We take care of it.
Info Letter No. 5
Zero sequence voltage in three-phase networks
1.
Zero sequence voltage in three-phase
networks
asymmetric currents) is directly recognizable from this
equation.
With balanced network operation and inequality of the
impedances in the consumer circuit, the phase voltages of
the two circuits, and thus the neutral points are no longer
congruent.
Figure 2
Voltages in three-phase three-wire systems
(Short-circuit impedances of the power source and the serial
impedance of the cable are ignored)
Figure 1
Voltage indicator in a three-phase three-wire network.
Between the neutral points, there is a voltage difference, which
is referred to as the zero sequence voltage and the amount
depends on the inequality of the impedances in the consumer
circuit.
1.1 Three-phase three-wire network
The geometric sum of the complex effective values of the
phase currents (see Figure 2) is zero and thus:
U 1N + U NN" U 2 N + U NN" U 3 N + U NN"
+
+
=0
Z"1
Z" 2
Z" 3
(1)
As a result:
U NN" =
1
[(U 1N" + U 2 N" + U 3N" ) − (U 1N + U 2 N + U 3N )] (2)
3
With symmetrical network operation U1N + U2N + U3N = 0
and thus the voltage UNN“ equal to the zero component
U0, which is therefore also called the zero sequence voltage.
U NN"
1
= (U 1N" + U 2 N" + U 3 N" )
3
(3)
Then also:
U NN" = −
1
[ I 1 (Z"2 − Z"1 ) + I 3 (Z"2 − Z"3 )]
3
(4)
Example 1
Three-phase three-wire network; sinusoidal alternating
values; voltages at the measurement point / measurement equipment:
U12 = 20287 e
j30°
U23 = 20162 e
-j90°
V;
U31 = 20345 e
j150°
V;
V;
Consumer circuit:
j25°
j30°
Z“1 = 30 e Ω ; Z“2 = 28 e Ω ;
Z“3 = 32 e
j35°
Ω
(Star connection; asymmetry 7 %);
What is the value of the zero sequence voltage?
Result (calculation with program E-1.4.1)
Currents:
–j25°
-j151°
j87°
I1“ = 384 e
A; I2“ = 422 e
A; I3“ = 368 e A
Voltages in the consumer circuit:
U1N“ = 11508 e
–j0°
U2N“ = 11815 e
-j121°
V;
U3N“ = 11782 e
j122°
V;
V
Zero sequence voltage:
–j171°
UN’N“ = 254 e
V (2 % of U1N“; corresponding to the
voltage difference between the neutral point of the consumer circuit and the neutral point of the power source).
The effect on the zero sequence voltage of unequal impedances in the consumer circuit (which in turn cause
A. Eberle GmbH & Co. KG • Frankenstraße 160 • D-90461 Nürnberg
info@a-eberle.de • www.a-eberle.de
Page 1 of 4
We take care of it.
1.2 Three-phase four-wire network
Just as in the three-phase three-wire system, in the threephase four-wire system the following also applies for symmetrical network operation:
U NN" =
1
(U 1N" + U 2 N" + U 3N" ) = I NN" Z "N
3
(5)
UNN“ = U0 (zero component)
If instead of the impedances of the consumer circuit, the
corresponding admittances are used, the zero sequence
voltage is given by:
U 1N Y "1 + U 2 N Y "2 + U 3 N Y "3
Y "1 + Y "2 + Y "3 + Y "N
U NN" = −
(6)
Zero sequence voltage:
-j152°
UNN“ = U0 = 5 e
V (2 % of U1N“)
1.3 Measurement of the zero sequence voltage
The zero sequence voltage can be determined either from
the phase-earth voltages measured at any point in the
network covered by three voltage transformers (sum of
the instantaneous values, null component of the voltages)
or directly at the auxiliary winding of an earth-fault compensation coil.
For the measurement of the zero sequence voltage, single
pole insulated voltage transformers are equipped with an
additional auxiliary winding (named da - dn, earlier e - n).
Between the beginning and the end (the open ends) of
the auxiliary windings connected in series, the total value
of the three phase-to-ground voltages can be measured.
The sizing of the auxiliary windings is usually such that a
with a saturated single-pole earth fault the effective values of the zero sequence voltage and phase-phase voltage are equal.
Figure 3
Voltages in three-phase four-wire systems
(Short-circuit impedances of the power source and the serial
impedance of the cable are ignored)
Example 2
Three-phase four-wire network; sinusoidal alternating
values; voltages at the measurement point / measurement equipment:
U12 = 401.2 V; U23 = 402.5 V; U31 = 401.9 V;
(30° is chosen for the angle of U12).
