIENTE 3.2 m3/h T AGUA CALIENTE 42
104.9

°C
°C

°C
°C

°C
°C

°C
°C

°C
°C

°C
°C
RESUMEN DE CAJAS DE VOLUMEN DE AIRE CONSTA

ITEM DESCRIPCION VI
m3/h
1 CIRUGIA 1 4,320
2 CIRUGIA 2 4,050
3 CIRUGIA 3 3,240
4 LAVADO CIRUGIA 1 1,125
5 ESCLUSA CIRUGIA 1 900
6 LAVADO CIRGUGIA 2 1,125
7 ESCLUSA CIRUGIA 2 900
8 LAVADO CIRGUGIA 3 1,125
9 ESCLUSA CIRUGIA 3 900
10 PASILLO 7,200
11 ESCLUSA ENTRADA 1 180
12 ESCLUSA ENTRADA 2 180
13 ESTERILIZACION 600
14 SALA DE RECUPERACION 6,480
MEN DE AIRE CONSTANTE

CODIGO TAG VE CODIGO TAG


m3/h
VAC-I-01 4,129 VAC-E-01
VAC-I-02 3,847 VAC-E-02
VAC-I-03 3,139 VAC-E-03
VAC-I-04 -131 VAC-E-04
VAC-I-05 1,091 VAC-E-05
VAC-I-06 1,125 VAC-E-06
VAC-I-07 1,103 VAC-E-07
VAC-I-08 1,125 VAC-E-08
VAC-I-09 1,001 VAC-E-09
VAC-I-10 8,456 VAC-E-10
VAC-I-11 180 VAC-E-11
VAC-I-12 180 VAC-E-12
VAC-I-13 600 VAC-E-13
VAC-I-14 6,480 VAC-E-14