Consumer circuit:
j28°
Z“1 = 17 e Ω;
Z“2 = 23 e
j30°
Ω;
Z“3 = 28 e
j34°
Ω;
Z”N = 1,0 e
j4°
Ω (Star connection; asymmetry 25 %).
What is the value of the zero sequence voltage?
Result (calculation with program E-1.4.2)
Voltages in the consumer circuit:
j0,6°
V;
U1N“ = 226.8 e
U2N“ = 232.4 e
-j121,2°
U3N“ = 236.9 e
j120,7°
V;
Figure 4
Measurement transformer circuitry for measuring the zero sequence voltage; at the series circuit of the auxiliary windings the
terminal da (e) of the first winding is preferably earthed.
Note
When there is an earth fault, the phase-earth voltages of
the earth-fault free conductor increase by a factor √3, so
that the total voltage on the secondary side of the voltage
transformer with the same dimensions of all the windings
is 100 V·√3.
However, to obtain the value of the total voltage of 100 V
with an earth fault, the voltage of the auxiliary winding
100V 100
=
3⋅ 3 3
must be
(Notation on the type plate of the voltage transformer).
V;
A. Eberle GmbH & Co. KG • Frankenstraße 160 • D-90461 Nürnberg
info@a-eberle.de • www.a-eberle.de
Info Letter No. 5
Page 2 of 4
We take care of it.
Effect of the measurement transformer error
Because of the amplitude and angular error of current
transformer, the sum of the three voltages also differs
marginally from zero in the earth fault-free three-phase
three-wire network.
Example 3
Three-phase three-wire network; sinusoidal alternating
values and the secondary windings of 3 voltage transformers are connected in series.
U1E = 100 V, Error: + 0.4 % / – 0.3°;
The zero sequence voltage also arises from the apparent
values between phase and earth, the apparent value of
the earth fault fire compensation coil and from the phasenuetral point voltages.
When there is an earth fault of a conductor, the impedance at the earth fault location acts in parallel to the
phase-earth impedance of that conductor.
U NE = −
U 1N Y 1E + U 2 N Y 2 E + U 3 N Y 3E
Y 1E + Y 2 E + Y 3E + Y NE
(9)
YiE apparent value between conductor Li and earth;
with an earth fault: YiE // YiF
U2E = 100 V, Error: – 0.25 % / – 0.4°;
U3E = 100 V, Error: + 0.3 % / + 0.3°
YNE apparent value between the neutral point of the
transformer and earth (earth fault compensation coil)
How big is the variance of the total voltage from zero?
Result (calculation with program E-1.7.1)
Instead of UΣ = 0 and ϕΣ = 0°, the following is displayed:
UΣ* = 0.68 V. This corresponds to 0.7 % of 100 V.
ϕ*Σ = 177°
1.4 Zero sequence voltage with an earth fault
A high zero sequence voltage is an indication of an earth
fault in the network, because in normal network conditions, the asymmetry of the phase-earth impedance and
thus the zero sequence voltage is low, in earth-fault free
networks it is only a few percent of the phase-earth voltage. Because of the significantly improved symmetry of
the phase-earth impedance of cables in these networks
the zero sequence voltage is even lower than in overhead
transmission networks. - With a saturated earth fault the
zero sequence voltage can reach the full value of the
phase-neutral point voltage. Due to the earth fault of a
conductor, the corresponding phase-earth impedance is
largely short-circuited in the entire, electrically connected
network. The increase in the zero sequence voltage thus
occurs independently of the location of the earth fault.
The value and angle are however location-dependent;
they are determined by the phase-phase voltages and the
phase-earth impedances at the measurement point. The
waveform and frequency of the network voltage and zero
sequence voltage are the same after the end of the short
transient process caused by the earth fault.
In the three-phase network with earth fault compensation:
With symmetry of the voltages UiN, both with the same
values YiE and earth fault-free network status, the numerator of the fraction and thus the zero sequence voltage occurring at the earth compensation coil becomes
zero.
With a saturated earth fault in one conductor, the associated value YiE acquires very high values, so that UNE ≈ UiN
(for ZiE = 0, thus YiE = ∞ there is an indefinite term!).
Example 4
Three-phase three-wire network; sinusoidal alternating
values; earth fault compensation; earth fault on conductor L1.
Voltages at the measurement location / measurement
equipment:
j31°
U12 = 20.16 e kV;
U23 = 20.01 e
–j90°
U31 = 20.24 e
j151°
kV;
kV;
Phase-earth capacitances:
C1 = 6.2 µF; C2 = 5.9 µF; C3 = 6.1 µF
(asymmetry 3 %);
Conductor derivations (conductor-earth):
R1 = 102 kΩ; R2 = 105 kΩ; R3 = 98 kΩ
(asymmetry 4 %);
Earth fault on conductor L1: Resistance ZF = 25 Ω;
(7)
Earth fault compensation coil:
j86°
Impedance ZNE = 173 e
Ω (Inductance L = 0.55 H; Copper resistance R = 9 Ω; Iron losses R = 7000 Ω).
With balanced network operation U1N + U2N + U3N = 0 and
thus the voltage UNE = U0 (null component)
What are the value and angle of the phase-earth voltages
and zero sequence voltage?
U NE =
U0 =
1
[(U 1E + U 2 E + U 3E ) − (U 1N + U 2 N + U 3N )]
3
1
(U 1E + U 2 E + U 3E )
3
(8)
A. Eberle GmbH & Co. KG • Frankenstraße 160 • D-90461 Nürnberg
info@a-eberle.de • www.a-eberle.de
Info Letter No. 5
Page 3 of 4
We take care of it.
Result (calculation with program E-1.7.2)
-j13°
U1E = 0.15 e
kV;
U2E = 20.05 e
-j150°
U3E = 20.09 e
j150°
kV;
kV
Zero sequence voltage UNE = 11.55 e
-j180°
kV
The phase-phase voltages are not changed by the earth
fault, therefore:
U12 = U1E – U2E
-j13°
-j150°
j31°
= 0.15 e
kV – 20.05 e
kV = 20.16 e kV
U23 = U2E – U3E
-j150°
j150°
–j90°
= 20.05 e
kV – 20.09 e
kV = 20.01 e
kV
U31 = U3E – U1E
j150°
-j13°
j150°
= 20.09 e
kV – 0.15 e
kV = 20.24 e
kV
1.5 Voltage gradient in the event of an earth fault
In the event of an earth fault, three tasks run at the same
time (see fig. 5) run within a very short period of time.
•
•
•
The phase-earth-voltage of the conductor with an
earth fault breaks down; with a saturated earth fault
this voltage drops to zero.
The instantaneous values of the phase-earth voltages
of the two earth fault-free conductors jump to the instantaneous value of the associated phase-phase
voltage.
The instantaneous value of the zero sequence voltage suddenly rises from the normal operating value
(several volts) to a value that, in a saturated earth
fault, corresponds to the instantaneous value of the
phase-neutral point voltage.
Figure 5
Change in the instantaneous values u1N, u2N, u3N, uNE before and
after a single-pole earth fault
This "shifting" occurring during an earth fault causes a
short-term high-frequency vibration (transient, ignition
oscillation), which is added to the fundamental frequency
of the zero sequence voltage, thus significantly determining their variation over time. For the consideration of the
stationary state (continuous earth fault) this settling
process has no significance.
After the occurrence of the earth fault, the zero sequence
voltage changes with a reversed sign in direct continuation of the previous course (amplitude and angle) of the
phase-earth voltage that has now decreased to zero.
Phase-phase voltages
In networks with fault compensation a conductor of the
associated line from the energy source is not shortcircuited by an earth fault (as opposed to the rigid
earthing of the neutral point of the energy source). Such
line voltages and thus also the phase-phase voltages remain unchanged with a single-pole continuous earth
fault.
If there is a continuous saturated earth fault on, for example, conductor L1 (high inequality of the phase-earth
impedance), then with symmetric phase-phase voltages:
U 1E = U 1N + U NE = 0
U 2 E = U 1E − U 12 = − U 12 = U 12 e − j150°
U 3E = U 2 E − U 23 = − U 12 − U 23 = U 31 e j150°
i.e., the phase-earth voltages of both earth fault-free
conductors have the same values as the associated phasephase voltages; the angles of U3E and U31 are the same,
those of U2E and U12 have almost the same value, but
inverse signs (see Figure 5).
Author: Helmut Karger
The Excel programs used for the examples can be obtained from:
www.a-eberle.de
(Download Center)
The series will be continued.
We will gladly supply missing Info Letters at any time!
Issue: 03-2013 / I005-1-D-1-001-04.docx
A. Eberle GmbH & Co. KG • Frankenstraße 160 • D-90461 Nürnberg
info@a-eberle.de • www.a-eberle.de
Info Letter No. 5
Page 4 of 4